ANSI-IsA S18.1-199 Annunciator Sequence and Spec
ANSI-IsA S18.1-199 Annunciator Sequence and Spec
ANSI-IsA S18.1-199 Annunciator Sequence and Spec
ANSI/ISAS18.11979 (R1992)
Annunciator Sequences
and Specifications
ISBN 0-87664-346-2
Copyright 1979 by the Instrument Society of America. All rights reserved. Printed in the United
States of America. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), without the prior written permission of the publisher.
ISA
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, North Carolina 27709
Preface
This preface is included for informational purposes and is not part of ANSI/ISA-S18.1.
This standard has been prepared as part of the service of ISA toward a goal of uniformity in the
field of instrumentation. To be of real value, this document should not be static, but should be
subject to periodic review. Toward this end, the Society welcomes all comments and criticisms
and asks that they be addressed to the Secretary, Standards and Practices Board, ISA, 67
Alexander Drive, P.O. Box 12277, Research Triangle Park, North Carolina 27709, Telephone
(919) 549-8411, e-mail: standards@isa.org.
Based on work started in 1955 by a survey committee titled Instrument Alarms and Interlocks,
the 8D-RP18 Committee on Annunciator Systems of the Production Processes was formed in
1969. Tentative Recommended Practice ISA-RP18.1, titled Specifications and Guides for the
Use of General Purpose Annunciators, was completed by that Committee in 1965.
The committee, reactivated as Committee SP18, Instrument Signals and Alarms, began revising
ISA-RP18.1 in 1976 to reflect current industry practice for annunciators; in 1991, the Nuclear
Power Plant Standards Committee, SP67, assumed responsibility for the reaffirmation of this
standard.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals and
interests in the development of ISA standards. Participation in the ISA standards-making
process by an individual in no way constitutes endorsement by the employers of the individual, of
ISA, or of any of the standards that ISA develops.
The information contained in the preface, footnotes, and appendices is included for information
only and is not a part of the standard.
The following people served as members of SP67 at the time of this standards 1992
reaffirmation:
NAME
COMPANY
R. Wiegle, Chairman
R. Naylor, Vice Chairman
M. Widmeyer, Managing Director
J. Mock, Secretary
R. Allen
B. Basu
M. Belew
B. Beuchel
N. Dogra
A. Ellis*
R. Estes
H. Evans
V. Fregonese
R. Givan
W. Gordon*
T. Grochowski
S. Hedden
J. Lipka
L. McNeil
G. Minor
J. Nay*
R. Profeta
F. Semper
W. Sotos
I. Sturman*
K. Utsumi
J. Weiss
G. Whitmore
Consultant
INPO
M.H. B. Technical Association
Westinghouse Electric Corporation
S. Levy, Inc.
Semper Engineering
American Electric Power Service Corporation
Bechtel Corporation
General Electric Corporation
Electric Power Research Institute
Duquesne Light Company
This reaffirmed standard was approved for publication by the ISA Standards and Practices Board
in 1992.
NAME
COMPANY
J. Rennie, Chairman
H. Baumann
D. Bishop
C. Gross
H. Hopkins
K. Lindner
G. McFarland
E. Nesvig
R. Prescott
D. Rapley
R. Reimer
R. Webb
W. Weidman
J. Whetstone
M. Widmeyer
C. Williams
P. Bliss**
W. Calder III**
L. Combs**
N. Conger**
T. Harrison**
R. Jones
R. Keller**
E. Magison**
R. Marvin**
A. McCauley, Jr.**
W. Miller**
J. Mock**
G. Platt**
K. Whitman**
J. Williams**
ANSI/ISA-S18.1-1979 (R1992)
Contents
1 Purpose .............................................................................................................................. 7
2 Scope ................................................................................................................................. 7
3 Definition of terms ............................................................................................................ 7
4 Sequences ........................................................................................................................11
4.1 Operation ............................................................................................................... 11
4.2 Presentation .......................................................................................................... 11
4.3 Designation method ............................................................................................... 12
4.4 Basic sequence letter designations ....................................................................... 20
4.5 Option number designations .................................................................................. 20
4.6 First out designations ............................................................................................ 22
5 Specifications .................................................................................................................. 23
5.1 All annunciators ..................................................................................................... 23
5.2 Remote logic annunciators .................................................................................... 24
5.3 Complex annunciator systems .............................................................................. 24
5.4 Annunciator accessories and special features ...................................................... 24
6 Documentation ................................................................................................................ 25
6.1 All annunciators ..................................................................................................... 26
6.2 Remote logic annunciators .................................................................................... 26
6.3 Complex annunciator systems .............................................................................. 26
6.4 Annunciator accessories and special features ...................................................... 26
ANSI/ISA-S18.1-1979 (R1992)
1 Purpose
2 Scope
This Standard is primarily for use with electrical annunciators that call attention to abnormal
process conditions by the use of individual illuminated visual displays and audible devices.
Annunciators can range from a single annunciator cabinet, to complex annunciator systems with
many lamp cabinets and remote logic cabinets.
The sequence designations provided can be used to describe basic annunciator sequences and
also many sequence variations. This Standard lists types of information that should be included
in annunciator specifications and types of documents that should be provided by manufacturers;
however, detailed design requirements and documentation formats are beyond the scope of this
Standard.
3 Definition of terms
The following are terms and their definitions that have special meaning in relation to
annunciators. Commonly used alternate terms are shown in parentheses. Defined terms used
in other definitions are in italics to provide a cross-reference.
acknowledge: the sequence action that indicates recognition of a new alarm.
active alarm point: see alarm point.
alarm: 1. an abnormal process condition. 2. the sequence state when an abnormal process
condition occurs. 3. a device that calls attention to the existence of an abnormal process
condition. See annunciator. Types of alarm include:
momentary: an alarm that returns to normal before being acknowledged.
maintained: an alarm that returns to normal after being acknowledged.
alarm module (point or sequence module): a plug-in assembly containing the sequence logic
circuit. Some alarm modules also contain visual display lamps or lamps and windows.
alarm point: the sequence logic circuit, visual display, auxiliary devices, and internal wiring
related to one visual display. Types of alarm point include:
ANSI/ISA-S18.1-1979 (R1992)
active: an alarm point that is wired internally and completely equipped. The window is labeled to identify a specific monitored variable.
spare: an alarm point that is wired internally and completely equipped. The window is not labeled to identify a monitored variable.
future (blank): an alarm point that is wired internally and equipped except for the
plug-in alarm module. The window is not labeled to identify a monitored variable.
alert: see process condition and sequence state.
analog input point: an alarm point for use with an analog monitored variable signal, usually
current or voltage. The logic circuit initiates an alarm when the analog signal is above or below a
set point.
