LFL Gas Burner Control
LFL Gas Burner Control
LFL Gas Burner Control
Burner Controls
451
LFL1...
Burner controls
For gas, oil or dual-fuel forced draft burners of medium to high capacity
For multistage or modulating burners in intermittent operation
With checked air damper control
Flame supervision
with UV detectors QRA...
and ionization probe
Burner control for oil burners or gas burners conforming to EN 298: 2012
Suitable for use with air heaters (WLE)
The LFL1... and this Data Sheet are intended for use by OEMs which integrate the
burner controls in their products!
Use
-
Control and supervision of forced draft burners of direct spark flame or interrupted
pilot construction
For medium to high capacity
For intermittent operation (at least one controlled shutdown every 24 hours)
For universal use with multistage or modulating burners
For use with stationary air heaters (WLE)
For burner controls conforming to EN 298: 2012
For use with dual-fuel burners
The flame supervision is ensured via a flame detector QRA or ionization probe. The
difference between 01 series and 02 series is the duration of the safety time for the pilot
burner of burners equipped with pilot gas valves.
For atmospheric burners of high capacity, use the LFL1.638.
CC1N7451en
20.04.2016
Supplementary documentation
Product type
Type of documentation
Documentation number
Data Sheet
N7785
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Do not open, interfere with or modify the unit!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not observed, there is
a risk of electric shock hazard
Ensure protection against electric shock hazard by providing adequate protection
for the burner controls connection terminals
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state and make the safety checks as
described in Commissioning notes
Press the lockout reset button only manually (apply a force of no more than 10 N),
without using any tools or pointed objects
Do not press the lockout reset button on the unit or the remote lockout reset button
(input 21)for more than 10 seconds since this damages the lockout relay in the unit
Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
For safety reasons self-test of the flame supervision circuit, etc. at least one
controlled shutdown must take place every 24 hours
In the case of flame supervision with UV detectors QRA..., it should be noted that
sources of radiation such as halogen lamps, welding equipment, special lamps,
ignition sparks, as well as X-rays and gamma radiation, can produce erroneous
flame signals
Mounting notes
Ensure that the relevant national safety regulations are complied with
Connect the earthing lug inside the terminal base to burner ground using a screw
with a lockwasher
An ignited UV tube is a source of UV radiation! In case of flame supervision by
means of flame detectors, the detectors must be placed such that there is no
direct visual contact between them. If this is not observed, there is a risk of loss
of safety functions
2/26
Building Technologies Division
CC1N7451en
20.04.2016
Installation notes
Always run the high-voltage ignition cables separately while observing the greatest
possible distance to the unit and to other cables
Do not mix up live and neutral conductors
Install switches, fuses and grounding in accordance with local regulations
Do not exceed the maximum permissible current rating of the connection terminals
The insulation of internal wiring which is subjected to the mains voltage must be
able to withstand the electrical loads occurring during proper use
Application notes
For use in applications in dual-fuel burners or oil burners, the oil supply must be
equipped with two shutoff valves connected in series.
Observe the following:
EN 298:2012, Section 7.101.3.3 Prepurge time for oil burner control systems and the
corresponding application standards.
3/26
Building Technologies Division
CC1N7451en
20.04.2016
Commissioning notes
When commissioning the plant or when doing maintenance work, make the following
safety checks:
Safety check to be carried out
Anticipated response
a)
b)
c)
Lockout
d)
e)
4/26
Building Technologies Division
CC1N7451en
20.04.2016
Engineering notes
1 2
21
13 12 14
16
17
18
19
20
11
10
LR
bv...
(1)/(3)
SB
GP
R
d1
d2
SA
M
22 23
EK2
M1
AL
24
QRA...
Si
L
N
22 23
LP
BV1
M2
BV3
LK
ZBV
3
BV2
Z
BV1
5
BV2
7451a14e/0604
24
ION
Connect safety limit thermostat in the line (manual reset, e.g. SB)
Remote reset
When remote reset button EK2 is connected between terminal 21 and
- terminal 3, only remote reset is possible
- terminal 1, both remote emergency shutdown and remote reset are possible
For use in oil applications, the oil supply must be equipped with two shutoff valves connected in
series.
Observe the following:
EN 298:2012, Section 7.101.3.3 Prepurge time for oil burner control systems and the corresponding
application standards.
