Primary Current

Injection Test Sets


PCITS600/2 & PCITS2000/2

User Guide

MEGGER
FOSTER

SAFETY WARNINGS

The Test Set must be properly earthed before use.

The output terminals must be clean and free of grease and dirt before switching on.

The output test leads must be of the correct rating.

The Test Set must be switched Off by the power switch before any connections on the set
or the equipment under test is touched.

After a period of testing under full load, the terminals and lead connectors may be hot.

The equipment under test must not be touched while the power is switched On.

The permitted duty cycle must not be exceeded.

Replacement fuses must be of the correct type and rating.

The main current terminals must not be connected to a live potential.

The Test Set must be switched Off when resetting circuit breakers.

Refer also to page 10 for further explanations and other precautions.

Warnings and Precautions must be read and understood before the Test Set is used.
They must be observed during use.

NOTE
THE TEST SET MUST ONLY BE USED BY TRAINED AND COMPETENT PERSONS

Symbols used on the Test Set :


Caution: Refer to accompanying notes.
Caution: Risk of electric shock.
Caution: Hot surface
Equipment complies with relevant EU
Directives

Contents
Safety Warnings

General Description

Applications

Specification

Accessories

Operation

10

Warnings

10

Precautions

10

Preliminary procedure

11

Setting the display options

12

Current injection and IDMT testing

12

Manual testing

13

IDMT Forward test

14

IDMT Runback test

15

IDMT Dual test

16

Auxiliary voltage testing

17

Other messages

18

Guidance in Choice of Test Leads for Current Carrying Capacity

19

Duration Tests

20

Circuit Description

21

Sicherheitshinweise

24

Betriebsanleitung

25

Repair and Warranty

36

Components List

37
Illustrations

Figure 1 PCITS 600/2 and PCITS 2000/2

Figure 2 Principle of primary current injection testing

Figure 3 Principle of secondary current injection testing

Figure 4 The main menu showing the testing options available

12

Figure 5 The 'CURRENT' testing options screen

13

Figure 6 The 'AUX VOLTS' testing options screen

18

Figure 7a Guidance for cross sections and lengths of cables

19

Figure 7b One - shot Test Duration PCITS600/2 and PCITS200/2

20

General Description

The PCITS600/2 and PCITS2000/2 Primary Current Injection Test Sets are rugged, self-contained
instruments designed for operation by one person. They provide facilities for testing all elements of
electricity supply/distribution protective equipment.
The PCITS600/2 is built into a tough moulded plastic casing, with carrying handles, and has a protective
cover over the terminal panel. A transportation trolley is available separately. The PCITS2000/2 is
constructed in a sheet steel case on a two wheeled trolley, and can be used in either its horizontal or
vertical position. The terminal panel for each instrument contains the range switch, power supply switch,
output terminals and time counter terminals. The test set is operated from a separate hand-held controller
linked to the main unit by an expandable coiled lead.
The, fully variable, current outputs from each test set are:PCITS600/2
600 A at 0-4 V a.c.
300 A at 0-8 V a.c.
PCITS2000/2
2000 A at 0-3 V a.c.
1,000 A at 0-6 V a.c.
The supply voltage requirements are 220 V/240 V + 6% -10% 50 Hz/60 Hz single phase, i.e. 198 V to
254 V, at full output current. Two auxiliary voltage outputs are available from each set; 0 to 125 V a.c. and 0
to 250 V a.c. It is important to note that on the main current outputs a duty cycle applies above 40% of rated
output.
The test sets have magnetic circuit breakers, fuse and thermal protection. Output test leads are available as
separate items.
The illustration of figure 1 shows the components of the terminal panel and controller and their function is
briefly described below.
Power Input
The mains supply cable is permanently connected through a strain relieving gland. Adjacent to this is a
green/yellow terminal by which the test set may be separately earthed so that total reliance for earthing is
not placed on the supply cable. The supply cable must be terminated with a suitable plug bearing in mind
the kVA rating of the test set. Observe the correct polarity when connecting a plug to the cable; brown to
line, blue to neutral and green/yellow to earth.
The power supply switch is a two-position on/off type marked
and , and there is an amber indicating
lamp to show when the power is switched on.
Output Terminals
The main heavy current output terminals have wing-nut screw clamps and those for the auxiliary voltage
output and time counter will take normal spade connectors or 4 mm plugs (Current output, voltage output
and time counter each have their own pair of terminals).
Range Switch
A two-position rotary switch selects the higher and lower current/auxiliary voltage ranges. Apart from this
coarse range selection the remainder of the operation of the test set is achieved via the hand-held
controller. The higher current range (600 A or 2000 A) should be used for most testing purposes. The lower
current range (300 A or 1000 A) is provided to enable current injection into high impedance loads at a
higher output voltage.
Hand-held Controller
The hand-held controller has grip pads whereby it may be fixed in place on the main unit of the test set. It
may be used in that position but more likely it will be lifted off and held in the hand during operation. This
facility enables the user to leave the heavy main unit on the floor and still control the test while observing
closely the protective relay under test (which may be a metre or so above the floor).
The test set incorporates a microprocessor and utilises the benefits from this type of circuitry. The controller
has an alpha-numeric dot-matrix liquid crystal display. The programme menus, set-up instructions and test

Figure 1 PCITS600/2 and PCITS2000/2

General Description
results appear on the display screen. Three tactile membrane key switches on the controller are used to
operate the test set. Each key is allocated more than one function during the test procedure, and these
functions are indicated on the display at the relevant point in the programme.
Time Counter (IDMT Testing)
Each test set has a built-in time counter for measuring the time the relay under test takes to operate, or to
reset itself. The relays contact-set, is connected to the TIMER STOP terminals allowing the operation
and/or runback times to be measured at the instant the contacts change state. The TIMER STOP inputs
accept either unenergised or 100-264 V a.c./d.c. energised contacts. Note that the PCITS600/2 and
PCITS2000/2 differ from the original versions of the PCITS regarding this feature.
For IDMT testing, the time counter is started when the test current is applied and stopped when the
contacts in the relay under test open or close. The test also stops upon cessation of current (due to load
disconnection) or by manual operation of the hand-held controller. In the runback mode, the time counter
starts automatically when the relay contacts operate, or upon cessation of test current, but it must be
stopped using the hand-held controller.
In-built Protection Mechanisms
In-built protection mechanisms include both current overload and thermal protection in the form of circuit
breakers, high breaking capacity fuses and a thermal cut-out.
The current output circuit is protected against overload by two resettable circuit breakers; a short delay
breaker is in series with the variac output and a long delay breaker protects the input circuit. One or both of
these breakers will trip in the event of a significant overload current or fault occurring in the output control
circuit.
For thermal protection, a bi-metallic sensor is mounted in the main transformer which will operate if the duty
cycle is exceeded and an adverse temperature rise in the test set results.
For safety, the circuit has been designed such that when the contacts of the relay under test operate to stop
the time counter, the output of the test set is also switched off. The test set is reset if there is a power
supply failure.
The HBC fuses provide overload protection for the auxiliary output and the controller unit. The solid state
relay which controls the switching on and off of the current output is approved to BASEEFA and ULE86767
standards.
In addition to these protection features of the test sets, a further safety measure is incorporated. If voltage is
detected on the terminals during the setting-up routine, or in the IDMT test-suspension states, then the
variac will automatically wind down to the zero position to ensure that no output is possible and an error
message will be displayed.
Current Setting Capability
The PCITS uses a variac to drive the main output transformer which supplies the required test current. Due
to the variacs finite winding resolution it is not generally possible to establish a test current that exactly
matches the programmed value. The situation worsens as the load resistance (load plus leads) decreases
since only a small portion of the total variac winding might then be used for setting the required test current.
This can produce a test current which deviates from the programmed value.
To improve the setting accuracy a longer lead set could be used. Additionally the instrument should, if
possible, be used on the high current (low voltage) range to lower the voltage output per winding of the
variac.
The PCITS600/2 normally sets the test current to within 1 A of the programmed value when supplying
higher resistance loads. For the wider range PCITS2000/2 this figure may increase to 3 A. This arises due
to the measurement resolution being 0,2% of the full scale indication.

