Explosions
Explosions
Explosions
Dust
Explosions
Course, Prevention, Protection
Preface
Dust represents the most hazardous form of solid matter. It may result from natural
or technical processes. Dust must be considered as a phase of its own with very specific characteristics. Dust is defined as fine particles of a solid dispersed in a gas. In
considering explosions, the gas will initially be thought of as air with its usual
oxygen content. In an explosion the dusty solid will always spontaneously oxidize.
The violence of an explosive oxidation increases with increased fineness of the
individual solid particle because each particle's surface area increases quite rapidly
in comparison with the total volume of the solid dispersed in the gas. An example
may illustrate this statement. Consider a solid with an initial volume assumed to be
1 cm3 If it exists in the form of a cube then its surface area will be 6 cm 2 However,
if the same volume is visualized as particles with a IlL diameter, then the total surface area will be 6.104 cm2 . The surface of the dust is therefore ten thousand times
larger than the reference cube. The actual effective conditions may even reach
much larger ratios as with decreasing particle size the inner surface area which
effects the oxidation process will generally be a multiple of the external surface
area. It is the surface of the dust which makes the dust become such a hazardous
material.
From a strictly scientific point of view, the course of an explosive oxidation process has so far only been investigated to a rudimentary degree. A satisfactory
insight into dust explosions is therefore only possible from comprehensive experimental tests. Due to the high cost of suchtests, it is necessary to analyze the results
with great care and to summarize the data with the help of empirical characteristic
parameters. These empirical parameters are the basis for the guidelines which have
been developed in order to help prevent explosions or at least to limit the consequences.
The author has summarized today's knowledge of the cause, course and consequences of dust explosions in an outstanding fashion. Explosions became the problem around which his professional life developed with great success. Whoever is
confronted with dusts, be it the field engineer or the scientist, will benefit from this
book and increase the safety of the facility for which he is responsible.
Heinz Brauer
Full Professor of Reaction Technology
Technical University Berlin
Table of Contents
Introduction
..................................
2
2.1
2.2
2.3
Historical Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Occurrence of Dust Explosions . . . . . . . . . . . . . . . . . . . . . .
The Nature of Dust Explosions . . . . . . . . . . . . . . . . . . . . . .
Apparatus for the Testing of Airborne Dusts . . . . . . . . . . . . . .
2
2
10
15
24
27
27
28
28
29
29
30
31
32
32
33
34
34
36
4.1
4.2
4.2.1
4.2.2
4.2.2.1
4.2.2.2
4.2.2.3
4.2.3
4.2.3.1
4.2.3.2
4.2.4
4.2.4.1
4.2.5
4.2.5.1
4.2.5.2
4.2.6
4.2.6.1
4.2.6.2
4.2.6.3
4.2.6.4
4.2.7
4.2.7.1
37
39
40
40
44
44
44
47
48
VIII
4.2.7.2
4.2.7.3
4.3
4.3.1
4.3.1.1
4.3.1.2
4.3.1.3
4.3.1.4
4.3.1.5
4.3.2
4.3.2.1
4.3.2.2
4.3.2.3
4.3.3
4.3.3.1
4.3.3.2
4.3.3.3
4.3.4
4.4
4.4.1
4.4.1.1
4.4.1.2
4.4.1.3
4.4.1.4
4.4.1.5
4.4.1.6
4.4.2
4.4.2.1
4.4.2.2
4.4.2.3
4.4.2.4
4.5
Table of Contents
Friction Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermal Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Material Safety Specifications for Dust Clouds Describing
the Explosion Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustible Dusts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Particle Size Distribution . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosible Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure Versus Explosion Violence . . . . . . . . . . . ..
Flock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Explosible Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure /Violence of Explosion . . . . . . . . . . . . . ..
Hybrid Mixtures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . .. . . . . . ..
Explosible Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure /Violence of Explosion . . . . . . . . . . . . . ..
Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Safety Characteristics of Airborne Dust Describing
the Ignition Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Minimum Ignition Energy . . . . . . . . . . . . . . . . . . . . . . . . ..
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Apparatus for the Determination of the
Minimum Ignition Energy . . . . . . . . . . . . . . . . . . . . . . . . ..
Ignition Behavior of Combustible Dusts . . . . . . . . . . . . . . . ..
Ignition Behavior of Flock . . . . . . . . . . . . . . . . . . . . . . . .
Ignition Behavior of Hybrid Mixtures . . . . . . . . . . . . . . . . .
Conclusions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Ignition Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Apparatus for Temperature Determination . . . . . . . . . . . . ..
Ignition Effectiveness of a Glowing Coil. . . . . . . . . . . . . . ..
Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Safety Characteristics of Airborne Dusts Describing the Course
of an Explosion in Pipelines . . . . . . . . . . . . . . . . . . . . . . ..
49
50
51
51
51
52
53
54
56
81
81
82
84
86
86
87
88
92
93
93
93
93
96
109
112
114
115
115
116
117
118
119
.
.
.
.
.
.
.
.
125
125
127
127
128
129
129
129
Table of Contents
5.2.3.1.2
5.2.3.1.3
5.2.3.1.4
5.2.3.1.5
5.2.4
5.2.4.1
5.2.4.2
5.2.5
5.2.6
5.2.7
5.3
5.3.1
5.3.2
IX
130
137
5.3.5
5.3.5.1
5.3.5.2
5.3.5.3
5.3.5.4
5.3.5.5
5.3.5.6
5.3.6
Combustible Dusts
Hybrid Mixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Vacuum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Admixture of Solids . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prevention of Effective Ignition Sources . . . . . . . . . . . . . . . .
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanically Generated Sparks . . . . . . . . . . . . . . . . . . . . .
Hot Surfaces / Autoignition . . . . . . . . . . . . . . . . . . . . . . . .
Static Electricity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Protection Through Design Measures . . . . . . . . . .
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure-resistant Design for the Maximum
Explosion Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure-resistant Design . . . . . . . . . . . . . . . . . .
Explosion Pressure Shock-resistant Design . . . . . . . . . . . . . .
Explosion Pressure-resistant Design for a Reduced Maximum
Explosion Pressure in Conjunction with Explosion
Pressure Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure Venting of Vessels . . . . . . . . . . . . . . . . .
Explosion Pressure Venting of Elongated Vessels (Silos) . . . . . .
Explosion Pressure Venting of Pipelines .... . . . . . . . . . . . .
Explosion-resistant Construction for Reduced
Maximum Explosion Pressure in Conjunction with
Explosion Suppression . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Diversion or Arresting of Explosions . . . . . . . . . . .
Preliminary Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extinguishing Barrier . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotary Air Locks (Rotary Valves) . . . . . . . . . . . . . . . . . . . .
Rapid-Action Valves: Gate or Butterfly Type . . . . . . . . . . . . .
Rapid-Action Valve: Float Type . . . . . . . . . . . . . . . . . . . . .
Explosion Diverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Concluding Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
246
Acknowledgements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
247
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explosion Pressure Venting . . . . . . . . . . . . . . . . . . . . . . .
Vessel: Area Determination by Calculation or Nomogram ...
ElongatedVessels (Silos) . . . . . . . . . . . . . . . . . . . . . . . .
248
248
248
249
5.3.2.1
5.3.2.2
5.3.3
5.3.3.1
5.3.3.2
5.3.3.3
5.3.3.4
5.3A
8.1
8.1.1
8.1.2
.
.
.
.
140
141
144
144
145
154
156
160
161
161
163
163
164
166
166
167
187
200
203
215
215
215
229
232
241
243
245
Table of Contents
References . . . .
254
10
260
11
263
12
Subject Index . . . . . . .
265
1 Introduction
In past years, the causes of dust explosions have been systematically researched by
laboratory-testing the combustion, ignition, and explosion behavior of combustible dust. Step by step, the results and the experience gained have been transferred
to industrial practice. Yet, dust explosions still occur, causing major damage and
sometimes fatalities. The "Berufsgenossenschaftliche Institut fUr Arbeitssicherheit" in Bonn [1] lists 357 dust explosions which occurred from 1976-1980 in the
Federal Republic of Germany, but only 155 of these cases had been officially reported. In contrast, the "Verband der Sachversicherer" (VDS) (organization of
insurance carriers) states 300 cases per year with damage exceeding 50,000 DM
each.
In conjunction with the above-mentioned laboratory tests, large, practice-related, full-scale tests were carried out with combustible dusts. The purpose was to
develop preventive measures and to test design measures which may not avert an
explosion but should limit its dangerous results to an acceptable level. The experience gained over the past years by applying such measures in facilities which process and convey combustible dusts indicates that damage to equipment and personnel can definitely be prevented.
The aim of this publication is to assist people dealing with industrial applications. It reflects the present state of the art and current knowledge of the course of
a dust explosion, induding the inherent danger of a dust layer.
2 Historical Review
Location
Installation
Dust type
Damage
1785
Turin (Italy)
Warehouse
Flour
Warehouse destroyed
1858
Stettin (Poland)
Roller mill
Grain
1860
Milwaukee (USA)
Mill
Flour
1864
Mascoutah (USA)
Mill
Flour
1869
unknown (Germany)
Mill
Pea flour
1887
Hameln (Germany)
Silo
Grain
In 1887, a grain dust explosion destroyed a silo of the "new Wesermilhle" in Hameln, Germany (Table 1). The journal of the "Verein Deutscher Ingenieure" of
November 1887 described the explosion as follows: "This accident is unique on the
continent. Until now, we had no idea of the enormous destructive effects of such
forces. "
With increasing industrialization and the change from smaller facilities to large
industrial complexes, the frequency of dust explosions has increased since 1887.
Fig.! alb. The "Neue Wesermiihle" in Hameln, Germany after the explosion in 1887
Most early dust explosions occurred in places where production and dust generation were high due to size and productivity. Up to 1922, the USA and Canada experienced 217 dust explosions. These involved organic dusts from mills, elevators,
and silos, starch plants and refineries, as well as plants processing aluminum, chocolate, paper, rubber, seasoning, etc. The multitude of installations affected by dust
explosions is striking.
A more recent USA statistic for the time period 1900-1952 lists the dust types
involved in 769 explosions (Table 2). The total damage amounted to 88 million dollars and involved 464 casualties and 1229 injured.
2 Historical Review
Number of explosions
Type of dust
24.8
191
Grain
16.8
129
Wood
14.7
113
Feedstuff
13.1
101
Flour
5.6
43
Starch
4.8
37
Cork
3.4
26
Sugar
3.3
25
Plastics
3.1
24
Sulfur
3.1
24
Malt
1.8
14
Bark
5.5
42
Miscellaneous
100
769
But not only the industrial establishment experienced dust explosions. The Pacific Northwest (USA) registered 300 dust explosions in combines during harvest
with damages exceeding 1 million dollars.
Statistical information on dust explosions in Germany is scarce for that time period. Nevertheless, 66 sugar dust explosions were reported for the time period
1890-1922, with moderate to catastrophic results. One of the worst explosions occurred on March 16,1917 in Frankenthal, killing 6 operators and causing considerable damage (Fig. 2).
Other branches of industry experienced dust explosions during the same time
period. 77 incidents were registered involving coal dust, dyestuffs, soot, and
aluminum. Coal dust explosions alone left 404 dead and 275 injured.
Approximately 30 years ago, one of the most comprehensive books on dust explosions was published byW. H. Geck [3]. The author, who lost his own business
due to a wood dust explosion with subsequent fire and who survived a severe sugar
dust explosion, described 116 dust explosions in various major industries. The
probable causes and effects are analyzed based on his own observations and over
30 years of experience as a consultant (Fig. 3).
In his work he reaches the remarkable and still valid conclusion that every dust
may behave differently in different plants due to the influence of innumerable factors unique to each industrial environment.
The years 1976-1978 saw numerous grain dust explosions in silos in the USA.
The incidents caused extensive damage and resulted in numerous fatalities and in-
Fig. 3. Wood dust explosion in a furniture factory with subsequent fire [3]
juries. Many symposia dealt with and are still dealing with the causes of these dust
explosions. The discussions have concentrated on the effectiveness of preventive
measures and other design measures to reduce the consequences of such mishaps
to a minimum.
Nowadays, dust explosions are - in the true sense of the word - commonplace
in the Federal Republic of Germany, although only a fraction are recorded, as men-
2 Historical Review
tioned earlier [1]. But not all the mishaps have such a terrible outcome as the 1979
flour dust explosion in the "Bremer Roland Mill" (Fig. 4) which left 14 dead, 17
injured, and property damage of 100 million DM.
357 dust explosions have been analyzed and the frequency of involvement of
the various dust categories tabulated (Fig. 5).
Almost one-third of the explosions were caused by wood dusts and every fourth
explosion happened in the food and feedstuff industry. These figures are practically identical with the ones recorded in the USA for the time period 1900-1952
(Table 2).
In Germany, as well as in the USA, most of the dust explosions occurred in the
industries cited above. The percentages given in Fig. 5 are therefore representative
of both countries.
Figure 6 shows the percentage of equipment categories involved in the dust explosions. Every fifth of these happened in a silo or bunker. Such silo explosions are
often spectacular, especially if an entire cluster of silos is involved (Fig. 7). Grinding and conveying systems, as well as dust collectors, participate at almost the same
ratio.
50.---------------------------------------------,
~
2....
til
QJ
D..
.;:+-
32
til
::J
"0
25
Fig. 5. Frequency distribution of dust types involved in 357 dust explosions [1] (1965-1980)
~ 50r-------------------------------------------~
+C
QJ
E
D..
5
CT
(lJ
is
:;::
25
24
::J
.0
"0
>,
&
!
QJ
0~~~~~9_-L~L-~~~~~~~~~~~~Y_~
Fig.6. Frequency distribution of types of equipment involved in 357 dust explosions [1]
(1965-1980)
In conclusion, Fig. 8 represents the frequency distribution of the various ignition sources responsible for the above dust explosions. Although it is sometimes
very difficult to determine the actual ignition source, it is apparent that mechanically produced sparks present the most frequent source in industrial practice, with
29 % . This includes sparks generated through friction, grinding, and impact. Therefore, it is not surprising that present research is concentrated on the effectiveness
2 Historical Review
VI
OJ
U
L.
50
::J
!i!
c
:;::
'c
29
.Ql
.....0
c
0
:;::
25
::J
.I:l
EVI
i5
>u
C
OJ
::J
rr
Fig. 8. Frequency distribution of ignition sources responsible for 357 dust explosions
(1965-1980)
of such sources in the case of dust/air mixtures. All other sources combined participate practically with the same probability as mechanical sparks. The outlined casehistories, which are certainly not complete, may serve as an overview of the dangers which have been known to exist for the past 200 years in processing or handling combustible dusts. The often-voiced opinion that a plant which processes dusts
Hiitet euch
vor
Staubexplosionen!
lli r v e rli c r t
SO Il St
Gut
lind
L ebe n
uod
Arbcit.
is safe because it has not experienced an explosion in the past years or decades has
been frequently disproven in practice.
The fact that about 36 % of all explosions have been caused by human error,
i. e., thoughtlessness, negligence, indifference, and ignorance shows clearly that effective instructions and training of employees are essential.
In this context, the poster designed by the US Departments of Agriculture and
Interior at the turn of the century is still valid with its slogan: "Watch out for dust
explosions. You may lose property and life, bread and work".
10
2 Historical Review
11
Name
Explosible dust
1844
M. Faraday
Coal dust
1878
R.Weber
Flour
1885
Engler
1891
1891
1899
H. Stockmeier
Barely 100 years later, G. Pellmont [7] reported extensively on the ignition and explosion behavior of such hybrid mixtures.
As early as the turn of the century, it was noted that organic and metallic dusts,
once dispersed in industrial applications, have to be considered explosible, whatever the "conditions for ignition". Weber and Stockmeier detected as early as 1878
the importance of particle size in assessing the danger potential of an explosion.
They noticed that the flour which was most readily dispersed reacted most violently. Also Weinman, who carried out tests at the Bergfiskalischen test site in 1922
in Neunkirchen (Saar, Germany) concluded that the finer the dust, the easier the
initiation of an explosion.
In 1925, the effect of particle size was deduced by Beyersdorfer [4] in the following way: Starting with a 10-cm cube, the volume would be V = 0.00l-m3 and the
total surface area SA = O.06-m2. Then the 3 coordinates were subdivided by decimal fractions and the sum of the surfaces of the thus-generated cubes compared
with the new edge (Fig. 10).
The increase of the total surface area with decreasing cube edge for the particle
becomes substantial. Every surface has the tendency to adsorb the surrounding
gaseous media; therefore, very fine dusts, which have a high surface activity, must
react more violently than coarse dusts.
At the same time, Jaeckel proved experimentally the validity of the claim. In
grinding plate sugar in a small air-tight ball mill, a distinct negative pressure was recorded after 24 h. This was explained by the adsorption of air on the newly created
large surfaces.
Dusts therefore have a marked surface activity. Particle size and the resulting
explosion hazard are approximately inversely proportional. Beyersdorfer was one
of the first to recognize the danger of standing dust layers which cannot be the immediate cause for an explosion. However, if such a layer is dispersed because of a
primary dust explosion, the ensuing secondary dust explosion may be devastating.
Beyersdorfer calculated the maximum allowable dust accumulation on the 6 surfaces of a cubical work area so that the dispersed dust would be just below the explo-
12
2 Historical Review
N~
104 I----I----+----~---I
VI
Q)
..a
:::l
103
d
'+-
Q)
102
.E':::l
VI
101
E0
-+-
Fig. 10. Surface increase from subdividing a large cube into smaller
cubes (length of original cube edge
lO-cm)
sible threshold. He based this on sugar dust with a lower explosible limit of 21 g/m3
(Fig. 11).
The smaller the work space, the smaller the tolerated dust accumulation presenting no dust explosion hazard. Dust accumulation of a few hundredths of a mm
suffice to create an explosible mixture. Cubically-shaped work spaces pose the
least hazard. The following equation relates work space parameters, the properties
of the dust, and the acceptable height or thickness of a dust accumulation:
C
2S
A=---1 1 1
i+;+h
where
A
acceptable height or thickness
C
lower explosible limit
S
density
1
length
w
width
h
height
Analyzing this equation for the acceptable height A of a dust accumulation gives
the following:
a) the acceptable height Ais smaller for non-cubical work spaces than for cubical
ones and
b) it is also smaller for a narrow building with low ceilings than for wide and high
spaces.
Beyersdorfer was also the first to make suppositions with regard to the mechanics
of a dust explosion. He assumed that the explosion of an organic dust was in reality
a gas explosion. He supported this with the following observation. A non-ex-
~
~
13
0.15
:c
.-.
E
..
<-
0.101-----+::~--__;
OJ
.-.VII
::J
"t:J
OJ
:i5
c
LEL = 21 g/m3
-a
Fig.n. Accumulations'of sugar dusts in a
cubical work space which will not present an
explosion hazard if swirled up
xc
E
0 0 - - - -.......- - - - - - '
o
2500
5000
plosible amount of sugar dust dispersed into a heated space would rapidly lower
the temperature 10-15C. Afterwards the temperature would rise a few degrees
above the initial temperature. He assumed that the observed temperature increase
was due to a chemical reaction between "sugar gas" and air. Such a heat generation
was thought to be the result of an oxidation, as atmospheric nitrogen does not qualify as a reactant. Therefore, the process of ignition has to occur in two phases:
14
2 Historical Review
For the observed metallic dust explosions, radiation is very important for the
transport of liberated energy. Gliwitzky and recently Leuschke [11] have shown experimentally that swirled-up metallic dust in air will explode through intensive
light radiation alone without conduction and convection.
Certain types of organic dusts with low minimum ignition energy and autoignition temperature can be ignited either by the radiation of a flash bulb or from a dust
explosion proper [11]. In the test, radiation seemed to be solely responsible because a glass window separated the fuel from the ignition source. Therefore, it can
be considered proven that the radiation from dust explosions participates to a great
extent in the energy transfer.
Zehr [12] recently confirmed the basic idea of Beyersdorfer with regard to the
combustion mechanics of combustible dusts. He observed that the combustion of
solid particles consisted of a reaction of oxygen in the gas phase surrounding the
particle surface. The combustible matter reacts to produce flames, i. e., the previously evaporated or smoldering gases oxidize or react in the flame with the diffused oxygen. After ignition, either by an outside source or by auto ignition - provided the conditions are right - the course of the incipient combustion of the dust/
air mixture will liberate energy, which is transported mainly through radiation to the
surrounding volume containing unreacted dust particles. Convection contributes a
minor share.
The combustion of 10 g of product will result in the following:
Substance
Temp .increase
Sulfur
Magnesium
Aluminum
The reaction propagates three dimensionally at a relatively high velocity. The
reactivity of the dust/air mixture varies with the type of dust. The analysis of coal
dust explosions has consolidated these findings [6]. Initially, it was thought that the
explosion occurred mainly in the gas phase. The volatile fraction of the ignited coal
particles was claimed to support the reaction. Others suggested that the oxidation
process at the surface of the coal particles was the determining factor. In recent
years, however, it is thought that the expelled volatile components, as well as the
solid coal substance determine the course of the explosion.
The volatile fraction seems to playa major role only at the start of the explosion. This seems to be supported by the results from experiments made worldwide.
The predominant interpretation describes the combustion of the coal particle
in 3 stages:
- heat-up of the granule and pyrolysis (formation and liberation of the volatile
fraction and tarry products)
- ignition and combustion of pyrolytic products
- ignition and combustion of the coke- and coal residues.
The time sequence of the appearance of the three phases depends mainly upon
the particle size and the heat rate. Howard and Essenhigh [13, 14] found with par-
15
ticles in the mm range and a heat rate of approximately 104 C/min a distinct dividing line between the liberation of volatiles and combustion. With smaller particles and a higher heat rate, however, the surface of the granule caught fire before
the volatiles were released.
The supposition that a coal dust explosion occurs in three stages may be proven
by the fact that the heat rate is estimated to be in the 106 -109 C/min range and the
particles which sustain the reaction are relatively fine.
Fig. U. Apparatus for the determination of the lower explosible limit, as per Weber
16
2 Historical Review
barely gave ignition. In such fashion, Weber determined the lower explosible limit
of flour at 25 g/m3.
In 1911, Tifanel and Durr used a photographic method to determine the relative
danger of a few dust types. A pre-weighed amount of dust was conveyed by a
stream of oxygen into a well-defined gasoline flame and a picture taken of the
length and size of the flame. Mainly flour, sugar, and Lycopodium were tested.
