C-PAC Gas R410A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

MITSUBISHI ELECTRIC SPLIT TYPE AIR CONDITIONERS

Series

Eco Changes is the Mitsubishi Electric Groups environmental statement,


and expresses the Groups stance on environmental management.
Through a wide range of businesses, we are helping contribute to the
realization of a sustainable society.

The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series
9000 of the International Standard Organization (ISO) based on a review of Quality management for
the production of refrigeration and air conditioning equipment.
ISO Authorization System
The ISO 9000 series is a plant authorization system relating to quality management as stipulated by
the ISO. ISO 9001 certifies quality management based on the "design, development, production,
installation and auxiliary services" for products built at an authorized plant.

FM33568 / ISO 9001;2008

Commercial Packaged
Air-conditioner

Cooling only series/Heat pump series


The Air Conditioning & Refrigeration Systems Works acquired environmental management system
standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO).
Registered on March 10, 1998.

Warning

Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.

- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, during repair, or at the time of disposal of the
unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.

http://Global.MitsubishiElectric.com

MEE13K027

New publication effective Feb. 2014


Specifications subject to change without notice

Product Line Up
New models made a debut
debut, employing HFC R410A
R410A.

With the comprehensive lineup of products, including the floor standing


type and ceiling concealed type, it has been made easier for you to use
them for offices, stores, factories, hotels and a variety of other applications.

Cooling Only series NEW


Type

50Hz

8HP

Page8 - Page14

PFV-P200YM-A

10HP
PFV-P250YM-A

16HP
PFV-P400YM-A

20HP
PFV-P500YM-A

Indoor unit
Floor standing
Outdoor unit
Page8 - Page14

PUV-P200YM-A
PEV-P200YM-A

PUV-P250YM-A

PUV-P400YM-A

PUV-P500YM-A

PEV-P250YM-A

Indoor unit
Ceiling concealed
Outdoor unit
PUV-P200YM-A

PUV-P250YM-A

Heat Pump

50Hz (Floor standing 50/60Hz)

Type
Page16 - Page18

8HP

Indoor unit
(Standard model)

10HP
PFAV-P250VM-E

16HP

30HP

20HP
PFAV-P500VM-E

PFAV-P750VM-E

Outdoor unit
PUHY-P250YHA

Floor standing
Indoor unit
(Fresh air
intake model)
Outdoor unit

Page 1

PFAV-P300VM-E-F

PUHY-P250YHA

PUHY-P250YHA x 2
PFAV-P600VM-E-F

PUHY-P250YHA x 2

PUHY-P350/400YHA
PFAV-P900VM-E-F

PUHY-P350/400YHA

Page 2

APPLICATION
Example 1. Hotel

Example 3. Printing factory

Requirements

Solution

Requirements

Solution

Different series adopted to each


optimum zone are required to
be managed with the same
controller.

Since both these Commercial Packaged


Air-conditioner series and CITY MULTI
series use M-NET, they can be controlled
with the same centralized controller.

There is large heat generation from


equipment and intake of outdoor air is
favored.

Heat pump series Fresh air intake


models.*1

CITY MULTI series Zone

Fresh air from outdoor supplied to the


room reduces the total air-conditioning
load in the room.

Commercial Packaged
Air-conditioner
series Zone

*1 Fresh air intake type indoor units supply pretreated outside air into the room. This type of units are not designed to handle internal thermal
load. Use other types of air conditioning units that are capable of handling internal thermal load in combination with the Fres h Air Intake
type units.

Example 2. Manufacturing plant

Example 4. Airport

Requirements

Solution

Requirements

Solution

Ducts cannot be installed in the ceiling


with crane rails. High ceiling and heat
generation from equipment need to be
considered. ON/OFF control by external input (level-signal) is required in the
system.

Cooling only floor standing series with


plenum chamber.*1
External signal based start/stop control
can be performed.*2

Air conditioning for spacious and high


ceiling room. Easy maintenance even
when people are in the room.

Floor standing series with plenum


chamber.*1

*1 For PFV-P200/250YM-A model, a plenum is embedded as standard accessory.


*2 Requires the remote ON/OFF adapter (PAC-SE55RA-E) and other parts (eg. Power supply of relay) need to be procured locally.

Page 3

*1 For PFV-P200/250YM-A model, plenum is embedded as standard accessories

Page 4

The New Cooling-only


Series
High Energy Efficiency

Widen installation and application options


Simple Piping
S

<New Compressor>

Use of inverter-based compressor that adopts DC brushless motor for increased


energy saving and load-following capability.

New
compressor

Capable of covering up to 20 HP with a single compressor.


Improved partial-load characteristics achieved by
the optimized scroll shape.
Reduced standby power consumption by heating the
compressor instead of a crankcase heater. (16/20 HP)

Comparison between

inverter air conditioner and


non-inverter air conditioner

Temperature

Crankcase
heater

Heated
compressor
motor

SCOP performance
Optimized scroll shape
(improved volumetric capacity ratio)

Compressor efficiency

High

Improved CSPF,

30%UP

Compression ratio

High

Room
temperature

R22

PE-10GAK
PU-10YAKD

*Based on EN 14825

R410A

PEV-P250YM-A
PUV-P250YM-A

User Friendry
Interface <Controller>

AG150A

Cooling only series

VRF series

Thermostat
OFF

Evaporating temperature was kept


constant.

Pressure

New control method


Evaporating temp. UP

Motor

(Option)

IIncrease in the limit of


piping length
p
Maximum piping length: 150 m
(70 m for 8/10 HP)
Height difference between indoor and
outdoor units is up to 50 m.
(16/20 HP; case with the outdoor unit
installed higher)
(30 m for 8/10 HP)

Centralized control
C
enabled by M-NET control
e

M-NET

M-NET

Thermostat
ON

Time

Rear suction flange

C
Capable of running cooling operations in the outdoor temperature of up to 52C.

Intermediate value
between thermostat
ON and OFF

PAR-31MAAE

Target evaporation
temperature

20HP

Compatibility to outdoor temperature of up to 52C *1


C

Existing Heat pump series

Current control method

Page 5

150m

100

<ET control
(Evap o rating Temperat ure control)>
Temperature

Max length

Index
130

Plenum

(Standard)

50m

Time

Low

Duct

Max height

Excessively cooled

CSPF,SCOP conditions

Evaporating temperature is raised


according to the operation load,
decreasing compressor input power
and increasing operation efficiency.

IIn addition to the standard duct blowing, the


plenum blowing and the rear suction are made
selectable as optional.
The airflow rate and the static pressure may
also be changed to meet the local needs (by the
use of optional parts and locally procured parts).

Inverter
air conditioner
Non-inverter
air conditioner

New Cooling only series

20HP

IIncreased adaptation to local needs (floor standing type 16/20 HP)

A bit hot

Comparison of CSPF

10HP

Capable of covering up to 20 HP with


a single module and a single compressor.

Comfortable

Operation
started

10HP

Small temperature difference

Cooled in a
short time

Set temperature

Reduced energy consumption in cooling by controlling the refrigerant temperature according to the
operation load and raising
evaporating temperature.

20HP

With the usage of MA controller


(PAR-31MAAE), which is embedded at the Cooling only series. Use
of LCD and back light for improved
visibility.
The display of error history and the
setting of night setback and
demand control are made possible
through the remote controller in
pursuit of increased user convenience.

Meeting the demand


M
control needs
c

100/75/50/0% fixed capacity


operation possible by external
signals.
Meets a variety of user needs,
such as the demand control for
restricting the power demand.

