ABB ME ASURE ME NT & AN AL YT ICS | D AT A SHE ET

TZIDC
Digital Positioner
2 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


For highly accurate and reliable
positioning of valves in all sectors


Easy Set-up
• Automatic adjustment function
• Straightforward initialization


Wide temperature range
• −40 to 85 °C (−40 to 185 °F)


HART Communication


Control Adaptive function
• Automatic adjustment of control parameters during
operation


Increased shock and vibration resistance
• Gearless sensor activation


Fail Save and Fail Freeze function
• Selectable safety position of the fitting


Low air consumption
• Highly efficient I/P converter
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 3

Change from one to two columns


Brief description
The TZIDC is an electronically configurable positioner with Use
communication capabilities designed for mounting on The positioner has a built-in operating panel providing a 2-
pneumatic linear or rotary actuators. It features a small and line LCD indicator and 4 operating buttons for
compact design, a modular construction, and an excellent commissioning, configuration and monitoring during live
cost-performance ratio. operation.
Fully automatic determination of the control parameters and Alternatively, the appropriate configuration program can be
adaptation to the positioner allow for considerable time used via the available communication interface.
savings as well as optimum control behavior.
Communication
Pneumatics The positioner has a local communication interface (LCI) as
An I/P module with subsequent pneumatic amplifier is used standard. Additionally, a ‘HART® communication’ option for
to control the pneumatic actuator. The well-proven I/P communication via the 20 mA signal is available. Both
module proportionally converts the permanent electrical communications are based on the HART® Protocol.
setpoint signal from the CPU into a pneumatic signal used to Alternatively, HART®5 or HART®7 are available.
adjust a 3/3-way valve.
Dosing of the air flow for pressurizing or depressurizing the Inputs / Outputs
actuator is continuously adjusted. As a result, excellent In addition to its input for the analog position setpoint, the
control results are achieved. When reaching the setpoint, the positioner is equipped with a digital input which can be used
3/3-way valve is closed in center position to minimize the air to activate control system functions in the device. A digital
consumption. output allows you to output collective messages (alarms /
The pneumatic system can be supplied in four versions: for faults).
single acting and double acting actuators and each with the
‘fail-safe’ / ‘fail-freeze’ safety function. Modular design
The basic model can be enhanced at any time by retrofitting
‘Fail-safe’ safety function optional equipment.
If the electric power supply fails, the positioner output 1 is Option modules can be installed for analog and digital
depressurized and the return spring in the pneumatic position feedback.
actuator moves the valve to the safe position. In case of a Additionally, a mechanical position indicator, proximity
‘double-acting’ version, output 2 is additionally pressurized. switches or 24 V microswitches are available for indicating
the position independently of the mother board function.
‘Fail-freeze’ function
If the electric power supply fails, the positioner Output 1
(and Output 2 if applicable) is closed and the pneumatic
actuator blocks the valve in the current position. If the
compressed air supply power fails, the positioner
depressurizes the actuator.
Change from two to one column
4 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Brief description
Schematic diagram
Basic device Optional upgrades

1 LCI plug 8 Position sensor


2 Setpoint signal 4 to 20 mA 9 Plug-in module analog feedback (4 to 20 mA)
3 Binary input 0 Plug-in module digital feedback
4 Binary output k Installation kit for mechanical position indication
5 Supply air: 1.4 to 6 bar (20 to 90 psi) l Limit value monitor with proximity switches
6 Exhaust m Limit value monitor with 24 V-microswitches
7 I/P module with 3/3-way valve

Figure 1: Schematic diagram of the positioner

Note
With optional extensions, either the ‘Limit value monitor with proximity switches’ l or the ‘Limit value monitor with 24 V-
microswitches’ m can be used. In both cases though, the mechanical position indication k must be installed.
Change from one to two columns
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 5


Mounting versions
Standardized mounting on pneumatic linear actuators Integral mounting to control valves
Lateral attachment is in accordance with DIN / IEC 534 The positioner featuring standard pneumatic action is
(lateral attachment to NAMUR). The required attachment kit available as an option for integral mounting.
is a complete set of attachment material, but does not The required holes are found at the back of the device.
include the pipe fittings and air pipes. The advantage of integrated mounting is that the point for
mechanical stroke measurement is protected and that the
positioner and actuator are linked internally. No external
tubing is required.

Figure 4: Integral mounting on control valves


1 Columnar yoke 2 Cast iron yoke

Figure 2: Mounting on linear actuators in accordance with DIN / IEC 534

Standardized mounting on pneumatic rotary actuators


This attachment is designed for mounting according to the
standard VDI / VDE 3845. The attachment kit consists of a
console with mounting screws for mounting on a rotary
actuator. The corresponding feedback shaft adapter has to
be ordered separately. Screwed pipe connections and air
pipes have to be provided on site.
Figure 5: Integral mounting on control valves with adapter plate

Special actuator-specific mounting versions


In addition to the mounting methods described above, there
are special actuator-specific attachments.

Figure 3: Mounting on rotary actuators in accordance with VDI / VDE 3845


6 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Mounting versions
External position sensors Note
To connect the TZIDC Remote Sensor, a cable with the
following specifications needs to be used:
• 3-wire, cross-section 0.5 to 1.0 mm²
• shielded, with at least 85 % coverage
• Temperature range up to at least 100 °C (212 °F)

The cable glands must also be approved for a temperature


range up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB optionally offers a cable gland and cable for the
TZIDC Remote Version.

B TZIDC Control Unit for remote position sensor


1 TZIDC Control Unit 5 Compressed air supply
In this version the positioner is supplied without a position
2 Connection cable 6 Set point signal
sensor.
3 TZIDC Remote Sensor 7 Remote position sensor
The following points should be observed during installation:
4 Actuator • Housing 1 (TZIDC Control Unit) contains the
Figure 6: TZIDC with external position sensors electronics and pneumatics and is mounted separately
from the actuator.
Note • The remote position sensor is mounted on the linear
If the device is being operated on a cylinder, for reasons and rotary actuator. Follow the operating instructions
associated with linearity you should run the Auto Adjust for the remote position sensor for mechanical
function for rotary actuators mounting!

A TZIDC Control Unit with TZIDC Remote Sensor*


In this version, the components are supplied in two housings,
which together form one harmonized unit.
The following points should be observed during installation:
• Housing 1 (TZIDC Control Unit) contains the
electronics and pneumatics and is mounted separately
from the actuator.
• Housing 2 (TZIDC Remote Sensor) contains the
position sensor and is mounted on the linear and
rotary actuator.

