Control of Moisture and Other Contaminants in Refrigerant Systems
Control of Moisture and Other Contaminants in Refrigerant Systems
Control of Moisture and Other Contaminants in Refrigerant Systems
MOISTURE
Sources of Moisture
Moisture in a refrigerant system results from
Table 1
Effects of Moisture
Excess moisture in a refrigerating system can cause one or all of
the following undesirable effects:
160
150
140
130
120
110
460
400
340
290
240
200
700
560
440
350
270
210
4100
3600
3150
2750
2400
2100
460
400
344
290
240
200
450
380
320
270
220
180
2600
2300
2000
1800
1600
1400
4200
3600
3200
2800
2400
2000
1780
1580
1400
1220
1080
930
100
90
80
70
60
168
140
113
90
70
165
128
98
76
58
44
1800
1580
1350
1140
970
168
140
113
90
70
148
120
95
74
57
1200
1000
900
770
660
1800
1500
1300
1100
880
810
690
580
490
400
50
40
30
20
10
55
44
34
26
20
44
32
23.3
16.6
11.8
26
14
830
690
573
472
384
55
44
34
26
20
44
33
25
18
13
560
470
400
330
270
730
600
490
390
320
335
278
225
180
146
0
10
20
30
40
15
11
8
6
4
8.3
5.7
3.8
2.5
1.7
308
244
195
152
120
15
11
8
6
10
7
5
3
2
220
180
140
110
90
250
200
150
120
89
115
90
69
53
40
1.1
0.7
0.4
0.3
0.1
0.1
91
68
50
37
27
19
70
53
40
30
22
16
66
49
35
25
18
12
30
22
16
11
8
5
50
60
70
80
90
100
Ice or solid hydrate separates from refrigerants if the water concentration is high enough and the temperature low enough. Solid
hydrate, a complex molecule of refrigerant and water, can form at
temperatures higher than those required to separate ice. Liquid water
forms at temperatures above those required to separate ice or solid
3
2
1
0.8
0.5
0.3
1.5
1
0.6
0.4
0.2
0.1
Data on R-134a adapted from Thrasher et al. (1993) and Allied-Signal Corporation.
Data on R-123 adapted from Thrasher et al. (1993) and E.I. DuPont de Nemours &
Company. Remaining data adapted from E.I. DuPont de Nemours & Company and
Allied-Signal Corporation.
6.1
6.2
R-22
100
90
80
70
30.1
34.8
5.5
6.1
6.3
7.5
0.400
0.397
0.405
0.404
4.25
4.57
4.53
4.69
0.542
0.571
0.573
0.585
0.63
0.64
0.65
0.66
60
50
40
30
43.1
50.5
8.2
9.0
9.9
11.2
0.401
0.391
0.390
0.378
19.7
21.7
24.7
26.9
4.82
4.97
5.16
5.17
0.625
0.637
0.650
0.654
0.66
0.66
0.66
0.65
20
0
20
40
57.9
62.4
71.0
11.9
13.1
15.3
17.1
0.351
0.301
0.251
0.203
29.5
32.1
37.4
52.2
5.09
4.91
4.78
4.43
0.639
0.584
0.543
0.484
0.61
0.53
0.47
0.40
1949). The opposite is true for Refrigerants 22 and 502. The ratio
of mass concentrations differs for each refrigerant; it also varies
with temperature. Table 2 shows the distribution ratios of water in
the vapor phase to water in the liquid phase for common refrigerants. It can be used to calculate the equilibrium water concentration
of the liquid-phase refrigerant if the gas phase concentration is
known, and vice versa. The water content in the vapor phase is
determined by
Pw
W = -------------0( P w)
( d w)
------------0
( d R)
(1)
where
W=
Pw =
(P w)0 =
(dw)0 =
(dR)0 =
Drying Methods
(2)
where
hL(liquid) = saturated liquid enthalpy for refrigerant at liquid temperature
hL(evap) = saturated liquid enthalpy for refrigerant at evaporating
temperature
hfg(evap) = latent heat of vaporization of refrigerant at evaporating
temperature
Table 1 lists the saturated water content of the R-12 liquid phase
at 20F as 3.8 ppm. Table 2 is used to determine the saturated vapor
phase water content as
Moisture Indicators
Moisture-sensitive elements that change color according to
moisture content can gage the systems moisture level; the color
changes at a low enough level to be safe. Manufacturers instructions must be followed because the color change point is also
affected by liquid-line temperature and the refrigerant used.
