Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

IntelliVAC Contactor Control Module 1503VC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

IntelliVAC

Contactor
Control Module
Bulletin 1503VC

User Manual

Important User Information


Read this document and the documents listed in the Additional Resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.


SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents
Product Description

Chapter 1
Introduction ..............................................................................1-1
Description ...............................................................................1-1
IntelliVAC Features ......................................................... 1-2
IntelliVAC Versions ......................................................... 1-3
Specifications .......................................................................... 1-4
Mounting and Connections .............................................. 1-4
Configuration ................................................................... 1-4
Firmware .......................................................................... 1-4
Electrical Ratings (Table 1.A) .......................................... 1-5
Mechanical Ratings (Table 1.B) ....................................... 1-6
Altitude Derating (Table 1.C) .......................................... 1-6

Receiving and Storage

Chapter 2
Receiving ............................................................................... 2-1
Storage .................................................................................... 2-1

Installation and Wiring

Chapter 3
General Precautions ................................................................ 3-1
Safety and Codes .................................................................... 3-1
Arrangements .......................................................................... 3-2
Integral to an Allen-Bradley MV Controller .................... 3-2
OEM ................................................................................. 3-3
Fuse Protection ....................................................................... 3-6
Grounding ............................................................................... 3-6
Connections ............................................................................ 3-7
Control Power .................................................................. 3-7
Status Relays .................................................................... 3-7
Interface Connections ....................................................... 3-8
Wiring Guidelines Electrically Held Contactors .................. 3-10
Two-Wire Control .......................................................... 3-11
Three-Wire Control ........................................................ 3-12
Wiring Guidelines Mechanically Latched Contactors .......... 3-14
Mechanically Latched Contactors ........................................ 3-15
Capacitor Trip ................................................................ 3-14
Motor Jogging Control ......................................................... 3-17
Time Delay Undervoltage ..................................................... 3-18

1503-UM051D-EN-P June 2013

ii

Table of Contents

Setup and Commissioning

Chapter 4
IntelliVAC Configuration ....................................................... 4-1

Monitoring & Troubleshooting

Chapter 5
Introduction .............................................................................
Module Status .........................................................................
Contactor Status ......................................................................
Series B Design ................................................................

Spare Parts

5-1
5-1
5-2
5-2

Chapter 6
Spare Parts List ....................................................................... 6-1
Optional Equipment ......................................................... 6-1

Appendix A

Typical Contactor Drop-out Times


Table A.1 Contactor Drop-out Times ................................. A-1

1503-UM051D-EN-P June 2013

Chapter

Product Description
Introduction

This document contains information for the Allen-Bradley Bulletin


1503VC IntelliVAC control module. The Bulletin 1503VC is
used to control the Allen-Bradley Bulletin 1502 vacuum contactors
that are a significant component of the Bulletin 1500/1900
Centerline Medium Voltage Motor Controllers offered by
Rockwell Automation.
An IntelliVAC control module may also be provided as a loose
component, for application with a Bulletin 1502 contactor by a
third party (OEM).

Description

IntelliVAC is an efficient and flexible solution for controlling


medium voltage vacuum contactors used in motor starter and
feeder applications. IntelliVAC may be used to control both 400
and 800 Amp contactors. Electrically held and mechanically
latched contactor types can be controlled with IntelliVAC.

Figure 1.1 IntelliVAC Contactor Control Module

1503-UM051D-EN-P June 2013

1-2

Product Description

Description (cont.)
External
Capacitor
(Optional)

Coil
Power
Supply

Current
Regulator

Control
Power
Supply

C
C

IGBT Coil
Switching

Close
Signal

Contactor Coil(s) Interface


Coil Current Transducer

Input
Power
Conditioning

Supply
Voltage
110-240
VAC
or
110-250
VDC

Vacuum Contactor
Trip Coil

Command
Inputs

Open
Signal

Vacuum Contactor
Auxiliary

Micro Controller

CC

Aux.
Feedback

Altitude
Select

Vacuum Contactor
Close Coil

Drop-Out
Select

c
c
c

c
c
c

Status
Outputs

TDUV
Time
Select

Module
Status

Configuration
Inputs
(DIP
switches)

Contactor
Select

Flash EEPROM
Interface

c
c

Power Up
Safety

Contactor
Status

Figure 1.2 IntelliVAC Block Diagram

IntelliVAC Features

1503-UM051D-EN-P June 2013

A wide range of supply voltage (110 240 V AC 50/60 Hz,


110 - 250 V DC) allows implementation in multiple applications

Consistent vacuum contactor pick-up time (at a given supply


voltage) ensures repeatable performance

Selectable vacuum contactor drop-out time improves


coordination with upstream power fuses

Electronic altitude compensation (400 A only) eliminates


mechanical compensation required for altitudes above 1,000
meters (800 A contactors include a user-friendly altitude
adjustment)

Power loss ride-through (TDUV) allows the vacuum contactor


to remain closed during short power loss (may require an
optional external capacitor, dependant on ride-through time)

Product Description

1-3

IntelliVAC Features (cont.)

Anti-kiss and anti-pumping protection ensure that the vacuum


contactor close open sequence occurs as expected, avoiding
rapid re-closure due to faulty control devices

Delayed restart protects the vacuum contactor by ensuring that


the rated duty cycle is not exceeded

Temporary jog function (electrically held contactors only)


allows the motor to be positioned for process set-up

IntelliVAC Versions
Series A

There are two versions of IntelliVAC control. The


first type is used to control vacuum contactors that
are electrically held, with a single electrical coil
that is economized electronically. The second is
used to control mechanically latched vacuum
contactors.

Series B

There is a single version of IntelliVAC, to control


both electrically held and mechanically latched
vacuum contactors.

