2468ca DB
2468ca DB
2468ca DB
Operating Manual
24685033
Copyright 2001
Solartron Mobrey
All rights reserved
Solartron Mobrey pursues a policy of continuous development and product improvement. The specification in this
document may therefore be changed without notice.
To the best of our knowledge, the information contained in this document is accurate and Solartron Mobrey cannot be
held responsible for any errors, omissions or other misinformation contained herein. No part of this document may be
photocopied or reproduced without prior written consent of Solartron Mobrey.
Appendices
All appendices are located at the end of this manual for easy reference.
Appendix A Approval Certificates contains copies of certificates complying with the
necessary safety approvals for the Hydrastep 2468.
Meaning
Direct Current
Alternating Current
Part 1
Hydrastep 2468CA & 2468CC
Electronic Gauging System
24685033_DA
Pt.1-1
Pt.1-2
24685033_DA
24685033_DA
Pt.1-3
Pt.1-4
24685033_DA
Part 1
Contents
Chapter 1
Chapter 2
Chapter 3a
Chapter 3b
Chapter 3c
Chapter 4
24685033_DA
Pt.1-5
Pt.1-6
24685033_DA
1.2
1.3
SYSTEM OPTIONS................................................................................6
1.3.1
1.3.2
1.3.3
1.4
Figure 1.1 - Front panel of the Hydrastep 2468 gauging system, with local display........... 2
Figure 1.2 - Schematic of resistance measuring cell and electrodes.................................. 3
Figure 1.3 - Typical Hydrastep 2468 System Installation .................................................... 4
Tables
Table 1.1 - Upgrade paths and available options................................................................ 7
24685033_DA
1-1
HYDRASTEP
FM
APPR O VED
STAS
TYPE APPR O VED
Ex
B86941:1988
Ex N IIC T4
Tam b 70 C
CERT No. Ex94Y4362X
Do Not O pen W hen Energised
TYPE 2468
Rating 110/240V
48-65Hz 30VA
24V
30W
Tem p : -20 C to +70 C
Ingress P rotection : IP65/N EM A 4X
M ade in U .K by Solartron M obrey
Slough, B erkshire, SL1 4U E, UK.
Houston, Texas 77084, US A. Tel: +1 281-398-7890
Figure 1.1 - Front panel of the Hydrastep 2468 gauging system, with local display
1-2
24685033_DA
1.1
A vertical row of electrodes is installed in the water level column attached to boiler and
typically aligned so that half the electrodes are above and half below the normal water level
(see Figure 1.2). The resistance measurement is made between the insulated tip of each
electrode and the wall of the column.
The cell constant defining the actual resistance measured is determined by the length and
diameter of the electrode tip and the column bore. In practice, the cell constant is chosen so
that the resistance in water is less than 100k ohms and the steam resistance is greater than
10M ohms. Since the resistivities of water and steam are substantially different, the system
is simple and requires no setting up adjustments. It is not susceptible to power supply
variations, ambient temperature changes, etc., resulting in a highly reliable system.
A general overview showing how a typical Hydrastep 2468 System is installed is illustrated
in Figure 1.3.
24685034_DA
1-3
1-4
24685033_DA
1.2
For both systems, the printed circuit boards are housed in the same enclosure, allowing
customers full capability to expand their system as and when conditions dictate.
Table 1.1 on page 1.7 is a summary of all upgrade paths and options for the Hydrastep 2468
system.
1.2.1
INPUT BOARDS
All versions of the Hydrastep 2468 unit contain one or two input boards. The input boards
mount on to the base plate in the enclosure. Each input board provides power supplies,
electrode drive, signal processing, fault analysis and an analogue output.
The input board can accept inputs from 8, 10, 12, 14 or 16 electrodes. When two input
boards are used (in a dual power supply system) the electrodes are interlaced; that is, the
odd numbered electrodes are connected to one input board and the even numbered
electrodes are connected to the other. Full details of the wiring are covered in Chapter 2
under Installation.
Each input board also includes a current output circuit that provides an analogue
representation of the water level in the column. The analogue output can be configured to
give a current output in one of the following ranges:
1.2.2
0 to 20mA
4 to 20mA
20 to 0mA
20 to 4mA
DISPLAY BOARD
The display board is mounted on to the hinged lid of the unit and provides indication through
the viewing window on the enclosure. It also supplies configuration information to the input
board(s); that is, the number of electrodes connected to the unit and the required
water/steam switching threshold.
Figure 1.1 shows the local display with water level and system fault indication. Water level
is indicated by two columns of LEDs, one red to indicate steam and one green to indicate
water. The number of LEDs illuminated is dependent on the number of electrodes present
and a blanking panel is available to mask the LEDs not used. In addition to the system fault
indication is an opto-isolated system fault output. Switches are provided to allow the
number of electrodes to be selected (8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30 or 32). Two
solder link pads are provided to select the water/steam switching-threshold (0.6S/cm or
1.6S/cm).
24685034_DA
1-5
1.2.3
1.3
SYSTEM OPTIONS
1.3.1
OUTPUT BOARDS
Each input board can accept one or two output boards that can be used for water level
signalling, alarm or trip functions. Each output board provides four relay outputs or four optoisolated outputs. The first output board is fitted directly on top of the input board using three
nylon pillars. A second output board (when required) can be fitted on top of the first output
board using the same type of fixture. The various output boards are described in Chapter 3.
1.3.2
1.3.3
OPTION DETAILS
1. Relay Board 24680504 has 4 fully configurable relay outputs
Chapter 3a
2. Relay with Time Delay board 24680509 has 4 fully configurable relay outputs Chapter 3b
3. Opto-isolator board 24680505 has 4 fully configurable opto-isolated outputs Chapter 3c
4. Remote Display 24683B. Panel mounted DIN size 8 to 32 electrode display
Chapter 4
5. Remote Display 24683C Panel mounted large LED 8 to 32 electrode display Chapter 4
6. Remote Display 24683D Wall mounted splash proof version of 24683C
1-6
Chapter 4
24685033_DA
1.4
Existing System
Available Options
Description
2468 CA or
2468 CC
16 point EGS with
local display.
Single Power
Supply.
2468 CB or
2468 CD
32 point EGS with
local display.
Comments
Part No.
24680504C
24680509B
Opto-isolated
output board
24680505A
}
}
} Up to two boards (of any one
} type) can be fitted.
}
}
Remote display
unit
24683B, C, or D
Up to 6 can be used
Input board
upgrade (ac)
24680501C
Input board
upgrade (dc)
24680516B
24680504C
24680509B
Opto-isolated
output board
24680505A
}
}
} Up to four boards (of any one
} type) can be fitted.
}
}
Remote display
unit
24683B, C, or D
Up to 6 can be used
Note: If required, a 24680501C board can be fitted to a 2468CC (or a 24680516B board
can be fitted to a 2468CA) to upgrade to a 2468CE. The 2468CE is a 32 point
Electronic Gauging System (EGS) with one ac mains source power supply and one
24Vdc source power supply.
Table 1.1 - Upgrade paths and available options
24685034_DA
1-7
1-8
24685033_DA
2
2468CA & 2468CC
Single Power Supply Version
Contents
Page No.
2.1
2.2
2.3
2.3.4
2.4
2.5
24685033_CB
2-1
2.5.2
2.6
2.6.2
2.7
SPECIFICATION................................................................................... 2-24
Illustrations
Figure 2.1 - Outline drawing showing PCB layout and interconnections .............................. 2-4
Figure 2.2 - Installation diagram for the Hydrastep 2468 electronic gauging system unit .... 2-9
Figure 2.3- Enclosure cable layout for 16 electrode system .... Error! Bookmark not defined.
Figure 2.4: Voltage Selection (110V or 240V)..................................................................... 2-12
Figure 2.5- Location of display board links LK1 to LK5 & switch SW1 with configuration
details............................................................................................................. 2-17
Figure 2.6- Split pads SP1, SP2, SP5 & SP6 locations and settings.................................. 2-19
Tables
Table 2.1 - Analogue output configurations......................................................................... 2-15
Table 2.2 - Number of electrodes being displayed.............................................................. 2-18
Table 2.3 - Fault analysis/corrective action chart ................................................................ 2-20
2-2
24685033_CB
2.1
INTRODUCTION
This chapter introduces the single power supply version of the Hydrastep 2468 Electronic
Gauging System, its mechanical installation, system configuration, simple fault
analysis/corrective action capability and its specification.
2.2
Number of Cables
Required
10-16
The electrode cable is pre-formed for simple installation. The connections to the electrodes
are terminated on the connection stud of the electrode. Either core can be connected to the
electronic enclosure as the signal drive or return.
2.3
ELECTRONIC ENCLOSURE
The basic arrangement of boards in the electronic enclosure is as follows:
The input board supplies power to the system and to the input signal processing
circuits. This board may be PCB 24680501 for an ac (mains) input, or PCB 24680516
for a dc input. The board is mounted on the right hand side of the base plate.
A display board (PCB 24680515) contains the LED drive circuits for the two columns
(32 red LEDs and 32 green LEDs) and the system fault LEDs. The board is mounted
on the rear of the front panel, with the LEDs protruding through the front panel.
Up to two output boards, Relay Board (PCB 24680504), Relay with time delay Board
(24680509) or Opto-isolator Board (PCB 24680505) may be fitted. Output board
mounting pillars are fitted to the input board during manufacture to support the first
output board mounted.
Refer to Figure 2.1 for an annotated view of the internal layout of the unit.
24685033_CB
2-3
2-4
24685033_CB
2.3.1
2.3.2
24685033_CB
2-5
2.3.3
2-6
24685033_CB
2.3.4
PCB INTERCONNECTIONS
Signal interconnection between the input board and the display board is by ribbon cable.