* The TZIDC Remote Version is temporarily not available for


the marine version.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 7


Device parameters
General Shut-off function

Microprocessor-based position control in the positioner This parameter can be set separately for each end position.
optimizes control. The positioner features high-precision When the associated limit value is up-scaled, the function
control functions and high operational reliability. Due to their causes immediate travel of the actuator to the selected end
elaborate structure and easy accessibility, the device position.
parameters can be quickly adapted to the respective If the value ‘0’ is entered for the corresponding parameter,
application. the position is further controlled, even in the respective end
position.
The total range of parameters includes:
• Operating parameters Actuator travel time prolongation
• Adjustment parameters This function can be used to increase the max. travel time for
• Operation monitoring parameters full travel. This time parameter can be set separately for each
• Diagnosis parameters direction.
• Maintenance parameters This function can only be used with the pneumatics with the
safety function ‘fail-safe’.

Operating parameters Switching points for the position


You can use these parameters to define two position limit
The following operating parameters can be set manually if
values for signaling, see option ‘Module for digital position
required:
feedback’.
Setpoint signal
Digital output
0 to 100 % freely selectable for split-range operation
The alarms generated in the positioner can be polled via the
digital output as a collective alarm.
For 4 to 20 mA and HART version:
The desired information can be selected via the operator
• Signal min. 4 mA, max. 20 mA (0 to 100 %)
panel or remotely via the configuration program.
• Minimum range 20 % (3.2 mA)
The output can be set to ‘active high’ or ‘active low’, as
• Recommended range > 50 % (8.0 mA)
required.

Action (set point signal)


Digital input
Increasing:
For the digital input, one of the following safety options can
• Position value 0 to 100 % = direction 0 to 100 %
be selected. You may use the operator’s panel or
Decreasing: configuration program to select an option.
• Setpoint signal 100 to 0 % = direction 0 to 100 % • No function (standard setting)
• Move to position 0 %
Characteristic curve (actuator travel = f {set point signal}) • Move to position 100 %
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely • Hold previous position
configurable with 20 reference points. • Block local parameterization
• Block local parameterization and operation
Actuator travel limit • Block all access (no local or remote access via a PC)
The actuator travel, i.e. the stroke or angle of rotation, can be
reduced as needed within the full range of 0 to 100 %, The selected function is activated when the 24 V signal is no
provided that a minimum value of 20 % is observed. longer connected to the digital input (< 11 V DC).
8 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Device parameters
Adjustment parameters Diagnosis parameters
The positioner has a special function for automatic The diagnostics parameters in the positioner's operating
adjustment of the parameters. Additionally, the control program provide information about the operating conditions
parameters can be set automatically (in adaptive control of the valve.
mode) or manually to optimally adapt them to the process From this information the operator can derive what
requirements. maintenance work is required, and when.
Additionally, limit values can be defined for these parameters.
Tolerance band When they are exceeded, an alarm is reported.
Upon reaching the tolerance band, the position is re-adjusted So, for example, the following operating values are
more slowly until the dead band has been reached. determined:
• Number of movements of the final control element
Dead band (sensitivity) • Sum of individual actuator travel events
When reaching the dead band, the position is held. The The diagnosis parameters and limit values can be called up,
factory setting for this parameter is 0,1 %. set, and reset via HART communication, using the
configuration program.
Actuator spring action
Selection of the direction of rotation of the sensor shaft
(looking at the open housing), if the safe position is Operator panel
approached as a result of the spring force in the actuator
The integrated operating panel of the positioner has four
(actuator is depressurized via Y1 / OUT1).
operating buttons which allow the device to be operated with
For double-acting actuators, the actuator spring action
an open housing cover. The following functions can be
corresponds to pressurizing the pneumatic output (Y2 /
controlled via the function keys:
OUT2).
• Observe live operation
• Manual intervention during live operation
Display 0 to 100 %
• Parameterization of the device
Adjust the display 0 to 100 % in accordance with the direction
• Fully automatic commissioning
for opening or closing the final control element.
The operating panel has a cover to protect against
unauthorized operation.

Operations monitoring parameters


Various functions for continuous device monitoring are
implemented in the operating program for the positioner.
The following states will be detected and indicated, e.g.:
• Setpoint signal out of range 4 to 20 mA
• Position out of the adjusted range
• Positioning time up-scaled (adjustable time
parameter)
• Positioner inactive
• Counter limits up-scaled (adjustable in diagnosis)
While automatic commissioning is in progress, the current
Figure 7: Open TZIDC with a view of the operating panel
state is continuously indicated on the integrated LCD display.
During operation, the LCD shows the most important process
variables:
• Current position in %
• Faults, alarms, messages (coded)
Access to extended monitoring parameters is possible via
HART communication and the DTM.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 9

‘One-button’ commissioning
Commissioning the positioner is especially easy. Standard
Auto Adjust is triggered by pressing a single operating
button. Detailed configuration knowledge is not necessary in
order to start the device.
Depending on the selected actuator type (linear or rotary
actuator), the displayed zero position is automatically
adapted:
• for linear actuators counter-clockwise (CTCLOCKW)
• for rotary actuators clockwise (CLOCKW).
Besides this standard function, a customized ‘Autoadjust’
function is available. The function is launched either via the
operator’s panel or HART communication.

LCD display
The multi-line LCD indicator is automatically updated during
operation to provide the user with relevant information as
necessary.
During control operation (control with or without adaptation)
the following data can be called up by pressing the
pushbuttons briefly:
• Current set point SP [mA] (up button)
• Electronics temperature [°C, °F, °R, K] (down button)
• Current control deviation DEV [%]
(both direction buttons)

Figure 8: LCD display with operating buttons


10 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


Communication
DTM FSK modem
The DTM (Device Type Manager) for the positioner TZIDC is The FSK modem establishes digital frequency-modulated
based on FDT/DTM technology (FDT 1.2/1.2.1) and can be communication (Frequency Shift Keying) with the positioner.
either integrated into a control system or loaded on a PC with Tapping is possible at any chosen point of the 20 mA signal
DAT200 Asset Vision Basic. This allows you to work with the line.
same user interface in the commissioning phase, during We recommend a modem with electrical isolation. This
operation, and for service tasks involving monitoring the modem is bus-compatible when used with isolating
device, setting parameters, and reading out data. amplifiers. The connection of Ex-field devices is also possible
Communication is based on the HART protocol. provided the modem is operated outside the Ex area or it
Communication with the device can take place optionally via corresponds to the Ex approval requirements and the Ex
an LCI adapter with USB interface or an FSK modem at any connection data of our device.
point on the 20 mA signal line. Reading out data from the
device has no effect on the operation in progress. Newly set
parameters are saved in the non-volatile memory directly
upon download to the device, and become active
immediately.

