2 Design Lab II: An Automatic Power Factor Correction System
2 Design Lab II: An Automatic Power Factor Correction System
2 Design Lab II: An Automatic Power Factor Correction System
System
(Dr. Rajesh Karki, Sept. 2009)
Some additional procedures for dealing with high potential equipment are included
below. Please familiarize yourself with these and follow them when appropriate.
Turning Power ON, Taking Readings and Turning Power OFF
Make sure everyone is clear of the circuit and equipment. Announce your
attention to turn the power on. Turn on the table breaker first to avoid accidental
human contact with the energized terminals on the table breaker. Turn on the
100-amp breaker at your work station (bench panel breaker) second to
energize the circuit.
Take meter readings immediately. Do not delay. Only one member of the
group should take readings from the meters. Place both hands behind your back.
Call out the readings. Be careful not to contact any part of the circuit or
equipment. Another member of the group should record the readings called out.
The recording person should be positioned a safe distance from the circuit. All
other members of the group should stay clear of the circuit and the meter reading
person. Turn power off immediately after the readings are taken. Do not
delay.
Turn the 100-amp breaker at your work station (bench panel breaker) off first,
followed by the table breaker. Always turn both breakers off. Have the circuit
rechecked if Any changes are made to the circuit.
= Q /(2f.V2)
(4)
where, V is the RMS voltage across the capacitor and f is the frequency.
It is obvious that the capacitance required for power factor correction of a power utility
customer will vary as the number and type loads vary throughout the day. It becomes
important to avoid resonance type situations when capacitors are used to neutralize the
lagging effect of inductors in a circuit, or else, some parts of the circuit may be
subjected to very high voltages or currents. Care must be taken to ensure the circuit
components are able to withstand the resulting currents or voltages.
It is important to maintain a steady RMS voltage at the load terminal, since residential
as well as industrial loads are rated to operate at a specific voltage level. When a load is
connected, the voltage at the load terminals will however decrease due to a voltage
drop in the circuit upstream to the load terminals. Corrective actions, such as
transformer tap-changing or reactive power injection, must be taken if the voltage at the
load terminal drops significantly. It should be noted that the corrective actions should be
removed or altered when the load is changed or disconnected, or else the voltage at the
load terminals can be excessive. These factors require careful attention when designing
a PFC system for a typical power consumer. PFC system can be static as well as
dynamic through automatic switching.
Figure 2.1