The power supplies to the display board come from the input board via a 6-core cable.
Grommeted slots are provided in the base plate to guide the cables towards the hinge-side
of the enclosure case, thus minimising any cable strain when the enclosure lid is opened.
See Figure 2.1 on page 2-4 for layout details.
24685033_CB
2-7
2.4
INSTALLATION
This section deals with the mechanical installation of the electronic enclosure and the
electrical connections required for the basic system. Any installation dealing with the options
available for use on this version of the system are covered in Chapters 3 & 4.
Notes:
1. The electronic enclosure cover should not be removed or opened until the equipment is
ready for physical installation to its fixing point. Under no circumstances should the
electronic enclosure be left open unless internal work is actually in progress.
2. When working on a bench with the enclosure open, the lid should be supported in its
open position.
2.4.1
MECHANICAL INSTALLATION
The electronic enclosure must be sited within electrode cable length of the water column
fixture. The preferred site for the electronic enclosure is a wall or vertical bracket structure
where easy access is available for viewing and servicing. It is assumed that the water
column is fully installed.
The electronic enclosure is equipped with four welded feet, allowing it to be secured in a
vertical position. Using a template derived from the enclosure details given in Figure 2.2 (on
page 2-9), drill the necessary holes in the prepared surface. Secure the electronic enclosure
with M10 bolts or equivalent fixings.
The wiring enters the unit through a gland plate in the bottom of the enclosure. A blank
gland plate is provided to give users a choice in the type of glands and gland configuration
for the required system. Alternatively, cable entry can be made directly via trunking. Note
that the gland plate should be removed for fitting of the glands.
The cabling involved is:
2-8
24685033_CB
Figure 2.2 - Installation diagram for the Hydrastep 2468 electronic gauging system unit
24685033_CB
2-9
2.4.2
ELECTRICAL INSTALLATION
This section deals with the interconnection between the electrodes and the electronic
enclosure, the connection of the ac mains power supply to the electronic enclosure and the
analogue output connections from the electronic enclosure.
Electrode connections
2-10
Pin
Number
Electrode Drive
Electrode Pickup
Functional Earth
Electrode Drive
Electrode Pickup
Electrode Drive
Electrode Pickup
Functional Earth
Electrode Drive
10
Electrode Pickup
24685033_CB
2.4.2.2
Four 10-way plugs are provided on each PCB1 to terminate all the necessary connections
from the electrode cables.
1. Ensure power is removed from electronic enclosure and open the front cover.
2. Feed Cables 1 and 2 into the enclosure through its gland (if applicable). Prepare the
cable screens and terminate the screens at the gland plate.
3. Prepare the individual conductor lengths to suit their orientation in the terminal blocks
PL2, PL3, PL4 and PL5 on PCB 24680501. Ensure that the cables run along the sides
of the box at or below base plate level.
4. Fit the free sockets into the terminal blocks PL2 and PL3, PL4 and PL5.
5. Prepare the conductor core ends, fit the crimp terminals and connect the conductors to
their respective free sockets.
6. Ensure that both cables have a stress-free run inside the enclosure.
24685033_CB
2-11
Fuse
Fuse
(A) 240V
L N
L N
TRANSFORMER
TRANSFORMER
(B) 110V
2-12
24685033_CB
Plug PL1 on each input board is used for the analogue output. A 2-core screened cable is
required and is connected into a 2-way socket such that:
Gain access to each PCB 24680501 and connect the analogue output cable as follows:
1. Pass the analogue cable through its gland (if applicable) and into the enclosure.
2. Prepare the cable to give a stress-free run to PL1
on each PCB 24680501.
3. Screens must be terminated at the gland plate.
4. Prepare the conductor ends, fit the crimp
connectors and connect the cores into their
respective socket SK1 terminals.
5. Fit the socket into plug PL1 and check the cable
run.
24685033_CB
2-13
Gain access to PCB 24680515 and connect the FAULT output cable as follows:
1. Pass the cable through its gland (if applicable) and into the enclosure. Prepare and
terminate the cable screen at the gland plate.
2. Prepare the cable to give a stress-free run to PL4 on PCB 24680515.
3. Prepare the conductor ends and connect the conductors into their respective terminal.
Check the cable run and tie it to the present loom. Tighten the gland nut (if applicable)
and close the instrument front cover.
This concludes the electrical installation requirements for the basic instrument configuration.
Connections within the enclosure for the options available will be covered in the Installation
sections of the appropriate Chapter 3a (Relay Outputs), 3b (Relay with time delay Outputs),
3c (Opto-isolated Outputs) or Chapter 4 (Remote Display).
2-14
24685033_CB
2.5
SYSTEM CONFIGURATION
This section describes user configuration of the input and display boards.
2.5.1
Two sets of split pads are provided to select the required range (0-20mA or 4-20mA) and the
sense of the mA current output (normal sense as shown or in reverse, i.e. 4-20mA or 204mA).
To configure the analogue output, refer to Table 2.1 then:
1. Ensure the power supply is disconnected.
2. Locate the position of split pads SP1 and SP2 on the input board (PCB1) to select the
range of output current required. Table 2.1 shows how the pads should be bridged, or
left open-circuit, to select each range. The detail of PCB1 shows where SP1 and SP2
are located. Where a pad is to be left open-circuit, ensure that all solder is removed and
that the gap is clean.
3. Check the resistance across any altered pad for short- circuit or open-circuit, as
appropriate.
24685033_CB
2-15
2-16
24685033_CB
1. Disconnect the power supply. Gain access to the input PCB by opening the cover and
removing the option board.
2. Check split pads SP6 & SP7 on the input PCB are open-circuit and clean (this is the
default setting).
3. To change the electrode error threshold value or to disable the feature, bridge the split
pads SP6 or SF7 with solder as shown in the table above.
This concludes the configuration on the input boards.
2.5.2
Note: Links LK1, LK2 and LK4 must be fitted. Links LK3
and LK5 must NOT be fitted.
An invalid switch setting causes the main column LEDs
to display a chequered pattern
Figure 2.4- Location of display board links LK1 to LK5 & switch SW1 with
configuration details
24685033_CB
2-17
SWITCH SW1
NO. OF
ELECTRODES
LINKS
CHANNEL NO.
IN WATER
2&4
COLUMN
Off
Off
Off
On
Off
On
On
Off
10
Off
Off
On
Off
12
Off
On
Off
Off
14
Off
Off
Off
Off
16
Fitted
1. Disconnect the power supply. Gain access to PCB 24680515 by opening the cover.
2. Locate position of Number of Electrodes switch SW1 (see Figure 2.4).
3. Depending upon the number of electrodes being used, set the switch SW1 as shown in
Table 2.2. The switch positions in the example in Figure 2.4 are for a 12-electrode
system.
1. Disconnect the power supply. Gain access to PCB 24680515 by opening the cover.
2. Check split pads SP1 and SP2 on the PCB are open-circuit and clean (this is the normal
setting 0.6S/cm). (See Figure 2.5 on page 2-19)
3. If the preferred setting is 1.6S/cm (low temperature), bridge the split pads SP1 and SP2
with solder.
2-18
24685033_CB
Figure 2.5- Split pads SP1, SP2, SP5 & SP6 locations and settings
24685033_CB
2-19
2.6
Indication
Top and
bottom halves
of fault LED
illuminated
Water conductivity
greater than
approximately
104S/cm
Electrode connection
open-circuit or shortcircuit to earth
Affected electrode
indicates water
Incorrect wiring,
broken connection or
damaged cable
assembly
2-20
24685033_CB
Indication
Top and bottom
halves of Fault
LED illuminated
(contd.)
Fault(s)
Incorrect wiring,
broken connection
or damaged cable
assembly
Dirt on electrode
2.
3.
24685033_CB
2-21
Indication
Fault(s)
Chequered
pattern on RED
& GREEN LED
display
Wrong setting of
Number of
Electrodes switch
on display board
ON/OFF pattern
on RED &
GREEN LED
display
Wrong setting of
Number of
Electrodes switch
or linking on LK2,
LK3, LK4, LK5
incorrect on Display
Board
As above
Lower
electrodes not
displayed
As above
As above
As above
2.6.1
COMPONENT REPLACEMENT
The Hydrastep 2468CA contains no user-replaceable components. Board failure requires
the replacement of the entire printed circuit board.
WARNING
2-22
24685033_CB
2.6.2
Solartron
Mobrey
Part No.
Item Description
Solartron
Mobrey
Part No.
Electronic Enclosure
Input PCB assembly (2468CA)
Fuse link 200mA (T) ceramic
Fuse link 400mA (T) ceramic
24680501C
360190330
360190340
24680515B
399100380
399100390
24680516B
360190320
24682003A
24682011A
24680210A
Earth lead
24680216A
24682007A
24682002A
24682003A
24682004A
24682005A
Electrode Cables
Electrode cable (3 metre)
Electrode cable (10 metre)
Electrode cable (18 metre)
Electrode cable (30 metre)
24680204A
24680205A
24680206A
24680207A
24685033_CB
2-23
2.7
SPECIFICATION
Enclosure:
Weight:
12kg (26.4lb)
Operating temperature:
Relative humidity:
up to 100%
Location:
Indoor or outdoor
110V ac nominal
93.5V - 130V ac / 48Hz - 65Hz
240V ac nominal
187V - 256V ac / 48Hz - 65Hz
30VA maximum
24V dc nominal
20-40V dc negative earth or isolated
(absolute limits 19V-44V dc)
30W maximum
Installation category:
III
Outputs:
Analogue output:
Range:
Accuracy:
Drive capability:
2-24
30V dc
1A dc
1.1V dc maximum at 1A dc
1mA maximum at 30V dc
27 maximum
7 maximum
1000m (3280ft) maximum
Electrical connections:
24685033_CC
2-WD.1
2-WD.2
24685033_CC
24685033_CC
2-WD.3
2-WD.4
24685033_CC
24685033_CC
2-WD.5
2-WD.6
24685033_CC
24685033_CC
2-WD.7
2-WD.8
24685033_CC
3a
3a.2
3a.2.2
3a.2.3
3a.3
3a.3.2
24685033_CC
3a-1
3a.4
3a.5
SPECIFICATION................................................................................................3a-20
Illustrations
Figure 3a.1 - View of relay output board showing switch positions and output pin details ...... 6
Tables
Table 3a.1 - Electrode selections for relays RL1 to RL4 .....................................................3a-7
3a-2
24685033_CC
3A.2 INSTALLATION
This sub-section deals with the mechanical and electrical installation of the Relay Output
Board (PCB 24680504) option. In the rest of this chapter the relay output board title is
shortened to relay board.
