Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Galvanic Isolator ETI 30: - Characteristies

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Galvanic Isolator ETI 30

DATA SHEET - N00318

for direct voltage or current signals

Characteristies

Measuring of direct voltage and current signals and galvanic


isolador.
Linear measuring field.
Output signal with or without suppressed zero.
Galvanic isolation between in- and output and auxiliary power
supply.
Reduced size for mounting space saving.
Case type housing for fastening with screws, or on rail.

Application

The galvanic separation is used for galvanic isolation between


independent circuits of a same loop, with different electric
potencials, which can damage the instruments and cause undesirable
interference to the measuring process..
It serves properly to convert a direct current or voltage input signal
into a proportional output signal, which is independent on the load.
The output signal is compatible for connection of various
instruments, such as: analogical or digital indicators, graph recirdes,
controllers, analogical-digital converters and others.

Page 1/4
August 2003

Technical data (NBR 8145)


Input

Voltage
Current
Input resistance

Functioning
Overload

Output

Current

Signal limit
The input signal is conditioned by the signal conditioner (1)
according to the type of input, voltage or current. In case of a
voltage input signal, a resistive divider is available, which conditions
the input signal, and in case of current input, a shunt resistor
transforms de current signal into a voltage signal. The signal is
amplified in module (2), form this it is sent to the module (3), which
transforms this direct current signal into a alternating current signal
with an amplitude, which is proportional to the input signal. The
transformer of module (4) is a galvanic isolator between the in- and
output signals. Module (5) rectifies the alternating current signal into
a direct current signal, which is proportional to the input signal. The
output amplifier (6) emits an output signal, which is independent on
the output load. All modules are powered by a stabilized power
supply (7), which isolates the auxiliary power supply from the input
signal as well as the output signal

Load limit
Output with load
divider (Optional)
Voltage
Residual ripple

Power supply:

with or without suppression


0..25mV up to 0..750V; 1..5V
(others on consult)
0...1mA up to 0...20mA; 4...20mA
(others on consult)
Voltage input: UI 10V : 80k/V
UI 10V : 5k/V
Current input: 60mV
I (mA)
Error limit 0,5%
1,00VA for error limit 0,25%
Current input: 0,15VA
permanently: 1,5 UrtdI ; 2IrtdI
briefly 4UrtdI/1s;50IrtdI/1s

0...1/5/10/20mA, 4...20mA
(others on consult)
1,5 IrtdO, UrtdO max. 25V
RC = infinite
Rc=
15.000(mV)

Max. output signal (mA)


f.ex.: Rc=750 for 20mA
To calculate RC use 7.500mV
instead of 15.000mV, the results will be the
same for both outputs
0...10V ; Rc Uo
20mA
0,5% (peak to peak)

AC

voltage:

DC

frequency:
consumption
voltage
consumption

110;220V 20%
(others on consult)
45...65Hz
5VA approx (3VA em 60Hz)
24V 25%
48; 125V -15...+25%
(others on consult)
4W approx

Galvanic Isolator ETI 30

DATA SHEET - N00318

for direct voltage or current signals

Influence magnitudes
Error limit
Reference conditions
Input:
Auxiliary power supply:
Load:
Ambient temperature:
Heat time
Additional error above
1,2IrtdI ou UrtdI
Linearity deviation
Load
Temperature
Auxiliary power supply
Response time
External magnetic fieldes
Radio frequency
interference

Page 2/4
August 2003

Construction and Mounting


0,5%
0,25% (Optional)

Type

U I = UrtdI
II = 0...IrtdI
UAX 2%
0,5RC mx.
25C 2K
20 min..

Fastening

Surface mounting with two screws M4, or


using DIN rail.

