Reactive Power Control
Reactive Power Control
Pr = (Vs*Vr Sin)/X
What is RP?
Sources of RP?
Sinks of RP?
S = P +jQ
S = VI*
S = Vs (Vs*-Vr*/-jX)
Ss = VxVrSin /X+ j(Vs2 - VsVrCos)/X
Ps = Pr = VsVrSin/X
Qs = Vs2-VsVrCos/X
Qr = VsVrCos-Vr2/X
Thus :
P and are closely coupled.
Q and V are closely coupled.
But P = EVSin/X,
So dP/dE = V/XSin +EV/X Cos .d /dE
Demand is constant so dP/dE=0,
So, d /dE =-tan /E
Hence, dQ/dV =1/X(E/Cos -2V)
Voltage Regulation
E-V= Vi +jVq = (Ip-jIq)(R+jX)
=IpR +jIpX-jIqR+IqX
= IqX+jIpX
= Qr(X/V) + j Pr(X/V)
dQsl/dV = ?
2.
3.
Conclusions !!
Stability
Power Quality
Reliability is the degree to which the performance of the elements of an
electrical power system results in power being delivered to consumers within
accepted standards and in the amount desired.
Stability
Stability refers to the attribute of a power system which enables it to develop
restoring forces equal or greater than the disturbing/destabilizing forces.
Stability limit is the max. power flow through some point in the system where
the entire system is operating with stability.
Voltage stability refers to the max. power transfer through a transmission line
beyond which voltage collapse occurs and stability is lost.
Limits of system ?
Thermal Limits (current based)
Dielectric Limits (voltage based)
Stability Limits (Load flow based)
What is a disturbance ?
Deviation from the normal condition.
Effect of disturbance ? It depends on :
Nature of disturbance, Magnitude of disturbance, Duration of disturbance
Stability
Stability
Definition:
Power system stability is the ability of an electric power system, for a
given initial operating condition, to regain a state of operating equilibrium
after being subjected to a physical disturbance, with most system
variables bounded so that practically the entire system remains intact.
Rotor Angle Stability:
Rotor angle stability refers to the ability of synchronous machines of an
inter-connected power system to remain in synchronism after being
subjected to a disturbance.
It depends on the ability to maintain/restore equilibrium between
electromagnetic torque and mechanical torque of each synchronous
machine in the system.
Instability, that may result, occurs in the form of increasing angular
swings of some generators leading to their loss of synchronism with other
generators.
Stability
Consider the power angle curve shown below :
Suppose the system is operating in steady state delivering a power of Pm at an
angle of 0 when due to malfunction of the line, circuit breakers open reducing
the real power transferred to zero. Since Pm remains constant, the accelerating
power Pa becomes equal to Pm .
The difference in the power gives rise to the rate of change of stored kinetic
energy in the rotor masses. Thus the rotor will accelerate under the constant
influence of non-zero accelerating power and hence the load angle will
increase.
Now suppose the circuit breaker re-closes at an angle c. The power will then
revert back to the normal operating curve. At that point, the electrical power
will be more than the mechanical power and the accelerating power will be
negative. This will cause the machine decelerate. However, due to the inertia of
the rotor masses, the load angle will still keep on increasing. The increase in
this angle may eventually stop and the rotor may start decelerating, otherwise
the system will lose synchronism.
Stability
Stability
Frequency Stability:
Frequency Stability refers to the ability of a power system to maintain
steady frequency following a severe system upset resulting in a
significant imbalance between generation and load.
It depends on the ability to maintain/restore equilibrium between
system generation and load, with minimum unintentional loss of load.
Instability that may result occurs in the form of sustained frequency
swings leading to tripping of generating units and/or loads.
Stability
Voltage Stability:
Voltage stability refers to the ability of a power system to maintain
steady voltages at all buses in the system after being subjected to a
disturbance from a given initial operating condition.
It depends on the ability to maintain/restore equilibrium between
load demand and load supply from the power system.
Stability
Small-disturbance voltage stability : Refers to the systems ability to
maintain steady voltages when subjected to small perturbations such
as incremental changes in system load.
Short-term voltage stability involves dynamics of fast acting load
components such as induction motors, electronically controlled loads
and HVDC converters. The study period of interest is in the order of
several seconds (0-10 sec).