24685033_CC
3a-3
This task can be performed on a mounted 2468 electronic enclosure or the enclosure can be
removed to a bench for the installation. Here it is assumed that the enclosure is in its normal
working location. The procedure for mounting the relay output board is as follows:
1.
Isolate the power supply from the 2468 electronic enclosure and open the instrument
front cover.
2.
If two output boards are to be fitted, make sure that the first output board to be fitted has
had its nylon spacers fitted before installation. Also ensure the first output board is fully
configured before fitting the second output board.
3.
Ease the pins of the Berg plug PL1 of the output board into the Berg socket SK1 on the
input board, checking that the mounting holes on the output board (the holes which are
not contained in white bordered areas) are aligned over the fitted spacers and gently
press the output board home until the spring-loaded spigot on each spacer is locked
firmly on to the output board.
Note:
When fitting a second output board, use the same procedure described in operation
3 but refer to the components, etc., on the mounted output board.
This concludes the mechanical installation of the output board(s) and should be followed by
the electrical installation. If the latter is not to be carried out in the immediate future then the
power supply can be reconnected.
3a-4
24685033_CC
24685033_CC
3a-5
SW6:
SW1 - SW4:
SW5:
Figure 3a.1 provides a view of the output board layout to highlight the positions of the various
configuration switches.
Figure 3a.1 - View of relay output board showing switch positions and output pin details
3a-6
24685033_CC
3a.3.1.2 Electrode/Relay Selection (Relays RL1, RL2, RL3 & RL4) - SW1 To SW4
Four identical switches are provided on the relay board for electrode selection. Any of the
electrodes, connected to the input board on which the relay board is mounted, can be
selected as the input for any of the relays.
With one input board installed, any electrode connected to the system can be used as the
source for any of the four relays. With two input boards installed, the relay board mounted
on the input board connected to the odd numbered electrodes, accepts inputs from the odd
numbered electrodes. Similarly, the relay board mounted on the input board connected to
the even numbered electrodes, accepts inputs from even numbered electrodes. Table 3a.1
details switch selection.
Switch SW1, SW2, SW3 or SW4
Settings for RL1 to RL4 respectively
Switch Contacts
Electrode Selection
One Input
Card
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
24685033_CC
OFF
3a-7
3a-8
24685033_CC
RL 2
RL 1
PL 2
To alarm
annunciator
PL 2
To alarm
annunciator
RL 2
PL 2
PL 2
To alarm annunciator
4
Odd fault relay
(RH input board)
4
Even fault relay
(LH input board)
RL 1
PL 2
PL 2
RL 1
1
2
RL 1
3
To alarm annunciator
Note:
24685033_CC
3a-9
3a.3.2.1 Philosophy
A requirement in regulations concerning steam raising plant is the provision of an automatic
low water level shut-down or trip device. In the 2468 Hydrastep the relay output board
provides the required output signals for such devices.
In practical applications of shut-down systems two factors must be considered, the
consequences of spurious trips and the non-availability of a trip when required, due to
protection system faults.
The following relay output circuits are specific to the 2468 Hydrastep Electronic Gauging
Systems.
3a-10
Before any relay interconnections are made it is necessary to fulfil any safety
regulations governing the plant shut-down procedures.
24685033_CC
PL 2
RL 1
2
3
4
PL 2
2
3
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
5
RL 2
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
PL 2
RL 1
2
3
4
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
24685033_CC
3a-11
PL 2
RL 1
PL 2
2
To alarm
annunciator
or tripping
device
3
4
To alarm
annunciator
or tripping
device
5
RL 2
5
RL 2
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
PL 2
RL 1
2
3
4
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
3a-12
24685033_CC
PL 2
PL 2
To alarm annunciator
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
PL 2
PL 2
RL 1
To alarm annunciator
Odd electrodes
(RH input board)
RL 1
Even electrodes
(LH input board)
PL 2
PL 2
1
2
2
3
To alarm annunciator
4
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
RL 1
PL 2
To alarm annunciator
PL 2
Odd electrodes
(RH input board)
Alarm off when contacts open
RL 1
Even electrodes
(LH input board)
(Switch SW5 is set to ES for low level alarms and set to EW for high level alarms)
24685033_CC
3a-13
PL 2
PL 2
To alarm annunciator
RL 1
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
PL 2
PL 2
3
To alarm annunciator
RL 1
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
PL 2
PL 2
To alarm annunciator
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
1
2
Odd electrodes
(RH input board)
PL 2
RL 1
PL 2
To alarm annunciator
RL 1
Even electrodes
(LH input board)
(Switch SW5 is set to ES for low level alarms and set to EW for high level alarms)
3a-14
24685033_CC
PL 2
RL 1
2
3
PL 2
2
4
To alarm
annunciator
or tripping
device
5
RL 2
5
RL 2
6
7
6
7
2
8
Even electrodes
(LH input board)
Odd electrodes
(RH input board)
PL 2
RL 1
2
3
3
4
5
RL 2
6
7
PL 2
RL 2
To alarm
annunciator
or tripping
device
6
7
2
8
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
24685033_CC
3a-15
PL 2
RL 1
2
3
PL 2
2
4
To alarm
annunciator
or tripping
device
5
RL 2
5
RL 2
6
7
6
7
2
8
Even electrodes
(LH input board)
Odd electrodes
(RH input board)
PL 2
RL 1
2
3
3
4
5
RL 2
6
7
PL 2
RL 2
To alarm
annunciator
or tripping
device
6
7
2
8
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3a-16
24685033_CC
PL 2
RL 1
2
3
PL 2
2
2
5
RL 2
5
RL 2
6
7
To alarm
annunciator
or tripping
device
6
7
RL 3
Even electrodes
(LH input board)
1
2
Odd electrodes
(RH input board)
4
PL 3
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
24685033_CC
3a-17
PL 2
RL 1
2
3
PL 2
2
2
5
RL 2
5
RL 2
6
7
To alarm
annunciator
or tripping
device
6
7
Even electrodes
(LH input board)
RL 3
1
2
3
Alarm off when contacts open
4
Odd electrodes
(RH input board)
PL 3
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
3a-18
24685033_CC
Item Description
Electrical:
Relay PCB assembly:
24685033_CC
Solartron
Mobrey Part
Number
Item Description
24680504C
Mechanical:
Spacer, nylon 15.9 LG
Washer, nylon
Nut, M4
351508100
351503100
Solartron
Mobrey Part
Number
412012080
411999910
410031020
3a-19
3A.5 SPECIFICATION
Outputs:
4 x Alarm/Trip Relays
ac
dc
Maximum voltage:
250V
125V
Maximum current:
8A
8A
1500VA
240W
65W
25W
Type N safety
( 30V)
( 60V)
( 125V)
5A at 12Vdc
100mA at 30Vdc
20mA at 125Vdc
3a-20
24685033_CC
3b
Delay Relay Output Board Option
Contents
Page No.
3b.1
3b.2
3b.2.2
3b.2.3
3b.3
3b.3.2
24685033_CD
3b-1
3b.4
3b.5
SPECIFICATION..................................................................................3b-22
Illustrations
Figure 3b.1 - View of relay output board showing switch positions and output pin details .......6
Figure 3b.2 - View of delay relay output board showing split pad positions............................11
Tables
Table 3b.1 - Electrode selections for relays RL1 to RL4 ...........................................................7
Table 3b.2 - Split pad functions on relay delay circuits ...........................................................10
3b-2
24685033_CD
3B.2 INSTALLATION
This sub-section deals with the mechanical and electrical installation of the Delay Relay
Output Board (PCB 24680504) option. In the rest of this chapter, the delay relay output
board title is shortened to output board.
24685033_CD
3b-3
3b.2.2.1 Fitting the Nylon Spacers to the Delay Relay Output Board
The spacers fit into the holes within the white bordered areas on
the output board, see Figure 3b.1 on page 3b-6.
1. Fit the nylon spacers into their prepared holes on the output
board and lock in position using the nylon washer and M4
nut,
see inset diagram.
2. Fit the output board on to the spacers and check for correct
alignment and adjust if necessary.
This task can be performed on a mounted 2468 electronic enclosure or the enclosure can be
removed to a bench for the installation. Here it is assumed that the enclosure is in its normal
working location. The procedure for mounting the delay relay output board is as follows:
1. Isolate the power supply from the 2468 electronic enclosure and open the instrument
front cover.
2. If two output boards are to be fitted, make sure that the first output board to be fitted has
had its nylon spacers fitted before installation. Also ensure the first output board is fully
configured before fitting the second output board.
3. Ease the pins of the Berg plug PL1 of the output board into the Berg socket SK1 on the
input board, checking that the mounting holes on the output board (the holes which are
not contained in white bordered areas) are aligned over the fitted spacers and gently
press the output board home until the spring-loaded spigot on each spacer is locked
firmly on to the output board.