Figure 13 shows the apparatus R. Bauer developed in 1917 for the determination of the lower explosible concentration of aluminium dust. The apparatus consisted of a vertical tube with an impeller with electric drive in the lower portion, plus
an ignition source and a loose cover. After the addition of a known amount of dust,
the motor was started and the ignition activated. With this arrangement, the lower
explosible limit of aluminium dust was determined at approximately 400 g/m3.
The apparatus which was developed by Steinbrecher [6] for the determination
of the lower explosible limit of industrial dusts (Fig. 14) differs from the previously
described unit in its singly activated dust dispersion system through a blast of air.
The combustion chamber consisted of a vertical glass pipe with a hemispherical
end and a volume of 0.1351. The pipe also housed an ignition source and a thermocouple.
The dust sample was stored just ahead of the explosion chamber and then
dispersed in the cylinder by a jet of air. These igniton tests often destroyed the glass
tube.
Between 1933 and 1935, the Chemisch-Technische Reichsanstalt [8] (German
Chemical Technical Institute) used the apparatus shown in Fig. 15 for the determination of the explosibility of dustlair mixtures.
The dust was first deposited at the bottom of the apparatus and then swirled up
by a jet of compressed air discharged through a nozzle. A glowing wire was used as
an ignition source. The test results indicated that zirconium was especially explosible over a markedly wide range of concentrations.
t
Fig. 13. Apparatus for the
determination of the lower
explosible limit, as per R.
Bauer
17
thermocouple
,..--111-- - __~-
ignition
volume: 0.135 l
Fig. 14. Apparatus for the determination of the lower explosible limit,
as per Steinbrecher
air
reservoir
Until recently, Eckhoff [17] used an oxyacetylene torch for ignition in testing
the explosibility of dust in order to eliminate the risk of a misjudgement.
The hazard of a combustible dust is not only defined by its explosibility and explosible range but also by the pressure and violence of its combustion. In such a
context, the maximum explosion pressure and thepertinent pressure rise are of spe-
!!iif=l==:zO=iij,- perforated
paper
glass tube
'-\-+-- ignition wire
Fig. 15. Apparatus used by the Chemisch-Technische Reichsanstalt to investigate the explosibility
of dust/air mixtures
18
2 Historical Review
Steel
tube
Acetylene
burner
Dust
chamber
cial interest. Closed equipment is needed to test for these parameters. Obviously,
the test equipment shown in Fig. 12-16 is unsuited for this purpose.
In 1937, Mason and Taylor [18] used a 0.75-1 cylindrical glass vessel as the explosion chamber (Fig. 17). For the dust dispersion, they employed Steinbrecher's principle (Fig. 14). A mechanical indicator for the time-pressure recording of the dust
explosion was flanged to the top of the vessel.
volume: 0.474
or
0.752l
Fig. 17. Apparatus for the determination of the pressure rise of dust explosions, as per Mason and Taylor
19
manometer
pnessure reservoir
vacuum gage
pressure
~==:X===-==-'" vacuum
Fig. IS. Apparatus for the determination of the pressure/time behavior of dust explosions, as
per Trostel and Frevert (Volnme of the explosion chamber: 1.4-1)
Trostel and Frevert developed a method which directed an air jet from the top
down into a cup containing the dust layer (Fig. 18). Thus, the dispersion of the dust/
air mixture occurred in a spherical explosion vessel of 1.4-1 volume. Again a mechanical indicator recorded the time-pressure behavior of the dust explosion.
In following Trostel's and Frevert's concept, the "Bundesanstalt fur Materialprufung" [19] (German Federal Institute for Materials Testing) used a very similar
apparatus for their dust testing (Fig. 19). Initially, lead strain gages were used for
the determination of the maximum explosion pressure. Once it became obvious
that the flame temperature influenced the results, it was decided to use a mechanical indicator for pressure recording. As the dust dispersion method generates a
slight pressure in the explosion vessel, a negative pressure was set at the start in order to arrive at 1 bar (abs) at the initiation of the dust explosion.
Subsequently, the apparatus was modified again. Figure 20 shows the arrangement developed in 1957. The sphere was made out of metal and had a volume of
1. 7-1. The pressure rise of the dust explosion was transmitted through a membrane
which had a mirror attached. The deflected light beam was photographically recorded.
Homemade "capignitors" served as the ignition source; with a composition similar to thermite, these ignitors required no atmospheric oxygen. This type of ignition was considered extremely powerful since it also made hard-to-ignite dusts explode. This method of ignition became the standard for all dust tests in order to
maintain equal starting conditions for dust explosions to be studied.
At approximately the same time, the US Bureau of Mines developed the so-called "Hartmann apparatus" . The closed explosion chamber was cylindrical and had
a volume of 1.2-1. The dust to be tested was dispersed into the chamber onto a continuous electrical spark (arc) or a glowing wire coil. The values of pressure and rate
of pressure rise were recorded with either a mechanical indicator or a piezoelectrical pressure transducer [36].
20
2 Historical Review
Fig. 19. Apparatus for the determination of the pressure/time behavior for dust explosions,
as per BAM (Volume of the explosion chamber: 1.4-1)
21
vacuum
Fig. 20. Improved BAM -apparatus with a metallic sphere and optical recording unit for dust
investigations (Volume of the explosion chamber: 1.7-1)
hinged cover
with angle
indication
.------ glass tube (Pyrex)
compressed - air
pulse
A better correlation of the values seemed to require increasing the size of the
explosion vessel and improving the dust dispersion.
In 1938 Gliwitzky took the first step towards a larger test vessel [8, 9] by using
a 43-1 explosion vessel for his tests (Fig. 22). Impellers dispersed the dust. He was
22
2 Historical Review
also one of the first to recognize that the activation of the ignition source had to be
synchronized with the dust dispersion in order to arrive at reproducible results. The
ignition source was a wire bridging two electrical terminals.
Such an apparatus was used to determine the explosion limits and the rate of
pressure rise of dust explosions. The values gained from this equipment for the maximum explosion pressure for combustible dusts, e. g., aluminum, approached very
closely the theoretical ones.
Fig. 22 alb. Apparatus for the determination of the explosion limits and the rate of pressure
rise of dust explosions, as per Gliwitzky; a: equipmentlb: ready for testing (Volume of the
explosion chamber = 43-1)
23
actuate valve
-----
20
c:Cl
dust
container
.0
7:'
Cl
.0
explosion
vessel
::l
III
III
Cl.
c
0
Vi
.9
Cl.
cl
~I
~I
:61
~I
WI
~I
III
QJ
Fig.23. Schematic representation of the dust testing procedure developed in 1966 (Volume
of the explosion chamber ;?!20-1)
All dispersed dusts which contain carbon can be ignited under certain conditions
and are therefore explosible in terms of industrial practice [3] . Because of its reduced particle size [22], every dust is distinct from the same substance in solid or
compact form .
This qualitative statement leads to a quantitative determination of the particle
size, i. e., the particle size distribution of a given dust sample . In industrial applications, dust is generated as the intended end product or as an unwanted waste product.
The useable products come from particle size reduction , which can involve:
1) spraying and evaporation of liquids containing dissolved solids,
2) filtration , and
3) centrifugal separation.
Waste dusts occur in generating useable dusts because of friction and also while
machining compact materials [23] .
10 JLm)
25
10 /-Lm)
Single dust particles can take extraordinary shapes. The external form can be
granular (Fig. 24) , flat and fibrous, pointed , polygonal, jagged, etc.
The size of particles varies greatly in mixtures. The largest particle can be a million times bigger than the smallest one . Therefore , the number of particles per unit
volume cannot be used to characterize the dust.
A dust which is homogeneous with regard to its particle size is practically nonexistent, and it is also very difficult to artificially generate such a dust.
The inherent motion of swirled-up dust creates local changes of concentration
in time (separation). The solid particles settle differently depending upon their
size. Gravity is the most important force for the settling of a given particle. The
free-falling particle is not constantly accelerated, but because of its friction reaches
a constant terminal velocity quite rapidly. This velocity can be approximated in accordance with the "Stokes' Law". Figure 26 shows the correlation of settling rate
with particle size at room temperature and different densities.
The above conclusion led the committee of specialists for dust technology in
the VD I to the following definition for the term dust: Dust consists of solid particles
which, due to their small size, will reach a uniform settling velocity in still air after
a short distance of acceleration. The velocity is approximately 0.03-100 cm/s,
which is much smaller than the one expected from the "gravitation laws."
A short time thereafter [24], the committee on "Combustible Dusts" gave the
following definition: "dust is a dispersed solid of any form, structure, and density."
In practice, it is common to use the term "dust" if the particle size of the solids
mixture is 100-300 p,m. Mixtures with particle sizes of 100-300 p,m are designated
as "fine" dust and the ones with particle size 30-100 p,m as "finest" dust. The
26
k'
u
o
Qj
>
Ol
c:
.....
.....
Q)
III
0.01 L - - _ - - L_ _L--_--L_----J
1
10
100
1000
10000
Fig. 26. Airborne dust ; rate of settling as a function of particle size (room temperature)
portion of particles less than 30 JLm are called by Geck [3] "dust in dust". They can
remain in suspension in air for up to 48 hours.
It should be pointed out that short fibers also fall into the category "dust". Such
fibers are generated by cutting synthetic continuous threads or through the grinding or processing of natural or synthetic fibrous material. Such solids (Fig. 27) are
known by the term "flock" , which is characterized by its dernier D equal to 1 g per
9 km of thread and the length 1 of the cut. Fibers, which once airborne are capable
of burning, are mainly used in industrial coating installations (carpet industry,
floor coverings, car supplies).
28
ZWAHLEN)
4.2.1 Flammability
Dust layers are considered to be flammable if they can be ignited with an outside
source and if the fire propagates to a certain extent once the source is removed. Various ignition sources are used in preliminary tests to determine the general behavior of dust layers with respect to flammability and combustibility. The sources are:
mechanically produced sparks (lighter with flintstone), glowing cigarette, burning
match, and gas flame. They often have played an important role in actual mishaps
(Fig. 28) [27].
A test may be repeated at an elevated temperature (e.g. , at lOOOe) , because
dusts behave differently at various temperatures (see sect. 4.2.2).
29
test in glass
tube
30
Test result
No ignition
Brief ignition
rapid extinction
No spreading
of fire
Fire
spreads
CL
Reference
product [20C]
Table salt
Tartaric acid
I-Amino-8-naphthol3,6-disulfonicacid (H-acid)
Sulfur
Black powder
+ Lactose
drying is contemplated), the combustibility test can be repeated at elevated temperature (e. g., at the anticipated drying temperature). This is not necessary if the test
already resulted in a class 6 at room temperature. Sometimes there is a marked difference in the combustion behavior (Table 5). Therefore, the test temperature has
to be listed together with the combustion class.
The testing can be done in accordance with Sect. 4.2.2.1 except that the sample
with its holder (e. g., ceramic plate) is preheated in a laboratory oven to the desired
test temperature (e.g., 100C). The sample is ignited with the glowing platinum
wire directly in the laboratory oven. Ample air flow has to be guaranteed.
CL20C
CL 100C
2
2
5
5
5
I-Diazo-2-naphthol-4-sulfonic acid
Dextrin
3
2
3
6
5
31
In practice, a special test arrangement has been proven successful which ensures enough air and removes the combustion gases. Additional tools are necessary,
such as: a mold for the sample, sample holder, glass tube, and a heat-resistant insulated support (Fig. 29).
The sample product is loosely filled into the mold and then covered with the
sample holder, so that the product rests in the center of the holder. The mold and
the sample holder are turned 180 and the mold lifted off. The sample holder with
the product is then inserted into the glass tube which sits on the support.
The complete assembly consisting of support, glass tube, and sample holder is
preheated in the oven for one hour at the desired temperature.
Afterwards, the complete assembly is removed from the oven and ignited with
the glowing platinum wire [29].
0
mold for
sam~
32
4.2.3 Deflagration
There are dusts which will decompose in an oxygen-deficient atmosphere, once
they are ignited by an outside source. The decomposition spreads through the total
amount of product more or less rapidly and produces a high temperature rise, liberating a substantial amount of gases. Such a behavior is called deflagration, in line
with the nomenclature used in the technology of explosives.
A deflagration, for example, can be initiated by a foreign particle which has
been heated up through friction in a mill and then discharged with the product into
a container. It can also develop from a localized fire, which can change to a deflagration because of insufficient air infiltration.
The course of a deflagration cannot be stopped through inerting or choking.
The residue of a deflagration (ashes) can still be combustible. If the hot ashes
from a deflagration are exposed to air, they may burst into flames spontaneously
like an explosion (secondary mishap).
A deflagration liberates a large amount of gases, which, if not vented, will result in a pressure build-up in a closed vessel. This may cause the vessel to tear or
rupture.
In the deflagration product, the transport of heat occurs primarily through convection of the hot gases from decomposition.
The spreading of the exothermic decomposition can be slowed or even prevented through an endothermic change such as melting of the product or evaporation
of residual moisture. Laboratory tests have been developed in order to detect the
tendency for deflagration of a product. All products should be subjected to such a
test: 1- if they have a combustion class ;:::4 at room or elevated temperature (Table
4) or 2 - when tested for thermal stability (see Sect. 4.2.6.1) they show a spontaneous, strong exothermic decomposition.
The chemical structure of a product may also give some clues with regard to its
tendency to deflagrate, e.g., if the molecule contains more than one nitro group or
if it contains elements which are known to beless stable [31].
4.2.3 Deflagration
evacuated
glass pot
(Witt'scher pot]
33
vacuum
The test is repeated with the ignition applied after the pot has been evacuated.
If the product catches fire under vacuum and the decomposition propagates , then
a deflagration is obvious.
34
glass tube
thermocouples
1-3
140
4H
inert g a S _ t
35
Table 6. Various products with smolder temperatures (taken from VDE 0165/8.69)
Product
Phosphorus
Iron powder
Rye flour
Wood flour (pine)
Charcoal
Naphthalene
Polyvinyl chloride
Max. particle
size
Bulk density
[/Lm]
Maj. portion
having particle
size [/Lm]
150
500
30- 50
100-150
200
150
20
300
10
30- 50
70-100
1- 2
80-100
4- 5
0.99
1.6
0.31
0.22
0.36
0.53
0.55
[kg/I]
Smolder
temperature
[0C]
305
240
325
315
340
Melted
Charred
Table 7. Correlation of smolder temperature with particle size and height of dust
layer [35]
Dust
Sieve fraction
Flame coal
(bituminous coal)
<200/Lm
< 70/Lm
295
270
270
230
Gas coal
(bituminous coal)
<200/Lm
< 70/Lm
400
270
270
245
Lean coal
(semi anthracite)
(subbituminous)
<200/Lm
450
350
< 70/Lm
340
280
36
thermOCOUllle
~ to recorder
heating plate
,-- - -
---!-
dust layer
-~'-
-- - - ------------ - ------,
'-_/
"-
-- ..-
m
Fig. 33. Apparatus for the determination of the smolder temperature (schematic)
4.2.5 Autoignition
It is understood that autoignition means the ignition of combustible matter in air
sUbjected to uniform heat. The temperature of the surrounding atmosphere (storage temperature) which initiates auto ignition after self-heating of the product is
called the auto ignition temperature.
250r-----.------,------.------.------.------.
......
OJ
<...
:::J
CL
200
2~
._.....
cL.l
0 0
'c01 150
.....:::Jo
d
100 1'-0-1:-----'-10"0---1-'-::01-,..----I10"'""2c-----l.10-:::-3----L.104.,....------l1a5
4.2.5 Autoignition
37
38
wire mesh
container 8 ml
with test or
reference
samples
king
Fig. 36. Apparatus for the determination of the relative auto ignition temperature, as per
Grewer (actual)
4.2.5 Autoignition
39
10 3
\
\
c
E
OJ
.......
102
\
"\
'\.
"-
I"
Fig. 37. Induction time versus
storage temperature (at constant
volume)
70
80
90
100
temperature rOC]
..........
........
110
120
40
to recorder
thermocouple
reference sample
platinum wire
)
ther
tes t
~'-'--'-''---''--'----
~----'---
41
f\
""'"
u
o
...-
......
time [min]
Fig. 40. Testing for exothermic decomposition under temperature-programmed conditions;
course of temperature
42
b) Isothermal test
If the temperature-programmed test results in an exothermic reaction, then the
LJ
0
ar180 \,
a
1160 !
OJ
r....
--e
::J
.'
/,[I
during 8 h
no reaction
OJ
0.
OJ
+-
time [min 1
Fig. 41. Isothermal test for exothermic decomposition. Normal temperature behavior
If
u
o
QJ
t...
zoo
180
1\
f' a
j\,
1\
i\
I \.
,,
, I
--e
::J
QJ
Cl..
time [min 1
Fig. 42. Isothermal test for exothermic decomposition. Autocatalytic temperature behavior
43
44
160
16 h
Bh
4h
150
L.J
o
~
.....
140
130
:::J
e
QJ
D.
5:j
.....
120
110
100
90
~
10
20
30
---
time [h 1
40
50
60
45
100
80
L.J
0
QJ
':::J
+-
60
Cl
'QJ
Cl..
QJ
+-
non-critical
40
20
ambient
temperoture : 20 0 [
0
10
20
30
40
time [h 1
Fig. 45. Example of self-heating due to an exothermic decomposition. Temperature gradient
in the center of a free-standing 150-1 drum
46
Critical heat
production
[I]
[mW/kg]
Critical
temperature
of the sample
reaction
[0C]
10000
37
1000
10
48
4 days
100
60
20 hours
10
60
280
73
Shours
1400
86
1 hour
product. The cork stopper may be protected with a thin teflon foil. It is advantageous to preheat the product to 1O-20C below the test temperature. The flask is put
into an oven (hot box) which is preheated to the test temperature and which has
vent openings. At the same time, a flask (e.g., Erlenmeyer flask) filled with graphite is put into the oven. The temperatures sensed by the thermocouples in the
product and the graphite are recorded. The temperature of the graphite is the reference temperature. The self-heating of the product is indicated by a rise of the product temperature over the reference temperature. The test is repeated with a fresh
sample at a 10 C lower temperature until exothermic reaction has ceased for three
days. In a special test procedure the oven temperature is adjusted to the product
temperature in order to prevent heat losses. Products which develop a significant
vapor pressure at the test temperature are better tested in a pressure vessel [44,26].
The report must include statements with regard to: sample volume, oven temperature, maximum product temperature reached, and induction time (the time it
takes for the sample to attain the peak temperature after it has reached oven temperature). In case there is no self-heating, the total elapsed test time is recorded.
The graph showing the correlation of induction time tj with oven temperature
to at constant volume expressed as log tj = f(lIto) is in most cases a straight line
(Fig. 46).
4.2.7 Explosibility
47
\
~
10
10
,--
r-- -
1-'
1\
(lJ
102
r-
10
100
120
140
160
180
200
temperature [Oel
4.2.7 Explosihility
An explosible substance can spontaneously decompose due to temperature
change, mechanical loading, shock waves from a detonation, or other reasons.
Large volumes of gases will be liberated in an short time resulting in a rapid pressure build-up (explosion, detonation).
The explosion hazard of solids is judged in accordance with the results gained
from the tests promoted by the European Community [45]:
a)Testing of the mechanical sensitivity towards impact loading (impact sensitivity)
b) Testing of the mechanical sensitivity against friction (friction sensitivity)
c) Testing of thermal sensitivity towards an external heat source (test with steel
tube)
There is no immediate connection between the three tests. A product which is
thermally sensitive, need not be mechanically sensitive and vice versa. However,
most products which are sensitive to friction are also impact-sensitive. Yet there are
a great number of products which are impact-sensitive but insensitive to friction.
48
Chances are small that a mechanically sensitive, explosible product would not
be detected if only the test for mechanical sensitivity were performed with the drop
weight (impact sensitivity) and no friction test (friction sensitivity) were performed. Various countries require additional testing in line with their laws covering
the handling of explosives. A tabulation of the usual methods is given in [46].
-r-rt--_
drop weight
49N(5kgJ:drop height:80cm
98 N(10kg J: drop height: 40cm
test sample
4.2.7 Explosibility
49
Fig. 48. Testing for impact sensitivity; detonation under the drop weight
load
',---+-!~
fixed
porcelain rod
porcelain plate
50
The dried product is put in between the porcelain plate and the porcelain pin
and exposed to friction by moving the plate at defined conditions. The maximum
speed of the plate is 7 cm/s. The sample amounts to approximately 1O-mm3 . The behavior of the product under friction exposure is observed and recorded.
The intensity of friction is changed by varying the weight load on the pin. The
criteria for judgment are: no reaction, partial reaction, ignition, crackling, or banging. If ignition, crackling, or banging is noticed at a load of :::::::360 N on the pin, then
the product is classified as friction-sensitive and explosible.
~nut
~nozzle
plate
threaded
4 gas burners
ring
steel
tube
test
sample
Fig. SO. Testing for thermal sensitivity; steel tube test (schematic)
51
The test is carried out with nozzle plates having different hole sizes.
The largest diameter of the hole is stated as the limiting diameter which causes
at least three fractures of the tube in one of three tests. With a limiting diameter of
:;:;:2.0-mm, the product is thermally sensitive and considered explosible. For transportation purposes, it is classified as an explosive, the same as impact- and frictionsensitive products are.
In order to carry out such tests, a bunker or suitable open-air spaces are
needed.
52
:::J
til
til
Q)
'Cl..,........
c'Od
.-..0
tIl~
D..
.----.--.=---.
"'--"",-"",
..
~
'd
..0
ignition at
zero
turbulence
Q)
til
'Q)
'-
:::J
til
til
Q)
'a.
4-
Q)
-I-
d
'-
high
medium
low
"'-
turbulence at ignition
the particle size distribution within a dust type (see Sect. 3) has a considerable influence upon the combustion of a dust/air mixture. Figure 52 shows such a particle
size distribution for two dusts. Such a distribution is obtained through sieving and
may vary greatly.
For practical purposes, it has been expedient to specify the so-called median value M of the particle size in comparing the safety characteristics of airborne dusts.
M is the 50 wt% point of the particle size distribution. In Fig. 52, Lycopodium dust
has a median value of M = 32 fLm, the cellulose dust M = 22 fLm. In both cases we
are dealing with fine dusts.
It is also clear that the median value is only descriptive and not definite. Dusts
with the same origin and median value may not have the same combustion behavior, the reason being that the proportion of fine and coarse dust varies and the particle size distribution is not the same. However, from testing experience, we know
that this variability becomes negligible if the median value is smaller than 63 fLm.
g;<-
53
median value
4-
c:
OJ
u
<-
OJ
Cl..