LCI Adapter
You can easily connect your positioner to a PC, e.g., in the
workshop or in the commissioning phase, by using the LCI
adapter.
The signals at the USB output of the PC are translated via an
LCI adapter to the level of the local communication interface
1 TZIDC 3 Controller
(LCI) of the positioner.
2 Modem

Figure 10: HART communication with modem via 20 mA signal line

SQUAWK
SQUAWK is a standardized command of the HART®7
communication standard. If a SQUAWK command is sent to
the device after connection (HART® command ‘0’), the
flashing of the lower menu line in the display makes it easier
to visually identify the affected device in an installation.

1 TZIDC 3 Controller
2 LCI Adapter

Figure 9: Local communication with LCI adapter


TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 11


Specification
Actuator travel Pneumatic connections

Rotation angle Cable Air Pipe


Measuring range 270° Thread ½-14 NPT Thread ¼-18 NPT
Thread M20 × 1.5 Thread ¼-18 NPT
Working range Linear actuators min. 25°, max. 45°
Thread M20 × 1.5 Thread G ¼
Rotary actuators min. 25°, max. <270°
Thread G ½ Thread Rc ¼
(cf. Figure 11)
(Optional: with cable gland(s) and blind plugs as necessary)
Actuator travel limit Min. and max. limits, freely configurable in
range of 0 to 100 %
of total travel (min. range > 20 %) Compressed air output

Actuator travel time Setting range of 0 to 200 seconds, Range Standard design:
prolongation separately for each direction 0 to 6 bar (0 to 90 psi)
Dead band time limit Setting range 0 to 200 seconds (monitoring Marine version:
parameter for the control deviation until the 0 to 5.5 bar (0 to 80 psi)
dead band is reached) Air capacity > 5 kg/h = 3.9 Nm3/h = 2.3 scfm at 1.4 bar
(20 psi) supply air pressure
> 13 kg/h = 10 Nm3/h = 6 scfm at 6 bar
(90 psi) supply air pressure
Output function For single acting or double acting actuators
Air is vented from actuator / actuator is
blocked in case of (electric) power failure
Shut-off values End position 0 % = 0 to 45 %
End position 100 % = 55 to 100 %

Instrument air*
Purity Maximum particle size: 5 μm
Maximum particle density: 5 mg/m3
Oil content Maximum concentration 1 mg/m3
Pressure dew point 10 K below operating temperature
Supply pressure** Standard design:
1.4 to 6 bar (20 to 90 psi)
Marine version:
1 Measuring range 2 Operating range 1.6 to 5.5 bar (23 to 80 psi)

Figure 11: Measuring and operating ranges of the positioner Air consumption*** < 0.03 kg/h / 0.015 scfm
* Free of oil, water and dust in accordance with DIN / ISO 8573-1.
Pollution and oil content n accordance with Class 3
** Do not exceed the maximum output pressure of the actuator
*** Independent of supply pressure
12 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Specification
Accessories Housing
Mounting material
• Attachment kit for linear actuators in accordance with DIN
Material / IP rating
/ IEC 534 / NAMUR
Aluminum with ≤ 0.1% copper
• Attachment kit for rotary actuators in accordance with
IP rating IP 65 / NEMA 4X (NEMA 4X does
VDI / VDE 3845
not permit overhead mounting),
• Attachment kit for integral mounting
(IP 66, optional)
• Attachment kit for actuator-specific mounting

Pressure gauge block Surface/color


• With pressure gauges for supply air and output pressure. Dipping varnish With epoxy resin, stove-hardened
Pressure gauges with housing ø 28 mm (1.10 in), with Housing varnished matt black RAL 9005
connection block in aluminum, black Case cover Pantone 420
• Installation material in black for mounting on positioner
Weight
Filter regulator
Aluminum 1.7 kg (3.75 lb)
All metal version in brass, varnished black, bronze filter
element (40 µm), with condensate drain.
Mounting orientation
Max. pre-pressure 16 bar (232 psi).
Any
Output can be adjusted to:
• 1.4 to 6 bar (20 to 90 psi)
Marine version:
• 1.6 to 5.5 bar (23 to 80 psi)
The filter regulator may only be installed in combination with
the pressure gauge block (accessory).

PC adapter for communication


• LCI adapter (HART – USB) for plug connection to
positioner
• HART – USB modem for HART communication

Control program for operation and parameterization on


a PC
DAT200 Asset Vision Basic with DTM for TZIDC / TZIDC-200
on CD-ROM.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 13

Transmission data and contributing factors Communication


• HART® protocol 5.9 (standard); optionally HART®7.4
Output Y1 • Local connector for LCI adapter
Increasing set point signal 0 to 100 % (not in explosion protection area)
Increasing pressure at output
• HART® communication via 20 mA signal line with ABB LCI
adapter with Um ≤ 30 V DC.
Decreasing set point signal 0 to 100 %
Decreasing pressure at output

Ambient conditions
Action (set point signal)
Increasing set point 4 to 20 mA
= actuator position 0 to 100 % Ambient temperature range
Decreasing set point 20 to 4 mA During operation, storage, and −40 to 85 °C (−40 to 185 °F)
= actuator position 0 to 100 % transport
Limit monitor with proximity switches −25 to 85 °C (−13 to 185 °F)
SJ2-SN
Characteristic curve (actuator travel = f {set point signal})
TZIDC remote sensor −40 to 100 °C (−40 to 212 °F)
Linear Equal percentage 1:25 or 1:50 or
* Increased temperature range only with TZIDC Remote Sensor.
25:1 or 50:1*
Deviation ≤ 0.5 %
Tolerance band 0.3 to 10 %, adjustable Relative humidity

Configurable dead zone 0.1 to 10 %, adjustable During operation with housing closed 95 % (annual average),
Resolution (AD-conversion) > 16,000 steps and air supply switched on condensation permissible

Sampling frequency 20 ms Transport and storage 75 % (annual average)

Ambient temperature effect ≤ 0.5 % per 10 K


Reference temperature 20 °C
Safety Integrity Level
Influence of vibration ≤ 1 % to 10 g and 80 Hz
* freely configurable with 20 reference points Applies to applications with single-acting and depressurizing
pneumatics.