Moisture Measurement
Techniques for measuring the amount of moisture in a compressor, or in an entire system, are discussed in Chapter 45. The following methods are used to measure the moisture content of various
halocarbon refrigerants. The moisture content to be measured is
generally in the parts-per-million range, and the procedures require
special laboratory equipment and techniques.
The Karl Fischer method is suitable for measuring the moisture
content of a refrigerant, even if it contains mineral oil. Although different firms have slightly different ways of performing this test and
get somewhat varying results, the method remains the common
industry practice for determining moisture content in refrigerants.
The refrigerant sample is bubbled through predried methyl alcohol
in a special sealed glass flask; any water present remains with the
alcohol. In volumetric titration, Karl Fischer reagent is added, and
the solution is immediately titrated to a dead stop electrometric
end point. The reagent reacts with any moisture present so that the
amount of water in the sample can be calculated from a previous calibration of the Karl Fischer reagent.
In coulometric titration (ARI Standard 700c), water is titrated
with iodine that is generated electrochemically. The instrument
measures the quantity of electric charge used to produce the iodine
and titrate the water and calculates the amount of water present.
These titration methods, considered among the most accurate,
are also suitable for measuring the moisture content of unused lubricant or other liquids. Special instruments designed for this particular analysis are available from laboratory supply companies.
Haagen-Smit et al. (1970) describe improvements in the equipment
and technique that significantly reduce analysis time.
The gravimetric method for measuring moisture content of
refrigerants is described in ASHRAE Standards 35 and 63.1. It is
not widely used in the industry. In this method, a measured
amount of refrigerant vapor is passed through two tubes in series,
each containing phosphorous pentoxide (P2O5). Moisture present
in the refrigerant reacts chemically with the P2O5 and appears as
an increase in mass in the first tube. The second tube is used as a
tare. This method is satisfactory when the refrigerant is pure, but
6.3
Desiccants
Desiccants used in refrigeration systems adsorb or react chemically with the moisture contained in a liquid or gaseous refrigerant/
lubricant mixture. Solid desiccants, used widely as dehydrating
agents in refrigerant systems, remove moisture from both new and
field-installed equipment. The desiccant is contained in a device
called a drier (also spelled dryer) or filter-drier and can be installed
in either the liquid or the suction line of a refrigeration system.
Desiccants must remove most of the moisture and not react unfavorably with any other materials in the system. Activated alumina,
silica gel, and molecular sieves are the most widely used desiccants
acceptable for refrigerant drying. Water is physically adsorbed on
the internal surfaces of these highly porous desiccant materials.
Activated alumina and silica gel have a wide range of pore sizes,
which are large enough to adsorb refrigerant, lubricant, additives,
and water molecules. Pore sizes of molecular sieves, however, are
uniform, with an aperture of approximately 0.3 nm for a type 3A
molecular sieve or 0.4 nm for a type 4A molecular sieve. The uniform openings exclude lubricant molecules from the adsorption
surfaces. Molecular sieves can be selected to exclude refrigerant
molecules, as well. This property gives the molecular sieve the advantage of increasing water capacity and improving chemical compatibility between refrigerant and desiccant (Cohen 1993, 1994;
Cohen and Blackwell 1995). The drier or desiccant manufacturer
can provide information about which desiccant adsorbs or excludes
a particular refrigerant.
Drier manufacturers offer combinations of desiccants that can be
used in a single drier and may have advantages over a single desiccant because they can adsorb a greater variety of refrigeration contaminants. Two combinations are activated alumina with molecular
sieves and silica gel with molecular sieves. Activated carbon is also
used in some mixtures.
Desiccants are available in granular, bead, and block forms. Solid
core desiccants, or block forms, consist of desiccant beads, granules,
or both held together by a binder (Walker 1963). The binder is
usually a nondesiccant material. Suitable filtration, adequate contact
between desiccant and refrigerant, and low pressure drop are
obtained by properly sizing the desiccant particles used to make up
the core, and by the proper geometry of the core with respect to the
flowing refrigerant. Beaded molecular sieve desiccants have higher
water capacity per unit mass than solid-core desiccants. The composition and form of the desiccant is varied by drier manufacturers to
achieve the desired properties.
Desiccants that take up water by chemical reaction are not recommended. Calcium chloride reacts with water to form a corrosive liquid.