Since the new Cooling only series


uses M-NET, the design of control
is simple and easy.
Through the centralized controller,
the centralized control is made
possible under the mixed use with
VRF CITY MULTI series.

Other new functions


O
- External signal-based
start/stop control
function (by the use of
optional parts)
- Fan ON/OFF control
signals can be taken
to the outside.

*1 : Any continuous operation over 46C may require an increased frequency of maintenance.

Page 6

NEW

What is the new energy-conservation standards CSPF?

Cooling only series


Cooling only series [ LINE UP ]

COP (Energy consumption efficiency)


C

Floor standing type

COP calculation method

COP is defined as the ratio of


cooling/heating capacity to 1 kW of
electrical power consumption at the
rated cooling/heating operation.

Features

Rated power consumption (kW)

Annual outside temperature occurrence


frequency (in Tokyo)
Measurement temperatures
for cooling/heating COPs

Heating COP
at 7C

Occurrence frequency (h)

The COP in cooling and heating


is calculated based on the measurements taken at the outside
temperature of 35C and 7C
respectively.
COP is an energy-conservation
index that is calculated under
very limited conditions in the
year.

Rated capacity (kW)

COP =

Cooling COP
at 35C

Easy installation and maintenance


Suitable for use in areas where duct installation
is not possible (i.e., high ceiling or ceiling with
crane rails)
Satisfies large capacity air conditioning needs
Adjustable air flow and static pressure

Wide temperature range


Cooling
100
80

relative humidity (%)

Characteristics of COP

Line up

60
40
20
15

20

-10

-7

-4

-1

8
11 14 17 20 23
Outside temperature (C)

26

29

32

35

38

15C

Indoor air
inlet temp (W.B.)

10

8 , 10 HP

CSPF (Cooling Seasonal Performance Factor)


C
Characteristics of CSPF

20

25

30

35

40

45

50

55

16 , 20 HP

Power consumption during cooling season (kWh)

200

100

Intermediate
cooling capacity

Out-of-use period

Occurrence frequency (h)

Cooling season

22 23 24 25 26 27 28 29 30 31 32 33 34 35
Outside temperature (C)

Features

Wide temperature range

Flexibly accommodates various types of duct


designs
Installable when no floor space is available
Suitable for use in areas where air flow from
floor-standing models would be interrupted by
the equipment in the space
Suitable for use in facilities such as food
manufacturing plants where floor-standing
models are not suitable because of cleaning
requirements

Cooling
100
80
60
40
20
15

20

25

30

35

Inlet air temperature (CDB)

Air conditioners for stores


and office buildings
Standard

CITY MULTI and


PAC air conditioners

JRA4048:2006

Area

Rated cooling
capacity

Ceiling concealed type

relative humidity (%)

Outside temperature occurrence frequency


used to calculate CSPF (in Kagoshima)

Calculation conditions for CSPF


C

Page 7

15

52C

Outdoor air inlet temp (D.B.)

Capacity output during cooling season (kWh)

CSPF =

Usage period

35

CSPF calculation method

CSPF is calculated based not only on


the measurements taken during rated
cooling operation, but also on those
taken during intermediate cooling
operation. The type of building usage
and variables that change during
different operating seasons are also
considered in the calculation of CSPF
to reflect actual usage conditions.

Operating season

30

24C

20C

Line up
15C

Kagoshima (Japan)

Building usage

25

Inlet air temperature (CDB)

Detached store
May 23-Oct. 10

Apr. 16-Nov. 8

Heating

Nov. 21-Apr. 11

Dec. 14-Mar. 23

8:00-21:00

8:00-20:00

24C

20C

Office

Cooling

Indoor air
inlet temp (W.B.)

10

15

20

52C

Outdoor air inlet temp (D.B.)


25

30

35

40

45

50

55

8 , 10 HP

Page 8

Cooling only series [ SPECIFICATIONS ]


Model name

Indoor
Cooling *1

System capacity
Cooling *2

BTU/h
kW
BTU/h
kW

System Power input Cooling


Syetem current
Cooling
Energy efficiency ratio (EER)
CSPF *5
Power source
Power input
Current

kW
A

kW
A

Type Quantity
Airflow rate (Lo-Hi)

FAN

m3/min

External static
pressure

Pa

Motor output

kW

Refrigerant

Cooling only series [ SPECIFICATIONS ]


PFV-P200YM-A
80,000
23.5
79,000
23.2
9.03
15.2/14.5/14.1
2.60
3.8

0.81
1.3/1.3/1.3
Sirocco fan2
58-71
(Plenum)

1.64
3.8/3.6/3.5
Sirocco fan2
150
30

30

0.75

0.75

2.2

3.7

R410A

R410A

R410A

R410A

FAN

18001200500
Over current protection

mm

9.52 Brazed

mm

22.2 Brazed
70
53-59

mm

Liquid pipe
Refrigerant piping
diameter
Gas pipe
Refrigerant piping allowable length

Sound pressure level (Lo-Hi) *3


Heat exchanger
Air filter
Net weight
Operating temperature
range
Model name
Power source

m
dB(A)

kg

PUV-P200YM-A (-BS)

297

352

PUV-P250YM-A (-BS)
PUV-P400YM-A (-BS)
3-phase 4-wire 380-400-415V 50/60Hz

PUV-P500YM-A (-BS)
65

mm (in)
mm (in)

9.52 (3/8) Brazed


22.2 (7/8) Brazed
Propeller fan1
170
2,834
6,003
Inverter-control,
Direct-driven by motor

9.52 (3/8) Brazed


22.2 (7/8) Brazed
Propeller fan1
170
2,834
6,003
Inverter-control,
Direct-driven by motor

12.7 (1/2) Brazed


28.58 (1-1/8) Brazed
Propeller fan1
200
3,334
7,062
Inverter-control,
Direct-driven by motor

15.88 (5/8) Brazed


28.58 (1-1/8) Brazed
Propeller fan2
340
5,668
12,005
Inverter-control,
Direct-driven by motor

Airflow rate

L/s
cfm

0.921
0Pa (0mmH2O)

Type Quantity
Manufacture
Starting method
Motor output

kW

Case heater

kW

Lubricant

External finish
External dimension H W D

mm
in

High pressure protection


Inverter circuit
(COMP. / FAN)
Compressor
Fan motor
Type original charge
Control
kg

Inverter
5.4
0.045
MEL56

0.921
0.921
0Pa (0mmH2O)
0Pa (0mmH2O)
Inverter scroll hermetic compressor
MITSUBISHI ELECTRIC CORPORATION

0.922
0Pa (0mmH2O)

Inverter
Inverter
7.0
11.7
0.045
MEL56
MEL32
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 3.0Y 7.8/1 1 or similar>

Inverter
12.9
MEL32

Cooling *1
Cooling *2

BTU/h
kW
BTU/h
kW

System Power input Cooling


Syetem current
Cooling
Energy efficiency ratio (EER)
CSPF *5
Power source
Power input
Current

kW
A

PEV-P200YM-A
80,000
23.5
79,000
23.2
9.49
16.0/15.2/14.7
2.47
3.4

1.02
1.8/1.7/1.7

m3/min

52-65

kW

Airflow rate (Lo-Hi)

FAN

1.12
2.0/1.9/1.9
Sirocco fan2
56-71

External static
pressure

Pa

80

100

Motor output

kW

0.50

0.72

Refrigerant

R410A
Galvanized steel

External dimension H W D
Protection devices

Sound pressure level (Lo-Hi) *3


Heat exchanger
Air filter
Net weight

mm
m
dB(A)

45-49

Cross fin (aluminum plate fin and copper tube)


Optional
74
Indoor : 15 to 24CWB
(Outdoor : 20 to 52CDB)

kg

dB(A)