Seismic vibration The positioner meets the following requirements:


• functional safety in accordance with IEC 61508
Meets requirements of DIN / IEC 60068-3-3 Class III for
• Explosion protection (depending on the version)
strong and strongest earthquakes.
• Electromagnetic compatibility in accordance with EN
61000
Without the input signal, the pneumatic module in the
Influence of mounting orientation
positioner vents the actuator and the spring installed in it
Not measurable. moves the valve to a predetermined end position (OPEN or
CLOSED).
SIL specific safety-related characteristics:
Noise emissions
Max. 100 db (A) Product SSF PFDav λdd + λs λdu
Noise-reduced version max. 85 db (A) TZIDC with supply current 94 % 1.76 * 10-4 651 FIT 40 FIT
0 mA

For details refer to the Management Summary in the SIL


Safety Instructions 37/18-79XA.
Change from two to one column
14 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Specification
Electromagnetic compatibility

Component / Connection Disturbance variable EMC basic standard Test value Assessment criteria
Required Complied
Housing Discharge of static electricity (ESD) IEC 61000-4-2 4 kV Contact discharge B A
8 kV Air discharge B A
Electromagnetic fields* IEC 61000-4-3 10 V/m (80 MHz to 1 GHz) A A
3 V/m (1.4 GHz to 2 GHz) A A
1 V/m (2.0 GHz to 2.7 GHz) A A
Supply frequency magnetic fields IEC 61000-4-8 30 A/m (50 Hz, 60 Hz) A A
Input / Output signals Fast transients (burst) IEC 61000-4-4 2 kV (5 / 50 ns, 5 kHz) B A
Impulse voltage (surge) IEC 61000-4-5 1 kV (wire / wire), B A
2 kV (wire / PE)
Conducted HF signals IEC 61000-4-6 10 V (150 kHz to 80 MHz) A A
* The digital positioner meets the requirements of Class 3 for environments with heavy electromagnetic radiation. The distance between radio
transmitters (e.g. mobile telephones) and the digital positioner, as well as its input and output signals must be at least 1 m (3.3 ft).

Assessment criteria A:
The device must work as intended during and after the test.

Assessment criteria B:
Impairment in operating performance of the device is permitted during the test. The device must continue to work as intended
after the test.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 15


Electrical connections
Positioner / TZIDC Control Unit Electrical Connection

A Basic device C Connection TZIDC Remote Sensor / remote position sensor (only for
TZIDC Control Unit version)
B Options
D Options, limit value monitor with proximity switches or microswitches
(not for TZIDC Control Unit version)

Figure 12: TZIDC Electrical connection

Change from one to two columns

Connections for inputs and outputs

Terminal Function / comments Terminal Function / comments


+11 / −12 Analog input +51 / −52 Limit switch Limit 1 with proximity switch
+81 / −82 Binary input DI (optional)
+83 / −84 Binary output DO2 +41 / −42 Limit switch Limit 2 with proximity switch
+51 / −52 Digital feedback SW1 (optional)
(Option module) 41 / 42 / 43 Limit switch Limit 1 with microswitch
+41 / −42 Digital feedback SW2 (optional)
(Option module) 51 / 52 / 53 Limit switch Limit 2 with microswitch
+31 / −32 Analog feedback AO (optional)
(Option module)
1/2/3 TZIDC remote sensor Note
(Only for options TZIDC Remote Sensor or TZIDC for remote The TZIDC can be fitted either with proximity switches or
position sensor) microswitches as limit switches. It is not possible to combine
both variants. For the version TZIDC Control Unit with TZIDC
Remote Sensor, the limit switches are located in the TZIDC
Remote Sensor.
Change from two to one column
16 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Electrical connections
TZIDC Remote Sensor Electrical connection

A Basic device 1 Position sensor


B Options 2 Limit monitor with proximity switches (optional)
3 Limit monitor with microswitches (optional)

Figure 13: TZIDC Remote Sensor Electrical Connection

Change from one to two columns

Connections for inputs and outputs Digital input


Input for the following functions:
Terminal Function / comments • no function
1/2/3 TZIDC control unit • move to 0 %
+51 / −52 Proximity switches Limit 1 (Option)
• move to 100 %
+41 / −42 Proximity switches Limit 2 (Option)
• Hold previous position
• block local configuration
41 / 42 / 43 Microswitches Limit 1 (Option)
• block local configuration and operation
51 / 52 / 53 Microswitches Limit 2 (Option)
• block any access (local or via PC)

Note
Binary input DI
The TZIDC Remote Sensor can be fitted either with proximity
switches or microswitches as limit switches. It is not possible Terminals +81 / −82

to combine both variants. Supply voltage 24 V DC (12 to 30 V DC)


Input ‘logical 0’ 0 to 5 V DC

Electrical data for inputs and outputs Input ‘logical 1’ 11 to 30 V DC

Analog input Input Current Maximum 4 mA

Set point signal analog (two-wire technology) Binary output


Terminals +11 / −12
Output configurable as alarm output by software.
Nominal operating range 4 to 20 mA
Split range configuration between 20 to 100 % of the nominal operating Binary output DO

range can be parameterized Terminals +83 / −84

Maximum 50 mA Supply voltage 5 to 11 V DC

Minimum 3.6 mA (Control circuit in accordance with

Starting at 3.8 mA DIN 19234/NAMUR)

Load voltage 9.7 V at 20 mA Output ‘logical 0’ > 0.35 mA to < 1.2 mA

Impedance at 20 mA 485 Ω Output ‘logical 1’ > 2.1 mA


Direction of action Configurable
‘logical 0’ or ‘logical 1’
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 17

Module for analog feedback AO* Assembly kits for limit monitor
Without any signal from the positioner (e.g. ‘no power’ or Two proximity switches or microswitches for independent
‘initializing’) the module sets the output to > 20 mA (alarm signaling of the actuator position, switching points are
level). adjustable between 0 to 100%

Terminals +31 / −32 Limit monitor with proximity switches Limit 1, Limit 2
Signal range 4 to 20 mA (split ranges can be
parameterized) Terminals +41 / −42, +51 / −52
• in the event of an error > 20 mA (alarm level) Supply voltage 5 to 11 V DC
Supply voltage, two-wire technology 24 V DC (11 to 30 V DC) (Control circuit in accordance with DIN
19234/NAMUR)
Characteristic curve rising or falling (configurable) Direction of action Metal tag in proximity Metal tag outside
Deviation <1% switch proximity switch
Type SJ2-SN (NC; log 1) < 1.2 mA > 2.1 mA
Module for digital feedback SW1, SW2*
Limit monitor with 24 V microswitches Limit 1, Limit 2
Terminals +41 / −42, +51 / −52
Supply voltage 5 to 11 V DC Terminals +41 / −42, +51 / −52
(Control circuit in accordance with Supply voltage maximum 24 V AC/DC
DIN 19234 / NAMUR) Load rating Maximum 2 A
Output ‘logical 0’ < 1.2 mA Contact surface 10 µm Gold (AU)
Output ‘logical 1’ > 2.1 mA
Direction of action Configurable Mechanical position indicator
‘logical 0’ or ‘logical 1’ Indicator disk in enclosure cover linked with device feedback
Description 2 software switches for binary shaft.
position feedback (position
adjustable within the range of These options are also available for retrofitting by Service.
0 to 100 %, ranges cannot overlap)
* The module for analog feedback and the module for digital feedback
have separate slots and can be used together.
18 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Electrical connections
Wire cross-sectional areas Option modules

