DP158LD C
DP158LD C
DP158LD
Ratings
( kWm/PS)
Standby
Prime
Standby
Prime
1500rpm(50Hz)
510/693
464/630
494/672
448/609
1800rpm(60Hz)
556/756
505/687
552/750
481/654
Ratings Definitions
The power ratings of Emergency Standby and Prime are in accordance with ISO 8528.
Fuel Stop power in accordance with ISO 3046.
Electric power(kWe) should be estimated by considering generator efficiency, cooling fan power loss and
power derating due to altitude and ambient temperature.
STANDBY POWER RATING is applicable for supplying emergency power for the duration of the utility power outage.
No overload capability is available for this rating. A standby rated engine should be sized for a maximum of an 70% average
load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating.
PRIME POWER RATING is available for an unlimited of hours per year in variable load application. Variable load should not
exceed a 70% average of the Prime Power rating during any operating period of 24 hours. The Total operating time at 100%
Prime Power shall not exceed 500 hours per year. A 10% overload capability is available for a period of 1 hour within
a 12 hour period of operation. Total operating time at the 10% overload power shall not exceed 25 hours per year.
GENERAL ENGINE DATA
Engine Model
DP158LD
Engine Type
Bore x stroke
128 x 142 mm
Displacement
14.618 liters
Compression ratio
15 : 1
Rotation
Firing order
1-5-7-2-6-3-4-8
Injection timing
Dry weight
Dimension (LxWxH)
SAE NO.1M
Fly wheel
Clutch NO.14M
160
ENGINE MOUNTING
Maximum Bending Moment at Rear Face to Block
1,325 N.m
EXHAUST SYSTEM
Maximum Back Pressure
5.9 kPa
2.16 kPa
6.23 kPa
0.125 kPa
COOLING SYSTEM
Water circulation by centrifugal pump on engine.
Cooling method
Coolant capacity
Engine Only : Approx. 20 lit, With Radiator (*Air On 43) : Approx 79 lit.
660 liters / min @ 1800 rpm, 550 liters / min @ 1500 rpm,
Pressure Cap
Max. 49 kPa
Water Temperature
- Maximum for standby and Prime
103
40.0
Water pump
Wax pellet type, Opening temp. 71C , Full open temp. 85C
Cooling fan
Not available
* Two radiator options are provided, based on allowable maximum Air temperature On radiator inlet (Air On) : Air On 43C / Air On 52C
- ATB(Ambient Temperature before Boiling) of generator set varies depending on the engine room ventilation design, even if the same radiator applied.
Adequate selection of radiator options by means of the cooling test is highly recommended, and generator set makers are responsible for the selection.
LUBRICATION SYSTEM
Force-feed lubrication by gear pump, lubricating oil cooling in cooling water circuit of engine.
Lub. Method
Oil pump
Oil filter
Oil capacity
120
Angularity limit
Lubrication oil
FUEL SYSTEM
Bosch type in-line pump with integrated, electromagnetic actuator.
Injection pump
Governor
Electric type
Speed drop
Feed pump
Injection nozzle
Opening pressure
28 MPa
Fuel filter
30 kPa
60 kPa
315 liters / hr
Used fuel
ELECTRICAL SYSTEM
Battery Charging Alternator
Voltage regulator
Starting motor
24V x 7.0 kW
Battery Voltage
24V
Battery Capacity
2 x 200 Ah (recommended)
Block heater
VALVE SYSTEM
Type
Number of valve
Valve timing
Opening
Close
-. Intake valve
24 deg. BTDC
36 deg. ABDC
-. Exhaust valve
63 deg. BBDC
27 deg. ATDC
PERFORMANCE DATA
Prime Power
Standby Power
rpm
1500
1800
1500
1800
rpm
800
800
800
800
rpm
1650
1980
1650
1980
kW
464
505
510
556
PS
630
687
693
756
MPa
2.53
2.30
2.78
2.53
m/s
7.1
8.5
7.1
8.5
Friction Power
kW
32
44
32
44
PS
43.5
59.8
43.5
59.8
25% load
liters/hr
30.3
35.2
32.3
37.4
50% load
liters/hr
55.1
62.3
60.9
68.1
75% load
liters/hr
83.4
92.9
91.1
101.0
100% load
liters/hr
115.1
127.1
127.8
139.6
g/h
441
481
485
529
Fan Power
kW
16
24
16
24
97.65
100.33
97.65
100.33
dB(A)
The all data and the specific fuel consumption are based on ISO 3046/1, Standard reference conditions are in accordance
with 298 K(25 Celsius) air temperature, 100kPa(1000mbar) air pressure, 60% relative humidity, 110m(361ft) altitude.
m3/min
30.8
34.2
33.1
36.6
536
539
561
567
m3/min
90
100
98
108
kW
426
470
473
517
kW
204
225
226
247
kW
104
115
115
126
kW
43
48
48
52
liters/min
590
660
590
660
m3/min
700
850
700
850
(Ambient Temp)
(52)(45) (38)
35% )
1500RPM
30%
(30)
(25)
Derate(%
35% )
20%
20%
15%
15%
10%
10%
5%
5%
500 1000 1500 2000 2500 3000 3500 4000
Altitude (m)
(30)
(25)
25%
1800RPM
30%
25%
0%
(Ambient Temp)
(52)(45)(38)
0%
Altitude (m)
ENGINE DIMENSION
CONVERSION TABLE
in. = mm x 0.0394
PS = kW x 1.3596
psi = kg/cm2 x 14.2233
in3 = lit. x 61.02
hp = PS x 0.98635
lb = kg x 2.20462
kW = kcal/sec x 0.239