annunciator: a device or group of devices that call attention to changes in process conditions
that have occurred. An annunciator usually calls attention to abnormal process conditions, but
may be used also to show normal process status. Usually included are sequence logic circuits,
labeled visual displays, audible devices, and manually operated pushbuttons.
audible device: a device that calls attention by sound to the occurrence of abnormal process
conditions. An audible device may also call attention to return to normal conditions.
audible device follower: see auxiliary output.
automatic reset: see reset.
auxiliary contact: see auxiliary output.
auxiliary output (auxiliary contact): An output signal operated by a single alarm point or group
of points for use with a remote device. Types of auxiliary output include:
field contact follower: an auxiliary output that operates while the field contact indicates an abnormal process condition.
lamp follower: an auxiliary output that operates while the visual display lamps indicate an alarm, silenced, or acknowledged state.
audible device follower (horn relay contact): an auxiliary output that operates
while the common alarm audible device operates.
reflash: an auxiliary output that operates when any one of a group of alarm points
indicates an abnormal process condition. The output usually returns to normal
briefly when each alarm point changes to an abnormal process condition and returns to normal when all alarm points in the group indicate normal process conditions.
blank alarm point: see alarm point.
field contact (trouble or signal contact): the electrical contact of the device sensing the
process condition. The contact is either open or closed. Annunciator field contacts are identified
in relation to process conditions and annunciator operation, not the disconnected position of the
devices. Types of field contact include:
normally open (NO): a field contact that is open for a normal process condition
and closed when the process condition is abnormal.
normally closed (NC): A field contact that is closed for a normal process condition
and open when the process condition is abnormal.
field contact follower: see auxiliary output.
field contact voltage (trouble or signal contact voltage): the voltage applied to field contacts.
ANSI/ISA-S18.1-1979 (R1992)
first out: reset of the first out indication occurs when the acknowledge or first out
reset pushbutton is operated, whether the process condition has returned to normal or not, depending on the sequence.
response time: the time period between the process condition becoming abnormal and initiation
of the alarm state. The minimum momentary alarm duration required for annunciator operation.
return alert: see ringback.
ringback (return alert): a sequence feature that provides a distinct visual or audible indication or
both when the process condition returns to normal.
sequence: the chronological series of actions and states of an annunciator after an abnormal
process condition or manual test initiation occurs.
sequence action: a signal that causes the sequence to change from one sequence state to
another. Sequence actions include process condition changes and manual operation of
pushbuttons.
sequence diagram: a graphic presentation that describes sequence actions and sequence
states.
sequence module: see alarm module.
sequence state: the condition of the visual display and audible device provided by an
annunciator to indicate the process condition or pushbutton actions or both. Sequence states
include normal, alarm (alert), silenced, acknowledged, and ringback.
sequence table: a presentation that describes sequence actions and sequence states by lines
of statements arranged in columns.
signal contact: see field contact.
signal contact voltage: see field contact voltage.
silence: the sequence action that stops the sound of the audible device.
spare alarm point: see alarm point.
test: an annunciator sequence initiated by operation of the test pushbutton to reveal lamp or
circuit failure. Types of test include:
operational (functional): test of the sequence, visual display lamps, audible devices, and pushbuttons.
lamp: test of the visual display lamps.
trouble contact: see field contact.
trouble contact voltage: see field contact voltage.
visual display: that part of an annunciator or lamp cabinet that indicates the sequence state.
Usually consists of an enclosure containing lamps behind a translucent window. The lamps can
be off, flashing, or on.
window (nameplate): a component of a visual display made from a translucent material that is
illuminated from the rear and labeled to identify the monitored variable.
10
ANSI/ISA-S18.1-1979 (R1992)
4 Sequences
4.1 Operation
Annunciators usually call attention to abnormal process conditions by the use of individual
illuminated visual displays and audible devices. Annunciators may also be used to show normal
process status. Changes from one annunciator sequence state to another are caused by
changes in process conditions and also by manual operation of pushbuttons. The new sequence
state may be dependent on the process condition that exists at the time pushbuttons are
operated. Process condition changes are usually sensed by field contacts.
The visual displays usually flash to indicate abnormal process conditions and change to on when
alarms are acknowledged. Additional types of flashing can indicate that process conditions have
returned to normal or which of a group of alarm points operated first. All of the alarm points of an
annunciator usually use the same sequence; however, different sequences can be used for
individual alarm points or groups of points in one annunciator.
In this Standard, sequences making use of more than one indication device as a part of each
visual display to indicate the sequence state are considered to be special because of their many
variations and relatively infrequent use. Examples include the use of lamps of different colors to
indicate different sequence states or which is the first of a group of alarms.
4.2 Presentation
Annunciator sequence tables describe the operation of annunciators, but often do not clearly
indicate all aspects of the sequences. Examples include failure to indicate the sequence actions
and states when process conditions return to abnormal again before the annunciator is reset and
also when pushbuttons are operated out of the normal sequence. A sequence diagram format is
used in this Standard to allow annunciator sequences to be defined completely and analyzed
logically. See Figures 2 to 8.
Sequence diagrams include a block for each annunciator sequence state. The process
condition, the sequence state, and the visual display and audible device conditions when in that
state are indicated in each block. The blocks are arranged to describe the annunciator sequence
from the normal state, through the other sequence states, and back to the normal state again.
Arrows between the blocks indicate all possible sequence actions that can cause a change from
one sequence state to another. Sequence actions include process condition changes and
manual operation of pushbuttons.
Sequence tables are also used in this Standard since it is not always convenient to use
sequence diagrams. These sequence tables are patterned after the sequence diagrams to
describe all aspects of the annunciator operation. See Figures 2 to 8.
The sequence tables include a line for the initial normal state and also a line for each possible
sequence action that can cause a change from one sequence state to another. The reference
line numbers in the tables are identified by suffixes A and B when the new sequence state
depends on the process condition that exists at the time pushbuttons are operated. References
to other lines in the table are used to avoid indicating each sequence state and the related visual
display and audible device conditions more than once.
When annunciators require auxiliary outputs, the output operation should be added to sequence
diagrams and sequence tables or the operation should be defined by notes. The operation of
auxiliary outputs during annunciator test should be defined also.
ANSI/ISA-S18.1-1979 (R1992)
11
Since most annunciators include a test pushbutton and operational test of the sequence, visual
display lamps, audible devices, and pushbuttons, the sequences in this Standard include
operational test as a standard feature.