Basic device
Cross section
Rigid / flexible wires 0.14 to 1.5 mm2 (AWG26 to AWG17)
Electrical connections
Flexible with wire end sleeve 0.25 to 1.5 mm2 (AWG23 to AWG17)
4 to 20 mA input Screw terminals max. 2.5 mm2 (AWG14)
no plastic sleeve
Options Screw terminals max. 1.0 mm2 (AWG18)
Flexible with wire end sleeve 0.25 to 1.5 mm2 (AWG23 to AWG17)
with plastic sleeve
Cross section
Rigid / flexible wires 0.14 to 2.5 mm2 (AWG26 to AWG14)
Multi-wire connection capacity (two wire with the same cross-section)
Flexible with wire end sleeve 0.25 to 2.5 mm2 (AWG23 to AWG14)
Rigid / flexible wires 0.14 to 0.75 mm2 (AWG26 to AWG20)
Flexible with wire end sleeve 0.25 to 1.5 mm2 (AWG23 to AWG17)
Flexible with wire end sleeve 0.25 to 0.5 mm2 (AWG23 to AWG22)
no plastic sleeve
no plastic sleeve
Flexible with wire end sleeve 0.14 to 0.75 mm2 (AWG26 to AWG20)
Flexible with wire end sleeve 0.5 to 1 mm2 (AWG21 to AWG18)
with plastic sleeve
with plastic sleeve

Multi-wire connection capacity (two wire with the same cross-section)


Limit switch with proximity switches or 24 V microswitches
Rigid / flexible wires 0.14 to 0.75 mm2 (AWG26 to AWG20)
Rigid wire 0.14 to 1.5 mm2 (AWG26 to AWG17)
Flexible with wire end sleeve 0.25 to 0.75 mm2 (AWG23 to AWG20)
Flexible wire 0.14 to 1.0 mm2 (AWG26 to AWG18)
no plastic sleeve
Flexible with wire end sleeve 0.25 to 0.5 mm2 (AWG23 to AWG22)
Flexible with wire end sleeve 0.5 to 1.5 mm2 (AWG21 to AWG17)
no plastic sleeve
with plastic sleeve
Flexible with wire end sleeve 0.25 to 0.5 mm2 (AWG23 to AWG22)
with plastic sleeve

Change from two to one column


TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 19


Dimensions
All dimensions in mm (in)

Figure 14: Top view

1 Threaded hole M8 (10 mm [0.39 in] deep) 3 Threaded hole M5 × 0.5 (air outputs for direct mount)
2 Threaded hole M6 (8 mm deep [0.31 in]) 4 Sensor shaft (shown larger than scale)

Figure 15: Front and rear view


20 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Dimensions

1 Pneumatic connections, NPT ¼ in-18 oder G¼

Figure 16: Side view (from left to right)


Change from one to two columns

* Dimensions A and B depend on the rotary actuator


Figure 18: Mounting on rotary actuators in accordance with VDI / VDE 3845

Figure 17: Mounting to linear actuators in accordance with DIN / IEC 534

Change from two to one column

All dimensions in mm (in)


TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 21

Figure 19: Positioner TZIDC with mounted pressure gauge block and filter regulator
Change from one to two columns
22 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


Use in potentially explosive atmospheres
hange from one to two columns

General requirements
• The ABB positioner has been approved only for • In potentially explosive atmospheres, assembly may
appropriate and intended use in standard industrial be conducted only in compliance with locally
atmospheres. Any breach of this rule leads to a applicable installation regulations. The following
cancellation of warranty and manufacturer's conditions have to be observed (incomplete):
responsibility! - Assembly and maintenance may only be conducted
• Make sure that only devices which comply with the types if there is no explosion hazard in the area and you
of protection relevant to the applicable zones and have a hot work permit.
categories are installed. - The TZIDC may be operated in a fully mounted and
• All electric equipment has to be suited for the respective intact housing only.
intended use.

Notes for operation


Commissioning, Installation • The positioner must be integrated in the local potential
The ABB positioner has to be mounted in a major system. equalization system.
Depending on the degrees of IP-protection, an interval for • Only either intrinsically safe or non intrinsically safe
cleaning the equipment (dust settlement) has to be defined. circuits may be connected. A combination is not permit -
Strict care has to be taken that only devices which comply ted.
with the types of protection relevant to the applicable zones • If the positioner is operated with non intrinsically safe
and categories is installed. When installing the device, the circuits, later use for the intrinsic safety type of
locally applicable installation regulations, such as protection is not permitted.
EN 60079-14, must be observed.
Other important facts to be observed:
• The electric circuits of the positioner must be put into Use, operation
operation in all zones by persons qualified in
The TZIDC is approved for proper and intended use only. In
accordance with TRBS 1203. The details on the type
case of non-compliance, the warranty and manufacturer’s
label are mandatory for doing this.
liability do no longer apply!
• The device has been designed in accordance with IP 65
• Only those auxiliary components which fulfill all the
(optionally IP 66) and must be protected accordingly
requirements of European and national standards may be
against adverse ambient conditions.
used in potentially explosive atmospheres.
• The EC Type Examination Certificate has to be taken
• The ambient conditions specified in the operating
into account, including any special conditions defined
instruction must be strictly followed.
therein.
• The TZIDC is approved for proper and intended use in
• The device may only be used in accordance with its
standard industrial atmospheres only. Where aggressive
intended use.
substances are present in the air, the manufacturer has to
• The device may only be connected when de-energized.
be consulted.
• The potential equalization of the system must be
established in accordance with installation regulations
applicable in the respective country (VDE 0100,
part 540, IEC 364-5-54)).
• Circulating currents must not be guided through the
housing!
• Make sure that the housing is properly installed and
that its IP rating has not been compromised.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 23

Maintenance, repair
Definition of terms according to IEC 60079-17: • Maintenance and exchange work may be conducted by
Maintenance qualified specialists only, i.e., qualified personnel in
Defines a combination of actions performed to maintain or accordance with TRBS 1203 or similar.
restore the condition of an item such that the item meets the • Only those auxiliary components which fulfill all the
requirements of the relevant specification and performs its requirements of European and national guidelines and
required functions. regulations may be used in potentially explosive
I ¬Analyzer module without electronics module (power atmospheres.
supply): • Maintenance works that require disassembly of the
Defines an action which involves careful inspection of an item system may only be performed in non-hazardous areas. If
(either without disassembly or with partial disassembly, as that is not possible, however, the usual precautions have
required) supplemented by measurements, aimed at to be ensured according to local regulations.
achieving a reliable conclusion regarding the condition of the • Components may only be replaced by original spare parts
item. which are therefore approved for use in potentially
Visual inspection explosive atmospheres.
Defines an inspection which identifies defects which are • The device must be regularly cleaned when used in
visible to the naked eye, such as missing screws, without the potentially explosive atmospheres. The intervals must be
use of access equipment and tools. defined by the operator in compliance with the ambient
Close inspection conditions present at the operating location.
Defines an inspection which encompasses the aspects • After all maintenance and repair work has been
covered by a visual inspection and in addition, identifies completed, any barriers and plates removed for that
defects such as loose screws, which can only be detected purpose must be put back in their original place.
with the use of access equipment (e.g. steps) and tools. • The flameproof joints differ from the tables of
Detailed inspection IEC 60079-1 and may be repaired by the manufacturer
Defines an inspection which encompasses the aspects only.
covered by a close inspection and in addition, identifies
defects, such as loose connections, which can only be
detected by opening the housing and / or by using tools and
test devices, as needed.