Barium oxide is known to cause explosions. Magnesium perchlorate
and barium perchlorate are powerful oxidizing agents, which are
6.4
Reactivation of Desiccants
Desiccant
Activated alumina
Silica gel
Molecular sieves
Temperature, F
400 to 600
350 to 600
500 to 660
LIVE GRAPH
Fig. 1
LIVE GRAPH
Fig. 2
LIVE GRAPH
Fig. 3
6.5
Fig. 5 Moisture Equilibrium Curves for Three Common Desiccants in R-134a and 2% POE Lubricant at 75F
LIVE GRAPH
LIVE GRAPH
Fig. 4
Desiccant Applications
In addition to removing water, desiccants may adsorb or react
with acids, dyes, chemical additives, and refrigerant lubricant reaction products.
Acids. Generally, acids can harm refrigerant systems. The
amount of acid a refrigerant system tolerates depends in part on the
size, mechanical design and construction of the system, type of
motor insulation, type of acid, and amount of water in the system.
Desiccants acid removal capacity is difficult to determine because the environment is complex. Hoffman and Lange (1962) and
Mays (1962) showed that desiccants remove acids from refrigerants
and lubricants by adsorption and/or chemical reaction. Hoffman and
Lange also showed that the loading of water on the desiccant, type
of desiccant, and type of acid play major roles in a desiccants ability to remove acids from refrigerant systems. In addition, acids
formed in these systems can be inorganic, such as HCl and HF, or a
mixture of organic acids. All of these factors must be considered to
establish acid capacities of desiccants.
LIVE GRAPH
6.6
additives may be adsorbed by silica gel and activated alumina.
Because of small pore size, molecular sieves generally do not adsorb
additives or lubricant.
Driers
A drier is a device containing a desiccant. It collects and holds
moisture, but also acts as a filter and adsorber of acids and other contaminants.
To prevent moisture from freezing in the expansion valve or capillary tube, a drier is installed in the liquid line close to these devices.
Hot locations should be avoided. Driers can function on the lowpressure side of expansion devices, but this is not the preferred location (Jones 1969).
Moisture is reduced as liquid refrigerant passes through a drier.
However, Krause et al. (1960) showed that considerable time is
required to reach moisture equilibrium in a refrigeration unit. The
moisture is usually distributed throughout the entire system, and time
is required for the circulating refrigerant/lubricant mixture to carry
the moisture to the drier. Cohen (1994) and Cohen and Dunne (1987)
discuss the kinetics of drying refrigerants in circulating systems.
Loose-filled driers should be mounted vertically, with downward
refrigerant flow. In this configuration, both gravity and drag forces
act in the downward direction on the beads. Settling of the beads
creates a void space at the top, which is not a problem.
Vertical orientation with upward flow, where gravity and drag act
in opposite directions, should be avoided because the flow will
likely fluidize the desiccant beads, causing the beads to move
against each another. This promotes attrition or abrasion of the
beads, producing fine particles that can contaminate the system.
Settling creates a void space between the retention screens, promoting fluidization.
Horizontal mounting should also be avoided with a loose-filled
drier because bead settling creates a void space that promotes fluidization, and may also produce a channel around the beads that
reduces drying effectiveness.
Driers are also used effectively to clean systems severely contaminated by hermetic motor burnouts and mechanical failures (see
the section on System Cleanup Procedure after Hermetic Motor
Burnout).
Drier Selection
The drier manufacturers selection chart lists the amount of desiccants, flow capacity, filter area, water capacity, and a specific recommendation on the type and refrigeration capacity of the drier for
various applications.
The equipment manufacturer must consider the following factors
when selecting a drier:
1. The desiccant is the heart of the drier and its selection is most
important. The section on Desiccants has further information.
2. The driers water capacity is measured as described in ARI Standard 710. Reference points are set arbitrarily to prevent confusion
arising from determinations made at other points. The specific
refrigerant, amount of desiccant, and effect of temperature are all
considered in the statement of water capacity.
3. The liquid-line flow capacity is listed at 1 psi pressure drop
across the drier by the official procedures of ARI Standard 710
and ANSI/ASHRAE Standard 63.1. Rosen et al. (1965) described a closed-loop method for evaluating filtration and flow
characteristics of liquid-line refrigerant driers. The flow capacity
of suction-line filters and filter-driers is determined according
to ARI Standard 730 and ANSI/ASHRAE Standard 78. ARI
Standard 730 gives recommended pressure drops for selecting
suction-line filter-driers for permanent and temporary installations. Flow capacity may be reduced quickly when critical quantities of solids and semisolids are filtered out by the drier.