5/26
Building Technologies Division
CC1N7451en
20.04.2016
Connection of fuel valves with direct spark flame burners. With 2-stage burners, BV2 is connected in place of BV3
Connection of fuel valves with interrupted pilot burners
Direct connection of a fuel valve to terminal 20 is only permitted
in plants with a main shutoff valve on the mains side (safety shutoff valve), which is controlled by terminal 18 or 19, and
if 2-stage valves are used, provided they fully close when the first stage, controlled by terminal 18 or 19, is switched off
For additional examples of air damper control, refer to Connection examples. In the case of actuators with no end switch
z for the fully CLOSED position of the air damper, terminal 11 must be connected to terminal 10 otherwise no burner
start.
For the permissible length and laying of detector cables, see Flame supervision
6/26
Building Technologies Division
CC1N7451en
20.04.2016
2014/35/EC
2009/142/EC
97/23/EC and
2014/68/EC (2016-07-16)
2014/30/EC
*) The compliance with EMC emission requirements must be checked after the burner control is
installed in equipment
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic burner control systems for burners and
DIN EN 298
appliances burning gaseous or liquid fuels
Safety and control devices for gas burners and gas burning
DIN EN 13611
appliances
DIN EN 60730-2-5
Automatic electrical controls for household and similar use
Part 2-5:
Particular requirements for automatic electrical burner
control systems
The relevant valid edition of the standards can be found in the declaration of
conformity!
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
Certified complete with plug-in base and flame detector:
Type
reference
---
LFL1.635
LFL1.638
---
---
LFL1.122
LFL1.133
LFL1.322
LFL1.333
LFL1.335
LFL1.622
-------
-----
---
---
---
---
---
---
7/26
Building Technologies Division
CC1N7451en
20.04.2016
Life cycle
Burner controls has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, correspond to approx. 10 years of usage
(starting from the production date given on the type field).
This lifetime is based on the endurance tests in the standard EN 298.
A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor) (www.afecor.org).
The designed lifetime is based on use of the burner controls according to the
manufacturers Data Sheet. After reaching the designed lifetime in terms of the number
of burner startup cycles, or the respective time of usage, the burner control is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
LFL1...
Plug-in design
Exchangeable unit fuse (including spare fuse)
Housing
8/26
Building Technologies Division
CC1N7451en
20.04.2016
Type summary
The type references given below apply to the LFL without plug-in base and without
flame detector. For ordering information for plug-in bases and other accessories, see
Accessories.
Switching times are given in seconds, in the burner startup sequence, valid for 50 Hz
mains frequency. At 60 Hz, switching times are about 17 % shorter.
The type references apply to burner controls operating on AC 230 V, 50...60 Hz.
Flash steam
generators
Flash steam
generators
D (incl.
stationary
air heaters)
F
A
D
GB
F
I
B
NL )
Large
atmospheri
c burners
LFL1.122 )
02 series
LFL1.133 )
02 series
LFL1.322 )
02 series
LFL1.333 )
02 series
LFL1.335 )
01 series
LFL1.622 )
02 series
LFL1.635 )
01 series
LFL1.638
01 series
t1
10
36
31
37
65
66
66
TSA
2.5
2.5
2.5
TSA
t3
t3
---
2.5
2.5
2.5
t4
10
11.5
12.5
10
12.5
12.5
t4
---
10
11.5
15
10
15
15
t5
10
11.5
12.5
10
12.5
12.5
t6
10
14.5
12
18
15
12
15
15
t7
2.5
2.5
2.5
t8
30
29
65
69
74
95
103
103
t9
7.5
t10
11.5
10
10
10
t11
Optional
t12
Optional
t13
10
14.5
12
17
15
12
15
15
t16
t20
32
60
---
26
22
---
---
---
t8
TSA
t9
t10
t1
t3
Preignition time
t11
t3
t12
t4
t13
t4
t16
terminal 19
t20
t5
t6
t7
9/26
Building Technologies Division
CC1N7451en
20.04.2016
Ionization probe
to be supplied by thirds
Connection accessories
for medium-capacity
burner controls
Others
Actuators
Actuator SQN72...
See Data Sheet N7802
Actuator SQN9...
See Data Sheet N7806
10/26
Building Technologies Division
CC1N7451en
20.04.2016
Technical data
General unit data
LFL1...