OJ
>
:5
E
:::1
Lycopodium
Cellulose
98
20
4.3.1.3 Explosibility
A dust is considered explosible if, after igniting the dust/air mixture with a suitable
source, there is a flame propagation (Fig. 53) in combination with a rise in pressure.
54
Such an explosion process occurs, as is generally known, due to mutual interaction between reactants. The products of reaction may be formed directly or
through complicated intermediate steps. The required oxygen for this reaction is
mostly supplied from the combustion air, with the nitrogen acting as ballast [50,
51]. It is important that the overall reaction is exothermic. For the following discussion, only dusts are called combustible in the airborne state if they require oxygen
from the air for an exothermic reaction.
There exists no uniform definition for the term explosion. Only the most important will now be described.
Beyersdorfer [4] suggests: "In a narrow sense, every sudden volume increase
due to a physical or chemical process is an explosion".
The VDI professional committee on "Combustible Dusts" [24] defines an explosion as "a combustion which occurs so quickly that the heat-related expansion
of the participating gases results in a marked and measurable rise in pressure."
As per DIN standard 20163 [52], an explosion is "a rapid conversion of potential energy into work of expansion or work of compression, or a combination of
both kinds of work with the generation of shock waves (compression shocks)."
The revisedVDI guideline 2263 [23] finally states: "an explosion is a rapid combustion, with a marked and measurable pressure increase".
55
25175
~
-0
LEL
>
.......
0~
UEL-
air
20/80
-0
>
a
.......
d
l.-
15/85
.......
0
10/90
0
500
1000
concentration [ g/m 3 )
dust
-E
01
-l
W
-l
1000
.......
'E
..5!:!
..a
500
(/)
0..
xQJ
I.QJ
0
"l)
100
10 3
lcf
105
106
107
56
E
en
SO
OJ
..Cl
VI
Cl..
X
OJ
o~------~------~
10
100
1000
temperature T rOC]
An increase oftemperature will reduce the value ofLEL (Fig. 56). This is more
pronounced the higher the value at ambient temperature.
dust
container
111~tJ
detonator
activated valve
semi - annular
dispersion nozzle
I exhaust
, gas
F1g.57. Test apparatus (V = I-m 3) for the determination of the explosion characteristics of
combustible dusts (schematic)
57
58
'd
20
..Cl
~_..QQ._ 1Q8
-432 bar
_ rote of
s - pressure rise
- dt -0.025 -
~t
X
OJ
CL
QJ
'-
10
::I
Vl
Vl
QJ
~p
'-
CL
ol--_ _
.Q
Vl
~C/-_:
=10.8 bar
time
----[s]--
Ci
X
moment of ignition
QJ
Fig. 59. Definition of the rate of pressure rise of a dust explosion (any concentration)
15
..Cl
10
--
maximum
108
. bar= explosion pressure p
max
1000
~~ 400
/'
Vl11
::1'-
~:;: 200
-...
CL"Cl
-CLO
O"Cl
QJQJ
d.~
,-,-
I
1
0
V'
1000
zaxl
I\.
maximum rate of
- 432 bar/s=pressure rise
(dp/dtl max
2000
dust concentration [g /~
The turbulence of the dust/air mixture at the moment of ignition exerts a significant influence on the above-mentioned explosion characteristics. Figure 61 shows
this influence for two dusts. This degree of turbulence is assigned a special significance for the maximum rate of pressure rise (dp/dt )max' With decreasing delay time
td (increasing turbulence) the maximum rate of pressure rise increases continuously. Therefore, for dust testing in the 1_m3 explosion vessel a constant ignition
59
mr---------~----------~
____ .
c...
Cl
~-'"'9'--
-Cl
.;?
Cl
"E
Cl..
"
-c
c:
0
200
.E
VI
0.. ..
-VI
c...
Cl
-Cl
100 I-------,----=...----l
turbulence:
o high
o
0.6
delay time oftd = 0.6 s has been selected. This value is only valid if dust containers
of 5.4-1 are used. The resulting time span ensures complete injection of the contents, i. e., the dust concentration in the air within the explosion chamber is known.
If the control of the standard delay time td is not maintained, the actual dust
concentration in the 1-m3 chamber will vary. Either the dust/air mixture will not yet
be dispersed (td <0.6 s) or the process of sedimentation will have started already
(td >0.6 s).
For the determination of the maximum explosion characteristics over a large
dust concentration range it is sometimes unwise to use the standardized 5.4-1 dust
container - expecially for dusts with a low density. It may become necessary to use
10-1 dust containers. In this case, the ignition delay time td must be changed in such
a way that the results determined with the 10-1 container are the same as the ones
obtained with a 5.4-1 container.
Figure 62 shows that the larger dust container (with the same propellant pressure of PT= 20 bar, air) has produced a higher turbulence for the dust/air mixtures,
compared with the smaller ones. The maximum rate of pressure rise (dp/dt)max is
more influenced than the maximum explosion pressure (Pmax). Therefore, in order
to obtain the same results with the 10-1 container as with the 5.4-1 container, an ignition delay time Oftd = 0.9 s must be used (Fig. 63).
60
10,-------:1..=---_---,
(f
r:::
-,
..Cl
turbulence:
high
medium
low
5r-
0.
oL - ._ _
-,--I_ _- ,
Vi
300 ,--------,;-------,
101 contoine ~
"\
t:::
200
=-"="""'-'-'=-'--'\.
~~..
1m 3 vessel
Cellulose: M= 22 ~m
E= 10000J
oO~---::'-:----:"
0.6
1.2
td [s1
Fig. 62. Influence of the container volume and the ignition delay time upon the explosion characteristics of a
dust
..Cl
ClJ
D-
O~
______
________
td =0.65
td = 0.95
~
________
~O.-----~-----,------,
1m 3 -vessel
Cellulose:M::22~m
E=10000J
--
200
Vl
..Cl
-+-
""t:l
100
D-
""t:l
1500
61
If the test volume is increased from 1-m3 to larger closed test vessels, the maximum explosion pressure pmax will remain constant. However, the maximum rate of
pressure rise (dpJdt)max decreases according to the "Cubic Law":
(dpJdt)max,l' (VI)
1/3
where K st represents a test- and procedure-specific characteristic value with the dimensions bar m1s; it is independent of the test volume.
Figure 64 compares the explosion characteristics measured in vessels of different volumes with those measured in the standardized 1-m3 vessel.
V = 1-m3 ; one 5.4-1 dust container
V = 2.4-m3 ; two 5.4-1 dust containers
V = 1O-m3 ; ten 5.4-1 dust containers
The figure shows that the values for the maximum explosion pressure pmax are independent of the volume of the explosion vessel within the range of accuracy. Only
the shape of the vessel can influence the peak value. In spherical vessels, higher
pressures are observed, compared with cyclindrically shaped vessels.
The differences in the height-to-diameter ratios of the various vessels are as follows: for the 1-m3- and 1O-m3-vessel, the ratio is 1; for the 2.4-m3 it is 1.55. This explains the slightly lower results obtained with the 2.4-m3 vessel.
Figure 64 shows also that the Kscvalue for different dusts is independent of the
volume of the explosion vessel.
o V = 2.4m 3
10 f-. V= 10m3
'QJ
V)
V)
QJ
>
.......
=
",
9 I--
.0
CL
"CJ
C
QJ
V)
V)
QJ
>
rrI
E
...:t-
-....
V)
300
c:..
.0
200
+V)
100
f-
62
Therefore, the validity of the "Cubic Law" is proven for the course of explosions of combustible dusts in closed vessels in this size range. The above-described
agreement of the peak values (Pmax and K st ) is only valid if the dust testing procedure is correctly followed. This means that the number of 5.4-1 dust containers
must be proportional to the volume of the explosion chamber (see description of
Fig. 64). Also the dust must be distributed from all dust containers through the
usual perforated half-ring, and the source of ignition must consist of two pyrotechnical ignitors with a total energy of E = 10 kJ. The ignition must be activated after
an ignition delay time td = 0.6 s. A corresponding number of 10-1 dust containers is
also acceptable provided that the ignition delay time is set at td = 0.9 s (Figs. 62/63).
Every deviation from the above-mentioned condition (e. g., changed volume of
the dust storage container, changed propellent pressure, changed discharge valve
of the storage container, change in the perforated half-ring for the dust distribution) can influence the explosion characteristics - especially the Kscvalue. The results of such changes can be so drastic that even if the standard ignition delay time
is used, there will be no correlation with the results from the standard I_m 3 vessel.
If such modified systems for dust investigations have to be used, the ignition delay
time has to be selected in such a way that the same results from testing a large number of dusts are obtained (within the range of accuracy) as are obtained from a I-m3
vessel [55, 56].
~~~ii====i=t===-:s~upport
base plate
63
Fig. 65 alb. 20-1 laboratory apparatus for the determination of the explosion characteristics
of combustible dusts (a) schematic, b) actual apparatus)
64
Pex
initial vacuum
explosion
[barl
~!
--O-+'---....-i"
!
o
(J)
dust outlet
valve opens
standard pressure
[msl
time t
(1 bar absolute) after expansion of the previously compressed air into the storage
chamber.
Figure 67 shows the explosion characteristics based on a large number of dusts,
measured in the 20-1 laboratory apparatus and in the 1-m3 vessel, using the same
ignition source (pyrotechnical ignitors with a total energy E = 10 kJ). The results
obtained in the 1-m3 vessel are based on a starting initial pressure of Pi = 0.1 bar
(1.1 bar absolute). This is inherent to the dust investigation test procedure. For the
above-mentioned correlation (Fig. 67), these results have to be corrected to a pressure of 1.0 bar (absolute).
Based on Fig. 67, the following conclusions can be drawn:
- the values for the maximum explosion pressure pmax in the laboratory apparatus
are slightly lower than the ones measured in the large test apparatus (1_m 3 vessel), but they can be adjusted by a correlation graph,
16
fine dusts
pyrotechnicul ignitors
t:'
Cl
..0
OJ
L-
OJ
~
I/)
8~--------~~~~--------~
.2C>
N
Cl.
O~----------~8~----------~~'
65
800 , - - - - - - - - , - - - - - - - "
fine dusts
pyrotechnical ignitors E=10000J
QJ
ffi
.c.
~~-----~~'-------4
Co
III
I
.....
Vl
::.::::
800
K st :1rrr-vessel
[barm/sl
- the Kscvalues are the same in both apparatus up to highly reactive metal dusts
(Kst = 700 bar m/s).
Figure 68 shows that this is also valid for various coating powders, i. e., combustible
dusts having the same process origins but not the same median values. In this case,
the measured maximum explosion pressures from the laboratory sphere have been
corrected.
..0
10
OJ
<-
OJ
..c:.
a..
VI
I
5 -
C>
N
E
a..
E
L-
o transparent powders
"
o EP/PES powders
'"
/),. aluminum-containin1
powders
,I
200
o trans~arent powders 0
~'
o EP/P S powders
",aluminum-containing ,6 c:f>
powders
A g",
..0
OJ
<-
OJ
..c:.
a..
VI
I
100 -
C>
N
-I--
l/l
10
[bar]
~,~;DO
'XlO
200
66
<-
.D
6r \
pyrotechnical ignitors
E=10000J
0-
0
600
E
i..
20 I -sphere &
1 m3 -vessel
400
.D
t
St3
St2
-+Vl
200
:.::::
............
0
15
standard deviation
St1
I
30 StO
[:t%]
Fig. 69. Standard deviation of the explosion characteristics for combustible dusts
67
Fig. 70. Electrically heated 20-1 laboratory apparatus for the determination of the explosion
characteristics of combustible dusts at elevated temperature
68
c::0
..0
EJ_Gl
8_13_8
e,.-e.
e,._e,.~
0-0
O_G_~
B
7
0..
11ft
~
t-
..0
101
0.01
0.1
1.0
10
69
'd
Ll
x
d
0..
200.-------,----,
Cellulose
2'-
100~----~~--~
Anti-oxidant
o~----~---~
100
50
12.----.---,,---.----.
'd
.D
X
0.
300.----.----.---,----.
'i7 Baking
200
~
E
'd
.D
flour
o Methyl cellulose
Polyethylene
~PVC dust
100
300
70
Fine dusts react more violently than coarse dusts. The median value M therefore has a marked influence on the explosion violence (the Kscvalue) and a less
pronounced one on the maximum explosion pressure. Therefore, to obtain the maximum values for industrial applications, the dust samples used for the determination of the maximum explosion characteristics should have a median value M ,;::;63
/-L m .
It also follows from Fig. 74 that, in general, dusts with a particle size of 400 to
500 /-Lm cannot be caused to explode, even with powerful ignition sources.
It must also be remembered that fine dust can be created by abrasion of a portion of a coarse dust. If that is the case (Fig. 75), it has to be recognized that - depending on whether this particle size limit is exceeded considerably (methylcellulose) or only slightly (polyethylene) - an admixture of fine dust of 10 % in the case
of methylcellulose or 5 % in polyethylene will be sufficient to make the mixture explosible. In fact, a relatively high maximum explosion pressure is reached. There is
no clearly defined lower level of concentration for fine dust within coarse dust below which no protective measures have to be considered [23]. But an explosion
hazard is always present if the content of the fine dust in the coarse, non-explosible
material exceeds its lower explosible limit.
If combustible dusts with particle sizes between 400 and 500 /-Lm are produced
or handled, an explosion hazard can still exist if sufficient fine dust is produced,
e.g., through abrasion, creating an explosible mixture.
Some dusts, e. g., red phosphorus, can ignite themselves by simply exiting from
the ring nozzle. The explosion occurs before the induced ignition and therefore at
an ignition delay time below the standard one. A determination of the explosion
characteristics according to the test procedure is therefore not possible without difficulties. It is known that the self-ignition of phosphorus decreases by lowering the
10
I-
..0
X
CI..
~
E
t:.
..0
+Vl
x::
non explosible
0
300
rr------.------,~
200
100
50
50
mixing ratio
Q 1)0
5.Q
100 0
50
: non explosible coarse dust [%]
explosible fine dust
[%]
71
10.------,-------"1,--,
I
I
1
I
.... _dr-6bar
L..
.,.'....
51."
.0
."
II
CL
600
-(/)
400
570 barm/s
,
I
;.
L.
.0
+-
til
200
I-
Fig. 76. Determination of the explosion characteristics of red phosphorus in oxygen-lean atmospheres (20-llaboratory apparatus; E = 10 kJ)
/1'1
0
I
I
I
I
.t: I
J!:!I
5:-1
~IL..
t; Ia
10
20
25
Oz-content in N2 [vol % 1
oxygen concentration. In the process of determining the explosion data in the 20-1
sphere at a low oxygen level, a relationship between the explosion values and the
oxygen concentration in nitrogen has been found (Fig. 76). This correlation is only
valid if the oxygen content in nitrogen is not too low. It is possible, according to
Fig.76, to extrapolate the explosion characteristics to normal atmospheric pressure. Control measurements in normal air without self-ignition proved the results
gained through the extrapolation procedure.
Often the statement is made that dusts containing a few percent of water can no
longer generate explosive dust/air mixtures. Figure 77 contradicts this assumption.
A decrease of the explosion violence is normally observed at relatively high water
content. However, many products exceeding 10 % water content cannot be dispersed (whirled up) properly. Therefore, the hazard decreases for the formation of
explosible dust/air mixtures from dust deposits. Products containing solvents show
a significantly different behavior. Figure 78 shows this influence of different solvents
on two pharmaceutical dusts.
In case of the product containing ethanol, the explosion characteristics will first
be decreased by increasing the solvent concentration. When a high solvent concentration is reached, the explosion characteristics begin to increase. The reason is
that at sufficient solvent concentration the product agglomerates and cannot be
properly dispersed. Also at still higher ethanol concentrations in the explosion
chamber, an ethanol/air mixture will be developed and ignited through the ignition
72
10
cd
..0
'-
..0
contain5
ethanol
CL
0
200
o~--~------~--~----~--~~
200.-------.---,-------,------.-,-,---,
contains
acetone
L
d
..0
E
L
.8
100,_I11;:;;:-""'"'()o-_-"
.....
Vl
100
::.::::
0~1----~----~5----~10~---*--~~~
source instead of the dust product. The observed effects are different for dusts containing acetone. Acetone evaporates four times faster than ethanol. Therefore, the
values for the explosion characteristics show that at acetone concentrations greater
than 15 % the stoichiometric combustion mixture in the explosion chamber is exceeded.
The above finding is of great technical safety importance concerning the assessment of risks created by the processing of products containing solvents, e. g., in fluidized bed driers.
The course of an explosion of dispersed combustible dust in closed equipment
is also influenced by the initial pressure Pi, the pressure existing at the moment of
ignition. Figure 79 shows, with the example of three combustible dusts, that the
maximum explosion pressure pmax and the Kscvalue are proportional to the initial
pressure Pi. Also, the optimum dust concentration for the explosion characteristics
increases proportionally as the initial pressure is increased.
A doubling of the initial pressure Pi causes a doubling of the explosion characteristics, and it must be stated again that the maximum explosion values at these elevated initial pressures can only be obtained at relatively high dust concentrations.
Because the straight lines do not intersect the origin of the coordinates, below a
73
300
Lycopodium
10
200
I-----+--,~
t-
L-
a
.0
.0
Melamine
formaldehyde
polymer
~ 5 f-----,g.,'---jf-------~
0..
100
.....
Vl
:.c::
[bar.abs]
initial
Fig. 79. Influence of the initial pressure Pi upon the explosion characteristics
7,5
c:
a
~
i
.
b
.'/~ .'
o
/~ /
.D
~:propone
./~
5,0
Cornstarch
Lycopodium
Sewage sludge
Dyestuff
!'~.'
D..
2,5
Pi =1bar (abs)
o0,002
0,003
1/ T
[1/Kl
0,004
74
The explosion pressure decreases linearly with the reciprocal value of the increasing temperature. The same trend was found with combustible gases. The explosion pressure varies the same way if the initial pressure Pi is varied (Fig. 81).
The observed variation of the maximum explosion pressure with temperature
is due to variations in the oxygen concentration (in nitrogen) which also changes in
accordance with the ideal gas law. Figure 82 shows an example with two dusts. The
/" 7-'
12
I Pi
[bar.abs)
Pi
'-
~::
..0
o.E
~1.0
~06
Lycopodium
Q002
QOO3
[barabs)
0.004 0.002
0.003
0004
[ 11 K1
11T
Fig.81. Influence of the temperature T and the initial pressure Pi upon the maximum explosion pressure Pmax
10
/
'-
0'
0/
;0/
.8
Lycopodium
)(
increasing
initial pressure
o
10
_i~ focror"'"/
polymer
)(
Co
/
0
0
rl~
o 40"[
o 1000[
l!.
0.005
2000[
0.01
0.015
75
150
.....
Vl
.......
100
Lycopodium
r.:...
d
..Cl
4-
Vl
Fig. 83. Influence of the oxygen concentration in nitrogen upon the Ks,-value
(initial pressure = normal pressure)
50
"'____
Pea flour
"'---Dyestuff C
0~------~1oo--------~200
temperatu re T
76
200,------,.----.-----r--o----,
rYe
Pi ~ 1barabs
1:,.//
100
/
.!(!
L.
200
E
d
/ts.
increasing
initial pressure
Lycopodium
.D
I:,
/0
.....
Vl
~
df:
~
:x::
100
.;
OL-______
0/
Melamine formaldehyde
polymer
________
0.005
______
~.
0.01
77
200:======:1=..(Q.=====~
I=====~:=====~I======::=
I====~
..!:(!
E
.:.
c:l
100
. . -.......orf'/
.JI-.''a..
.D
--______
_~
-o--~--_o_--
__-
+Vl
:.:::
0101
Fig. 85. Influence of the ignition energy upon the explosion characteristics of easily or
normally ignitable dusts
Figure 85 is proof that this is not the case. The dusts shown here are easily or
normally ignitable by condenser discharge. For these dusts, the ignition source is
not important. Weak condenser discharges as well as strong pyrotechnical ignitors,
such as the ones specified for dust testing, give the same results.
There exists another group of dusts, which are difficult to ignite (Fig. 86). Adecrease in the ignition energy will normally result in a linear reduction of the Kscvalue. The maximum explosion pressure is generally not affected by such an influence. Only with dusts which are very difficult to ignite (e.g., dyestuff), is this decreasing tendency noticeable.
These conclusions are valid for all test apparatus having a volume V = 0.02 to
l.0-m 3 and which are operated in accordance with the prescribed procedure for
dust testing (Fig. 72).
With the large number of dusts produced and handled in industrial operations
it was appropriate to classify them in accordance with their violence of explosion as
expressed by the Kst-value. Such classes are used in the design of constructive safety measures against dust explosions. The range of the Kst-values covered by each
class is defined in Table 9.
It must be made clear that a given dust explosion class is only an indication of
the expected course of a dust explosion. The classification gives no indication as to
how easily a given dust ignites. Relatively weak reacting dusts may ignite very easily, while violently reacting dusts may be very difficult to ignite with a condenser discharge as the ignition source. Therefore, the classification of a dust into a given
dust explosion class does not indicate or address the probability of an explosion occurring nor does it predict the consequences from such an explosion in industrial
practice.
78
~
0.0.0000 -00.0. {
c....
d
.IY"/'rA
.0
x
d
E
CL
0
120
Bromphenoxime
~
0:..
..8
L1
~;'
60
4'
D"
;1
Dyestuff
.,i.
olO'!,---1OO:h;--
.;(
1000
10000
ignition energy IE [J 1
>
0-200
201-300
>300
10,000 J)
The explosion characteristics of more than 500 dusts have been systematically
determined. Figure 87 shows the distribution or frequency per dust explosion class
or Kscvalue, respectively. The majority of the combustible dusts fall into the dust
explosion class St l.
Figure 88 shows the distribution of the maximum explosion pressure within the
three dust explosion classes for more than 500 dusts. Each ofthe three dust explosion classes has an optimum pressure range which occurs most frequently. This optimum pressure range increases at higher dust explosion classes.
79
wr---------.---------~--------_r---------
st 2
st 1
St 3
30
o~
>.
u
20
QJ
:::J
0QJ
t...
4-
o~--------~--------~--------~~------~
100 KSt
200 [bar.m/s 1
Fig. 87. Frequency of the dust explosion classes for more than 500 dusts
c,. St 3
516 dusts
60~--~~--~--~--~
o~
~
c
30
Q)
::::J
CT
Q)
t...