Refer to Chapter 6, for catalog numbers for each version of


IntelliVAC.
A Series B IntelliVAC module can be used to replace a Series A
module.

1503-UM051D-EN-P June 2013

1-4

Product Description

Specifications

Mounting & Connections


The IntelliVAC control modules are mounted using two (2) screws
(see Figure 1.3). They are typically located in the low voltage
control panel of the medium voltage controller (Bulletin 1500/1900
controllers, in the case of Rockwell Automation).
IntelliVAC is interfaced to the Bulletin 1502 vacuum contactors
using a quick connector, located at the module, a wire harness
and quick connector at the contactor. Control power and other
control circuit connections are similarly achieved with quick
connectors.

Configuration
IntelliVAC is easily configured for a wide variety of medium
voltage motor and feeder control applications. It is configured
using DIP switches, located within the enclosure (front side).
Please refer to Chapter 4 for information.
Bulletin 1500/1900 controllers are shipped with IntelliVAC preconfigured for the required application. Please refer to the
documents provided with the order.

Firmware
IntelliVAC has firmware stored in flash EEPROM; therefore, this
may be updated in the field (if necessary). The IntelliVAC board
firmware is updated using the mini-DIN connector, which is
accessible inside the enclosure.

1503-UM051D-EN-P June 2013

Product Description

1-5

Table 1.A Electrical Ratings


Main Input Voltage
(L1 to L2/N)

AC 110 to 240 V rms, +10/-15%, 47 to 63 Hz


DC 110 to 250 V, +10/-15%
Description

Main Input Current


(L1 to L2/N)

Contactor Ratings Control Voltage


(Amps)
(AC or DC)
400/800

120/240

25 A peak
(1/2 cycle)

25 A peak

Idle Current
(Maximum without contactor
coil energized)

400/800

120/240

125 mA

35 mA

Hold Current (maximum)

400/800

120/240

300 mA

100 mA

120

4.6 A

3.6 A

240

3.4 A

3.3 A

120

11.3 A

4.8 A

240

8.9 A

4.5 A

120

7.0 A

3.7 A

240

3.6 A

2.0 A

120

7.0 A

3.3 A

240

4.3 A

1.9 A

Close Current

Trip Current (latch)

400
800

400

(0.2 sec)
800

Command Inputs
\

AC 100 to 240 V rms


DC 24 to 250 V
Maximum on state current for open or close command:
9mAAC @ 250 V AC, 60Hz, TA=60C
9mADC @ 250 V DC, TA=60C
Minimum on state current for open or close command:
2mAAC @ 100 V AC, 60Hz, TA=60C
600ADC @ 24 V DC, TA=60C
Maximum off state current for open or close command:
400AAC @ 11 V AC, 60Hz, TA=60C
400ADC @ 15 V DC, TA=60C

Status Output
Contacts

AC 250 V rms, 5 A, R load; 2 A (reactive), PF=0.4


DC 30 V, 5 A, R load; 2 A (reactive), L/R=7 ms

Standards and
Approvals

CE , cULus, CSA, IEC pending

DC Rating

Inrush Current

(0.2 sec)

AC Rating

TA = Ambient Temperature
Refer to Chapter 6 for suitable EMC filter needed to meet CE requirements.
Also refer to Chapter 3 for EMC filter installation guidelines.
Please consult Factory for DC input current ratings.
Includes idle current.
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed.

1503-UM051D-EN-P June 2013

1-6

Product Description

Specifications (cont.)

Table 1.B Mechanical Ratings


Temperature

Operating: 0 to 60C ambient at the control module X


Non-Operating: -40 to 85C

Altitude

-1000 to 5000 meters

Pollution

Pollution level II (as defined by UL 840 and IEC 60664-1)

Humidity

Class II

Shock and
Vibration
(Operational)
X

Shock 15 g peak, 11 milliseconds


Vibration 10 to 57 Hz, 0.015 inch displacement peak to peak
- 57 to 150 Hz, 2.5 g acceleration

Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet).


Please refer to Table 1.C.

Table 1.C Altitude Derating

X
Y

Altitude

DIP Switch Setting 1, 2, 3 X

Maximum Operating Ambient


at the control module (C) Y

-1000 to 0

000

60

1 to 1000

001

60

1001 to 2000

010

58

2001 to 3000

011

56

3001 to 4000

100

54

4001 to 5000

101

52

Refer to Chapter 4.
Derate by 2C / 1000 m for high altitude operation

5.1 (0.20)

29.7
(1.17)

165.9 (6.53)

5.8 (0.228)
2 places
174.8
(6.88)
185.3
(7.29)

59.4
(2.34)

Dimensions in mm (inches)

Figure 1.3 Mechanical Dimensions

1503-UM051D-EN-P June 2013

Chapter

Receiving and Storage

Receiving

Upon receiving the controller, remove the packing and check for
damage that may have occurred during shipping. Report any
damage immediately to the claims office of the carrier.
NOTE: If the IntelliVAC module is an integral component of a
complete MV controller (Bulletin 1500/1900), special receiving
and handling instructions will apply. For details, refer to the
service manual provided with the equipment.

Storage

It is important to consider the following storage requirements if you


are not installing your controller immediately after receiving it.
Store the controller in a clean, dry, dust-free environment.
Storage temperature should be maintained between -40C and
85C (-40F and 185F).
Relative humidity must not exceed 95%, non-condensing.

1503-UM051D-EN-P June 2013

2-2

Receiving and Storage

(This page is intentionally left blank.)