Mains voltage
Mains frequency
Unit fuse (built-in)
Primary fuse (external)
Weight
Power consumption
Mounting position
Degree of protection
Safety class
Perm. input current at terminal 1
Perm. load on control terminals 3, 6, 7,
9...11, 15...20
Required switching capacity of switching
devices
Between terminals 4 and 5
Between terminals 4 and 12
Between terminals 4 and 14
AC 230 V 15 / +10 %
AC 115 V 15 / +10 %
50...60 Hz 6 %
T6.3H250V to DIN EN 60 127
max. 10 A (slow)
approx. 1,000 g
approx. AC 3.5 VA
optional
IP 40, when built in, with the exception of
the connection area (terminal base)
II
max. 5 A continuously (peaks 20 A / 20 ms)
max. 4 A continuously (peaks 20 A / 20 ms)
1 A, AC 250 V
1 A, AC 250 V
min. 1 A, AC 250 V
depending on the load on terminals 16...19
Permissible length of the standard detector See Technical Data, chapter Flame
cable (laid separately)
supervision
Capacity
Optional (with ignition <120 kW)
Output on startup (without fan
assistance)
Optional
Nominal output
Environmental
conditions
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60721-3-1
class 1K3
class 1M2
-20...+60 C
< 95 % r.h.
DIN EN 60721-3-2
class 2K3
class 2M2
-20...+60 C
< 95 % r.h.
DIN EN 60 721-3-3
class 3K3
class 3M3
-20...+60 C
< 95 % r.h.
Warning!
Condensation, formation of ice and ingress of water are not permitted!
11/26
Building Technologies Division
CC1N7451en
20.04.2016
AC 330 V 10 %
AC 380 V 10 %
max. 0.5 mA
0...50 A
max. 80 m
max. 140 m (e.g. high-frequency cable;
shielding connected to terminal 22)
min. 6 A
max. 200 A
Supply voltage
- Operation
- Test
Required detector current
Possible detector current
- Operation
- Test
Perm. length of detector cable
- Normal cable, laid separately )
- Shielded cable
AC 330 V 10 %
AC 380 V 10 %
min. 70 A
max. 700 A
max. 1000 A )
max. 100 m
max. 200 m (e.g. high-frequency cable;
shielding connected to terminal 22)
) During the prepurge time with higher test voltage: Self-ignition and extraneous light test
) Multicore cable not permitted
Detector current measurement
Ionization probe
M
+
LFL1...
7451v01/0204
24
+
C
M -
A
ION
QRA...
23 22
LFL1...
C
7451v02/0204
C
ION
M
12/26
Building Technologies Division
CC1N7451en
20.04.2016
Function
2-stage direct spark flame burner
Legend
A
t7
t6
t1
M1
M2
M
~
t3
TSA
BV1
R
TP
t4
t5
LR
100%
LK
min.
0...
BV2
t11
t13
t12
FS
7451a06/0600
A
R
M
~
M1
M2
t7
t6
t3
100%
LK
t11
Start command by R
Operating position of burner
Burner operation
Controlled shutdown
Sequence switch travels to start position
A, postpurging
End of control sequence
t1
t3/t3
t4/t4
t5
t9
t4
LR
A
B
B-C
C
C-D
t6
t7
TSA
BV1
R
t1
Fuel valve
Flame signal amplifier
Air damper
Load controller
Fan or burner motor
Control thermostat or pressurestat
Modulating fuel valve
Ignition transformer
Pilot gas valve
D-A
TP
BV...
FS
LK
LR
M...
R
RV
Z
ZBV
t11
t5
t12
t12
min.
0...
RV
t13
TSA/
TSA
t13
FS
7451a07/0600
B
t7
t3
TSA
ZBV
t5
LR
100%
LK
min.
0...
BV2
t9
t4
BV1
R
D
t6
t1
M1
M2
M
~
t11
t13
t12
FS
7451a08/0202
13/26
Building Technologies Division
CC1N7451en
20.04.2016
Function (cont'd)
General
The following features enable the LFL1... to offer a high level of additional safety:
Detector and extraneous light test are resumed immediately on completion of the
afterburn time t13. Fuel valves that are not closed, or not fully closed,
immediately initiate lockout on completion of the afterburn time t13. The test will
only be terminated when the prepurge time t1 of the next startup sequence has
elapsed.
The proper functioning of the flame supervision circuit is automatically checked
during each startup phase of the burner.
During the postpurge time t6, the control contacts for the release of fuel are
checked to ensure they have not welded.