12
ANSI/ISA-S18.1-1979 (R1992)
ANSI/ISA-S18.1-1979 (R1992)
13
14
ANSI/ISA-S18.1-1979 (R1992)
ANSI/ISA-S18.1-1979 (R1992)
15
SEQUENCE DIAGRAM
PROCESS
NORMAL
SEQUENCE
NORMAL
RESET
NORMAL
PROCESS
OFF
ALARM
AUDIBLE
SILENT
RINGBACK
AUDIBLE
SILENT
TO ABNORMAL
SEQUENCE
ABNORMAL
OR NORMAL
ALARM
VISUAL
FAST FLASHING
ALARM
AUDIBLE
AUDIBLE
RINGBACK
AUDIBLE
SILENT
RETURN TO
ABNORMAL
SEQUENCE
RINGBACK
VISUAL
SLOW FLASHING
ALARM
AUDIBLE
SILENT
RINGBACK
AUDIBLE
TIMED AUDIBLE
RETURN TO
NORMAL
VISUAL
PROCESS
ACKNOWLEDGE
WHILE NORMAL
PROCESS
ABNORMAL
PROCESS
ABNORMAL
OR NORMAL
SEQUENCE
ACKNOWLEDGED
SEQUENCE
SILENCED
VISUAL
ON
VISUAL
FAST FLASHING
SILENT
ALARM
AUDIBLE
SILENT
SILENT
RINGBACK
AUDIBLE
SILENT
ALARM
AUDIBLE
RINGBACK
AUDIBLE
ACKNOWLEDGE
WHILE ABNORMAL
SILENCE
SEQUENCE TABLE
LINE
PROCESS
CONDITION
NORMAL
ABNORMAL
ABNORMAL
OR NORMAL
4A
ABNORMAL
PUSHBUTTON
OPERATION
SILENCE
SEQUENCE
STATE
NORMAL
ALARM
SILENCED
ACKNOWLEDGE ACKNOWLEDGED
4B
NORMAL
ACKNOWLEDGE
NORMAL
ABNORMAL
NORMAL
RESET
VISUAL
DISPLAY
OFF
FAST
FLASHING
FAST
FLASHING
ON
ALARM
AUDIBLE
DEVICE
RINGBACK
AUDIBLE
DEVICE
SILENT
SILENT
AUDIBLE
SILENT
LOCK-IN
SILENT
SILENT
LOCK-IN
SILENT
SILENT
MAINTAINED ALARM
SILENT
TIMED
AUDIBLE
MANUAL RESET
REQUIRED
RETURN TO
ABNORMAL
SILENT
MANUAL RESET
TO LINE 5
RINGBACK
SLOW
FLASHING
MOMENTARY ALARM
TO LINE 2
NORMAL
OFF
REMARKS
SILENT
SEQUENCE FEATURES
1 - SILENCE, ACKNOWLEDGE, RESET, AND TEST PUSHBUTTONS.
2 - ALARM AND RINGBACK AUDIBLE DEVICES.
3 - LOCK-IN OF MOMENTARY ALARMS UNTIL ACKNOWLEDGED.
4 - OPTION 1 - SILENCE PUSHBUTTON TO SILENCE THE ALARM AUDIBLE DEVICE WHILE RETAINING FAST
FLASHING INDICATIONS.
5 - OPTION 2 - SILENCE INTERLOCK TO REQUIRE OPERATION OF THE SILENCE PUSHBUTTON BEFORE THE
ACKNOWLEDGE PUSHBUTTON.
6 - RINGBACK VISUAL AND AUDIBLE INDICATIONS WHEN PROCESS CONDITIONS RETURN TO NORMAL.
7 - OPTION 9 - AUTOMATIC RINGBACK SILENCE TO SILENCE THE RINGBACK AUDIBLE DEVICE AFTER A SET TIME.
8 - MANUAL RESET OF RINGBACK INDICATIONS.
9 - OPERATIONAL TEST.
16
ANSI/ISA-S18.1-1979 (R1992)
Figure 6 Sequence F1A, automatic reset first out with no subsequent alarm
state
ANSI/ISA-S18.1-1979 (R1992)
17
Figure 7 Sequence F2M-1, manual reset first out with no subsequent alarm
flashing and silence pushbutton
18
ANSI/ISA-S18.1-1979 (R1992)
SEQUENCE DIAGRAM
LEGEND:
P = PROCESS
S = SEQUENCE
V = VISUAL
A = AUDIBLE
ABNORMAL
SUB. ACKNOWLEDGED
ON
SILENT
NORMAL
NORMAL
OFF
SILENT
FIRST TO
ABNORMAL
RETURN
TO NORMAL
SUBSEQUENT
TO ABNORMAL
ACKNOWLEDGE
WHILE NORMAL
ACKNOWLEDGE
WHILE ABNORMAL
ABNORMAL
OR NORMAL
SUB. ALARM
FAST FLASHING
AUDIBLE
S
FIRST OUT RESET
V
A
ABNORMAL
OR NORMAL
FIRST ALARM
INTERMITTENT
FLASHING
AUDIBLE
ABNORMAL
OR NORMAL
FIRST ACKNOWLEDGED
SLOW FLASHING
SILENT
P
FIRST OUT RESET
WHILE ABNORMAL
ACKNOWLEDGE
SEQUENCE TABLE
LINE
PROCESS
CONDITIONS
NORMAL
PUSHBUTTON
OPERATION
NORMAL
FIRST
ABNORMAL
FIRST ALARM
SUB.
ABNORMAL
SUB. ALARM
FIRST
ABNORMAL
OR NORMAL
FIRST
ABNORMAL
OR NORMAL
6A
SUB.
ABNORMAL
6B
SUB.
NORMAL
7A
FIRST
ABNORMAL
7B
FIRST
NORMAL
VISUAL
DISPLAY
SEQUENCE
STATE
OFF
INTERMITTENT
FLASHING
SILENT
LOCK-IN
LOCK-IN
TO LINE 3
FIRST
ACKNOWLEDGED
SLOW
FLASHING
SILENT
SUB.
ACKNOWLEDGED
ON
SILENT
MAINTAINED ALARM
FIRST OUT
RESET AFTER
ACKNOWLEDGE
NORMAL
REMARKS
AUDIBLE
FIRST OUT
RESET BEFORE
ACKNOWLEDGE
ACKNOWLEDGE
ALARM
AUDIBLE
DEVICE
NORMAL
TO LINE 8
MOMENTARY ALARM
TO LINE 6A
TO LINE 8
OFF
SILENT
AUTOMATIC RESET
SEQUENCE FEATURES
1 - ACKNOWLEDGE, FIRST OUT RESET, AND TEST PUSHBUTTONS.
2 - ALARM AUDIBLE DEVICE.
3 - LOCK-IN OF MOMENTARY ALARMS UNTIL ACKNOWLEDGED.
4 - FIRST OUT FLASHING DIFFERENT FROM SUBSEQUENT FLASHING.
5 - FIRST OUT RESET PUSHBUTTON TO CHANGE THE FIRST OUT VISUAL INDICATION TO BE THE SAME AS SUBSEQUENT
VISUAL INDICATIONS.
