Construction and Performance of Curtain Wall Systems For Super Highrise Buildings - The Hong Kong's Experience
Construction and Performance of Curtain Wall Systems For Super Highrise Buildings - The Hong Kong's Experience
Construction and Performance of Curtain Wall Systems For Super Highrise Buildings - The Hong Kong's Experience
ABSTRACT
The construction of super highrise buildings has been very active in Hong Kong for decades.
Recent renowned projects like the 50-storey Manulife Tower, the 62-storey Cheung Kong Center,
the 80-storey Center, the 88-storey International Financial Center, and a number of recent
residential buildings exceeding 60-storey tall, are without exception, using curtain wall as their
external envelope.
Using thin wall as external envelope for tall buildings has always been a challenge to designers
and builders, in particular in terms of cost, energy, water-tightness, installation, dimensional and
structural stability, interfacing arrangement with other building components and maintenance etc.
Making use of the Hong Kongs experience, the writer wish to highlight some local practices and
summarize how such thin wall systems are designed and installed.
More deluxe commercial buildings were built in the late 70s as the economy of Hong Kong
growing hotter and hotter. Developers tended to request for systems with higher performance as the
external envelop for their buildings, in terms both of appearance, material, construction and
maintenance concerns.
Due to the relative lack of experience at that stage, the performance of these second generation
curtain wall systems (from late 70s to mid 80s) could still hardly described as satisfactory.
Problems like seepage, staining, deformation, deterioration and rapid aging of the jointing materials,
were very common to many walling cases, often to a condition that made repair and maintenance
almost impossible. The replacement of these walling systems not only costly, but also created great
disruption to the normal utilization of the building users, and at the same time badly lowered the
property value of the entire premises.
Photo 1 Commercial centres of Hong Kong where buildings with curtain wall of various era form an excellent showcase (from left,
Central in HK and Tsim Sha Tsui on the Kowloon side.
The third generation of curtain wall systems roughly started in the mid/late 80s, by the time Hong
Kong was experiencing her economic climax before the handing over of her sovereignty back to
China in 1997. Accommodated experience in the application of curtain wall systems in highperformance buildings contributed solidly in the process of perfecting these systems. Throughout
the period, the design and production teams, as well as the manufacturers and the engineering
supporting teams, were growing more mature in the mastering of the local situation and market.
Most problems appeared in the previous cases have been much effectively taken care of. Systems of
this generation are in general much more satisfactorily received by most users.
There are many ways to serve the purpose, depending on a number of factors such as the design and
budget for the project, layout and shape of the building structure, as well as other architectural or
structural requirements. According to the American Architectural Manufacturers Association,
curtain wall systems can be classified in five types, namely, the stick system, unit system, unit and
mullion system, panel system, and the column-cover-and-spandrel system. However, due to the
introduction of high-performance framing/articulation products and high-strength structural glass,
some newer forms of curtain wall systems such as large-area glazed wall using spider clips, bow
mullions, hangers or cable stiffeners as supports and connections, are new systems that cannot
easily be classified using traditional concepts.
Stick system
Curtain wall using the stick system consists of mullions which provide the major loading support to
the wall. The mullions are usually of extruded aluminum sections, secured to the building structure
using brackets, cramps and anchors, or to a backing structure that provides the form of the external
wall.
This system has the following merits/demerits:
Merits
-
Low cost, components can be made in standard design and stocked as proprietary product
for use in bulk quantity.
Require relatively simple sections to form the mullions and the backing frame.
The design the infilling panels can be very flexible and form various combination using
different materials to provide the appearance or fulfill other functional requirements.
Installation of the system only requires simple tool like a manually operated pulley set-up.
Demerits
-
Higher risk of leaking due to the existence of large amount of in-situ joints between mullion
and panels.
Involvement of large number of framing members coming from the mullion, transom or
other framing parts that make the fixing at spot quite troublesome and inconsistent.
Less fashionable for the design limited basically to monotonous grid without the elegance
that other systems may achieve.
