Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Kam

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

KAM

Primary Current Injection Test System

High current output up to 7000 A

KAM test system is designed for primary injection testing of


protection relays and circuit breakers, for commissioning and
revamping of substations and electrical network.

Powerful output up to 35 kVA


Modular design for easy transport
Primary current injection testing
Protection relay testing
Low voltage Breaker testing
Heat runs
CT testing

OUTPUT CURRENT

Model

Steady
Current
A

Steady
Power
VA

Peak
Current
5s

Peak
Power
5s

Peak
Current
1s

Peak
Power
1s

KAM 2/5
KAM 5/12.5
KAM 5/12.5G
KAM 10/25
Duty Cycle

500; 1000; 2000


500; 1000; 2000
750; 1500; 3000
500; 1000; 2000
Continuous

2000
5000
5000
10000
Continuous

6000
6000
6000
6000
5 seconds

5000
12500
12500
25000
5 seconds

7000
7000
7000
7000
1 second

5000
15000
15000
35000
1 second

KAM

KAM SPECIFICATION
The test system KAM is a high current unit consisting of a
control unit and one or two external power transformers, that
can be easily taken in proximity of bus-bars, thus keeping to
the minimum the test cable length.
KAM range comprises four models:
. KAM 2/5;
. KAM 5/12.5;
. KAM 5/12.5G;
. KAM 10/25.
Current range or voltage output selection: by means of a fiveposition I/V selector switch: 500A 1000A 2000A 6000A
V (750 1500 3000 - 6000 V for the G model).
Current and power range selection.
Coarse and fine output adjustment.
Current metering: by 4 and half digit instrument, with hold
function.
Adjustable voltage output characteristics:
. Range: 0 to 270 V AC;
. Current output: 0 to 15 A.

Timer
Metering: from current injection to contact tripping (relay tests)
or current injection duration (circuit breaker tests); switch
selection.
Timer range: 999.99 s or 99.999 s; switch selectable. Accuracy:
0.01% 1 digit.
Display on 5 digits, and with built-in 10 MHz quartz oscillator
Input contacts dry or wet.
Voltage range: 24 V to 220 V, DC or AC.

Power supply
Power supply: 230 V 15%; 50/60 Hz.

Protections
Magneto-thermal circuit breaker on the mains supply.
Fuses on DC supplies.
Alarm light and buzzer if the output current exceeds 120% of
the selected range.
Current cannot be injected if the transformer is not connected.
Thermal protection on the power transformers, with alarm light.
Impulse current cut-off is not reset at power down.
Fuse protection on the auxiliary voltage output: T5.

The adjustable, not isolated voltage, is not available unless with


V selection.

Case
Control unit: aluminium case with cover and handles.
Power transfomers: aluminium case with handles and wheels.

Weight and dimensions


CONTROL UNIT
KAM 2/5, KAM 5/12.5 and KAM 5/12.5G: 33 kg.
KAM 10/25: 37 kg.
Dimensions: 300 x 620 x 260 mm.
POWER TRANSFORMERS
Number: one for KAM 2/5; two for KAM 5/12.5, KAM 5/12.5G,
and KAM 10/25.
Weight: KAM 2/5: 70 kg. KAM 5/12.5 and KAM 5/12.5G: 70 kg
and 85 kg. KAM 10/25: 104 kg and 125 kg.
Dimensions: KAM 2/5, KAM 5/12.5 and KAM 5/12.5G: 310 x 270
x 400 mm; KAM 10/25: 450 x 270 x 400 mm.
Transformers are supplied with a C-shaped plate, for their
interconnection.

Accessories supplied with the unit


Each KAM unit is supplied complete with the following accessories:
. Interconnection cables between the control box and the transformers, 2 m long.
. Mains cable.
. Cable to the trip contact, 2 m long.
. Operating manual.
Cables for connection to the load are not provided as standard
accessories.

OPTIONAL CONNECTION CABLES


The following connection cables are available upon request:
1. Code 15085. Set made of 4 cables, 200 sq. mm. cross
section, length 0.5 m, terminated with ring terminals on
both sides, and complete with 2 screw-driven clamps to
lock the cable to the bar. Cables are to be used in parallel,
in order to reach 400 sq. mm in all, and allow reaching 6000
A peak on all types of test sets.
2. Code 16085. Set made of 4 cables, 200 sq. mm. cross
section, length 1 m, terminated with ring terminals on both