'<-
6-7
Pmax [barl
80
Table 10 summarizes the explosion characteristics and the dust explosion classes of some combustible dusts.
The values in Table 10 are for reference purposes only, because the configuration of the dust particles may influence the course of the explosion as explained earlier.
Additional explosion characteristics are listed in the original research paper
[61]. Their usefulness is limited due to two main factors: 1) the various test methods
used [1 m3-vessel (Fig. 57) versus modified Hartmann apparatus (Fig. 21)] and 2)
especially the effects of particle size (Fig. 74). For example, flour dust (corn) did
not ignite in the 1_m3 vessel due to its median particle size value of M = 550 p,m.
But the fine dust M :::;;63 p,m) ignited in the modified Hartmann apparatus as expected. Such a fine dust would, of course, also ignite in the 1-m3 vessel.
Type of dust
PVC
Milk powder
Polyethylene
Coal dust
Metallic soap
Chicory
Toner
Resin dust
Brown coal
Wood dusts
Cellulose
Organic peroxide
Bromphenoxime
Pigments
Musk (nitrated)
Red phosphorus
Aluminum
Pmax
[bar]
8.5
9.7
8.8
8.2
8.4
8.5
7.5
8.9
10.0
9.4
9.8
9.0
11.9
10.7
10.0
~ 6.0
12.5
98
130
131
135
140
157
166
174
176
208
229
273
342
344
360
~570
650
St1
4.3.2 Flock
81
4.3.2 Flock
4.3.2.1 Preliminary Remarks
Flock is a monofilament fiber having a range of deniers of 0.8 to 20 with lengths of
0.5-2.5-mm (Fig. 27).
In 1968, the VDE-ordinance 0147 was validated. In this ordinance the ignition
and explosion behaviors of coating powders and flock were treated equally. This
triggered systematical testing [62, 63].
The following statements are based on flock made of polyamide 66, polyamide
6, acrylics, nylon, polyesters, and cotton with deniers 0.5-6.0 and lengths of 0.51.5-mm. The flock was available in cut or ground form. Various preparations have
also been tested.
Due to the high bulk density of flock, it was necessary to use the large I-m 3 vessel for the explosion tests. The dispersion of the flock with the standard semi-annular nozzle (Fig. 57) was quite difficult because of plugging. Therefore, it was necessary to develop a special nozzle (Fig. 89) for proper dispersion. This is permissible
because the explosion characteristics of combustible dusts remained the same,
within the range of accuracy, as the ones obtained using the so-called semi-annular
nozzle (Fig. 90).
The test results indicate that the product of denier times length of cut (weight
of flock particle) determines the explosion behavior and not the type of flock. This
product has the same significance for flock as the median particle size M for combustible dusts.
Fig. 89. Special nozzle for the dispersion of flock into the large vessel (V = I-m 3)
82
L.
d
.D
OJ
D...
0'<)---,----,
200
200
Vl
L.
d
.D
.......
100
"D
"'D...
"D
0
0
:ill
1000
Fig. 90. Comparison of explosion indices obtained with different dust dispersions in the large vessel (V = I-m 3)
4.3.2 Flock
83
---en
o Cut flock
-
0"
..
special
b. Ground flock
OJ
J5
.iii
o
0..
x
OJ
t..
OJ
5,0
10
Table 11. Correlation of lower explosible limit (LEL) of flock with the product: denier
times cut length (E = 10,000 J)
1.11 denier x cut length in mm
0.54
3.30
4.90
6.70
8.50
15
30
60
125
250
800r---------.---------.---------,,--------~
Q"'"----0250
""""""'11---;)----0--0 125
I!:n___~==~t:::~~;;~~~~~~~~~~~6030
101
102
103
104 15
ignition energy IE [J 1
Fig. 92. Influence of ignition energy (IE) upon the lower explosible limit (LEL) of flock
84
10
t:'
t:I
..0
Sr-
t:I
c.
0
200
~
0
0
/:;,
Cut flock
Cut floc k special
Ground flock
c.:..
t:I
..0
......
Vl
'Kl
4.3.2 Flock
85
Table 12. Correlation of explosion indices with the product: denier times cut length
(E = 10,000 J)
1.11 denier x
cut length in mm
Pmax
[bar]
Kst
[bar m/s]
0.54
1.70
3.3
6.7
9.0
8.4
7.5
6.3
140
88
52
21
1000~----'--"'-----""
e
o
4-
cOJ
0~ mE
__
500
UOI
4-
VI
::J
-0
Vi
~ ~\:d 00~------I----~
5
10
.-
4-
-o...
Figure 95 shows the influence that the ignition energy has upon the explosion
pressure pex and the pressure rise dp/dt. The values are not identical with the maximum pressure and the maximum pressure rise because they were not determined
at optimum flock concentrations. The optimum explosion pressure is practically independent of the ignition energy. This is also true for the pressure rise if it is equal
or larger than 60 bar/so For less violently reacting flock, the pressure rise decreases
with decreasing ignition energy. Here again, the behavior is similar to that of combustible dusts (Figs. 85 und 86).
86
V=1m3;td =0.6/Q9s
1~r---.--.----r--~
60
1"0'---1""'"'01;;----'10'-:;2:---1J...
O. , - - - 11O 4
ignition energy IE [J I
87
[65].
An exception to the rule exists in mixing PVC with methane, where the correlation is hyperbolic. This effect is probably caused by the methane because the same
dust in a propane-air mixture follows the law of Le Chatelier. Methane has a lower
normal velocity of combustion than propane. At present, no generally valid correlation can be given. However, newer test results confirm Engler's statement of 1885
that the admixture of non-explosible dust and gas-air mixtures will form an explosible hybrid mixture.
--
01
..0
til
a.
~
L
OJ
~
Fig. 96. Lower explosible limit of hybrid mixtures consisting of combustible dusts and propane
1.5
88
Cellulose I C3 He
Cornstarch IC 2 H60
'" PVC ICH 4
6.
+
c
a
:.;::
......
c
1.0 0 . . - - - - - - , - - - - - - ,
ClJ
c
a
......
III
~
-0
-0
ClJ
N
0.5
~
d
-0
EIII
OL-______~____~~
05
10
Furthermore, dusts which, for instance, will not ignite due to the particle size,
even with a potent ignition source, will probably become explosible in an admixture of flammable gas or vapor.
In hybrid mixtures with a given dust concentration which is below the LEL, the
required amount of flammable gas or vapor to reach an explosible mixture becomes smaller the lower the explosible limit.
89
'--
.L)
o.aJ
Vl
---
500~/_~
400 I
~
6'----
'-d
..0
300,/
+-
200}/
-0
---
100~
0.
-0
o ~.
o
Fig. 98. Influence of the propane concentration in air upon the pressure rise of cellulose
(V= I-m 3 ; E = 1O,000J)
II
.~I
125
250
375
dust concentration [g
500
1m 3 ]
'-d
.L)
0.
,,+ -"",~~
500
Vl
---E
L.
d
.L)
+Vl
Fig. 99. Influence of the propane concentration in air upon the explosion
indices of combustible dusts
(V = I-m3 ; E = 10,000 J)
3006~
y.
./ ~
I/
.,
200t
.'"
0"'
'<8~
.:,,:.
100'"
oLo~
0
90
law). The mixing of a flammable gas with a dust has a lesser influence if the dust by
itself reacts more violently (optical brightener). However, the influence is more
pronounced with a weak reacting dust such as pea meal.
These findings are not only valid for large equipment but also for laboratory apparatus [63].
In designing protective measures against the outcome of dust explosions, one
has to consider that the presence of flammable gases and vapors may classify the
fuel into a higher dust explosion class (Table 13).
The change to the next higher dust explosion class is imminent once the LEL of
the flammable gas or vapor in air is reached; and is complete, once this limit is exceeded.
All dusts are categorized in the highest class once the concentration increases
to, for example, the optimum concentration.
How do the explosion indices of cellulose change if, for example, butane or methane is added to the combustion air instead of propane? In order to make the corresponding comparison, the optimum concentrations for the explosion indices
have been standardized as shown in Fig. 100. Again, it can be shown that the Ksc
value is only marginally influenced with a linear dependency upon the flammable
gas concentration, which in turn is partially influenced by the type of admixed gas.
Propane and butane cause a much more pronounced increase in the explosion indices of cellulose than methane. The reason is that in a turbulent stage, propane and
butane react more violently (Pmax = 9.6 bar, ~ = 460 bar rn/s) than methane (Pmax
= 9.0 bar, ~ = 313 barrn/s).
In summarizing, it can be stated that the optimum value for the maximum explosion pressure of hybrid mixtures consisting of combustible dust and flammable
gases will occur slightly above the LEL. The maximum Kscvalue of hybrid mixtures, however, occurs at the optimum concentration of the flammable gas addition.
The Kst-values coincide in general with the ~-values of the flammable gas if
brought to an explosion out of a turbulent state. But they can also be up to 15 %
higher.
Table 13. Influence of propane content upon the dust classification into dust explosion
classes
Pea meal
Cellulose
110
220
b)
1. 25 a )
2.5
4.25 b )
(St l/St2)
(St 21St 3)
(St 21St 3)
St3
St3
St3
St3
St3
St3
~--.i5~-~~
10
..
c::
d
9 +-
.0
-~
'"
______
"',
Propane
[] Bulone
D-
8~
",
91
\11
Methane
________
______
~O.-----.---,-----~~~~-----.
400
~
E 300
L.
d
.0
.....
VJ
200
OJ
:n
_Cl
100
O~
Fig. 100. Influence of the type of flammable gas addition upon the explosion
indices of cellulose
-lE
wCl
-l-==
__
__
0.29
________
to
OS
______
1S
Figure 101 shows the behavior of the optimum dust concentration for maximum
explosion pressure and Kscvalue at various flammable gas admixtures for hybrid
mixtures with cellulose.
Again, the previously shown standard presentation was used for the flammable
gas concentration. In general, the optimum concentration for the maximum explosion pressure decreases linearly with increased flammable gas concentration. For
the Kscvalue, this occurs only after the LEL of the added flammable gas has been
markedly exceeded.
optimum concentration of
flammable gases
--
mE 500
01
c
o
:;::::
E!
4-
~
c
o
u
::J
.
4-
D-
400
300
-"0
\",
~o
200 r-
\Kst
Pm~o
100 I-
o
o
0.5
Ll.
\
\&
"-to
"0
1.5
92
4.3.4 Conclusions
Combustible dusts, as well as flammable gases, are only capable of exploding
within a limited range, which is given by the lower explosible limit (LEL) and the
upper explosible limit (UEL).
The LEL is of special importance for industrial practice because it determines
whether dust explosions have to be anticipated once effective ignition sources are
present. Then, constructive protective measures have to be selected. The LEL is
only marginally affected by the applied ignition energy, but it is considerably dependent upon the process temperature. The maximum explosion pressure Pmax and
the maximum pressure rise dp/dt describe the violence with which dust explosions
can occur. The maximum explosion pressure in closed, almost-spherical vessels of
sufficient size (V~20-1) is independent of the volume. The maximum pressure rise,
however, is volume-dependent. It decreases with increased volume in accordance
with the cubic law. The Kscvalue which results from this law is specific for the dust
and the test method but is independent of the vessel size for volumes V~20-1. Both
explosion indices are mainly influenced by the particle size and are only representative for the dust if the median particle size M :::; 63 p,m and the sample is tested in
a dry state. Other parameters include product moisture, initial pressure, and temperature. The determination of the above-mentioned explosion indices has to be in
accordance with a given test procedure because of the additional dependency upon
the turbulence of the dust/air mixture at the time of ignition. Basically, such statements are also valid for flock as a combustible product. In such a case, the product
of denier times length of cut, to measure the weight of the flock particle, will take
the place of the usual median particle size M.
Special consideration has to be given to reactions of dust/air mixtures which occur in the presence of gas or vapor/air mixtures. With such hybrid mixtures, it has
to be kept in mind that:
a) non-explosible dust and non-explosible gas or vapor/air mixtures can create explosible hybrid mixtures.
b) the maximum explosion pressure of combustible dusts will increase with admixture of flammable gases.
b) the Kst-value of combustible dusts will increase drastically and reach a Kscvalue at optimum concentration which is equivalent to the one obtained when
igniting under turbulent conditions. Therefore, a higher dust explosion class
will result.
93
94
95
~'
K1
I-----<Je.,....-nni~
L2
L3
main electrodes, the ohmic resistance drops, and the charged capacitor C can discharge. The energy of the auxiliary spark is so small that the error in the energy
statement for the main spark is negligible. The activation of the main spark is
synchronous with the formation of the dust cloud which has to be ignited.
The potential energy E of the charged capacitor at the high voltage U and
capacitance Cis:
E
1I2CU2
The charging and discharging process also charges additional capacitors which are
provided by the cables, connectors for the electrodes, and the arrangement of
the electrodes. They may affect the accuracy of the energy statement made above.
In [60] it is documented that even for small stored energies (::; 10 mJ) such an influence is negligible, and within the range of accuracy, provided the additional capacitance of the electrode arrangement is less than 200 pF.
96
97
~ '{~
5
10
~ 104
>.
f103 ./
l"
1
J~
c 10
'E
Fig. lOS. Correlation of minimum
ignition energy MIE with dust concentration (Lycopodium, 20-llaboratoryapparatus)
m~
'"
e.""'-..!d~
Ji:I=100ms
_~-1~~______~1~___"__
' - -~~
-___
.A.__
~~
o
500
1000
1500
.....,
g 1~.-------.-------.-----~
Fat coal
o
Pea flour
t;.Cellulose
o Lycopodium
o Light
agent
0 "0
Protectio~ "'
t;.,n
~~
+-
lfi
CD
.9 100
50
100
150
[msl
the explosion indices (td = 60 ms), that is, at a lower turbulence of the dust/air mixture. Therefore, an ignition delay time td = 120 ms is used in the laboratory apparatus for the determination of the energy boundary value.
In case a large vessel V = I-m3 is used for the determination ofthe LMIE, a similar correlation appears (Fig. 107), whereby the size of the dust container will
98
10
10 l - container
E 103
Z
'\
\JO
102
w
5.4-l-container
::E:
.-J
101
1)0
......
turbulence
high
medium
OS
td
low
1.0
[s]
1.5
have an additional influence (compare Fig. 62). For the 5.4-1 container size, an ignition delay time td= 1.2 s is to be selected for the determination ofthe energy boundary value. For the 10-1 size such a value is td= 1.5 s. Here again, the ignition delay
times are distinct from the ones which have to be used for the determination of the
explosion indices (td= 0.6 s versus td= 0.9 s)
In comparing the values of the minimum ignition energies gained in the 20-1 laboratory apparatus and the I_m 3 vessel, using the prescribed test procedure, there
is no difference within the range of accuracy (Fig. 8). Glarner [60, 63] has proven
that the materials of construction for the electrodes (tungsten, stainless steel,
brass, aluminium, lead) do not noticeably influence the ignition behavior of combustible dust; this, however, is not true for the distance of the main gap and the existence or non-existence of an inductance in the discharge circuit.
10 5. - - - - - - - - - - - - - - - Q
condenser discharge
low turbulence
-,
1041 - - - - - - - - - - - ,
1031--------~
(JJ
.::
0..
VI
I
=
N
1021 - - - - -
..
w
::E:
.-J
3
LMIE: 1m-vessel [mJ]
99
10 6
I
I
,
I
10 5
Melamine
104
-.,
E
w
L
103
I
102
....J
101
I
I
~o:
I
.~
100
0
l$Qp-odium
5 6
With an increasing length of the main spark gap the value of the LMIE for combustible dust decreases (Fig. 109). Very short sparks which are generated with a discharge circuit without inductance (Fig. 110) are generally markedly less ignition-effective than the time-extended sparks which have an inductance in the discharge
circuit. However, an inductance within the range of L = 1.32 - 46.4 mH does not
exert a supplementary influence upon the ignition behavior of the dusts.
The LMIE measured with a plain capacitor discharge is ten times greater than
the one obtained with the extended capacitor discharge in accordance with the test
procedure [65]. Such a fact is of great importance in practice for the evaluation of
the danger of, e. g., electrostatic ignition sources. The latter are pure spark discharges and their energies cannot simply be compared with the minimum ignition
energy generated as per procedure. However, recent findings indicate that there
are dusts, e.g., sulfur, which have a LMIE which is independent of the existence of
an inductance in the discharge circuit. Therefore, the lowest results for the LMIE
are only obtained with the following parameters for the electrode arrangement:
-
100
106
usual inductance
....v
11
I
10 5
Melamine
I
I
10 4 ~
I
I
-..
10 3
UJ
---l
10 2
I
~A
Pea flour
I
I
I
101
I
Lycopodium
10 0 I
25
50
inductance L I mH]
Figures 111 and 112 show statistically the influence of the number of tests per
energy upon the ignition probability for two differently ignitable, combustible
dusts, at the most ignitable concentration. Both ranges are practically independent
of the number of tests per energy provided it is ;:::: 10.
That the 100% ignition probability is reached at a low ignition level with only
five and not with more tests can be explained by the higher likelihood of a non-ignition in a longer test run.
o~
100r--------.--::A-----,
j"
0...
'c
.!2l
'5
50 -
.J
e0.
0
A
~.~
"
tests/energ~
10 ..
020"
"bJ
>.
........
.J
'0
c
.2
........
040 ..
100
101
t!
0-
c
0
:
c
.QI
.....0
SO
020 "
m40 "
>......
..c
d
..c
ec..
5 tests /energy
10 "
O .
101
102
ignition energy IE [mJ)
103
Furthermore, the determination of the LMIE for the easily ignitable cellulose
(LMIE = 10 mJ) requires only five tests per energy level whereas the hard-to-ignite
flour (LMIE = 100 mJ) requires at least 10 tests per energy level. An increase in the
number of tests will in both cases not lower the energy level. As was already shown,
the number of necessary tests increases with decreasing ease of ignition. It is, therefore realistic to test in accordance with the test procedure [66] for the LMIE with
twenty tests per energy level at the readily ignitable concentration, especially for
hard-to-ignite dusts.
Figure 113 indicates that the range of transition for the statistical probability is
influenced by the ease of ignition of combustible dusts. The range expands with increasing energy and can be one thousand-fold for hard-to-ignite dusts (LMIE
~100 J). This again explains why the stated high test energy (E = 10,000 J) has to
be used for testing the explosibility of combustible dusts. Figure 114 shows the frequency of the LMIE obtained in testing approximately 200 dusts which is mostly in
.2
+c
.Q1
50
102
Fig. 113. Influence of the lowest minimum ignition energy upon the ignition probability
1d+
102
o~
C;' 25
QJ
:::J
0QJ
'-
4-
LMIE [mJ 1
Fig. 114. Frequency of the lowest minimum ignition energy for approximately 200 tested
dusts
the range of LMIE= 10 mJ. The frequency decreases with increased energy and
then again increases. The latter seems to be true for mixtures of easy- and hard-toignite dusts and for mixtures of organic and inorganic dusts, based on current
knowledge.
In Table 14, the explosion indices of some randomly selected fine dusts are compared with the lowest minimum ignition energy (LMIE).
Apparently there is no correlation between the maximum explosion pressure
Pmax or the Kscvalue, on one hand, and the LMIE, on the other hand. There are
dusts which, after the explosion is initiated, react weakly and which may have
either a low energy boundary value (dicarbonic acid) or a relatively high energy
boundary value (melamine polymer). This is also true for very violently reacting
dusts. Bromphenoxime is very hard to ignite; hydroxyazobenzene, however, is
very easy to explode with an extended capacitor discharge. Figure 114 and Table 14
show that the LMIE values of combustible dusts cover a wide range.
Table 14. Comparison of explosion indices with the lowest minimum ignition energy of
fine dusts
Dust type
Dicarbonic acid
Melamine polymer
Bromphenoxime
Hydroxy-azo-benzene
Aluminum
M
[f.Lm]
Pmax
44
10
50
4.4
7.7
10.5
<10
<20
9.4
11.4
[bar]
K st
[bar m/s]
LMlE
[ml]
24
35
10
100.103
229
305
624
250.103
<1
<1
103
Some dusts can only be made to explode with high energies (E :::::10,000 J)
others with lower levels (E = 10 mJ) or very low energies (E < 1 mJ). The latter are
as readily ignitable as the flammable gases: methane, butane, propylene, or propane. Such a statement is contrary to earlier findings [67, 68]. According to these
findings, the required energy to ignite dust/air mixtures should be one hundred to
one thousand times higher than the ones needed to ignite normally ignitable flammable gases.
The prevention of ignition sources as the sole safety measure for equipment
which processes and conveys especially easily ignitable dust should only be adopted with expert judgement in justifiable, exceptional cases [23].
The question can now be raised concerning which additional parameters influence the LMIE of combustible dusts [60]. Figure 115 shows the correlation between initial pressure Pi and the LMIE for an easily ignitable (Lycopodium), normally ignitable (pea flour), and hard-to-ignite dust (melamine polymer). In the
range of 1-1.6 bar (abs) for the initial pressure, there is no noticeable influence.
For negative pressures [Pi <1 bar (abs)], however, the readiness for dusts to ignite
decreases. This is understandable because the most readily ignitable dust concentration decreases with decreased initial pressure which, in turn, may call for an increase in the energy boundary value. For the melamine polymer, such an influence
was not observed for the pressure range tested, but one can assume that the LMIE
will increase with an additional lowering of the initial pressure [Pi <0.6 bar (abs)].
If normal fluctuations occur around standard pressure in installations handling
combustible dusts, a change in the ignition behavior need not be considered for the
safety evaluation.
10 6
Melamine
10 5 1-
10 4 -
1)3,
-,
~eQfIOUrL
10 2 f--
w
L
-1
10 1 f--
Lycopodium
10
I'
p.
[bur,ubs]
104
1041-_ _ _ _ _ _ _ _ _-1
Polyethylen
1031 - - - - - - - - + - - - - _ 1
-.
E
25
50
100
250
500
1000
A critical inspection of the test results published in the literature [67] makes
evident that often the median particle size or the particle distribution is not reported. Therefore, the impression is created that such a parameter has no noticeable
influence upon the LMIE of combustible dusts. But this is not the case (Fig. 116):
the finer the dust, the easier it can be ignited with an extended capacitor discharge.