56

58

mm (in)
mm (in)

9.52 (3/8) Brazed


22.2 (7/8) Brazed
Propeller fan1
170
2,834
6,003
Inverter-control,
Direct-driven by motor

9.52 (3/8) Brazed


22.2 (7/8) Brazed
Propeller fan1
170
2,834
6,003
Inverter-control,
Direct-driven by motor

0.921
0Pa (0mmH2O)

0.921
0Pa (0mmH2O)

m3/min
Airflow rate

L/s
cfm

Control, Driving mechanism


Motor output

kW
External static pressure

Inverter scroll hermetic compressor


MITSUBISHI ELECTRIC CORPORATION

Manufacture

Over-heat protection,
Over-heat protection,
Over-heat protection,
Over-heat protection,
Over-current protection
Over-current protection
Over-current protection
Over-current protection
Over-heat protection
Over-heat protection
Over-heat protection
Over-heat protection
Thermal switch
Thermal switch
Thermal switch
Thermal switch
R410A5.5kg (13lbs)
R410A6.5kg (15lbs)
R410A11.5kg (26lbs)
R410A11.8kg (27lbs)
LEV and HIC circuit
LEV and HIC circuit
LEV and HIC circuit
LEV and HIC circuit
180
193
239
306
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

Compressor

Starting method
Motor output

kW

Case heater

kW

Lubricant

External dimension H W D

mm
in

High pressure protection


Inverter circuit
(COMP. / FAN)
Compressor
Fan motor

Refrigerant
Net weight
Heat exchanger

Inverter
7.5
0.045
MEL56

Inverter
5.4
0.045
MEL56
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 3.0Y 7.8/1 1 or similar>

External finish

Protection devices

46-50

PUV-P250YM-A (-BS)
PUV-P200YM-A (-BS)
3-phase 4-wire 380-400-415V 50/60Hz

Outdoor

Liquid pipe
Gas pipe
Type Quantity

9.52 Brazed
22.2 Brazed
70

mm

Cooling

Sound pressure level


(measured in anechoic room)

Refrigerant piping
diameter

4001600634
Over current protection

mm
FAN

Liquid pipe
Refrigerant piping
diameter
Gas pipe
Refrigerant piping allowable length

Model name
Power source

PEV-P250YM-A
100,000
29.3
99,000
28.9
13.74
23.3/22.1/21.4
2.13
3.4

3-phase 4-wire 380-400-415V (50Hz)

Type Quantity

Type Quantity

1650920740
1650920740
16501220740
16501750740
64-31/3236-1/429-5/32
64-31/3236-1/429-5/32 64-31/3248-1/1629-5/32 64-31/3268-29/3229-5/32
High pres. Sensor & High pres. High pres. Sensor & High pres. High pres. Sensor & High pres. High pres. Sensor & High pres.
Switch at 4.15MPa (601psi)
Switch at 4.15MPa (601psi)
Switch at 4.15MPa (601psi)
Switch at 4.15MPa (601psi)

Note 1. Cooling capacity indicates the value at operation under the following conditions.
Indoor : 27CDB / 19.5CWB, Outdoor : 35CDB
2. <Reference cooling capacity> Indicates the value at operation under the following conditions.
Indoor : 27CDB / 19CWB, Outdoor : 35CDB
3. The sound pressure level is measured in an anechoic room.
4. Long period operation in a high temperature and humidity atmosphere (dew point of 23C or more) may cause condensation to form in the indoor unit.
5. Cooling Seasonal Performance Factor

Page 9

Indoor

System capacity

Operating temperature
range

62

kW
External static pressure

Net weight
Heat exchanger

28.58 Brazed
150
66

58

Motor output

Refrigerant

15.88 Brazed

56

Control, Driving mechanism

Protection devices

18001860650
Over current protection

22.2 Brazed
28.58 Brazed
70
150
57-61
63
Cross fin (aluminum plate fin and copper tube)
PP Honeycomb fabric filter
165

Model name

External finish

dB(A)

m3/min

Compressor

2.35
5.3/5.0/4.8
Sirocco fan2
200

Indoor : 15 to 24CWB
(Outdoor : 20 to 52CDB)

Outdoor

Liquid pipe
Gas pipe
Type Quantity

Refrigerant piping
diameter

164

Galvanized steel plate (with polyester coating)


MUNSELL 3.0Y 7.8/1.1 or similar
18001200500
18001860650
Over current protection
Over current protection
9.52 Brazed
12.7 Brazed

Cooling

Sound pressure level


(measured in anechoic room)

PFV-P500YM-A
191,000
56.0
188,000
55.1
20.53
35.9/34.1/32.9
2.72
3.5

0.74
1.3/1.3/1.3
Sirocco fan2
52-65
(Plenum)

External finish
External dimension H W D
Protection devices

PFV-P250YM-A
PFV-P400YM-A
100,000
160,000
29.3
46.9
99,000
158,000
28.9
46.3
11.76
18.14
19.7/18.8/18.2
31.6/30.0/29.0
2.49
2.58
3.8
3.7
3-phase 4-wire 380-400-415V (50Hz)

Type original charge


Control
kg

1650920740
64-31/3236-1/429-5/32
High pres. Sensor & High pres.
Switch at 4.15MPa (601psi)

1650920740
64-31/3236-1/429-5/32
High pres. Sensor & High pres.
Switch at 4.15MPa (601psi)

Over-heat protection,
Over-current protection
Over-heat protection
Thermal switch
R410A5.5kg (13lbs)
LEV and HIC circuit
180
Salt-resistant cross fin & copper tube

Over-heat protection,
Over-current protection
Over-heat protection
Thermal switch
R410A6.5kg (15lbs)
LEV and HIC circuit
193
Salt-resistant cross fin & copper tube

Note 1. Cooling capacity indicates the value at operation under the following conditions.
Indoor : 27CDB / 19.5CWB, Outdoor : 35CDB
2. <Reference cooling capacity> Indicates the value at operation under the following conditions.
Indoor : 27CDB / 19CWB, Outdoor : 35CDB
3. The sound pressure level is measured in an anechoic room.
4. Long period operation in a high temperature and humidity atmosphere (dew point of 23C or more) may cause condensation to form in the indoor unit.
5. Cooling Seasonal Performance Factor

Page 10

Cooling only series [ OUTLINE DIMENSIONS ]

Cooling only series [ OUTLINE DIMENSIONS ]

Minimum necessary dimension.

Required space for service and air flow


Minimum necessary dimension.
1914
1886

62

67
392

400

Required space for service and air flow

1226

400

1254

Floor standing type

PFV-P500YM-A

Indoor unit

6
1200

50

Secure the proper space for


installation work such as
piping and wiring separately.

500

50

542

50

800

Indoor unit

Secure the proper space for


installation work such as
piping and wiring separately.

Air outlet

Air outlet

1860

650

Remote controller

1800

2
183

Drain cap

1174

107
139

70

NO.
1
2
3
4
5
6

Notes 1. Be sure to wire the transmission line and power line separately.
2. No.3 indicate left-sided drainage.The right drainage is also
possible by a change getting a cap.

Required space for service and air flow


Minimum necessary dimension.

60

Notes 1. Be sure to wire the transmission line and power line separately.
2. When the room in which the unit is installed is airtight,
the pressure in the room may become negative.
This may result in problems such as the door to becoming difficult
to open etc.
To avoid these kinds of problems please ensure that a small amount of
air is able to ventilate the room via some kind of small hole or vent.
3. No.3 indicate left-sided drainage.The right drainage is also
possible by a change getting a cap.