Change from two to one column

Activity Visual inspection Close inspection Detailed inspection


(every 3 months) (every 6 months) (every 12 months)
Visual inspection of the positioner for integrity, removal of dust 
deposits
Inspection of electric installation for integrity and proper 
operation
Inspection of the entire installation Responsibility of the operator

Change from one to two columns


24 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Use in potentially explosive atmospheres
Product identification Preconditions for safe operation of the
Depending on the type of explosion protection, Ex-marking is positioner
attached to the positioner on the right, next to the main
name plate.
DANGER
This indicates the level of explosion protection and the Risk of explosion due to hot parts
device's relevant Ex certificate. Hot parts inside the device pose an explosion hazard.
• Never open the device immediately after switch-off.
• A waiting time of at least four minutes should be
Marking (name plate)
observed before opening the device.

When using in hazardous areas, observe the following points:


• Observe the specification and special conditions
applicable for the device in accordance with the
relevant valid certificate.
Figure 20: Marking • Manipulation of the device in any form by the user is
not permitted. Only the manufacturer or an explosion
Note protection specialist may modify the device
A legible marking showing the type of protection required for • The IP 65 / NEMA 4x IP rating is only achieved if the
the intended area of application must be affixed to the device splash guard is screwed in place. Operating the unit
before it is put into operation for the first time. without splash guard cap is prohibited.
• The device may only be operated using instrument air
that is free from oil, water and dust. The use of
flammable gas, oxygen, or oxygen-enriched gas is not
permitted.

Cable gland
Limited temperature range of the M20 × 1.5 plastic cable
gland for explosion protection variants.
The permissible ambient temperature range of the cable
gland is −20 to 80 °C (−4 to 176 °F). When using the cable
gland, make sure that the ambient temperature is within this
range. The cable gland must be installed in the housing with a
tightening torque of 3.8 Nm. When installing the connection
of the cable gland and cable, check for tightness to ensure
that the required IP rating is met.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 25

ATEX / EAC TR-CU-012 Electrical Data

(limited functionality with EAC TR-CU-012) In intrinsically safe explosion protection types Ex ib IIC /
Ex ia IIC or Ex ia IIIC, only for connection to a certified
ATEX Ex i intrinsically safe circuit.

Ex marking Current circuit (terminal) Electrical information (maximum values)


Marking II 2 G Ex ia IIC T6 resp. T4 Gb Signal circuit Ui = 30 V Ci = 6.6 nF
II 2 G Ex ib IIC T6 resp. T4 Gb (+11 / −12) Ii = 320 mA Li = negligibly small
Type Examination Test TÜV 04 ATEX 2702 X Pi = 1.1 W
Certificate Contact input Ui = 30 V Ci = 14.5 nF
Type Intrinsically safe equipment (+81 / −82) Ii = 320 mA Li = negligibly small
Device class II 2 G Pi = 1.1 W
Standards EN 60079-0:2012 Switch output Ui = 30 V Ci = 14.5 nF
EN 60079-11:2012 (+83 / −84) Ii = 320 mA Li = negligibly small
Pi = 500 mW
Temperature Data Mechanical limit monitor, Ui = 20 V
(Pepperl & Fuchs SJ2-SN) Ci = ≤ 30 nF

Device group II 2 G (Limit1: +51 / −52), Li = ≤ 100 µH


(Limit2: +41 / −42) Ii = 25 mA
Temperature class Ambient temperature Ta
Pi = 1.1 W
T4 −40 to 85 °C
Plug-in module for limit Ui = 30 V Ci = 3.7 nF
T5 −40 to 50 °C
monitor Ii = 320 mA Li = negligibly small
T6* −40 to 40 °C*
(+51 / −52) Pi = 250 mW
* When using the ‘Limit monitor’ plug−in module in temperature class T6,
(+41 / −42)
the maximum permissible ambient temperature range is −40 to 35 °C.
Plug-in module for analog Ui = 30 V Ci = 6.6 nF
position feedback Ii = 320 mA Li = negligibly small
(+31 / −32) Pi = 1.1 W
Interface with the TZIDC U0 = 5.4 V Ex ia or Ex ib type of
Remote Sensor I0 = 74 mA protection
(X2-2: +Uref, X3-2: GND, X3- P0 = 100 mW IIC:
1: signal) Ci = negligibly L0 = 5 mH
small C0 = 2 μF
Li = negligibly IIB:
small L0 = 5 mH
C0 = 10 μF
Local communication Only for connection to a programming device
interface (LCI) using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.

Special conditions
• Prevent electrostatic charging due to propagating brush
discharge when the equipment is used for applications
involving combustible dust.
26 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Use in potentially explosive atmospheres
IECEx Ex i
The following modules may be operated as an option:
Ex marking
Marking Ex ia IIC T6 or T4 Gb
Current circuit Electrical information (maximum values)
Ex ib IIC T6 or T4 Gb
(terminal)
Type Examination Test Certificate IECEx TUN 04.0015X
Plug-in module for Ui = 30 V Ci = 3.7 nF
Type Intrinsic safety ‘i’
limit monitor Ii = 320 mA Li = negligibly small
Standards IEC 60079-0:2011
(+51 / −52) Pi = 250 mW
IEC 60079-11:2011
(+41 / −42)
Plug-in module for Ui = 30 V Ci = 6.6 nF
Temperature Data
analog position Ii = 320 mA Li = negligibly small
feedback Pi = 1.1 W
Temperature class Ambient temperature Ta
(+31 / −32)
TZIDC Ex ia IIC TZIDC Ex ib IIC
T4 −40 to 85 °C −40 to 85 °C Special conditions
T6* −40 to 40 °C* −40 to 40 °C • For the ‘Limit monitor with proximity switches’ circuit,
* When using the ‘Limit monitor’ plug−in module in temperature class T6, measures outside of the device must be implemented to
the maximum permissible ambient temperature range is −40 to 35 °C. prevent the rated voltage from being up-scaled by more
than 40 % due to transient disturbances.
Electrical Data • It is only permissible to connect, disconnect, and switch
In ‘intrinsically safe Ex ib IIC / Ex ia IIC’ type of protection, live circuits during installation or maintenance, or for the
only for connection to a certified intrinsically safe circuit. purpose of carrying out repairs. Note: It is considered very
unlikely that a hazardous atmosphere would be present in
Current circuit Electrical information (maximum values) Zone 2 at the same time that installation, maintenance or
(terminal) repair work was being carried out.
Signal circuit Ui = 30 V Ci = 6.6 nF • Only non-flammable gases may be used for pneumatic
(+11 / −12) Ii = 320 mA Li = negligibly small power supply.
Pi = 1.1 W • Only use suited cable entries that meet the requirements
Contact input Ui = 30 V Ci = 14.5 nF of EN 60079-15.
(+81 / −82) Ii = 320 mA Li = negligibly small
Pi = 1.1 W
Switch output Ui = 30 V Ci = 14.5 nF
(+83 / −84) Ii = 320 mA Li = negligibly small
Pi = 500 mW
Local communication Only for connection to a programming device
interface (LCI) using an ABB LCI adapter (Um ≤ 30 V DC) outside
the hazardous area.
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 27