Note:
When fitting a second output board, use the same procedure described in operation
3 but refer to the components, etc., on the mounted output board.
This concludes the mechanical installation of the output board(s) and should be followed by
the electrical installation. If the latter is not to be carried out in the immediate future then the
power supply can be reconnected.
3b-4
24685033_CD
24685033_CD
3b-5
Figure 3b.1 provides a view of the output board layout to highlight the positions of the various
configuration switches.
Figure 3b.1 - View of relay output board showing switch positions and output pin details
3b-6
24685033_CD
3b.3.1.2 Electrode/Relay Selection (Relays RL1, RL2, RL3 & RL4) - SW1 to SW4
Four identical switches are provided, one for each relay (but see SW6) each having four sets
of contacts. This allows coded selection for one of 16 electrodes for each switch and
therefore for each relay in the case of the single input card. When dual input cards are fitted,
odd numbered electrodes feed into one input card with the even numbered electrodes being
fed into the other input card. Each input card then offers any mounted relay output card the
choice from its electrode inputs, with the resultant selectivity as shown in Table 3b.1.
Electrode Selection
One Input
Card
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
3
5
7
9
Ii
13
15
17
19
21
23
25
27
29
31
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Example:
24685033_CD
OFF
3b-7
3b-8
24685033_CD
PL 2
1
RL 1
To alarm
annunciator
RL 2
PL 2
1
To alarm
annunciator
RL 2
PL 2
PL 2
RL 1
1
2
To alarm annunciator
PL 2
PL 2
3
4
RL 1
3
To alarm annunciator
Note:
24685033_CD
3b-9
3b-10
24685033_CD
Figure 3b.2 - View of delay relay output board showing split pad positions
Note: The following split pads
must be set as follows:
For Delayed Operation of the
Nominated Relay:
RL1
RL2
RL3
RL4
24685033_CD
RL1
RL2
RL3
RL4
3b-11
3b.3.2.1 Philosophy
A requirement in regulations concerning steam raising plant is the provision of an automatic
low water level shut-down or trip device. In the 2468 Hydrastep the relay output board
provides the required output signals for such devices.
In practical applications of shut-down systems two factors must be considered, the
consequences of spurious trips and the non-availability of a trip when required, due to
protection system faults.
The following relay output circuits are specific to the 2468 Hydrastep Level Indicator
versions.
3b-12
Before any relay interconnections are made it is necessary to fulfil any safety
regulations governing the plant shut-down procedures.
24685033_CD
PL 2
RL 1
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
PL 2
RL 1
2
3
4
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
24685033_CD
3b-13
PL 2
RL 1
2
To alarm
annunciator
or tripping
device
3
4
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
PL 2
RL 1
2
3
4
To alarm
annunciator
or tripping
device
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
3b-14
24685033_CD
PL 2
PL 2
RL 1
1
2
To alarm annunciator
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
PL 2
PL 2
To alarm annunciator
Odd electrodes
(RH input board)
RL 1
Even electrodes
(LH input board)
PL 2
PL 2
To alarm annunciator
RL 1
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
RL 1
Odd electrodes
(RH input board)
PL 2
To alarm annunciator
PL 2
RL 1
Even electrodes
(LH input board)
(Switch SW5 is set to ES for low level alarms and set to EW for high level alarms)
24685033_CD
3b-15
PL 2
PL 2
To alarm annunciator
Odd electrodes
(RH input board)
RL 1
Even electrodes
(LH input board)
PL 2
PL 2
RL 1
3
To alarm annunciator
4
Odd electrodes
(RH input board)
RL 1
4
Even electrodes
(LH input board)
PL 2
4
Odd electrodes
(RH input board)
RL 1
PL 2
To alarm annunciator
Even electrodes
(LH input board)
1
2
PL 2
RL 1
PL 2
To alarm annunciator
RL 1
Odd electrodes
(RH input board)
Alarm off when contacts open
Even electrodes
(LH input board)
(Switch SW5 is set to ES for low level alarms and set to EW for high level alarms)
3b-16
24685033_CD
PL 2
RL 1
2
3
2
4
To alarm
annunciator
or tripping
device
5
RL 2
PL 2
5
RL 2
6
7
6
7
2
8
Even electrodes
(LH input board)
Odd electrodes
(RH input board)
PL 2
RL 1
2
3
3
4
5
RL 2
6
7
PL 2
RL 2
To alarm
annunciator
or tripping
device
6
7
2
8
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
24685033_CD
3b-17
PL 2
RL 1
2
3
PL 2
2
4
To alarm
annunciator
or tripping
device
5
RL 2
5
RL 2
6
7
6
7
2
8
Even electrodes
(LH input board)
Odd electrodes
(RH input board)
PL 2
RL 1
2
3
3
4
5
RL 2
6
7
PL 2
RL 2
To alarm
annunciator
or tripping
device
6
7
2
8
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3b-18
24685033_CD
PL 2
RL 1
2
3
PL 2
2
2
5
RL 2
5
RL 2
6
7
To alarm
annunciator
or tripping
device
6
7
RL 3
Even electrodes
(LH input board)
1
2
Odd electrodes
(RH input board)
4
PL 3
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
24685033_CD
3b-19
PL 2
RL 1
2
3
PL 2
2
2
5
RL 2
5
RL 2
6
7
To alarm
annunciator
or tripping
device
6
7
Even electrodes
(LH input board)
RL 3
1
2
3
Alarm off when contacts open
4
Odd electrodes
(RH input board)
PL 3
(Switch SW5 is set to ES for low-level alarms and set to EW for high-level alarms)
3b-20
24685033_CD
Spacers will only be fitted on the output board if a second output board is to be fitted
or has been fitted.
The spacers are secured in their holes by nut and nylon washer. To carry out a spacer
replacement, the output board has to be removed from the input board. The procedure
adopted is:
WARNING
Solartron
Mobrey Part
Number
Electrical:
Delay relay PCB assembly:
24680509B
351508100
351503100
24685033_CD
Item Description
Mechanical:
Spacer, nylon 15.9 LG
Washer, nylon
Nut, M4
Solartron
Mobrey Part
Number
412012080
411999910
410031020
3b-21
3B.5 SPECIFICATION
Outputs:
4 x Alarm/Trip Relays
ac
dc
Maximum voltage:
250V
125V
Maximum current:
8A
8A
1500VA
240W
65W
25W
Type N safety
( 30V)
( 60V)
( 125V)
5A at 12Vdc
100mA at 30Vdc
20mA at 125Vdc
3b-22
24685033_CD
3c
2468 Opto-isolated Output Board Option
Contents
Page No.
3c.1
3c.2
3c.2.2
3c.2.3
3c.3
3c.3.2
24685033_CC
3c-1
3c.4
3c.5
Figure 3c.1 - View of opto-isolated board showing switch positions and output
pin details ......................................................................................................3c-6
Tables
Table 3c.1
3c-2
24685033_CC
The term energised is used to describe the ON (low resistance) state of the optoisolated output.
Each of the opto-isolated outputs can be energised by any one of up to 16 electrodes, with
an individual choice of being energised when its selected electrode is in steam or is in
water. Furthermore, opto-isolated output 1 can be used to monitor an electrode state or to
register an ALARM condition. When set to register the ALARM state, the opto-isolated
output is energised in the system normal state and de-energised when an ALARM
condition exists.
This option comes complete with the nylon spacers and two 8-way output sockets.
3C.2 INSTALLATION
This sub-section deals with the mechanical and electrical installation of the Opto-isolated
Output Board (PCB 24680505) option. In the rest of this chapter the opto-isolated output
board title is shortened to output board.
24685033_CC
3c-3
This task can be performed on a mounted 2468 electronic enclosure or the enclosure can be
removed to a bench for the installation. Here it is assumed that the enclosure is in its normal
working location. The procedure for mounting the output board is as follows:
1. Isolate the power supply from the 2468 electronic enclosure and open the instrument
front cover.
2. If two output boards are to be fitted, make sure that the first output board to be fitted has
had its nylon spacers fitted before installation. Also ensure the first output board is fully
configured before fitting the second output board.
3. Ease the pins of the Berg plug PL1 of the output board into the Berg socket SK1 on the
input board, checking that the mounting holes on the output board (the holes which are
not contained in white bordered areas) are aligned over the fitted spacers and gently
press the output board home until the spring-loaded spigot on each spacer is locked
firmly onto the output board.
Note:
When fitting a second output board, use the same procedure described in operation
3 but refer to the components, etc., on the mounted output board.
This concludes the mechanical installation of the output board(s) and should be followed by
the electrical installation. If the latter is not to be carried out in the immediate future then the
power supply can be reconnected.
3c-4
24685033_CC
24685033_CC
3c-5
SW6:
SW1 - SW4:
SW5:
Figure 3c.1 provides a view of the output board layout to highlight the positions of the various
configuration switches.
Figure 3c.1 - View of opto-isolated board showing switch positions and output pin details
3c-6
24685033_CC
Gain access to the printed circuit board assemblies inside the Hydrastep 2468 enclosure as
follows:
1. Isolate the 2468 electronics enclosure from its power supplies.
2. Gain access to the output PCB and set the relevant switches for the required function.
3c.3.1.1 Electrode/Opto-Output Selection (Opto-1, Opto-2, Opto-3 & Opto-4 Outputs) SW1 to SW4
Four identical switches are provided, one for each output (but see SW6) each having four
sets of contacts. This allows coded selection of any one of 16 electrodes for each switch in
the case of the single input card. When dual input cards are fitted, odd numbered electrodes
feed into one input card with the even numbered electrodes being fed into the other input
card. Each input card then offers any mounted output card the choice from its electrode
inputs, with the resultant selectivity as shown in Table 3c.1.