Stability
Stability Indices
Loading Margin :
Loading Margin is the most basic and widely accepted method to approximate a
voltage collapse in the power system.
For a current operating point, the total increment of load that would cause a
voltage collapse is called the loading margin.
The PV and QV curves are used to determine the loading margin of a power
system at an individual load bus.
Stability
With Q-V curve, it is possible to know the maximum reactive power
that can be achieved or added to a bus before reaching the minimum
voltage limit.
The reactive power margin is the MVAR distance from the operating
point to the bottom of the Q-V curve. The Q-V curve can be used as
an index for voltage instability. The point where dQ/dV is zero is the
point of voltage instability.
Stability
Line Stability Index
Line stability index is based on the power transmission concept in a
single line, in which the discriminator of the voltage quadratic
equation is set to be greater or equal than zero to maintain stability.
For Lmn less than 1, system is stable; and when it exceeds 1, the system loses its
stability and voltage collapse occurs.
Stability
Voltage collapse prediction index
VCPI is based on voltage phasor information of the buses in the system
and the network admittance matrix.
The technique is derived from basic power flow equations which are
solved by Newton Raphson method and the index at bus k is written as
follows:
Where,
Stability
A power system undergoes voltage collapse if post-disturbance voltages are
below acceptable limits.
Voltage collapse may be due to Voltage OR Angular instability.
Main factor causing volt. instability is the inability of power system to maintain
a proper balance of reactive power and voltage control.
The driving factor of voltage instability is usually the load.
Causes of V. Instability :
Increase in load, switching of transmission lines, outage of transmission
lines, RP sources reaching their reactive power limits, tap changing
operation of OLTCs, load switching / load recovery dynamics.
Possible outcome of voltage instability :
Loss of loads, Loss of integrity of entire power system
2.
Stability
Voltage stability timeframes:
Short term/transient voltage instability: 0 - 30 seconds
long-term voltage stability: 1 60 minutes
RP Requirement of Utilities
Fixed:
Keep the Trafos. Energised
Min. Base Load
Variable:
Load Increases
Add. System demand
Requirement of a Trafo:
1. It requires magnetizing current / kVAR at all times. Magnetizing Current has
02 comp. (Active Comp-Losses at no load, Reactive Comp-To hold the
magnetizing field)
2. Its load current also has a reactive comp. (determined by the PF of load)
which is transferred to primary side.
3. When load current increases, it causes internal voltage drop.
4. Tap changing also increases inductive voltage drop.
Trafo.
1.
2.
Constant Mag. Current is required from no load to full load (~1.8% of Ifl)
3.
Tap changing can increase the internal reactance upto 6%; Full rated
current passes through it, demanding increased reactive power
4.
Hence it is preferable to use cap. rather than OLTC for voltage support
5.
Low PF Load requires increased reactive power; Trafo itself requires more
reactive power while working on reduced pf loads.
6.
7.
8.
RP Requirement of Utilities
Trafo.
Sources of RP
1. Sources with reactive power output as secondary function
Synchronous generators
Synchronous motors
EHV Transmission lines
2. Sources whose primary function is to produce reactive power
Synchronous Condensers
Electric Power capacitors
Static VAR regulators
STATCONS etc.
Synch. Gen
Synchronous generators are rated in terms of the maximum kVA
output at a specified voltage and power factor (usually 0.8 or
0.85 lagging) which they can carry continuously without
overheating.
The active power output is limited by the prime mover capability
to a value within the MVA rating.
The continuous reactive power output capability is limited
by three considerations: armature current limit, field current
limit and core end heating limit.
Synch. Gen.
Synch. Gen
Leading PF Loads
Many electrical loads incorporate elements that can impose a
leading power factor on the power source.
While these loads are typically not a problem for utility power
sources, they can cause generator set failures or the failure of
certain loads to operate properly on a generator set.
The problems seen when attempting to operate generator sets
with leading power factor loads may seem mysterious, but in
reality, they are not too much different from another energy
absorption problem: the limited ability of a generator set to
absorb real kW power from loads some elevator drives, and in
crane applications.
