ETM50EN
ETM50EN
ETM50EN
Page 1/4
July 2005
Caractersticas
Application
Functioning
Voltage
Current
Power consumption
Rated frequency
Overload
The transformer (1) attenuates the input signal for the rectifier (2) and
effectuates a galvanic isolation between the in- and output signals. The
amplifier (3) converts the input signal into an output of alternating
voltage or current.
The rectifier (2) and the output module (3) need an auxiliary power
supply (4).
Characteristic curves
Output
Current
Signal limit
Load limit
Voltage
Residual ripple
Power supply
0..100/110/220/380/500V
(others on consult)
01A ou 05A (others on consult)
Voltage version: 0,65VA for class 0,5%
1,00VA for class 0,25%
Current version: 0,15VA
50;60 Hz 10% (others on consult)
permanently: 1,5 x UrtdI ; 2 x IrtdI
briefly: 4 x UrtdI/1s; 50 x IrtdI/1s
maximum: 250A/1s
0.20mA, 4...20mA,010V
(others on consult)
1,5 IrtdO, UrtdO mx.
25V; RC = infinite
Rc=
15.000(mV)
85265Vca e 90300Vcc
2060Vca/Vcc
consumption: 3W aprox.
Transducer ETM 50
Influence Magnitudes
Error limit
Reference condictions
Input:
Frequency:
Form factor:
Auxiliary Power supply:
Load:
Ambient temperature:
Heat up time:
Additional error above
1,2IrtdI or UrtdI
Linearity deviation
Load
Temperature
Auxiliary power supply
Response time
External magnetic fields
Radio frequency
interference
Electrical Test
Test voltage
Surge Voltage
Radio frequency
0,5% (standard)
0,25% (option)
UI = UrtdI
II = 0...IrdtI for sinusoidal
electrical magnitudes without
zero displacement
frtdI 2%
1,111
UAX 2%
0,5 RC mx.
25C 2K
. 20 min
0,2%
0,2% (included in error limit)
0,05% RC = 0....RC mx.
(included in error limit)
0,2% /10 K; rated
temperature 25C
0,05% within the permitted
tolerance range for the supply
voltage
voltage
200 ms
0,5% for field intensity of
0,4 kA/m
0,5% between 27...460MHz
at a distance of 1m; power 1W
Uax. 85V : 2,5kV/1mim ; 60Hz
(for all circuits mutually).
Uax. 60V : 1,5kV/1min ; 60Hz
(for all circuits mutually).
5kV; 1,2/50us; 0,5Ws
2,5kV;1MHz; 400 pulsos / 1s
Notes:
- With respect to the output span.
- UrtdI = Rated voltage
- IrtdI = Rated Current
Response times below 200ms result in bigger residual ripple.
Page 2/4
July 2005
Climatic conditions
Operation temperature
Functioning temperature
Transport and storage
temperature
Relative humidity
Mechanical test
Impact
Vibration
-20...+60C
-25...+70C
-40+80C
75% of anual average, with
light condensation
(others on consult)
acceleration 30g ; during 11ms
acceleartion 2g ;frequency
5..150Hz
Transducer ETM 50
Page 3/4
July 2005
Additional information
Electric Conections
II
II , UI
UAx
O1
5
UI
=
=
=
13 14
+ _
61 62
UAX
O1
Dimensional Drawing
Dimensions in mm
Cautions
Mounting Instructions
For mounting on DIN rail, use the snap-in device on the rear of the
instrument.
The connections can be made with pin for shaped cable shoes.
Transducer ETM 50
Page 4/4
July 2005
Ordering information
Catalog number
TRANSDUCER ETM-50 for alternated current or alternated voltage
Housing
Normal
RMS
3
9
Rated Frequency
50 Hz
60 Hz
400 Hz
Others
1
2
3
0
Measuring range:
Voltage: between 0...10 up to 0..20VAC
between 0...21 up to 0...50VAC
between 0...51 up to 0...97VAC
between 0...98 up to 0...180VAC
between 0...181 up to 0...340VAC
between 0...341 up to 0...600VAC
Current: 0...1A
0...5A
Others
Auxiliary Power Supply
2060Vca/Vcc
85265Vca and 90300Vcc
1
2
3
4
5
6
7
8
0
12
13
Output Signal
0...20mADC
4...20mADC
0...10VDC
Others( 0...1mAdc at 20mAdc e 0...1Vdc at 0...15Vdc)
Optional
Error Limit 0,25%
Others response times between 50ms and 2s
Standard (Class 0,5%)
Additional information
Standard
Complement (Inform input signal voltage)
For quoting and ordering please issue your order according to the specification text.
Example:
Transducer ETM 50
Rated frequency:
60Hz
Measuring range:
05A
AuxiliaryPower supply:
85265Vca e 90300Vcc
Output Signal:
420mADC
Options:
Error limit 0,25%
Additional information:
Standard
Code number : N003932813511
4
5
6
0
1
4
5
1
C