1503-UM051D-EN-P June 2013

Chapter

Installation and Wiring


General Precautions

In addition to the precautions listed throughout this manual, the


following statements, which are general to the system, must be read
and understood.
ATTENTION

ATTENTION

ATTENTION

Safety and Codes

ATTENTION

The controller contains ESD (electrostatic


discharge) sensitive parts and assemblies.
Static control precautions are required when
installing testing, servicing, or repairing the
assembly. Component damage may result if
ESD control procedures are not followed. If
you are not familiar with static control
procedures, refer to applicable ESD
protection handbooks.
An incorrectly applied or installed controller
can damage components or reduce product
life. Wiring or application errors, such as
incorrect or inadequate AC supply, or
excessive ambient temperatures, may result
in malfunction of the system.
Only personnel familiar with the controller
and associated machinery should plan or
implement the installation, start-up, and
subsequent maintenance of the system.
Failure to do this may result in personal
injury and/or equipment damage.

The Canadian Electrical Code (CEC),


National Electrical Code (NEC), or other
local codes outline provisions for safely
installing electrical equipment. Installation
MUST comply with specifications regarding
wire type, conductor sizes, branch circuit
protection, interlocking and disconnect
devices. Failure to do so may result in
personal injury and/or equipment damage.

1503-UM051D-EN-P June 2013

3-2

Installation and Wiring

Arrangements

The IntelliVAC is offered in two arrangements, Integral (part of a


Bulletin 1500/1900 MV controller) or as an OEM component.

Integral to an Allen-Bradley MV Controller


The IntelliVAC is available as a primary component of an AllenBradley Bulletin 1500/1900 MV controller as shown in Figure 3.1.

Figure 3.1 - Typical IntelliVAC Installation within a Bulletin 1500/1900 MV Controller


(Shown with optional external capacitor)

1503-UM051D-EN-P June 2013

Installation and Wiring

3-3

OEM
The IntelliVAC may be ordered as an OEM component. This allows
the OEM to mount the components in a configuration most suitable
to the motor controller equipment layout. Care must be exercised to
ensure the IntelliVAC has adequate ventilation provided around it.
Refer to Figure 3.2 for mounting the IntelliVAC. It is recommended
that a minimum of 1.5 inches (38.1mm) of free air space be provided
between the IntelliVAC and any solid barrier above or below.
The OEM is responsible for controller fusing, motor overload
protection, control devices (eg. Start/Stop push buttons), and wiring
between the IntelliVAC and 1502 vacuum contactor (using optional
wire harness). Wiring and mounting for optional items, such as
TDUV Capacitor are also the OEMs responsibility. Refer to Figure
3.3 or 3.4 for basic connections.
An optional EMI filter is required to meet CE EMC requirements
(refer to Chapter 6 for recommended type).
Minimum top clearance
38.1
(1.50)

Dimensions in mm (inches)

38.1
(1.50)
Minimum bottom clearance

6.4 (0.25)

Additional Modules
(as required)

Figure 3.2 Typical Mounting Configurations

Note: Adjacent IntelliVAC modules may be mounted with a


minimum separation of 6.4 mm (0.25 inches).

1503-UM051D-EN-P June 2013

3-4

Installation and Wiring

Arrangements (cont.)
CONTROL POWER

M-INTELLIVAC

CONTROL
POWER
FUSE

7 +

9 +
OVERLOAD

STOP

- 8

OPEN

CLOSE

START
16

- 10

CONTACTOR
STATUS

15

14

MODULE
STATUS

CAPACITOR
(OPTIONAL)

13

1 EC
2 +

TCO

4
3

11
AUX
12

CCO

6
5

MOV
M

CONFIGURATION
DIP SWITCHES

L1

INPUT POWER
G
L2/N

Refer to Table 3.A for recommended fuse sizing.

Figure 3.3 IntelliVAC Typical Schematic (Electrically Held Vacuum Contactor)


Without Optional EMC Filter

1503-UM051D-EN-P June 2013

Installation and Wiring

3-5

CONTROL POWER
M-INTELLIVAC

CONTROL
POWER
FUSE

7 +

9 +
OVERLOAD

STOP

- 8

OPEN

- 10

CLOSE

START
16

CONTACTOR
STATUS

15

14

MODULE
STATUS

CAPACITOR
(OPTIONAL)

13

1 EC
2 +

TCO

4
3

11
AUX
12

CCO

6
5

MOV
M

CONFIGURATION
DIP SWITCHES

L1
P'
P

INPUT POWER
G
L2/N
EMC FILTER
G

N'
N

Refer to Table 3.A for recommended fuse sizing.

Figure 3.4 IntelliVAC Typical Schematic (Electrically Held Vacuum Contactor)


With Optional EMC Filter

1503-UM051D-EN-P June 2013

3-6

Installation and Wiring

Fuse Protection

The IntelliVAC module requires external fuse protection to


coordinate with the power supply and contactor. The fuse ratings
shown in Table 3.A allow the passage of inrush currents expected
when the contactor is closed, or from recommended external
capacitors for the TDUV option. They will also protect the contactor
coils in the event of a module malfunction.
The recommended fuses have been tested to ensure reliable
protection of the module. If the supply voltage is DC, the module
must be used with an external fuse that is approved for and rated to
interrupt the DC voltage supply. The types listed are Ferraz-Shawmut
Midget Fuses (1-1/2" X 13/32"). The TRM is a time-delay type,
rated 250 VAC. The ATM is a fast-acting type, rated 500 VDC.
Table 3.A IntelliVAC Fuse Protection
Rated Supply Voltage

110/120 VAC

220/240 VAC
125 VDC
250 VDC

Contactor Type

400A EH
800A EH
400/800A ML
400A EH
800A EH
400/800A ML
400A EH/ML
800A EH/ML
400A EH/ML
800A EH/ML

Recommended Fuse
(minimum)
TRM 2
TRM 2
TRM 2
TRM 2
TRM 2
TRM 2
ATM 3
ATM 5
ATM 3
ATM 5

(maximum)
TRM 3.2
TRM 6.25
TRM 3.2
TRM 6.25
TRM 6.25
TRM 6.25
ATM 3
ATM 6
ATM 5
ATM 6

EH = Electrically Held vacuum contactor


ML = Mechanically Latched vacuum contactor

Grounding

The IntelliVAC module must be connected to a common ground


terminal (PE) on the controller panel. The ground terminal is located
on top of the module enclosure for Series A design (refer to Figure
3.7), and on the bottom of module enclosure for Series B design,
(refer to Figure 3.6)
ATTENTION

1503-UM051D-EN-P June 2013

It is important that IntelliVAC is properly


grounded using the ground connection
provided. Failure to do so may result in
damage to equipment or personal injury.