Synch. Gen
Q: A 480V, 50Hz, Y connected, 6 pole genertor is rated at 50kVA,
0.8pf lag with Xs=1ohm and is run by a 45kW Turbine.
Draw its capability curve.
Find the value of Q at Pmax.
Find the value of Qmax that can be delivered by the gen.
It is connected to a 56A,0.7 lag load. Check if it is within the
desired limits of operation of the generator?
Synch. Gen
Q: Xs = 1.724pu, Vt =1<0 deg, pu, Iload = 0.8pu at 0.9 lag.
Find P & Q ?
Find the variation in Q with 20% variation (plus and minus) in
excitation voltage?
Synchronous Condenser
The leading power factor of a synchronous motor can be exaggerated by
removing the mechanical load and over exciting the field of the synchronous
motor. Such a device is known as a synchronous condenser.
The leading power factor can be adjusted by varying the field excitation. This
makes it possible to nearly cancel an arbitrary lagging power factor to unity
by paralleling the lagging load with a synchronous motor.
A synchronous condenser is operated in a borderline condition between a
motor and a generator with no mechanical load to fulfill this function. It can
compensate either a leading or lagging power factor, by absorbing or
supplying reactive power to the line. This enhances power line voltage
regulation.
Since a synchronous condenser does not supply a torque, the output shaft
may be dispensed with and the unit easily enclosed in a gas tight shell. The
synchronous condenser may then be filled with hydrogen to aid cooling and
reduce windage losses.
Synchronous Condenser
The ability of synchronous condensers to absorb or produce reactive power
on a transient basis stabilizes the power grid against short circuits and other
transient fault conditions. Transient sags and dips of milliseconds duration are
stabilized. This supplements longer response times of quick acting voltage
regulation and excitation of generating equipment.
The synchronous condenser aids voltage regulation by drawing leading
current when the line voltage sags, which increases generator excitation
thereby restoring line voltage. A capacitor bank does not have this ability.
Helps to prevent harmful oscillations in the system.
Capacitors
Easy to install, portable source of RP
Reduction in PF Penalty
Reduction in Bill Demand Charges (Reduced/Lower Tariff)
Support Bus Voltages (By reducing reactive current)
Selection of Capacitors
kVAR Requirment
Voltage Level where Cap. Needs to be installed
Type of end user
Nature of load / load characteristic
Harmonics
Ambient conditions
Availability
Selection of Capacitors
Q: A 3 Phase, 50 kW Induction Motor has a PF of 0.75 lagging. What size of
Capacitor is required to improve the PF to 0.90?
Motor input = P = 50 kW, Original P.F = Cos1 = 0.75, Final P.F = Cos2 = 0.90
1 = Cos-1 = (0.75) = 41.41; Tan 1 = Tan (41.41) = 0.8819
2 = Cos-1 = (0.90) = 25.84; Tan 2 = Tan (25.50) = 0.4843
Required Capacitor kVAR to improve PF from 0.75 to 0.90 = P x (Tan 1 - Tan 2)
= 50kW x (0.8819 0.4843)
= 19. 9 kVAR ~ 20kVAR
And Rating of Capacitors connected in each Phase
19.9/3 = 6.63 kVAR
Selection of Capacitors
Q: An Alternator is supplying a load of 650 kW at PF of 0.65. What size of
Capacitor is required to raise the PF to unity ? And how many more kW can the
alternator supply for the same kVA loading when PF is improved to unity?
Supplying kW = 650 kW, Original P.F = Cos1 = 0.65, Final P.F = Cos2 = 1
1 = Cos-1 = (0.65) = 49.45; Tan 1 = Tan (41.24) = 1.169
2 = Cos-1 = (1) = 0; Tan 2 = Tan (0) = 0
Required Capacitor kVAR to improve P.F from 0.75 to 0.90 = P (Tan 1 - Tan 2)
U/G Cables
An underground (U/G) power cable has the capability to store and release
electrical energy with the voltage variation.
The capacitive or charging current has a limiting effect on cable rating capacity
(MW).
This effect is quantified by the fact that when intended to supply energy to a
resistive receptor (active load consumer) in a radial network, via a power cable
circuit, it is needed to inject a higher current at the source to compensate for
cable capacitance.