Change from two to one column


Ordering Information
Main ordering information TZIDC

Base model V18345 XX X X X X X XX X


TZIDC digital positioner, intelligent, configurable, with indicator and operator panel
Case / Mounting
Case made of aluminium, varnished, for mounting to linear actuators acc. DIN / IEC 534 / NAMUR or to
rotary actuators acc. VDI / VDE 3845 10
Case made of aluminium, varnished, with mechanical position indicator, for mounting to linear actuators
acc. DIN / IEC 534 / NAMUR or to rotary actuators acc. VDI / VDE 3845 20
Case made of aluminium, varnished, for integral mounting to control valves (see dimensional drawing) 30
Case made of aluminium, varnished, with mechanical position indicator, for integral mounting to control
valves (see dimensional drawing) 40
Remote sensor control unit 70*
Input / Communication Port
Input 4 bis 20 mA, two-wire, with connector plug for LCI adapter 1
Input 4 bis. 20 mA, two-wire, with connector plug for LCI adapter and FSK module for HART 2
communication
Explosion Protection
Without 0
ATEX II 2 G Ex ib IIC T6 resp. T4 Gb 1
FM / CSA 2**
IECEx Ex ib IIC T6 resp. T4 Gb 5
ATEX II 2 G Ex ia IIC T6 resp. T4 Gb 7
EAC TR-CU-012 Ex ia IIC T6/T4 Gb H**
EAC TR-CU-012 Ex ib IIC T6/T4 Gb J**
IECEx ia IIC T6 resp. T4 Gb K
NEPSI Ex ia II CT4/T5/T6 Gb U
NEPSI Ex ib II CT4/T5/T6 Gb V
INMETRO Ex ia IIC Gb / Ex ib IIC Gb P
Output / Safe Position (in case of an electrical power failure)
Single acting, fail safe 1
Single acting, fail freeze 2
Double acting, fail safe 4***
Double acting, fail freeze 5***
* With standard characteristic curve, if delivered without remote sensor
** Reduced Functionality
*** Not for for integral mounting

Continued see next page


28 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Ordering Information

TZIDC digital positioner, intelligent, configurable, with indicator and operator panel X X XX X
Connections
Cable: Thread ½-14 NPT, air pipe: Thread ¼-18 NPT 2
Cable: Thread M20 × 1.5, air pipe: Thread ¼-18 NPT 5
Cable: Thread M20 × 1.5, air pipe: Thread G ¼ 6
Cable: Thread G ½, air pipe: Thread Rc ¼ 7
Option Modules for Analog or Digital Position Feedback
Without 0
Plug-in module for analog position feedback, signal range 4 bis 20 mA, two-wire 1
Plug-in module for digital position feedback 3
Plug-in module for analog position feedback, signal range 4 bis 20 mA, two-wire, and digital position feedback 5
Optional Mechanical Kit for Digital Position Feedback
Without 00
Mechanical kit for digital position feedback with proximity switches SJ2-SN (NC or logical 1) 10*
Mechanical kit for digital position feedback with 24 V AC / DC microswitches (change-over contacts) 50**
Design (Varnish / Coding)
Standard 1
Higher Stiffness + Lower Air Capacity H***
Protection Class IP 66 / NEMA 4X P
Increased Corrosion Protection S
* Only for model with mechanical position indicator, no IECEx
** Not for explosion protected version and only for model with mechanical position indicator
*** Only with Type Double Acting

Continued see next page


TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 29

Additional ordering information TZIDC

Additional ordering information XX XXX XXX


Documentation Language M1
German M2
Italian M3
Spanish M4
French M5
English M7
Swedish M8
Finnish M9
Polish MA
Portuguese MB
Russian MC
Czech MD
Dutch MF
Danish MG
Greek MH
Croatian ML
Latvian MM
Hungarian MO
Estonian MP
Bulgarian MR
Romanian MS
Slovak MU
Lithuanian MV
Slovenian M1
SIL2 - Declaration of Conformity
SIL2 - Declaration of Conformity CS2*
Certificate of Compliance
Certificate of compliance with the order acc. EN 10204-2.1 (DIN 50049-2.1) with item CF2
description
Test report 2.2 acc. EN 10204 (DIN 50049-2.2) CF3
Ships Register Certifications DNV_GL CM1
* With single acting, fail safe pneumatic only
30 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Ordering Information

Additional ordering information XXX XXX XXX XXX XXX XX XX XX XX XX


Inspection Certificate
Inspection certificate 3.1 acc. EN 10204 CBA
Handling of Certificates
Send via e-mail GHE
Send via mail GHP
Send via mail express GHD
Send with instrument GHA
Only archived GHS
Certificate preparation
Per device GPD
Per salesorder item GPP
Device Identification Label
Stainless steel 18.5 × 65 mm (0.73 × 2.56 in) MK1*
Sticker 11 × 25 mm (0.43 × 0.98 in) MK3
Special Option Cable Gland
With cable gland ZG1
Remote Sensor
Basic unit RS**
Basic unit with position indicator RD**
Remote Sensor Temperature Range
Extended ambient temperature range −40 to 100 °C (−40 to 212 °F) RT**
Remote Sensor Vibration Resistance
Advanced vibration range 2 g @ 300 Hz RV**
Remote Sensor Protection Class
Protection class IP 67 RP**
Remote Sensor Cable
5 m cable enclosed R5**
10 m cable enclosed R6**
* Plain text, max. 16 letters
** Only with remote sensor control unit
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 31