OTHER CONTAMINANTS
Refrigerant filter-driers are the principal devices used to remove
contaminants from refrigeration systems. The filter-drier is not a
substitute for good workmanship or design, but a maintenance tool
necessary for continued and proper system performance. Contaminants removed by filter-driers include moisture, acids, hydrocarbons with a high molecular weight, oil decomposition products, and
insoluble material, such as metallic particles and copper oxide.
6.7
Noncondensable Gases
Gases, other than the refrigerant, are another contaminant frequently found in refrigerating systems. These gases result (1) from
incomplete evacuation, (2) when functional materials release sorbed
gases or decompose to form gases at an elevated temperature during
system operation, (3) through low-side leaks, and (4) from chemical
reactions during system operation. Chemically reactive gases, such
as hydrogen chloride, attack other components, and, in extreme
cases, the refrigerating unit fails.
Chemically inert gases, which do not liquefy in the condenser,
reduce cooling efficiency. The quantity of inert, noncondensable
gas that is harmful depends on the design and size of the refrigerating unit and on the nature of the refrigerant. Its presence contributes
to higher-than-normal head pressures and resultant higher discharge
temperatures, which speed up undesirable chemical reactions.
Gases found in hermetic refrigeration units include nitrogen,
oxygen, carbon dioxide, carbon monoxide, methane, and hydrogen. The first three gases originate from incomplete air evacuation
or a low-side leak. Carbon dioxide and carbon monoxide usually
form when organic insulation is overheated. Hydrogen has been
detected when a compressor is experiencing serious bearing wear.
These gases are also found where a significant refrigerant/lubricant
6.8
Motor Burnouts
Motor burnout is the final result of hermetic motor insulation
failure. During burnout, high temperatures and arc discharges can
severely deteriorate the insulation, producing large amounts of carbonaceous sludge, acid, water, and other contaminants. In addition,
a burnout can chemically alter the compressor lubricant, and/or
thermally decompose refrigerant in the vicinity of the burn. Products of burnout escape into the system, causing severe cleanup problems. If decomposition products are not removed, replacement
motors fail with increasing frequency.
Although the Refrigeration Service Engineers Society (RSES
1988) differentiates between mild and severe burnouts, many compressor manufacturers service bulletins treat all burnouts alike. A
rapid burn from a spot failure in the motor winding results in a mild
burnout with little lubricant discoloration and no carbon deposits. A
severe burnout occurs when the compressor remains online and
burns over a longer period, resulting in highly discolored lubricant,
carbon deposits, and acid formation.
Because the condition of the lubricant can be used to indicate
the amount of contamination, the lubricant should be examined
during the cleanup process. Wojtkowski (1964) stated that acid in
R-22/mineral oil systems should not exceed 0.05 total acid number
(mg KOH per g oil). Commercial acid test kits can be used for this
analysis. An acceptable acid number for other lubricants has not
been established.
Various methods are recommended for cleaning a system after
hermetic motor burnout (RSES 1988). However, the suction-line
filter-drier method is commonly used (see the section on System
Cleanup Procedure after Hermetic Motor Burnout).
Field Assembly
Proper field assembly and maintenance are essential for contaminant control in refrigerating systems and to prevent undesirable refrigerant emissions to the atmosphere. Driers may be too
small or carelessly handled so that drying capacity is lost. Improper tube-joint soldering is a major source of water, flux, and
oxide scale contamination. Copper oxide scale from improper
brazing is one of the most frequently observed contaminants.
Careless tube cutting and handling can introduce excessive quantities of dirt and metal chips. Take care to minimize these sources
of internal contamination. In addition, because an assembled system cannot be dehydrated easily, oversized driers should be installed. Even if components are delivered sealed and dry, weather
and the amount of time the unit is open during assembly can introduce large amounts of moisture.
In addition to internal sources, external factors can cause a unit to
fail. Too small or too large transport tubing, mismatched or misapplied components, fouled air condensers, scaled heat exchangers,
inaccurate control settings, failed controls, and improper evacuation
are some of these factors.