Applications
Applications
The main application of these Primary Current Injection Test Sets is the testing of complete electrical
distribution/supply relay protection systems. They are normally employed at the time of commissioning
protection equipment or after major repair since it is usually inconvenient to take the complete system off
line. All components of the protection system are tested i.e. the isolated high voltage conductor, the current
transformer, the protection relay and the circuit breaker.
Most electricity supply protective equipment is fed from a current transformer on the supply cable or bus
bar. A high test current, sufficient to cause the protection equipment to operate, is injected into the supply
cable and the time taken for the protecting relay to operate is then measured.
Primary testing will detect current transformers connected with incorrect polarity or relays that have been
set in the wrong sequence in differential systems. However the inconvenience of breaking the primary
circuit means that the method is unsuitable for routine testing.
For routine testing secondary current injection testing is usually employed. This checks the operation of the
protecting relay etc. but does not test the overall system including the current transformer.
Primary testing usually requires a high current (over 500 A). Secondary current injection testing is easier
since there is not the need to break the primary circuit and the current required through the operating coil of
the protective device is lower (up to 100 A).
The relay incorporated in systems usually has a critical performance in relation to time. The built-in timer
will enable the operating time of the relay to be thoroughly tested.
Several methods of measuring the operating time are possible. Figure 2 illustrates two methods when the
test current is not interrupted by the relay operating. Condition A tests the relay by sensing the relay
changing state with the timer stop terminals. Note: the relay contacts are connected directly across the
TIMER-STOP terminals. Similarly, condition B tests the relay and the circuit breaker trip coil by monitoring
auxiliary contacts. Figure 3 shows the PCITS measuring the total trip time by sensing the interruption of
current flow in the circuit under test.

PCITS

PCITS

X
Closed

PROTECTIVE
RELAY

PROTECTIVE
RELAY
Condition A
Condition C

Aux
Contact

Condition B

Figure 2

Figure 3

A further application of these test sets is the testing of the current transformers phasing. Again the test is
normally performed at the commissioning stage or after major repair.
The auxiliary voltage outputs may be used for testing voltage operated relay coils or checking the
magnetization characteristics of current transformers.

Specification
Maximum Current Output a.c.
PCITS2000/2
PCITS600/2

2000 A at 0 to 3 V, 50 Hz/60 Hz
1000 A at 0 to 6 V, 50 Hz/60 Hz
600 A at 0 to 4 V, 50 Hz/60 Hz
300 A at 0 to 8 V, 50 Hz/60 Hz

Auxiliary Voltage Output a.c.

0 to 250 V, 0-2 A, 50 Hz/60 Hz


0 to 125 V, 0-2 A, 50 Hz/60 Hz
All outputs are able to rise to 50 V above earth potential.

Timer Stop Inputs

Inputs for volt-free or a.c./d.c. energised contacts at


100 V to 264 V

Display
Current Range PClTS 2000/2
Current Range PCITS 600/2
Auxiliary Voltage Range
Accuracy
Elapsed Time

Dot matrix l.c.d.


0-2000 A, range resolution 1 A
0-600 A, range resolution 1 A
0-250 V, resolution 1 V; 0-2 A, resolution 0,01 A
3% of reading 2% LS digits
0-600 s, resolution 0,01 s, accuracy 0,1% 0,05s

Duty Cycle

212 minutes on circuit and 15 minutes off circuit at full


range current and voltage. Duty cycle increases until
continuous use is possible at 40% of full range.

Temperature Range
Operation
Storage

0C to 40C
-20C to + 60C

Humidity Range
Operation
Storage

(900% RH at 40C for 48 hours)


(93% RH at 40C for 12 hours)

Supply Voltage

Equipment Protection
Circuit Breakers

220 V/240 V +6%-10%, 50 Hz/60 Hz, single phase i.e.


198 V to 254 V at full output current.
7 kVA for PCITS2000/2, 3,5 kVA for PCITS600/2

Auxiliary Output Fuse

2 x 30 A rating breakers for PCITS2000/2, one short


delay and one long delay.
2 x 15 A rating breakers for PCITS600/2, one short delay
and one long delay.
2 A ceramic HBC 20 mm x 5 mm IEC 127/1

Controller Supply Fuse

1 A ceramic HBC 20 mm x 5 mm IEC 127/1

Safety

The test set will, in general, meet the requirements of the


IEC 1010-1 specification

Dimensions
PCITS2000/2

Controller

320 mm x 305 mm x 510 mm (1212 in x 12 in x 20 in


approx.) excluding handles and wheels.
495 mm x 307 mm x 310 mm (1912) in x 12 in x 1214 in
approx.) excluding handles.
202 mm x 127 mm x 55 mm (8 in x 5 in x 218 in approx.)

Weight
PCITS2000/2
PCITS600/2

61 kg (134 lb approx.)
38 kg (8312 lb approx.)

PCITS600/2

Cleaning

Wipe disconnected, cooled Test Set with a clean cloth


damped with soapy water or Isopropyl Alcohol (I.P.A.)

Accessories
Optional extras

Part Number

2000 A low inductance lead set (3 m long)

6220-462

600 A low inductance lead set (5 m long)

6220-463

(Duty cycle on test leads, 212 minutes on and 15 minutes off)


Trolley for PCITS600/2

6320-224

Leads for timer stop and auxiliary voltage outputs

6220-125

Operation
Warnings
1. The test set is only to be used by a suitably trained and competent person who is familiar with current
injection testing and who is aware of the hazards involved in working with heavy current equipment.
2. Ensure that the test set is properly earthed before use, either through the mains supply cable or
through the separate green/yellow wing-nut terminal on the terminal panel.
3. Ensure that all output terminals and the test leads used are free from dirt and grease prior to switching
the test set on.
4. Be aware that the PCITS600/2 and PCITS2000/2 are capable of hazardous outputs in excess of 50 V,
therefore do not touch the terminals, connectors or the equipment under test while the power is
switched on.
DO NOT CONNECT MAIN CURRENT OR AUXILIARY VOLTAGE TERMINALS TO A LIVE
POTENTIAL.
5. The flow of heavy current from the test set through the circuit under test will inevitably produce heat. Be
aware that the metal parts of terminals and lead connectors may be quite hot when touched. This is
unlikely to be the case however, unless the set is used at high output currents for long periods.
6. Only correctly rated output test cables must be used. Suitable leads are available optionally; 600 A
rating for the PCITS600/2 and 2000 A rating for the PCITS2000/2. Do not make connections to the
auxiliary voltage terminals when connections to the current terminal are already made, and vice
versa.
7. Do not exceed the permitted duty cycle of the test set, as defined in the Specification section.
8. Ensure that the correct power supply voltage is used and that the supply cable is terminated by a
suitable plug. The supply capacity must be sufficient to maintain the supply voltage within range at the
full output of the test set.
9. Use a supply socket that is provided with a protective earth contact. Do not use an extension cable
without a protective conductor. (Ensure that any extension cable is adequately rated).
10. Do not open the casing of the test set while it is connected to the supply.
11. It is important that replacement fuses are of the correct type and rating.
12. Whenever it is likely that the protection has been impaired, the test set must not be used but returned to
the manufacturer or his approved agent for repair. The protection is likely to be impaired if, for example,
the test set shows visible damage, fails to perform the intended measurements, has been subjected to
prolonged storage under unfavourable conditions or has been subjected to severe transport stresses.
Precautions
1. Any servicing or repair must be carried out by the manufacturer, otherwise any warranty covering the
test set may be invalidated.
2. The instrument contains static sensitive devices. If the instrument is opened for any reason (this will
automatically invalidate any warranty covering the equipment unless carried out by the manufacturer)
care must be exercised in handling the printed circuit boards. This should be done in accordance with
DEF STAN 59-98 and BS 5873, specifications for handling electrostatic sensitive devices.
3. If, after prolonged use, the test set appears faulty and fails to produce the required output current or
voltage, it may be that the variacs wiped track needs cleaning. Consult the manufacturer or one of his
approved agents for advice on this.