Accessories

Accessories Order number


Communication
LCI adapter with USB interface – only for TZIDC Rev. 5 3KXE000128U0100
Mounting bracketole
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 80/20 mm 319603
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 80/30 mm 319604
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 130/30 mm 319605
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 130/50 mm 319606
Montage Kit
EDP300 / TZIDC Mounting Kit Uhde Type 4 Stroke 400 mm cropped 7959500
Attachment kit for linear actuators
EDP300 / TZIDC Attachment kit for linear actuators, stroke 10 to 35 mm 7959125
EDP300 / TZIDC Attachment kit for linear actuators, stroke 20 to 100 mm 7959126
Lever
EDP300 / TZIDC Lever 30 mm 7959151
EDP300 / TZIDC Lever 100 mm 7959152
Adapter
EDP300 / TZIDC Adapter (shaft coupler) for rotary actuators (mounting to VDI / VDE 3845) 7959110
EDP300 / TZIDC Form – locking shaft adapter 7959371
Pressure gauge block
TZIDC Pressure gauge block, single acting, black, 2 pressure gauges 28 mm, connectors G ¼ in, 1 × 0 to 10 bar / 0 to 140 psi for 7959112
air supply, 1 × 0 to 10 bar / 0 to 140 psi for output pressure, including attachments
TZIDC Pressure gauge block, 0.6 MPa, single acting, G ¼ connection 7959364
TZIDC Pressure gauge block, 0.6 MPa, single acting, Rc ¼ connection 7959358
TZIDC Pressure gauge block, 0.6 MPa, single acting, NPT ¼ connection 7959360
TZIDC Pressure gauge block, single acting, black, 2 pressure gauges 28 mm, connectors ¼ in NPT, 1 × 0 to 10 bar / 0 to 140 psi 7959114
for air supply, 1 × 0 to 10 bar / 0 to 140 psi for output pressure, including attachments
TZIDC Pressure gauge block, double acting, black, 3 pressure gauges 28 mm, connectors G ¼ in, 1 × 0 to 10 bar / 0 to 145 psi for 7959116
air supply, 2 × 0 to 10 bar / 0 to 145 psi for output pressure, including attachments
TZIDC Pressure gauge block, 0.6 MPa, double acting, G ¼ connection 7959365
TZIDC Pressure gauge block, 0.6 MPa, double acting, Rc ¼ connection 7959359
TZIDC Pressure gauge block, 0.6 MPa, double acting, NPT ¼ connection 7959361
TZIDC Pressure gauge block, double acting, black, 3 pressure gauges 28 mm, connectors ¼ in NPT, 1 3 0 to 10 bar / 0 to 140 psi 7959118
for air supply, 2 × 0 to 10 bar / 0 to 140 psi for output pressure, including attachments
TZIDC Pressure gauge block, double acting, black, 3 pressure gauges stainless steel 28 mm, connectors ¼ in NPT, 1 × 0 to 10 bar 7959185
/ 0 to 140 psi for air supply, 2 × 0 to 10 bar / 0 to 140 psi for output pressure, incl. attachments
TZIDC Filter regulator, brass, connections thread G ¼, incl. material for mounting to pressure gauge block 7959119
TZIDC Filter regulator, brass, connections thread ¼-18 NPT, incl. material for mounting to pressure gauge block 7959120
TZIDC Pressure gauge block black, 2 pressure gauges stainless steel 28mm, Connectors G¼ in, 1 × 0 to 10 bar / 0 to 140 psi for
air supply, 1 × 0 to 10 bar / 0 to 140 psi for output press, single acting, G ¼, 0 to 10 bar, incl. attachments 7959179
TZIDC Pressure gauge block black, 2 pressure gauges stainless steel 28mm, Connectors G¼in, 1 × 0 to 10 bar / 0 to 140 psi for
air supply, 1 × 0 to 10 bar / 0 to 140 psi for output press, double acting, G ¼, 0 to 10 bar, incl. attachments 7959183
32 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


… Ordering Information

Accessories Order number


Attachment kit
EDP300 / TZIDC Attachment kit for Fisher 1051-30, 1052-30 7959214
EDP300 / TZIDC Attachment kit for Fisher 1061 size 130 7959206
EDP300 / TZIDC Attachment kit for Fisher 471 7959195
EDP300 / TZIDC Attachment kit for Fisher 657 / 667 Size 10 to 90 mm 7959177
EDP300 / TZIDC Attachment kit for Fisher Gulde 32/34 7959344
EDP300 / TZIDC Attachment kit for Gulde DK 7959161
EDP300 / TZIDC Attachment kit for Keystone 79U/E-002(S) ... 79U/E-181(S) 7959147
EDP300 / TZIDC Attachment kit for Masoneilan CAMFLEX II, VARIMAX, MINITORK II 7959144
EDP300 / TZIDC Attachment kit for Masoneilan VariPak 28000 series 7959163
EDP300 / TZIDC Attachment kit for MaxFlo MaxFlo 7959140
EDP300 / TZIDC Attachment kit for NAF 791290 7959207
EDP300 / TZIDC Attachment kit for NAMUR stroke 100 to 170 mm 7959339
EDP300 / TZIDC Attachment kit for NELES BC6-20, B1C6-20, BJ8-20, B1J8-20 7959146
EDP300 / TZIDC Attachment kite, lever for linear stroke, length 150 to 250 mm 7959210
TZIDC Attachment kit for Valves Nuovo Pignone, pressure gauge block with 2 manometers, material stainless steel single acting,
¼ in NPT, 0 to 10 bar 7959181
EDP300 / TZIDC Attachment kit for Samson 241, 271, 3271 7959145
EDP300 / TZIDC Attachment kit for Samson 3277 7959136
EDP300 / TZIDC Attachment kit for Schubert&Salzer GS 8020 / 8021 / 8023 7959200
EDP300 / TZIDC Attachment kit for SED SED stroke 100 mm 7959141
EDP300 / TZIDC Attachment for remote sensor control unit (for wall or pipe mounting) 7959381
TZIDC Mounting kit TZIDC-200 Lever 30 mm 7959262
TZIDC Attachment Kent Introl 170 mm 7959376
TZIDC Attachment Kent Introl 250 mm 7959377

Change from one to two columns


TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 33


Trademarks
HART is a registered trademark of FieldComm Group, Austin, Texas, USA

Sales Service
34 TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E


Notes
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. E 35

ABB Measurement & Analytics

For your local ABB contact, visit:


www.abb.com/contacts

For more product information, visit:


www.abb.com/positioners


DS/TZIDC-EN Rev. E 05.2020

We reserve the right to make technical changes or modify the contents of this document without
prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.

We reserve all rights in this document and in the subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB.

© ABB 2020 3KXE341201R1001

You might also like