Analysis and Application of Scott Connection
Analysis and Application of Scott Connection
Analysis and Application of Scott Connection
Scott Connection
Term Paper as a part of Course
November 26, 2015
Abstract
Scott Connection is mainly used for deriving two-phase current from three-phase supply and
vice-versa. Scott Connection is widely used in industrial furnace transformer and for traction
purpose. It is used in electric railway system when there are two unbalanced single phase loads
as Scott connected transformer can reduce unbalanced currents. This paper investigates the main
application of Scott transformer and also analyze weather this connection can reduce unbalanced
current. It also includes the complete analysis of balanced and unbalanced condition of the Scott
Connected Transformer.
1. Introduction
Analysis and Application of Scott Connection
Page 1
Scott connection (Scott T-transformer) is a type of circuit used to derive two-phase current from
a three-phase source or vice-versa. The Scott three-phase transformer was invented by an
engineer Charles F. Scott. In 1980s to bypass Thomas Edisons rotary converter and thereby
permit two-phase generator plants to drive Nikola Teslas three-phase motors.
In many situations it becomes necessary to supply a balanced and unbalanced two phase or three
phase supply. One way for a two phase load, to connect two phases between two lines, the
following is one possibility:
Two Phase loads
However, even when these phases are balanced, impendences are balanced; they will draw
unbalanced current from supply. Not only that many two phase loads will require a balanced two
phase supply as well. Some of these two phase loads are arc furnaces or induction melting
furnaces. They will consume power in megawatts. So care should be taken to make sure that the
loading of the three phase system is balanced top the extent possible. This can be done by a Scott
Connected Transformer.
In order to overcome the disadvantage of the T connection, the Scott connection uses two singlephase transformers of a special design to transform three-phase voltages and currents into twophase voltages and currents. The first transformer, called the main, has a center-tapped
primary winding connected to the three-phase circuit with the secondary winding connected to
the two-phase circuit. It is vital that the two halves of the center-tapped primary winding are
wound around the same core leg so that the ampere-turns of the two halves cancel out each other.
The ends of the center-tapped main primary winding are connected to two of the phases of the
three-phase circuit.
The second transformer, called the teaser, has one end of its primary winding connected to the
third phase of the three-phase circuit and the other end connected to the center tap of the primary
winding of the main. The Scott connection requires no primary neutral connection, so zero-
Page 2
sequence currents are blocked. The secondary windings of both the main and teaser transformers
are connected to the two-phase circuit.
The Scott connection is shown in figure for a two-phase, five-wire circuit, where both secondary
windings are center-tapped and the center taps are connected to the neutral of the five wire
circuit. Three-wire and four-wire configurations are also possible. If the main transformer has a
turn ratio of 1: 1, then the teaser transformer requires a turn ratio of 0.866:1 for balanced
operation. The principle of operation of the Scott connection can be most easily seen by first
applying a current to the teaser secondary windings, and then applying a current to the main
secondary winding, calculating the primary currents separately and superimposing the results.
Page 3
In the above diagram we have taken two single phase transformers. Let us say we have N, N 1 and
N2 be the number of turns of the transformers. The second transformer is tapped by 50% so the
number of turns of coil becomes N1/2 on both sides of tapping. Then we supplied balanced three
phase supply to VA, VB and VC respectively. Let Va and Vb be the induced voltages.
Now drawing the phasor VBC, VAB & VCA. Now the voltage phasor VMC will be half of VBC and
voltage phasor VAM will be VAC-VMC. It shows that the voltage phasor VAM is right angle to the
voltage phasor VBC, hence, induced voltage Va will be in phase with the voltage VAM and its
magnitude will be (N2/N)*VAM . Voltage phasor Vb will be in phase with the voltage V BC and its
magnitude will be (N2/N1)*VBC .
Analysis and Application of Scott Connection
Page 4
Va
(N2/N)*VAM
(N2/N1)*VBC
Vb
Now we want the voltages VAB and VBC to be balanced two phase i.e. they are already 9 00 and
if we want their magnitude also to be same then it is imperative that it should have
(N2/N)*VAM = (N2/N1)*VBC
or we want N/N1=VAM/VBC
Page 5
Page 6
Example
(Note: The following example is taken from an actual case that occurred a number of years ago.)
A small industrial electric customer has a plant with an antiquated two phase electrical system.
The customer has a Scott-connected transformer bank connecting this system to the local utility
company which provides power. This Scott-connected bank catastrophically failed and there are
no replacement transformers readily available.
The utility company was called in to restore service to the two-phase system, but the utility only
has standard single-phase and three-phase distribution transformers in its storerooms. The
customer has a five-wire, two-phase system with a phase-to-neutral voltage of 120 V. The utility
companys distribution system has a phase-to-phase voltage of 12,470V and a phase-to-neutral
voltage of 7200 V. Customers are routinely supplied with 120/240 V service using single-phase
transformers connected either phase-to-phase or phase-to-neutral on the primary side.
One solution would be to use the T connection with the standard transformers that the utility had
on hand, but this would result in unbalanced three phase currents. A bright young engineer
working for the utility found a way to construct a Scott-connected bank using standard
transformers. The teaser was replaced by a standard distribution transformer with a 12,470 V
primary and a 120/240 V center-tapped secondary. The main transformer was replaced by two
standard distribution transformers, each having a 7200 V primary and a 120/240 V center-tapped
secondary.
The primary windings of the replacement main transformers were connected in series and their
secondary windings were connected in parallel. These connections are shown in the figure below.
Since the two transformers substituted for the main transformer are not wound on the same core
leg, the secondary windings of the main transformers
Page 7
Page 8
4. Conclusion
The Scott T connection in theory would be suitable for supplying a three, two and single phase
load simultaneously, but such loads are not found together in modern practice. The neutral points
can be available for grounding or loading purposes. Scott transformer causes two unbalanced
single-phase loads to be presented less unbalanced to the power system
Page 9
5. Bibliography
i.
http://en.m.wikipedia.org/wiki/Scott-T_transformer
ii.
iii.
iv.
Pg no.1-7, 2009
Irving L. Kosow, Electric Machinery and Transformers, Second edition, pg. no. 559560, Prentice Hall of India, 2004
Page 10