Photo 2 Projects using Stick system the 68-storey Shun Hing Plaza in Shenzhen (left) and the Gateway in Tsim Sha Tsui. Close-up
look at the wall detail (Center photo), Shun Hing Plaza (top) and Gateway (bottom)
Unit System
Unit systems are composed of modulated panels that are fabricated in factory and delivered to site
in one-piece for installation. The panels are fully provided with all the glazing and/or the spandrel
panels, incorporated with the required insulation and other architectural features, thus requiring very
limited second-fixed installation works on site. The panels are usually spanned in a floor-to-floor
arrangement and may be designed in a number of standard/optional panels such as fully glazed,
glazed with opaque panels, fully opaque in metal or stone slab, louvered panels, or other special
modules like the corner or bayed units. In order to get the best benefit of using this system, units are
often produced to an optimistic large size so as to minimize the number of units used.
This system has the following merits/demerits:
Merits
-
Easy to install merely by securing the modulated panels onto the building exterior using
fixing/connection devices which are usually very dimensionally flexible.
Higher performance units can be produced to meet stringent requirements due to better
control under factory environment.
Preferably to be used in buildings with large walling area for the economy of scale in
production as well as the elimination of countless assembly of minor components on site.
Demerits
It takes longer lead time to carry out the coordination, design and fabrication of the
system/units.
Require higher dimensional accuracy in the building structure for the fixing of the units.
Lifting appliances may be required to assist the hoisting and installation of the large-sized
walling units
Difficult to carry out replacement or maintenance due to the interlocking nature of the
modulated units.
Photo 3 Projects using unit system curtain wall. From the left, Cheung Kong Center (62-storey), The Center (80-storey) and
the Manual Life Tower (50-storey)
or for buildings of industrial purposes. In this case, the panels can be constructed of sheet materials
and manufactured in large quantity in very low cost.
Column-cover-and-spandrel system
Column-cover-and-spandrel system consists of column covers, which are usually made of alloyed
aluminum, metal sheet or other laminated/fibre-reinforced sheet, and with glazing components and
spandrel panels that fit between them. It resembles certain similarity to a unit-and-mullion system
except that the structure of the building is exemplified by the column covers.
With the exception of the stick system and the unit system, other curtain wall systems are seldom
used in Hong Kong.
Very large-sized building, with external walls sometimes up to 50,000m2, fully cladded
with curtain wall.
Typhoons that occur during the summer season with wind speed up to 60m/s.
Extreme of temperature difference with surface temperature more than 60oC under tropical
sun in summer.
In order to cater such special/local requirements, curtain wall systems suitable for use in Hong
Kong should meet the following functional requirements.
Strength and stability
Besides taking up its own weight, curtain wall must be able to resist wind forces and transmitting
them reliably to the building structure. Wind loads increase in severity to the height of the building.
Members of the walling frames and their fixings must be strong and durable enough for the purpose.
The following factors should be noted during the design of the walling system and its support:
-
Avoid too clumsy and complicated design for the ease of construction and maintenance.
Anchorage provision to the structure should be sufficiently and securely provided using
appropriate devices and methods that serve the need of a particular system.
Walling units should be strong enough to take up positive and negative wind pressure, or
avoid damage so caused due to deflection or distortion under expected building movements,
and the subsequent building up of undesirable stresses to the units or their glazing.
The members of the frame and their fixing should be made of strong and corrosion-resisting
material, with appropriate design to allow expansion due to various kinds of movement.
Weather resistance
Weather resistance to a curtain wall system refers to its ability to keep out water and wind. In
principle the weather tightness of curtain wall can be achieved by the use of impervious infilling or
paneling materials such as glass, metal, plastic sheet or stone slab. However, joints between the
materials as well as their fixing to the other contacting components often cause failures in the
keeping out of weather. Appropriately designed jointing or sealing provision can improve or
overcome the situation; yet the natural aging, deformation, constant movement due to wind or
thermal effect, or gradual deterioration of the joints in a long run can still reduce the ability of the
walling against weather. Severe environmental conditions of Hong Kong in this respect form a very
challenging exercise for designer and manufacturer in most cases.
Thermal insulation and condensation
Tall and large-sized buildings using certain wall can create huge energy loss especially when air
conditioning for cooling is provided. In order to minimize the loss, in addition to the use of doubleglazing glass of appropriate material and design, the other non-glazed portion should also be
properly insulated with thermal effective materials under the right design. According to the
Building Regulation (Energy Efficiency) of Hong Kong, it requires tower-type building to maintain
a maximum of 30 W/m2 in the overall thermal transfer value (OTTV) in the design.