6 - AUTOMATIC RESET OF ACKNOWLEDGED ALARM INDICATIONS WHEN PROCESS CONDITIONS RETURN TO NORMAL.
7 - OPERATIONAL TEST.
Figure 8 Sequence F3A, automatic reset first out with first out flashing and reset
pushbutton
ANSI/ISA-S18.1-1979 (R1992)
19
Key Words
Description
Automatic
Reset
Manual
Reset
Ringback
Sequence diagrams and sequence tables for these basic sequences are shown in Figures 2, 3,
and 4.
The types of flashing shown in this Standard such as fast flashing and slow flashing are
examples based on frequent use. Alternate types of flashing may be used without requiring a
change in the sequence designation.
Since annunciator sequences usually include lock-in of momentary alarms, sequences in this
Standard include lock-in as a standard feature. A sequence option number is provided to permit
deleting the lock-in feature. Some alarm modules have provisions for deleting the lock-in feature
on individual alarm points.
Variations in the basic sequences can be defined using basic sequence letter designations
combined with option numberssee 4.5, Option Number Designations.
First out sequences require a first out designation in addition to the basic sequence letter
designationsee 4.6, First Out Designations.
20
ANSI/ISA-S18.1-1979 (R1992)
Option
Number
Key Words
Description
Silence Pushbutton
Silence Interlock
First Out
Reset Interlock
No Lock-In
No Flashing
No Audible
Automatic
Alarm Silence
Common Ringback
Audible
Automatic
Ringback Silence
10
No Ringback Audible
11
Common Ringback
Visual
12
Automatic Momentary
Ringback
13
14
Lamp Test
ANSI/ISA-S18.1-1979 (R1992)
21
Key Words
Description
F1
No Subsequent
Alarm State
F2
No Subsequent Alarm
Flashing
F3
First Out
Flashing and
Reset Pushbutton
First out sequences can be automatic reset or manual reset or can provide ringback indication
when alarms return to normal. First out sequences are designated by a combination of the first
out designation, the basic sequence letter designation, and option numbers. An example of a
first out sequence designation is in Figure 1.
First out sequence diagrams consist of an outer loop of actions and states associated with the
first alarm and an inner loop associated with subsequent alarms. The two loops have a common
normal state.
Not all of the possible first out sequences are readily available. In some cases, a particular first
out sequence may be a standard design for only one manufacturer. Sequence designations for a
range of first out sequences are listed below. Some of these use a silence pushbutton, option
number 1, to silence the audible device while retaining the visual display indications in the alarm
statesee 4.5, Option Number Designations. The sequences commonly available at the time of
publication are indicated. Sequence diagrams and sequence tables for three of the common first
out sequences are shown in Figures 6, 7, and 8.
22
ANSI/ISA-S18.1-1979 (R1992)
Automatic
Reset
Key Words
Manual Reset
Ringback
No Subsequent
Alarm State
F1A
(Common)
(Figure 6)
F1M
(Common)
F1R
No Subsequent
Alarm State and Silence
Pushbutton
F1A-1
(Common)
F1M-1
(Common)
F1R-1
No Subsequent
Alarm Flashing
F2A
(Common)
F2M
(Common)
F2R
No Subsequent
Alarm Flashing and
Silence Pushbutton
F2A-1
(Common)
F2M-1
(Common)
(Figure 7)
F2R-1
F3A
(Common)
(Figure 8)
F3M
F3R
5 Specifications
2)
3)
4)
*Refer to ISA Standard ISA-S20, Specification Forms for Process Measurement and Control Instruments, Primary Elements, and Control Valves.
ANSI/ISA-S18.1-1979 (R1992)
23
5)
6)
7)
8)
9)
Window engraving: legend list, lettering size, maximum number of lines, maximum
characters per line (May also be provided later.)
Field contact operation: normally open (close to alarm), normally closed (open to
alarm), mixed
2)
3)
4)
Prefabricated cables: supplier, length, conductor size, insulation type, jacket type
5)
6)
2)
24
1)
2)
3)
Special cabinet finish: annunciator or lamp cabinet color, logic cabinet color, materials
to be used, application methods
4)
5)
6)
7)
8)
9)
10) Solid state field contacts or solid state auxiliary outputs: type, electrical rating,
common potential
11)
6 Documentation
ANSI/ISA-S18.1-1979 (R1992)
25
2)
3)
4)
Schematic diagram drawings: logic circuit, circuit wiring, jumper and switch settings,
modules, pushbuttons, audible devices, field contact voltage, lamp voltage, power
supply circuit, electrical ratings
5)
Wiring diagram drawings: external wiring, power source voltage and frequency
6)
7)
8)
Logic cabinet arrangement drawings: internal devices, terminal blocks, wiring space,
ground connections, receptacles, lights, fans
2)
3)
2)
26
ANSI/ISA-S18.1-1979 (R1992)
This Appendix is included for informational purposes and is not a part of this Standard.
A.1 Purpose
The purpose of this Appendix is to provide information to assist in specifying annunciators that
will best serve the requirements of the users while making use of standard and special features
that are readily available. Catalogs and other information from annunciator manufacturers
should also be used because of the wide variety of features that are available.
A.2 Introduction
Annunciators are normally used to call attention to abnormal process conditions. Annunciators
may also be used to show normal process status. Annunciators usually include individual
illuminated visual displays that are labeled to identify the particular monitored variable that is
abnormal and audible devices. Annunciators may also call attention to the return to normal of the
process conditions.
Visual displays usually flash to indicate abnormal process conditions. Manual operation of
pushbuttons is usually required to silence audible devices and acknowledge new alarms. Visual
displays usually change from flashing to on when alarms are acknowledged. Figure A.1
illustrates a typical annunciator sequence.
Additional types of flashing can indicate that process conditions have returned to normal or which
of a group of alarm points operated first. Additional pushbuttons can be used to acknowledge
alarms that return to normal, to reset first out indications, and to test annunciator lamps and
circuits.
Annunciators are available in an almost infinite variety of physical arrangements, operating
sequences, and special features. In some cases, the annunciation function is performed by
computer systems using CRT (cathode ray tube) visual displays or recording annunciatorssee
A.5, Special Annunciators.
This Standard is primarily for use with electrical annunciators that use illuminated visual displays
and audible devices. Enclosures with lamps behind labeled translucent windows are commonly
used as visual displays. Annunciators usually operate from electrical contacts that are part of the
devices that sense the process conditions.
In this Standard, sequences making use of more than one indication device as a part of each
visual display to indicate the sequence state are considered to be special because of their many
variations and relatively infrequent use. When additional wiring and sockets are provided,
colored lights such as red and green may be used along with flashing to indicate sequence states
or which is the first of a group of alarms. Colored lights may also be used to uniquely identify
some of the alarms in an annunciatorsee A.8.2, Windows.
