What Is Power System Protection
What Is Power System Protection
Deals with the protection of electrical power systems from faults through the isolation of
faulted parts from healthy electrical network
The objective of a protection schemes is to keep the power system stable by isolating only
the components that are under fault, whilst leaving as much of the network as possible still
in operation
Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition
Speed: Usually the faster the better in terms of minimizing equipment damage and
maintaining system integrity
Simplicity: KISS
Since If cant be controlled easily therefore t must be minimized. Protection system helps in
reducing this t to minimize damage.
Power System Protection-An Art or Science?
Power System Protection is considered to be a combination of Art & Science since there are multiple
feasible Solutions that can be offered to overcome a certain issue.
Protection Relays:
Hence,
Protection System Typically are Designed for N-1
Overcurrent Relay (also known as Over current & Earth Fault relay)
Distance Relay
Differential Relay
Breaker Failure Relay
Synchro-check Relay
Auto-reclosure Relay
Trip circuit Supervision Relay
Tripping/Lockout Relay
DC Trip Unit
Fault Current Locator
History of Relaying:
1. Electromechanical Relays
Robust in use
Slower in response
Difficult to install
Expensive
Lacks modern features like fault locator, telecommunication signals, reclosing etc
2. Static Relays:
High performance
Sophisticated characteristics
Faster response
3. Numerical Relays:
Highly economical
Continuous self-monitoring
More reliable
Easy to install
Characteristics
Electromechanical
Static
Numerical
Speed of Response
Slow
Fast
Very Fast
Timing Accuracy
Temperature
Dependent
Size
Bulky
Small
Very Compact
Required
Required
Not Required
CT Burden
High
Low
Low
Reset Time
Very High
Less
Less
Functions
Single Function
Single Function
Multi-Function
Maintenance
Frequent
Frequent
Very Low
Yes
No
No
Reliability
High
Low
High
SCADA Compatibility
No
No
Yes
Zones of Protections:
Polarity Test,
Saturation Test,
Hi-Pot Test
Miscellaneous Testing:
Earth Resistance Test
Earth Continuity Test
HV Test of LAs, 11 KV B.B, Wall Bushings, EHT Cables etc.
Tele Protection Testing
It is one of the earliest protection being used in Utilities & commonly known as
Over-current & Earth-fault protection.
It uses the CT inputs while working on the simple principle of excess current i.e.
Relay picks-up when current exceeds pickup value and send trip signal.
There are various types of O/C Protection following IEEE & IEC standard curves:
Large Motors in Network having rating above 1200 HP against Overload & Short
circuit.
Static
Numerical
GEC MCGG22
Siemens 7SJ6025
Westinghouse 50 (obsolete)
GEC MCGG21
Siemens 7SJ511
GEC MCGG62
ABB REF543
GEC MCGG82
Areva MICOMP122
ASEA RXIDF-2H
SIEMENS 7SK8855
(obsolete)
ABB SPAJ140C
LED Indications:
1 = Phase (Time)
2 = Earth (Time)
3 = Phase / Earth (Inst.)
4 = General Trip
LED Run = Relay Healthy
LED Error = Relay Blocked
LCD Display:
L1 = Red phase
L2 = Yellow phase
L3 = Blue phase
E = Earth
LED Indications:
1 = Measurement Supervision
2 = L1 Pickup
3 = L2 Pickup
4 = L3 Pickup
5 = Earth Pickup
6 = Breaker Failure
LED Run = Relay Healthy
LED Error = Relay Blocked
LED Indications:
1 = Trip
2 = Alarm
3 = Warning
4 = Healthy
5 = Phase (Time)
6 = Phase (Inst.)
7 = Earth (Time)
8 = Earth (Inst.)
LCD Display:
L1 = Red phase
L2 = Yellow phase
L3 = Blue phase
E = Earth
LED Indications:
1 = Protection Healthy
2 = Pickup
3 = Trip
4 = Phase A
5 = Phase B
6 = Phase C
7 = Earth (Time)
8 = Earth (Inst.)
9 = Phase (Time)
10 = Phase (Inst.)
LED Indications:
Red LED1 :
Instantaneous Trip
Red LED2 :
Time Delay Trip
Green LED-3 : I > Is = Relay Pickup
CASE SCENARIOS:
CASE SCENARIO 1
(Transformer)
CASE SCENARIO 2
(Transmission Line)
2. Differential Relay:
It is also used as back-up protection for short length EHV lines in Network.
IP
CT-X
IP
CT-Y
IS
IS
Relay
IR-X
IR-Y
+1
Current, pu
1 + (-1) = 0
0
-1
DIFF CURRENT
At the time of Transformer energization (No load); Inrush Current (2nd Harmonics)
Block Option is used to avoid unnecessary tripping due to Inrush (magnetization)
current.