U/G Cables
The charging current generates heat losses in cable which are of significant
magnitude in very long high and extra high AC U/G power cable connections.
As the capacitance and the charging current increase linearly with the length of
the cable circuits the generated heat losses by the charging current could be as
high as its entire thermal rating capacity.
In other words, it could be said that for long and uncompensated cable circuits
the entire cable rating capacity could be consumed by the circulation of charging
current; i.e. no real power transmitted without overheating the cable.
The length of a cable at which its thermal capacity was consumed by the
charging current is called critical length and it is calculated with the following
formula:
Lc = I *3 x 10^3 (km)
wCV
where:
C = capacitance per unit length (F/km)
w= 2pif ; f = System frequency
V= Line (phase to phase) voltage (kV)
I = phase current (A)
U/G Cables
The maximum transmitting power of a radial cable circuit is given by:
PL= SG2- (w . C. L. V2. 10_ 3)2 (MW)
Where,
PL = Active power at load receptor (MW)
SG = Apparent power at injecting point (MVA)
C = capacitance per unit length (F/km)
w= 2f ; f = System frequency
V= Line (phase to phase) voltage (kV)
L = Length of cable (km)
It could be seen that the critical length LC is determined by the system voltage
and frequency and by cable rating which is determined by the conductor size,
environmental and installation conditions and cable capacitance.
The larger active current transmitted on cable the longer the critical length; i.e.
the charging current is of a lesser importance.
Transmission Lines
The series inductive reactance causes voltage drop which is a function of load
current, so it absorbs reactive power Qind.
This inductance increases with the length of line.
The shunt cap. reactance supplies reactive power Qcap which is a function of
voltage V.
The supply and absorption of reactive power varies along the length of line.
If the load is such that Qcap = Qind, it is called SIL.
The line is then said to have Natural Load or unit SIL.
Profile
Reactive power should be supplied during heavy loads (switching of shunt cap.)
Reactive power should be absorbed during low loads (switching of shunt
reactors)
Reactive power requirement increases with length, so intermediate substations
are needed.
Transmission Lines
Transmission lines are generally designed for a common value of surge imp.
Charging an EHV line is equivalent to charging a capacitor high inrush
A charged EHV line supply stead state kVAR, irrespective of load current.
During the day, it provides reactive support, during the night it increases system
voltages.
Surge impedance and charging kVAs are calculated as follows:
1.
2.
3.
where L is length of
Shunt Compensation
Q: A 4 MVA, 33/11 kV Substation has a minimum load of 0.5MW, 0.8 PF lag and a
maximum load of 2.8 MW, 0.78 PF lag.
It is required to hold the PF at 0.9 lag through out the day as required by the local
utility company. Propose the value of fixed and switched capacitor banks?
kVAR max = P* (tan 1 tan 2) = 2800 (tan cos inv0.78 tan cos inv0.9) = 900
KVAR min = 500 (tan cos inv 0.8 tan cos inv0.9)= 135
150 fixed + 750 switched kVARs, as per standard available ratings.
Q=I*Xc , C =I/wQ,
The high magnitude current is not seen by the power system as it occurs
between the parallel banks.
Voltage Stability
2.
3.
4.
5.
6.
7.
Financial Aspects
P = (Vs*Vr Sin)/X,
So either we increase V or we decrease X for increased power transfer.
Series Capacitor cancel out the inductive line reactance of Tx line.
Vector Diagram :
Series Compensation
Advantages of SC:
1. Automatic V. Reg
2. Instant V. Reg Mitigation of Flickers
3. Reduction in transmission losses
4. Increased active power transfer
5. Adjustment of line impedance Control of power flow
6. Effective for severe fluctuating loads e.g. Arc Furnace
7. To serve loads far away from gen.
8. Saves the cost of new Tx line
9. Environmental effect Saves environment, land, forest
10. Reduced right of way cost
Issues / Problems with SC:
1. Steep voltages under Short Cct.
2. Value & Cost is proportional to V2
3. Compromised Robustness of Tx Line
4. Can not carry full short cct.
5. Issues of Sparking at capacitor under fault/short circuit
The current limiting damping circuit normally consists of an air core reactor or a
combination of reactor + resistor (if high damping is required).