Electrical
connection

Frontal terminals for eye and fork type cable


shoes

Protection class
(NBR 6146)

IP 50 in housing
IP 20 at the connection terminals

Weight

0,7 kg

0,2%
0,2% (included in error limit)
RC = 0....RC max.
0,05%
(included in error limit)
/10 K; rated temperature
0,2%
25C
within the permitted
0,05%
tolerance range for the supply voltage
200 ms
0,5% for field intensity of
0,4 kA/m
0,5% between 27...460MHz
at a distance 1m; power 1 W

Electrical test
Test voltage between for all circuits mutilly - 2,5kV/1 min. 60Hz
Test between direct current power supply and output:
UAX = 24VDC...Test voltage = 0,75kV/1 min. 60Hz
UAX = 48VDC...Test voltage = 1,5kV/1 min. 60Hz
UAX = 110/125VDC...Test voltage = 2,5kV/1 min. 60Hz
Pulse voltage
5kV; 1,2/50 us; 0,5Ws
Peaks
2,5kV;1MHz; 400 pulses / 1s
Notes:
Related to the final output value.
UrtdI = Rated voltage
IrtdI = Rated current
Response times below 200 ms result in bigger residual ripple.

Housing

Case

Base and cover of plastic

Climatic conditions
Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity

Mechanical test
Impact
Vibration

-20...+60C
-25...+70C
-40...+80C
75% of annual average with
light condensation
(others on consult)

acceleration 30g during 11ms


acceleration 2g frequency
5..150Hz

Galvanic Isolator ETI 30

DATA SHEET - N00318

for direct voltage or current signals

Electric Connections

Additional information

51 52

51 52

13 14

II -

+ UI -

UAX

II , UI
UAx
O1
O2

=
=
=
=

+ _ + _
61 62 63 64
O1

O2

Input Current or Voltage


Auxiliary power supply
Current or voltage output - normal
Output with load divider ( double output)
Optional

Notes
When using only O2 jump terminals 61 and 62
When using double output, there is no galvanic isolation between
the output signals.

Dimensional Drawing
Dimensions em mm

Page 3/4
August 2003

The following items contain tips and cautions to be observed by the user
for a good functional performance, as well as the maintenance of the
instrument and the safety of the installations.

Cautions

Be sure the voltages and currents to be connected to the instrument, are


compatible.
Loosen all connections from the instrument before removing it from the
installation .

Mounting Instructions

Oserve the ambient temperature range. At the place of installation, values


for vibration, dust, dirt and humidity, which must remain between the
limits, established by the protection class of the housing and the climatic
group, specified in this data sheet, have to be observed
.
For fastening on flat area use two M4 screws. For mounting on DIN rail,
use the snap-in device on the rear of the instrument.
The connections can be made with eye or fork type cable shoes.

Instructions for use

When connections have been made, switch on the power supply and
check at the output the functioning of the transducer.

Galvanic Isolator ETI 30

DATA SHEET - N00318

for direct voltage or current signals

Page 4/4
August 2003

Ordering information

Catalog number

Transducer cc/cc and Galvanic Isolator ETI-30

Housing
Case

Input Signal
0... 20mADC
4... 20mADC
0... 5VDC
0... 10VDC
Others (between 01mA up to 020mADC)
and (between 0... 25mV up to 750VDC)
Auxiliary power supply
110Vac
120Vac
127Vac
220Vac
24Vdc
48Vdc
110Vdc
125Vdc
Others

1
2
3
4
0

01
02
03
04
07
08
10
11
00

Output Signal
0...1mADC
0...5mADC
0...10mADC
0...20mADC
4...20mADC
0...10VDC
Others (+/-1mAdc, +/-20mAdc, +/-1Vdc e +/-15Vdc)
Options
Error limit 0,25%
Output with load divider (double output)
Standard (Class 0,5%)
Additional Information
Standard
Complement (Inform input signal )

1
2
3
4
5
7
0
1
2
5
1
C

For quoting and ordering please issue your order according to the specification text
Example:
Galvanic Isolator ETI-30 case
Input Signal
4...20mADC
Auxiliary power supply
220VAC
Output Signal
4...20mADC
Optional
Class 0,5%
Additional information
Standard
Code number : N00318204551

ABB Ltda - ATLV/IE Instrumentation Electrical


Avenue Dos Autonomistas, 1496 - 06020-902 - Osasco - SP
Phone +55 11 3688-8320 / 8323 / 8347 - Fax: +55 11 3688-322
instrumentacao@br.abb.com

You might also like