KAM

PRIMARY CURRENT INJECTION TEST SYSTEM

sides, and complete with 2 screw-driven clamps to lock the


cable to the bar. Cables are to be used in parallel, in order
to reach 400 sq. mm in all, and allow reaching 6000 A peak
KAM-5/12.5, and 2000 A on KAM-2/5.
3. Code 17085. Set made of 4 cables, 200 sq. mm. cross
section, length 2.5 m, terminated with ring terminals on
both sides, and complete with 2 screw-driven clamps to
lock the cable to the bar. Cables are to be used in parallel,
in order to reach 400 sq. mm in all, and allow reaching 6000
A peak on KAM-10/25, and 2000 A on KAM-5/12.5. With
series connection, you get 5 m, and you can reach 2000 A
on KAM 10/25.
4. Code 18085. Set made of 4 cables, 200 sq. mm. cross
section, length 5 m, terminated with ring terminals on both
sides, and complete with 2 screw-driven clamps to lock the
cable to the bar. Cables can be connected in parallel, in
order to reach 400 sq. mm in all, they allow reaching 2000
A on KAM-10/25. If connected in series, you have 10 m, and
you can reach 1000 A on KAM-5/12.5.
5. Code 19085. In addition to the above cables, we can
provide a cable set made of three cables, each of which, in
its turn, is made of four pairs of 25 sq. mm twisted pairs:
this arrangement reduces the reactive component of the
cable impedance, and is designed to reach 2000 A on KAM
5/12.5 at the distance of 6 m. The set is complete with 2
screw-driven clamps to lock the cable to the bar. Cables can
be connected in series or in parallel, according to the desired test current and the distance to the target. The weight
of each cable is 15 kg, so that the set is 45 kg: this is to
be considered, if cables cannot be lifted and screwed to the
clamp separately.

All the above cables are provided with two high current
screw-driven clamps for the connection to bars, having the
following characteristics:
- Material: aluminium.
- Opening range: from 5 to 60 mm.
- Short-circuit current rating: 41 kA / 1 s.
- Applicable standard: EN 61230.
- Hole to lift the clamp on the conductor, and ring to screw
it up.

APPLICABLE STANDARDS
Electromagnetic compatibility
Directive no. 2004/108/EC.
Applicable Standard : EN61326-1 + A1 + A2.

Low voltage directive


Directive n. 2006/95/EC.
Applicable standards, for a class I instrument, pollution degree
2, Installation category II: IEC EN 61010-1.
In particular:
- Dielectric Rigidity: 1.4 kV, 1 minute.
- Isolation resistance: > 2 MOhm.
- Earth resistance : < 0.1 Ohm.
- Dispersion current: < 5 mA.
- Inputs/outputs protection: IP 2X .
- Operating temperature: 0 - 50C; storage: -25C to 70C.
- Relative humidity : 5 - 95%, not condensing.

6. Code 20085. Cable set made of four cables, each of


which, in its turn, is made of four pairs of 25 sq.mm twisted
pairs: this arrangement reduces the reactive component of
the cable impedance, and is designed to reach 3000 A on
KAM 5/12.5G at the distance of 1,8 m. The set is complete
with 2 screwdriven clamps to lock the cable to the bar.
Cables can be connected in series or in parallel, according
to the desired test current and the distance to the target.

KAM

ORDERING INFORMATION
30084
16085
15085

80085
17085
19085
16085

50085
20085

15085

60086
18085
17085

MODULE
KAM 2/5 Digital Hold
Compatible connection cables:
4 cables of 200 sq. mm, connected in
parallel,1m long (2000A max)
4 cables of 200 sq. mm, connected in
parallel, 0,5 m long (6000A max 5 seconds)
KAM 5/12.5 Digital Hold
Compatible connection cables:
4 cables of 200 sq. mm, connected in
parallel, 2,5 m long (2000A max)
1 set of 3 cables, each of which,in its turn,
is made of 4 pairs of 25 sq. mm twisted
pairs, 6m long (2000A max)
4 cables of 200 sq. mm, connected in
parallel,1m long (6000A max 5 seconds)
KAM 5/12.5-G Digital Hold
Compatible connection cables:
1 set of 4 cables,each of which,in its turn,is
made of 4 pairs of 25 sq.mm twisted pairs.
They can be connected in series or in paral
lel, 1,80m long (3000A max)
4 cables of 200 sq. mm, connected in
parallel, 0,5 m long (6000A max 5 seconds)
KAM 10/25 Digital Hold
Compatible connection cables:
4 cables of 200 sq. mm, connected in
parallel, 5 m long (2000A max)
4 cables of 200 sq. mm, connected in
parallel, 2,5 m long (2000A max)

ISA Srl
Via Prati Bassi, 22
21020 Taino VA - Italy
Tel +39 0331 956081
Fax +39 0331 957091
Web site: www.isatest.com
E-Mail: isa@isatest.com
4

EN - KAM - 04/2014

CODE

The document is subject to change without notice.


Always refer to our technical specification for more detailed
information and as formal contract document.