By-Pass Switch : The bypass switch is usually an automatic SF6 circuit Breaker
(with auto reclosure duty cycle) for EHV Series Capacitor applications.
The breaker also allows the operator to insert or bypass the series capacitor.
The damping reactor limits the capacitor discharge resulting from gap
sparkovers or bypass breaker closure.
The communication of platform connection (current monitoring & control
commands) to the ground is accomplished using fiber optics.
SSR
Resonant frequencies below the fundamental frequency are called subsynchronous frequencies.
Sub-synchronous resonance (SSR), occurs due to interaction between series
capacitors and nearby turbinegenerators.
Application of series capacitors in long electric power transmission lines is a
costeffective method to increase power transfer but use of series capacitors
has sometimes been limited because of the concerns for sub-synchronous
resonance (SSR).
Turbinegenerators have rotating shaft systems comprised of large inertial
masses that are interconnected with shafts that act as springs.
These large masses and shafts create torsional resonant frequencies some of
which are also subsynchronous.
If the transmission line resonant frequency is close to the complementary
mechanical system frequency of the generating machine, then the two
oscillatory systems can interact with each other.
SSR
In some operating conditions, the interaction can result in damaging shaft
torques on a turbinegenerator shaft.
This interaction is called SSR, and it occurs because of the interchange of
energy between the series capacitors on the transmission lines and the mass
spring system of the turbinegenerator shaft.
This interchange occurs at the subsynchronous resonance frequency by
modulating the 50 Hz wave form.
The SSR phenomenon actually occurred at some generating plants resulting
in shaft failures.
SSR
SSR Mitigation
Installing SSR blocking filters to block the currents at SSR frequencies flowing
through the generator stepup transformer.
Installing supplemental excitation damping controls (SEDCs) to provide
damping at the SSR frequencies.
Torsional relays with proper design of TCSC.
Torsion relay monitors shaft speed at one or two locations and trips the unit
or a line that isolates the affected turbinegenerator from the source of
torsional stimulus.
Torsion Relay is the most wideused technique for addressing risks
due to SSR.
Bypassing series capacitors.
Amortisseur windings on generator rotors.
It is achieved through thyristor firing angle control in the desired and appropriate
range.
For small conduction times (larger firing angle), the resulting impedance is
capacitive while for larger conduction times (smaller firing angle), it becomes
inductive.
Such oscillations can be excited by a number of reasons such as line faults, switching of
lines or a sudden change of generator output.
The presence of active power oscillations acts to limit the power transmission capacity
of interconnections between areas or transmission regions.
TCSC offers a cost-effective, robust power oscillation damper, insensitive to its location
in the system and non-interacting with local oscillation modes. In a number of cases, it
turn out to be the best practicable solution.
thyristor-switched capacitor
A comprehensive static var system (SVS) is an aggregation of SVCs and
mechanically switched capacitors / reactors whose outputs are coordinated.
SVC is the first generation shunt compensator. It has been around since 1960s.
In the beginning it was used for load compensation such as to provide var
support for large industrial loads, for flicker mitigation etc.
With the advancement of semiconductor technology, the SVC started
appearing in the transmission systems in 1970s. Today a large number of SVCs
are connected to many transmission systems all over the world.
Increased transmission capacity - defer or eliminate the need for new lines
Higher transient stability limit
Power oscillation damping
In the active control range, current and reactive power is varied to regulate
voltage (Vref) according to a slope / droop characteristic.
The slope value depends on the desired sharing of reactive power
production between various sources, and other needs of the system. The
slope is typically 1-4 %.
At the capacitive limit, the SVC becomes a shunt capacitor (V= - I/Bcmax).
At the inductive limit, the SVC becomes a shunt reactor (V= - I/Blmax).
STATCOM
STATCOM basically performs the same function as of SVC but with some advantages.
The term Static Synchronous Compensator is derived from its operating principle,
which is similar to rotating synchronous compensators / condenser, but without any
moving part & obviously faster operation .
It connects the inverter output to the power system (usually a coupling trafo).
4- Harmonic Filters
To mitigates harmonics / high frequency components due to the inverter.
STATCOM
Basic Principle of Operation:
If two AC sources, which have the same frequency are connected through a
series reactance, then the power flows will be:
1.