Designation
Refrigerant pipe <Gas> 28.6 brazed
Refrigerant pipe <Liquid> 15.88 brazed
Drain connectionRc1-1/4
Power supply wiring hole52
Wiring hole(The outdoor unit connection,Transmission line)27
For mounting anchor bolt 4-12 Holes

Unit : mm

Ceiling concealed type

PEV-P200, 250YM-A
<Accessory>
Pipe cover 2pcs.
(For dew condensation prevention of
local piping and unit connection.)
Remote controller 1pc.

400

1914
1886

210-3 Holes
42

Indoor unit
Rubber bush <Remote
controller wiring>

Secure the proper space for


installation work such as
piping and wiring separately.

Air outlet

Control box

Rubber bush
<Outdoor unit
connection wiring>

1302
66

1309=1170

20

Rubber bush
<Power supply wiring>

650

124

Return air
duct flange

199

50

800

542

50

1860

Rear air inlet

124

Unit : mm

Floor standing type

278

174

PFV-P400YM-A

62

1834

1500

55

20

28-3.1 Holes

10

40

200

70

50
612

131

462

Designation
Refrigerant pipe <Gas>22.2 brazed
Refrigerant pipe <Liquid>9.52 brazed
Drain connectionRc1
Power supply wiring hole37
Wiring hole(The outdoor unit connection,Transmission line)27
For mounting anchor bolt 4-12 Holes

21

100

50

162

462

183

129

1
2
3
4
5
6

70 75

43

NO.

Rear air inlet

Drain cap

21

35

180

Front air inlet

178

Remote controller

Front air inlet

1800

50

800

Floor standing type

PFV-P200, 250YM-A

4-12 Holes
<For hanging bolt M10>
[Field supply]

Remote controller

130
45

1307=910

Supply air
duct flange

Top view

Front air inlet

50
612

1834

70

278

124

Return air

1
2
3
4
5
6

Designation
Refrigerant pipe <Gas> 28.6 brazed
Refrigerant pipe <Liquid>12.7 brazed
Drain connectionRc1-1/4
Power supply wiring hole52
Wiring hole(The outdoor unit connection,Transmission line)27
For mounting anchor bolt 4-12 Holes

95
250

400

100

376

39

NO.

25

73

35

22

Rear air inlet

60

1000

Supply air
11

21

1460
255

23-3.1 Holes

100

162

145

35

183

Drain cap

1540
10

10

262

144

40

530

130

330

1600
634
50

89

130

1800

Return air sensor


23-3 Holes
Refrigerant pipe(Gas)
22.2 (7/8 braze)

Refrigerant pipe (Liquid)


12.7 (1/2 braze)

Notes 1. Be sure to wire the transmission line and power line separately.
2. When the room in which the unit is installed is airtight,
the pressure in the room may become negative.
This may result in problems such as the door to becoming difficult
to open etc.
To avoid these kinds of problems please ensure that a small amount of
air is able to ventilate the room via some kind of small hole or vent.
3. No.3 indicate left-sided drainage.The right drainage is also
possible by a change getting a cap.

Drain R1

565

Left side view

1484

Front view

Unit : mm
Unit : mm

Page 11

Page 12

Cooling only series [ OUTLINE DIMENSIONS ]

Cooling only series [ OUTLINE DIMENSIONS ]

PUV-P500YM-A

PUV-P200, 250YM-A
1pc.
1pc.

Note1. Please refer to the Installation Manual for information


regarding necessary spacing around the
unit and foundation work.
2. At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C.

920

Top view
303
80

760
(Mounting pitch)

80

2
3

For wires

5
6

303
54

102 72 Knockout hole

57

Bottom through hole 150 94 Knockout hole


Front through hole

65 or 40 Knockout hole

Front through hole

52 or 27 Knockout hole

20

586

20

57

Left side view

Bottom through hole 52 Knockout hole

98
102

Front view
561
590
516

Bottom through hole 65 Knockout hole

For transmission cables Front through hole

544
591
150

83

34 Knockout hole

80

Unit : mm

795
(Mounting pitch)

795
(Mounting pitch)

Bottom view

<Accessories>

740

Note1. Please refer to the Installation Manual for information


regarding necessary spacing around the
unit and foundation work.
2. At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C.

Top view

Discharge air

Connecting pipe specifications

303

Diameter
Model

Control box

PUV-P400YM-A(-BS)

4
88

1
2

Left side view

254
301

98
102

89

57

586

Bottom through hole

150 94 Knockout hole

Front through hole

65 or 40 Knockout hole

Front through hole

52 or 27 Knockout hole

Bottom through hole

65 Knockout hole

Bottom through hole

52 Knockout hole

For wires

6
7

For transmission cables Front through hole

34 Knockout hole

80

Unit : mm

2X2-80X35 Oval hole


<Sling hole>

29.5

84

145

2X2-14X20 Oval hole

4
5
6
7

For wires

Front through hole

Specifications
102 72 Knockout hole

Bottom through hole 150 94 Knockout hole


Front through hole

65 or 40 Knockout hole

Front through hole

52 or 27 Knockout hole

Bottom through hole 65 Knockout hole


Bottom through hole 52 Knockout hole

For transmission cables Front through hole

34 Knockout hole

Description

Model

Applicable capacity

Plenum

PAC-PLE20PL-E

PFV-P400,P500YM-A

OA duct flange

PAC-ODF20DF-E

PFV-P400,P500YM-A

Air filter8/10HP

PAC-KE210AF

PEV-P200,P250YM-A

High Static Pressure Motor (3.7kW)

PAC-HPM16SP-E

PFV-P400YM-A

High Static Pressure Motor (5.5kW)

PAC-HPM20SP-E

PFV-P500YM-A

Wireless Remote Controller

PAR-FL32MA-E

PEV-P200,P250YM-A

Signal Receiver Unit

PAR-SA9CA-E

PEV-P200,P250YM-A

Optional Parts for control


Description

Model

Multiple Remote Controller Adapter

PAC-SA88HA-E

Remote sensor

PAC-SE41TS-E *1

Remote On/Off Adapter

PAC-SE55RA-E

*1 : Only for PEV series

2 Refrigerant service
valve <gas>

Refrigerant service
valve <liquid>

80

1060
(Mounting pitch)

Bottom view

80

29.5

94

5
6

681
(Mounting pitch)
(740)

121

144

196

Usage
For pipes

Front view
272 150
301
83
227

Service valve
Liquid
Gas
15.88
28.58

1650

NO.

131

172
238

54

72

Refrigerant service valve


<liquid>
Refrigerant service valve
<gas>

1347

Service
panel

Refrigerant pipe *1
Liquid
Gas
12.7 Brazed 28.58 Brazed

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.

Intake
air

Intake
air

Intake
air

20

102 72 Knockout hole

Optional Parts for indoor units

Connecting pipe
<Gas>
Elbow
(ID28.58XOD28.58) P400 1pc.
<Liquid> Pipe
(ID15.88XOD15.88) P400 1pc.
Pipe reducer(ID15.88XOD12.7)P400 1pc.

1220

20

For pipes

Specifications

Front through hole

Cooling only series [ OPTIONAL PARTS ]

PUV-P400YM-A

57

1650

2X3-14X20 Oval hole

Refrigerant service Refrigerant service


valve <liquid>
valve <gas>

Bottom view

1347

2X2-80X35 Oval hole


<Sling hole>

Usage

131

Front through hole

29.5

For pipes

28.58

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
NO.

