Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Armstrong

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Series 4600F

HSC Fire Pumps & Packaged Systems


FILE NO:
DATE:
SUPERSEDES:
DATE:

F43.11
May 26, 2008
F43.11
Dec. 15, 2007

Series 4600F

Series 4600F - Truly Superior


The Series 4600F, drawing on
over 100 years of pump design

Recirculation

expertise and leadership, is the

f External Water Seal


Recirculation Lines

state of the art in Horizontal Split


Case pumps. It meets or exceeds
the requirements of NFPA and
testing laboratories involved in fire

Coupling

protection such as UL, ULC, & FM.

fUL Listed close-coupled coupling

The family of pumps capitalize on


the Tilted Parting concept to
minimize turbulence at the eye of
the impeller by its straight laminar
approach, thus maximizing
efficiency. The family was
designed with commonality of
parts, low installation cost, and
ease of maintenance objectives.
The pumps compact sizes are
ideally suited for space saving
packages and retrofit applications.

Stuffing Box Housing


fSelf contained Combination
Bearing & Seal Housing
f Permits packing change-out
without having to be removed

Drip Containment
fFitted with drain connection

Casing Wear Ring


f Replaceable Case Wear Rings
fLocked to prevent rotation or
axial displacement
f Impeller Wear Ring available
as an option

Pump Casing
f Designed to withstand the high
pressure requirement typical in
fire protection

Impeller

Shaft Sealing with Packing

fHydraulically balanced double suction


fDynamically balanced
fMinimum axial thrust
fHigh efficiency throughout operating range

fThree-piece Split Gland standard


fPacking replaceable without
disturbing wetted parts
fStuffing Box Extension
designed for easy access

Shaft Sleeves
fReplaceable bronze sleeves
fProtects shaft throughout
Stuffing Box

Bearings
f Easy removal with bearing nut
f Sealed, permanently greased
bearings
f Low Friction Lost Bearing
f Maintenance free

Tilted Parting Design Casing


fPermits laminar approach to eye of Impeller
fLower NPSH required
fLower pump profile
fMinimum pump footprint
fRemoveable rotating element without disturbing piping
fLow foot-mounted Casing to reduce vibrations

Bearing Housing

15 ANGLE CASING

f Removable without
removing top casing

Shaft
fMinimum deflection for long bearing life
fMinimum vibrations
f Identical shaft and parts for left and
right-hand drives

Suction and
Discharge on
same center line

HSC Fire Pumps & Packaged Systems

JOCKEY
CONTROLLER

FIRE PUMP
CONTROLLER

FUEL
TANK

12

3
M
AR

10

ST RONG

11

Horizontal
Fire
Systems

With years of experience in fire protection


industry, Armstrong can supply fire pump
systems with all necessary accessories ready
for site installation.

GUARANTEED ADVANTAGES
f Simplifies piping design
f Single source unit responsibility
f A complete package that will meet
NFPA-20 requirements
FIRE PUMP - ELECTRIC DRIVEN
1. Pump/motor
2. Fire pump controller
(with optional transfer switch)
3. Suction and discharge gauges
4. Air release valve
5. Casing relief valve (not shown)
6. Jockey pump
7. Common base

Features common to electric and diesel


Accessories - (electric or diesel)
Accessories - special for diesel or VFD

7
FIRE PUMP - DIESEL ENGINE DRIVEN
1. Pump/engine assembled with
fCooling system
fFuel system
fBattery system
fExhaust system
2. Fire pump controller
3. Suction and discharge gauges
4. Air release valve
6. Jockey pump
7. Common base

ACCESSORIES - ADDITIONAL (ELECTRIC OR DIESEL)


8.
9.
10.
11.

Suction OS&Y gate valve


Discharge butterfly valve
Check valve
Test tee

ACCESSORIES - SPECIAL FOR DIESEL OR VFD


12. Main relief valve
13. Enclosed cone (not shown)

fFire Pump Coverage Chart


Electrical 60 hz
Rated Capacity (L/min)
1890

2850

3800

4750

5700

7600

9500

11400

250

3600 RPM

1750

6 X 5 X 12
6 X 5 X 12

6 X 5 X 12

8 X 6 X 12.5

1500

200
1250
150

8 X 6 X 10
5 X 4 X 10

5 X 4 X 10

6 X 5 X 10

8 X 6 X 15

100
6 X 5 X 15

8 X 6 X 15
10 X 8 X 14

6 X 5 X 15

50

5 X 4 X 12

6 X 5 X 12

8 X 6 X 12.5

1000

12 X 8 X 18

8 X 6 X 10

12 X 8 X 18

750

12 X 8 X 18
10 X 8 X 14

500

8 X 6 X 12.5

275

500

750

1000

1250

1500

2000

2500

4750

5700

7600

9500

3000

Rated Capacity (USGPM)


Electrical 50 Hz
Rated Capacity (L/min)
1890

2850

3800

3000 RPM

250

1750

6 X 5 X 15

200

1500
6 X 5 X 15

6 X 5 X 15
10 X 8 X 14
10 X 8 X 14

6 X 5 X 12

150

1250

6 X 5 X 12

1000

8 X 6 X 12.5
8 X 6 X 12.5
5 X 4 X 10

100

10 X 8 X 11

6 X 5 X 10
8 X 6 X 10

5 X 4 X 10

50

6 X 5 X 9.5

8 X 6 X 10

8 X 6 X 16

8 X 6 X 16

8 X 6 X 16

750

8 X 6 X 10

8 X 6 X 15

10 X 8 X 14

12x8x18

500
275

500

750

1000

1250

1500

2000

Rated Capacity (USGPM)


Note: Higher ranges may be available for diesel driven applications.