2.
Active or Real Power flows from the leading source to the lagging source.
Reactive Power flows from the higher to the lower voltage magnitude
source.
Consequently, the phase angle difference between the sources decides the active
power flow while the voltage magnitude difference between the sources
determines the reactive power flow.
Based on this principle, a STATCOM can be used to regulate the reactive power
flow by changing the output voltage of the voltage-source converter with respect
to the system voltage.
STATCOM
STATCOM
STATCOM
Modes of Operation
The STATCOM can be operated in two different modes:
1- Voltage Regulation Mode (Normal mode of operation)
It regulates voltage at its connection point by controlling the amount of reactive
power that is absorbed from OR injected into the power system through VSC.
The voltage V2 generated by the VSC through the DC capacitor is in phase with the
system voltage V1 i.e. =0, so only reactive power is flowing (=0 , P=0).
1. When system voltage is high, the STATCOM will absorb reactive power
(inductive)
2. When system voltage is low, the STATCOM will generate and inject reactive
power into the system (capacitive).
Subsequently, the amount of reactive power flow is given by the equation:
Q = [V1(V1-V2)] / X
2- VAR Control Mode
In this mode, the STATCOM reactive power output is kept constant , independent of
other system parameters.
STATCOM
STATCOM
Usually a large DC capacitor is used to supply dc power to the three-phase
rectifier/inverter.
The rectifier uses PWM to from an AC (usually 48 pulse operation).
The voltage across capacitor is maintained so that STATCOM is able to
exchange reactive power with the ac power network i.e., to a value high
enough for the STATCOM to be able to produce ac voltage at the value
required.
The voltage across the capacitor is maintained by continually adjusting the
magnitude and polarity of the active component of the current at the ac side
of the STATCOM.
When the voltage across the capacitor needs to be increased, the STATCOM
adjusts the magnitude and polarity of the active component of the current
at its ac side so that active power is drawn from the ac power system and
converted to dc power in order to charge the capacitor.
Conversely, when the voltage across the capacitor needs to be decreased,
the STATCOM adjusts the magnitude and polarity of the active component of
the current at its ac side so that active power is returned to the ac power
system, thereby discharging the capacitor.
STATCOM
Comparison between STATCOM and SVC:
Both STATCOM
and SVC are commonly used for voltage profile
maintenance, reactive power compensation, and power factor correction.
Both STATCOMs and SVCs are commonly installed in ac transmission lines or
in industrial applications with large random peaks of reactive power
demand.
Depending on the design criteria of the system to which they are connected,
either a STATCOM or an SVC can be more efficient, practical or simply
cheaper to use than the other, and thus better suited for that particular
application.
STATCOMs and SVCs each possess characteristics that differentiate one from
the other during normal operation.
The main operating characteristic differences between STATCOMs and SVCs
are summarized in the following table:
STATCOM
STATCOM
One of the main differences between STATCOMs and SVCs is that STATCOM
operation in under voltage conditions is as good as in normal conditions,
while SVC operation in under voltage conditions is limited.
This difference is very crucial, since under low-voltage conditions is precisely
where the reactive power compensation is most needed.
This operating difference gives an advantage to STATCOMs over SVCs.
Another important advantage of STATCOMs over SVCs is faster response
time. STATCOMs begin to compensate the reactive power requirements of a
system approximately 1 cycle before SVCs.
In dynamically variable systems (such as ac transmission lines or industrial
applications operating with large random peaks of reactive power), this
faster response time can have a significant impact on the effectiveness of
the reactive power compensation.
For example, the use of a STATCOM is necessary in industrial applications
operating with large random peaks of reactive power to reduce the light
flicker phenomenon to an acceptable level, so STATCOMs have an advantage
over SVCs in systems requiring a critically fast response time.
STATCOM
Finally, the installation size and costs differ between STATCOMs and SVCs.
STATCOM installations are smaller in size than SVC installations, but are
significantly more expensive.
Size and cost can be a decisive factor in choosing between a STATCOM and an
SVC, depending on the available space and budget for any given application.
For example, if the large size of an SVC installation is not feasible for a
particular application, it might be necessary to install a STATCOM even if it is
more expensive than an SVC.