For polyethylene and aluminum the readiness for ignition changes with the third
power of the median particle size. This is not the case for the optical brightener
which had its energy boundary values determined with pyrotechnic ignitors of gradated energy levels. Such a type of ignition has a different effectiveness than the
extended capacitor discharge. In order to characterize the ignition behavior of a
combustible dust, it is therefore necessary to test its fine fraction.
Systematic tests pertaining to the ignition behavior of pure coating powders
[69] with an organic content of 99 % have shown that they have to be considered
relatively easily ignitable if they are present as a fine dust, Fig. 117. Extruded, fine
coating powders with an organic content down to 60% are similarly ignitable. The
addition of aluminum decreases the LMIE (Fig. 118). Exploratory tests with epoxy
powders have shown that the energy boundary value may be ten times larger
(LMIE > 10 mJ) if a pure capacitor discharge is used.
Zeeuwen and van Laar [70] researched the influence of the water content of
dusts upon the LMIE. They found that the effect of water is much more pronounced (Fig. 119) than that of the median particle size (Fig. 116). Therefore, the
ignition behavior of combustible dusts has to be tested in the dry state.
105
oA
10
Polyester resin
V= 20(,td =120ms
101
~~
~~
--.
E
w
L:
with
6% Aluminum
100
....
Of::,.
without Aluminum
101
0
1000
2000
106
,' /
I~
-.,.~ /
~.
..,
E
lLJ
....J
rl-~"
V "
(orn
Rour
'K)1r
'" Tapioca
~O~__~I__*I__~I~~.
10
15
20
Another parameter which has a major influence upon the ignition behavior of
combustible dusts is the temperature. Glarner [60] observed that the LMIE for
hard-to-ignite dusts (melamine) decreases much more rapidly with increased temperature (Fig. 120) than for easily ignitable dusts (Lycopodium). He noticed that
the straight lines in a double logarithmic plot intersect at one point having the coordinates [lOOOC; 0.088 mJ]. The boundary energy level referenced to a temperature T= 1000C coincides with LMIE = 0.088 mJ for all tested dusts. From today's
view point, the mechanism of a dust explosion can roughly be explained as the combustion of the volatile components at the particle surface (see sec. 2.2.). Glarner's
interpretation therefore suggests that the smoldering gases driven-off have a similar ignition behavior towards an extended capacitor discharge. This is parallel to
the ignition behavior of the homologous flammable gases of the alkanes, which
also have a similar lowest minimum ignition energy (LMIE = 0.24-0.31 mJ).
It also must be mentioned that the assumption for the calculation of the LEL of
combustible dusts [53] is as follows: a complete flame propagation through the
entire explosion volume is only possible if the energy liberated through the reaction is capable of heating the products of the reaction, the excess air and all other
ballast to approximately 1000C. This again is an interesting parallel to the common intersection of the minimum ignition energy at a temperature of 1000C.
A substantially erroneous estimate is possible if the MIE values determined at
room temperature are used for the assessment of the dangers of electrostatic ignition sources for installations which process and handle combustible dusts at elevated temperatures. On one hand, the importance of the MIE of combustible dust
for safety evaluations is undisputed; on the other hand, its determination requires
a large test effort which will increase further if temperatures higher than room temperature are studied. Therefore, it became necessary to study whether a statement
about the range of the energy boundary was possible from, e. g., the determination
of the normal explosion indices. Such a path was indeed found [7, 60, 63]. Every
107
106 r - - - - - - , - - - - - - - - - ,
o Melamine
t::,.
10 5
Sewage sludge
Pea flour
Herbicide
o Lycopodium
104
103
.......
E
LU
10 2
101
....J
100
10.1
10
10
temperature T [OC)
test for the determination of the explosion indices of a combustible dust which is
done with two pyrotechnic ignitors having a total energy of E = 10,000 J renders
automatically the time intervals for the duration of combustion t1 and induction t2.
The definitions of these parameters are shown in Fig. 121 and are as follows:
t1 - the duration of combustion - is the time interval between ignition and the attainment of the maximum explosion pressure.
t2 - induction time - is the time interval between ignition and the intersection of the
tangent at the point of inflection of the pressure curve with the abscissa through
the initial pressure.
The time indices which are defined above are principally valid for any dust concentration. The following statements refer to the minimum values which are obtained during the normal testing for the dust explosion indices.
For more than fifty dusts which have been tested in the 1-m3 vessel and the 20-1
laboratory apparatus, the following unequivocal correlation has been shown:
The LMIE and the shortest induction time or the minimum combustion time
can be correlated (Fig. 122) when plotted on a double logarithmic scale. The times
have to be derived from tests using the usual IE of 10,000 J.
A dust can be classified as very easily ignitable (LMIE < 10 mJ) if the minimum
times indicated in Fig. 122 are less than 50 ms for the normal test results gained in
108
c::
Ll
J5
OJ
':::J
Vl
Vl
OJ
'-
CL
C
0
'Vi
0
D..
induction time t2
OJ
2S
50
75
100
125
time t [msl
104
10 4
1m3-vessel
td = 0,65
103
10 3
.,
.,
E
~ 101
llJ
101
-l
-l
I
I
t2 mi = minimum
, n induction
time
1cfl
t ,= minimum
1,mm duration of
combustion
-1
'
10 11;,-0--"J:25:---:5~0-~10"""0--:2'*'50:---:500
t2,min [msl
t 1,min
[msl
Fig. 122. Correlation of the lowest minimum ignition energy with the time indices tl,min and
tZ.min for combustible dusts
the 20-1 or I_m3 test apparatus using the given test procedure. A similar correlation
exists for the LMIE [60, 63] at a longer ignition delay time (td = 120 ms).
The correlation shown in Fig. 122 is also valid at varying initial pressures, at differing oxygen/nitrogen concentrations in the air of combustion and at changing
temperatures.
109
In order to circumvent the determination of the time indices at elevated temperatures, it is easier to reproduce the temperature dependence of the LMIE of the
dust in accordance with Fig. 120 by drawing a straight line through the coordinates
[25 DC; LMIE] and [1000 DC; 0.088 mJ]. This is a fast and easy method for the determination of the range of the LMIE of dusts. But it is only valid if the explosion indices are independent of the applied ignition energy within the range of accuracy
(Fig. 85). If this is not the case, then the energy boundary value can be estimated
from the linear behavior of the Kscvalue with the ignition energy (Fig. 86).
10 3
<jl
-.
lLJ
:L
10 2
medium
turbulence
10 1
10 0
10-1
10-2
0
500
1000
110
-,
10 3
LLJ
-1
>D1
10 2
,I
'-
QJ
QJ
c
0
10 1
4-
E
E
10 0
::J
'c
'E
4-
til
QJ
3:
.s
5.0
fineness
10
Table 15. Correlation of lowest minimum ignition energy LMIE of flock with the product
denier times cut length
1.11 denier x
cut length in mm
LMIE
0.49
0.020
0.200
4.000
1.53
2.97
6.03
[J]
>100
Very extensive testing with flock allows a statement with regard to the influence
of ignition energy upon the statistical transition of the ignition probability
(Fig.125). Analogous to combustible dusts (Fig. 114), the range of transition increases with increased LMIE. For a flock with a high value of the product denier
times cut length a very potent ignition source is required in order to recognize instantly its explosibility. In performing the normal explosion tests in, e. g., the l_m 3
vessel, the time indices are obtained automatically (see Fig.121 for the definition).
Therefore, a linear correlation exists on a double logarithmic plot for the LMIE
versus the minimum induction time t2,min' This allows an estimate of the energy
boundary value in an easy fashion, similar to combustible dusts (Fig.126).
111
.0
L.
D..
~~----~--~A~------~~---------J OLMIE
100
10 2
10 4
Fig. 126. Correlation of lowest minimum ignition energy (LMIE) of flock with minimum induction time tZ,min (l-m 3 vessel, low turbulence)
10-21:-----~----~~~--~
50
Flock machines may generate pure capacitor discharges generally not exceeding 500 mJ. Therefore, it was of interest to know the LMIE of flock without inductance in the discharge circuit. The results of such tests are shown in Fig. 127.
The LMIE of a fine easily ignitable flock increases approximately one hundredfold, which is slightly higher than anticipated from the dust results (Fig. 110). If
such a result is confirmed through additional tests, then no concentration limitation will be needed (see sect. 4.3.2.2) in flock machines which have the above-mentioned limited energy for spark discharges.
112
10 1 , - - - - - - - - - - r - - - - - ,
3.84
--
~D
._._-
without inductance
0.02
10-2 L.-_ _ _---'-_ _ _ _- '
o
500
1000
o Dyestuff M= 20).lm
OJ
106
-,
LW
--l
>-
2'
OJ
OJ
c
0
->C
.Q1
E
::J
E
c
'E
......
113
"'
..... Ho27",
FlJ!tfeneM=
125).lm
PVC
M= 20).lm
PVC
M=125).lm
- - - Propane without dus t
8
co
\
'tA \"
105
OJ
104
10
C'J
aJ
J5
d
"
.Q
d'-
~-+-
" "
llf~\\
.S!1 ~
101
ti
o
Vl
OJ
"'6 \
e
>."
~ 8
d OJ
OJ "
R
0
5.
3:
10-1
~0--~--2---3~~4--"5--~
conclusion is reached that not so potent sparks (E <LMIE) which normally are incapable of igniting pure dust/air mixtures will ignite hybrid mixtures.
But not only is the ignition capability of dust increased with the addition of
flammable gas, conversely the ease of ignition of certain propane/air mixtures can
also be enhanced by the admixture of easily ignitable dust, as shown in Fig. 128. An
energy of E = 100 J is required to ignite a propane/air mixture slightly above the
LEL. However, in the presence of a dyestuff with a very low ignition energy, this
minimum energy level decreases to E = 10 mJ. The question pertaining to the
fignition behavior of hybrid mixtures in the presence of propane or similarly ignitable flammable gases or vapors can be answered as follows:
- In processing normal or hard-to-ignite dusts (LMIE 2: 100 mJ), the flammable
gas content may reach the LEL without resulting in a lowest minimum ignition
level for the hybrid mixture, which is equivalent to the energy of a brush discharge.
- In processing easily ignitable dusts (LMIE :::;10 mJ), the minute addition of
flammable gas (solvent vapor) will intensify the danger potential. Although not
experimentally proven, the ignition of such hybrid mixtures by brush discharge
is conceivable.
114
- The two ranges described above for the minimum ignition energy of combustible dusts cannot be unequivocally separated from the ignition behavior of their
hybrid mixtures. Additional safety considerations are required relative to the
ignition capability of brush discharges.
If the content of flammable gas or vapor, however, exceeds the LEL, then an
easy ignition which is within the ignition capability of brush discharges can basically be expected.
4.4.1.6 Conclusions
The lowest minimum ignition energy (LMIE) and the minimum ignition energy
(MIE) , respectively, represent a quantity which allows a comparison of the ignition
behavior of combustible dusts towards an extended capacitor discharge, as defined
[65]. Contrary to earlier assumptions, newer investigations have shown that a substantial number of dusts are relatively easy to ignite. Some very easily ignitable
dusts are as ignitable as normally ignitable flammable gases, e. g., methane, propylene, propane (Fig. 129).
The LMIE of combustible dusts is, within the range of standard pressure, practically independent of the initial pressure (starting pressure of the explosion). But
it is very dependent upon the median particle size, the temperature of the mixture,
105
Methylene
104 chloride
.......
E
w
~
10 3
Sewage treatment
sludge
Ammonia
-l
>.
D"I
<-
10 2
101
Corn starch
Cellulose
100
Lycopodium
Epoxy resin
OJ
C
OJ
.Q
-<-
.Q1
E
:::J
E
Propane
'E 10.1
Aluminum
Hydroxyazo benzene
-<-
II)
Acetylene
OJ
3:
10-2
10-3
115
and the moisture content of the product. The range of the boundary energy can be
estimated with sufficient accuracy from the minimum combustion time and minimum induction time, which routinely result from the normal dust explosion tests.
The values for the LMIE are based on extended capacitor discharges. These are
generally much more ignition-efficient than pure capacitor discharges. A conversion to practical conditions is only possible if there the capacitors also discharge
with an inductance present. But this is normally not the case. The capability of
brush discharges to ignite flammable gas/air mixtures has been confirmed [73].
Tests have shown that they have the same ignition effectiveness as extended capacitor discharges with a maximum energy of 5 mJ. However, up to now it has been impossible to ignite easily ignitable dusts (LMIE < 10 mJ) by a brush discharge which
supposedly is due to the lack of induction. Therefore, it can be expected that brush
discharges will only ignite dust/air mixtures which have a LMIE substantially below 1 mJ. The investigations are not yet concluded.
The above statements are basically also valid for the corresponding boundary
energy of flock as a fuel. In such a case, the product denier times cut length has to
be taken as the reference instead of the median particle size M which is customary
for dusts. Here again, the values for the LMIE cannot be transferred to industrial
practice because only pure capacitor discharges occur in flock machines. An estimate of the range of ignition energy is also possible from the times which are generated in the standard explosion tests.
The LMIE of dusts in hybrid mixtures is lowered differently, depending upon
the admixture of flammable gases or vapors. This is deemed most dangerous for already easily ignitable dusts. The ignition behavior of hybrid mixtures can be described as a straight line in a semi-logarithmic plot which connects the LMIE of the
dust with the one for the flammable gas at its most easily ignitable concentration.
116
heatin (1500)
oven
fla
test chamber
deflecting
surface
air inlet i e
rubber bulb
c::
.;:
::J
g)
OJ
r;1-+-+-+~
"2
c::
II
LL
II
~
117
118
f-
o Dyestuff B
Pea flour
e
:::J
QJ
Cl.
!D ~ 1200
...... u
QJo
'-
'3
t:Jl
LMIE = 1mJ
.'."""
"~"" ........_-...
............-
LMIE=100 mJ
The coil is made out of Kanthal A-I (22 Cr, 5.5 AI) with a wire diameter of 1.2
mm which corresponds to an area of 1.13-mm2 The straightened wire measures 470
mm and has a resistance of 0.6 nat 20e. The coil has ten turns with a diameter of
13.5 mm and is electrically heated. Glarner [60] has documented with systematic
tests that there is no correlation of coil temperature with the LMIE of dusts
(Fig. 133). For example, dyestuff B (LMIE = 1 mJ) which is very easily ignitable
with an electric spark, requires a coil temperature of around IOOOC for the ignition
of its mixtures. Pea flour (LMIE =100 mJ), however, which is much harder to
ignite, can be made to explode over a wide range of concentrations with a coil temperature T Ol = 700e.
Glarner, however, found a unequivocal linear correlation between the glowing
coil temperature which was necessary to ignite dust/air mixtures and the ignition
temperature in the BAM-oven. He states absolutely that at the prescribed glowing
coil temperature ofTol = 1200C, only such dusts will be recognized as explosible
which have an ignition temperatureT BAM :::; 540 0e. As some combustible dusts may
also have a higher ignition temperature, a misjudgement of the dust explosibility is
quite possible when the glowing coil is used as a test tool.
4.4.2.4 Conclusions
The ignition temperature of a combustible dust is an important characteristic. It
not only describes the ignition behavior of mixtures on hot surfaces but also indicates, together with the LMIE, whether mechanically generated sparks will be capable of igniting dust/air mixtures. More on this issue will be discussed in a later paragraph.
119
In addition, it has been documented, that no correlation exists between ignition behavior of dust/air mixtures with extended capacitor discharges and the temperature of the glowing coil which is required for the ignition of the mixtures. The
effectiveness of the two sources cannot be compared as the ignition source is in one
case an electrical discharge and in the other a "hot surface".
In this case, the flame travels first into the pipe which is filled with the gas mixture
and the whole mixture burns in the pipe. The normal combustion velocity will not
exceed a few cmls or mis, depending upon the type of flammable gas, because the
products of combustion can flow away. With continuing combustion, however, the
gas mixture contained in the pipe will be excited to its natural frequency, and the
gas motion will not be laminar but turbulent. Therefore, the normal combustion
velocity will increase. The flame front is no longer planar but concave, and the combustion area larger than the pipe section. With such test conditions, the normal
combustion velocity is slightly increased by the quotient combustion area over pipe
section.
2. Ignition of the explosive mixture at the closed end of the otherwise open pipe.
In this case the combustion velocity is substantially larger than with the ignition at
the open end. Due to the major volume increase while burning, a so-called "displacement velocity" will affect the unburnt mixture ahead of the flame front, which
will not only increase the turbulence but also the combustion area. Only a small
portion of the gas mixture burns in the pipe. The rest is pushed through the open
end and gets ignited outside the pipe by the trailing flame.
A third case exists for the combustion of gas/air mixtures with ignition at the
closed end of a completely closed pipe.
During the first phase of combustion, i. e., initially after ignition, the normal
combustion velocity is again influenced by the already-mentioned displacement
velocity with the consequent increase in turbulence relative to the ratio combustion surface/pipe section. This combustion velocity is therefore relatively high. In
the last phase of combustion, the displacement velocity, and, therefore, the turbulence, both decrease towards the closed pipe end, finally approaching zero, which
means that the combustion velocity is also decreased. But this is only the case for
relatively slow combustion reactions of, for instance, methane or propane. For the
120
30
""2
d
..0
X
~
OJ
'-
Z)
:::J
III
III
OJ
'-
CL
c:
0
10
'Vi
0
D..
x
D--------~O-=U~~----D
OJ
1000.--------r------~r-------,
....>'w
o
Q)
>
500
OJ~
E~
.9E
'<--
~m3Corn starch
_+3%C 3 H
o ~~500g/rrf
MLI.~
Corn starch
~:::;;.--D
10
20
30
Fig. 134. Explosion characteristics of combustible dusts in a pipeline closed at one end (DN
= 400-mm, lp = 30-m; ignition: closed end) corn starch: pmax = 9.7 bar, Kst = 210 bar.m/s,
corn starch/propane: Pmax = 9.5 bar, K st = 412 bar.rnIs, aluminum: pmax = 11.4 bar, Kst = 625
bar.rnIs
121
flame velocity Vex increases with increased length travelled. Figure 134 depicts such
a behavior for two dusts and the hybrid mixture corn starch and propane in a pipeline having a 400-mm diameter. The velocity increase becomes larger as the dustspecific characteristic Ks! of the fuel increases. This trend is also true for the explosion pressure Pex (except for corn starch).
If the testing is carried out over a wide range of concentrations, then there is a
linear correlation between the maximum flame velocity Vmax and the maximum explosion pressure pmax in the pipeline, as shown in Fig. 135.
If the dust explosion occurs in a pipeline with a large diameter, the secondary
explosion of the displaced unburnt mixture will be especially violent at the given
ignition location (Fig. 136).
50
IJ Corn stnrch
"'''
" + 3 vol
o Aluminum
c::::-
% Propane
'"
..D
25
Cl..
00
1500
V max
[m/s
Fig. 135. Optimum explosion characteristics of combustible dusts in a pipeline closed at one
end (DN = 400-mm, lp = 30-m, ignition: closed end)
Fig. 136. Flame propagation of a dust explosion in the vicinity of the opening of a pipeline
(DN = l600-mm, lp = lO-m, ignition: closed end)
122
For dust explosions in pipelines closed at both ends, the displacement velocity
and turbulence have the same influence as described for flammable gases
(Fig. 137). Corn starch explosions will not even reach the pipe end opposite the
ignition source. Hybrid reactions, however, result in a constant terminal flame velocity. The flame velocity of the very violently reacting aluminum dust increases
with increased distance, although the maximum value reached is markedly lower
than the one for the pipe closed only at one end (see Fig. 134).
At first, the explosion pressure pex is independent of the point of measurement
and is only influenced by the dust-specific characteristic K st .Very high pressure values are registered in the area of the end flange opposite the ignition source. This is
caused by the explosion flame running into the pre-compressed dust/air mixture.
Pressures and dust-specific characteristics correlate linearly. The reaction of dust/
air mixtures in pipelines is especially violent if they are ignited by a flame jet which
has originated from a dust explosion in an upstream explosion vessel. In such a
case, the mixtures are not only dispersed but also in motion.
Figure 138 may serve as a guideline. It shows the correlation of the maximum
explosion pressure Pmax and the maximum flame velocity V max with the dust-specific
characteristic K st for flame jet ignition in a pipe having a nominal diameter of 400
mm and varying lengths.
It may be noted that the pipe length has a decisive influence upon the explosion. For lengths in the range of 20 to 40-m, explosions of combustible dusts with
the dust-specific characteristic K st >200 bar.mfs (wood flour, pigment, aluminum
150
125
t:
250g/m3Aluminum
Cl
~ 100
~ 50
Cl..
25
0
L!.
0-
1000
Vex: sect ionally
averaged
5001-
10
20
23
length of pipe lp [m I
Fig. 137. Explosion characteristics of combustible dusts in a pipe line closed at both ends.
(DN = 400-mm, lp = 23-m; Ignition at one
pipe end, for characteristics see Fig. 134)
123
25
20
'd
.0
dI-~I
15
Cl.
.I
10
5
0
2000
--
w~'\\)~
./
.1,,,."-
-'
~,
Vl
x
d
E
>
1000
KSt [barm/s)
dust) may convert into detonations with velocities in the range of2,OOO m/s. The resulting pressures are equivalent to the ones from gas detonations. A detonation of
combustible dust is defined as a combustion process which maintains a constant
high velocity over a long length. At the moment it cannot be decided whether it involves a stable detonation over a long pipe length or an unstable quasi-detonation.
As with flammable gases, small pipe diameters favor the occurrence of detonations
for combustible dusts [78,79], but the distance required to reach the very high velocities is greater for dusts than for flammable gases which detonate with comparable
violence.
As per Fig. 139, there seems to be a quasi-linear correlation between the maximum explosion pressure Pmax and the maximum flame velocity V max which is almost
independent of the dust type for dust explosions initiated in pipelines with a flame
jet ignition. The values deviate because of the different maximum explosion pressures of the dusts (see Fig. 88) and the superimposed oscillations of the reaction
over time. Long pipelines with elbows and end flanges will show similarly high
pressures as in Fig. 137 if such pipelines are attached to vessels which suffer dust explosions.
In summarizing, it can be stated that the course of combustion of dust/air mixtures in pipelines mainly depends upon the displacement effects with the resulting
change in turbulence of the still unburned mixture ahead of the flame front. In particular, with flame jet ignition from attached vessels, such explosions may convert
124
c::
Cl
C .0
.Q~
II)
0..
.9
Cl
~o..
