Ringing On A Transmission Line
Ringing On A Transmission Line
Ringing On A Transmission Line
Bounce Diagrams:
Draw the bounce diagram for a 100 transmission line terminated in a 200 resistance. The source is
a 10V step function, with internal resistance of 50. The line is 10cm long. Dielectric inside the
transmission line is air. Draw 4 bounces. Label the time when the generator is turned on as 0. Label
each other time step at both load and generator sides.
0.01
, =
sec = 0.33
3 108
=
= 0.33
=
360
1
1
=
= 1
1
(0.33 360)
360
=
=
= 120
1
= 120
=
Bounce Diagram:
Schematic:
Fig 1 Schematic
Fig1.2 Schematic
10
2. Repeat the above simulation if source-series termination is applied to rectify the problem. What is
the source-series termination? Explain what do you have to add to the circuit? How does that prevent
ringing?
Ans: Source-series termination : As we know, the origin of the ringing is the impedance discontinuities
at the source and the far end and the multiple reflections back and forth. To prevent this ringing, we can
add impedance on the source side, to match the impedance of the transmission line so that when the
reflected signal comes back to the source and if it sees the same impedance then it will not reflect back.
This addition of additional resistance, we call it as a source series termination as we add the additional
resistor in the series at the input of the transmission line, so we call it as source-series transmission.
In our circuit, the impedance of the transmission line is 50 and the impedance of the voltage source is
10. To match the impedance at the input side with the impedance of the transmission line, we have to
add additional resistor of 40 in series with the source so that the total impedance will be 10 + 40 =
50. We can see the addition of source-series termination resistor in the circuit shown below.
As we know, ringing happens only when there is a change in impedance in the transmission line. So,
when the reflected signal from far end travels back to the source and reaches the series terminating
resistance, it sees looking into the source resistance and that is just the same as transmission line; so the
signal will encounter no impedance change and there will be no reflection. Thus, source-series
termination prevents ringing. We can see the output result in the output waveform in below figure.
11
Fig 2 Schematic
12
3. Re-create diagrams in Figure 8-20, page 308, for three widths of transmission line 25, 50! and 75 on
an electrically long line. What should the percent change of the characteristic impedance be to keep
the reflection noise below 5%? Demonstrate this with your simulations. What should the length of the
line be in terms of percent of rise time to keep the discontinuity negligible? Prove it with your
simulations.
Ans:
To keep the reflection noise to less than 5% of the voltage swing requires keeping the characteristicimpedance change to less than 10%. The reason behind this is the impedance discontinuities contribute
to reflection noise. The more the impedance discontinuities, the more reflection noise.
We can see in our examples of three transmission lines with different characteristic impedance 25, 50
and 75 .
13
Fig 3 Schematic
15
Fig3.4 Schematic
Fig3.5 Simulation
We can conclude from the simulation results that reflection noise can be kept low to 5% of the voltage
swing by keeping the characteristic impedance change to less than 10%. In simulation, we can see, when
we keep characteristic impedance change from 25 to 50 or 75 to 50 , there is always the
16
reflection noise. But, when we kept the characteristic impedance change from 50 to 50 , there is no
reflection noise on the transmission line.
What should the length of the line be in terms of percent of rise time to keep the discontinuity
negligible? Prove it with your simulations.
To keep the discontinuity negligible, the length of the line should be such that the time delay (TD) is
shorter than 20% of the rise time.
To prove this, we have kept the length of the transmission line such that the timedelay will be 40%, 30%
and 20% of the risetime, the impedance as 25 ohm, and then we have observed the output for each
circuit.
17
18
Fig3.8 Schematic
19
Fig3.11 Simulation
Fig3.12 Schematic
Fig3.13 Simulation
From the simulation results, we can conclude that the length of the line should be such that the time
delay will be less than 20% of the rise time to keep the discontinuity negligible.
21
4. Re-create diagrams in Figure 8-22, page 311, for three stub lengths (0, 20%, 40% and 60% of RT.
What should be the stubs time delay of the stub transmission line 25, 50 and 75 on an
electrically long line? What is the maximum length of the stub in terms of percent of rise time that will
keep the reflection noise acceptable? Demonstrate this in your simulation, and find the actual length
of the stub in that case.