10

Preliminary Procedure
1. Isolate the protection equipment to be tested. Ensure that the test set is disconnected from the mains
supply before making (or breaking) connections.
2. Connect the test cables to the test set and to the equipment under test. For current injection and IDMT
relay testing connect heavy current test cables to the wing-nut current terminals. For auxiliary voltage
testing connect 2 A rated test leads to the voltage terminals.
3. When using the time counter facility, connect the protective relay contacts to the TIMER STOP
terminals.
4. Set the RANGE switch to the required output range.
5. Open the lid of the controller to gain access to the display and key-pad.
Note:-

If desired, lift the controller from its fixing on the main unit.

6. Switch the mains power supply on and switch the test sets POWER switch to I (i.e. on).
7. The display screen will show a copyright message briefly, followed immediately by the message
SYSTEM RESETTING PLEASE WAIT which also appears only briefly. (SYSTEM RESETTING
flashes on and off to give the message more emphasis).
Note:-

This message occurs frequently during the testing procedure but remains only for a short time
while the variac returns to zero and the circuit makes itself ready to continue.
When the test set is switched on the variac is wound through a full turn by the stepper motor to
clean away any dust or dirt that may have settled on the track and which may cause a
discontinuity. During this operation the solid state relay is turned off so that no output should
appear at the terminals. If this is not the case the circuit will detect an output voltage; the
variac will be wound back to zero and the display screen will indicate a relay fault.
After the variac has reset normally the main menu will be displayed on the screen.

8. The main menu showing the testing options then appears on the display screen as in figure 4.

SELECT OPTION
A

0-600A

0-125V

DISP

Figure 4 The main menu (for PCITS600/2) showing the testing option available
The options given and allocated to the three keys below the display are:A
0-600 A
the display shows the maximum current of the range
(0-300 A)
selected by the RANGE switch.
V
0-125 V
the display shows the maximum voltage of the range
(0-250 V)
selected by the RANGE switch.
DISP
the option used to set the display requirements.

11

Operation
Setting the Display Options
1. From the main menu display screen press the right hand key labelled DISP. The DISPLAY OPTIONS
sub-menu appears. The keys are labelled CONTRAST, LANG and MENU. Pressing the MENU key
returns to the main menu as shown in figure 4.
2. Press the CONTRAST key to enter the DISPLAY CONTRAST sub-menu. The keys are now labelled

,
and SET. The arrow head keys are used to increase or decrease the contrast of the display to
suit the prevailing lighting conditions and the SET key accepts the setting and returns to the DISPLAY
OPTIONS sub-menu.
3. Press the LANG key to enter language options menu. Press the left hand key to scroll through the
languages until the desired one is highlighted then press SELECT to make the choice and return to the
DISPLAY OPTIONS sub-menu.
Note:-

The language options screen display may be entered directly by pressing the right hand control
key while turning the main power switch on.

4. Press the MENU key to return to the main menu.


Note:a.
b.
c.
d.
e.

If the test set is operated or stored at extreme temperatures the display might need altering to
obtain visibility. The following procedure can be used for recovering normal display contrast.
Using the POWER switch turn the test set off (
) and then on () again.
Wait at least 30 seconds for the variac to fully reset.
Press and release the right hand control button followed by the left hand control button.
Press and hold the left hand control button to steadily increase the display contrast or the
centre button to decrease it.
Press the right hand control button to set the display contrast and quit the contrast menu.

Current Injection and IDMT Relay Testing


1. From the main menu press the key labelled A (with the range selected). The options MANUAL and
IDMT are given from the CURRENT options screen. (Press MENU to return to the main menu).
2. The route through these options is shown diagrammatically below. The display screen appears as
shown in figure 5.

CURRENT: 0-600A

MANUAL

IDMT

MENU

Figure 5 The CURRENT testing options screen (for PCITS600/2)


Note:- Up to this point in the procedure the RANGE switch may be altered without detriment to the test
programme. But if it is changed after this a message SYSTEM ERROR RANGE SWITCH CHANGED
PLEASE WAIT might appear, and any preprogrammed test data could be lost.

12

3. Manual testing
From the CURRENT testing options screen press MANUAL. Preset the required test current using
up-arrow or down-arrow keys.

MANUAL

IDMT

MENU

SET CURRENT: xxA


Press START
to begin a test
START

xxxA

Use arrow keys to


increase or decrease
the SET CURRENT

SET CURRENT: xxxA

OFF

Pressing START automatically begins a test and causes the current to rise to the set level. It will
remain at that level until the OFF key is pressed (this choice leads back to the current testing option
screen). To increase or decrease the test current during the test, use the respective arrow key to alter
the SET CURRENT target value.

13

Operation
4. IDMT testing
a) Forward test
From the CURRENT testing options screen press IDMT, then FWD.

MANUAL

IDMT

MENU

IDMT: SELECT TEST

FWD

RUNBACK

DUAL

IDMT: FORWARD
SET CURRENT: xxxA
Use arrow keys to
increase or decrease
the SET CURRENT

SELECT

Return to the
current testing
option screen

SET CURRENT: xxxA

SET

RETURN

ESCAPE

SETTING CURRENT
LOAD CURRENT: xxxA
SET CURRENT: xxxA

START

Output being
set to achieve
the desired
current when
test is started

ESCAPE

xxxA
OPERATION: xxx.xxS

Test current applied and


time for relay to operate
being counted in seconds

STOP

The operation time is shown on the display. The test can be stopped by:
(i) cessation of current (ii) operation of the relay contacts (iii) by pressing the STOP key, or (iv) the
operating time exceeding 600 seconds. A final display of the operating time is given, with the option to
REPEAT the test or ESCAPE to the current test sub-menu (figure 5).

14

b) Runback test
From the CURRENT testing options screen press IDMT,then RUNBACK.

MANUAL

IDMT

MENU

IDMT: SELECT TEST

FWD

RUNBACK

DUAL

IDMT: RUNBACK
SET CURRENT: xxxA
Use arrow keys
to increase or
decrease the
SET CURRENT

SELECT
Return to the
current testing
option screen

SET CURRENT: xxxA

SET

RETURN

ESCAPE
Output being
set to achieve
the desired
current when
test is started

SETTING CURRENT
LOAD CURRENT: xxxA
SET CURRENT: xxxA
Test current applied
START

xxxA

LOAD CURRENT: xxxA


RUNBACK: xxx.xxS

START
RUNBACK

ESCAPE

Test must
be ended
by STOP
key

OFF
STOP

The runback test is started by: (i) cessation of current (ii) operation of the relay contacts (iii) by pressing
the START RUN BACK key, or (iv) the current-on time exceeding 600 seconds. The run back timer is
halted by pressing the STOP key, or if the runback time exceeds 600 seconds. A final display of the
runback time is then given, with the option to REPEAT the test or ESCAPE to the current test sub-menu
(figure 5).

15

Operation
c) Dual test
From the CURRENT testing options screen press IDMT, then DUAL. This is a combined forward and
runback test.
MANUAL

IDMT

MENU

IDMT: SELECT TEST

FWD

RUNBACK

DUAL

IDMT: DUAL
SET CURRENT: xxxA
Use arrow keys to
increase or decrease
the SET CURRENT

SELECT
Return to the
current testing
option screen

SET CURRENT: xxxA

SET

Output being set to achieve


the desired current when
test is started

RETURN

ESCAPE

SETTING CURRENT
LOAD CURRENT: xxxA
SET CURRENT: xxxA

Test current applied and time


for relay to operate being
counted in seconds
START

ESCAPE

Test must
be ended
by STOP
key

xxxA

LOAD CURRENT: xxxA


OPERATION: xxx.xxS
RUNBACK: xxx.xxS

OPERATION: xxx.xxS
START
RUNBACK

OFF

STOP

The runback test is started by: (i) cessation of current (ii) operation of the relay contacts (iii) by pressing
the START RUNBACK key, or (iv) the operating time exceeding 600 seconds. The runback test is halted
by pressing the STOP key, or if the runback time exceeds 600 seconds. A final display of the operation
and runback times is then given, with the option to REPEAT the test or ESCAPE to the current test submenu (figure 5).

