(Sabre) : Non-Extensible UNIT
(Sabre) : Non-Extensible UNIT
(Sabre) : Non-Extensible UNIT
LUCY SWITCHGEAR
(Sabre)
LUCY SWITCHGEAR
(Sabre)
2- Housing
The housing of the Sabre VRN2a is fully treated; using zinc coated steel and electro
statically applied oven cured paint, to resist weather and pollution attacks. All units
are provided with a hinged, weatherproof and lockable door. The external support
legs can provide a Tee-Off bushing height of 1402, 1320mm or 1100mm.
4-Ring Switches
The two ring switches are of the single break, fault-make / load- break 3 position
types, 'ON', 'OFF' and 'EARTH'.
5- Operation
All operating positions and instructions are indicated on the main panel at the front of
the unit. Operation is by means of manually independent mechanisms, which are
mounted externally to the gas enclosure The tee-off vacuum circuit breaker has two
operating positions, 'ON' or 'OFF', with an off-load, interlocked selector allowing
isolation & earthing of the tee-off circuit A single, "Y"-bar type operating handle is
stored at the front door. Symbols located on the end of the operating handle indicate
direction of operation.
.
.
6-Test Facilities
The Sabre VRN2a has fully interlocked integrated ring switch cable test facilities in
accordance with ENATS 41-36 requirements. Access to the test terminals is
achieved by pulling a lever located on the front fascia inside the front door. This will
allow the cover underneath the unit to drop down. Where cable test facilities are
required on the T-off, an alternative interlocked system, using plug-in
connectors, is available.
7- Interlocks
Positive safety interlocks are incorporated on all switch positions.
8- Padlocks
The door has a quarter-turn lock that can be padlocked. The handle has a padlock
hasp hole size 8mm diameter.
All switch and selector positions can be padlocked. The padlock hasp hole size is
8.5mm diameter.
9- Transformer Protection
The circuit breaker enables the VRN to protect transformers with ratings well in
excess of those of a comparable HV fused unit. Protection is achieved by the use of
ring core current transformers in combination with Time Limit Fuse links or a
protection relay. The ring core current transformers are mounted around the rear teeoff bushings, external to the SF6 chamber, but within the cladding of the unit. The
Time Limit Fuses, or the protection relay, are mounted behind a cover at the front of
the unit.
10- Time Limit Fuse Protection (TLF)
Dual ratio CT's are provided as standard transformer protection. Access for CT ratio
change is provided by means of a cover plate on the front panel of the unit.
The following types of terminations can be used with the Sabre VRN2a
PROFILE C
Bolted Separable
14- Earthing
The Sabre VRN2a unit should be earthed at either of the primary earth points.
These earth points are located at the rear of the unit, either side of the Cable
Test Access Cover as shown.
Technical data
Non Extensible Unit VRN2a
1- Rated Voltage
2- Impulse Withstand Voltage
12KV (15.5KV)
75KV (95KV )
3- Normal Current
- Ring Switches
630Amp
250Amp
50KA
50KA
20KA RMS
20KA
20KA
20KA
7.9 KA
8-
9-
Freestanding
20KA 1 sec
Transformer Mounted
20KA 1 sec
Gas pressure
- Min Operating Pressure
O Bar G
10-
IP Rating
11-
Weight
up to IP54W
350kg