ANSI/ISA-S18.1-1979 (R1992)
27
28
ANSI/ISA-S18.1-1979 (R1992)
29
Sequence M usually cannot be used with reflash circuits or to operate from remote reflash
auxiliary outputs since the sequence does not return to the alarm state when the field contact
circuit returns to normal briefly. Refer to A.9.3, Shared Alarm Points, and A.9.5, Auxiliary
Outputs. If this feature is required, sequence A or R should be usedsee A.3.3, Sequence A,
Automatic Reset and A.3.5, Sequence R, Ringback.
A.3.5 Sequence R, ringback
Sequence R is a basic annunciator sequence with ringback that provides distinct visual and
audible indications when process conditions return to normal. The ringback indications are
retained until the process conditions return to normal and the manual reset pushbutton is
operated. A sequence diagram and sequence table for sequence R are shown in Figure 4 of this
Standard.
In some applications, sequence R may have a disadvantage since new momentary alarms
change to slow flashing and new maintained alarms change to on when and during the time the
audible device is silenced by operation of the acknowledge pushbutton. New alarms may be
confused with existing alarms. New alarms may have to be reviewed or logged while fast
flashing, with the continual distraction of the alarm audible device signal. If these features are
not desirable, sequence R-1 with a silence pushbutton or sequence R-1-2 with silence
pushbutton and interlock should be usedsee 4.5, Option Number Designations.
Sequence R includes different visual display indications and different audible device signals for
alarm and ringback. Several variations of this arrangement can be used. Sequence R-8 uses a
common audible device for both alarm and ringback and relies on the different visual display
indications for differentiation. Sequence R-9 uses a time delay device to silence the ringback
audible device after a set time. Sequence R-10 deletes the ringback audible device and uses
only the ringback visual displays. Sequences R-9 and R-10 avoid the need for pushbutton
operation to silence an audible device when process conditions return to normal. Sequence R11 uses a common type of flashing for both alarm and ringback and relies on the different audible
devices for differentiation. See 4.5, Option Number Designations.
Sequence R retains both momentary and maintained alarms in the alarm state until
acknowledged. Sequence R-12 causes momentary alarms to go to the ringback sequence state
as soon as process conditions return to normal. New momentary alarms are evident sooner, but
may be confused with existing alarms in the ringback state.
Sequence R-1-2-9, shown as an example of the use of option number designations in Figure 5,
of this Standard, includes a silence pushbutton and interlock to allow new alarms to be reviewed
or logged while flashing after the audible signal has been silenced and to require operation of the
silence pushbutton first. In addition, the ringback audible device is silenced after a set time to
retain a ringback signal while avoiding the need for pushbutton operation to silence the ringback
audible device when process conditions return to normal.
A.3.6 First out
First out annunciators are used to indicate which one of a group of alarm points operated first. To
accomplish this, the visual display indication for the alarm point that operates first must be
different from the visual display indication for subsequent alarm points in that group. Only one
first out alarm indication can exist in any one first out group.
30
ANSI/ISA-S18.1-1979 (R1992)
When first out annunciators are used primarily to identify the first alarm, a flashing visual display
can be used to indicate the first alarm, and visual displays without flashing can be used to
indicate subsequent alarms. With this approach, the visual display indication for subsequent
alarms does not differentiate between new and acknowledged alarms. Two methods using this
approach are in common use. (1) First out designation F1 designates a first out sequence with no
subsequent alarm state. Subsequent alarms appear in the acknowledged state. Subsequent
visual displays do not flash. The audible device does not operate when subsequent alarms
occur, unless still operating from the first alarm. The first out indication is reset by the
acknowledge pushbutton. It should be noted that subsequent alarms do not lock in when
sequence F1A is used. (2) First out designation F2 designates a first out sequence with no
flashing for subsequent alarms. The audible device operates when subsequent alarms occur.
The first out indication is reset by the acknowledge pushbutton.
To allow the first out visual display indication to be reviewed or logged after silencing the audible
device when using first out designations F1 and F2, a separate silence pushbutton should be
used in addition to the other annunciator pushbuttons. The silence pushbutton feature is
designated by option number 1. see 4.5, Option Number Designations.
When use of the annunciator requires differentiation between new and acknowledged
subsequent alarms, the first out sequence should include different types of visual display flashing
to identify the first alarm while new subsequent alarms are indicated by the usual flashing visual
display. One method using this approach is in common use. First out designation F3 designates
a first out sequence with first out flashing to identify new and acknowledged first alarms and a
first out reset pushbutton to reset the first out indication, whether the process condition was
returned to normal or not. If desired, an interlock can be provided to require operation of the
acknowledge pushbutton before the first out indication can be reset by the first out reset
pushbutton by use of option number 3see 4.5, Option Number Designations.
After the first out indication is reset, that alarm point indicates the process condition in the same
manner as subsequent alarms. The next alarm point to operate will display a first out indication.
First out sequences can be automatic reset or manual reset or can provide ringback indication
when alarms return to normal. First out sequences are designated by a combination of the first
out designation, the basic sequence letter designation, and any required option numbers. Refer
to Figure 1, in this Standard for a first out sequence designation example.
Sequence designations for a range of first out sequences are listed in 4.6, First Out
Designations. Sequence diagrams and sequence tables for three of the common first out
sequences are shown in Figures 6, 7, and 8 of this Standard. Because of the complex nature of
first out annunciator sequences, use of those sequences that are readily available should be
considered when making a selection.
When annunciators include both first out alarm points and alarm points without the first out
feature, the first out windows and alarm modules are usually located together for easy
recognition and to facilitate first out logic bus interconnections. Colored window bezels,
windows, or lamps may be used to identify first out alarm points. Several separate first out
groups can be created by using several first out logic buses.
Annunciator first out windows may not be needed if a recording annunciator or computer printer
is provided for sequence of events analysis.
A.3.7 Test
Annunciator test pushbuttons initiate an annunciator sequence to reveal lamp or circuit failures.
Most annunciators include a test pushbutton and operational test of the sequence, visual display
lamps, audible devices, and pushbuttons. The sequences in this Standard include operational
test as a standard feature.
ANSI/ISA-S18.1-1979 (R1992)
31
Operation of the test pushbutton simulates simultaneous abnormal process conditions on all
related alarm points. Release of the test pushbutton simulates return to normal. Operation of the
other annunciator pushbuttons to complete the sequence and observation of the operation of the
visual displays and audible devices can reveal lamp or circuit failures. Alarm points in the
acknowledged state as a result of actual abnormal process conditions usually remain in the
acknowledged state during test and will be in the acknowledged state after the test sequence.
Since the test signal usually operates the sequence logic circuit in the alarm module, annunciator
input auxiliary circuits such as reflash or time delay circuits and some auxiliary output circuits
may not operate during the test sequence. In some cases, operation of auxiliary outputs during
the test sequence may not be desirable since false alarm signals would be transmitted to the
connected alarm, recording, or control circuits.
