Split-System Evaporator Blower: K2ES120A25 10 Nominal Tons With Two 5 Ton Circuits
Split-System Evaporator Blower: K2ES120A25 10 Nominal Tons With Two 5 Ton Circuits
Split-System Evaporator Blower: K2ES120A25 10 Nominal Tons With Two 5 Ton Circuits
13-TG11Y (0500)
SPLIT-SYSTEM
EVAPORATOR BLOWER
K2ES120A25
10 NOMINAL TONS
WITH TWO 5 TON CIRCUITS
EER 8.5
DESCRIPTION
This completely assembled dual circuit evaporator blower
includes a well-insulated cabinet, a DX cooling coil with copper
tubes and aluminum fins, two expansion valves, two
distributors, throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor, a
24-volt control circuit transformer and a small holding charge of
refrigerant-22.
The unit is shipped in the vertical position ready for field
installation. For horizontal mounting, reverse the solid bottom
panel and the return air duct flange on the front of the unit.
This UL approved blower unit with two (2) 5 ton circuits can be
applied with the following condensing units:
One HCE120
Two HDB048s
Two HDB060s
ACCESSORIES
Base - 1BS0451
ARI RATINGS*
CONDENSING
UNIT
HCE120
EVAPORATOR
BLOWER
UNIT
K2ES120
CAPACITY
MBH
EER
122
8.5
*Certified in accordance with the Unitary Large Equipemnt certification program, which
is based on ARI Standard 340/360.
EER = Energy Efficiency Ratio
550.13-TG11Y
APPLICATION FLEXIBILITY
The KES120 is built in a single cabinet with two condensate drain pans.
This allows the unit to be installed in either the vertical or horizontal
position for maximum flexibility.
On vertical applications, the air velocity across the cooling coil keeps
the condensate from dripping off the finned surface onto the filters.
On horizontal applications, the unit must be installed with the
condensate drain pan under the entire cooling coil.
The Supply Air Plenum and the Return Air Grille accessories
can be used on either arrangement.
SP2
0.49
0.84
1.18
1.37
1.56
3200
BHP3
1.01
1.25
1.48
1.61
1.75
KW
0.94
1.16
1.38
1.50
1.62
SP2
0.34
0.71
1.06
1.26
1.46
3600
BHP3
1.17
1.42
1.70
1.86
2.02
KW
1.09
1.32
1.57
1.71
1.85
SP2
0.14
0.53
0.91
1.11
1.32
CFM
4000
BHP3
1.33
1.60
1.92
2.12
2.30
KW
1.24
1.48
1.75
1.95
2.10
SP2
0.30
0.70
0.91
1.13
4400
BHP3
1.80
2.18
2.39
2.60
KW
1.64
1.99
2.18
2.38
SP2
0.43
0.65
0.87
4800
BHP3
2.45
2.67
2.90
KW
2.24
2.44
2.65
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to Form 550.13-TG4 for the resistance of these accessories
and to the table below for additional motor and drive data.
The motor can operate into its service factor because its located in the moving air stream, upstream of any heating device. Units with steam or hot water coils are the only exception.
On these units, the BHP must not exceed the nominal HP rating of the motor.
Blower
RPM
700 - 950
Motor Specifications:
1750 RPM
208/230/460-3-60*
Solid Base
56 Frame
Designation
A36
Belt
Pitch Diameter, (in.)
37.3
Inherently protected
1.15 service factor
Permanently lubricated
ball bearings
*Although the motor is suitable for 460 volts, the unit control transformer is only suitable for a 208 or 230 volt power supply. The motor will always be wired for 208 or 230 volts.