The built-in unit fuse protects the control contacts against overloads.
Flame supervision
Preconditions for
startup
14/26
Building Technologies Division
CC1N7451en
20.04.2016
Function (cont'd)
Preconditions for burner
startup
15/26
Building Technologies Division
CC1N7451en
20.04.2016
Startup sequence
A
t1
t5
Interval
On completion of t5, power is fed to terminal 20; at the same time, control outputs 9...11 and input 8
are galvanically separated from the units control section
The LFL1... is now protected against return voltages from the power control loop
The startup sequence of the LFL1 ends with the release of LR at terminal 20
After a number of idle steps (steps with no change of the contact position), the sequence switch
switches itself off
t3
Preignition time
Release of fuel via terminal 18
t4
16/26
Building Technologies Division
CC1N7451en
20.04.2016
Preignition time
Release of fuel for pilot burner via terminal 17
TSA
TSA
t4
t4
Interval ZBV-BV1
Up to the release of the fuel valve at terminal 19 for the main burners start load
t9
B-C
Burner operation
During burner operation, LR drives the air damper to the high-fire or low-fire position, depending on
the demand for heat
Release of high-fire is enabled by auxiliary switch v in the actuator
In the event of loss of flame during operation, the LFL1 will initiate lockout
Controlled shutdown
On controlled shutdown, the BV... will immediately be closed. At the same time, the sequence switch
starts and programs t6
C-D
t6
Postpurge time
Fan M2 connected to terminal 7
Shortly after the start of t6, power is fed to terminal 10
air damper will be driven to the MIN position
Full closing of the air damper starts only shortly before t6 has elapsed
triggered by the control signal at terminal 11
During the following burner off period, terminal 11 remains live
t13
D-A
Times TSA, t3 and t4 only exist with burner controls of the 01 series.
17/26
Building Technologies Division
CC1N7451en
20.04.2016
No start
One of the contacts is not closed (also refer to Preconditions for burner startup)
Extraneous light
Lockout during or after completion of the control sequence.
Examples:
Flames that have not extinguished
Leaking fuel valves
Defect in the flame supervision circuit
Startup
interruption
Terminal 8 has not received the OPEN signal from end switch a
Terminals 6, 7 and 14 remain live until the fault has been corrected
Lockout
Lockout
>
Startup
interruption
Terminal 8 has not received the positioning signal from auxiliary switch m for the
low-fire position
Terminals 6, 7 and 14 remain live until the fault has been corrected
Lockout
Lockout
No flame signal on completion of the second safety time (flame signal of main flame
with interrupted pilot burners)
Lockout
After the reset, the burner control sequence switch first returns to the start position and
then initiates a burner restart. If lockout occurs any other moment in time between start
and preignition not indicated by a symbol, the usual cause is a premature flame signal,
that is, a faulty flame signal, caused for instance by a self-igniting UV tube.
Lockout indicator
a-b
Startup sequence
b-b
Idle steps
(with no contact confirmation)
b (b)-a
LFL1... Series 01
LFL1... Series 02
Postpurge program
When lockout has occurred, the burner control can immediately be reset.
Do not press the lockout reset button for more than 10 seconds
The sequence switch always returns to its start position first
After resetting
After correction of a fault which resulted in plant shutdown
After each power failure
During that period of time, power is only fed to terminals 7 and 9...11.
The burner control then carries out a burner restart
Note!
Do not press the lockout reset button for more than 10 seconds.
18/26
Building Technologies Division
CC1N7451en
20.04.2016
z
t7
t10
m a
t16
t11
t1
t3
t12
t3
TSA
t4
TSA
t4
t9
t5
t5
B
C
AS
1 2
t6
D
A
3 13 12 14
21
t13
16
17
18
19
20
11
10
LR
(1)/(3)
SB
bv...
GP
d1
d2
SA
M
22 23
EK2
M1
AL
24
QRA...
Si
L
N
22 23
LP
BV1
M2
BV3
LK
ZBV
3
BV2
Z
BV1
5
BV2
7451a02e/0604
24
ION
Attention!
Do not press lockout reset button EK... for more than 10 seconds!
For the connection of the safety shutoff valve, refer to the plant diagram
provided by the burner manufacturer.
19/26
Building Technologies Division
CC1N7451en
20.04.2016
SB
1
ION
AS
br1
a
ar1
I
a
22
ar2
a XV
7
QRA...