Procedure
A. Make sure a burnout has occurred. Although a motor that will
not start appears to be a motor failure, the problem may be
improper voltage, starter malfunction, or a compressor mechanical fault (RSES 1988). Investigation should include the following steps:
1. Check for proper voltage.
2. Check that the compressor is cool to the touch. An open internal overload could prevent the compressor from starting.
3. Check the compressor motor for improper grounding using a
megohmmeter or a precision ohmmeter.
4. Check the external leads and starter components.
5. Obtain a small sample of oil from the compressor, examine it
for discoloration, and analyze it for acidity.
B. Safety. In addition to electrical hazards, service personnel
should be aware of the hazard of acid burns. If the lubricant or
sludge in a burned-out compressor must be touched, wear rubber
gloves to avoid a possible acid burn.
C. Cleanup after a burnout. Just as proper installation and service
procedures are essential to prevent compressor and system failures, proper system cleanup and installation procedures when
installing the replacement compressor are also essential to prevent repeat failures. Key elements of the recommended procedures are as follows:
1. U.S. federal regulations require that the refrigerant be isolated in the system or recovered into an external storage container to avoid discharge into the atmosphere. Before
opening any portion of the system for inspection or repairs,
refrigerant should be recovered from that portion until the
vapor pressure reduces to less than 12.7 psia (4 in. Hg vacuum) for R-22 or 9.8 psia (10 in. Hg vacuum) for CFC or
other HCFC systems.
2. Remove the burned-out compressor and install the replacement. Save a sample of the new compressor lubricant that has
not been exposed to refrigerant and store in a sealed glass bottle. This will be used later for comparison.
3. Inspect all system controls such as expansion valves, solenoid valves, check valves, etc. Clean or replace if necessary.
4. Install an oversized drier in the suction line to protect the
replacement compressor from any contaminants remaining
in the system. Install a pressure tap upstream of the filterdrier, to allow measuring the pressure drop from tap to service valve during the first hours of operation to determine
whether the suction line drier needs to be replaced.
5. Remove the old liquid-line drier, if one exists, and install a
replacement drier of the next larger capacity than is normal
for this system. Install a moisture indicator in the liquid line
if the system does not have one.
6. Evacuate and leak-check the system or portion opened to the atmosphere according to the manufacturers recommendations.
7. Recharge the system and begin operations according to the
manufacturers start-up instructions, typically as follows:
a. Observe pressure drop across the suction line drier for the
first 4 h. Follow the manufacturers guide; otherwise,
Fig. 7
Fig. 7
6.9
2. Make a trap from 1 3/8 in. copper tubing and valves. Attach
this trap to the suction and discharge gage port connections
with a charging hose. By blowing discharge gas through the
trap and into the suction valve, enough lubricant will be collected in the trap for analysis. This trap becomes a tool that
can be used repeatedly on any system that has suction and
discharge service valves. Be sure to clean the trap after every
use to avoid cross contamination.
B. On semihermetic compressors, remove the cylinder head to
determine the severity of burnout. Dismantle the compressor for
solvent cleaning and hand wiping to remove contaminants.
Consult the manufacturers recommendations on compressor
rebuilding and motor replacement.
C. In rare instances on a close-coupled system, where it is not feasible to install a suction line drier, the system can be cleaned by
repeated changes of the cores in the liquid line drier and repeated
lubricant changes.
D. On heat pumps, the four-way valve and compressor should be
carefully inspected after a burnout. In cleaning a heat pump after
a motor burnout, it is essential to remove any drier originally
installed in the liquid line. These driers may be replaced for
cleanup, or a biflow drier may be installed in the common reversing liquid line.
E. Systems with a critical charge require a particular effort for
proper operation after cleanup. If an oversized liquid-line drier
is installed, an additional charge must be added. Check with
the drier manufacturer for specifications. However, no additional charge is required for the suction line drier that may be
added.
F. The new compressor should not be used to pull a vacuum. Refer
to the manufacturers recommendations for evacuation. Normally, the following method is used, after determining that there
are no refrigerant leaks in the system:
a. Pull a high vacuum to an absolute pressure of less than
500 m Hg for several hours.
b. Allow the system to stand several hours to be sure the vacuum is maintained. This requires a good vacuum pump and
an accurate high-vacuum gage.