Terminal box

15.88

681
(Mounting pitch)
(740)

Refrigerant service
valve <gas>

Specifications

Service valve
Liquid
Gas

PUV-P500YM-A(-BS) 15.88 Brazed 28.58 Brazed

Refrigerant pipe *1
Liquid
Gas

29.5

6
Refrigerant service
valve <liquid>

94

Usage

681
(Mounting pitch)
(740)

94

88

2X2-14X20 Oval hole

196
147
121

222 150
251
83
177

196
144
121

Front view

Left side view

2X2-80X35 Oval hole


<Sling hole>

NO.

172
238

98
102

29.5

204
251

Service
panel

72

1347
1650

72

88

57

Service panel
Refrigerant service valve
<liquid>
Refrigerant service valve
<gas>

131

262

Intake
air

Intake
air

Intake
air

29.5

20

586

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.

Diameter
Model

25.4

9.52

Connecting pipe specifications

Control box

89

20

PUV-P200YM-A(-BS)
PUV-P250YM-A(-BS) 9.52 Brazed 22.2 Brazed

Service
panel

Diameter
Service valve
Refrigerant pipe*1
Liquid
Gas
Liquid
Gas

89

Intake
air

1pc.

1750

84

Model

137
84

57

222

54

Refrigerant service valve


<gas>
Refrigerant service valve
<liquid>

1pc.

(ID15.88XOD15.88) P500

Connecting pipe specifications

Control box

Intake
air

(ID28.58XOD28.58) P500

<Liquid> Pipe

Top view

Discharge air

Intake
air

<Accessories>
Connecting pipe
<Gas> Elbow

Note1. Please refer to the Installation Manual for information


regarding necessary spacing around the
unit and foundation work.
2. At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C.

145

Discharge air

(ID25.4XOD22.2)P200,P250
(ID9.52XOD9.52)P200,P250

740

740

<Accessories>
Connecting pipe
<Gas> Pipe
<Liquid> Pipe

Unit : mm

Page 13

Page 14

Heat pump series


Cooling only series [ REMOTE CONTROLLER ]

NEW

Heat pump series

Wired MA remote controller PAR-31MAAE


Temperature will be displayed either in Centigrade in 0.5or 1-degree increments, or in Fahrenheit, depending on
the indoor unit model and the display mode setting on
the remote controller.
Backlit LCD (Liquid Crystal Display)
Large, easy-to-see display
Full-dot LCD display with large characters for easy viewing
Contrast also adjustable
Night Setback
To prevent indoor dew or excessive temperature rise, this
control starts cooling operation when the control object
group is stopped and the room temperature rises above
the preset upper limit temperature.

Dimensions: 120(W) x 120(H) x 19(D) mm


: 4-3/4(W) x 4-3/4(H) x 3/4(D) in.

Simple button arrangement


Large, easy-to-press buttons
Buttons are arranged according to usage to allow for
intuitive navigation.
Frequently used buttons are larger than other buttons to
prevent unintended pressing of other buttons.

Example of system configuration


ex. 1

M-NET

MA remote controller

ex. 2

Heat pump series is a large capacity floor standing indoor unit with high air flow
operation especially designed for various types of large spaced application.
The unit is a one-to-one connection unit meaning one indoor is connected to
one outdoor unit. The lineup consists of two models; standard model and fresh
air intake model, selectable depending on usage.

Adaptable to various applications


With wide range of airflow and static pressure,
and piping length up to 165m, Heat pump
series can provide flexibility in design by
adapting to various applications from shops,
schools, and to factories.

Air flow rate


PFAV-P250VM-E
PFAV-P500VM-E
PFAV-P750VM-E
PFAV-P300VM-E-F
PFAV-P600VM-E-F
PFAV-P900VM-E-F

External static
pressure

m3/min
90
180
260
45
90
120

Pa
30/90
30/130
100/310
80
110/170
210/330

Large capacity indoor unit


Heat pump series is a floor standing large capacity indoor unit, which reduces the piping and installation burdens, moreover
makes maintenance easy.

OUTDOOR UNIT
Compact outdoor unit

M-NET

Heat pumpseriescan only be connected to PUHY-YHA


outdoor units. YHA series offers small footprint and
lightweight inversely to high heating capacity, which
allows easy transportation and saves installation space.

Non-polarized
2-wire

MA remote
controller
*When a PAR-31MAAE is connected to a group, no other MA remote controllers can be connected
to the same group.

Installation space 1.43m2


200kg

Height
1650mm

Width
920mm

High Reliability

Depth
760mm

Outdoor heat exchangers have been treated with an anti-corrosion coating ensuring higher resistance against salt
damage or air pollution.
*Standard:Anti-corrosion Blue Fin treatment & copper tube.
BS type (optional):salt-resistant cross fin & copper tube.

Functions
: Each group
Item
ON/OFF
Operation mode switching
Room temp. setting
Ventilation equipment control
Error information

Timer

Allows/disallows local operation


Operation lock
Temperature range restriction
Auto return
Smooth Maintenance

Page 15

Description

: Not available
Operations Display

Switches between ON and OFF.


Switches among Cool/Fan.
The temperature can be set within the following range.
Cool : 19C - 30C / 67F - 87F
* Set temperature range varies depending on the model.
Interlocked setting and interlocked operation setting with the CITY MULTI LOSSNAY units can be made.
The Stop/Low/High settings of the ventilation equipment can be controlled.
When an error occurs, an error code and the unit address appear.
Air conditioning unit model, serial number, and contact number can be set to appear when an error occurs.
(The information above needs to be entered in advance.)
* An error code may not appear depending on the error.
ON/OFF timer
Turns ON and OFF daily at a set time.
Time can be set in 5-minute increments.
It is also possible to set the ON time only or the OFF time only.
Auto-OFF timer
Turns off the unit after a certain period of operation.
Operation time can be set to a value from 30 to 240 minutes in 10-minute increments.
The following operation can be prohibited by making certain settings on the centralized controller: ON/OFF,
operation mode setting, temperature setting, fan speed, air direction, and filter sign reset.
* While an operation is prohibited, the operation icon lights up (only on the Main display in the "Full" mode).

With the usage of MA controller (PAR-21MAA), which is embedded at the Heat


pump series, following energy saving functions can be provided.

Auto-OFF timer

Limiting set temperature range

Automatically switches off based


on presetting time. (Preset time
can be 30min-4hours, per 30min)

By limiting lowest / highest temperature, it


is possible to save energy when air
Standard
conditioners are frequently used.
setting

PAR-21MAA
Cooling

14C

30C
25C

30C

Low temperature limit

The following operation can be prohibited respectively: ON/OFF, operation mode setting, temperature setting, and
airflow direction setting.
The room temperature range for each operation mode can be restricted.
The units operate at the preset temperature after a designated period.
(Time can be set to a value from 30 to 120 in 10-minute increments.)
* Not valid when the temperature setting range is restricted.
Using the Stable Operation Control (fixed frequency) of the Smooth Maintenance function, the operating status of
the inverter can be checked easily via the screen on the remote controller.

CONTROL

Locking function

Temperature in this
range is not selectable.

Prevents overcooling

To sustain optimal temperature, and prevent operational errors, buttons can be locked to only ON/OFF control.
X

Page 16

Heat pump series [ LINE UP ]

Heat pump series [ SPECIFICATIONS ]


S TA N D A R D m o d e l

STANDARD model

Model Name

Outdoor

Line up

Features
Highly energy efficient with easy installation
and maintenance, the standard Heat pump
series is suitable for working places where
large capacity air conditioning is required.

relative humidity (%)

relative humidity (%)

100

80
60
40
20
20

25

30

80

10C
-20

-15

-10

40

15

kW

Current

A
Airflow rate

m3 / min

External static pressure

Pa

Motor output

kW

20

25

10

20

30

Inlet air temperature (CDB)

15C
43C

30

35

40

45

-20C
-20

-15

-10

-5

10

Indoor air
inlet temp (D.B.)

