Armstrong
Armstrong
Armstrong
F43.11
May 26, 2008
F43.11
Dec. 15, 2007
Series 4600F
Recirculation
Coupling
Drip Containment
fFitted with drain connection
Pump Casing
f Designed to withstand the high
pressure requirement typical in
fire protection
Impeller
Shaft Sleeves
fReplaceable bronze sleeves
fProtects shaft throughout
Stuffing Box
Bearings
f Easy removal with bearing nut
f Sealed, permanently greased
bearings
f Low Friction Lost Bearing
f Maintenance free
Bearing Housing
15 ANGLE CASING
f Removable without
removing top casing
Shaft
fMinimum deflection for long bearing life
fMinimum vibrations
f Identical shaft and parts for left and
right-hand drives
Suction and
Discharge on
same center line
JOCKEY
CONTROLLER
FIRE PUMP
CONTROLLER
FUEL
TANK
12
3
M
AR
10
ST RONG
11
Horizontal
Fire
Systems
GUARANTEED ADVANTAGES
f Simplifies piping design
f Single source unit responsibility
f A complete package that will meet
NFPA-20 requirements
FIRE PUMP - ELECTRIC DRIVEN
1. Pump/motor
2. Fire pump controller
(with optional transfer switch)
3. Suction and discharge gauges
4. Air release valve
5. Casing relief valve (not shown)
6. Jockey pump
7. Common base
7
FIRE PUMP - DIESEL ENGINE DRIVEN
1. Pump/engine assembled with
fCooling system
fFuel system
fBattery system
fExhaust system
2. Fire pump controller
3. Suction and discharge gauges
4. Air release valve
6. Jockey pump
7. Common base
2850
3800
4750
5700
7600
9500
11400
250
3600 RPM
1750
6 X 5 X 12
6 X 5 X 12
6 X 5 X 12
8 X 6 X 12.5
1500
200
1250
150
8 X 6 X 10
5 X 4 X 10
5 X 4 X 10
6 X 5 X 10
8 X 6 X 15
100
6 X 5 X 15
8 X 6 X 15
10 X 8 X 14
6 X 5 X 15
50
5 X 4 X 12
6 X 5 X 12
8 X 6 X 12.5
1000
12 X 8 X 18
8 X 6 X 10
12 X 8 X 18
750
12 X 8 X 18
10 X 8 X 14
500
8 X 6 X 12.5
275
500
750
1000
1250
1500
2000
2500
4750
5700
7600
9500
3000
2850
3800
3000 RPM
250
1750
6 X 5 X 15
200
1500
6 X 5 X 15
6 X 5 X 15
10 X 8 X 14
10 X 8 X 14
6 X 5 X 12
150
1250
6 X 5 X 12
1000
8 X 6 X 12.5
8 X 6 X 12.5
5 X 4 X 10
100
10 X 8 X 11
6 X 5 X 10
8 X 6 X 10
5 X 4 X 10
50
6 X 5 X 9.5
8 X 6 X 10
8 X 6 X 16
8 X 6 X 16
8 X 6 X 16
750
8 X 6 X 10
8 X 6 X 15
10 X 8 X 14
12x8x18
500
275
500
750
1000
1250
1500
2000
2500
1500 RPM
1800 RPM
fTypical Specifications
1. FIRE PUMP
One Armstrong, SERIES 4600F, Size _____________ double suction
horizontal split case fire pump listed by [Underwriters Laboratories of
Canada (ULC)], [Underwriters Laboratories Inc. (UL)] and/or [approved by
Factory Mutual (FM)] having a capacity of _______________ USGPM for a
pressure boost of _______________ PSIG. Suction pressure
______________ PSIG.
Pump casing shall be of cast iron, axially split with a 15 angle that will
minimize NPSH requirements and dimensions. Lower half shall contain
suction and discharge nozzles. Suction and discharge connections shall be
on the same elevation. Top half and rotating element shall be removable
without disturbing the piping. Casing shall be fitted with replaceable bronze
wearing rings. Impeller shall be bronze, double suction, enclosed type fully
balanced and keyed to an alloy steel shaft. Shaft shall to be fitted with
replaceable bronze sleeves. Shaft shall be mounted in two dust tight deep
grooves, sealed, and permanently greased ball bearings.
Each stuffing box shall be fitted with a three piece bronze gland. Stuffing box
shall be fitted with a stuffing box extension to facilitate the packing rings
removal. Packing rings shall be removable without disturbing wetted parts or
the pump bearings. Water seal recirculation lines made from non-corroding
material shall be piped to pump volute.
6. JOCKEY PUMP
2. ELECTRIC MOTOR
The fire pump shall be directly coupled through flexible coupling to a
horizontal electric motor with a maximum HP of_____________ at
__________RPM, _________ VOLT , _______ PHASE _________ CYCLE.
Motor shall be UL Listed for fire pump service, open drip proof, standard
efficiency with 1.15 service factor.
f
f
f
One (1) combination suction gauge 3 dial type with cock and lever
handle.
One (1) discharge gauge, 3 dial type, with cock and lever handle.
One (1) air release valve.
One (1) casing pressure relief valve.
4. OTHER ACCESSORIES
Pump shall be fitted with one (1) eccentric suction reducer and one (1)
concentric discharge increaser, as required (by mechanical contractor) to fit
NFPA20 recommended piping sizes.
One (1) outside test header shall be supplied with one (1) set of ____ x
2 hose valves with caps and chains.
S. A. Armstrong Limited
23 Bertrand Avenue
Toronto, Ontario
Canada, M1L 2P3
T: (416) 755-2291
F (Main): (416) 759-9101
3. MINIMUM FITTINGS
* Please refer to Armstrong Fire Pump Catalogue for Diesel Driven Typical
Specifications.