Installation and Wiring

Connections

3-7

There are three green connectors on the IntelliVAC module for


connections to the control circuitry. Connector plugs are provided
with the module. If additional plugs are required, refer to Chapter 6,
Spare parts.

Control Power
The IntelliVAC can accept either AC or DC control power. Refer to
Table 1.A for acceptable input power and control signal ratings.
Control power is applied to the module with a two-pole connector
located at the bottom rear portion of the module. Refer to Figures
3.5 and 3.6 for connections. The L1 connection is intended to be
the Hot or + side of the control power, and the L2/N connection
is intended to be the Neutral, Return, or - side of the control
power.
In order to meet CE electromagnetic interference requirements, an
external EMC filter must be installed. Refer to Chapter 6 for suitable
EMC filter part number and install per Figure 3.4.

Status Relays
Status relay connections are accessed with a four-pole connector
located at the bottom front portion of the module. Refer to Figure
3.5 or 3.6 for connections. There are two status relays, each with one
normally-open contact:
Module Status:
Contactor Status:

Terminals 13 and 14
Terminals 15 and 16

Refer to Chapter 5 Monitoring and Troubleshooting for a description


of operation for the relays.
Refer to Table 1.A for electrical ratings of the status relays.

13

14

15

16
CONTACTOR STATUS OUTPUT (N.O.)

L1 L2/N
MODULE STATUS OUTPUT (N.O.)

POWER INPUT

Figure 3.5 Bottom side connections (Series A)

1503-UM051D-EN-P June 2013

3-8

Installation and Wiring

Connections (cont.)

Interface Connections
Ground Connection

13 14 15 16

L1 L2/N

CONTACTOR STATUS OUTPUT (N.O.)

MODULE STATUS OUTPUT (N.O.)

POWER INPUT

Figure 3.6 Bottom side connections (Series B)

Interface Connections
All other control interface connections are made at a twelve-pole
connector located on the top of the module. Refer to Figure 3.7 or
3.8 and Table 3.B for connections. Refer to the Wiring Guidelines
section in this chapter for guidance in making connections to the
control circuit.

10 11 12

EX. CAP. CONTACTOR INTERFACE

Ground Connection

Figure 3.7 Top side connections (Series A)

9 10 11 12

EX. CAP. CONTACTOR INTERFACE

Figure 3.8 Top side connections (Series B)

1503-UM051D-EN-P June 2013

Installation and Wiring

3-9

Table 3.B Terminal Assignments for IntelliVAC Interface Connections X


Terminal No.

X
Y
Z

Terminal Designation

External capacitor (negative) Y

External capacitor (positive) Y

Latch trip coil (common) Y

Latch trip coil Y

Close coil (common)

Close coil

Open / Jog command Y Z

Open / Jog command (common) Y Z

Close command Z

10

Close command (common) Z

11

Contactor auxiliary contact Z

12

Contactor auxiliary contact Z

Description

Power connection for TDUV or capacitor


trip options only
Output for mechanical latch contactor trip
coil
Output to close coil of electrically held &
mechanical latch contactors
Input to open a mechanical latch contactor
or jog an electrically held contactor
(mutually exclusive)
Input to initiate the closure of electrically
held & mechanical latch contactors
Input to indicate the state of the contactor
(typically wired to a normally closed
auxiliary contact)

Refer to Table 1.A for electrical ratings.


No connection required if option is not used.
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors).
Consult factory for assistance, if needed.

1503-UM051D-EN-P June 2013

3-10

Installation and Wiring

Wiring Guidelines
Electrically Held
Contactors

The IntelliVAC can be applied with two- or three-wire control


circuits. The control system utilized will determine the configuration
of the input wiring. Consider the following input and output for the
type of control used:
Terminals 9 and 10
Terminals 15 and 16

Close Contactor
Contactor Status

In either case, the CLOSE input must receive a maintained voltage


high to keep the contactor closed.
Note:
1. When used with electrically held contactors, the IntelliVAC
allows close commands every six seconds. This is to ensure the
rated contactor duty cycle is not exceeded.
2. If a contactor close command is applied and then removed in less
than 500 milliseconds the IntelliVAC may fault. To clear the
fault, module power has to be removed and reapplied.
3. If IntelliVAC powers up configured for an electrically held
contactor, and the vacuum contactor is detected as being closed,
the module will not respond to a close command until the vacuum
contactor auxiliary contact input is in the correct (open) state and
module power is removed and re-applied. (See Chapter 5). This
is true if the power-up safety DIP switch is enabled.
4. In general, a Close command should only be applied 4 seconds
after energizing IntelliVAC.

