Calculate Size of Inverter & Battery Bank: Electrical Notes & Articles
Calculate Size of Inverter & Battery Bank: Electrical Notes & Articles
Calculate Size of Inverter & Battery Bank: Electrical Notes & Articles
1 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
Factor
80
1.00
70
1.04
60
1.11
50
1.19
40
1.30
30
1.40
20
1.59
Calculation:
Step 1: Calculate Total Load:
Fan Load= No x Wa =260=120 Wa
Fan Load=(No x Wa )/P.F=(260)/0.8= 150VA
Computer Load= No x Wa =1200=200 Wa
Computer Load=(No x Wa )/P.F =(1200)/0.8= 250VA
Tube Light Load= No x Wa =230=60 Wa
Tube Light Load=(No x Wa )/P.F =(230)/0.8= 75VA
Total Electrical Load=120+200+60 =380 Wa
Total Electrical Load=150+250+75= 475VA
Step 2: Size of Inverter:
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
2 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
3 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
4 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
(h ps://electricalnotes.les.wordpress.com/2015/10/series-parallel_ba ery_cong.jpg)
Summary:
Total Electrical Load=380 Wa
Total Electrical Load=475VA
Size of Inverter= 712 VA
Size of Ba ery Bank= 101.3 Amp/Hr
For 120 Amp/Hr , 12V DC Ba ery : Series Connection & 2 Nos of Ba ery or
For 60 Amp/Hr , 12V DC Ba ery : Series-Parallel Connection & 4 Nos of Ba ery
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
5 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
Thanks
Reply
electroninz says:
December 3, 2015 at 5:01 pm
Hi Mr. Parmar,
This is the rst time I actually follow and review the content of your mails. Theres a lot of error here.
Firstly, you wont be able to get 712VA with your formula of 475 + (1+20%) / 80%, unless you multiply 475 to rests of the equation,
not add.
Secondly, total load of ba ery bank is 31.66 Ah, not 32.66.
Thirdly, the unit for size of ba ery bank should remain Ah not Amp/Hour.
I did not nish the rest of the article. Theres probably more error down there.
Thanks for the eort, anyway.
Best regards, Ben
>
Reply
ravindrababu uba says:
December 4, 2015 at 5:46 pm
how to prepare single line diagram,slection of panels
Reply
prathap singh says:
January 7, 2016 at 9:26 am
type-2 cordetation chart
Reply
S.Prashant says:
December 6, 2015 at 5:22 pm
Thank you sir, these calculation is realy very useful.
Reply
Vikas G says:
December 7, 2015 at 7:33 am
Thanks Sir.
It is a great help.
Regards, Vikas Gupta.
Vikas Gupta.
Reply
vilas harlapur says:
December 7, 2015 at 10:34 am
Dear sir, will be there any major problem if one ba ery of 12 70 Ah in a bank of 15 ba eries (series parallel combination) is repalced
by 12 V 75 Ah ba ery. with regards,
vkh
Reply
Ajanta Mahanta says:
December 11, 2015 at 5:23 am
Dear Sir,
As directed for expert/OEM opinion i am jo ing down the schemes in which the 11.5MW Myntriang Small Hydro Electric
Project(MSHEP) run.
*1st Scheme:* Originally 21.5MW MSHEP grid oriented machines get synchronized in the 33KV side. The 33 KV evacuation line is
8Km which feed this 3MW power from the generating station to 220KV grid substation through a 220/33KV Station Resesrve
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
6 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
Transformer(SRT).
*2nd Scheme:* Due to non-availability of 220/33KV SRT this 3MW power of MSHEP was synchronized with another 33/132 KV
grid substation. this 33/132KV grid substation is around 40Km away from MSHEP. this 40Km, 33 KV line passes via two numbers of
33/11Kv distribution substations. The faults of this 33KV line is very frequent.
whether the *2nd scheme *of evacuation for this particular 21.5MW MSHEP machines is proper. Kindly suggest some measures to
run the machines in *2nd scheme *smoothly.
With regards, A.Mahanta DM,APGCL.
Reply
Renjith Kumar says:
December 14, 2015 at 11:19 pm
nice calculation use full for normal man thangs
*Thank you for your kindness and consideration*, RENJITH PILLAI
t
Reply
Andrea AP says:
December 21, 2015 at 9:25 am
Thanks for sharing
Reply
B.D. says:
January 2, 2016 at 6:33 am
This post is very helpful, though the calculations done for condition I and II are quite confusing like
for 60 Ah ba ery
Parallel Conguration
Condition-I :
Selection of Ba ery for Amp Hr = Amp Hr of Ba ery Bank / Amp Hr of Each Ba ery <=1
Selection of Ba ery for Amp Hr =101/60 = 1.63=1 Nos
Condition-I is O.K
How ? it does not fullls Amp Hr of Ba ery Bank / Amp Hr of Each Ba ery <=1
There are lot more
Reply
A.Balan says:
January 4, 2016 at 2:33 pm
Thanks for a nice explanation. Like to second conrmation with your permission for the following :1) parallel connection with similar Ah and same Voltage of each ba ery:
(a) Ah is increased&Voltage is same
2) Series connection for the ba eries as(1):
(b) Ah is same&Voltage is increased
Clarication :
The lowest Ah should be taken in to an account for DIFFERENT Ah with same / similar voltage ba eries to the above(1) & (2).
Advise me with diagrams pl.
Reply
prathap singh says:
January 5, 2016 at 9:28 am
dear sir
how to desired amp hr of ba ery bank in series connection 3
and parallel connection 101
please explain
Reply
prathap singh says:
January 5, 2016 at 9:32 am
dear sir
this is very excellent explanation. but how to desired amp hr of ba ery bank in series connection 3 and parallel connection 101
Reply
1/18/2017 5:45 PM
Calculate Size of Inverter & Battery Bank | Electrical Notes & Articles
7 of 7
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-invert...
Blog at WordPress.com.
1/18/2017 5:45 PM