16

Auxiliary Voltage Testing


1. From the main menu press the key labelled V (with the range selected). The options MANUAL and
MENU are given from the AUX VOLTS options screen. (Press MENU to return to the main menu).

AUX VOLTS: 0-250V

MANUAL

MENU

Figure 6 The AUX VOLTS testing options screen


Note:-

Up to this point in the procedure the RANGE switch may be altered without detriment to the
test programme. But if it is changed after this a message SYSTEM ERROR RANGE SWITCH
CHANGED PLEASE WAIT might appear and any pre-programmed test data could be lost.

2. Manual testing
From the AUX VOLTS testing options screen press MANUAL.

MANUAL

MENU

SET VOLTAGE: xxxV


Press START
to begin a test
START

xxxV

Use arrow keys to


increase or decrease
the SET CURRENT

LOAD CURRENT: x.xxA


SET VOLTAGE:

xxxV

OFF

Pressing START automatically begins a test and causes the voltage to rise to the set level. It will
remain at that level until the OFF key is pressed (this latter choice leads back to the auxiliary voltage
option screen). To increase or decrease the LOAD VOLTAGE during the test, use the respective arrow
key to alter the SET VOLTAGE target value.

17

Operation
Other Messages
During operation events might occur which prohibit the normal operation of the test set. When this happens
the display screen will show SYSTEM ERROR and a message to indicate what is causing the the
malfunction A brief Summary of these messages is given below.
THERMAL OVERLOAD
This message is given if the permitted duty cycle has been exceeded and the thermal cut-out has operated.
When the test set has cooled sufficiently the CONTINUE key can be pressed to return to the main menu.
OPEN CIRCUIT
If, during a programmed test, the test set does not give any current , then the output is shut off and this
message is given. This can occur due to an open circuit in the item under test, or, a ruptured fuse or a
circuit breaker having operated in the test set.
FAILURE TO SET and -!-
The -!- symbol appears on the current ranges if the set current is not attained within 36 seconds of the test
commencing. If proper set-up cannot be achieved after a further 55 seconds then a FAILURE TO SET
warning is issued and the test is aborted.
On the manual current ranges the -!- warning is cleared if the test current is corrected in the allowed time.
However the indication remains for the duration of an IDMT test and the subsequent results screen. This
warns the operator that a consistent current was not obtained during the test and a retest might be advisable.
RANGE CHANGED
This appears if the range switch is altered during a test. The test is aborted and the instrument resets to
acknowledge the new range selected.
RELAY FAULT
This appears if an output is detected when the internal solid-state relay is normally off. This is defined as a
hazardous condition and the only instruction, after a complete rewind of the variac, is to DISCONNECT the
instrument from the mains supply immediately. If recurrent, the instrument must be returned for servicing.
DATA ERROR
This will appear if an internal data corruption occurs in the microprocessor hardware. To avoid processing
errors, you are instructed to DISCONNECT the instrument from the mains supply, and restart operation
over again. Please note that this is a rare fault and really just a precaution to avoid unpredictable operation.
Resetting the instrument should fully restore normal operation. You should seek advice if this condition
frequently occurs.

18

Guidance in Choice of Test Leads for Current Carrying Capacity


The impedance of any lead set used to connect the Test Set to the load directly affects the maximum
current that can be achieved.
Given that impedance comprises both resistance and reactance, it is important that both these parameters
are kept to a minimum to allow the higher currents to be achieved. Therefore from a resistive viewpoint
leads of minimum length and maximum cross section will deliver the highest currents (eg Foster 2000 A
Lead Set, 3 m/190 mm2), and exhibit the least heating. However, it is often not realised that for leads
where the feed and return are placed far apart the inductive reactance is a maximum and of similar ohmic
value to the resistance, whereas if the feed and return are strapped together, the inductive fields around the
cables largely cancel and the associated inductive reactance becomes much less significant.
To give some guidance regarding the performance of various cross sections and lengths of cables, figure
7a is provided.
70C

20C

Area (mm )

300

B
C

200

100

10

Length (m)

Figure 7a

With the leads strapped together the Foster PCITS2000/2 will deliver 2000 A for all dimensions falling into
zones A and B, but for leads apart zone A only is achievable. Likewise with leads strapped together 1000 A
may be delivered for all cable dimensions in zones A, B, C and D, but for leads apart zones A, B and C
only are achievable.
Note:
1

The graph shows results of tests conducted with a short-circuit load. No allowance is made for breaker
or current transformer impedance. The length of the leads is defined as being from the PCITS to the
load (not twice that).

The upper- and left-most edges of the delimiting curves correspond to operation at 70C, the others to
operation at 20C.

For operation at or below 1000 A use the 6 V 1000 A setting.

These curves are based on nominal performance of the PCITS2000/2, to give guidance in the selection
of suitable test leads.

19

Operation
Duration Tests
The graph below gives a guide to the maximum duration of a single test at a specified output current, at
20C ambient.
Recovery time after a full duration test is 15 minutes; operation is continuous at approximately 40% of full
power.

50

PCITS600/2

PCITS2000/2

Duration (mins)

40

30

20

10

2,5
0

200

400

600

800

1,000

1,200

1,400

1,600

Output Current (A)

Figure 7b One-Shot Test Duration PCITS600/2 and PCITS2000/2

20

1,800

2,000

Circuit Description
The PCITS600/2 and PCITS2000/2 are mainly intended for use in testing protection relays in electricity
supply installations. Other general uses include current transformer testing.
Each test set provides a variable high current source and an auxiliary voltage source. Both outputs can be
pre-set before a test and remain stable under varying load conditions or varying supply voltages during
operation. The PCITS2000/2 contains a 6 kVA step down transformer and the PCITS600/2 a 2,4 kVA unit.
Both are intermittently rated at maximum output. The loading transformer is fed from a stepper motor
controlled variable transformer. Two ranges are provided by switching the connections of the transformers
primary circuit.
A hand-held controller houses the l.c.d. display and the software defined keys that are used to select the
required current and voltage settings and operate the test set. A built in timer is used to measure the
time/current and runback performance of the relay under test.
The circuit can be considered in three sections:The high current circuit
made up of the mains supply input, main switches, variable
transformer and loading transformer.
The power supply p.c.b.
including the high current measurement and d.c. voltage supplies.
The control p.c.b.
which is housed in the controller and contains the microprocessor
and all its associated circuitry.
High Current Circuit
The mains input is directly connected to the power on/off switch. Overcurrent protection is provided by two
circuit breakers in the high current circuit and a 1 A fuse for the low-current power supply. Circuit breaker
CB1, a long delay magnetic device, is used on the input to the variable transformer to safeguard the mains
input. A solid state relay switches the input to this variable transformer and its wiper brush is protected by
circuit breaker CB2, a short delay device, since the brush current can be more that the input current.
Switch SW2 configures the loading transformer in either series or parallel primary connections to change
the output range of the test set. It has an extra pole which is used to send a signal to the microprocessor
so that the correct range can be indicated on the display. This transformer is a step down transformer with
a large cross section copper secondary. A thermal cut-out is fitted to the secondary to prevent the windings
heating to over 100C (PCITS2000/2) or 90C (PCITS600/2). This cut-cut will safeguard the primary
insulation. The transformer also has a low current auxiliary winding with a maximum output of 250 V and
protected by a 2 A fuse.
All metal surfaces on the test set are connected to earth and a separate earth terminal is provided.
Power Supply Circuit
Several power supply rails are used. These are derived from transformers on the power supply p.c.b. One
transformer provides the 5 V supply for the logic ICs, 12 V for the analogue ICs and the display contrast,
and an unregulated 12 V supply for the stepper motor and solid-state relay drives. A separate transformer
supplies the isolated contact-sense circuit.
Current Measurement
Current is measured in both the main and auxiliary outputs using a current transformer and an a.c. to d.c.
converter. The current transformer has two windings a 333 turn (PCITS2000/2) or 100 turn
(PCITS600/2) auxiliary winding and a 4000 turn (PCITS2000/2) or 1200 turn (PCITS600/2) drive coil.
Isolated Contact Sensor
This determines the status of the contacts of the relay under test and allows them to float above the earth
potential. Isolation is provided by the separate supply transformer and a relay unit. A rectified a.c. voltage
appears at the timer sockets to break through any contamination on the contacts. The circuit can detect
changes in both volt-free and 100 V-264 V a.c./d.c. energised contacts.
Stepper Motor Drive
The step per motor which controls the variable transformer is driven by a Darlington driver IC on the power
supply p.c.b. A constant current supply is used by this IC to maintain reliable operation across a range of
mains supply voltages. The spikes produced by the stepper motor changing state are reduced by a
capacitor.