Besides meeting the OTTV targets, very humid, extreme temperature difference and providing long
period of cooling, like most building environment in Hong Kong, is typical situations that easily
generate condensation problems. The result of this may cause dampness to the affected walling
components, and sometimes even damp the ceiling board, dry wall or window lining that located
near the cold-bridging zone. There are a number of practical ways that may further exemplify such
problems, such as:
-
Large amount of cold-bridging locations appear in the connections and the backing frame
which are usually made of conductive materials such as alloyed aluminum, galvanized or
stainless steel.
Large number of inaccessible voids between opaque panels or spandrels, or gaps between
curtain wall and structural members of building, where insulation can hardly be applied.
Discontinuation of the insulating materials or vapour barrier due to the overlooking in the
design or imperfect workmanship during installation.
Sound insulation
Most of the high-quality deluxe type buildings in Hong Kong are situated within the congested
downtown area, some even located less than a hundred meter aside super-highway. Background
noise of more than 70dB is often encountering under such situations. Fortunately, most curtain wall
systems of appropriate design can meet the requirement by reducing at least 25dB of air-borne
sound. Some factors such as the lack of ventilation provision in the window to benefit internal
cooling, or the strong and heavy-duty design of the walling units to provide resistance to wind load,
are favourable for the insulation of sound in the Hong Kongs systems. However, modern buildings
may be quite noisy due to the extensive use of building services equipment like the chilling plants,
pumps and networks of pipes and ducts. The introduction of discontinuity in the jointing design at
the connecting points of the major framing members and by cushioning the anchorages are often
proved to be quite effective in disconnecting the structure-borne sound.
Fire resistance
Tower-type buildings using curtain wall usually do not impose specific fire resisting requirements
due to enough separating distance from the relevant boundary. However, fire spread between
building compartments should be provided especially between floors or units under separate
occupancy. This can be ensured by the use of fire resisting construction in the non-glazing portion
of the wall, and sealing all voids and gaps between such compartments by fire resisting materials.
Air infiltration
Sometimes in-situ tests may also be required such as the Pull-out test to ensure the performance of
the fixing connections, or water test to ensure the water-tightness of larger area of wall section.
Photo 5 rack and lift trolley for the storing and transporting
of the wall units inside the working floor.
Anchorage provision is required no matter which type of curtain wall system is used. For buildings
in RC construction, cast-in anchor in the form of dovetail channel (Photo 7) or connecting plate
(Photo 8) for the welding of hangers or cramps are usually used for the securing of the components
(Photo 9). For buildings of structural steel construction, the same provisions can be welded onto the
steel members directly. Dimensional flexibility to convenient installation or to allow necessary
movements should be provided in the connection devices. Such flexibility can be made by the
provision of slotted holes in the fixing brackets, by adjusting the position of the fixing bolts in the
dovetail channels, or using teethed shimming plate between connections (Photo 10), so that
alignment, level, verticality or plain of the wall can be adjusted and fine-toned.
Photo 8 steel plate positioned in the floor slab for the fixing
bracket to weld onto afterward.
Installation arrangement
Usually lighter and smaller-sized components such as the mullion, transom, spandrel board or
glazing panes are involved in stick system curtain wall, thus the installation process does not require
any lifting instrument except a simple lifting rod with pulley. However, the stick system often
involves a large number of components in different sections and sizes, it requires more labours for
fixing and installation, and at the same time increase the inconsistence of workmanship.
The fixing and installation of unit system curtain wall can be very neat and simple. In most design,
independent units with appropriate jointing provision to the adjoining units are fabricated and
delivered to site for immediate installation. This is further made easy by very flexible connecting
devices so that the units can almost be placed in position at one-fix and final adjusted by using the
dimensional flexibility provided in the connection devices. However, the weight of the unit will
require the erection of special lifting tool like a winching machine mounted on track or provision of
external work gondola (Photo 10).
Owing to the structural requirements and specific nature of the backing frame, which is often
constructed of structural steel, its installation usually regarded as part of the building work other
than as curtain walling.
In any case, the installation is done at high level on building exterior, safety provisions such as
personal protection equipment, rail and fence at building edges (Photo 11) should be provided at the
work spot at all time.