M1
N
5
fr1
b
a
a
XIII
b
22 23 24
M2
14
13
d2
d1
LP
GP
fr3
FR
fr2
V
(1) (2)
XII
NTC
XIV a b
AR
IV
a
VII
br2
EK1
L1
E
A
3 21
15 16
VI
VIII
II
BR
24
12
XI
23
17
18
19
SM
11 10
20
b
ar3
III
LR
(1)/(3)
EK2
N
SA v
AL
ZBV
BV1
BV1
a
BV2
LK
7451a12/0204
BV2
Attention!
Do not press lockout reset button EK... for more than 10 seconds!
For the connection of the safety shutoff valve, refer to the plant diagram
provided by the burner manufacturer.
20/26
Building Technologies Division
CC1N7451en
20.04.2016
Switchgear sequence
II
a
b t7
a
b
III
a
b
Control output
D at terminal:
12
t3
19
t11
t1
t4
t12
t6
16
10
9
IV
a
b
11
t16
20
VI
VII
a
b
VIII
X
a
b
a
b
XI
a
b
XII
a
b
XIII
a
b
XIV
a
b
XV
a
b
t20
TSA
18
*t3
*t4
t9
17
*TSA
t5
t10
t13
12
t8
7451d01/0604
LFL
21/26
Building Technologies Division
CC1N7451en
20.04.2016
17 18 19
BV2
N
BV1
7451a10/1295
M
N
7451a11/0396
Brown
Black
AGM30
1
23
L...
LR
SA
BV1/BV2
16
17
19
18
20 11
10
LR
7
11
6 5
2 10 8
SA
IV
13 12
N
BV1
I M
BV2
7451a03/0396
B
t7
LK
C
t6
t1
M1
M2
M
~
III
N 3
A
R
TP
II
t3
TSA
BV1
t4
t5
LR
100%
R
M
LK
min.
0...
BV2
t11
t13
t12
FS
7451a06/0600
22/26
Building Technologies Division
CC1N7451en
20.04.2016
(contd)
SA
BV1
16 17 18
19
20
11 10
LR
N
BV1
SA
a
z
M
RV LK
7451a04/1295
A
TP
M
~
M1
M2
t7
t3
TSA
BV1
t4
LR
100%
LK
t6
t1
t11
t5
t12
min.
0...
RV
t13
FS
7451a07/0600
2-stage interrupted pilot burner (burner with pilot burner) Controlled and supervised by a burner control of the 01
series.
L...
LR
SA
BV1/BV2
ZBV
16
1 7 18 1 9
20 9
11
10
LR
ZBV
LK
BV2
BV1
SA v
7451a05/0496
A
TP
B
t7
TSA
ZBV
t5
LR
100%
LK
min.
0...
BV2
t9
t4
BV1
t3
D
t6
t1
M1
M2
M
~
t11
t13
t12
FS
7451a08/0202
23/26
Building Technologies Division
CC1N7451en
20.04.2016
Legend
a
AL
AR
AS
BR
BV...
bv...
d1 / d2
EK...
FR
FS
GP
H
ION
L1
L3
LK
LP
LR
M1 / M2
m
NTC
QRA...
R
RV
SA
SB
Si
SM
V
v
W
Z
z
ZBV
(1)
(2)
Input for increasing the operating voltage for the QRA... (detector test)
Input for forced energizing of the flame relay during the functional test of the flame supervision circuit
(contact XIV) and during safety time TSA (contact IV)
A
A-B
B
B-C
C
C-D
D-A
24/26
Building Technologies Division
CC1N7451en
20.04.2016
Legend (contd)
Lockout position indication when there is no input signal (see Control sequence in the event of faults):
1
2
P
I
No start
Startup interruption
Startup interruption
Lockout (disturbance in the flame supervision circuit)
Lockout (no flame)
Lockout (no flame)
Lockout (no air pressure)
Lockout
Time table
TSA
TSA
t1
t3
t3
t4
t4
t5
t6
t7
t8
t9
t10
t11
t12
t13
t16
t20
25/26
Building Technologies Division
CC1N7451en
20.04.2016
Dimensions
Dimensions in mm
123
108,5
1,5
LFL1...
AGM14.1
27,5
7,5
103
37
27,5
103
26/26
Building Technologies Division
2016 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change!
CC1N7451en
20.04.2016