21

Circuit Description
Solid State Relay Drive
A solid state relay is used to switch the mains supply to the primary of the variac. The secondary cannot be
switched because the secondary voltage falls below the 28 V required to turn on the back to back SCRs in
the relay.
The solid state relay is turned on by a technique which reduces the in-rush current in the variac and loading
transformer combination. A phased turn-off prevents residual magnetization of the loading transformer and
ensures proper re-energisation. These features significantly reduce nuisance effects caused by protective
device operation when a test commences.
Current Cessation Detector
This circuit uses a comparator to detect cessation of the main output current, and has a built-in time
constant to prevent impulsive operation. The output signal is used by the microprocessor system to
acknowledge current cessation and stop the test accordingly.

22

SICHERHEITSHINWEISE

Das Prfgert mu vor Gebrauch ordnungsgem geerdet werden.

Die Ausgangsanschlsse mssen vor dem Anschalten sauber und frei von Fett und Schmutz sein.

Es mu die richtige Klasse von Ausgangsprfkabeln verwendet werden.

Vor dem Berhren der Anschlsse des Prfgertes oder irgendwelcher Teile des geprften Gertes
mu das Prfgert ber den Netzschalter ausgeschaltet werden.

Nach einer Prfung mit voller Belastung knnen die Anschlsse und Kabelverbindungen hei sein.

Bei eingeschaltetem Netzschalter darf das geprfte Gert nicht berhrt werden.

Die zulssige Betriebsdauer darf nicht berschritten werden..

Beim Austausch von Sicherungen mu die richtige Klasse und Sorte verwendet werden.

Die Netzstromanschlsse drfen nicht an eine stromfhrende Spannung angeschlossen werden.

Vor dem Zurckstellen von Sicherheitsschaltern mu das Prfgert ausgeschaltet werden.

Die Sicherheitshinweise und Warnungen mssen vor dem Gebrauch des Instruments gelesen und
verstanden und beim Gebrauch beachtet werden.

HINWEIS
DAS INSTRUMENT DARF NUR VON ENTSPRECHEND AUSGEBBILDETEN UND KOMPETENTEN PERSONEN VERWENDET
WERDEN

Auf dem Gert verwendete Symbole


Elektroschockgefahr

In Bedienungsanleitung nachsehen

Heie Oberflche

Gert entspricht den gegenwrtigen Richtlinien der EU

24

Betrieb
Sicherheitshinweise
1. Dieses Prfgert dauf nur von einer geschulten und sachkundigen Person in Betrieb genommen
werden, der die modernen Methoden der Injektionsprfung und die Gefahren bei der Arbeit mit
Starkstromausrstung bekannt sind.
2. Vor Benutzung sicherstellen, da das Prfgert richtig geerdet ist. Die Erdung kann entweder ber das
Netzkabel erfolgen oder ber den separaten grn-gelben Flgelmutteranschlu an der Klemmenleiste.
3. Vor dem Anschalten des Prfgertes sicherstellen, da alle Ausgangsanschlsse und Prfkabel frei von
Schmutz und Fett sind.
4. Der PCITS600/2 und PCITS2000/2 knnen gefhrliche Spannungen ber 50 V erzeugen.
Anschlsse, Stecker und geprftes Gert nicht bei eingeschaltetem Prfgert berhren.
NETZSTROM- ODER HILFSSPANNUNGSANSCHLSSE NICHT MIT EINER STROMFHRENDEN
SPANNUNG VERBINDEN
5. Der Starkstrom, der vom Prfgert durch den geprften Stromkkreis fliet, erzeugt unweigerlich Hitze.
Die metallischen Teile des Anschlsse und Kabelstecker knnen sehr hei werden, was allerdings nur
bei langer Benutzung des Gertes mit hohen Ausgangsstromstrken auftreten kann.
6. Es drfen nur Ausgangsprfkabel der richtigen Klasse verwendet werden. Als Zubehr sind geeignete
Kabel von 600 A fr den PCITS600/2 und von 2000 A fr den PCITS2000/2 erhltlich. Wenn bereits
ein Anschlu an das Netz vorgenommen wurde, darf kein Anschlu an die Hilfsstromanschlsse
vorgenommen werden und umgekehrt.
7. Die in den Technischen Daten angegebene zulssige Hchstdauer des Testzyklus darf nicht
berschritten werden.
8. Sicherstellen, da Netzstrom mit der richtigen Spannung verwendet wird und das Netzkabel mit dem
richtigen Stecker versehen ist. Die Netzstromkapazitt mu ausreichend sein, um die
Netzstromspannung innerhalb des Bereiches der vollen Leistung des Prfgertes zu halten.
9. Nur Netzsteckdosen mit Schutzerdung verwenden. Keine Verlngerungskabel ohne Schutzleiter
benutzen. (Sicherstellen, da die richtige Klasse von Verlngerungskabel verwendet wird.)
10. Vor ffnen des Prfgertgehuses Netzstecker ziehen.
11. Nur Sicherungen der richtigen Klasse und Amperezahl verwenden.
12 Wenn ein Verdacht auf Beschdigung von Schutzvorrichtungen besteht, darf das Prfgert nicht
weiterverwendet werden, sondern mu zum Hersteller oder einem autorisierten Vertreter zur Reparatur
gebracht werden. Die Schutzvorrichtungen knnen Z. B. beschdigt worden sein, wenn das Prfgert
sichtbare Beschdigungen aufweist, nicht die gewnschten Messungen durchfhrt, lngere Zeit unter
ungeeigneten Bedingungen aufbewahrt wurde oder beim Transport schweren Belastungen ausgesetzt
war.
Warnungen
1. Alle Wartungs- oder Reparaturarbeiten mssen vom Hersteller ausgefhrt werden. Widrigenfalls
erlschen alle fr das Gert bernommenen Garantien.
2. Dieses Instrument ist mit statisch empfindlichen Vorrichtungen ausgestattet. Bei einer ffnung des
Instruments (durch die automatisch alle fr das Gert bernommenen Garantien erlschen, sofern die
ffnung nicht vom Hersteller vorgenommen wird) mssen die Leiterplatten mit uerster Vorsicht
behandelt und die Vorschriften von DEF STAN 59-98 und BS 5873 ber Arbeiten mit elektrostatisch
empfindlichen Gerten beachtet werden.
3. Wenn nach lngerem Gebrauch das Prfgert fehlerhaft arbeitet und keinen Ausgangsstrom der
bentigten Spannung oder Strke erzeugt, sind evtl. die Schleifkontakte des Variac verschmutzt. ber
Manahmen in einem solchen Fall erteilen der Hersteller oder einer seiner autorisierten Vertreter
Auskunft.

25

Betrieb
Vorbereitung
1. Schutzausrstung, die geprft werden soll, isolieren. Vor dem Vornehmen (oder Unterbrechen) von
Anschlssen sicherstellen, da das Prfgert nicht an den Netzstrom angeschlossen ist.
2. Prfkabel am Prfgert und an der zu prfenden Ausrstung anschlieen. Zur Strominjektion und zur
Prfung von IDMT-Relais Starkstromkabel an die Flgelmutterklemmen anschlieen. Fr
Hilfsspannungsprfungen Prfkabel von 2 A an die Spannungsklemmen anschlieen.
3. Zur Verwendung des Zeitschalters mssen die Schutzrelaiskontakte an die Klemmen "TIMER STOP"
angeschlossen werden.
4. "RANGE"-Schalter auf den gewnschten Ausgangsbereich stellen.
5. Um an Bildschirm und Tastatur zu gelangen, wird der Deckel des Regelpults geffnet.
Hinweis:

Das Regelpult lt sich vom Hauptgert abheben.