6.10
CHILLER DECONTAMINATION
Chiller decontamination is used to clean reciprocating, rotary
screw, and centrifugal machines. Large volumes of refrigerant are
circulated through a contaminated chiller while continuously
being reclaimed. It has been used successfully to restore many
chillers to operating specifications. Some chillers have been saved
from early retirement by decontamination procedures. Variations
of the procedure are myriad and have been used for burnouts,
water-flooded barrels, particulate incursions, chemical contamination events, brine leaks, and oil strips. One frequently used technique is to perform numerous batch cycles, thus increasing the
velocity-based cleansing component. Excess oil is stripped out to
improve chiller heat transfer efficiency. The full oil charge can be
removed in preparation for refrigerant conversion.
Low-pressure units require different machinery than high-pressure
units. It is best to integrate decontamination and mechanical
services early into one overall procedure. On machines that require
compressor rebuild, it is best to perform decontamination work while
the compressor is removed or before it is rebuilt, particularly for
reciprocating units. Larger-diameter or relocated access ports may
be requested. The oil sump will be drained. For chillers that cannot
be shut down, special online techniques have been developed using
reclamation. The overall plan is coordinated with operations personnel to prevent service interruptions. For some decontamination
REFERENCES
ARI. 1999. Appendix C to ARI Standard 700Analytical procedures for
ARI Standard 700. Standard 700c-1999. Air-Conditioning and Refrigeration Institute, Arlington, VA.
ARI. 2004. Liquid-line driers. Standard 710-04. Air-Conditioning and
Refrigeration Institute, Arlington, VA.
ARI. 2001. Flow-capacity rating and application of suction-line filters and
filter-driers. Standard 730-01. Air-Conditioning and Refrigeration Institute, Arlington, VA.
ASHRAE. 1992. Method of testing desiccants for refrigerant drying. Standard 35-1992.
ASHRAE. 1995. Method of testing liquid line refrigerant driers. ANSI/
ASHRAE Standard 63.1-1995 (RA 01).
ASHRAE. 1996. Method of testing liquid line filter-drier filtration capability. ANSI/ASHRAE Standard 63.2-1996.
ASHRAE. 1985. Method of testing flow capacity of suction line filter driers.
ANSI/ASHRAE Standard 78-1985 (RA 03).
ASHRAE. 2002. Reducing the release of halogenated refrigerants from
refrigerating and air-conditioning equipment and systems. ANSI/
ASHRAE Standard 147-2002.
ASTM. 2003. Standard specification for seamless copper tube for air conditioning and refrigeration field service. Standard B280-03. American
Society for Testing and Materials, West Conshohocken, PA.
Brisken, W.R. 1955. Moisture migration in hermetic refrigeration systems as
measured under various operating conditions. Refrigerating Engineering
(July):42.
Castrol. 1992. Technical Bulletin 2. Castrol Industrial North America,
Specialty Products Division, Irvine, CA.
Cavestri, R.C. and W.R. Schafer. 1999. Equilibrium water capacity of desiccants in mixtures of HFC refrigerants and appropriate lubricants.
ASHRAE Transactions 104(2):60-65.
Cavestri, R.C. and D.L. Schooley. 1998. Test methods for inorganic acid
removal capacity in desiccants used in liquid line driers. ASHRAETransactions 104(1B):1335-1340.
Cohen, A.P. 1993. Test methods for the compatibility of desiccants with
alternative refrigerants. ASHRAE Transactions 99(1):408-412.
Cohen, A.P. 1994. Compatibility and performance of molecular sieve desiccants with alternative refrigerants. Proceedings of the International Conference: CFCs, The Day After. International Institute of Refrigeration,
Paris.
Cohen, A.P. and C.S. Blackwell. 1995. Inorganic fluoride uptake as a measure of relative compatibility of molecular sieve desiccants with fluorocarbon refrigerants. ASHRAE Transactions 101(2):341-347.
Cohen, A.P. and S.R. Dunne. 1987. Review of automotive air-conditioning
drydown rate studiesThe kinetics of drying Refrigerant 12. ASHRAE
Transactions 93(2):725-735.
DeGeiso, R.C. and R.F. Stalzer. 1969. Comparison of methods of moisture
determination in refrigerants. ASHRAE Journal (April).
Doderer, G.C. and H.O. Spauschus. 1966. A sealed tube-gas chromatograph
method for measuring reaction of Refrigerant 12 with oil. ASHRAE
Transactions 72(2):IV.4.1-IV.4.4.