Some annunciator sequences make use of visual display indications that are dim in place of off
to reveal lamp failures in addition to an operational test sequence. The dim lamp monitor feature
is designated by option number 13see 4.5, Option Number Designations.
Test pushbuttons used with some electromechanical relay logic annunciators test only the visual
display lamps. Operation of the test pushbutton turns all related visual display lamps on
simultaneously. The lamp test feature is designated by option number 14see 4.5, Option
Number Designations.
A.4 Arrangement
A.4.1 Integral logic annunciators
Integral logic annunciators include visual displays and sequence logic circuits in one assembly
as illustrated in Figure A.2. Plug-in alarm modules contain the sequence logic circuits. The
visual display lamps and windows may or may not be a part of the plug-in alarm modules.
Terminal blocks are provided for the field contact, pushbutton, audible device, and power source
wiring.
32
ANSI/ISA-S18.1-1979 (R1992)
Since the space in integral logic annunciator cabinets is limited, it may be necessary to locate
special power supplies and accessories such as auxiliary output, reflash, ground detector, and
power failure detector components in separate cabinets. The separate cabinets are usually
designed for surface mounting.
Integral logic annunciators should be located so that alarm module replacement and other
required maintenance can be done without excessive interference with nearby activities.
Panel wiring is often used to connect from the annunciator terminal blocks to larger panel
terminal blocks where the field wiring is terminated.
A.4.2 Remote logic annunciators
Remote logic annunciators locate visual displays and sequence logic circuits in separate
assemblies as illustrated in Figure A.3. Lamp cabinets contain the visual displays and the
necessary terminal blocks or plug connectors. The plug-in alarm modules, accessory
components, and special power supplies can be supplied in separate assemblies for rack or
cabinet mounting by the user, or else complete logic cabinets can be supplied by the
manufacturer. Pushbuttons and audible devices are usually located near the lamp cabinets.
Logic cabinets are usually arranged to suit the requirements of a particular annunciator
specification. The arrangement can include space for power supplies and accessories such as
auxiliary output, reflash, ground detector, and power failure detector components. A ground bus
may be required and electrical receptacles or lights may be desirable for use during
maintenance. Large terminal blocks and adequate space for field wiring and terminations can be
provided.
When required, terminal blocks can be specified to be separated from the logic circuits to
minimize circuit damage during installation or to allow installation of terminal blocks and field
wiring before the logic circuits are installed.
To reduce congestion, logic cabinets are often located such that field contact wiring avoids
control panel wiring areas. Special cables with large numbers of small conductors are usually
used to connect between the logic cabinets and the lamp cabinets. These cables often connect
directly to the lamp cabinets so that panel wiring and terminal blocks are not required.
Installation time may be reduced if prefabricated lamp cabinet cables with plug connectors are
provided by the manufacturer. Care must be taken when specifying the length of prefabricated
cables with plug connectors on both ends. In some cases, plug connectors on one end of each
cable are installed in the field after the cables are cut to the correct length.
The higher cost of remote logic annunciators is often justified for large or complex annunciator
systems. Installation and maintenance costs are reduced since the logic cabinets can contain
special power supplies and accessory components, field contact wiring terminates away from
control panels, special requirements for field wiring space and terminal blocks can be met, and
lamp replacement is the only annunciator maintenance required in the control panel area.
ANSI/ISA-S18.1-1979 (R1992)
33
34
ANSI/ISA-S18.1-1979 (R1992)
ANSI/ISA-S18.1-1979 (R1992)
35
All Alarms
Audible Device
and Pushbuttons
A.5.9 Multiplexing
Multiplexing is the use of a single communication channel to transmit many individual signals.
Multiplexing systems may include redundant circuits and communication channels for increased
reliability. While multiplexing is not inherently related to alarms, it is being used with increasing
frequency along with annunciators or as a part of annunciation systems to reduce the amount
and the cost of field contact wiring. Multiplexing should be considered when the length of field
contact wiring is greater than about 1000 feet (300 m).
36
ANSI/ISA-S18.1-1979 (R1992)
Audible devices should meet the environmental requirements that apply to other panel mounted
devices.
A.7 Pushbuttons
Annunciator pushbuttons are momentary manual switches that cause a change from one
annunciator sequence state to another. They are usually located on the panels below the
annunciators or lamp cabinets. Pushbuttons can also be provided on the front of annunciator
cabinets. Usually one normally open or normally closed pushbutton contact is wired to the
annunciator. Pushbuttons can be supplied with annunciators or provided by others.
Miniature or heavy duty pushbuttons can be used, depending on the application and the need to
coordinate with other panel devices. Since annunciator pushbuttons may be operated frequently
and in a hurry when responding to alarms, they should be selected and located for convenient
operation and to minimize the possibility of accidental operation of other nearby pushbuttons.
Pushbuttons should meet the environmental requirements that apply to other panel mounted
devices.
An interlock is usually provided to require operation of acknowledge pushbuttons before alarms
can be reset. It may also be desirable to require operation of silence and acknowledge
pushbuttons or acknowledge and first out reset pushbuttons in sequence to avoid accidental loss
of alarm indications. Sequence option numbers 2 and 3 are provided to add these interlocks
see 4.5, Option Number Designations.
When several annunciators or lamp cabinets in a large control room operate together as a
system, the pushbuttons should be arranged and connected to allow operation from appropriate
locations. As an example, the following arrangement could be used in a control room with
separate supervision and control panels.
Silence Pushbuttons
Acknowledge Pushbuttons
Reset Pushbuttons
Test Pushbuttons
ANSI/ISA-S18.1-1979 (R1992)
37
A.8.2 Windows
The size of annunciator windows has not been standardized among manufacturers. Windows
commonly used are in the order of 2 inches (50 mm) high and 3 inches (75 mm) wide. These
windows often can be subdivided to form two, three, or four smaller windows to reduce the
required panel space when the viewing distance is short or a small amount of lettering is
necessary. These alarm points may make use of a common window or alarm module.
Annunciator windows are usually translucent white with black letters. Clear or white lamps are
normally used. When it is necessary to uniquely identify some of the alarms in an annunciator,
such as more important alarms or alarms related to one process area, it is usually possible to
obtain colored window bezels, windows, or lamps. Methods used and colors available vary
widely. Lamps are often colored by the addition of colored boots that are slipped over the lamps.
The brightness and legibility of displays are reduced when colored windows or lamps are used.
To avoid interfering with more alarms than necessary during relamping, windows or alarm
modules usually can be removed individually from the front.