1503-UM051D-EN-P June 2013

Installation and Wiring

3-11

Two-Wire Control
If using two-wire control, the CLOSE contactor input is maintained
high using a single contact. Momentarily opening this input will
cause the IntelliVAC to open the contactor. Maintaining the contact
will provide a CLOSE command to IntelliVAC (given that all
permissives are satisfied). If a fault occurs, in addition to cycling
control power to the IntelliVAC module, the CLOSE command must
be removed for a minimum of 4 seconds, before being re-applied.
Refer to Figure 3.9.
Some two-wire control schemes may be configured such that a close
command is present when IntelliVAC is energized. In this case, the
Power-Up Safety feature may be disabled by setting DIP switch 12
accordingly. (Available with an IntelliVAC using firmware 2.001
(or newer) refer to Table 4.B).
Note: Only disable the Power-Up safety feature when absolutely
necessary. Doing so can create unsafe operating conditions.
CONTROL POWER
CAPACITOR
(OPTIONAL)

CONTROL
POWER
FUSE

1 EC
2 +
11
AUX
12
L1
P'
P

TCO

4
3

CCO

6
5

G
EMC FILTER
G

MOV
M

L2/N
N'
N

RUN

OVERLOAD

M-IV

Refer to Table 3.A for recommended fuse sizing.

M-IV
9 + - 10
CLOSE

Figure 3.9 Two-Wire Control

1503-UM051D-EN-P June 2013

3-12

Installation and Wiring

Wiring Guidelines
Electrically Held
Contactors (cont.)

Three-Wire Control
If using three-wire control, the CLOSE contactor input is maintained
high using two contacts. Momentarily opening this input will cause
the IntelliVAC to open the contactor. Momentarily closing the
START contact will provide a CLOSE command to IntelliVAC
(given that all permissives are satisfied).
In this configuration, the STATUS output acts as a seal-in contact. If a
fault occurs, in addition to cycling control power over to the IntelliVAC
module, the CLOSE command must be removed for a minimum of 4
seconds before being re-applied. Refer to Figure 3.10.

CONTROL POWER
CAPACITOR
(OPTIONAL)

*
CONTROL
POWER
FUSE

1 EC
2 +

11
AUX
12
L1
P'
P

OVERLOAD

M-IV

STOP

TCO

4
3

CCO

6
5

MOV
M

L2/N

EMC FILTER
G

N'
N

START

9 + - 10

M-IV

Refer to Table 3.A for recommended fuse sizing.

15

CLOSE

16

CONTACTOR
STATUS

Figure 3.10 Three-Wire Control

1503-UM051D-EN-P June 2013

M-IV

Installation and Wiring

3-13

15mS
CLOSE COMMAND
TO MICRO

DEBOUNCE
80mS

15mS
DEBOUNCE

Y
5mS

CLAMP DELAY

MICRO OUTPUT
TO CLOSE COIL

200mS

CLOSE LEVEL OF
CURRENT TO CLOSE
COIL

CONTACTOR STATUS
RELAY OUTPUT

SELECTABLE DROP
OUT TIME
(0 TO 190mS)

60mS

ACKNOWLEDGE
WINDOW

MODULE STATUS
RELAY OUTPUT

CONTACTOR PICK UP
90mS
(@120VAC)

NATURAL
CONTACTOR
DROP OUT

30mS

CONTACTOR
AUXLIARY
INPUT TO MICRO

Contact status relay closes on request to close. It will open if the contactor auxiliary contact does not close within 200 milliseconds and
module will fault (opening module status relay).

For this example, the 130 millisecond drop-out time has been selected. The base drop-out time is 50 milliseconds. The microcontroller delay is
130-50=80 milliseconds.

Figure 3.11 Timing Diagram 400A (Electrically Held) Contactor


with IntelliVAC Control for three-wire Control

1503-UM051D-EN-P June 2013

3-14

Installation and Wiring

Wiring Guidelines
Mechanically Latched
Contactors

IntelliVAC control may be used for mechanically latched contactors.


A momentary control signal is needed to close the contactor, and a
second momentary control signal is needed to open the contactor.
The momentary open/close commands must be at least 50
milliseconds in duration.
Refer to Figure 3.12 for a typical mechanical latch control scheme.
Note:
1. A mechanically latched contactor may already be closed when
power is applied to the IntelliVAC control module.
2. It is permissible to apply an open command to the IntelliVAC
module as power is re-applied.
CONTROL POWER
M

1 EC
2 +

CONTROL
POWER
FUSE
M

M-IV
TCO

4
3

MOV
TC
MOV

11
AUX
12
L1
P'
P

CCO
G

EMC FILTER
G

CLOSE

6
5

CC

L2/N
N'
N

M-IV
9 + - 10
CLOSE

OPEN
OVERLOAD

M-IV
7 + OPEN

Refer to Table 3.A for recommended fuse sizing.

Figure 3.12 Mechanically Latched Contactor Control

1503-UM051D-EN-P June 2013

Installation and Wiring

Mechanically Latched
Contactors

3-15

Capacitor Trip
The IntelliVAC can be configured to provide capacitor trip
functionality with mechanically latched contactors. A capacitor must
be connected to the IntelliVAC (terminals #1 and #2) in order to
provide this capability. The capacitor provides control power for the
IntelliVAC as well as stored energy to trip the contactor. Maximum
recommended capacitor size is 1650 F for 120V control or 330 F
for 240V control. Use of larger capacitors will require a current
limiting circuit to prevent opening the control fuse on energization.
The IntelliVAC must receive an OPEN command within a few
seconds of losing AC control power. This time limit depends on
voltage and capacitor size as shown in the table below. If the
elapsed time exceeds this limit, the contactor cannot be tripped by
IntelliVAC.
A separate voltage source is needed to provide the OPEN command.
This may be taken from the external capacitor as shown in Figure
3.13.
Table 3.C Mechanically Latched Contactor Capacitor Trip Times
Contactor
Rating

Nominal Voltage
(Vac)

Actual
Vinput (Vac)

Ext.
Capacitor
(F)

120
120
400 Amp

3.5
1650

100
240

Note:

110
240
200

Max. time
for trip
(sec)

2.7
1.7

330

7.5
4.7

Minimum capacitor voltage ratings


120V applications 200V DC (250V DC preferred)
240V applications 400V DC (450V DC preferred)

1503-UM051D-EN-P June 2013

3-16

Installation and Wiring

CONTROL POWER

M-IV

OPEN

CONTROL
POWER
FUSE

OVERLOAD

7 + -

OPEN

M
CAPACITOR

1 EC
2 +

TCO

4
3

MOV
TC
MOV

11
AUX
12
L1
P'
P

CLOSE

M-IV

CCO
G

EMC FILTER
G

6
5

CC

L2/N
N'
N
M-IV
9 + - 10

Refer to Table 3.A for recommended fuse sizing.