Switch SW1, SW2, SW3 or SW4 Settings for
Opto 1 to Opto 4 respectively
Switch Contacts
Electrode Selection
One Input
Card
On
On
On
On
Off
On
On
On
On
Off
On
On
Off
Off
On
On
On
On
Off
On
10
Off
On
Off
On
11
12
On
Off
Off
On
13
14
Off
Off
Off
On
15
16
On
On
On
Off
17
18
Off
On
On
Off
10
19
20
On
Off
On
Off
11
21
22
Off
Off
On
Off
12
23
24
On
On
Off
Off
13
25
26
Off
On
Off
Off
14
27
28
On
Off
Off
Off
15
29
30
Off
Off
Off
Off
16
31
32
Example:
24685033_CC
OFF
3c-7
3c-8
24685033_CC
1
- VE
2
3
Opto-output 1
TR4
To alarm
annunciator
+ VE
Note:
6
7
Opto-output 2
TR2
Opto-output 1
Odd Electrodes
(RH Input Board)
PL 2
+ VE
- VE
PL 2
Note:
TR4
Opto-output 2
Even Electrodes
(LH Input Board)
Note: Systems with a local display have an opto-isolated system fault available from the
display board.
24685033_CC
3c-9
3c.3.2.1 Philosophy
A requirement in regulations concerning steam raising plant is the provision of an automatic
low water level shut-down or trip device. In the 2468 Hydrastep the opto-isolated output
board provides the required output signals for such devices.
In practical applications of shut-down systems two factors must be considered, the
consequences of spurious trips and the non-availability of a trip when required, due to
protection system faults.
The following opto-isolated output (for brevity this output title will be shortened to optooutput) circuits are specific to the 2468 Hydrastep Level Indicator versions.
3c-10
Before any opto-output interconnections are made it is necessary to fulfil any safety
regulations governing the plant shutdown procedures.
24685033_CC
Case 1A - Opto-output circuit normally open circuit, short circuit either one to trip
PL 2
TR2
1
- VE
2
3
Opto-output 1
TR4
+ VE
Note:
6
7
Opto-output 2
To alarm
annunciator
or tripping
device
External power must
be applied as shown.
See specification for
power requirements
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
Case 1B - Opto-output circuit normally short circuit, open circuit either one to trip
PL 2
TR2
- VE
To alarm
annunciator
or tripping
device
3
Opto-output 1
TR4
5
6
7
Opto-output 2
+ VE
Note:
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
24685033_CC
3c-11
Case 2A - Opto-output circuit normally open circuit, short circuit both to trip
PL 2
TR2
- VE
To alarm
annunciator
or tripping
device
3
Opto-output 1
TR4
+ VE
Note:
6
7
Opto-output 2
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
Case 2B - Opto-output circuit normally short circuit, open circuit both to trip
PL 2
TR2
1
2
- VE
3
Opto-output 1
TR4
5
6
7
Opto-output 2
+ VE
Note:
To alarm
annunciator
or tripping
device
External power must
be applied as shown.
See specification for
power requirements
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
3c-12
24685033_CC
Case 3A - Opto-output circuit normally open circuit, short circuit either one to trip
To alarm annunciator or
tripping device
TR2
Opto-output 1
+ VE
PL 2
- VE
PL 2
Odd Electrodes
(RH Input Board)
Note:
TR2
Opto-output 1
Even Electrodes
(LH Input Board)
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
Case 3B - Opto-output circuit normally short circuit, open circuit either one to trip
To alarm annunciator or
tripping device
TR2
Opto-output 1
Odd Electrodes
(RH Input Board)
PL 2
+ VE
- VE
PL 2
Note:
TR2
Opto-output 1
Even Electrodes
(LH Input Board)
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
24685033_CC
3c-13
Case 4A - Opto-output circuit normally open circuit, short circuit both to trip
To alarm annunciator or
tripping device
TR2
Opto-output 1
+ VE
PL 2
- VE
PL 2
Odd Electrodes
(RH Input Board)
Note:
TR2
Opto-output 1
Even Electrodes
(LH Input Board)
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
Case 4B - Opto-output circuit normally short circuit, open circuit both to trip
To alarm annunciator or
tripping device
TR2
Opto-output 1
Odd Electrodes
(RH Input Board)
PL 2
+ VE
- VE
PL 2
Note:
TR2
Opto-output 1
Even Electrodes
(LH Input Board)
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
3c-14
24685033_CC
Case 5A - Opto-output circuit normally open circuit, short circuit one pair to trip
PL 2
PL 2
TR2
Opto-output 1
TR4
TR2
3
Opto-output 1
4
1
Opto-output 2
TR4
Odd Electrodes
(RH Input Board)
To alarm
annunciator
or tripping
device
5
6
Opto-output 2
+ VE
Note:
- VE
Even Electrodes
(LH Input Board)
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
Case 5B - Opto-output circuit normally short circuit, open circuit one in each
pair to trip
PL 2
PL 2
TR2
Opto-output 1
TR4
Opto-output 2
Odd Electrodes
(RH Input Board)
4
1
TR2
Opto-output 1
TR4
4
2
7
Opto-output 2
+ VE
To alarm
annunciator
or tripping
device
Note:
- VE
Even Electrodes
(LH Input Board)
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
24685033_CC
3c-15
Inputs from electrodes 1 & 2 are applied to two separate opto-outputs on their
respective boards.
Case 6A - Opto-output circuit normally open circuit, short circuit two to trip
PL 2
PL 2
TR2
Opto-output 1
TR4
Opto-output 2
TR6
TR2
Opto-output 1
TR4
Note:
4
2
7
Opto-output 2
+ VE
To alarm
annunciator
or tripping
device
- VE
Even Electrodes
(LH Input Board)
1
2
3
Opto-output 3
Odd Electrodes
(RH Input Board)
4
PL 3
(Switch SW5 is set to S for low level alarms and set to W for high level alarms)
3c-16
24685033_CC
PL 2
PL 2
TR2
Opto-output 1
TR4
TR2
3
Opto-output 1
TR4
Note:
4
2
7
Opto-output 2
+ VE
To alarm
annunciator
or tripping
device
Opto-output 2
TR6
- VE
Even Electrodes
(LH Input Board)
1
2
3
Opto-output 3
Odd Electrodes
(RH Input Board)
4
PL 3
(Switch SW5 is set to W for low level alarms and set to S for high level alarms)
24685033_CC
3c-17
Spacers will only be fitted on the output board if a second output board is to be fitted
or has been fitted.
The spacers are secured in their holes by nut and nylon washer. To carry out a spacer
replacement, the output board has to be removed from the input board. The procedure
adopted is:
WARNING
3c-18
Electrical:
Delay relay PCB assembly:
Solartron
Mobrey Part
Number
Item Description
Solartron
Mobrey Part
Number
24680505A
Mechanical:
Spacer, nylon 15.9 LG
412012080
351508100
Washer, nylon
411999910
351503100
Nut, M4
410031020
24685033_CC
3C.5 SPECIFICATION
Outputs:
30V dc
1A
1.1V maximum at 1A
1mA at 30V dc
24685033_CC
3c-19
3c-20
24685033_CC
4
Remote Display Options 24683B, C, & D
Contents
Page No.
4.1
4.2
4.3
4.4
INSTALLING THE 24683B AND 24683C PANEL MOUNTED UNITS ..... 4-6
INSTALLING THE 24683D WALL MOUNTED UNIT ................................ 4-6
4.5
4.6
4.7
4.8
SPECIFICATION................................................................................... 4-16
24685033_CC
4-1
Illustrations
Figure 4.1 - Location of link headers for selecting the display mode .................................... 4-4
Figure 4.2 - Interconnection cable for a single remote display.............................................. 4-7
Figure 4.3 - Star and daisy chain connections of remote displays........................................ 4-8
Figure 4.4 - Star connection example for two remote displays ............................................. 4-9
Figure 4.5 - Daisy chain connection example for two remote displays ............................... 4-10
Figure 4.6 - Cable connection details for the remote display .............................................. 4-11
Tables
Table 4.1 - Fault Analysis and Correction Chart ................................................................. 4-12
Table 4.2 - Remote Display Replacement Parts ................................................................. 4-15
4-2
24685033_CC
4.1
24685033_CC
4-3
4.2
CONFIGURATION
All remote displays can be configured for operation with 8 to 16 electrodes (two LEDs per
electrode) or 18 to 32 electrodes (one LED per electrode). Remote displays are supplied
ready for operation with 8 to 16 electrodes. If a remote display is required to operate with 18
to 32 electrodes then it must be reconfigured. The procedure for each type of remote display
is described below.
4.2.1
2.
Undo the six screws securing the side panel and remove the panel.
3.
Carefully remove the link headers from sockets LK2 and LK4 on the decoding PCB, by
easing them out with a suitable flat-bladed screwdriver. (See Figure 4.1)
4.
Fit the link headers, removed in step 3, into sockets LK1 and LK3.
5.
Note: This figure shows the layout of the decoding pcb fitted to the 24683C and 24683D Remote
Displays. The layout of the decoding pcb in the 24683B Remote Display is slightly different, but the
arrangement of links LK1-LK4 is the same.
LK1
LK2
18-32
8-16
LK3
LK4
18-32
8-16
Figure 4.1 - Location of link headers for selecting the display mode
4-4
24685033_CC
4.2.2
4.2.3
1.
Undo the four screws securing the rear panel and remove the panel.
2.
Withdraw the decoding PCB from the rear of the display unit. (Some force may be
necessary, initially, to disengage the decoding PCB from the LED PCB.)
3.