550.13-TG11Y
95F
Sensible Capacity, MBH
Entering Dry Bulb, F
86
80
74
68
WB
F
Total
Cap.,
MBH
Power
Input,
KW
72
67
62
57
72
67
62
57
72
67
62
57
106.0
96.3
87.1
79.6
109.2
99.3
89.9
82.1
101.7
92.1
83.9
10.9
10.1
9.3
8.6
11.2
10.4
9.6
8.9
10.6
9.8
9.1
70.6
83.8
87.1
79.6
77.6
93.4
89.9
82.1
101.8
92.1
83.9
55.0
68.1
81.3
79.6
58.9
74.7
89.9
82.1
81.0
92.1
83.9
52.5
65.6
78.7
56.0
71.7
82.1
59.7
77.5
86.9
72
67
62
57
72
67
62
57
72
67
62
57
124.4
114.3
105.2
97.7
128.4
118.0
108..5
100.6
131.5
120.9
111.0
102.7
12.8
11.7
10.8
10.0
13.2
12.1
11.1
10.3
13.5
12.4
11.4
10.5
81.2
96.6
105.2
97.7
90.2
108.7
108.5
100.6
98.7
120.4
111.0
102.7
63.4
79.0
94.5
97.7
68.8
87.4
105.9
100.6
73.4
95.4
111.0
102.7
61.3
76.9
92.4
66.1
84.6
100.6
70.5
92.0
102.7
72
67
62
57
72
67
62
57
72
67
62
57
135
124
113
103
139
128
117
107
143
132
121
110
13.5
12.9
12.3
11.7
13.7
13.1
12.5
11.9
13.9
13.3
12.7
12.1
85
100
113
103
95
114
117
107
103
125
121
110
67
83
98
103
73
92
111
107
78
100
121
110
65
81
95
70
89
107
75
96
110
3400
4000
49.9
63.0
53.1
68.7
56.2
74.0
96.1
87.6
79.4
72.3
90.1
81.8
74.5
92.0
83.6
76.1
11.8
10.9
10.0
9.2
11.2
10.3
9.5
11.4
10.5
9.7
67.2
80.5
79.4
72.3
89.8
81.8
74.5
92.0
83.6
76.1
51.5
64.7 49.0
77.9 62.2
72.3 72.3
71.2 52.6
81.8 68.2
74.5 74.5
77.5 56.1
74.0 74.0
76.1 -76.1
46.5
59.6
49.6
65.2
52.6
70.5
78.8
71.7
65.0
80.9
73.6
66.8
82.3
75.0
68.2
11.7
10.8
9.9
11.9
11.0
10.1
12.1
11.2
10.3
77.1
71.7
65.0
80.9
73.6
66.8
82.3
75.0
68.2
61.3
71.7
65.0
67.8
73.6
66.8
73.9
75.0
68.2
45.5
58.8
65.0
49.1
64.7
66.8
52.5
70.4
68.2
43.0
56.2
46.0
61.6
49.0
66.9
101.3 14.8
93.2 13.6
55.0 85.8 12.6
70.4 79.3 11.5
95.8 13.9
59.0 88.1 12.8
77.3 81.4 11.8
97.4 14.2
62.6 89.5 13.1
82.7 12.0 82.7
72.9
88.2
85.8
79.3
95.8
88.1
81.4
97.4
89.5
82.7
55.1
70.5
85.8
79.3
78.8
88.1
81.4
86.5
89.5
82.7
52.8
68.2
79.3
57.5
75.7
81.4
61.7
82.9
79.3
50.6
65.9
54.5
72.7
58.1
80
95
100
91
89
108
104
94
98
118
107
97
63
77
92
91
68
86
103
94
73
94
107
97
60
74
89
65
82
94
69
90
97
57
71
61
78
65
86
4000
4800
59.3
74.9
63.4
81.9
67.1
88.6
112.9
103.8
95.5
88.5
116.3
106.9
98.3
91.0
109.2
100.3
92.7
13.8
12.6
11.6
10.7
14.2
13.0
11.9
11.0
13.3
12.2
11.2
77.1
92.4
95.5
88.5
85.8
104.4
98.3
91.0
109.2
100.3
92.7
59.3
74.8
95.5
88.5
64.5
83.1
98.3
91.0
91.0
100.3
92.7
57.1
72.6
88.5
61.8
80.2
91.0
66.1
87.5
84.0
4000
4800
63
78
67
85
71
92
129
118
107
97
133
122
111
101
136
125
114
104
14.2
13.6
13.0
12.4
14.4
13.8
13.2
12.6
14.6
14.0
13.4
12.8
83
98
107
97
92
111
111
101
101
123
114
104
65
80
95
97
71
89
107
101
76
97
114
104
63
77
92
68
85
101
72
93
104
60
74
64
81
68
89
122
111
100
91
126
115
104
94
129
118
107
97
14.9
14.3
13.7
13.1
15.1
14.5
13.9
13.3
15.3
14.7
14.1
13.5
Nominal Rating
NOTE: These capacities are gross ratings. For net capacities, determine the KW requirement of the supply air blower motor per the published BLOWER PERFORMANCE data.
Convert KW to MBH per the following equation and deduct this equivalent heat from the gross cooling ratings.
Blower Motor KW x
3.415 MBH
= Blower Motor Heat (MBH)
KW
The KW input ratings listed above include the compressor(s) and condenser fan motors.
550.13-TG11Y
PHYSICAL DATA
Evaporator Coil
Centrifugal Blower
(Forward Curve)
Filters
(Throwaway)
Distributor
Operating Charge
Weight, Lbs.
ELECTRICAL DATA
3 x 32
46
10.2
3/8
13
15 x 15
4
11.1
5-3-6 per circuit
2-0 per circuit
395
355
Blower
Motor
HP
Power
Supply
Voltage1
FLA
208
230
7.5
6.8
Max.
Fuse
Size2
(Amps)
10
10
Min.
Wire
Length3
(Feet)
145
178
MINIMUM CLEARANCES
Side with RETURN AIR opening
Side with SUPPLY AIR opening
Side with PIPING CONNECTIONS
Side opposite PIPING CONNECTIONS
Side with access for both POWER & CONTROL WIRING
Bottom
1
Overall height of the unit will vary if supply air plenum and/or base accessory is used.