STATCOM
Typical STATCOM Applications:
Utilities with weak grids or fluctuating reactive loads
Unbalanced loads
Arc furnaces
Wind farms
Wood chippers
Welding operations
Car crushers & shredders
Industrial mills
Mining shovels, hoists and mills
Harbor cranes
STATCOM
STATCOM
STATCOM
STATCOM
SSSC usually injects the series voltage in quadrature with line current i.e.
pure inductive or pure capacitive injection.
SSSC contains a solid-state voltage source inverter, connected in series with
the transmission line through an insertion / coupling transformer.
This connection enables the SSSC to control power flow in the line for a wide
range of system conditions.
SSSC is able to rapidly provide both capacitive and inductive impedance
compensation independent of the power line current.
An SSSC can also be used to improve the damping of power oscillations
(POD) in the transmission network.
SSSC is able to transfer both active and reactive power to the system,
permitting it to compensate for both the resistive and reactive voltage
drops.
It can maintain high effective X/R that is independent of the degree of series
compensation.
However, this is costly as a relatively large energy source is required. If
control is limited to reactive compensation only, then a smaller supply is
enough.
The compensation of the real part of the impedance can maintain high X/R
ratio even if the line has a very high degree of series compensation.
Reduction of Short Cct. Current
No classical network resonance risk
Flexibility to inject any reactive (or active) power independent of line current.
PHASE SHIFTERS
Phase Shifting or Phase Angle Regulating transformers (phase shifters) are used to
control the flow of electric power over transmission lines.
Both the magnitude and the direction of the power flow can be controlled by
varying the phase shift across the series transformer.
The phase shift is obtained by extracting the voltage of one phase and injecting a
portion of it in series with another phase.
The two transformers are quite large, and because of transport limitations they are
usually placed in separate tanks.
Thyristors are used in the switching network to control the mangitude of phase
shift.
PHASE SHIFTERS
PHASE SHIFTERS
PHASE SHIFTERS
Load Sharing of Parallel Lines
Any difference in impedances will cause unbalanced line loading. A PST inserted
in the line that does not pick up sufficient load shall provide an advance phase
shift, meaning that the load side voltage phasor should lead the source side
voltage. Alternatively, a PST with retard phase angle could be inserted in the line
that tends to overload.
Mitigation of post contingency overloads
When two systems are coupled via long and highly loaded transmission lines, the
trip of one line may cause a significant phase difference. Such a phase shift may
be too large to allow immediate re-closure. By using a PST, the phase difference
can be compensated, allowing the lines to be reconnected immediately
Mitigation of unwanted power transfer
PSTs placed in one or several of the infeeds can balance the phase angle
difference given by the external transmission network and eliminate the transfer
flows.
PHASE SHIFTERS
PHASE SHIFTERS
FACTS COMPARISON
FACTS COMPARISON
RP PRICING
Reactive Power Pricing Options :
There are two general ways to compensate generators for providing
reactive power.
One way is the capacity payment option, in which the generator is paid
in advance for the capability of producing or consuming reactive power.
The payment could be made through a bilateral contract or through a
generally applicable tariff provision.
Once the generator is paid, it could be obligated to produce or consume
reactive power up to the limits of its commitment without further
compensation when instructed by the system operator.
To ensure that the generator follows instructions in real time, the
generator
could face penalties for failing to produce or consume when instructed.
Currently, this is the most common method for compensating reactive
power providers.
RP PRICING
The other way is the real-time price option.
In this option the generator is paid in real-time for the reactive power
that it actually produces or consumes.
Under this option, the generator is paid only for what it produces or
consumes, but it pays no penalty for failing to produce when instructed.
It is also possible to combine some of the features of each of these
options.
For example, a generator might receive a capacity payment in advance in
exchange for the obligation to produce or consume reactive power
within a specified power factor range upon instruction by the system
operator, but might also receive a spot price for producing or consuming
additional reactive power beyond the specified range.
RP PRICING
Under the capacity payment option, there are at least four methods for
determining the capacity payment:
1. A cost-based payment based on estimated costing of equipement.
RP PRICING
Under the real-time pricing option, there are at least four methods for
determining the spot price:
1. Pay nothing at least for reactive power produced within a specified
power factor range.