E ~
::::J
'x
::::J
II)
II)
Cl ~
Eo..
20
KSt [OOrm/s]
Coal dust:
85
Methyl cellulose, 130
Powdered sugar, 160
10
Wood dusts
230
+ +
Pigments
300
1: +
Aluminum
550
O~~~--~--~--~----~--~--~--~
500
1000
1500
2000
2500
3000
3500
4000
vmax [m/s 1
40-m as
to detonations or quasi-detonations with substantial pressures. Small pipe diameters will favor a detonation. However, the pipe length required to reach the high
constant velocity over a long stretch is longer for combustible dusts than for flammable gases. The maximum explosion pressure is generally higher in closed pipes
than in open pipes, with extreme pressure values at connecting flanges or elbows.
not new. Reliable documented experience extends almost 200 years back in technical history. As long as organic chemistry is applied on an industrial scale, there are
always unforeseen explosions (Figs. 1-4, 7, 140).
Pressure build-up and the resulting fires cause much damage to manufacturing
equipment and buildings, along with fatalities. It is the task of safety technology to
prevent such damage or limit its effects. It should not adjust the safety yardstick because of increased numbers of accidents, but rather take preventive action based
on analysis. Explosion protection consists of the assessment of the explosion danger resulting from the handling of materials which may create dangerous and explosible atmospheres, plus the assessment of the effectiveness of protective measures
for the prevention of such dangers. The risk of an accident must be reduced to a jus-
126
tifiable level. In the 1960s, the chemical industry worldwide suffered from dust explosions which could not be explained satisfactorily with the knowledge available
at that time.
Therefore, in 1967, a few German and Swiss chemical companies, together with
the Bergbau-Versuchsstrecke" in Dortmund-Derne, formed a collaborative circle
called "Combustible Dusts". Its goal was to formulate possibilities for the prevention of dust explosions altogether or to limit the effects to an acceptable level. This
was to be done in close collaboration with research institutes and the German Society of Engineers (VDI). In the last decade, all concerned contributed very successfully, as was reported in numerous VDI colloquia. Important insights have
been shared relative to the practical application of explosion protection against
dust explosions.
In 1976, the guideline for the prevention of the dangers of explosive atmospheres with examples was issued by the "Berufsgenossenschaft der Chemischen
Industrie" and has been adopted. It is called in short Ex-RL [97]. It should facilitate the assessment for the user of whether a dust explosion danger exists in a given
manufacturing installation. For clarification, the following questions are raised
[Sl ]:
- "Will there be an explosive atmosphere in the area of the installation to be analyzed or within the equipment?"
- "What is the amount of explosive atmosphere present or possible based on local
or manufacturing conditions and where will it be generated?"
- "Is the amount of expected explosive atmosphere dangerous?"
If the questions are positively answered, then a decision has to be made with regard
to the selection of the protective measure against the imminent dust explosion. The
guideline distinguishes between three groups:
a) measures which will prevent or limit the formation of explosible atmospheres.
Such a measure is often called "primary explosion protection".
b) measures which will prevent the ignition of explosible atmospheres and
c) measures which will limit the results of a dust explosion to a harmless level.
Measures a) and b) prevent the start of dust explosions and are summarized under
the heading "preventive explosion protection" in the revisedVDI-guideline 2263
"Dust fires and dust explosions: hazards-assessment-protective measures" [23].
Measure c), which limits the effects of dust explosions is classified as "explosion
protection through design measures". The basis for the assessment of the scope of
protective measures is the classification into zones, as per Ex-RL [SO]. The zones
reflect the probability of the existence of dangerous, explosible atmospheres. The
definitions for combustible dusts are as follows:
Zone 10
Zone 11
includes locations in which dusts present a dangerous, explosible atmosphere intermittently or frequently.
includes locations in which an occasional dispersion of settled dust
may be expected, forming a dangerous, explosible atmosphere.
The inside areas of equipment (e. g., mills, dryers, mixers, conveyors, ducts, silos, .. ) belong in general to zone 10.
127
fuel
128
(ignition range), then dust explosions are prevented. Such a measure can be used
alone or in conjunction with other safety measures. This depends upon the process
technology and the safety characteristics of the dusts. In such a context, the lower
explosible limit (LEL) is of particular importance (see sect. 4.3.1.4) (Fig. 142).
In individual cases, the limitation of the dust concentration in equipment or
parts of the equipment can be used as the safety measure, provided a constant concentration can be guaranteed which is well below the LEL of the fine dust (M <63
,um) (e. g., room air exhaust or clean air downstream offilters). With time, some
settling of dust has to be expected. The dispersion of the settled product may present an explosion danger which can be eliminated through frequent cleaning.
A simple overall consideration of, e. g., the amount of dust per vessel volume
may not reflect the true concentration in all partial volumes due to the likely inhomogeneous dust distribution. The calculated average dust concentration for spray
dryers shows that the LEL will not be reached. Experience, however, indicates that
an explosible dust/air mixture has to be expected in the conical section of the dryer
and in the equipment downstream from a dryer (cyclones, filters). In high-performance pneumatic conveyors, the upper explosible limit is in general exceeded due
to the loading. Tests with a dust filter [81] have shown that a dust explosion with
polyethylene fine dust (M = 26 ,um; Pmax = 7.5 bar; Kst = 104 bar.rnls) in the vented
'-
.D
O~~~c--~--------~--~
!::ll~~'
..g.
LEL
50
100
125
'1
129
filter housing will extinguish in the feed pipe DN 400 after 20-40-m provided that
the dust concentration is at least 2-3 kg/m3 or more. At start up or when the product enters the filter, cyclone, or silo the formation of an explosible dust mixture is
possible. In such an operational phase, additional safety measures may be necessary, e. g., inerting (see sect. 5.2.3).
In order to prevent an explosible concentration de-dusting with a liquid may be
advisable, for instance, with water or special oil [83].
In order to prevent dust explosions, the preventive measure inerting may be used.
By introducing ample amounts of inert gas - mostly nitrogen - into the volume
which needs to be protected (e. g., inside of containers, mills, silos) the volumetric
oxygen content will be reduced to such a level that no ignition of the dust/air mixture will occur [23].
The application of such a safety measure calls for expert knowledge, mastery of
the process and gas-tight equipment. By inerting the air of combustion, the ratio
oxygen/nitrogen is changed in favor of nitrogen.
The lowest minimum ignition energy (LMIE) of combustible dust increases linearly in a semi-logarithmic plot (Fig. 143). The rapid decrease of the readiness for
ignition of the mixture is naturally due to the nitrogen which as a ballast absorbs the
heat released without participating in the combustion. Excess oxygen, however,
flattens the curve [60].
With the change of the ignition source (extended capacitor discharge - ? pyrotechnic ignitors) a break occurs in the line for hard-to-ignite dusts (pea flour, melamine) in normal air because the pyrotechnic ignitor has a better efficiency due to
its longer burn-time.
The oxygen concentration in nitrogen giving LMIE = 107 mJ (= 10,000 J)
which is equivalent to the energy used for the determination of explosion indices,
is called "limiting oxygen concentration (LOC) " . The LOC of a dust/air/inert gas
mixture is experimentally determined using varying dust concentrations and oxygen/nitrogen ratios. The oxygen concentration which will just not allow an explosion will be called the limiting concentration. It is a specific value for the dust and
inert gas used and has to be determined experimentally due to the lack of any other
correlation. For practical applications, a safety margin of generally 2 % is allowed,
depending upon circumstances. Such a concentration is called "maximum allowable oxygen concentration [23]. This means that not all of the oxygen has to be displaced in order to prevent a dust explosion if the safety measure "inerting" is used.
Total exclusion of oxygen is only needed in case fires have to be prevented. It
has to be pointed out that inerting is not an effective safety measure against thermal decompositions or deflagrations.
130
107.----------1:xD---,------,
')J5
T
OJ
10 4
-,
E"
-5III
'0
<-
OJ
III
c:
OJ
"0
c:
Fig. 143. Influence of the ratio oxygen/nitrogen in the air for combustion upon the
lowest minimum ignition energy of combustible dusts
As already stated (see sect. 4.3.1) it is customary to determine the explosion indices in a 1-m3 vessel or the 20-1 laboratory apparatus. It was also pointed out
(Fig. 54) that a reduction of the oxygen content through the addition of nitrogen to
the air of combustion will reduce the explosible range. The oxygen reduction has
to be greatest at the LEL in order to prevent a dust explosion. At the same time,
the explosion indices are being reduced. They include:
- explosion pressure pex
- pressure rise dp/dt
which describe the course of a dust explosion in closed vessels as a function of the
dust concentration. Figures 144 and 145 give a practical example from tests made
in the large vessel as well as in the laboratory equipment.
In analyzing the effects of decreasing oxygen content upon the behavior of the
optimum explosion characteristics
- maximum explosion pressure pmax and
- dust-specific Kscvalue
131
10r--------.--------~
'-
.8
~
0
8-~
~~
'. ~e.
.~
~\
021 vol% 02 in N2
El17.4vol%02 in N2
a14.6vol%02 in N2
",11.9 vol%~ in N2
200
~
: 1
...!!!
'd
.c
......
:!2
100
G.....-~"
8",
.
0"0
0
0
Fig. 144. I-m3 vessel. Insecticide: Influence of oxygen content upon explosion indices
500
1000
10 ....--------,----------,
21vol% D;zinN2
18.9vol% 02 in N2
16Bvol%02 inN2
'iii'
--
.8
12.6vol% ~inN2
400
......
--
"0
0"0
500
1)00
132
for either type of equipment the following can be stated (Fig. 146):
- For both equipment, the maximum explosion pressure Pmax decreases slowly at
first and then rapidly in the range of the limiting oxygen concentration. This is
especially true for the larger vessel.
- The behavior of the Kscvalue, however, noticeably depends upon the size ofthe
test vessel. For the large vessel, there is a linear correlation with the oxygen content in nitrogen.
The intersection with the abscissa gives the limiting oxygen concentration. For
the 20-1 laboratory apparatus, however, the Kst-value approaches the abscissa
asymptotically, rendering a much lower LOC than in the large vessel.
The reason for the sensitive behavior of the laboratory equipment in comparison with the larger vessel is the influence of the energy of the ignition source. The
pyrotechnic ignitors which are used for the dust explosion testing have an energy
content of 10,000 J and present a point source in the 1_m3 vessel. In the 20-1 equipment, however, they affect the whole explosion volume once ignited. A number of
combustible dusts were comparatively tested in both vessels [62]. The results gave
the following correlation for the limiting oxygen concentrations (LOC):
LOC (1_m3 vessel) = 1.64 LOC (20-1 apparatus)
The LOC for the large vessel averages 64 % higher than the laboratory equipment.
LOC values determined in the laboratory equipment have to be adjusted in line
10.-------,-------~1~1--'
o--t
/1
:
I
0.-0
IJ
/0
! (
I'
o~__~~~-------u--~
200.--------.---------..--.
I
E11m3- vessel
o 2()(- sphere
E
c:..
.0
o/:
[]
100
1
1
1=
10
1
......
l.I)
~
10
- content in
20
N2
25
[vo[%]
Fig. 146. Insecticide: Influence of the oxygen content in nitrogen upon the maximum
explosion pressure and Kscvalue in the larger (1_m3) and smaller laboratory equipment
133
with the above equation for large vessels before they are suitable for practical application. References [55, 56] accept only equipment for dust testing which renders
the same safety characteristics for airborne dusts as the standard I_m3 vessel.
The LOC for combustible dusts has to be determined experimentally from case
to case due to the lack of a correlation. But there are certain tendencies to be seen
[63].
- the LOC is higher, the weaker the dust reacts (Fig. 147)
- the LOC is higher, the higher the ignition temperature in the BAM-oven is
(Fig. 148).
400
II
I
I
I
I
I
0
300
'8
III
........
200 -
00
ei
.0
~
0
00
iB0
L-
.Cj
a'l (!3
0\
+Vl
~
100
0\
0
0
80~.
II
20
25
LJ
.....
500
10{,,".~
i=
L
:J
+eI
OJ
0-
400
OJ
+-
A.
A
A
:;::::
.Ql
1
1
1
I.!::
I'"
1
1
1
1
00
II
Ai
JA V
OJ
I
10
300
limiting
L 1m3-vessel
I
0
10
15
20
25
134
"
N
IIIIIII
12
.!:
c
o
4=,
d
'--l-
C
OJ
20C
Lycopodium
td = 60ms
u
C
o
u
100C
200C ...
4L-______~------~~----~~------~
250
500
dust concentration
750
[g/m 3 ]
10 0
Fig. 149. Lycopodium: Influence of the limiting oxygen content in nitrogen and the temperature upon the dust concentration (20-1 laboratory apparatus)
In industrial practice, the inerting safety measure is often applied at above room
temperature for grinding and drying operations. Glarner [59] systematically studied the influence of temperature upon LOC in a heated 20-1 laboratory equipment
(Fig. 70).
Figure 149 shows the influence the oxygen concentration and the temperature
have upon the explosible range of Lycopodium. Increasing temperature expands
1:15d
c:
en
10~~-------'---------'
>..
x
o
en 7,5
c:
E
Melamine
5 --0
100
temperature T
200
roc 1
135
the explosible range and reduces the LaC [63]. Because of the resulting linear correlation (Fig. 150), the average decrease amounts to 1.8 vol% per 100C temperature increase.
Wiemann [84] investigated the temperature dependence of the LaC for various dusts in a heated I_m3 vessel. He also found a linear correlation, with an average decrease of 1.4 vol% per 100C temperature increase. From this, it can be concluded that the influence of the vessel size V < I_m3 has to be considered and corrected for in the determination of the LaC but that the temperature dependency is
not affected within the range of accuracy. The LaC is dust-specific and, in general,
requires an experimental determination. Its is not only dependent upon the dust
type but also upon the particle size. For a few combustible fine dusts, the LaC at
room temperature is summarized in Table 16, with nitrogen as the inerting medium.
Table 16. Combustible dusts: limiting oxygen concentration (LaC) for inerting with
nitrogen (l_m 3 vessel, E = 10,000 J, room temperature)
Dust type
Pea flour
Cadmium laurite
Hard coal
Barium stearate
Rye flour
Brown coal
Soot
Organic pigment
Herbicide
Cadmium stearate
Calcium stearate
Wheat flour
Polyacrylonitrile
Cellulose
Wood
Resin
Methylcellulose
Polyethylene (HDPE)
Dibenzoylperoxide
Beta-naphthol
BisphenolA
Cornstarch
Sulfur
Paraformaldehyde
Aluminum
M
[~m]
LaC
[vol%]
25
<63
17
<63
29
63
13
<10
10
<63
<63
60
26
22
27
63
70
26
59
<30
34
17
30
23
22
15.5
14
14
13
13
12
12
12
12
12
12
11
11
10.5
10
10
10
10
10
9.5
9.5
9
7
6
5
136
Table 17. Brown coal: Influence of the type of inert gas/vapor upon the limiting oxygen
concentration (LaC) (1- m 3 vessel, E = 10,000 J, T= 150 a C)
Inert gas/vapor
LOC[vol%]
Nitrogen
Water vapor
Carbon dioxide
11.0
12.4
13.0
For most organic dusts, a reduction of the oxygen content by half (relative to
air) results in a complete inerting. If the maximum allowed oxygen concentration
in nitrogen is maintained at 8 vol%, then no dust explosion will be possible. But
there are exceptions, e. g., beta-naphthol, paraformaldehyde. Wiemann [84] also
investigated the influence of the type of inert gas or vapor at elevated temperatures
upon the LOC for brown coal (Table 17).
The effectiveness of water vapor is between that of nitrogen and carbon dioxide.
If "inerting" is used a a safety measure in practice for the protection of vessels
and equipment, the LOC has to be monitored in such a way that it will not be exceeded.
This may be accomplished by continuous or intermittent measuring. Special
attention has to be given to the following [85]:
- selection of a suitable parameter for monitoring (oxygen concentration, inert
gas flow)
- selection of suitable instrumentation
(e. g., principle of measurement, sensitivity, accuracy, response, response delay
due to the distance sampling point - measuring point)
- selection of a suitable sampling point considering the flow pattern, which must
reflect the worst condition for the oxygen concentration. Multiple sampling
points may be necessary.
The proper measures have to be defined in case of an upset:
- Shutting down the equipment in case the highest allowable oxygen concentration is exceeded or a higher flow of inert gas is called for than required for proper
inerting. In general, shut-down should be automatic.
- Selection of the proper level for an alarm which, once exceeded, will trigger
counter-measures (automatic, mechanical).
If the measuring is done intermittently, it has to be ensured that:
- the system is completely closed with well-defined reproducible gas flows (danger: cleaning ports)
- the necessary test period was long enough to arrive at safe operating conditions
for inerting
137
- if the system is subsequently modified, the operating conditions for inerting will
be checked and reset if necessary
- the degree of inerting will be known for all operating conditions and affected
pieces of equipment
- an alarm will be actuated in case the supply of inert gas fails.
5.2.3.1.3 Hybrid Mixtures
In case hybrid mixtures, consisting of combustible dust and flammable gases, have
to be inerted, the behavior of the range of ignition of the flammable gas has to be
known at reduced oxygen levels [63]. Such a reduction is, of course, accomplished
by adding nitrogen to the air of combustion. The behavior of propane is shown in
Fig. 151 for the case of ignition:
1) in a quiescent state and
2) the same turbulence used for dust explosion tests.
A reduction in oxygen content will not change the lower explosive limit (LEL) but
will markedly reduce the upper explosive limit (DEL), similar to combustible
dusts. The state of the mixture has a slight influence upon the ignition range but not
upon the limiting oxygen concentration (LOC) , which is 10 vol%. However, an additional consideration involves the influences upon the limiting concentration from
the potent ignition source (E = 10,000 J) used for dust testing. The LOC is markedly higher at 11.8 vol% if the standard ignition source for flammable gas testing
is used, namely the contino us induction spark with an energy E = 10 J.
Figure 152 shows the correlation of the explosion characteristics with the degree of inerting with nitrogen for pea flour, propane, and their hybrid mixtures.
The LOC for dust is at 15.5 vol%, markedly higher than the one for the flammable
gas, which is 10 vol%.
201~~~--'---'---'---~T-r'
I"
~-".~'"
4=
-<-
10
c
o
L~
1----
limiting oxygen
------coocentrntionLO(
Ql
8
I
5 -
('oJ
10
12
138
/It
./ j-;:/
/
AI
__ 0_--l~_...1 A -....~_-'-_........
~400
+2.7 vol%
.+4.5'<01%
[3 H8
[3 H8
~.
~BOO
..0
[3HS
~'00/;P
A
O._.~d.:_...L-_.....I lLill----"--...,j
~200
~~
The reduction of the oxygen content causes a slight reduction in the maximum
explosion pressure pmax, at first, independent of the propane concentration, and
then gives a drastic change at the LOC. It influences the dust-specific Kscvalue linearly, in the same fashion as with dust alone, if the propane content is near its LEL.
The Kscvalue approaches the abscissa asymptotically with a high gas content
similar to propane alone.
In general, hybrid mixtures can be ignited at oxygen concentrations which will
not allow pea flour to explode. The LOC of the mixture moves towards the one for
propane alone and then away from it, for higher flammable gas concentrations.
Such a statement is generally valid for any combustible dust (Fig. 153) and flammable gas (Fig. 154). In order to allow comparisons in the latter case, the concentrations are referenced to the optimum concentration for the explosion indices. This
serves as the standard.
In summary, it can be stated:
For hybrid mixtures consisting of combustible dust and flammable gases or vapors, the LOC is given by the fuel with the lowest limiting value. For flammable
gases, the following correlation exists for the LOC determined in the I-m 3 vessel
and the 20-1 laboratory apparatus [63]:
LOC (l_m3 vessel) = 1.32 LOC (20-1 laboratory app.)
139
16r----r-.r-------r------.--~
-g
c
o
04-
12
04-
QJ
1S.----,--,--------.-------r~,
/-
/'
~
g'
~tiOXidont
....- - F ' - - - - - - - - - - -
.....
--02 limit : p r o p o : /
~
'-
..CJ
12
~IlUlose
>.
.c
-'---~--------
9~__~~------~-------L--~
140
-v:.
LEL:
glSes
13
optimum concentration;
gases
12
c
.Q
11
OJ
10
8,
~
-<u
('oJ
.~
-<-
./
I
[;l/
I ,/
y(" prollWJe..
/V
tI/1
~'/
//
,
/fl
6o-=-~=-....-...:tI-,
5~~~
__
LOC
Methane
I_Butane
I
Propane
I
I -
I
I
______ I ______
05
10
~~
On the average, the LOC in the large equipment is 32 % higher than in the 20-1 laboratory apparatus. The size of the test vessel influences the results for flammable
gases only half as much as in the case of combustible dusts (see sect. 5.2.3.1.2). As
a consequence, the LOC for, e. g., cellulose with 10.5 vol% in the large equipment
is above, and the 6.0 vol% in the laboratory equipment markedly below the one for
the flammable gases butane, propane, and methane. But this case again shows
(Fig. 155) that the LOC is determined by the fuel with the lowest limit.
Otherwise, the statements made in sect. 5.2.3.1.2, for the monitoring of the
highest allowable oxygen concentration for combustible dusts are also valid for
hybrid mixtures.
5.2.3.1.4 Use of Vacuum
It was already mentioned (Fig. 79) that the explosion indices of combustible dusts
(maximum explosion pressure pmax, dust-specific Kscvalue) in closed vessels are
proportional to the initial pressure pi, i. e., the starting pressure for the explosion.
By reducing the starting pressure below atmospheric, one can accomplish the
following:
- no dust explosion will occur (this is generally the case for initial pressures Pi :5 50
m bar) or
- the maximum explosion pressure remains below atmospheric pressure (for organic dusts, this will be the case at initial pressures Pi :50.1 bar).
141
At the same time, the lowest minimum ignition energy increases (Fig.U5). The larger the negative pressure, the higher the safety margin. Such a safety measure
against the start of a dust explosion is often used for vacuum-rotary dryers. The vacuum has to be monitored with instruments and in case of failure (e. g., air entrainment) be replaced with another safety measure (e. g., inerting or preventing of ignition source through shut-off).
5.2.3.1.5 Admixture of Solids
Combustible dusts may be inerted through the additional of inert powdery solids
[63]. This has to happen in such a fashion that the fuel is intensively mixed with the
inert powder.