For best visibility, the windows should be approximately perpendicular to the line of sight of
viewers. Since annunciators and lamp cabinets are often located above other devices on control
panels, some windows are wedge-shaped for better visibility from below. Some control panels
are designed with an inclined section at the top for improved visibility. These factors should be
considered during the design of control panels.
The size of lettering used on annunciator windows should be selected to be legible from any
point in the related operating area. A compromise is required, however, since larger lettering
reduces the number of characters available to identify alarms. For uniform appearance, the
same lettering size should be used for all windows of a given size in any one control room.
Recommended reading distances for different letter sizes are included in ISA Recommended
Practice ISA-RP60.6, "Nameplates, Tags, and Labels for Control Centers" (being prepared at the
time of publication).
In order to identify the monitored variable completely in the space available, abbreviations are
usually required. Abbreviations should be consistent, and periods are usually omitted. For
standard abbreviations, refer to American National Standards Institute Standard ANSI Y1.1,
"Abbreviations for Use on Drawings and in Text." The lettering on each line is usually centered.
To facilitate maintenance, windows can be marked with instrument numbers or small
identification numbers to correlate with similar numbers adjacent to alarm modules. Annunciator
legend lists should be prepared with care, since the legends will appear exactly as indicated.
The arrangement of information on annunciator windows should be consistent. From top to
bottom, the words usually become increasingly specific. For example:
COOLING WATER
HEADER PRESS
BEARING TEMP
LOW
HIGH TRIP
A.8.3 Lamps
Annunciator visual displays usually are incandescent lamps. Two lamps are usually connected
in parallel to light the windows more evenly and also to allow visual displays to function even if
one lamp has failed. Lamps with bayonet bases are usually used to avoid loss of electrical
contact because of vibration.
To minimize maintenance, annunciator lamps are usually operated below the rated voltage. The
particular type of lamp, the rated voltage, and the applied voltage are usually selected by
38
ANSI/ISA-S18.1-1979 (R1992)
annunciator manufacturers. Lamps with a higher watt rating usually cannot be substituted
without damage to annunciator circuits or windows.
Care should be taken so the illumination level in areas where annunciator windows are located is
not so high that legibility is reduced below an acceptable level.
ANSI/ISA-S18.1-1979 (R1992)
39
and normally closed field contacts. Open circuits in the field contact wiring prevent alarms from
normally open contacts, but cause false alarms from normally closed contacts. Short circuits in
the field wiring cause just the opposite results. Disconnecting field contact wiring briefly to locate
grounded wires temporarily prevents alarms from normally open contacts, but causes false
alarms from normally closed contacts. Spare alarm points with normally closed field contacts
require shorting jumpers on the field contact terminal blocks or some other action to avoid the
continuous display of alarms.
The field contact voltage is the voltage applied to the field contacts by the annunciator circuits. It
is usually from 12 to 125 volts and can be either ac or dc. Annunciators with normally open field
contacts often use from 48 to 125 volts for more reliable operation when electromechanical field
contacts are contaminated. Lower voltages may be used with normally closed field contacts
where contamination cannot prevent an alarm and also to be compatible with other low voltage
instrument and control circuits. A single voltage is used when both field contact types are used
with one annunciator.
The annunciator response time is the time period between the operation of the field contacts and
initiation of the alarm state. Momentary field contact operations with a duration of less than the
response time do not initiate alarms. Annunciator response times are in the order of 5 to 50
milliseconds, depending on the manufacturer. Electrical transients induced in the field contact
wiring may cause false annunciator operation if the response time is not long enough. Because
of the filtering provided by the response time, annunciators usually do not require shielded field
contact wiring.
Longer response times or special time delay circuits can usually be provided when required to
prevent false operation caused by extraneous circuit pulses or to avoid nuisance alarms caused
by momentary operation of field contacts.
The steady state current that passes through field contacts from annunciators is usually in the
order of 1 to 10 milliamperes, depending on the manufacturer. This current is necessary to
minimize false operation caused by electrical transients and to provide enough arcing to assist in
cleaning electromechanical field contacts. This current is usually sufficient for proper operation
of solid state field contacts.
The maximum length of field contact wiring that can be used with annunciators depends on the
conductor dc resistance or ac impedance, leakage resistance, the field contact voltage, and the
annunciator input circuit design. Special design may be required when field contact wiring
involves unusually small conductors or long lengths.
A.9.3 Shared alarm points
In many cases, annunciator alarm points are connected to only one field contact. Sometimes
alarm points operate from two or more contacts that are wired in a series or parallel arrangement
to develop the required alarm logic or to avoid nuisance alarms during certain operating or
maintenance conditions. These series or parallel contact arrangements operate together as a
single field contact in relation to the annunciator alarm point.
40
ANSI/ISA-S18.1-1979 (R1992)
In order to conserve space on control panels, it may be desirable to use one annunciator visual
display for more than one related monitored variable. This can be done by operating alarm
points from two or more normally open field contacts in parallel or normally closed field contacts
in series so any field contact operation causes an alarm. When this is done, that alarm point
alarms when the first abnormal process condition occurs, and can return to normal only after all
process conditions have returned to normal. That alarm point cannot alarm subsequent
abnormal process conditions that occur while the first abnormal process condition still exists.
This method is convenient and economical because it does not require special annunciator
circuits, but it should be used only when knowledge of the occurrence of subsequent abnormal
process conditions is not required.
The loss of information that occurs when two or more field contacts are connected in parallel or
series does not occur if reflash circuits are added to the annunciator. Reflash circuits allow two
or more abnormal process conditions to initiate or reinitiate the alarm state of one annunciator
alarm point at any time. Reflash alarm points cannot return to normal until all related process
conditions return to normal.
Two or more field contacts are wired independently to reflash circuits. The reflash circuit outputs
are connected to sequence logic circuits. The annunciator sequence operates in the usual
manner when the first abnormal process condition occurs. When subsequent abnormal process
conditions occur while previous abnormal process conditions still exist, the reflash circuit causes
the sequence to go to the alarm state again. The sequence cannot return to the normal state
until all related process conditions return to normal. Reflash circuits allow annunciators to alarm
the first and all subsequent abnormal process conditions, but the identity of the individual
monitored variables must be determined from nearby instruments, field instruments, or
observation of process conditions.
The number of individual reflash circuits on one reflash module is determined by the
manufacturer. Reflash circuit outputs are interconnected to accommodate the required number
of field contacts and then wired to alarm modules. Unused individual reflash circuits on some
reflash modules may not be available for use with another group, depending on the module
internal connections. In some cases, annunciator circuit design limits the number of reflash
circuits that can be in any one reflash group.
Reflash modules are usually located together and not intermixed with alarm modules. This
allows flexibility as the annunciator requirements develop and change.
A.9.4 Analog input alarm points
While annunciators usually operate from field contacts, they can operate from analog input
signals also. Analog input points are for use with analog monitored variable signals. Additional
logic circuits initiate alarms when the analog signals are above or below set points.