15

20

25

35

40

45

By controlling the air volume of the outdoor unit fan, operation is available even when the outdoor temperature is
-5C for cooling and -20C for heating.

17.85 / 18.84

17.00 / 17.99

26.33 / 27.40

23.93 / 25.00

32.3-30.7-29.6 / 32.6-31.0-29.9

30.8-29.3-28.2 / 31.1-29.6-28.5

48.1-45.7-44.1 / 47.5-45.1-43.5

43.4-41.2-39.8 / 42.8-40.6-39.2

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

0.82 / 0.89

2.37 / 3.36

4.30 / 5.37

3.4-3.2-3.1 / 2.3-2.2-2.1

6.2-5.9-5.7 / 6.5-6.2-6.0

10.9-10.4-10.0 / 10.3-9.8-9.4

Sirocco fan 2

Sirocco fan 1

Sirocco fan 1

90

180

260

30 / 90

30 / 130

100 / 310

5.5

7.5
R410A

Galvanized steel plate (with polyester coating)

Galvanized steel plate (with polyester coating)

Galvanized steel plate (with polyester coating)

<MUNSEL 5Y 8/1 or similar>

<MUNSEL 5Y 8 / 1 or similar>

<MUNSEL 5Y 8 / 1 or similar>

1748 1200 485

1899 1420 635

1860 1750 1064

Thermal switch

Thermal switch

Thermal switch

9.52 Brazed (12.7 for over 90m)

15.88 Brazed

19.05 Brazed

22.2 Brazed

28.58 Brazed

34.93 Brazed

Refrigerant piping allowable length m

165

165

165

Sound pressure level

55

59 / 62

65

Cross fin (Aluminum plate fin and copper tube)

Cross fin (Aluminum plate fin and copper tube)

Cross fin (Aluminum plate fin and copper tube)

Synthetic fiber unwoven cloth filter

Synthetic fiber unwoven cloth filter

PP Honeycomb fabric filter

156

265

External dimension H W D

mm

Protection devices

Fan motor
Liquid pipe

dB(A)

kg

Heating

Cooling

Heating

Cooling

Heating

Indoor:10CWB~25CWB

Indoor:15CDB~28CDB

Indoor:10CWB~25CWB

Indoor:15CDB~28CDB

Indoor:10CWB~25CWB

Indoor:15CDB~28CDB

(Outdoor:-5CDB~43CDB)

(Outdoor:-20CWB~15.5CWB)

(Outdoor:-5CDB~43CDB)

(Outdoor:-20CWB~15.5CWB)

(Outdoor:-5CDB~43CDB)

(Outdoor:-20CWB~15.5CWB)

1. Cooling/Heating capacity indicates the maximum value at operation under the following conditions.
<Cooling> Indoor:27CDB/19CWB Outdoor:35CDB
<Heating> Indoor:20CDB
Outdoor:7CDB/6CWB
Pipe length :7.5m,Level difference:0m
2. The sound pressure level is measured in an anechoic room.

Indoor

Operation

Fresh air intake model takes in fresh air from


the outdoor suitable for application such as
factories and laboratories where intake of
indoor air is not favored.

10 HP

20 HP

30 HP

relative humidity (%)

relative humidity (%)

100

40
20

40

45

-10

-5

10

15

Current

Cooling

Heating

Cooling

Heating

26.5 (Maximum 28.0)

56.0 (Maximum 67.0)

50.0 (Maximum 56.0)

20

25

60

7.57 / 7.56

14.69 / 15.05

15.43 / 15.79

22.54 / 22.74

21.43 / 21.63

14.0-13.3-12.8 / 13.6-12.9-12.4

26.1-24.9-24.0 / 26.2-25.0-24.0

27.4-26.1-25.1 / 27.5-26.2-25.1

40.5-38.5-37.1 / 39.6-37.6-36.2

38.7-36.8-35.5 / 37.8-35.9-34.6

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

0.37 / 0.36

0.90 / 1.26

10

20

30

1.77 / 1.97

1.9-1.8-1.7 / 1.5-1.4-1.3

2.9-2.8-2.8 / 3.0-2.9-2.8

5.6-5.3-5.1 / 4.7-4.4-4.2
Sirocco fan 1

Sirocco fan 2

Sirocco fan 1

m3 / min

45

90

120

External static pressure

Pa

80

110 / 170

210 / 330

Motor output

kW

1.5

2.2

3.7

R410A

R410A

R410A

Galvanized steel plate (with polyester coating)

Galvanized steel plate (with polyester coating)

Galvanized steel plate (with polyester coating)

<MUNSEL 5Y 8 / 1 or similar>

<MUNSEL 5Y 8 / 1 or similar>

<MUNSEL 5Y 8 / 1 or similar>

1748 1200 485

1899 1420 635

1860 1750 1064

Thermal switch

Thermal switch

Thermal switch

9.52 Brazed (12.7 for over 90m)

15.88 Brazed

19.05 Brazed

22.2 Brazed

28.58 Brazed

34.93 Brazed

Refrigerant piping allowable length m

165

165

165

Sound pressure level

48.5

50 / 53

57

Cross fin (Aluminum plate fin and copper tube)

Cross fin (Aluminum plate fin and copper tube)

Cross fin (Aluminum plate fin and copper tube)

Synthetic fiber unwoven cloth filter

Synthetic fiber unwoven cloth filter

PP Honeycomb fabric filter

151

248

External dimension H W D

mm

Protection devices

Fan motor
Liquid pipe

30

35

40

45

-4C
-20

-15

-10

dB(A)

kg

437

Cooling

Heating

Cooling

Heating

Cooling

Heating

Indoor:15CWB~35CWB

Indoor:0CDB~20CDB

Indoor:15CWB~35CWB

Indoor:0CDB~20CDB

Indoor:15CWB~35CWB

Indoor:0CDB~20CDB

(Outdoor:20CDB~43CDB)

(Outdoor:-4CWB~15.5CWB)

(Outdoor:20CDB~43CDB)

(Outdoor:-4CWB~15.5CWB)

(Outdoor:20CDB~43CDB)

(Outdoor:-4CWB~15.5CWB)

1. Cooling/Heating capacity indicates the maximum value at operation under the following conditions.
<Cooling> Indoor,Outdoor:33CDB/28CWB
<Heating> Indoor,Outdoor:7CDB/3CWB
Pipe length:7.5m,Level difference:0m
2. The sound pressure level is measured in an anechoic room.
3. The indoor intake air temperature should be kept more than 0C.

40

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

Airflow rate

40

Heating
71.0 (Maximum 80.0)

6.73 / 6.72

Operating temperature range

20

Cooling
80.0 (Maximum 100.0)

12.6-11.9-11.5 / 12.2-11.5-11.1

Type Quantity

Net weight

4. At factory setting, the fan temporary stops in defrosting. Change DIP SW for fan to operate in defrosting.
5. Indoor temperature and humidity cannnot be controlled with Fresh air intake type.
6. Works not included: Installation / foundation work, electric connection work, duct work, insulation work. The power
source switch and other items are not specified in the specifications.

Indoor air
inlet temp (D.B.)
Outdoor air
inlet temp (W.B.)

20C
15.5C

0C
-5

10

15

20

25

30

35

40

Heating operation is available at -4C Outdoor temperature making it adaptable for places with frequent heating
requirements.