6. Netzstrom einschalten und "POWER"- Schalter des Gerts auf "I" (Ein) schalten.
7. Auf der Anzeige erscheint kurz ein Copyright-Hinweis und anschlieend die Meldung "SYSTEM SETZT
ZURCK BITTE WARTEN", die ebenfalls nur kurz erscheint. Zur Hervorhebung der Meldung blinken
die Wrter "SYSTEM SETZT ZURCK".
Hinweis:
Diese Meldung erscheint beim Prfen mehrmals fr kurze Zeit, wenn sich der Variac auf Null
stellt und der Stromkreis zum Fortsetzen der Prfung vorbereitet wird. Beim Einschalten des
Prfgertes vollzieht der Schrittmotor des Variac eine volle Umdrehung, um die Bahn von Schmutz oder
Staub zu befreien, durch die der Kontakt unterbrochen werden knnte. Das Festkrperrelais bleibt bei
diesem Vorgang ausgeschaltet, so da an den Anschlssen keine Ausgangsspannung auftreten sollte.
Sollte eine Ausgangsspannung auftreten, wird diese vom Stromkreis registriert, woraufhin der Variac auf
Null zurckgestellt wird und die Anzeige einen Relaisfehler anzeigt. Sobald sich der Variac normal
zurckgestellt hat, erscheint auf dem Bildschirm das Hauptmen.
8. Die verschiedenen Prfoptionen des auf dem Bildschirm erscheinenden Hauptmens werden in
Abbildung 4 dargestellt.

WHLE OPTION
A

0-600A

0-125V

ANZ

Abbildung 4: Hauptmen (des PCITS600/2) mit Prfoptionen


ber die drei Tasten unter dem Bildschirm lassen sich die folgenden Optionen aufrufen:
A

V
ANZ

26

0- 600 A
(0-300 A)
0 - 125 V
(0 - 250 V)

auf der Anzeige wird die hchste Stromstrke des ber den
"RANGE"-Schalter gewhlten Bereiches dargestellt
auf der Anzeige wird die hchste Spannung des ber den
"RANGE"-Schalter gewhlten Bereiches dargestellt
Option zum Einstellen der Bildschirmanzeige

Einstellung der Bildschirmanzeige


1. Drcken Sie im Bildschirm des Hauptmens die mit "ANZ" gekennzeichnete rechte Taste. Es erscheint
das Untermen "ANZEIGEOPTIONEN. Die Tasten sind mit "KONTRAST, "SPRACHE und "MEN"
gekennzeichnet. Durch Drcken der Taste "MEN" knnen Sie zu dem in Abbildung 4 gezeigten
Hauptmen zurckkehren.
2. Durch Drcken der Taste "ANZEIGE" wird das Untermen "ANZEIGEKONTRAST" (Bildschirmkontrast)
aufgerufen. Die Tasten sind nun mit "", "" und "EINST" gekennzeichnet. Mit den Pfeiltasten lt sich
der Kontrast des Bildschirms an die Lichtbedingungen der Umgebung anpassen. Mit der Taste "SET"
werden die gewhlten Einstellungen besttigt, woraufhin wieder das Untermen "ANZEIGEOPTIONEN"
erscheint.
3. Zum Aufrufen des Sprachenmens wird die Taste "SPRACHE" gedrckt. Zum Whlen einer Sprache
bewegen Sie sich durch Drcken der linken Taste durch die Sprachen, bis die gewnschte Sprache
markiert ist. Durch Drcken von "WHLE" wird die Auswahl besttigt und zum Untermen "ANZEIGE
OPTIONEN" zurckgekehrt.
Hinweis:
Wenn die rechte Steuertaste beim Einschalten des Gertes ber den Netzschalter gedrckt
wird, wird das Sprachenmen direkt aufgerufen.
4. Um zum Hauptmen zurckzukehren, drcken Sie die Taste "MEN".
Hinweis:
Wenn das Prfgert unter extremen Temperaturbedingungen benutzt oder aufbewahrt wird,
mssen die Bildschirmeinstellungen evtl. verndert werden, um ein Ablesen der Werte zu ermglichen.
Der normale Bildschirmkontrast lt sich wieder wie folgt einstellen:
a.
Schalten Sie das Prfgert ber den Netzschalter (POWER) aus (O) und wieder ein (I).
b.

Warten Sie mindestens 30 Sekunden lang, bis sich der Variac ganz zurckgestellt hat.

c.

Drcken Sie auf die rechte und anschlieend auf die linke Steuertaste.

d.

Um den Bildschirmkontrast allmhlich zu erhhen, drcken Sie die linke Steuertaste und halten
Sie sie fest. Mit der mittleren Taste wird der Kontrast verringert.

e.

Um den eingestellten Bildschirmkontrast zu besttigen und das Kontrastmen zu verlassen,


drcken Sie den rechten Steuerknopf.

Strominjektion und IDMT-Relaisprfung


1. Drcken Sie im Hauptmen (nach Whlen des Bereiches) auf die mit "A" gekennzeichnete Taste. Auf
dem Optionsbildschirm "STROM" erscheinen die Optionen "MANUEL" und "RELAIS". (Mit "MEN" wird
zum Hauptmen zurckgekehrt).
STROM: 0-600A
2. Die Abfolge dieser Optionen wird in dem unteren Diagramm dargestellt. Der Bildschirm wird in
MANUEL

RELAIS

MEN

STROM: 0-600A

MANUEL

RELAIS

MEN

Abbildung 5. Prfoptionsbildschirm "STROM" (fr PCITS600/2)


Hinweis:
Bis zu diesem Schritt des Verfahrens lt sich der gewhlte Bereich ber den Schalter
"RANGE" ohne Auswirkungen auf das Prfprogramm ndern. Bei einer spteren nderung erscheint die
Meldung "SYSTEMFEHLER, BEREICHSGENDERT, BITTE WARTEN; vorprogrammierte Prfdaten
sind dann mglicherweise verlorengegangen.

27

Betrieb
3.
Manuelle Prfung
Drcken Sie im Prfoptionsbildschirm "STROM" auf "MANUEL". Der gewnschte Prfstrom wird ber die
Aufwrts- und Abwrtspfeiltasten gewhlt.

MANUEL

RELAIS

MEN

WHLE STROM: xxA

START

xxxA
WHLE STROM: xxxA

AUS

Nach Drcken von "START" wird die Prfung automatisch begonnen und der Strom bis zum eingestellten
Stand erhht. Dieser Stand wird beibehalten, bis die Taste "EIN" gedrckt wird (womit zum StromprfungsOptionsbildschirm zurckgekehrt wird). Whrend der Prfung lt sich der Prfstrom erhhen oder
verringern, indem ber die jeweilige Pfeiltaste der Zielwert in "WHLE STROM" verndert wird.

28

4. IDMT-Prfung
a) Vorwrtsprfung
Whlen Sie im Prfoptionsbildschirm "STROM" zunchst "RELAIS" und anschlieend VORL.

MANUEL

MEN

RELAIS

RELAIS WHLE TEST

VORL

RCKLAUF

BEIDE

RELAIS VORLAUF
WHLE STROM: xxxA

WHLE

WHLE STROM xxxA

EINS

ZURCK

MEN

ESCAPE

EINSTELLUNG
LASTSTROM: xxxA
WHLE STROM: xxxA

START

ESCAPE

xxxA
ARBEITET: xxx.xxS

STOP

Die Betriebszeit wird auf dem Bildschirm dargestellt. Die Prfung wird unter einer der folgenden
Bedingungen beendet:
(i) Abschalten des Stroms (ii) Bettigung der Relaiskontakte (iii) Drcken der STOP-Taste oder (iv) nach
600 Sekunden Betriebszeit. Die Betriebszeit wird ein letztes Mal angezeigt, und der Benutzer kann die
Prfung entweder ber WIEDERHOLEN oder mit ESCAPE zum Stromprfungs-Untermen zurckkehren
(Abbildung 5).