Analog input points can operate from a variety of dc currents and voltages. In some cases
thermocouples, resistance temperature detectors, and ac currents and voltages can be used
also. When required, terminal block points should be specified for grounding the shields of
analog input point field wiring.
Solid state circuits compare the analog input signals against set points established on the printed
circuit boards by adjustable potentiometer. Movable jumpers or switches can be set to determine
whether alarms occur when the signals are above or below the set points. The analog signal
dead band is usually adjustable.
Separate analog input modules have output contacts for connection to alarm modules. In some
cases, the analog input circuits and sequence logic circuits are included in one module.
ANSI/ISA-S18.1-1979 (R1992)
41
42
ANSI/ISA-S18.1-1979 (R1992)
ANSI/ISA-S18.1-1979 (R1992)
43
44
ANSI/ISA-S18.1-1979 (R1992)
ANSI/ISA-S18.1-1979 (R1992)
45
46
ANSI/ISA-S18.1-1979 (R1992)
A.11 Cabinets
Annunciator cabinets and lamp cabinets are usually flush mounted on steel panels. The cabinet
bezels and windows extend about 1 inch (25 mm) in front of the panels. Annunciator cabinets
extend further behind the panels than lamp cabinets. Cabinets usually fit into rectangular cutouts
in the panels and are held in place by clamps. Access for lamps and alarm modules is usually
from the front. Access for wiring is usually from the rear. Openings for ventilation may be
provided. Forced ventilation and high temperature alarm contacts are usually not required.
Special surface mounted annunciator and lamp cabinets with access from the front are also
available.
Logic circuits for use with remote logic annunciators usually can be supplied as open chassis
assemblies, enclosed chassis assemblies, or 19 inch (475 mm) rack mount assemblies for
mounting in logic cabinets by others. Logic circuits can also be provided in free-standing or
surface mounted logic cabinets.
Annunciator cabinets are usually for general purpose indoor installation and are classified as
NEMA 1. Special cabinets to meet NEMA 12 indoor driptight and dusttight requirements, and
NEMA 4 indoor and outdoor watertight and dusttight requirements may also be available. For
NEMA enclosure requirements, refer to National Electrical Manufacturers Association Standard
NEMA ICS 6, "Enclosures for Industrial Controls and Systems." For annunciators located in
hazardous atmospheres, see A.10, Hazardous Atmosphere Location Annunciators.
47
occur on ungrounded annunciator circuits, ground detectors operate annunciator alarms and the
grounds can be located and removed without affecting the annunciator operation or the power
source.
Inverters and power supplies used with annunciators should be provided with overload protection
and should not require manual actions when voltage is applied or after brief overloads occur.
A.12.3 Backup power
Annunciators are no more reliable than the power on which they operate. The power sources,
power supplies, and power distribution systems for annunciators should provide the reliability
required by the annunciation function.
A single power supply may provide power for only a few alarm points or for an entire annunciator.
An annunciator power source may come from a 120 volt ac lighting panel or from a large battery
and charger system. The failure of a single power supply or power source can disable an entire
annunciator, or backup power supplies and power sources can be used so that any single failure
affects no more than one alarm point. Power supply system designs should suit the power
sources available and provide the required annunciator reliability.
While an annunciator powered from a dc power source provides reliable operation, a single
failure in the dc distribution panel or annunciator feeder can leave the annunciator without power.
In addition, dc power source buses are often ungrounded. When a ground occurs, the load
circuits are switched off and on again in turn until the grounded circuit is located. When the
annunciator feeder is switched off and on again, the alarm points usually assume a random
sequence state and auxiliary outputs may operate incorrectly. It is then necessary for the
annunciator pushbuttons to be operated before the correct alarms are displayed again.
When two independent power sources are used to power an important annunciator, the reliability
becomes very high. Backup power supplies can also be used so that failure of a single power
supply does not affect annunciator operation. When backup power sources or power supplies
are used, power failure detectors should be provided to alarm the failure of each power source
and power supply.
A.12.4 Power failure detectors
Power failure detectors provide outputs to alarm the loss of voltage on annunciator logic circuit,
lamp, and field contact power buses. Power failure detectors cannot alarm on the failed
annunciator, so another alarm device must be used.
Local annunciator power failure can be alarmed on central control room annunciators. Separate
CRT visual display or recording annunciators can be used to alarm control room annunciator
failure. In some cases, separate annunciator audible and visual devices powered by an
independent power source are provided to alarm annunciator power failure. In these cases the
independent power source must, in turn, be monitored by the annunciator.
A.12.5 Ground detectors
Annunciator buses are often ungrounded so that accidental circuit grounds can be detected and
ground alarms initiated without affecting the operation of annunciators. Grounds on the field
contact wiring are the most common since this wiring is often run in areas that have an adverse
environment.
Ground detectors are usually connected to alarm the presence of a ground on either conductor of
an ungrounded system. The ground should be located and removed before a second ground
occurs, since two or more simultaneous grounds can affect annunciator operation.
48
ANSI/ISA-S18.1-1979 (R1992)
Grounds are usually located by disconnecting individual circuits in turn until the ground detector
indicates that no ground exists. The ground is on the disconnected circuit.
Annunciator circuits are usually disconnected to check for grounds by briefly disconnecting field
contact wires or by briefly removing individual alarm modules. Large annunciators often include
power supply system disconnect switches to subdivide the system for more convenient ground
isolation and maintenance. Some remote logic annunciators include field contact wiring terminal
blocks that include switches or other devices to allow ground isolation without affecting the field
wiring terminations.
The location of grounds is made easier if an indication of grounds is within sight of the
disconnecting devices. Lights operating from ground detectors can be located in alarm module
and terminal block areas for this purpose.
ANSI/ISA-S18.1-1979 (R1992)
49
50
ANSI/ISA-S18.1-1979 (R1992)
This Appendix is included for informational purposes and is not a part of this Standard.
The sequences in ISA Recommended Practice ISA-RP18.1-1965 that are superseded and the
corresponding new sequence designations used in this Standard are listed below.
ISA-RP18.1-1965
ISA-Sl8.1 Sequence
Designations
Sequences
ISA-1
ISA-1A
ISA-1B
ISA-1C
ISA-1D
A
A-5
A-4
A-4-5
A-13
ISA-1E
Special(1)
ISA-1F
Special(1)
ISA-2
ISA-2A
ISA-2B
ISA-2C
ISA-2D
Special(1)
R-8
R-11
M
M-5
ISA-3
Special(2)
ISA-3A
Special(2)
ISA-3B
Special(2)
ISA-4
ISA-4A
Special(1)
F1A
ANSI/ISA-S18.1-1979 (R1992)
51
ISBN: 0-87664-346-2