CLOSE

Figure 3.13 Mechanically Latched Contactor with Capacitor Trip Option

1503-UM051D-EN-P June 2013

Installation and Wiring

Motor Jogging Control

3-17

When used with electrically held contactors, the IntelliVAC allows


close commands every six seconds. This is to ensure the rated
contactor duty cycle of 600 operations per hour is not exceeded.
For motor jogging operations, the second control input, or OPEN
command, will close the contactor for as long as the input is present,
and open the contactor when the input is removed. (Refer to Figure
3.14.) This method will bypass the standard six second motor restart delay for jogging purposes only.
CONTROL POWER

CONTROL
POWER
FUSE

1 EC
2 +

11
AUX
12
L1
P'
P

OVERLOAD

M-IV

STOP

TCO

4
3

CCO

6
5

MOV
M

L2/N

EMC FILTER
G

N'
N

START

9 + - 10

M-IV
15

CLOSE

16

CONTACTOR
STATUS

JOG

M-IV

M-IV
7 + -

* Refer to Table 3.A for recommended fuse sizing.

OPEN

Figure 3.14 Motor Jogging Control

1503-UM051D-EN-P June 2013

3-18

Installation and Wiring

Time Delay Undervoltage

The IntelliVAC can be configured to provide time delay undervoltage


(TDUV) protection. The feature is available to keep electrically held
contactors closed during a voltage dip or brief power loss. This
option may require the addition of a capacitor (see below). Refer to
Chapter 6 for typical capacitor sizing. The capacitor is connected to
terminals 1(-) and 2(+) of the IntelliVAC. (Refer to Figure 3.15.)
Table 4.B of the Setup and Commissioning chapter has the dip
switch settings to provide TDUV from 0.2 to 2 seconds. IntelliVAC
can provide TDUV protection without the use of an external
capacitor, as shown in Table 3.D.
Table 3.D Maximum TDUV Time (without Capacitor)
Control Voltage

Max. TDUV Time (secs)

110/120 V
220/240 V

0.2
1.0

The following conditions will initiate TDUV protection, regardless


of the supply voltage:
1. If the supply voltage drops below 90 VAC/VDC after the first
200 milliseconds after a contact close request.
2. When the supply voltage drops below 72 VAC/FDC after the
200 millisecond close sequence.
If the undervoltage condition persists beyond the set delay time, the
contactor will be opened and an undervoltage fault condition will occur.
CONTROL POWER
CAPACITOR

*
CONTROL
POWER
FUSE

1 EC
2 +
11
AUX
12
L1
P'
P

OVERLOAD

M-IV
TCO

4
3

CCO

6
5

MOV
M

L2/N

EMC FILTER
G

N'
N

START

STOP

9 + - 10

M-IV

Refer to Table 3.A for recommended fuse sizing.

15

M-IV
CLOSE

16

CONTACTOR
STATUS

Figure 3.15 TDUV Control Circuit

1503-UM051D-EN-P June 2013

Chapter

Setup and Commissioning


IntelliVAC Configuration

The IntelliVAC module is configured for a specific application by


setting DIP switches. They are accessed by loosening the two
screws on the front of the unit, and removing the cover by sliding it
forward. The switches are found on the front edge of the IntelliVAC
circuit board (see Figure 4-1). There are 12 switches, with number 1
being at the top next to the mini DIN connector. (Refer to Table 4.B).
Remove power from the module before
removing the cover and before changing the
DIP switch settings. The new settings are
recognized only on power-up.

IMPORTANT

Ground Stud (Series A)


Interface Connections

EEPROM Programming Port


(Mini DIN Connector)
DIP Switches
Ground Stud (Series B)
Status Relay Outputs

Supply Power Input

Internal Control Fuse

Figure 4.1 DIP Switch and Connector Locations

An IntelliVAC unit shipped separately from the factory will have a


default configuration per Table 4.A.
Table 4.A DIP Factory Default Settings
Description
Altitude: 0 1000m
Drop-out time: 130 msec
Contactor config.: 400A EH
TDUV config.: No TDUV
Ext. cap TDUV time: 0.2 sec
*Power-Up Safety: Enable

1
0

2
0

3
1

DIP switch
6
7

10

11

12

1
0

1503-UM051D-EN-P June 2013

Setup and Commissioning

4-2

IntelliVAC units shipped in a complete MV controller (Bulletin


1500/1900) will be configured to suit the installed application (i.e.
contactor type). The user should verify the settings before energizing
the equipment. Table 4.B defines the settings for each switch.

IntelliVAC Configuration
(cont.)

UP = 1
DOWN = 0

DIP switch SW1


1

10

11

12

12

Power-Up Safety Y

-1000 to 0

Enable

1 to 1000

Disable

1001 to 2000

2001 to 3000

10

11

Ext. cap. TDUV time

3001 to 4000

1
1
1
1

0
0
1
1

0
1
0
1

0
0
1
1

0
1
0
1

0.2 sec

Not defined
Not defined

TDUV config.

No TDUV

TDUV Enabled

Drop out time Z

50 msec

75 msec

Contactor Config.

