Overcurrent Protection
Overcurrent Protection
Introduction
Co-ordination Procedure
Principles of Time/Current Grading
Standard IDMT Overcurrent Relays
Combined IDMT and High Set Instantaneous Overcurrent Relays
Very Inverse (VI) Overcurrent Relays
Extremely Inverse (EI) Overcurrent Relays
Independent (definite) Time Overcurrent Relays
Relay Current Setting
Relay Time Grading Margin
Recommended Grading Margins
Calculation of Phase Fault Overcurrent Relay Settings
Ring Mains
Conclusion
Introduction
3
Correct overcurrent relay application requires knowledge of the fault current that can
flow in each part of the network.
The data required for a relay setting study are:
• a one-line diagram of the power system involved, showing the type and rating
of the protection devices and their associated current transformers
• the impedances in ohms, per cent or per unit, of all power transformers, rotating
machine and feeder circuits
• the maximum and minimum values of short circuit currents that are expected to
flow through each protection device
• the maximum load current through protection devices
• the starting current requirements of motors and the starting and locked
rotor/stalling times of induction motors
• the transformer inrush, thermal withstand and damage characteristics
• decrement curves showing the rate of decay of the fault current supplied by the
generators
• performance curves of the current transformers
Co-ordination Procedure
5
The relay settings are first determined to give the shortest operating times at
maximum fault levels and then checked to see if operation will also be satisfactory
at the minimum fault current expected.
Among the various possible methods used to achieve correct relay co-
ordination are those using either time or overcurrent, or
a combination of both.
That is to say, each one must isolate only the faulty section of the
power system network, leaving the rest of the system undisturbed.
Discrimination by Time
7
Discrimination by current relies on the fact that the fault current varies
with the position of the fault because of the difference in impedance
values between the source and the fault.
Hence, typically, the relays controlling the various circuit breakers are
set to operate at suitably tapered values of current such that only the
relay nearest to the fault trips its breaker.
Discrimination by Current
9
There are two important practical points that affect this method of co-
ordination:
• it is not practical to distinguish between a fault at F1 and a fault at
F2, since the distance between these points may be only a few metres,
corresponding to a change in fault current of approximately 0.1%
• in practice, there would be variations in the source fault level,
typically from 250MVA to 130MVA. At this lower fault level the
fault current would not exceed 6800A, even for a cable fault close to
C. A relay set at 8800A would not protect any part of the cable
section concerned
A safety margin of 20% to allow for relay errors and a further 10% for
variations in the system impedance values, it is reasonable to choose a
relay setting of 1.3 x 2200A, that is, 2860A, for the relay at B.
Discrimination by both Time and Current
10
IEC 60255 IDMT Relay Characteristics: TMS=1.0 North American IDMT Relay Characteristics: TD=7
Combined IDMT and High Set Instantaneous Overcurrent Relays
14
The reach of a relay is that part of the system protected by the relay if a
fault occurs.
A relay that operates for a fault that lies beyond the intended zone of
protection is said to overreach.
The initial current due to a d.c. offset in the current wave may be
greater than the relay pick-up value and cause it to operate.
This may occur even though the steady state r.m.s. value of the fault
current for a fault at a point beyond the required reach point may be less
than the relay setting.
Very Inverse (VI) Overcurrent Relays
16
The reach of a relay is that part of the system protected by the relay if a
fault occurs.
An overcurrent relay has a minimum operating current, known as the
current setting of the relay.
The current setting must be chosen so that the relay does not operate
for the maximum load current in the circuit being protected, but does
operate for a current equal or greater to the minimum expected fault
current.
Although by using a current setting that is only just above the maximum
load current in the circuit a certain degree of protection against overloads
as well as faults may be provided, the main function of overcurrent
protection is to isolate primary system faults and not to provide
overload protection.
Relay Current Setting
20
The time interval that must be allowed between the operation of two
adjacent relays to achieve correct discrimination between them is called
the grading margin.
If a grading margin is not provided, or is insufficient, more than one
relay will operate for a fault, leading to difficulties in determining the
location of the fault and unnecessary loss of supply to some consumers.
The grading margin depends on a number of factors:
1. the fault current interrupting time of the circuit breaker
2. relay timing errors
3. the overshoot time of the relay
4. CT errors
5. final margin on completion of operation
Recommended Grading Margins
22
The total interval required to cover circuit breaker interrupting time, relay timing error,
overshoot and CT errors, depends on the operating speed of the circuit breakers and
the relay performance.
At one time 0.5s was a normal grading margin.
With faster modern circuit breakers and a lower relay overshoot time, 0.4s is
reasonable, while under the best conditions even lower intervals may be practical.
It should be noted that use of a fixed grading margin is only appropriate at high fault
levels that lead to short relay operating times.
At lower fault current levels, with longer operating times, the permitted error specified
in IEC 60255 (7.5% of operating time) may exceed the fixed grading margin, resulting
in the possibility that the relay fails to grade correctly while remaining within
specification.
Recommended Grading Margins
23
It has been established by tests that satisfactory grading between the two
fuses will generally be achieved if the current rating ratio between them
is greater than two.
Recommended Grading Margins
25
9 Introduction
9 Co-ordination Procedure
9 Principles of Time/Current Grading
9 Standard IDMT Overcurrent Relays
9 Combined IDMT and High Set Instantaneous Overcurrent Relays
9 Very Inverse (VI) Overcurrent Relays
9 Extremely Inverse (EI) Overcurrent Relays
9 Independent (definite) Time Overcurrent Relays
9 Relay Current Setting
9 Relay Time Grading Margin
9 Recommended Grading Margins
9 Calculation of Phase Fault Overcurrent Relay Settings
9 Ring Mains
Reference
30
minlwinthein@gmail.com