Carefully remove the link headers from sockets LK2 and LK4 on the decoding PCB, by
easing them out with a suitable flat-bladed screwdriver. (See Figure 4.1 on page 4-4)
4.
Fit the link headers, removed in step 3, into sockets LK1 and LK3.
5.
Undo the four screws securing the transparent cover and remove the cover.
2.
Undo the four screws securing the front panel and lay the panel carefully away from the
top of the box, still connected by the ribbon cable.
3.
Carefully remove the link headers from sockets LK2 and LK4 on the decoding PCB, by
easing them out with a suitable flat-bladed screwdriver. (See Figure 4.1 on page 4-4)
4.
Fit the link headers, removed in step 3, into sockets LK1 and LK3.
5.
24685033_CC
4-5
4.3
MECHANICAL INSTALLATION
Of the three types of remote display units, types 24683B and 24683C are intended for panel
mounting and type 24683D is intended for wall mounting. The installation procedures for
panel and wall mounting are described below.
4.3.1
Aperture:
Ensure that the panel on which the remote display is to be fitted provides easy access
to the electrical connections and is sited in a good viewing position.
2.
Cut an aperture in the panel to the dimensions given above and remove any burrs.
3.
Remove the clamps (if fitted) from the remote display unit and fit the unit into the
aperture from the front of the panel.
4.
Refit the clamps to the display unit and secure the unit to the panel.
The two clamps on the 24683B are held in place by knurled nuts. Tighten the nuts so that
the clamps press firmly against the panel to hold the unit in place.
The two clamps on the 24683C each clip onto two metal studs on the case of the unit.
Adjust the clamps from the rear of the unit with a suitable flat bladed screwdriver. Tighten
the clamps until they press firmly against the panel to hold the unit in place.
4.3.2
4-6
1.
Place the unit against the surface to which it is to be fixed and mark the positions of the
fixing points. These should be positioned on centers 190mm apart horizontally and
305mm apart vertically. Install suitable fixings and secure the unit to the wall.
2.
Remove the four screws securing the clear cover of the unit and place the cover
carefully to one side.
3.
Remove the four screws securing the front panel of the unit and lay the panel, still
attached by its ribbon cable, on top of the case.
4.
Loosen the cable gland nuts, pass the cables through the glands, prepare the cable
terminations, and fit the cable to the terminal block. (See Section 4.4.4 for details.)
5.
Ensure that the cables are unstrained within the unit, tighten the cable glands, and refit
the front panel and clear cover.
24685033_CC
4.4
ELECTRICAL INSTALLATION
Up to six remote displays may be driven by the Hydrastep 2468 unit. One remote display
can be powered from the main unit, but all the others must have a local supply. A remote
display has a dual serial data input and a dual power input. When the remote display is
powered from the main unit an eight-core cable is required to connect the two units. When a
remote display is locally powered, however, a six-core cable will suffice. See the example in
Figure 4.4: remote display unit 1 is powered from the main unit and uses an eight-core cable;
remote display unit 2 is locally powered and uses a six-core cable. All cables must be
screened to comply with the EMC directive.
For remote displays powered from the main unit the loop resistance of the power conductors
must be less than 27 ohms for an ac powered unit or 7 ohms for a dc unit. To provide for
cable runs of up to 1000 metres, without the use of heavy cables, the main unit and the
remote display unit each have internally linked multiple terminals for the power and ground
connections. This allows the power and ground lines to be doubled to reduce the loop
resistance.
Hydrastep 2468
Remote Display
Display Board
Power +ve
PL3
Power ve
Alternative supply
from local PSU: 20V
to 54V at 240mA
Power +ve
PL7
Power ve
TB1
24685033_CC
4-7
4.4.1
RDU 1
RDU 1
RDU 2
RDU 3
RDU 2
RDU 4
RDU 3
Star
2468
2468
Daisy
Chain
RDU 5
RDU 4
RDU 5
RDU 6
RDU 6
4-8
24685033_CC
4.4.2
TB1
1
HINGE
4
5
6
7
8
9
10
PL3
Signal
PL7
Power Power
0V
+ve
Signal
11
Power Power
0V
+ve
12
13
14
14
+ +
+ +
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
15
16
12
17
3
2
5
4
7
6
Screens terminated
at gland plate
10
9
12
11
14
13
18
19
20
Cable screens at
remote display
connected together,
but not connected to
ground.
TB1
1
System 0V
reference
3
4
5
6
7
8
9
10
11
12
13
14
15
16
13
17
Local P.S.
18
19
11
20
10
+ve
0V
24683BB
REMOTE DISPLAY UNIT 2
(Rear View)
20V - 54V dc
240mA
24685033_CC
4-9
4.4.3
TB1
H ING E
10
11
7
8
9
10
P L3
S ign a l
P owe r
0V
11
P L7
P owe r
+ ve
S ign a l
P owe r P owe r
0V
+ ve
+ +
+ +
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
3
2
13
14
7
6
12
15
12
16
17
13
18
14
19
20
C able screens at
rem ote display
connected together,
but not connected
to ground.
term ination
resistor
TB1
1
10
System 0V
reference
3
4
5
11
6
7
8
9
10
11
12
13
14
15
16
12
17
Local P.S.
18
19
13
20
14
+ve
0V
24683BB
R EM O T E D ISPLAY UN IT 2
(R ear View)
term ination
resistor
20V - 54V dc
240m A
Figure 4.5 - Daisy chain connection example for two remote displays
4-10
24685033_CC
4.4.4
Gain access to the remote display terminal block. On the 24683B and 24683C remote
displays the terminal block is located at the rear of the unit. The terminal block of the
24683D remote display is located within the unit and must be accessed as described in
Section 4.3.2.
2.
Prepare the cable ends and fit identity sleeves to the leads.
3.
Fit the leads into the respective terminals (see Figure 4.6 for details) and tighten the
terminal screws. The interconnections for multiple remote displays are shown in the
examples in Figure 4.4 and Figure 4.5.
4.
Ensure a stress-free exit for the cable, from the panel, by providing any necessary cable
support.
Terminal
Service
1&3
2&4
5, 6 & 7
8&9
12 & 13
14, 15 & 16
17 & 19
18 & 20
10 & 11
Earth
4.4.5
Ensure a stress-free cable run between the remote display unit and Hydrastep 2468.
2.
Gain access to the display board in the 2468. The cable from the remote display
requires connecting to connectors PL3 and PL7 on PCB 24680515.
3.
Enter the cable through the gland port in the 2468 enclosure (if this is applicable) and
ensure a stress-free run inside the enclosure.
4.
Prepare the cable ends, fit identity sleeves on the leads and connect them to their
respective terminals. See the example in Figure 4.5 on page 4-10.
5.
24685033_CC
4-11
4.5
SYSTEM OPERATION
When the system is brought on line check for complete agreement between the remote
display and the Hydrastep level indicator display.
4.6
Fault
Loss of power to
remote display
unit.
No display of EVEN
LEDs (including top
half of fault LED)
Loss of power to
remote display
unit.
4-12
24685033_CC
Indication
Bottom half of
fault LED
illuminated and
ODD LEDs
flashing at 1Hz, or
ODD LEDs off.
Fault
Power present,
but loss of serial
data.
Bottom half of
fault LED
illuminated and
EVEN LEDs
flashing at 1Hz, or
EVEN LEDs off.
Power present,
but loss of serial
data.
24685033_CC
4-13
Indication
Flickering
Display
Fault
Corruption of
signal data
Chequered
pattern on red
and green LED
display
Wrong setting
of Number of
Electrodes
switch on 2468
display board.
On/off pattern on
red and green
LEDs.
Wrong setting
of Number of
Electrodes
switch on 2468
display board,
or wrong setting
of links LK1,
LK2, LK3 and
LK4 on the
24683BB
decoding pcb.
As above.
If a fault is not found, check the link setting on the 24683BB
and reset the links if necessary.
Indication not
displayed for
lower electrodes.
As above.
As above.
Each electrode
represented by
only one LED
when 16 or less
electrodes are
used.
As above.
As above.
LEDs display an
irregular
red/green
pattern.
As above.
As above.
4-14
24685033_CC
4.7
COMPONENT REPLACEMENT
Hydrastep remote display units contain no user-replaceable electronic components. Board
failure requires the faulty PCB to be removed and returned for service and a serviceable
PCB to be fitted in its place. A list of replacement parts is given in Table 4.2.
The procedure for replacing a PCB in a remote display is:
1.
2.
Gain access to the interior of the remote display unit. The method depends on the type
of remote display being serviced:
For a 24683B: Remove the cables from terminal block TB1 at the rear of the unit.
Remove the clamps. Withdraw the unit from the front of the mounting panel and lay on
a clean surface. Pull off the bezel from the unit front panel, unscrew and remove the
side panel, and lift off the front and rear panels, and use a suitable flat bladed
screwdriver to prise apart the PCB interconnecting edge connectors. Both PCBs can
now be removed from their securing slots in the unit case.
For a 24683C: Remove the cables from terminal block TB1 at the rear of the unit.
Remove the clamps. Withdraw the unit from the front of the mounting panel and lay on
a clean surface. Remove the front and rear panels. Both PCBs can now be removed
from the unit case.
For a 24683D: Remove the unit clear cover and the front panel. The LED display and
the decode PCB can now be accessed and it can easily be seen which screws and
connections it is necessary to remove in order to remove the faulty board(s).
3.
Fit the serviceable PCB(s), following the reverse order to that given in step 2.
Item
Solartron Mobrey
Part No.