Final fixing and inspection
Before the final securing of all the connections, the alignment, level, verticality and plain of the
curtain wall should be checked for slight adjustment can still be made at this stage. Similarly, other
details such as the position and condition of the expansion joints, edging strips, sealing or insulation
materials, and other filling arrangement for the adjoining void and gaps, are to be checked to ensure
they are in order before the sealing off of the walling system permanently by the finishing panels.
MAINTENANCE CONSIDERATION
Maintenance for curtain wall is a long-term consideration involving both the quality of design,
control during construction and adequate maintenance throughout the life span. Once failure occurs
in the curtain wall it will be very expensive to have the defects rectified and at the same time
causing great disturbance to the building users. Below are some common problem sources where
failures usually occur.
1.
Design failure selection and appropriateness of the system, non-compliance to design and
performance standards, imperfection in the jointing design and detailing, improper use of
materials etc.
2.
3.
Aging and deterioration discolouring and surface damaging due to weather action;
corrosion due to air pollution, acid rain, or electro-chemical effect to dissimilar metals;
aging and hardening of the glazing compound or sealing gasket, deteriorating of the
insulating materials that lead to further dampening of the walling materials/components,
disfiguring or loosening of the fixing and connections, loosening or broken-off of the
glazing or other fitting items.
Curtain wall systems should be inspected regularly after they have been installed in buildings.
Proper maintenance and repair are essential to keep them in a safe condition. Inspection
arrangement should be made in particularly before and after typhoons. The below signs are
recommended to observe closely during each inspection.
-
extrusion, wrinkle, split, missing or other signs of deterioration of the sealing materials.
CONCLUSION
The application of curtain wall systems in super-highrise buildings is a big topic. Within the scope
of this paper it can only cover a very little of the key issues. Having witnessed the evolution of
using curtain wall in Hong Kong for the past 2 to 3 decades, a general trend, as summarized below,
can be observed.
Starting from low-cost, local-design and manufactured walling products in the early systems
to the imported, deluxe, tailor-designed proprietary systems in recent years.
Starting from simple requirements fulfilling just very basic functional needs of buildings to
very specialized products or systems that can meet any stringent requirements as set by
designer, engineers or environmental experts.
The old systems were mainly stick systems due to more simple in design and production.
Though labour-intensive, the relatively much cheaper labour cost at that time still made it
worked acceptably. Contemporary systems are using mainly unit systems that make
installation very easy and labour saving, though the design quality and coordination with
other building activities are much more demanding.
The old systems that have been used in the first and second generations often inherited with
quite a lot of design imperfections and latent defects; while new systems are more reliable,
some can be regarded as almost maintenance-free.
Traditional external walling methods using applied-onto products such as tile or spray-on coating
are still dominating in Hong Kong. However, it is notable that the use of curtain wall is gaining its
popularity quite rapidly among designers and developers due to its unreplaceable attractiveness as
well as slim and fashionable appearance.
Further development and improvement in the use of curtain wall systems is an ongoing process in
Hong Kong. The areas of improvement may be aiming at the development of more specific
functioned, more reliable and long-life systems. Such targets may be achieved by the use of more
advanced glass products, sealing compounds, gaskets or in the development of more sophisticated
connecting systems; as well as the introduction of other additional functions that curtain wall may
take up like the incorporation of photo-cell onto panels of wall, the providing of automatic/robotic
machine in the system for external wall cleansing, or curtain wall capable to perform light show at
night. Meanwhile, the continual improvement of workmanship and refinement of work detailing in
particular to the areas directly in touch with the building structure or other building finishes, is a
prime concern to the ensurance of a good curtain wall system, that sometimes project executives
may easily overlooked.
REFERENCES
[1]
Harold B, Loin, Construction Principles, Materials and Mehtods, John Eiley & Sins, 1994.
[2]
J S Foster & R Harington, Structure & Fabric 2, Mitchell Building Series, Longman, 1994.
[3]
[4]
W S Wong, External Wall Hong Kong Case Studies, China Planning Publication &
PACE Publishing Ltd., 1997
[5]
Building Department, Curtain Wall Systems, Practice Note for Authorized Persons and
Registered Structural Engineers, Government of Hong Kong, 1999
[6]
T Youngs, Curtain Wall projects, Building Journal, China Trends Press, January 2002.