Page 17

PFAV-P900VM-E-F

PUHY-P500YSHA(-BS) (PUHY-P250YHA(-BS) 2,CMY-Y100VBK2) PUHY-P750YSHA(-BS) (PUHY-P350YHA(-BS)+PUHY-P400YHA(-BS),CMY-Y200VBK2)

28.0 (Maximum 33.5)

Air filter

80

Inlet air temperature (CDB)

Indoor air
15C
35C
inlet temp (W.B.)
Outdoor air
20C
43C
(
inlet temp D.B.)
-15

kW

Heat exchanger

-10

Inlet air temperature (CDB)

-20

PFAV-P900VM-E-F

PFAV-P600VM-E-F

Gas pipe

60

35

Power input

Refrigerant piping diameter

80

30

External finish

Heating

25

PFAV-P600VM-E-F

PFAV-P300VM-E-F

Refrigerant

100

20

kW

System current

Fan

Wide temperature range

15

System Power input


Power source

Features

Cooling

kW

3. Long period operation in a high temperature and humidity atmosphere(dew point of 23C or more) may cause
condensation.
4. Works not included: Installation / foundation work, electric connection work, duct work, insulation work. The power
source switch and other items are not specified in the specifications.

PFAV-P300VM-E-F
PUHY-P250YHA(-BS)

System capacity

459

Cooling

Outdoor

Line up

3-phase 4-wire 380-400-415V (50Hz / 60Hz)

R410A

Model Name

FRESH AIR INTAKE model

Heating
80.0 (Maximum 90.0)

8.27 / 8.34

F R E S H A I R I N TA K E m o d e l

*In heating operation, operation capacity may fall below the rated capacity in low outdoor temp. / indoor inlet temp. conditions.

Cooling
71.0 (Maximum 80.0)

2.2

28C
30

Heating
56.0 (Maximum 63.0)

15.8-15.0-14.4 / 14.7-14.0-13.4

Operating temperature range

15.5C

Outdoor air inlet temp (W.B.)

Cooling
50.0 (Maximum56.0)

R410A

Net weight

40

Heating
28.0 (Maximum 31.5)

7.46 / 7.53

Air filter
0

PUHY-P500YSHA(-BS) (PUHY-P250YHA(-BS) 2,CMY-Y100VBK2) PUHY-P750YSHA (-BS) (PUHY-P350YHA(-BS)+PUHY-P400YHA(-BS),CMY-Y200VBK2)

14.5-13.8-13.3 / 13.4-12.8-12.3

Type Quantity

Heat exchanger

20

25C

Indoor air
inlet temp (W.B.)

10

Power input

25.0 (Maximum28.0)

Gas pipe

-10

35

Outdoor air inlet temp (D.B.)


-5

Refrigerant piping diameter

60

Inlet air temperature (CDB)

-5C

kW

System current

External finish

Heating

15

PFAV-P750VM-E

Refrigerant

100

10

System Power input

Fan

Wide temperature range


Cooling

kW

30 HP

PFAV-P750VM-E

PFAV-P500VM-E

Cooling

System capacity

Power source

20 HP

PFAV-P500VM-E

PFAV-P250VM-E
PUHY-P250YHA(-BS)

Operation

10 HP

PFAV-P250VM-E

Indoor

45

Optional parts
Indoor unit
Outdoor unit

Description
Plenum chamber

Twinning kit

Model

Applicable capacity

PAC-CC83PL-E

PFAV-P250VM-E

PAC-CC85PL-E

PFAV-P500VM-E

PAC-CC87PL-E

PFAV-P750VM-E

CMY-Y100VBK2

PUHY-P500YSHA

CMY-Y200VBK2

PUHY-P750YSHA

Page 18

Installation information
Installation information

1. General precautions
1-1. Usage
The air-conditioning system described in this catalogue is designed for human comfort.
This product is not designed for preservation of food, animals, plants, precision equipment, or art objects. To
prevent quality loss, do not use the product for purposes other than what it is designed for.
To reduce the risk of water leakage and electric shock, do not use the product for air-conditioning vehicles or
vessels.
1-2. Installation environment
Do not install any unit other than the dedicated unit in a place where the voltage changes a lot, large amounts
of mineral oil (e.g., cutting oil) are present, cooking oil may splash, or a large quantity of steam can be
generated such as a kitchen.
Do not install the unit in acidic or alkaline environment.
Installation should not be performed in the locations exposed to chlorine or other corrosive gases. Avoid near a
sewer.
To reduce the risk of fire, do not install the unit in a place where flammable gas may be leaked or inflammable
material is present.
This air conditioning unit has a built-in microcomputer. Take the noise effects into consideration when
deciding the installation position. Especially in a place where antenna or electronic device are installed, it is
recommended that the air conditioning unit be installed away from them.
Install the unit on a solid foundation according to the local safety measures against typhoons, wind gusts, and
earthquakes to prevent the unit from being damaged, toppling over, and falling.
1-3. Unit characteristics
Heat pump efficiency depends on outdoor temperature. In the heating mode, performance drops as the outside
air temperature drops. In cold climates, performance can be poor. Warm air would continue to be trapped near
the ceiling and the floor level would continue to stay cold. In this case, heat pumps require a supplemental
heating system or air circulator. Before purchasing them, consult your local distributor for selecting the unit and
system.
When the outdoor temperature is low and the humidity is high, the heat exchanger on the outdoor unit side
tends to collect frost, which reduces its heating performance. To remove the frost, Auto-defrost function will be
activated and the heating mode will temporarily stop for 3-10 minutes. Heating mode will automatically resume
upon completion of defrostprocess.
Air conditioner with a heat pump requires time to warm up the whole room after the heating operation begins,
because the system circulates warm air in order to warm up the whole room.
The sound levels were obtained in an anechoic room. The sound levels during actual operation are usually
higher than the simulated values due to ambient noise and echoes. Refer to the section on "SOUND LEVELS"
for the measurement location.
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow,
and pressure changes even when operating normally. Please consider to avoid location where quietness is
required.
When the unit is started up for the first time within 12 hours after power on or after power failure, it performs
initial startup operation (capacity control operation) to prevent damage to the compressor. The initial startup
operation requires 90 minutes maximum to complete, depending on the operation load.

Page 19

Installation information

1-4. Relevant equipment


Use an earth leakage breaker (ELB) with medium sensitivity, and an activation speed of 0.1 second or less.
Consult your local distributor or a qualified technician when installing an earth leakage breaker.
If the unit is inverter type, select an earth leakage breaker for handling high harmonic waves and surges.
Leakage current is generated not only through the air conditioning unit but also through the power wires.
Therefore, the leakage current of the main power supply is greater than the total leakage current of each unit.
Take into consideration the capacity of the earth leakage breaker or leakage alarm when installing one at the
main power supply. To measure the leakage current simply on site, use a measurement tool equipped with a
filter, and clamp all the four power wires together. The leakage current measured on the ground wire may not
accurate because the leakage current from other systems may be included to the measurement value.
Do not install a phase advancing capacitor on the unit connected to the same power system with an inverter
type unit and its equipment.
If a large current flows due to the product malfunctions or faulty wiring, both the earth leakage breaker on the
product side and the upstream overcurrent breaker may trip almost at the same time. Separate the power
system or coordinate all the breakers depending on the system's priority level.
1-5. Unit installation
Your local distributor or a qualified technician must read the Installation Manual that is provided with each unit
carefully before performing installation work.
Consult your local distributor or a qualified technician when installing the unit. Improper installation by an
unqualified person may result in water leakage, electric shock, or fire.
Ensure there is enough space around each unit.
1-6. Optional accessories
Only use accessories recommended by Mitsubishi Electric. Consult your local distributor or a qualified
technician when installing them. Improper installation by an unqualified person may result in water leakage,
electric leakage, system breakdown, or fire.
Some optional accessories may not be compatible with the air conditioning unit to be used or may not suitable
for the installation conditions. Check the compatibility when considering any accessories.
Note that some optional accessories may affect the air conditioner's external form, appearance, weight,
operating sound, and other characteristics.
1-7. Operation/Maintenance
Read the Instruction Book that is provided with each unit carefully prior to use.
Maintenance or cleaning of each unit may be risky and require expertise. Read the Instruction Book to ensure
safety.
Consult your local distributor or a qualified technician when special expertise is required such as when the
indoor unit needs to be cleaned.