For 24683B:
LED PCB assembly
Decode PCB assembly
Header (for 8-16, 18-32 electrode operation)
Holding bar (two off, with two knurled knobs)
24680514A
24680513B
399100390
460202260
For 24683C:
LED PCB assembly
Decode PCB assembly
Header (for 8-16, 18-32 electrode operation)
24680519A
24680520A
460202260
For 24683D
LED PCB assembly
Decode PCB assembly
Header (for 8-16, 18-32 electrode operation)
24680521A
24680522A
460202260
24685033_CC
4-15
4.8
SPECIFICATION
REMOTE DISPLAY UNITS
INDICATION
CASE STYLE
DIMENSIONS
PANEL CUT-OUT
24683B: 139mm67mm
24683C: 186mm92mm (7.323.62)
POWER SUPPLY
TERMINALS
Screw-clamp
CABLES
Note: The following cables fulfil the minimum requirements. Heavier cables may be used.
Maximum gauge accepted by connectors is 16AWG (1. 5mm2).
2
* The main Hydrastep 2468 unit is approved for operation in a hazardous environment to ExN11C T4.
Compliance with this approval requires that armoured cable is used to connect a remote display to the main unit.
A remote display must not be used in a hazardous environment.
4-16
24685033_CC
Part No:
24675030
Status:
Issue:
Authors:
Date:
Copyright 2000
Solartron Mobrey
All rights reserved
Solartron Mobrey pursues a policy of continuous development and product improvement. The specification in this
document may therefore be changed without notice.
To the best of our knowledge, the information contained in this document is accurate and Solartron Mobrey cannot be
held responsible for any errors, omissions or other misinformation contained herein. No part of this document may be
photocopied or reproduced without prior written consent of Solartron Mobrey.
Solartron Inc.
Email: sales@solartron.com
Web: http://www.solartron.com
For details of our agents in other countries, please contact our Slough, UK office.
Pt.2-2
24675030_AK
Appendix
Appendix A Approval Certificates contains copies of certificates complying with the
necessary safety approvals for the Hydrastep system.
CAUTION: The procedures described in this manual do not overrule any mandatory
regulations and procedures applied on site regarding the installation, testing and
safety precautions affecting the specific Hydrastep System.
The objective of this manual is to describe various procedures involved in the installation of
the water columns, their attachments and the electrodes used in determining the level of
water in the column as required by the following Hydrastep Systems.
Commissioning the water column and limited component repair procedures on the system
pipework are also covered.
24675030_AK
Pt.2-3
Pt.2-4
24675030_AK
REMINDER
ELECTRODE INSTALLATION
THREADED ELECTRODE(S), PART Nos. 4596006 & 456008
MAKE SURE THAT THE COMPRESSION GASKET IS REGISTERED IN THE
PROBE RECESS PRIOR TO TIGHTENING THE ELECTRODE. THIS CENTRES
THE GASKET TO THE PROBE.
GASKET
ELECTRODE
SEAT SURFACE
COLUMN BODY
CORRECT
24675030_AK
INCORRECT
Pt.2-5
Pt.2-6
24675030_AK
NOTICE
24675030_AK
Pt.2-7
Pt.2-8
24675030_AK
24675030_AK
Chapter 1
General Introduction
Chapter 2
Installation Procedures
Chapter 3
Chapter 4
Unit Description
Chapter 5
Appendix A
Approval Certificates
Pt.2-9
Pt.2-10
24675030_AK
General Introduction
1
General Introduction
1.1
1.2
Figure 1.1 - Schematic of high pressure resistance measuring cell and electrodes............. 1-3
Figure 1.2 - Low pressure water column (120bar, 1740psi).................................................. 1-4
Figure 1.3 - High pressure water column (210 bar, 3045psi and 300 bar, 4350psi)............. 1-5
24675030_AK
1-1
General Introduction
1-2
24675030_AK
1.1
General Introduction
PRINCIPLE OF OPERATION
The Hydrastep systems have been designed as electronic alternatives to conventional visual
water gauges on boilers, giving more reliable and safer water level indication.
The system is based on the significant differences in resistivities of water and steam over
the range 100C (212F) to 370C (698F). (Series 3 super-critical components are used up
to 560C, 1040F)
A vertical row of electrodes is installed in the water column which forms a side arm attached
to a boiler arid aligned, typically, such that an equal number of electrodes appear above and
below the normal water level, see Figure 1.1. The resistance measurement is made
between the insulated tip of the electrode and the wall of the column. The cell constant,
defining the actual resistance measured, is determined by the length and the diameter of the
electrode tip and the water column bore. In practice, the cell constant is chosen so that the
resistance in water is less than 100k ohms, with a consequent resistance in steam of greater
than 10M ohms.
Since the resistivities of water and steam are substantially different, the system is simple
and requires minimum setting up adjustments. It is not critical in terms of power supply
variations, ambient temperature changes, etc., resulting in a highly reliable system.
Figure 1.1 shows the resistance-measuring cell complete with installed electrode. Figure 1.2
and Figure 1.3 show examples of the Low Pressure (120bar, 1740p.s.i.) and the Series 3
and Super 3 High Pressure (210bar, 3045p.s.i. & 300bar, 4350p.s.i.) Water Columns
respectively.
1.2
Figure 1.1 - Schematic of high pressure resistance measuring cell and electrodes
24675030_AK
1-3
General Introduction
1-4
24675030_AK
General Introduction
Figure 1.3 - High pressure water column (210 bar, 3045psi and 300 bar, 4350psi)
24675030_AK
1-5
General Introduction
1-6
24675030_AK
Installation Procedures
2
Installation Procedures
Contents
Page No.
2.1
SCOPE OF PROCEDURES.....................................................................2-3
2.2
STORAGE................................................................................................2-3
2.2.1
2.2.2
2.2.3
2.2.4
2.3
2.4
Illustrations
Figure 2.1 - Universal weld profile ........................................................................................ 2-5
Figure 2.2 - Typical water column installation ...................................................................... 2-7
Figure 2.3 - Typical water column suspension ..................................................................... 2-8
24675030_AK
2-1
Installation Procedures
2-2
24675030_AK
Installation Procedures
2.1
SCOPE OF PROCEDURES
The procedures apply to the Hydrastep Boiler Drum Water Level Equipment supplied by
Solartron-Mobrey, who are responsible, under their supply contract, for delivery of all items of
the above equipment listed in the delivery schedules.
Solartron-Mobrey are not responsible for handling, storage, installation and protection of
equipment on-site. However, the procedures define the requirements for these activities
which must be complied with to allow Solartron-Mobrey to meet their contractual obligations
for the efficient performance of equipment supplied by them.
The items of equipment are listed in detail on the Packing Note that is issued with the
equipment to the site.
2.2
STORAGE
2.2.1
AMBIENT CONDITIONS
The storage area must be dry, dust-free and under cover. Storage conditions should be
controlled within the temperature range of 10C to 40C (50F to 104F) with a maximum of
80% R.H.
2.2.2
PHYSICAL PROTECTION
The equipment shall be stored, where possible, in the original or robust packages to prevent
accidental mechanical damage. The equipment shall be stored on shelving or racks above
ground level as further protection from mechanical damage and to eliminate dampness.
2.2.3
INSPECTION
If the equipment is to be stored for a long period, suitable access is to be provided so that
regular inspection can take place. These inspections should check for signs of physical
deterioration, and should take place at least every three months.
2.2.4
HANDLING PRECAUTIONS
The water columns are heavy and lifting equipment suitable for hoisting up to 50kg should be
used, both for inspection and carriage. The electrodes should be handled with considerable
care, both for inspection and installation. The electronic units should be protected from
electrostatic damage, induced via signal input terminals.
2.3
24675030_AK
2-3
Installation Procedures
The water column is delivered along with the correct number of electrodes of the relevant
pressure type (high or low) and complete with gaskets or ferrules and fixing nuts, where
applicable. The electrodes should only be fitted to the column after all erection and electrical
work is completed and the water column is ready to be commissioned.
Caution: It is essential that the electrodes are NOT fitted until the acid and steam purging
of the boiler drum has been completed. However, if it is essential that the
Hydrastep be used to gauge the water level during acid cleaning, a sacrificial set
of electrodes must be used for this task with a new set of electrodes provided for
installation before normal operation is started. Sacrificial electrodes should be
discarded.
The water column is provided with a lifting eye at its upper end to be used for support from
the local site superstructure.
Before fitting the water column, the following points must be checked:
a) Ensure that access to work on this part of the plant is clear and that the Column isolating
Valves have been fitted to the Steam and the Water connections on the Drum and are
ready to have the water column welded to them. All steam isolation valves should be
fitted with their spindles horizontal.
b) Check that items of hardware required for supporting the water column are available and
that the suspension points on the superstructure have been installed.
c) Water columns are normally supplied with a lifting/support eye, but where this is not the
case, alternative support must be provided.
d) The water column and associated pipework are secured to resist sympathetic vibrations
from surrounding plant.
e) Ensure that the relevant installation diagrams, support services including that of an
approved welder, and suitable welding plant are available.
Note:
2-4
All joints in pipework must be welded, tested and inspected in accordance with
the approved welding procedure documents. Ideally, this should be to ASME B &
PVC Section IX Welding Qualifications, but Local Regulations may otherwise
apply. To minimise errors due to temperature difference between the water in the
boiler drum and the water in the Hydrastep column, the length of the pipework
between the drum and the Hydrastep column should not exceed 2 metres. Paths
should be as straight and direct as possible.
24675030_AK
Installation Procedures
45
1.5mm
Material:
Size:
Material:
Size:
Material:
Size:
SA106B
1" N.B, Sch. 160 pipe dim.
SA479 - 316
1" N.B, Sch. XXS PPE
SA106B
1" N.B, Sch. 80 pipe dim.