Short stub reflections
Figure 3.4.1: Schematics for Short stub reflections due to varying stub lengths (0%, 20%, 40%, and 60%
of RT)
22
Figure 3.4.2: Simulations for Short stub reflections due to varying electrical lengths
We changed the electrical length of the transmission line stub to 0, 20%, 40% and 60% of rise time and
observed reflections for different electrical lengths.
Here we are given different stub lengths we have calculated electrical length for those different cases as
below:
23
Hence length should be shorter than the rise time of the signal as said in eqn 8.16 from the book
Maximum acceptable length for a discontinuity is _ <
Where:
24
What is the maximum length of the stub in terms of percent of rise time that will keep the reflection
noise acceptable? Demonstrate this in your simulation, and find the actual length of the stub in that
case.
Since for 20% of the rise time have Length of the stub as 0.6 inches, which is greater than the rise time
value o.5nsec. Thus we can approximately say that Maximum length of the stub can be kept as as high
as 15% of the rise time
TD = 15 % of rise time
Here, rise time = 0.5 ns, so TD = 0.5 ns * 15 / 100 = 0.075 ns
So, the Maximum electrical length = 6inches/nsec * 0.075 = 0.45 inches
Thus actual length of the stub will be 0.45inches
Since 0.45 < 0.5 so it implies that Lstub max < Rise Time
Thus at 15% of the rise time the reflection noise will be acceptable.
Figure 3.4.3: Schematics for Short stub reflections due to stub length 15% of the Rise Time and ideal
case (To keep reflection noise acceptable)
25
Figure 3.4.4: Simulations for Short stub reflections due to stub length 15% of the rise time and ideal
case
Thus from the above graph we can see that maximum length of the stub should be 15% of the Rise time
that will keep the reflection noise acceptable.
26
5. Re-create diagrams in Figure 8-23, page 312, for a transmission line end-terminated in three
capacitance values 2pF, 5pF and 10pF. What is modeled by these capacitances? Give several
examples. Can you estimate the new rise times (at the beginning and end of TL) and the increase in
time delay for these specific cases? How do your calculations compare to your simulation results?
Reflections due to capacitive load
27
If the rise time is short compared to the charging time of the capacitor, then initially, the voltage will rise
up very fast and the impedance will be low. But as the capacitor charges, the voltage across it gets
smaller and dV/dt slows down. The exact behavior will depend on the characteristic impedance of the
line (Z0), the capacitance of the capacitor and the rise time of the signal.
Thus this capacitors in the circuit model to the RC circuit behavior where C is the capacitance of the
load and R is the characteristic impedance of the transmission line, Z0.
28
For 5pF
For 10pF
29
6. Re-create diagrams in Figure 8-24, page 314, for a transmission line with capacitive load in the
middle of a trace for three capacitance values: 2pF, 5pF and 10pF. Calculate the maximum capacitance
for a specific rise-time and transmission line impedance. Compare the value with your simulations.
What should be done to keep capacitive discontinuities from causing excessive undershoot noise?
Reflection from Capacitive Loads in the Middle of a Trace
30
For 0.5 nsec, maximum allowable capacitance is 2 pF. For 0.5 nsec rise time, capacitance above 2pF will
have more undershoot problems
31
7. Re-create diagrams in Figure 8-34, page 329, for a transmission line with inductive load in the
middle of a trace for three inductance values: 1nH, 5nH and 10nH. What is the maximum acceptable
inductive discontinuity for this example? Compare calculations and simulations. How can we
compensate this series inductance, if its large value is unavoidable? Propose a solution and simulate
it.
Reflections from Inductive Discontinuities
32
Fig. 3.7.2: Simulation Results for reflections due to varying inductive discontinuity
Maximum allowable inductive discontinuity is given as < 0.2 0
Lmax< .2*50*50<.5nH
So, Inductance should be less than .5nH
Inductive discontinuity can be turned into a transmission line segment by adding a small capacitor to
either side. The capacitance to be added is given by
C=L/ (Z0)2
C= the total compensation capacitance to add, in nF
L= the inductance of discontinuity, in nH
Z0=the characteristic impedance of the line, in ohms
Assume the inductance of discontinuity to be 10nH, if we plug in the values in equation C=L/(Z0)2
The compensation capacitance comes out to be 4pF.For optimum compensation, the 4pF capacitance
should be distributed with 2pF on each side of the inductor.
33
34