2500

Rated Head (kPa)

Rated Head (psi)

1500 RPM

Rated Head (kPa)

Rated Head (psi)

1800 RPM

fTypical Specifications

Horizontal Fire Pump - Electric Motor Driven*


Supply and install as indicated on plans one (1) fire pump system consisting of:

1. FIRE PUMP
One Armstrong, SERIES 4600F, Size _____________ double suction
horizontal split case fire pump listed by [Underwriters Laboratories of
Canada (ULC)], [Underwriters Laboratories Inc. (UL)] and/or [approved by
Factory Mutual (FM)] having a capacity of _______________ USGPM for a
pressure boost of _______________ PSIG. Suction pressure
______________ PSIG.
Pump casing shall be of cast iron, axially split with a 15 angle that will
minimize NPSH requirements and dimensions. Lower half shall contain
suction and discharge nozzles. Suction and discharge connections shall be
on the same elevation. Top half and rotating element shall be removable
without disturbing the piping. Casing shall be fitted with replaceable bronze
wearing rings. Impeller shall be bronze, double suction, enclosed type fully
balanced and keyed to an alloy steel shaft. Shaft shall to be fitted with
replaceable bronze sleeves. Shaft shall be mounted in two dust tight deep
grooves, sealed, and permanently greased ball bearings.

5. FIRE PUMP CONTROLLER


The fire pump controller shall be specifically approved for fire pump service
by [ULC], [UL] and/or [FM]. The controller shall be of the combined manual
and automatic stop, _______________starting method, Model ____________
as manufactured by___________. All equipment shall be enclosed in an
approved drip proof enclosure. The control equipment shall be completely
assembled, wired and tested at point of manufacture prior to shipment.
Circuit breaker shall have an interrupting capacity of _________kAmps or a
withstand rating of ____________ kAmps RMS.
Water pressure switch shall be suitable for _________ PSI working pressure.

5A. FIRE PUMP CONTROLLER AND AUTOMATIC TRANSFER


SWITCH COMBINATION
The automatic transfer switch controller combination shall be approved by
[UL], [ULC] and/or [FM], Model ________________ as manufactured
by________________. The automatic transfer switch and the pump controller
shall each be mounted in separate enclosures, mechanically attached to
form one unit and provide for protected interlock wiring.

Bearings shall be mounted in cartridge type housing so that they shall be


replaceable without opening pump casing. Bearings shall be easily
removable by rotating bearing removal nut. No special tools or bearing puller
are to be necessary.

The automatic transfer switch shall be capable of automatic power transfer


from normal to alternate_______________ [generator] / [second utility]
emergency power source in case of normal supply failure and automatically
re-transfer after restoration of normal power conditions.

Each stuffing box shall be fitted with a three piece bronze gland. Stuffing box
shall be fitted with a stuffing box extension to facilitate the packing rings
removal. Packing rings shall be removable without disturbing wetted parts or
the pump bearings. Water seal recirculation lines made from non-corroding
material shall be piped to pump volute.

6. JOCKEY PUMP

2. ELECTRIC MOTOR
The fire pump shall be directly coupled through flexible coupling to a
horizontal electric motor with a maximum HP of_____________ at
__________RPM, _________ VOLT , _______ PHASE _________ CYCLE.
Motor shall be UL Listed for fire pump service, open drip proof, standard
efficiency with 1.15 service factor.

The pump shall be supplied with the following accessories:

f
f
f

One (1) combination suction gauge 3 dial type with cock and lever
handle.
One (1) discharge gauge, 3 dial type, with cock and lever handle.
One (1) air release valve.
One (1) casing pressure relief valve.

4. OTHER ACCESSORIES
Pump shall be fitted with one (1) eccentric suction reducer and one (1)
concentric discharge increaser, as required (by mechanical contractor) to fit
NFPA20 recommended piping sizes.
One (1) outside test header shall be supplied with one (1) set of ____ x
2 hose valves with caps and chains.

S. A. Armstrong Limited
23 Bertrand Avenue
Toronto, Ontario
Canada, M1L 2P3
T: (416) 755-2291
F (Main): (416) 759-9101

7. JOCKEY PUMP CONTROLLER


The jockey pump shall be controlled by an automatic jockey pump
controller model___________ as manufactured by ___________with
full voltage starter.
8. MOUNTING AND TESTING

3. MINIMUM FITTINGS

The jockey pump shall be manufactured by _____________


Model______________ for a capacity of __________ USGPM and a pressure
boost of ____________ PSIG. The jockey pump shall be driven by an [open
drip proof] [totally enclosed fan cooled] electric motor of _______HP
________ RPM __________ VOLT ______ PHASE________ CYCLE.

Armstrong Pumps Inc.


93 East Avenue
North Tonawanda, New York
U.S.A., 14120-6594
T: (716) 693-8813
F: (716) 693-8970

The fire pump shall be suitable for a maximum working pressure of


__________. The fire pump shall be hydrostatically tested at twice the
maximum working pressure for at least 5 minutes. The fire pump shall be
performance tested at rated speed. The fire pump shall furnish not less than
150% of rated capacity at a pressure not less than 65% of rated head. The
shut-off total head of the fire pump should not exceed 140% of total rated
head. A certified test curve, indicating the flow, head, power and efficiency
shall be supplied for the field acceptance test. The fire pump and electric
motor shall be base mounted and aligned at the pump manufacturers
factory. Final alignment shall be made after installation on site

* Please refer to Armstrong Fire Pump Catalogue for Diesel Driven Typical
Specifications.

Armstrong Holden Brooke Pullen


Wenlock Way
Manchester
United Kingdom, M12 5JL
T: +44 (0) 161 223 2223
F: +44 (0) 161 220 9660
S.A. Armstrong Limited 2008

For Armstrong locations worldwide, please visit www.armstrongpumps.com

You might also like