29

Betrieb
b)
Rcklaufprfung
Whlen Sie im "STROM"-Prfoptionsbildschirm "RELAIS" und anschlieend "RCKLAUF".

MANUEL

MEN

RELAIS

RELAIS WHLE TEST

RCK

VORL

BEIDE

RELAIS RCKLAUF
WHLE STROM: xxxA

WHLE

WHLE STROM: xxxA

EINS

ZURCK

MEN

ESCAPE

EINSTELLUNG
LASTSTROM: xxxA
WHLE STROM: xxxA

START

xxxA

LASTSTROM: xxxA
RCKLAUF: xxx.xxS

START
RCKLAUF

ESCAPE

AUS
STOP

Die Rcklaufprfung wird auf eine der folgenden Weisen in Gang gesetzt: (i) Abschalten des Stroms (ii)
Bettigung der Relaiskontakte (iii) Drcken der START RCKLAUF -Taste oder (iv) nach 600 Sekunden mit
laufendem Strom. Der Rcklaufzeitschalter wird durch Drcken der STOP-Taste angehalten oder stellt sich
nach 600 Sekunden automatisch ab. Anschlieend wird ein letztes Mal die Rcklaufzeit angezeigt, und der
Benutzer kann die Prfung entweder ber WIEDERHOLEN wiederholen oder mit ESCAPE zum
Stromprfungs-Untermen zurckkehren (Abbildung 5).

30

c)
Doppelte Prfung
Whlen Sie im Prfoptionsbildschirm "STROM" zunchst "RELAIS" und anschlieend "BEIDE". Hierbei
handelt es sich um eine kombinierte Vorwrts- und Rcklaufprfung.

MANUEL

MEN

RELAIS

RELAIS WHLE STROM

RCKL

VORL

BEIDE

RELAIS RCKLAUF: xxxA

WHLE

WHLE STROM: xxxA


MEN

EINS

ZURCK

ESCAPE

EINSTELLUNG
LASTSTROM: xxxA
WHLE STROM: xxxA

START

xxxA

LASTROM: xxxA
ARBEITET: xxx.xxS
ZURCK: xxx.xxS

ESCAPE

ARBEITET: xxx.xxS
START
ZURCK

AUS

STOP

Die Rcklaufprfung wird auf eine der folgenden Weisen in Gang gesetzt: (i) Abschalten des Stroms (ii)
Bettigung der Relaiskontakte (iii) Drcken der START RCKLAUF -Taste oder (iv) nach 600
Sekunden mit laufendem Strom. Der Rcklaufzeitschalter wird durch Drcken der STOP-Taste
angehalten oder stellt sich nach 600 Sekunden automatisch ab. Anschlieend wird ein letztes Mal die
Betriebs- und Rcklaufzeit angezeigt, und der Benutzer kann die Prfung entweder ber
WIEDERHOLEN oder mit ESCAPE zum Stromprfungs-Untermen zurckkehren (Abbildung 5).

31

Betrieb
Prfen der Hilfsspannung
1. Drcken Sie (nach Whlen des Bereiches) im Hauptmen die mit "V" gekennzeichnete Taste. Es
erscheint der "HILFSSPANNUNG"-Bildschirm mit den Optionen "MANUEL" und "MENU". (Mit "MEN"
kehren Sie zum Hauptmen zurck.)

HILFSSPANNUNG: 0-250V

MEN

MANUEL

Abbildung 6. Prfoptionen-Bildschirm "HILFSSPANNUNG"


Hinweis:
Bis zu diesem Schritt des Verfahrens lt sich der gewhlte Bereich ber den Schalter
"BEREICH" ohne Auswirkungen auf das Prfprogramm ndern. Bei einer spteren nderung erscheint
die Meldung "SYSTEMFEHLER, BEREICH GENDERT, BITTE WARTEN; vorprogrammierte
Prfdaten sind dann mglicherweise verlorengegangen.
2. Manuelle berprfung
Drcken Sie im Prfoptionen-Bildschirm "HILFSSPANNUNG" auf "MANUEL".

MEN

MANUEL

WHLE SPANNUNG: xxxV

START

xxxV
LASTSTROM: x.xxA
WHLE SPANNUNG:

xxxV

EIN

Wenn Sie auf "DRCKEN, wird automatisch eine Prfung begonnen und die Spannung auf den
eingestellten Stand gebracht. Der Stand wird solange beibehalten, bis dieTaste "AUS" gedrckt wird
(woraufhin zum Hilfsspannungs-Optionsbildschirm zurckgekehrt wird). Whrend der Prfung lt sich
die LADESPANNUNG erhhen oder verringern, indem ber die jeweilige Pfeiltaste der Zielwert in
"WHLE STROM" verndert wird.

32

Weitere Meldungen
Wenn der normale Betrieb des Prfgertes gestrt wird, erscheint auf dem Bildschirm die Meldung
"SYSTEMFEHLER" zusammen mit einer Meldung, die auf die Ursache der Strung hinweist. Die
Bedeutung dieser Meldungen wird im Folgenden kurz zusammengefat.
"THERMISCHE BERLAST"
Diese Meldung erscheint, wenn die zulssige Betriebsdauer eines Durchgangs berschritten wurde und der
Wrmeschutzschalter des Gertes sich daraufhin abschaltet. Wenn das Prfgert ausreichend abgekhlt
ist, kann mit der Taste "WEITER" zum Hauptmen zurckgekehrt werden.
"UNTERBRECHNUNG"
Wenn das Prfgert whrend einer programmierten Prfung keinen Strom liefert, wird der Ausgangsstrom
abgeschaltet, und diese Strungsmeldung erscheint. Eine solche Strung kann auftreten, wenn der
Stromkreis des geprften Gegenstandes unterbrochen ist oder im Prfgert eine Sicherung durchgebrannt
ist bzw. sich ein berlastschalter ausgeschaltet hat.
"EINSTE UN MGLICH" und "-!-"
Das Zeichen "-!-" erscheint bei den Strombereichen, wenn der eingestellte Strom nicht innerhalb von 36
Sekunden nach Beginn der Prfung erreicht wurde. Wenn die Einstellungen nach weiteren 55 Sekunden
nicht erreicht werden knnen, erscheint die Meldung "EINST UNMGLICH", und die Prfung wird
abgebrochen.
Bei den manuellen Strombereichen erlischt die Meldung "-!-", wenn der Prfstrom innerhalb der
vorgegebenen Zeit korrigiert wird. Bei einer IDMT-Prfung wird das Ausrufezeichen jedoch whrend der
Testdauer und auf dem folgenden Ergebnisbildschirm weiterhin angezeigt, um den Bediener darauf
hinzuweisen, da der Strom bei der Prfung nicht gleichmig flo und evtl. eine Wiederholung der
Prfung ratsam ist.
"BEREICH GENDERT
Diese Meldung erscheint, wenn die Stellung des Bereichsschalters whrend einer Prfung verstellt wird.
Gleichzeitig wird die Prfung abgebrochen, und das Gert stellt sich zurck und bernimmt den neuen
Bereich.
RELAIS FEHLERN
Diese Meldung erscheint, wenn eine Ausgangsspannung auftritt, obwohl das interne Festkrperrelais
eigentlich geschlossen sein sollte. Dieser Zustand ist mit einer erheblichen Gefhrdung verbunden. Nach
einem vollstndigen Zurckstellen des Variac mu das Gert daher ber "DISCONNECT" sofort vom
Netzstrom getrennt werden. Wenn der Fehler erneut auftritt, mu das Gert zur Reparatur gebracht
werden.
"DATENFEHLER"
Diese Meldung erscheint, wenn die internen Daten des Mikroprozessors beschdigt sind. Zur Vermeidung
von Verarbeitungsfehlern sollten Sie das Gert ber "DISCONNECT" vom Netzstrom trennen und die
Arbeit von vorne beginnen. Dieser Fehler tritt nur uerst selten auf, und das Abschalten dient als reine
Vorsichtsmanahme, um unerwnschte Ergebnisse zu vermeiden. Nach einem vollstndigen Zurckstellen
des Gertes sollte der Betrieb wieder ohne Strungen verlaufen. Wenn sich dieser Fehler huft, sollten Sie
das Gert untersuchen lassen.