100 msec

0
0
1
1

1
1
0
0

0
1
0
1

0
0
1
1

0
1
0
1

400A Mech. Latch

1
1

1
1

0
1

130 msec
150 msec
175 msec
200 msec
240 msec

Y
Z

Altitude X

4001 to 5000

0.5 sec
1.0 sec
2.0 sec

400A Elec. Held


800A Mech. Latch
800A Elec. Held

The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted
for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).
Available with IntelliVAC using version 2.001 firmware or newer.
By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.
Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.

1503-UM051D-EN-P June 2013

Chapter

Monitoring and Troubleshooting


Introduction

The IntelliVAC module has two light emitting diodes (LEDs) and
relay outputs to indicate the status of the contactor and the module.
The LEDs are visible on the front of the module and the relay
outputs are accessed on the bottom front of the module.

Figure 5.1 IntelliVAC LEDs

Module Status

The Module Status is indicated with a Green LED if the module is


functioning properly and has a valid configuration. If the module
powers up with an invalid configuration the LED will be Red,
indicating a Fault condition which will not allow the contactor to
close. If the module powers up properly and experiences an
undervoltage condition when attempting to close the contactor or
while the contactor is closed, the LED will be Red (Fault). If the
contactor does not close properly, a Fault is generated, the LED turns
Red, and inputs are inhibited until the module power is removed and
reapplied. If the processor has an internal fault, the LED will be Red,
the outputs will be cleared, and the processor will be reset. If the
reset is successful, the LED will be Green and the module will respond
to the control inputs. The input command must be toggled before the
module will respond to a new command (rising edge triggered).
Module Status output relay has a normally open contact. The contact
is open during a Fault condition (LED red), and closed during a
healthy condition (LED green).
The module states for Series A are summarized in Table 5.A.

Series B Design
Additional module states are indicated with the LED as per Table 5.B.

1503-UM051D-EN-P June 2013

5-2

Monitoring and Troubleshooting

Contactor Status

The Contactor Status is indicated with a yellow LED that is off until
a CLOSE command is received. The LED will stay on if the
contactor closes properly, until the contactor is opened.
Contactor Status output relay has a normally open contact. The
contact is open when the contactor is open (LED off), and closed
when the contactor has received a close command (for 200
milliseconds) or if it is closed (LED on).

Series B Design
Additional module states are indicated with the LED as per Table 5.B.
Table 5.A IntelliVAC Status Indication (Series A design)
Parameter

Conditions

Module Status
Y

Contactor
Status

X
Y
Z
[

1503-UM051D-EN-P June 2013

rated supply voltage


and
valid configuration
undervoltage
or
contactor fault
or
invalid configuration X
or
internal fault
insufficient supply voltage
rated supply voltage
and
close command present [
and
contactor closed
insufficient supply voltage
or
close command absent [
or
contactor open

LED State

Relay Contact State

Green

Closed

Red Y

Open

Off

Open

Yellow

Closed

Off

Open

Applies only to power-up condition.


Fault is reset by cycling control power.
If a contactor close command is applied and then removed in less than 500 milliseconds, the
IntelliVAC may fault and the module status LED will turn red. To clear the fault, module power has to
be removed and reapplied.
For mechanical latch contactors a close command does not need to be maintained for the contactor
to remain closed (resulting in a yellow state for contactor status).

Monitoring and Troubleshooting

5-3

Table 5.B IntelliVAC Status Indication (Series B design)


Conditions
XY

Description

Module Status
LED Color

Contactor Status

Relay

LED Color

Relay

Normal

Healthy Module and Contactor OPEN

Green

Closed

Off

Open

Normal

Healthy Module and Contactor CLOSED

Green

Closed

Yellow

Closed

Warning

Invalid Command Present ^

Yellow

Closed

Off

Open

Warning

Mechanical Latch Fail to Trip

Yellow

Open

Yellow

Closed

Fault

Power Up with Contactor CLOSED

Red Flash 2 [

Open

Yellow

Closed

Fault

Contactor Fails to Pick Up

Green

Open

Red Flash 1 Z

Open

Fault

Contactor Drop Out During Hold

Green

Open

Red Flash 2 [

Open

Fault

Long Contactor Drop Out Time

Green

Open

Red Flash 3 Z

Open

Fault

Microcontroller Malfunction

Red

Open

Red

Open

Fault

Power Up with Invalid Dip Switch Configuration

Red Flash 1

Open

Off

Open

Fault

Undervoltage with a CLOSE Command Present

Red

Open

Off

Open

X
Y
Z
[
\
]
^

Warning = Recoverable Condition Remove and retry offending signal


Fault = Non-recoverable condition Module power must be removed and re-applied.
Flash 1 = 1 Flash Red LED followed by a pause.
Flash 2 = 2 Consecutive Red LED flashes followed by a pause.
Flash 3 = 3 Consecutive Red LED flashes followed by a pause.
EH = Only for Electrically Held Contactor
Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence.
2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before re-applying these signals.
NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).

1503-UM051D-EN-P June 2013

5-4

Monitoring and Troubleshooting

Table 5.C Module Troubleshooting


Problem or Trip Indicated
Contactor does not energize

Indication of the following conditions


Motor Protection activated
Both Status LEDs Off

Possible Solutions

Module Status LED Red upon power up


(Series A)
Module Status LED Red upon power up
(Series A)
Module Status Red Flash 1 upon power up
(Series B)
Loose connection in control circuit.

Contactor closes momentarily and


will not reclose.

Module status LED Red and Contactor


Status LED Off (Series A)

Module status LED Red and Contactor


Status LED Off (Series A)
Module status LED Green and Contactor
Status LED Red Flash 1 (Series B)
Both status LEDs Off

1503-UM051D-EN-P June 2013

Investigate and reset


Check Control Power
Loose connections in control circuit
Verify IntelliVAC power input plug is in place
and properly seated
Verify internal control fuse has not opened
(Refer to Figure 4.1 for location)
IntelliVAC faulted. Cycle control power to
reset. Replace IntelliVAC if unsuccessful.
Improper setting of dip switches. Check
settings and cycle control power.