2
This dimension is required for removal of the DX coil. Only 26" is required for normal servicing.
3
24"
24"1
52"2
12"
-3
-4
Although no clearance is required for service and operation, some clearance may be required for routing the
power wiring and the control wiring.
4
Allow enough clearance to trap the condensate drain line.
550.13-TG11Y
TYPICAL INSTALLATION (K2ES120 BLOWER UNIT WITH TWO HDB048 OR 060 CONDENSING
(TYP. 2)
HDB048 OR 060
550.13-TG11Y
FIELD WIRING
T E R
S U P
B L O
C O N
M IN A
P L Y
W E R
T A C
L S O N
A IR
M O T O R
T O R 1 0 M
3 -P H A S E
L IN E V O L T A G E
P O W E R S U P P L Y
P O W
D IS C
A N D
S U P
E R W
O N N E
F U S IN
P L IE D
IR IN
C T
G T
B Y
G
S W IT C H
O B E
F IE L D
U S E C O P P E R C O N D U C T O R S
O N L Y
W ir e in A c c o r d a n c e W ith L o c a l
A n d N a tio n a l E le c tr ic a l C o d e s
G R O U N D S C R E W
4 T B
R
G
T E R M
2 -S T A
O N L Y
2 T H 1 3
S U B -B
2 T B 0 5
IN
G
T
7
A
7
A L S
E C O
H E R
0 0 4 2
S E
0 0 1 2
R
Y
O
X
5 3
G
6 0
6 6
O N
O L IN G
M O S T A T
4 W IT H
C
Y
T E R M
O N B L
O F T H
C O N D
T
IN A L S
O C K 3 T B
E
E N S IN G U N IT *
2 4 -V O L T
C O N T R O L
W IR IN G
W h
K E
p ip
re m
T h e fie ld w ir in g c o n n e c t to th e s e d u m m y te r m in a ls o n 4 T B
c a n b e r o u te d d ir e c tly fr o m th e c o n d e n s in g u n it to th e
th e r m o s ta t if d e s ir e d .
e n a
S 1 2 0
in g o
o v e
1 . D
m
2 . D
3 . D
4 . R
is
o
is
is
e
p p ly in
e v a p
u ts id e
its tr a
g a n H
o ra to r
th e c a
n s fo rm
c o n n e c t
to r c o n ta
c o n n e c t
c o n n e c t
m o v e tra
w ir e
c to r
w ir e
w ir e
n s fo
C E
b lo
b in
e r
s 1
1 0
3 4
3 2
rm
1 2
w e
e t
a s
0 c o n
r, m a
o f th e
o u tlin
d e n
n ifo
K E
e d
s in g
ld th
S 1 2
b e lo
w
u n it w ith a
e r e fr ig e r a n t
0 a n d
0 7 C a n d 1 1 2 C fro m
b lo w e r
fr o m c ir c u it b r e a k e r C B .
A fr o m te r m in a l R o n 4 T B .
e r 1 T w ith th e a b o v e w ir e s .
T E R
S U P
B L O
C O N
M IN A
P L Y
W E R
T A C
L S O N
A IR
M O T O R
T O R 1 0 M
3 -P H A S E
L IN E V O L T A G E
P O W E R S U P P L Y
IN
G
T
7
A
7
A L
E C
H E
0 1 7
S E
0 0 1
S O
O O
R M
2 4
L IN G
O S T A T
W IT H
2 4
G
S W IT C H
O B E
F IE L D
W IR E # 7
W IR E # 9
T E R M
2 -S T A
O N L Y
2 T H 0 4
S U B -B
2 T B 0 4
IR IN
C T
G T
B Y
W ir e in A c c o r d a n c e W ith L o c a l
A n d N a tio n a l E le c tr ic a l C o d e s
4 T B
G
E R W
O N N E
F U S IN
P L IE D
U S E C O P P E R C O N D U C T O R S
O N L Y
G R O U N D S C R E W
P O W
D IS C
A N D
S U P
W IR E # 7
W IR E # 9
O
X
5 3
G
6 0
6 6
2 4 -V O L T
C O N T R O L
W IR IN G
C O N T R O L W IR IN G
O N F IR S T S T A G E
C O N D E N S IN G U N IT
C O N T R O L W IR IN G O N
S E C O N D S T A G E
C O N D E N S IN G U N IT
T h e fie ld w ir in g c o n n e c t to th e s e d u m m y te r m in a ls o n 4 T B
c a n b e r o u te d d ir e c tly fr o m th e c o n d e n s in g u n it to th e
th e r m o s ta t if d e s ir e d .
TWO STAGE COOLING WITH TWO (HDB048 OR 060) 5 TON CONDENSING UNITS
550.13-TG11Y
550.13-TG11Y
Code: EBY, EGY
Supersedes: 550.13-TG11Y (299)