33

Betrieb
Hinweise zur Auswahl von Prfkabeln mit geeigneter Stromstrke
Von der Impedanz des Prfkabels, ber welches das Prfgert mit der Ladung verbunden wird, hngt es
ab, welche Stromstrke sich maximal einstellen lt.
Da sich die Impedanz aus dem Widerstand und der Reaktanz zusammensetzt, mssen beide Parameter so
niedrig wie mglich gehalten werden, um mglichst hohe Stromstrken erzielen zu knnen. Unter dem
Aspekt des Widerstands betrachtet, erlauben daher Kabel mit mglichst geringer Lnge und mglichst
groem Durchschnitt (wie z. B. der Foster Kabelsatz mit 2000 A, 3 m / 190 mm2) bei geringster
Wrmeentwicklung die hchsten Stromstrken. Hierbei wird jedoch oft nicht bercksichtigt, da bei Kabeln,
bei denen Zufuhr- und Rckstrom in groem Abstand voneinander entfernt verlaufen, die Induktanz auf ein
Maximum ansteigt und ihre Ohmwerte sich denen des Widerstands annhern. Wenn die Zufuhr- und
Rckstromkabel hingegen zusammengebunden werden, heben sich die Induktionsfelder um den Kabeln
weitgehend auf, und die resultierende Induktanz spielt eine weitaus geringere Rolle.
In Abbildung 7a werden die Eigenschaften verschiedener Kabellngen und -querschnitte dargestellt.
70C

20C

Flche (mm2)

300

B
C

200

100

5
6
Abbildung 7a

10

Lnge (m)

Bei zusammengebundenen Kabeln liefert Foster PCITS2000/2 bei allen Kabelgren der Bereiche A und B
2000 A, whrend bei nicht zusammengebundenen Kabeln lediglich die Kabel des Bereiches A diesen Wert
erreichen. 1000 A wiederum werden bei zusammengebundenen Kabeln von allen Kabelgren der
Bereiche A, B, C und D erreicht, bei nicht zusammengebundenen Kabeln jedoch nur von den Kabeln der
Bereiche A, B und C.
Hinweis:
1. Die Kurve stellt die Ergebnisse von Prfungen dar, die mit einer Kurzschluladung durchgefhrt werden.
Die Impedanz von Unterbrechern oder Stromwandlern wurde nicht bercksichtigt. Unter der Kabellnge
ist die Strecke zwischen dem PCITS und der Ladung zu verstehen (nicht die doppelte Lnge).
2. Die oberen und linken Kanten der Begrenzungskurven entsprechen einem Betrieb bei 70 C; die
anderen einem Betrieb bei 20 C.
3. Bei einem Betrieb mit bis zu 1000 A ist die Einstellung 6 V, 1000 A zu verwenden.
4. Diese Kurven dienen als Hilfe zur Auswahl von geeigneten Prfkabeln auf der Grundlage der
Nennleistung des PCITS2000/2.

34

Dauerprfungen
In der untenstehenden Kurve wird die Hchstdauer einer einzelnen Prfung bei einer bestimmten
Ausgangsstromstrke und einer Umgebungstemperatur von 20 C dargestellt.

Die Erholungszeit nach einer vollen Testlnge betrgt 15 Minuten; ein kontinuierlicher Betrieb ist bei ca.
40 % der vollen Leistung mglich.

50

PCITS600/2

PCITS2000/2

DAUER (min)
Duration
(mins)

40

30

20

10

2,5
0

200

400

600

800

1,000

1,200

1,400

1,600

1,800

2,000

Output
Current (A)
AUSGANGSSTROM
(A)

Abbildung 7b. Testdauer fr einen Schritt

35

Reparaturen und Garantie


Das Instrument enthlt statisch empfindliche Bauteile, weshalb die gedruckte Schaltung sorgfltig behandelt
werden mu. Falls die Schutzvorrichtungen eines Instruments beschdigt worden sind, sollte es nicht
verwendet, sondern an eine geeignete Reparaturwerkstatt geschickt werden. Die Schutzvorrichtungen sind
wahrscheinlich beschdigt, wenn folgende Bedingungen vorliegen: sichtbare Beschdigung, fehlende
Anzeige der erwarteten Meergebnisse; lngere Lagerung unter widrigen Bedingungen oder starke
Transportbelastung.
NEUE INSTRUMENTE UNTERLIEGEN EINER GARANTIE VON 1 JAHR AB DEM DATUM DES
KAUFS DURCH DEN BENUTZER.
Hinweis: Das Gehuse darf nur von entsprechend autorisierten Reparaturfirmen geffnet werden, da sonst
die Garantie fr dieses Instrument automatisch erlischt.
Reparaturarbeiten und Ersatzteile
Wenden Sie sich zwecks Wartungsarbeiten an FOSTER -lnstrumenten entweder an:
AVO INTERNATIONAL
Archcliffe Road
Dover
Kent CT17 9EN
England
Tel: +44(0)1304 502243
Fax: +44(0)1304 207342

oder an

AVO INTERNATIONAL
510 Township Line Road
Blue Bell
PA 19422-2785
USA
Tel: +1 (215) 646-9200
Fax: +1 (215) 643-7215

oder an eine autorisierte Reparaturfirma.


Autorisierte Reparaturfirmen
Eine Reihe von Firmen sind fr die Reparatur der meisten FOSTER- lnstrumente unter Verwendung von
Original FOSTER-Ersatzteilen autorisiert. Wenden Sie sich wegen Ersatzteilen, Reparaturwerkstatten und
Beratung ber die jeweils bestgeeigneten Manahmen an eine autorisierte Auslieferung bzw. Vertretung.
Einsenden Eines Instruments Zur Reparatur
Wenn ein Instrument zwecks Reparatur zurck geschickt werden mu, sollte es mit vorbezahiter Fracht an
die angebrachte Anschrift gesandt werden. Gleichzeitig sollte zur Erledigung der britischen Zollformalitten
per Luftpost eine Kopie der Rechnung zusammen mit dem Packzettel eingesandt werden. Auf Wunsch wird
dem Absender vor Ausfhrung irgendwelcher Arbeiten am Instrument ein Kostenvoranschlag unter
Bercksichtigung der Frachtkosten und anderer Gebhren zugesandt.

36

Components List
Major Components

Part Number
PCITS 600/2

PCITS 2000/2

Output transformer TX6

6331-624

6430-538

Variable transformer VT1 (variac)

6280-270

6280-271

Current transformer TX5

6280-298

6280-301

Stepper motor

25994-004

25994-004

Solid state relay SSR1

25980-028

25980-028

Switch, on/off

25975-019

25975-086

Switch, range

25975-084

25975-087

Circuit breaker CB1

25980-023

25980-025

Circuit breaker CB2

25980-024

25980-026

Fuse FSl 1 A

25413-284

25413-284

Fuse FS2 2 A

25413-287

25413-287

Fuse FS3 100 mA (internal)

25413-295

25413-295

Lamp LP1

25990-007

25990-007

Power supply p.c.b. (complete)

6331-677

6331-677

Control p.c.b. (complete)

6331-637

6331-637

37

AVO INTERNATIONAL
Archcliffe Road
Dover
Kent, CT17 9EN.
England.
Tel: +44 (0) 1304 502100
Fax: +44 (0) 1304 207342

PO Box 9007
Valley Forge
PA 19484-9007
U.S.A.
Tel: +1 (610) 676-8500
Fax: +1 (610) 676-8610

4651 S. Westmoreland Road


Dallas
TX 75237-1017
U.S.A.
Tel: +1 (800) 723-2861 (U.S.A. only)
Tel: +1 (214) 330-3203 (International)
Fax: +1 (214) 337-3038

MEGGER SA,
29 Alle de Villemomble,
93340 Le Raincy
Paris, France
Tel: +33 (1) 43.02.37.54
Fax: +33 (1) 43.02.16.24

This Test Set is manufactured in the United Kingdom.


The company reserves the right to change the specification or design without prior notice.