Verify contactor auxiliary set up. Reference


Publication 1502-UM052A-EN-P (400A) or
1502-UM051B-EN-P (800A) Auxiliary
Contact Set-up Procedure.
Verify circuit continuity (is contactor plug
connected properly?)
Coil damaged or connections are loose.
Repair and cycle control power.
Auxiliary Contact Assembly improperly
adjusted. Reference Publication 1502UM052A-EN-P (400A) or 1502-UM051B-EN-P
(800A) Auxiliary Contact Set-up Procedure.
Cycle control power to reset.
Undervoltage fault (no TDUV), control voltage
dipped below trip point. Cycle control power
to reset. Verify voltage levels are 110 to 240
VAC, 110 to 250VDC
Armature Plate obstructed from closing to coil
face. Verify no foreign material behind the
armature plate. Cycle control power to reset.
Check internal control fuse. Verify IntelliVAC
operation in test mode before applying Medium
Voltage. (Refer to Fig. 4.1 for location.)

Monitoring and Troubleshooting

5-5

Table 5.C Module Troubleshooting (cont.)


Problem or Trip Indicated
Contactor opens during operation

Indication of the following conditions


Motor Protection activated
Stop command initiated
Module Status LED Red

Possible Solutions

Contactor does not open


(mechanical latch only)

Module Status LED Green and Contactor


Status LED Red Flash 2 (Series B only)

Both status LEDs Off

Module Status LED Red and Contactor


Status LED Yellow (Series A, with firmware
2.001 or newer)
Module Status LED Yellow and Contactor
Status LED Yellow (Series B, with firmware
2.001 or newer)

Investigate and reset.


Verify circuit
Undervoltage fault (no TDUV), control voltage
dipped below trip point. Cycle control power
to reset. Verify voltage levels are 110 to 240
VAC, 110 to 250 VDC.
With external capacitor and TDUV feature
activated, undervoltage condition for longer
than programmed TDUV time. Undervoltage
fault activated. Cycle control power to reset.
Contactor Status feedback between Terminals
11 and 12 on the IntelliVAC has closed. The
IntelliVAC will de-energize the coil, thinking
the contactor has opened for other reasons.
Check control voltage and internal control
fuse. (Refer to Figure 4.1 for location.)
Check control power to ensure that it has not
dipped below minimum (see Table 5.D).
Trip mechanism is damaged. Inspect and
replace if needed.
Check for loose connections in the control
circuit.

Refer to Tables 5.A or 5.B for definition of Module LED states.

Table 5.D Minimum IntelliVAC Operational Supply Voltages


Voltage Level

Contactor Rating
(Amps)

Minimum Voltage
(VAC, 47 to 63 Hz)

Pick-Up

400/800

95

Drop-Out

400/800

75

400

70

800

80

Trip (Mechanical Latch)

1503-UM051D-EN-P June 2013

5-6

Monitoring and Troubleshooting

(This page is intentionally left blank.)

1503-UM051D-EN-P June 2013

Chapter

Spare Parts
Spare Parts List

IntelliVAC (electrically held) Series A


IntelliVAC (mechanical latch) Series A
IntelliVAC (electrically held and
mechanical latch) Series B

1503VC-BMC1
1503VC-BMC2

Internal Fuse: 6.3 A, 250 V (Littlefuse 21506.3)

80174-902-14-R

Multi-pole connectors:
2 pole (module power)
4 pole (status outputs)
12 pole (coil and I/O connections)

80174-014-01-R
80174-014-03-R
80174-014-11-R

1503VC-BMC3

Optional Equipment
TDUV Capacitor*
For 110/120V AC control (1650 F)
For 220/240V AC control (330 F)

80158-779-51-R
80158-779-52-R

*Includes mounting bracket and terminal guards

EMC Filter
Schnaffer (FN 670-10/06)

80026-430-01-R

1503-UM051D-EN-P June 2013

6-2

Spare Parts

1503-UM051D-EN-P June 2013

Appendix

Typical Contactor Drop-out Times


The contactor drop-out times shown in the following table are typical
values used when the power fuses are provided as part of a complete
MV controller from Rockwell Automation. The recommendations
are based on Ferraz Shawmut power fuses. Other fuse types may
require alternate drop-out time settings.
Table A.1 Contactor Drop-out Times
Fuse Rating
Voltage

< 5000

< 5000

Contactor Drop-out Time (msec)


Current
2R
3R
4R
6R
9R
12R
18R
19R
24R
32R
38R
48X
57X
2 x 24R
2 x 32R
2 x 38R
20E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
250E
300E
350E
400E
450E
500E
600E
750E
900E

400A

800A

50
50
100
240

75
200
100
240
240 *

50
50

75
100
130

75
200
240 *

Fuse not suitable for use with 400A contactor.

1503-UM051D-EN-P June 2013

A-2

Typical Contactor Drop-out Times

Table A.1 Contactor Drop-out Times (cont.)


Fuse Rating
Voltage

7200

8250

Contactor Drop-out Time (msec)


Current
2R
3R
4R
6R
9R
12R
18R
24R
2X18R
2X24R
20E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E

400A

800A

50
50
75
150

130

50

50

Fuse not suitable for use with 400A contactor.

Note: The drop-out time is chosen to be equal to or greater than the intersection of the rated
contactor interrupting current and the fuse melt time curve (except where noted *)

1503-UM051D-EN-P June 2013

Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1) 519.623.8930, www.ab.com/mvb
Publication 1503-UM051D-EN-P June 2013

Supersedes Publication 1503-UM051C-EN-P January 2006

Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in Canada.

You might also like