2. Precautions for Indoor unit


2-1. Operating environment
The refrigerant (R410A) used for air conditioner is non-toxic and nonflammable. However, if the refrigerant
leaks, the oxygen level may drop to harmful levels. If the air conditioner is installed in a small room, measures
must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant
should leak.
If the units operate in the cooling mode at the humidity above 80%, condensation may collect and drip from the
indoor units.

Page 20

Installation information

2-2. Unit characteristics


The return air temperature display on the remote controller may differ from the ones on the other thermometers.
The clock on the remote controller may be displayed with a time lag of approximately one minute every month.
The temperature using a built-in temperature sensor on the remote controller may differ from the actual room
temperature due to the effect of the wall temperature.
Use a built-in thermostat on the remote controller or a separately-sold thermostat when indoor units installed
on or in the ceiling operate the automatic cooling/heating switchover.
The room temperature may rise drastically due to Thermo OFF in the places where the air conditioning load is
large such as computer rooms.
Be sure to use a regular filter. If an irregular filter is installed, the unit may not operate properly, and the
operation noise may increase.
The room temperature may rise over the preset temperature in the environment where the heating air
conditioning load is small.
2-3. Unit installation
When a field-supplied external thermistor is installed or when a device for the demand control is used,
abnormal stop of the unit or damage of the electromagnetic contactor may occur. Consult your local distributor
for details.
Operating fresh air intake on the indoor unit may increase the sound pressure level.

3. Precautions for Outdoor unit


3-1. Installation environment
Outdoor unit with salt-resistant specification is recommended to use in a place where it is subject to salt air.
Even when the unit with salt-resistant specification is used, it is not completely protected against corrosion.
Be sure to follow the directions or precautions described in Instructions Book and Installation Manual for
installation and maintenance. The salt-resistant specification is referred to the guidelines published by JRAIA
(JRA9002).
Install the unit in a place where the flow of discharge air is not obstructed. If not, the short-cycling of discharge
air may occur.
Provide proper drainage around the unit base, because the condensation may collect and drip from the outdoor
units.
Provide water-proof protection to the floor when installing the units on the rooftop.
In a region where snowfall is expected, install the unit so that the outlet faces away from the direction of the
wind, and install a snow guard to protect the unit from snow. Install the unit on a base approximately 50 cm
higher than the expected snowfall. Close the openings for pipes and wiring, because the ingress of water and
small animals may cause equipment damage. If SUS snow guard is used, refer to the Installation Manual that
comes with the snow guard and take caution for the installation to avoid the risk of corrosion.
When the unit is expected to operate continuously for a long period of time at outside air temperatures of below
0C, take appropriate measures, such as the use of a unit base heater, to prevent icing on the unit base.
Install the snow guard so that the outlet/inlet faces away from the direction of the wind.
When the snow accumulates approximately 50 cm or more on the snow guard, remove the snow from the
guard. Install a roof that is strong enough to withstand snow loads in a place where snow accumulates.
Provide proper protection around the outdoor units in places such as schools to avoid the risk of injury.
3-2. Unit characteristics
When the Thermo ON and OFF is frequently repeated on the indoor unit, the operation status of outdoor units
may become unstable.

Page 21

Installation information

3-3. Relevant equipment


Provide grounding in accordance with the local regulations.

4. Precautions for Control-related items


4-1. Product specification
To introduce the MELANS system, a consultation with us is required in advance. Especially to introduce the
electricity charge apportioning function or energy-save function, further detailed consultation is required.
Consult your local distributor for details.
Billing calculation for AG-150A, GB-50ADA, TG-2000A, or the billing calculation unit is unique and based on
our original method. It is not based on the metering method, and do not use it for official business purposes. It
is not the method that the amount of electric power consumption (input) by air conditioner is calculated. Note
that the electric power consumption by air conditioner is apportioned by using the ratio corresponding to the
operation status (output) for each air conditioner (indoor unit) in this method.
In the apportioned billing function for AG-150A and GB-50ADA, use separate watthour meters for A-control
units, K-control units, and packaged air conditioner for City Multi air conditioners. It is recommended to use an
individual watthour meter for the large-capacity indoor unit (with two or more addresses).
When using the peak cut function on the AG-150A or GB-50ADA, note that the control is performed once every
minute and it takes time to obtain the effect of the control. Take appropriate measures such as lowering the
criterion value. Power consumption may exceed the limits if AG-150A or GB-50ADA malfunctions or stops.
Provide a back-up remedy as necessary.
The controllers cannot operate while the indoor unit is OFF. (No error)
Turn ON the power to the indoor unit when operating the controllers.
When using the interlocked control function on the AG-150A, GB-50ADA, PAC-YG66DCA, or PAC-YG63MCA,
do not use it for the control for the fire prevention or security. (This function should never be used in the way
that would put people's lives at risk.) Provide any methods or circuit that allow ON/OFF operation using an
external switch in case of failure.
4-2. Installation environment
The surge protection for the transmission line may be required in areas where lightning strikes frequently occur.
A receiver for a wireless remote controller may not work properly due to the effect of general lighting. Leave a
space of at least 1 m between the general lighting and receiver.
Install the wired remote controller (switch box) to the place where the following conditions are met.
Where installation surface is flat
Where the remote controller can detect an accurate room temperature
The temperature sensors that detect a room temperature are installed both on the remote controller and
indoor unit. When a room temperature is detected using the sensor on the remote controller, the main
remote controller is used to detect a room temperature. In this case, follow the instructions below.
Install the controller in a place where it is not subject to the heat source.
(If the remote controller faces direct sunlight or supply air flow direction, the remote controller
cannot detect an accurate room temperature.)
Install the controller in a place where an average room temperature can be detected.
Install the controller in a place where no other wires are present around the temperature sensor.
(If other wires are present, the remote controller cannot detect an accurate room temperature.)
To prevent unauthorized access, always use a security device such as a VPN router when connecting
AG-150A, GB-50ADA, or TG-2000A to the Internet.

Page 22

MITSUBISHI ELECTRIC SPLIT TYPE AIR CONDITIONERS

Series

Eco Changes is the Mitsubishi Electric Groups environmental statement,


and expresses the Groups stance on environmental management.
Through a wide range of businesses, we are helping contribute to the
realization of a sustainable society.

The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series
9000 of the International Standard Organization (ISO) based on a review of Quality management for
the production of refrigeration and air conditioning equipment.
ISO Authorization System
The ISO 9000 series is a plant authorization system relating to quality management as stipulated by
the ISO. ISO 9001 certifies quality management based on the "design, development, production,
installation and auxiliary services" for products built at an authorized plant.

FM33568 / ISO 9001;2008

Commercial Packaged
Air-conditioner

Cooling only series/Heat pump series


The Air Conditioning & Refrigeration Systems Works acquired environmental management system
standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO).
Registered on March 10, 1998.

Warning

Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.

- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, during repair, or at the time of disposal of the
unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.

http://Global.MitsubishiElectric.com

MEE13K027

New publication effective Feb. 2014