ETPETQEN
ETPETQEN
ETPETQEN
Characteristics
Active power measuring in balanced and unbalanced singlephase or three-phase mains. Power measuring for sinusoidal
signals.
Output signal with or without suppressed zero.
Galvanic isolation between input and output and auxiliary
power supply
Reduced size for mounting space saving.
Case type housing for fixing with screws or in din-rail
Output with load divider (optional).
Application
Page 1/5
August 2003
Characteristic curves
Functioning
Examples of zero-displacement.
Power
direction
Unidirectional
The transforming units (1) attenuate the voltage and current input
signals, condition them to the multiply module (2) and establish a
galvanic isolation between the input and output signals
The multiplier (2) uses the TDM (time-division-multiplication)
principle working with an insignificant deviation from the above
mentioned equation. The result is a voltage signal proportional to be
measured power. The amplifier (3) filters this signal and converts it
into a direct current or voltage signal. The power supply (4) feeds
auxiliary power to all intern circuits with galvanic isolation from the
power net by means of an own transformer. The output module (5)
transmits 180 displaced pulses via two transmission channels in a
frequency, which is proportional to the input signal.
Bi-directional
Io
IrtdO
A
=
=
=
A/B
Characteris
tics
Measuring
Field (kW)
Output
(mA)
Zerodisplacement
A
C
F
A/B
A/B
E
D
0....100
0....100
20..100
-100..0...+100
-20....0...+100
-50....0....+100
-75....0....+50
0...20
4...20
0...20
-20...0...+20
-4...0...+20
0...20
4...20
no
yes
yes
no
no
yes
yes
Rated voltage
Current
Signal limit
Calibration
factor (cf)
Zero
displacement
Consumption
Rated frequency
Overload
Ground voltage
0..110/220/380/500V
0..1//5 A (other on consult)
UrtdI = 10...660V
IrtdI = 0,5...5 A
0,5...1,5 (others on consult)
The scale end value has to be calculated with a
factor between 0,5...1,5 times the value of the
apparent power. The apparent power (S) is
calculated using the value of the primary winding
of the transformers:
S = U x I (single phase circuit)
S = U x I x 3 (three phase circuit)
cf = P or Q = wanted power (scale end)
S
apparent power
max. 75%
voltage input: 1mA
current input: 0,15VA
50;60:400 Hz 10%
(others on consult)
permanently: 1,5 x UrtdI ; 2 x IrtdI
briefly: 4 x UrtdI/1s; 50 x IrtdI/1s
maximum: 250 A/1s
660V max. (IEC 348)
Output
Unidirectional
measuring
Bi-directional
measuring
Signal limit
Load limit
Residual ripple
Output with load
divider (optional)
Rc =
15.000(mV)
max output signal (mA)
0,5% (peak to peak)
To calculate Rc use 7.500mV instead of
15.000mV, the results will br the same
for both outputs.
Page 2/5
August 2003
Power supply
a) 2060Vac/Vdc
b) 85265Vac/90300Vdc
consumption: 4W
Influence magnitudes
Error limit
Reference
conditions
Input
Frequency
Form factor:
Auxiliary power
supply:
Power factor
II = 0...IrtdI;
UI = 0...UrtdI
frtd 2%
1,111
UAX 2%
c o s = 1 (active power)
s e n = 1 (reactive power)
0,5RC max.
Load:
Ambient
temperature:
25C 2K
Heat up time:
20 min.
Additional error above
1,2IrtdI or UrtdI
0,2%
Linearity deviation
0,2% (included in error limit)
Load
0,05% RC = 0....RC max.
(included in error limit)
Temperature
0,2% /10 K;
rated temperature 25C
Auxiliary power supply
0,05% within the permitted
tolerance range for the supply voltage
Response time
200 ms
External magnetic
interference
0,5% for field intensity of
0,4 kA/m
Radio frequency
interference
0,5% between 27...460MHz
at a distance of 1m; power 1 W
Crest factor
4 for alternating not sinusoidal
electrical magnitude
Electrical test
Test voltage:
UAX = 2060Vca/Vcc = 1,5kV/1 min. 60Hz
between auxiliary power supply and others
Test voltage:
UAX = 85265Vca/90300Vcc = 2,5kV/1 min. 60Hz
Between auxiliary power supply and others
Peak and transient
protection
5kV; 1,2/50 Uo; 0,5Wo
High frequency
interference
2,5kV; 1MHz; 400 pulses / 1s
Electrical
connection
Protection class
(NBR6146)
Weight
Climatic conditions
Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity
-20...+60C
-25...+70C
-40...+80C
75% of annual average with light
condensation (others on consult)
Mechanical test
Impact
Vibration
Notes:
Umin = 50V for single-phase circuit power or equilibrated threephase circuit with a simulated phase.
Frequency deviation = 0,6% max. for active power measuring in
single-phase circuit or reactive power measuring in equilibrated
three-phase circuit with a simulated phase.
Unidirectional measuring related to the end value of the output
signal. Bi-directional measuring related to the end value of the
biggest signal range.
Response times below 200 ms result in bigger residual ripple.
Electrical Connections
13 14
UAX
Uax
O1
O2
=
=
=
+ _ + _
61 62 63 64
O1
Page 3/5
August 2003
Input without PT
Case
Housing
Fastening
O2
Notes
When using only O2 jump terminals 61 and 62
When using double output, there is no galvanic isolation
between the output signals.
Page 4/5
August 2003
Input with PT
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
Dimensional drawing
Dimension in mm
Additional information
The following items contain tips and cautions to be observed by the user for
a good functional performance, as well as the maintenance of the instrument
and the safety of the installations.
Cautions
Mounting Instructions
When connections have been made, switch on the power supply and
check at the output the functioning of the transducer.
For quoting and ordering please issue your order according to the
specification text.
Example:
Transducer ETP-30
Housing:
Rated frequency:
Measuring circuit:
Input voltage and current:
Auxiliary power supply:
Calibration factor:
Output signal:
Measuring field:
Optional:
Case
60Hz
Single-phase
0...110V/ 0...5A
85265Vca/90300Vcc
0,909
4...20mADC
200..500W
Class 0,5%
Page 5/5
August 2003
Ordering information
TRANSDUCER FOR POWER, housing case
Model / Variable
ETP-30 active power
ETQ-30 reactive power
Rated Frequency
50 Hz
60 Hz
400 Hz
Others
Measuring Circuit
Single-phase
3-wire 3-phase balanced load 3 ~1 E
3-wire 3-phase unbalanced load 3 ~2 E
4-wire 3-phase unbalanced load 3N ~3 E
Input Voltage (+/- 15% )
66V
110V
220V
380V
500V
Input Current
1A
5A
Others
Power Supply
20 60Vca/Vcc
86265Vca/90300Vcc
Output Signal
0...1mADC
0...5mADC
0...10mADC
0...20mADC
4...20mADC
0...10VDC
Others(+/- 1mAdc, +/- 20mAdc, +/- 1Vdc and +/- 15Vdc)
Option
Error limit 0,25%
Output with load divider ( double output)
Others response times between 50ms and 2s
Standard (Class 0,5%)
Additional Information
Standard
Complement (Inform measuring field, TP, TC, etc)
Catalog number
-
2
4
1
2
3
0
1
2
4
7
1
2
3
4
5
1
2
0
12
13
1
2
3
4
5
7
0
1
2
4
5
1
C