WavePak Loop Splitter - 792040

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Datasheet

Wa v e P a k
Loop Splitter

The WavPak Loop Splitter module is a 4-20mA


current loop isolator with one loop powered
input and two independent, loop powered, isolated outputs. It is ideal for interfacing one transmitter to two devices such as a PLC and a local
indicator.
Some loop splitters are actually two single channel devices with their inputs connected in
series.This increases the loading on the current
loop. Weidmullers Loop Splitter has a single
input circuit with a near constant voltage drop of
no more than 3.5V, regardless of the output loop
load. This is accomplished through the use of
optical isolation as opposed to transformer coupling. Optical isolation also provides higher isolation levels - 1000V in the case of the Loop
Splitter.
Features:
loop powered
near constant input voltage drop
just 12.5mm wide
mounts on 35mm DIN rail
CSA approved, Class 1 Division 2 approved

Canada

United States

Mexico

W Interconnections Canada Inc.

W Interconnections, Inc.

W Interconnections, S.A. de C.V.

10 Spy Court

821 Southlake Blvd.

Boulevard Hermanos Serdn 698

Markham, Ontario L3R 5H6

Richmond, Virginia 23236

Col. San Rafael Oriente, C.P. 72029

Telephone: (800) 268-4080

Telephone: (800) 849-9343

Puebla, Pue. Mexico

Facsimile: (905) 475-2798

Facsimile: (804) 379-2593

Telephone: (222) 268 62 27

Email: info1@weidmuller.ca

Email: info@weidmuller.com

Facsimile: (222) 268 62 19

Website: www.weidmuller.ca

Website: www.weidmuller.com

Website: www.weidmuller.com.mx

WavePak Current Loop Splitter


Specifications:
Input:

4-20mA

Input voltage drop:

<3.5V over 4-20mA range

Isolation:

Optical
1000V between input and each output + output to output

Output:

4-20mA

Output loop supply:

19-30Vdc per loop

Output loop impedance:

up to 500 with a 24Vdc loop supply

Accuracy (each channel):

@25C 0.1% typical


-15C to +50 C temperature range: 0.8% typical

Response time (each channel):

10mS typical

Operating temperature range:

-15C to +50C

Ordering Data

Catalog No.

WavePak-I/2I

792040 0000

Notes
The Unit should be recalibrated under the normal operating conditions (factory calibated at 24C into 250W). Inadequate ventilation
and/or multiple loop splitters (or warm adjacent modules) can affect linearity. Optimal resilts can be achieved with 1cm (1/4) space
either side of the loop splitter.

Subject to technical changes Printed in Canada 999900274 08/2006