If, e. g., pea flour is inerted with an extinguishing powder having ammonium
phosphate as a basis (Tropolar), then the lowest minimum ignition energy (LMIE)
of the combustible dust/inert powder mixture will increase rapidly with increased
inert powder content (Fig. 156). Here, the correlation is similar to the ignition behavior of combustible dusts inerted with nitrogen (Fig. 143). Therefore, that inert
powder concentration in the whole mixture which requires lowest minimum ignition energy LMIE = 104J is defined as the limiting inert powder concentration. In
Fig. 156, this would correspond to 75 % Tropolar in the combustible dust/inert powder mixture. As there exists no general correlation for inerting with solids, the socalled limiting concentration has to be determined for every application.
m5.-______- ,________~
OJ
~~
Co
OJ..c::
"Ow
c",
0w"O
102~_ _ _-:l.:-_-_-J
m
o
5.Q.
50
JL
100
mixing ratio: P
,-e"'TQ,--fl~o--;ur,-,-_ _--,--[wt % 1
extinguishing powder [wt% 1
142
~
~
LEL
~
~ 10010 I):-r.,,-;;'TT--r--;,.---,,----r-.,,-;;r-rT---y-r-l~_r"71
~
4-
i:::~
concentration
.......
cf.d
0/100 0
500
1000
1500
2000
2500
mixture concentration [g 1m 3 ]
Figure 157 shows the influence upon the ignition range of the admixture ofTropolar to pea flour. There is only a minor influence upon the LEL, but a pronounced
limitation of the VEL can be observed, similar to the inerting with nitrogen. At the
same time, the explosion indices (maximum explosion pressure Pmax, dust specific
Kscvalue) decrease and reach zero at 75 wt% Tropolar (Fig. 158).
10r--------.--------~
..CI
x
d
Cl..
100
-III
L.
d
..CI
+-
50
V1
::.::::
..0.100
[wt%/wt% 1
143
100
100
mixing ratio:
Another parameter which influences the limiting inert concentration is the ignition energy used (Fig. 159). Results from tests in the 1-m3 vessel indicate that lowering the ignition energy also lowers the limiting concentration for inert powder admixture. If not so potent ignition sources are actually expected in the equipment or
apparatus to be protected, then the admixture of only approximately 20 wt% of
inert powder (Tropolar) will suffice to inert a cellulose mixture.
There are no comparative test results available for the limiting inert powder
concentration in the 1-m3 vessel and the 20-1 laboratory apparatus. But the determination of this value means also to determine an explosion characteristic in both
apparatus which does not influence the composition of the air of combustion. As
concurring characteristics have been proven for the large and laboratory test equipment (Fig. 67), it can be anticipated that the limiting inert powder concentration
will not fluctuate in the same major fashion as the LOC. Analogous to inert gases,
inert solids have a varying effectiveness when inerting combustible dusts as shown
in Table 18.
In conclusion, Table 19 shows the required minimum concentration of inert
powders necessary to completely inert combustible dusts subjected to the usual potent ignition source for dust testing:
144
Table 18. Effectiveness of various inert powders for inerting combustible dusts
(l-m 3 vessel, E = 10,000 J)
Combustible
dust
Coal dust
Sugar
Dextrin
Organic pigment
Aluminum
NH4H 2P0 4
KHC0 3
KCl
KCI
NaCI
NaCl
NaHC0 3
NaHC0 3
NH4 H 2 P0 4
NaHC0 3
Inert
powder
[/tm]
Pea flour
Methyl cellulose
Cellulose
Hard coal (bituminous)
Hard coal (bituminous)
Organic pigment
Aluminum
Dextrin
Sugar
25
70
22
20
20
<10
<10
<63
30
NH4H 2P0 4
CaS04
NH 4H 2 P0 4
CaC0 3
NaHC0 3
NH4H 2 P0 4
NaHC0 3
KHC0 3
NaHC0 3
10,000 J)
[/tm]
Required minimum
concentration
for inerting
[wt%]
29
<15
29
14
35
29
35
25
35
75
70
65
65
65
65
65
55
50
Generally, more than 50 wt% of inert powder has to be admixed for inerting.
However, as shown in Fig. 159, markedly lower concentrations of inert powders are
needed if less potent ignition sources are anticipated in industrial practice.
145
tional upsets have to be considered which may generate ignition sources [22]. The
application of the safety measure "prevention of effective ignition sources" has to
be justified and assumes sound knowledge.
The following distinction has to be made:
- trivial ignition sources (e. g., unauthorized smoking, welding, cutting, using
open flames)
- ignition sources inherent in the process or operational upset (e. g., foreign particles, pin breakage in mills, glowing particle nests).
Trivial ignition sources can positively be excluded in a well-managed modern facility through administrative measures (e. g., permits). Inherent operational ignition
sources can be prevented through the use of dust explosion-proof electrical equipment, adhering to temperatures given by safety considerations, sound bonding and
grounding for electrostatic purposes, and avoidance of mechanical drives with high
rpm or power. Once both ignition categories can be excluded, then,based on today's knowledge, such a safety measure can be considered sufficient to prevent the
start of a dust explosion. Special precaution is necessary for hybrid mixtures and
dusts having a low LMIE < 10 m]. Every installation has to be analyzed with regard
to potential ignition sources and whether they can be avoided with a sufficient margin of safety. The guideline for explosion protection [SO] lists 13 types of ignition
sources. In the following, the most important ignition sources for combustible
dusts will be characterized.
The assumption that there is no ignition danger at low relative velocities has been
confirmed by recent test results [S5]. In these tests, grinding sparks are generated
by quickly contacting, e. g., a steel pin with a vitrified type ceramic wheel. Friction
sparks and hot surfaces, however, are generated by rubbing steel pins against steel
wheels over an extended time. Figure 160 shows the boundaries for the generation
of grinding and friction sparks, as well as hot surfaces as a function ofthe thrust PA
and the peripheral wheel velocity. It illustrates that at velocities v :;:;; 1 m/s no ignition is to be expected unless exceptionally high thrust will generate steel sparks or
hot steel surfaces. The materials of construction listed in Fig. 160 are referenced to
the "steel nomenclature" [S7] as follows (Table 20).
146
st 37
0\.
0
100
[J~
z:
'\:~
50
D_[J~_a
0 ........ D__... rn
CL-4:.
~
til
::J
'-
...c:::
f-
__ o []
V2A
0 ~----------~--------~
100
50
St 79
0
1
10
100
00 t;,
() 11 ~
Marking
V2A
St37
St79
1.4435
1.0037
1.1663
In order to compare the ignition capabilities of the different types of mechanically generated sparks in fuel/air mixtures, an electrical equivalent energy (EE) is
assigned. EE is defined as the energy released through the discharge of a capacitor
over an extended time period (see sect. 4.4.1). which has the same ignition capability as a given mechanically generated spark [88]. The procedure will be explained
with the example of the flintstone friction spark (Fig. 161).
Figure 162 shows for propane the correlation of minimum ignition energy with
the flammable gas concentration. Included also is the range of ignition for the flintstone friction spark. For such a spark there exists an electrical equivalent energy
EE = 4.103 mJ = 4 J for a below stoichiometric gas concentration. Above the stoi-
147
'Os
-.
'0 4
I
I
I
I
I
10 3
,,,
I
>,
2'
QJ
102
QJ
.Q
.....
c
10 1
=:l
10 0
'E
Fig. 162. Comparison of the minimum ignition energy of propane with the range of
ignition of a flintstone friction spark
10-1
12
148
-.
E
ll.J
ll.J
103
>-.
Ol
'OJ
102
OJ
OJ
\
\
\D
-<-
\
\
.::!
::J
cr
OJ
10-1
\
0\
OJ
10-2
0
above
stoichiometric
Cl
10 0
c
-<u
101
500
ignition temperature TI
1000
[O(
149
10 5, - - - - - - - , - - - - - - ,
..,
E
10 4
l.!.J
>-
2'
OJ
.,
I
I'
I,
II
1\
. \
OJ
td =60ms
J
I
.Q
.....
c
.Ql
E
E
.f:
::l
10 1
10 0
500
1000
..,
E
w
>~
OJ
OJ
.....c
OJ
Ci
>
0OJ
u
.;:
.....u
OJ
Qj
150
I!.-~
-.
E
L1.J
L1.J
D\"'\,;
>..
en
10 4
\
102
QJ
Ci
.!!:
:::J
0-
101
QJ
u
.<::
.....u
grindin~sparks
103
QJ
.....
c::
titanium
<-
c::
QJ
O()
\ \
100
' \ .,ili"
\ \\\
i,.,m \ \\\
o
6.
()
QJ
oJ
10-1 L----'_---'-_......I.._....J.._....J..._...J
200
300 400 500
600 700 800
ignition temperature TI
roc 1
Grinding sparks occur if materials of construction briefly touch an, e. g., vitrified type ceramic wheel (grinding time tg = 20-50 ms). For such a case (Fig. 166),
parallel lines can be drawn, within the range of accuracy, that give the boundary for
ignition, which depends upon the type of spark-producing material. Ignition of the
combustible dust/air mixture is always to be expected if the minimum ignition
energy is below the boundary, and no ignition, if it is above the boundary line. It is
also obvious that dust/air mixtures with a low ignition temperature (e. g., TI =
300C) will ignite even if they have a high LMIE. If the ignition temperature, however, is high (e. g., TI = 600C), then only mixtures can be ignited having a very low
value for the LMIE. Grinding sparks which are generated by grinding steel against
steel [85] will, based on today's knowledge, only ignite mixtures of dust having ignition temperatures TI < 300C and LMIE < 10 mJ. Sulfur, for instance, is such a substance.
Impact sparks have a very different ignition effectiveness, which depends upon
the materials used to generate the sparks, as shown in Figs. 167 and 168. This is also
reflected by the course of the corresponding ignition boundary lines (Fig. 169) [88].
Based on the results presented so far, the ignition effectiveness of mechanically
generated sparks decreases as follows (Figs. 166-169):
-
151
152
w
>-
en
<-
QJ
QJ
4-
g
QJ
:::J
0-
Ci
4U
QJ
aJ
Fig 169. Impact sparks: correlation of electrical equivalent energy (EE) with ignition temperatureTI
10 2
'O'~
~~~~um
Irust~act spark
QJ
u
.;:
no ignition
--.
1~ igOit"O'~
101
200
300
ignition
400
500
--'-----'----'
600 700
800
temperature
TI roc 1
Steel grinding sparks (Fig. 170) have a relatively poor ignition effectiveness among
the examples given (Fig. 166). With an ignition temperature TI = 400C as a reference, they are only capable of igniting dust mixtures having LMIE <10 mJ. Such
behavior does not explain the previously stated frequent occurrence of dust explosions initiated by mechanically generated sparks in industrial practice. If steel is
rubbed against steel (Table 20) for a longer duration, e. g., rubbing times tr = 0.52.0 s, then friction sparks are generated (Fig. 171) which are much more ignition-efficient (Fig. In). At the same ignition temperature, dusts will be ignited which
have LMIE < 100 mJ [86]. The likely reason for such behavior is the higher starting
temperature of the sparks due to the heating-up of the pin. Therefore, the occurrence of the above-mentioned ignition source in practice is more likely.
In summarizing, it can be stated than the type of spark-producing material, together with the ignition temperature and the LMIE requirement, will determine
whether an ignition of the dust/air mixture has to be anticipated from grinding, friction, or impact sparks.
153
154
.....
E
10 4 -
L!.J
L!.J
>O"l
<-
103
QJ
QJ
+-
10 2
~
d
.~
:::J
cr 101
QJ
du
<+u
10 0
QJ
ill
10 1
200
300
500
400
ignition temperature TI
roc 1
155
LJ
2III
......
III
500
no ignition
::J
-0
::J
......
e
QJ
Cl.
400
Topt ;, 1200 0 (
c
0
o 4mm - pins
:E
.!2' 300
6mm - pins
l:i.
10
100
Topt. x DR
X S
1000
[mm 2 ]
::.T
Fig. 174. Correlation of heated pin surface with ignition temperature of combustible dusts
156
struction upon the course of ignition could not be observed within the range of
measuring accuracy.
In addition, auto-ignition may occur in dust-piles (see sect. 4.2.5). The resulting glowing particle nests or fires may themselves become the ignition source for
dust/air mixtures. The question whether a glowing particle nest is actually capable
of igniting a dust/air mixture cannot be answered at present. Experience indicates
that in certain cases (coal dust) this is very hard to accomplish; in others (e. g., certain pigments) it is easily done.
157
158
159
160
5.2.7 Conclusions
There are a number of possibilities for applying preventive explosion protection to
avoid dust explosions in practice. One possibility is limiting the dust concentration.
If it is possible to maintain the dust concentration in the equipment outside the explosible range, then dust explosions are prevented.
In accordance with the guideline "explosion protection" [80], inerting is one of
the measures which prevent the formation of dangerous, explosible atmospheres.
This can be accomplished by admixing gaseous inert matter to the combustion air
in the equipment to be protected. Inerting is the surest protective measure against
the start of dust explosions. Therefore, it is a major tool for preventive explosion
protection. In administering inerting by admixing nitrogen to the combustion air,
it is important to know the limiting oxygen concentration (LOC) for industrial applications which will just prevent a dust explosion. Such a concentration is determined experimentally. Over a wide range it is independent of the initial pressure,
the starting pressure of a dust explosion [93], but dependent upon the size of the
test vessel (Fig. 180). The limits obtained in the standardized 1_m3 vessel are the
guiding concentrations for practical applications; therefore, the values obtained in
smaller apparatus have to be adjusted accordingly. By deducting a 2 vol% safety
margin, the maximum allowable oxygen concentration is obtained which has to be
maintained for inerting with nitrogen.
j= .t--
(7'/
to 7
'--
Ll
2.5
l-
It I'
50
~
oY=1m 3
fO.Y=381
o Y=20f
"d
Ll
.0-
25
I
I
I(
I
I
I ...
lei
I
I
I
I I
.6--Lo
I/)
~
I I
Jf
...
d
/o}
0
Lo
~C!
10
20
2 content in N2 [vol%l
25
161
162
eXj:1losion resistant
~q~Qment--
~~
explosion pressure
resistant:
explosion pressure
shock resisfant:
safety factor
yield stress versus design
stress = 1.5
safety factor:
yield stress versus design
stress = 1.0
Fig. lSI. Design possibilities for explosion resistant equipment using ductile materials of construction
In the case of a vessel buit for a design pressure of 6 bar, its explosion pressure
shock-resistance will be 9 bar. Such a vessel in a closed state will withstand explosions of practically all organic dusts (Fig. 88).
If such a vessel is available having a code design pressure of 2 bar, it may be used
in conjunction with the measure explosion pressure venting for a maximum
reduced explosion pressure Pred,max = 3 bar. In exceptional cases, permanent deformation has to be expected for pressure shock-resistant vessels, when subjected to
163
164
Despite the use of explosion pressure-resistant equipment for the full explosion
pressure or other design measures outlined later, everything possible must be done
to prevent effective ignition sources because loss of product and interruption of
production are equally undesirable. The entrance of tramp metal into milling and
size reduction equipment can be prevented to a large degree, e. g., through the use
of precrushers or safety crushers with slip clutches or inductive metal detectors.
165
Fig. 183. Double rotary air lock built to be explosion pressure shock-resistant [96]
Generally, pressure vessels are subjected to a pressure test with water. For ductile materials, the test pressure is 0.9 times the design pressure, and for cast iron
twice the design pressure. An explosion test can also be made in the form of a specific prototype test.
Figure 184 (left) shows a small container for bulk material with flat surfaces and
Fig. 184 (right) the same container after exposure to an aluminum dust explosion
with a maximum explosion pressure Pmax = 10 bar. The walls are deformed, but the
container did not rupture. It can therefore be classified as explosion pressure
shock-resistant up to the test pressure and be used, e. g., as a receptacle for dust explosible products from milling systems which are protected through appropriate
design measures. A number of dust explosion incidents in practice have documented that the tested container has met all the required demands. Some guidelines
which have to be watched in the design of explosion pressure shock-resistant vessels are given in [102] and [103].
166
Fig. 184 alb. Small container for bulk material (V = I-m i ) (a) as received; b) after explosion
test)
167
Pressure-venting systems can be built either for only one exposure, e. g., rupture discs, or multiple exposures, e. g., explosion flaps (doors).
The safety measure "explosion pressure venting" presumes a certain pressure
rating of the vessel. The vessels which are to be protected must be designed as "explosion pressure-resistant" or "explosion pressure shock-resistant" as per sect.
5.2.4.l. The design pressure is a reduced maximum explosion pressure pred,max compared with the maximum explosion pressure pmax. The pressure reduction is accomplished through a properly sized vent system. Attention has to be paid to ensure
that all parts which are exposed to the explosion pressure be included in the considerations for the suitable protective measures.
1.0,.-------------------,
.Pred=(~)
.tred
L..
dt red 0.02
pressure rise
Cl
e.G
0-
'Vi
% 13
iiSct-
0.5
'O~
QJ=:J
UI/)
=:JI/)
'Ow
wL..
L.. Cl.
i--_~
moment
of
ignition
tre d=0.02 s
time
[s1
Fig. ISS. Definition of the reduced rate of pressure rise (dp/dt)red of a pressure-vented dust
explosion
168
100.-------,-------,---------j
0.75 bar: reduced maximum
_ 0.75
cd
..0
Il
0.50
"D
OJ
c-
D..
0.25
~Pred,max
'
OL--------L--------~------~
20.-------.-1----,-1---~
a 15 -
.';Q
..0
310
15barls=reduced maxim~!ll
of pressure rise
-~-rate
rio" / '
",P/dtlred, max
r/
O~------~I--------~I------~
500
1000
1500
dust concentration
169
The knowledge gained from those dust explosion tests was the basis for the VDI
guideline 3673 "Pressure release of dust explosions" (Fig. 189) [55]. The guideline
includes nomograms (Fig. 190) which give in a convenient way the required relief
area for known vessel volume, vessel design pressure (equivalent to the reduced
maximum explosion pressure Pred,max), and the dust explosion class St for static
venting pressures Pstat = 0.1-0.5 bar.
The nomograms are valid:
- for the case of pressure venting with a safety membrane (Fig. 191) or a metallic
rupture panel (Fig. 192)
- for dust having a maximum explosion pressure pmax = 10 bar for dust explosion
classes St 1 and St 2, as well as pmax = 12 bar for the dust explosion class St 3
In order to determine the vent areas for any Kst-value, a mathematical adjustment of the measured values has been made. The resulting nomograms can also be
taken from the referenced VDr guideline. There are differences in the resulting
vent sizes between the nomograms which can be justified from a safety point of
view. Extensive tests have shown that the deviation of the test data markedly increases with increased maximim reduced explosion pressure. Therefore, Pred,max
was limited in the nomograms to pred,max = 2 bar gage. Upon actuation of the relief
device, a substantial flame formation and pressure build-up has to be expected,
even for relatively small vessels (Fig. 187), due to the exhaust of combustible dust.
The vented, at first unburnt dust will then be ignited outside the vent opening.
Therefore, the flame propagation will be larger the smaller the static venting pressure of the relief device. If pressure venting is applied to vessels or equipment inside a building, it is imperative that the pressure be vented through ductwork outside in a safe direction in order to protect personnel and production areas
170
VEREIN
DEUTSCHER
INGENIEURE
deutllCh: JunI151751
En'llllah: October 1983
fr.n~.I Octob.-. 1983
VDI-RICHTLINIEN
VOl 3673
Ausgabe/ue/edltJon
deutllCh/englJtranzOsisch
German/English/French
allem.langl.lttanrralse
Le pro)et de eette dlfectlVe a ete susceptible d'opposition pubilQue apres nob',cation dans Ie Bundesanzeiger (bulletm
federal).
Vorwort
Introduction
Preface
Die !"ationalkomitees der Mltglieder des FEM. "federation Europeenne de la Manutention", Sektion II, haben wahrend ihrerVollversammlung in Malmo (Juni
1982) beschlossen. die Rlchtlmle
VDI3673 "Druckentlastung von
Staubexplosionen" anzuerkennen.
"federatIOn Europeenne de la
Manutention" (FEM) ha .... e decided at their Plena!) Meeting in
Malmo (June 1982) to adopt the
VDI Guideline on the "Pressure
release of dust explosions" (Ref.
VDI 3673).
Section II of the FEM also decided
to recommend to its members and
to their clients the utihsation of
thiS document \I.. ith practical indications, v.hlch have prO\en themsehes. for the selection and the
calculatIOn of the release deYlces.
'lJb&:',p!,on}
Reg,sler-Nr 10
Preisgr.20
Fig. 189. Cover sheet VDI guideline 3673 "Pressure release of dust explosions"
171
St 1
::,t 2
st 3
II IIIII
'\
I\.
I\.
r-- ~tat=0.1txJ.r
KSt[bar.m!s) ~
high energy ignition
1 <KSt <200 St 1
201 <KSt < 300 :St 2
301 <KSt -< 600 : st 3
I I
V....::'l:%
f'l:;
/1-'::
I"\.'"\.
1\.11\.
III
relief area A
1000
1--
100
H-i [m L )
10
L01Y
~t/
~
/
1
1::2'
Pred,max
0.2bar
0.4bar
0.6 bar
0.8 bar
10 bar
1.5 bar
2.0 bar
I\.
......::
ij'"
Q11
volume of vessel V
[m 3 )
10
100
1000
Fig. 190. Nomogram for the determination of the pressure relief area for dust explosions in
vessels (Example: static venting pressure Pst a! = 0.1 bar)
Fig. 191. Safety membrane made out of plastic foil (left: before actuation; right: after actuation)
172
(Fig. 193). However, such ductwork will substantially increase the violence of the
explosion and the pressure in the protected vessel. This amplification of the course
of the explosion is caused by the influence of the secondary explosion in the vent
duct upon the explosion in the vessel proper.
Fig. 193. Vent ducts attached to the vent openings of filter housings
173
Upon actuation of the vent, the initially dust-free vent pipe will be filled with
unburnt dust ahead of the flame front. The explosible mixture will then be ignited
by the trailing flame jet from the protected vessel. The pressure build-up of the secondary explosion restricts the exhaust and markedly increases the reduced maximum explosion indices. The increase is especially pronounced if the flame velocity
in the vent duct reaches or exceeds sonic velocity.
This is always to be expected if the length of the vent duct is more than 3 m. The
reduced maximum explosion pressure with unobstructed venting determines the
increase of the pressure in the protected vessel with a vent pipe. The corresponding
values can be taken from Fig. 194.