Differential Relays covers all the Equipment that lie between Both CTs including CTs,
PTs, Lightening Arrestors (LA), Bus bars, Transformer & Power Cables etc.
Differential Relays operates instantaneously once triggers to limit the Damaging
effect due to Short circuit.
VA Burden, Turns Ratio, Accuracy limits of all CTs should be matched to avoid maloperation.
Low Impedance Bus bar protection scheme: combines all CTs input together
before gets entered into Relay.
High Impedance Bus bar protection scheme: All CTs input gets entered into the
Relay separately.
Used to protect Transformer & Short length Extra High Voltage lines.
Static
Numerical
BBC D202
ASEA RADSB
Siemens 7UT513
BBC D21SE3
ASEA RADSE
Siemens 7UT612
GEC DMH
BBC DT92
Areva P631
BBC D22SE3
GEC MBCH12
Areva P632
SIEMENS 7UT92
ABB RET670
ABB RET316
ABB SPAD
LED Indications:
L1 = Red Phase Pickup
L2 = Yellow Phase Pickup
L3 = Blue Phase Pickup
Trip I>
Trip I>>
nth Harmonics
LED Run = Relay Healthy
LED Error = Relay Blocked
LED Indications:
Ready = Relay Healthy
Start = Relay Pickup
Trip = Relay Trip Command
Diff. Trip = Diff. Prot Operated
LED Indications:
Healthy = Relay is Healthy
Blocked = Relay is Blocked
Alarm = For any Internal Fault
L1 = Red Phase Pickup
L2 = Yellow Phase Pickup
L3 = Blue Phase Pickup
Trip = General Trip
LED Indications:
Healthy = Relay is Healthy
Blocked = Relay is Blocked
L1 = Red Phase Pickup
L2 = Yellow Phase Pickup
L3 = Blue Phase Pickup
General Trip
Stage-1 I> Operated
Stage-2 I>> Operated
Nth harmonics
LCD Display:
1 = Diff. Stage-1 Trip
2 = Diff. Stage-2 Trip
3 = 2nd Harmonic / 5th Harmonic
Block
LED Indication:
L1 = Red
L2 = Yellow
L3 = Blue
LED Indications:
Trip = General Trip
CASE SCENARIOS:
CASE SCENARIO 1
CASE SCENARIO 2
3. Distance Relay:
a. Also known as Impedance Relay & considered to be the fundamental protection
for Transmission Lines in Utilities.
b. Relay measures the Impedance, reactance or admittance between the Location of
Relay & the fault Point using the Input from both CT & PT.
c. It works on the Principal that the Impedance/ reactance of a transmission line is
proportional to its Length.
d. In case of fault on Transmission line, current flowing to the Faulty point increases
and the Voltage at relay point decreases. Hence, Relay sees this as fall in impedance
and if this is below a pre-fixed setting, relay operates.
e. It is designed/ distributed in multiple Zones to ensure High speed Protection System.
f.
Static
Numerical
BBC LZ3
ASEA RAZOA
Siemens 7SA511
BBC LZ31
ASEA RAZFE
Siemens 7SA522
BBC LZ32
GEC (Quadramho)
Siemens 7SA612
BBC L3WYS
GEC (Micromho)
Siemens 7SA611
BBC L8B
Siemens 7SD60
BBC LH1W
Siemens 7SD61
Areva P443
Areva P543
ABB REL670
GEC (Optimho)
GE (D-60)
9. Electromechanical Distance
Relays (BBC LZ3, LZ31, LZ32,
L3WYS, LHIW, L8B)
Red
Pickup
Yellow
Pickup
Earth
Pickup
Zone-II
Pickup
II
III
Zone-III
Pickup
Distance
Trip
Carrier
Recieve
Carrier
Send
Blue
Pickup
CASE SCENARIOS:
Auto-Reclosure Relay:
In 80 to 90 % of faults on transmission lines, the faults are of transient nature as of insulator
flashes. Thus, if line is tripped and time is allowed for the fault arc to de-ionize(i.e. Dead
Time), reclosure of the circuit breaker will result in the successfully re-energization of line
through Auto-reclosure relay which attempts under some determined conditions.
Hence, Auto-reclosure helps in improvement in continuity of supply.
Miscellaneous Relays:
Trip circuit Supervision Relay:
This relay operates when Negative terminal of Supply to relay gets disappeared.
Tripping/ Lock out Relay:
This relay blocks the possibility of any other operation on subject breaker unless reset. DC
Trip Unit Relay:
This relay checks the availability of DC supply on switches and operates in case of DC
unavailability to avoid any damage to Network due to any fault.
Fault Locator Relay:
This relay is used to calculate the possible distance of fault from feeding end by using the
Input from CTs & PTs during Fault scenario to measure Impedance and compares it with the
defined Impedances of Lines.
DC Trip Unit:
Operates when DC disappears to any relay.