24675030_AK
2-5
Installation Procedures
The water connection to the water column must be fully insulated by lagging. The steam
connection must also be lagged, but a minimum length of 0.5 metre of the steam leg must be
left unlagged where the steam leg joins the water column (see Figure 2.2).
Lagging the water column will reduce the density error, provided that 0.5 metre minimum of
the steam leg is left unlagged.
If errors in the water level indication are observed, it may be necessary to lag the water
column, either up to NWL or for its full length, depending on the ambient conditions
prevailing at the site. Suitable lagging, part number 450601450, is available from SolartronMobrey
When the installation of the water column has been completed, precautions must be taken to
protect it against damage during the installation of adjacent plant and pipework.
Note:
Caution: If there is any possibility of the ambient temperature at drum level falling below
zero C for any period when the boiler is not operational, it is ESSENTIAL that the
water column is isolated, drained and vented to prevent ice-expansion damage to
the electrodes in the column. Ice-expansion damage can also affect adjacent
valves.
For instructions regarding the assembly of electrodes in the water column, see Chapter 3,
sub-section 3.1.4 (low pressure electrodes) and 3.1.5 (high pressure electrodes).
2.4
2-6
24675030_AK
Installation Procedures
Figure 2.2 - Typical water column installation, showing optional column lagging.
24675030_AK
2-7
Installation Procedures
2-8
24675030_AK
BACKGROUND .......................................................................................3-3
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.2
Note:
THERE IS NO NEED TO BLOW WATER COLUMN DOWN WHEN COMMISSIONING.
THE SYSTEM CONTINUOUSLY FLUSHES THE WATER COLUMN.
24675030_AJ
3-1
3-2
24675030_AJ
3.1
BACKGROUND
With any steam/water detection gauge, a partial blockage or leak within the pressurised
system may result in incorrect water level indication. The Hydrastep water column design is
such that density errors in water level indication (due to the water temperature in the column
being lower than the water temperature in the boiler drum) are minimised for the
temperatures and pressures specified. This is achieved by stimulating condensate flow in
the upper part of the column by omitting lagging on the column steam pipe. The flow of
condensate maintains the temperature of the water column close to that of the boiler drum.
Caution: If a serious blow occurs, immediate attention is required. Ensure that the
column or manifold is VALVED OFF AS SOON AS POSSIBLE otherwise any
resulting electrode seat erosion may require the removal of the column or
manifold for re-machining of the ports. Site machining of the water column is
possible and satisfactory results can usually be obtained (for small leak damage).
3.1.1
3.1.2
SAFETY PRECAUTIONS
a)
Ensure that tripping, where fitted, is disabled and that the operators are briefed to
expect erroneous indications or alarms.
b)
Ensure that you know the valve positions and other procedures BEFORE working on the
water column.
c)
Allow the water column to cool before changing electrodes and check for signs of steam
at the drain to ensure complete isolation.
d)
e)
f)
b)
Where the column is connected to a closed drain, open the drain valve and, when the
pressure equalises, close the drain valve.
c)
Check for no-pressure condition of water column. A failure to cool and a re-filling of the
water column would indicate a pressure condition. Alternatively, carefully unscrew the
first electrode and look out for the presence of steam.
Warning: Great care is required during the check on the first electrode.
Where a separate atmospheric drain is used, open the drain valve and leave it open.
d)
24675030_AJ
3-3
3.1.3
3.1.3.1
Failure to remove the old washer on a previous occasion before inserting the
replacement washer and electrode.
b)
c)
Failing to ensure that the land and the recess in the electrode port were clean and
undistorted at the last inspection.
Note: When installing low pressure electrodes, ensure that the threads in the electrode port
are free of loose particles. Lightly coat the electrode threads with anti-seize
compound (Part No. 830007220). Insert the electrode, ensuring that the new gasket
is centred in the electrode groove, and tighten the electrode with a torque wrench to
40 lbft (55Nm). After 15 minutes, re-tighten the electrode with the torque wrench set
to 40 lbft (55Nm). The maximum torque is 50 lbft (68Nm) so DO NOT OVERTIGHTEN.
Where scoring or erosion of the electrode port seat has occurred in the water column, the
seat can be re-cut to acceptable standards using Service Tool Part No. 24579AA.
3.1.3.2
3-4
24675030_AJ
3.1.3.3
Ensure the electrode is clean and the electrode port bore is clean and free of debris.
b)
Lightly coat the column port thread with anti-seize compound (Part No.: 830007220).
c)
Assemble the electrode to the column port and tighten the electrode nut until the
electrode will not rotate in its seat.
d)
Finally, tighten the electrode nut a further /8 to turn to complete the procedure.
NOTE: The final /8 to turn corresponds to a torque level of between 28lbft (35Nm)
1
and 47lbft (60Nm). /8 turn is the recommended tightening condition. turn is the
maximum allowable, and the tightening torque used must be the minimum to achieve
this. Failure to comply with this limitation may cause damage to the port or to the
electrode, due to over tightening.
If necessary, where the sealing surfaces can be recovered by simple cleaning practices, the
old electrode can be refitted and tightened to within the maximum torque value given and the
system pressure tested. However, it is recommended that the best solution to minimise the
system down time is to fit a new electrode.
Where scoring or erosion of the sealing seat has occurred in the water column port, this can
be re-cut to acceptable standards using the Service Tool 246791AA.
3.1.4
Remove the electrode cover guard, taking care to avoid knocking the electrodes.
Note: Remove only one electrode at a time (avoids risk of incorrect reconnection).
b)
Disconnect the leads, extract the electrode and the gasket carefully without damage to
the seat face.
c)
Inspect the column seat, making sure that it is free of loose particles and is not pitted or
corroded.
d)
Carefully unpack the new electrode and check that there is no damage to the ceramic
insulators or to the sealing gasket.
e)
Assemble the new electrode to the water column as detailed in sub-paragraph 3.1.3 for
low pressure electrodes, paragraph d.
f)
Refit the electrical lead(s) and guard. Recommission as detailed later in this Chapter.
24675030_AJ
3-5
3.1.5
Remove the electrode cover guard, taking care to avoid knocking the electrodes.
Note: Remove only one electrode at a time (avoids risk of incorrect reconnection)
b)
Disconnect the leads, extract the electrode carefully without damage to the seat face.
c)
Inspect the column seat, remove any scaling or residue taking care not to damage the
seat.
d)
Carefully unpack the new electrode and check that there is no damage to the ceramic
insulators or to the seating ferrules.
e)
Lightly coat the electrode threads with anti-seize compound (Part No.: 830007220) and
assemble the new electrode to the water column as detailed in sub-section 3.1.3 for
high pressure electrodes.
Note:
f)
3-6
At the first pressure/temperature test, check for leaks and tighten electrode nut
as necessary, but not exceeding turn from the nipped electrode
condition.
Refit the electrical lead(s) and guard. Recommission as stated in section 3.2.
24675030_AJ
3.2
3.2.1
a)
Notify the unit operator of the intention to commission the column, in accordance with
recognised procedures.
b)
c)
d)
Crack open the steam valve. Check with the display or the unit operator that the column
fills with condensate slowly (10 to 15 minutes).
e)
Crack open the water isolating valve. Check with the unit operator that the water level is
falling (1 to 2 minutes) to approximately normal water level and allow to stabilise and
heat up for 15 minutes.
f)
g)
3.2.2
24675030_AJ
3-7
3.2.3
3-8
Ensure that all valves are left correctly set and locked.
24675030_AJ
Unit Description
Unit Description
Contents
Page No.
4.1
4.2
4.3
4.4
4.5
Illustrations
Figure 4.1 - Low pressure electrode...................................................................................... 4-3
Figure 4.2 - High pressure electrode ..................................................................................... 4-4
24675030_AK
4-1
Unit Description
4-2
24675030_AK
4.1
Unit Description
24675030_AK
4-3
Unit Description
4.2
4-4
24675030_AK
4.3
Unit Description
24675030_AK
4-5
Unit Description
4.4
4-6
24675030_AK
4.5
Unit Description
24675030_AK
4-7
Unit Description
4-8
24675030_AK
ELECTRODES
Type 459600602
Type 459600802
Type 246781A:
Type 246782A:
Type 246784A:
Type 246781Z:
24675030_AK
5-1
5.2
5-2
WATER COLUMNS
Type Low Pressure:
24675030_AK
Appendix A
Approval Certificates
This appendix contains copies of the Safety and System Certificates for the Hydrastep 2468 Electronic
Gauging System and the Declarations of Conformity with EEC directives.
Safety and System Certificates
Certificate Type
Certificate
No.
Date
Issuing
Authority
No. of
Pages
Comments
Company Licence
M0941
8-Jul 97
EECS
System Certificate
Ex94Y4362X
1-Nov 94
BASEEFA
Ex94Y4362X/1
24-Feb 95 BASEEFA
Ex94Y4362X/2
6-Jun 95
BASEEFA
Ex94Y4362X/3
12-Jun 96
BASEEFA
IMPORTANT NOTE: The System Certificate Ex94Y4362X is issued with special conditions for safe
use (indicated by the X suffix). It is essential that these conditions - given on page 5 of the certificate
- are implemented fully.
For further details, contact Solartron-Mobrey.
24675030_AH
A-1
Declarations of Conformity
Directives Covered
Product
Basis of Conformity
Date
89/336/EEC Electromagnetic
Compatibility Directive, amended
by 92/31/EEC and 93/68/EEC.
Oct. 2000
Oct. 2000
As above
BS EN 50081-2:1994
Oct. 2000
As above
BS EN 50081-2:1994
A-2
BS EN 50082-2:1995
Oct. 2000
BS EN 50082-2:1995
24675030_AH
Deutschland
China
Polska
Sverige
France
Belgium
USA
abcdef
24685033
DB, Jan 01