Dunne, S.R. and T.J. Clancy. 1984. Methods of testing desiccant for refrigeration drying. ASHRAE Transactions 90(1A):164-178.
DuPont. 1992. Acceptance specification for used refrigerants. Bulletin H31790-1. E.I. DuPont de Nemours and Company, Wilmington, DE.
Elsey, H.M. and L.C. Flowers. 1949. Equilibria in Freon-12Water systems. Refrigerating Engineering (February):153.
Elsey, H.M., L.C. Flowers, and J.B. Kelley. 1952. A method of evaluating
refrigerator oils. Refrigerating Engineering (July):737.
Griffith, R. 1993. Polyolesters are expensive, but probably a universal fit. Air
Conditioning, Heating & Refrigeration News (May 3):38.
Gully, A.J., H.A. Tooke, and L.H. Bartlett. 1954. Desiccant-refrigerant
moisture equilibria. Refrigerating Engineering (April):62.
Gustafsson, V. 1977. Determining the air content in small refrigeration systems. Purdue Compressor Technology Conference.
Haagen-Smit, I.W., P. King, T. Johns, and E.A. Berry. 1970. Chemical
design and performance of an improved Karl Fischer titrator. American
Laboratory (December).
Hoffman, J.E. and B.L. Lange. 1962. Acid removal by various desiccants.
ASHRAE Journal (February):61.
6.11
Walker, W.O., S. Rosen, and S.L. Levy. 1962. Stability of mixtures of refrigerants and refrigerating oils. ASHRAE Journal (August):59.
Wojtkowski, E.F. 1964. System contamination and cleanup. ASHRAE Journal (June):49.
BIBLIOGRAPHY
Boing, J. 1973. Desiccants and driers. RSES Service Manual, Section 5, 62016B. Refrigeration Service Engineers Society, Des Plaines, IL.
Burgel, J., N. Knaup, and H. Lotz. 1988. Reduction of CFC-12 emission
from refrigerators in the FRG. International J ournal of Refrigeration
11(4).
Byrne, J.J., M. Shows, and M.W. Abel. 1996. Investigation of flushing and
clean-out methods for refrigeration equipment to ensure system compatibility. Air-Conditioning and Refrigeration Technology Institute, Arlington, VA. DOE/CE/23810-73.
DuPont. 1976. Mutual solubilities of water with fluorocarbons and fluor ocarbon-hydrate formation. DuPont de Nemours and Company, Wilmington, DE.
Guy, P.D., G. Tompsett, and T.W. Dekleva. 1992. Compatibilities of nonmetallic materials with R-134a and alternative lubricants in refrigeration
systems. ASHRAE Transactions 98(1):804-816.
Jones, E. 1964. Determining pressure drop and refrigerant flow capacities of
liquid line driers. ASHRAE Journal (February):70.
Kauffman, R.E. 1992. Sealed tube tests of refrigerants from field systems
before and after recycling. ASHRAE Transactions 99(2):414-424.
Kitamura, K., T. Ohara, S. Honda, and H. SakaKibara. 1993. A new
refrigerant-drying method in the automotive air conditioning system
using HFC-134a. ASHRAE Transactions 99(1):361-367.
Manz, K.W. 1988. Recovery of CFC refrigerants during service and recycling by the filtration method. ASHRAE Transactions 94(2):2145-2151.
McCain, C.A. 1991. Refrigerant reclamation protects HVAC equipment
investment. ASHRAE Journal 33(4).
Sundaresan, S.G. 1989. Standards for acceptable levels of contaminants in
refrigerants. In CFCsTime of Transition, pp. 220-223. ASHRAE.
Walker, W.O. 1960. Contaminating gases in refrigerating systems. In RSES
Service Manual, Section 5, 620-15. Refrigeration Service Engineers
Society, Des Plaines, IL.
Walker, W.O. 1985. Methyl alcohol in refrigeration. In RSES Service Manual, Section 5, 620-17A. Refrigeration Service Engineers Society, Des
Plaines, IL.
Zahorsky, L.A. 1967. Field and laboratory studies of wax-like contaminants in
commercial refrigeration equipment. ASHRAE Transactions 73(1):II.1.1II.1.9.
Zhukoborshy, S.L. 1984. Application of natural zeolites in refrigeration
industry. Proceedings of the International Symposium on Zeolites,
Portoroz, Yugoslavia (September).