Tests over the past years with various combustible dusts [105, 106] have confirmed that the correlation shown in Fig. 194 is not affected by the mounting of the
ducts to the vents of such equipment as sifters, vessels, filter housings, or mills. Because of the anticipated increase of the maximum reduced explosion pressure in
the vented vessel, either the vent area or the explosion resistance (pressure shock
resistance or explosion pressure resistance) have to be increased. It has to be at
least 0.5-1.0 bar for large vent areas and pressure build-ups in the range of the static vent pressure. Vessels with a lower pressure rating cannot be practically protected using explosion pressure venting through vent ducts. Vent ducts have to be as
short as possible and must lead in the direction of the discharge directly into an
open area.
Bent pipes result in an unforeseeable additional increase of the reduced maximum explosion pressure. In exceptional cases, bent pipes are acceptable if there is
a straight run for quite a distance immediately after the vent opening. The vent
pipes must have at least the same cross section as the vent area.
Around cross section is preferred. The explosion pressure shock resistance (or
explosion pressure resistance) of the pipe has to be equivalent to that of the vessel
c::::
d
..Cl
5.0
~
'5..
2.5
2.0
g;!
1.0
....c
'3
x
d
E
o. 5
1--
.---
----
.,..-
_r-
_f--
-.- ~.-
0.
0.2
.......
vent QiQe:
-lp>3m to 10m
--lp>Om to 3m
u
~
O.1
0.1
-------
0.4
0.6
0.8 1.0
1.5
2.0
174
to be protected. If there are inspection openings in the vicinity of the vent area,
they, as well as the closures, require the same design strength.
In designing vent pipes, one has to consider that dust explosions in pipelines
may be similar to detonations (Fig. 138). Pressures of 20-30 bar will then be
reached (Fig. 139) . Therefore, it is sensible to limit the length of the vent pipes to
approximately 6-1O-m. Otherwise extremely high pressures are to be expected at
the mouth of the vent pipe. The pressure rating of a pipe has to be at least 10 bar if
such a limitation cannot be maintained due to urgent circumstances. In case rupture panels are substituted with explosion flaps (doors) (Fig. 195) for the pressure
venting of the vessels, efficient venting may be limited by the mass of the flap, depending upon the violence of the dust explosion. Therefore, explosion flaps have
to be built as light as possible and be subjected to a performance test before being
used in practical applications. At the same time, the venting capability must be
compared with that of a rupture panel (Fig. 196). Any limiting influence can be met
by increasing the pressure rating of the vessel or the size of the vent area.
An increase in the static venting pressure may be caused by corrosion, improper painting of movable parts, icing, or snow loads. The venting device has to be
checked in predetermined intervals with respect to functional condition and mobility. Explosion pressure venting is used very frequently as a safety measure. The
175
venting efficiency =
A1
100 [0/1
/0
OJ
c...
III
III
l:l
Cl..
test data:
burs ting discs
c:
o
'Vi
.9
0..
~
E
I
I
-0
1:1
~
-0
Fig. 196. Determination of the venting capability of an explosion flap (door) for dust
explosions
--- 1"t
f~-
OJ
c...
A1
vent area
test value:
explosion door:
I A= A2
I
9
A2
A [m 2 J
pressure venting process not only consists of pressure build-up and flame propagation outside the vessel but also creates a recoil force (Newton's force of reaction
principle). Such a force may pull vessels or equipment off their anchors, tip them,
and cause substantial secondary damage, even if the vessel is properly designed for
the given reduced maximum explosion pressure. VDI guideline 3673 "Pressure release of dust explosions" points towards the dangers which may be caused by recoil
forces.
Several publications deal specifically with the stated problem [107-110]. Ritter
uses a thermodynamic method for the calculation of the recoil force which makes
allowances for the vent flow [108]. Experimental results have led to the following
equation, which is based on a static venting pressure pstat = 0.1 bar for a vent system
consisting of a safety membrane or rupture panel.
FR
pred.max
patm
IX
The value of the dynamic coefficient fluctuates in line with the test arrangement.
For a rigid support of vented vessels having sizes V = 0.25-25-m3 , the range of
IX = 1.19-1.21. For a flexible support, as it may exist for vessels mounted to the ceiling of a manufacturing building, the dynamic coefficient for a 1O-m3 vessel was de-
176
termined at ex = 1.13. The experimentally determined value of the recoil force per
area is therefore in the middle between the calculated values using the thermodynamic approach and the stationary approach, which ignores the vent flow
(Fig. 197). This is not valid for vent pipes which are downstream of vent openings.
In such a case, the values from the stationary method will be approached. Such a
phenomenon may be explained by the flow restrictions given by the vented vessel.
The recoil forces are independent of the kind of combustible dust; however,
they are influenced by the dust-specific Kscvalue, which reflects the pressure behavior per time the explosion takes in the vented vessel.
For a given dust and a defined vessel size, the reduced maximum explosion
pressure decreases hyperbolically with increased vent area. Recoil forces, however, behave differently. They first increase and reach an "optimum recoil force"
for an "optimum vent area" and then decrease with increasing vent areas. For
several dusts, it was found that the corresponding reduced maximum explosion
pressure amounted to Pred,max = 3.3 bar.
For very large vent areas and direct vessel venting, the reduced maximum explosion pressure approaches more and more the static venting pressure. Therefore,
the recoil force will reach a minimum and thereafter increase proportionally with
the vent area. The so-called "optimum recoil force" will not be reached with designs based upon the VDI guideline 3673 "pressure release of dust explosions" and
with no vent lines since the nomograms are restricted to a reduced maximum explosion pressure pred,max = 2 bar because of already-stated reasons. With existing vent
lines, however, depending upon their length, the optimum recoil force may be
1000
-E
:z:
500
--
0:::
LL
OL...-o'------l..-_ _---l
10
177
reached or exceeded for oversized vent areas. For more details pertaining to recoil
forces, consult the listed publications. Figure 198 shows a spray drier protected
with explosion pressure venting. Fluidized bed driers are also often protected with
the design safety measure "explosion pressure venting". In accordance with outline 5.1, they have to be explosion-resistant for a certain reduced maximum explosion pressure. As the first basic explosion tests were made more than 10 years ago,
it was necessary to confirm the earlier results [111,112]. In particular, the influence
of the shape of the vent pipes upon the course of dust- and hybrid explosions was
studied in a certain fluidized bed drier to be protected.
The test results coincide with the requirements of the safety rules issued by the
"Berufsgenossenschaft" [113] with regard to size of the vent area and explosion resistance of the apparatus subjected to dust explosions. In addition, it was found
that:
- the product filter (filter bag) will only amplify the explosion if there is no vent
pipe (Figs. 203 and 204)
- a vent pipe with enlarged cross section will not improve the venting process
- the reduced explosion pressure in the fluidized bed drier linearly increases with
the length of the vent pipe and in the absence of a product filter will follow. the
VDI guideline 3673 "pressure release of dust explosions".
178
Fig. 199. Fluidized bed drier with vent pipe without change in cross section
Fig. 200. Fluidized bed drier with vent pipe having enlarged cross section
- a reduced cross section (Fig. 201) markedly elevates the reduced maximum explosion pressure to a much greater degree than a bend in the vent line (Fig. 202).
In conjunction with hybrid explosions, it was found [112] that the area requirements called for by the "Berufsgenossenschaftliche" safety rules [113] are not suffi-
179
Fig. 201. Fluidized bed drier with vent pipe having reduced cross section
Fig. 202. Fluidized bed drier with vent pipe with bend
cient. This can only be alleviated by increasing the vent size and, if not possible, by
increasing the explosion resistance of the apparatus to be protected.
Mechanical mills are always to be considered as possible ignition sources for explosible dust/air mixtures as per today's knowledge. This is also true for non-inerted coal pulverizers, in which an ignition of the coal dust mixtures has to be ex-
180
Fig. 203. Dust explosion in a fluidized bed drier without filter bag and vent pipe
Fig. 204. Dust explosion in a fluidized bed drier with filter bag and without vent pipe
pected. The results of dust explosion tests [114] in an initially unprotected pulverizer with volume V = 8_m3 have shown that the system will survive the explosion
without damage, provided coal dust has a maximum explosion pressure pmax :::;8.1
bar and a dust -specific characteristic KSI :::; 105 bar m/s. The large inserts and the
venting through three pipes must restrain the explosion from full development.
181
Low values have been recorded in the pulverizer proper as well as in the feeder
[Pred,max :s 1.2 bar; (dp/dt)red,max :s 16 bar/s]. Substantial flame propagation and
escaping combustion gases mixed with unburnt dust/air mixtures were observed at
the mouth of the coal dust pipe.
An explosion with a more violently reacting coal dust (Pmax = 9.4 bar; Ks! = 185
barm!s), however, resulted in a pressure of pred,max = 2.4 bar in the housing,
deforming the inspection doors, and a pressure of pred,max = 2.5 bar in the feeder,
leading to its destruction (Fig. 205).
In order to remedy the situation, a suitable vent opening was installed on top of
the feeder (Fig. 206) which was closed with a safety membrane [115]. Such modification not only markedly reduced the explosion characteristics in the pulverizer
with the less violently reacting coal dust (Fig. 207), but it also withstood the explosion of the violently reacting coal dust, even with a vent pipe attached to the vent
opening.
The above statements may certainly not be generalized. They show, however,
that cost-efficient design solutions may be found from properly conducted tests
which improve certain unprotected systems.
182
The development of the VDI guideline 3673 "pressure release of dust explosions" (Fig. 190) was based upon the assumption that the cubic law was not only valid for closed apparatus (Fig. 64) but also for vented apparatus.
V
( ~)
dt red.max.vl 1
1/3 -
and
A2
(V2)
VI
2/3
A1
(~)
1/3
dt red,max.v2 2
183
In other words:
- the product of reduced, maximum rate of pressure rise times the cube root of
volume is constant and
- for a constant reduced maximum explosion pressure referenced to a given static
venting pressure, the vent area A2 for a volume V2 can be calculated from the
known areaA] of volume V].
The results from explosion pressure venting tests from vessels V = 2.4-250-m3
(Fig. 208) with combustible dusts confirmed this only conditionally [104].
It was shown that with increased vessel size:
for dusts belonging to the dust explosion class St 1 (Ks! :::; 200 bar m/s) , the area
requirements increase more rapidly and the reduced maximum rate of pressure
rise decreases more slowly than projected with the cubic law.
the same statement is true for dusts belonging to the dust explosion class St 2
(Ks! :::;300 barmls) for vessel sizes V <25-m 3 . For larger vessel sizes, however,
the area requirement and the explosion violence follow the cubic law.
184
As a consequence (Fig. 209), the area requirements of very large vessels (V>600
m3) at a given reduced maximum explosion pressure are independent of the dustspecific characteristic K st and probably follow the cubic law.
This phenomenon may possibly be explained as follows: The amount of initially
unburnt dust which is pushed out of the vent opening, ahead of the flame front, is
much larger for dusts belonging to the dust explosion class St 1 than the one for
dusts belonging to class St 2. This is documented by film sequences showing venting
action. Therefore, the secondary explosion initiated in the free atmosphere by the
departing flame is much more severe for St 1 dusts than for St 2 dusts. Pressure
measurements outside the vessel point also in that direction. Therefore, it is conceivable that the pressure produced by the dust's secondary explosion will obstruct
the venting process and raise the level of the reduced maximum explosion
pressure.
This is more pronounced for less violently reacting dusts of the dust explosion
class St 1 than for the more violently reacting St 2 dusts and may therefore explain
the behavior of the area requirement in Fig. 209. These statements are based on a
maximum explosion pressure Pmax = 9 bar, whereas the nomograms of the VDI
guideline 3673 [55] allow Pmax = 10 bar. A comparison of the area requirements is
possible in Figs. 210 and 211 for two constant values for the reduced maximum
explosion pressure.
185
10 lN
01
d
QJ
<d
10.0
4-
eQJ
>
10
01
10.---------------------~--~
p"".~. O.5b~ , /
N"
oS
to
:/.
r/./
<!J
<d
.....
e
-J;.
0 VOl 3673:Pmax=10bar,KSt=ZOObar.mts
. , / . Test results:Pmax = 9bar,Kst=ZO barmts
O.1L-.:;...-----I-----.l...------J
10.-------------------------~
oS
1.0
<!J
<d
.....e
<!J
>
10
100
Volume V
lm3)
1000
186
'ceJ."~oO.5b"
/ "
~?~
<l: 10
V).:.
///
6'~.
.4 Test
CI
1:
~0.1-
Ll VDI3673
10
Pred,max =1.5 bar
.s
<l: 1.0
CI
OJ
L-
CI
c:
OJ
>
0.1
10
Volume V
100
lm 3)
1000
The reduction in area requirements, especially for smaller vessels, in comparison to the VDI guideline is most pronounced for dusts belonging to the dust explosion class St 1 (Fig.21O) which includes a majority of the dusts tested so far
(Fig. 87). The area reduction decreases with increased vessel volume and lies between 41 % and 5 % . For dusts belonging to the dust explosion class St 2 (Fig. 211),
an area reduction is possible for the whole range of volumes. The reduction decreases slightly from 50 % to 36 % .
In order to transfer the results from the newer explosion pressure venting test
into practice, all vent areas for a constant reduced explosion pressure were calculated for volume VI = 1-m3 and tabulated (Table 21). For any given vessel size V 2,
shown in column 3, the required vent areaA2 can be calculated as follows:
It must be emphasized again that the equation is only valid together with Table 21
if the maximum explosion pressure of the dusts does not exceed pmax = 9 bar and
the static venting pressure amounts to pstat = 0.1 bar. If the maximum explosion
pressure of a dust is more than pmax = 9 bar, then the calculation of the necessary
vent area has to be in accordance with the nomograms of the VDI guideline 3673
"Pressure release of dust explosions" [55] (nomograms, see Addendum 8.1.1).
187
Table 21. Specific vent area, referenced to V I = 1-m3 , as the basis for the calculation of
vent areas for vessels exposed to dust explosions. (Maximum explosion pressure Pmax =
9 bar, static venting pressure of safety membrane psta, = 0.1 bar)
2.0
Pred.max [bar]
pmax
KSI
[bar]
[bar m/s]
9.0
200
9.0
300
1.5
I::sV< 6
6::sV< 18
~ 18
1.0
0.5
0.25
0.089
0.096
0.110
0.140
0.160
0.120
0.150
0.160
0.180
0.240
0.127
0.142
>0.17
>0.20
0.240
Al [m 2]
0.048
0.048
0.058
0.081
0.081
0.056
0.058
0.063
0.089
0.089
0.068
0.072
0.Q75
0.068 0.079
0.068 0.079
0.084 0.098
0.096
0.096
0.120
0.110
0.110
0.170
188
189
(roof) of an oblong vessel (silo) represents the largest possible vent area A 2 , the
maximum volume V 2 which can be protected with such an area can be calculated
from the cubic law:
The area requirement Al for the volume V = I-m3 can be taken from the nomogram.
The reduced maximum explosion pressure pred.max and the static venting pressure
Pstat of the venting device coincide for both vessels (VIand V 2); they are given and
therefore constant. The consequences from the equation for the maximum allowed
silo height for dust explosions are shown in Fig. 214 for two silo diameters (D = 4
mand D = 6-m). For a height H :55D (e.g., D = 4-m, H:520-m; D = 6-m, H:530
m), the nomograms are applicable without restrictions. For a height H >5 D (e. g.,
D = 4-m, H >20-m; D = 6-m, H >30-m), the whole roof area ofthe silo has to become the vent area. The maximum height and with it the maximum volume of the
silo to be protected will increase with increased pressure resistance of the vessel.
For dusts belonging to the dust explosion class St 1 and for a static venting pressure
Pstat = 0.1 bar, the height of the silo is only limited in case the volume of the silo exceeds lOOO-m 3 (e.g., D = 4-m, H 2:80-m; D 6-m, H 2:35-m).
The recommendations of the VDI guideline 3673 "Pressure release of dust explosions" are based on knowledge pertaining to the course of an explosion of combustible dusts in pipelines. Other basic experimental facts were unavailable at the
time the guideline appeared. With 20 % of the incidents, silos and bunkers repre-
..
::J:
.9 50
.iii
'ts
-<-
..c
.Ql
QJ
..c
cubic vessel:
nomograms apply
cylindrical vessel:
entire roof area used
for venting
V,,1000m3:
height of silo not
acceptable
0
4m
diameter of silo 0
6m
Fig. 214. Influence of the explosion resistance of silos upon the silo height when using nomograms
190
= 6.25)
191
sent the largest group involved in explosions (Figs. 6 and 7). Therefore, in 1981,
dust explosion tests were started in vented silos V = 20-m3 (height/diameter ratio
6.25) in order to obtain information about the actual course of an explosion in a
horizontal (Fig. 215) or vertical arrangement (Fig. 216) [116-119]. The mixture was
tested in accordance with the agreed-upon procedure [55], utilizing rapid dispersion of the combustible dust out of a dust storage chamber plus initiation of ignition
after a predetermined delay time with pyrotechnic ignitors having an energy content E = 10,000 J.
While the reduced maximum explosion pressure decreases linearly in a vented
cubic vessel with decreasing filling ratio (Fig. 217), such a decrease is noticeable
only for a filling ratio <50% in the horizontal silo. This is caused by the unburnt
mixture which is pushed ahead of the flame front. This is also the cause for the
higher explosion violence in a silo compared with a cubic vessel.
The arrangement of the silo also has a major influence upon the explosion behavior. The maximum flame velocity increases with increased vent area A (Fig. 218),
as anticipated. However, it is markedly lower for the vertical silo than for the horizontal arrangement due to the force of gravity.
The reduced maximum rate of pressure rise shows just the reverse behavior
(Fig. 219). The values stemming from the horizontal silo are generally lower than
3~1~------~-------'
cubic
vessel
3.0
c::
o
siloWD=6.25
.0
~ 2.0
E
~CJ..
Cellulose
V =20m l
A =02m 1
1.0
fi;tafO,1baf
40.---------..r.-----,
Fig. 217. Comparison of reduced maximum explosion characteristics at partial filling with dust/air mixture
degree
[%)
100
192
KSt=135-241 bar"",
arrangement
50
0~------~--------~2
Fig. 218. Influence of the silo arrangement upon the flame velocity Vex,max
30~--------~---------'
Vl
'd
..0
20
--
"D~
aJ
..-f-"D
Cl...
10
"D
averages
the ones from a vertical arrangement. These are the reasons why different area requirement curves exist for every dust tested which depend upon the silo arrangement and the location of the ignition source. Figures 220 and 221 show the "composite area requirement curves" for wheat and corn starch dusts in a silo in comparison
with the ones determined in a cubic vessel.
For small area venting (A <0.4-m2) the reduced maximum explosion pressure
in the silo is lower than in the cubic vessel, independent of the dust type, because
once the dust explosion is initiated, the flame reaches the cooling wall of the silo
193
3r-~'----'--------'--------'--------,
CI
-0Ol
<....
a.
OO~------~O.~5-v-e-n~t:a~r~ea~1P:A::~[m~2=1==1~.5~====~~
3r---~'--'--------'--------'--------,
2
<....
CI
.0
X
CI
-o-
ct
Fig. 221. Corn starch: consolidated area re,\uirement
curves (V = 20-m ,
Pstat = 0.1 bar)
00
Q5
to
vent area A [m2 ]
1.5
20
much more rapidly. For large area venting (A >0.4-m2), however, the values of the
reduced pressure are markedly higher in the silo than in the cubic vessel, the more
so the higher the dust-specific characteristics.
Silos, therefore, have larger area requirements than cubic vessels. The demand
of the VDI guideline 3673 "Pressure release of dust explosions" [55] to allocate the
whole roof of a silo for the pressure release system is therefore justified. In such a
case (A = 2.0-m2), the pressure developed by the weaker-reacting wheat corresponds approximately to the static venting pressure of the venting system. For the
more violently reacting corn starch, such pressure is 400 % higher. This can only be
194
Fig. 222. Solidly cast, reinforced concrete cover as the vent arrangement
on top of a silo
FIg. 223. Hinged, reinforced concrete cover as the vent arrangement on top of a silo
195
196
Source of ignition
t:'
.0
fil m, Pstat
OL-______
= 0.1 bar
o
-L-ll~
os
______~__________~________~
1.0
1.5
2.0
A [m 2 ]
vent area
Fig. 225. Vent efficiency of reinforced concrete covers as the vent arrangement on top of a
silo
15
/0
o...-p~
/6/t'\
I6 I\ 60
..0
i-
-u
OJ
<D-
<d
1.0
.-l-9~
o Q =15.8m3Jmin
Q =13.4m 3! min
to. Q =11.3m3! min
0.5
30
I
I
I
I
I
I
/~~o
<-
..0
"0
OJ
20
<-
:;:::-
I
I
D-
::s
L.
10
'Il 12,5 15
20
197
At first, the direct conveying of the product into the silo will be analyzed. As
shown in Fig. 226, there exists an optimum for the reduced explosion indices at an
optimum material-to-air loading ML and a chosen air volume Q. The reduced explosion indices have a linear correlation with the air volume (Fig. 227). Through extrapolation, an air volume Q = 21 m 3/min corresponding to a feed velocity v = 45
rnIs will result in the same values obtained using the VDI dust dispersion procedure. The optimum material-to-air ratio is independent of the chosen vent size.
Figure 228 compares the pressure/area curves obtained in the silo using different
dust dispersion procedures with the ones measured in a cubic vessel of equal size.
Except for very ~mall vent sizes, the reduced maximum explosion indices
obtained with pneumatic conveying are markedly higher than the ones obtained in
cubic vessels, but slightly below the ones gained from using the VDI dust dispersion
procedure in the silo. Therefore, the reduced explosion pressure (Pred,max = 0.32
bar) reached with direct filling using the whole silo top as a vent area will be 167 %
higher than in the cubic vessel (Pred,max = 0.12 bar). These figures are referenced to
an air volume Q = 15.8 m 3/min. Once increased to approximately 21 m 3/min, the
area requirement curve will coincide with the one valid for the VDI dust dispersion
procedure. In that case, the pressure generated in the silo (Prcd,max = 0.51 bar) will '
be 325 % higher than in the cubic vessel. This has to be considered when the explosion resistance is chosen for the silo to be proteced.
2.0 . - - - - - - , - 1 - - - - , - - 1 - - - ,
+-
~
0.
-0
I-
10-
10
1S
20
I
1
225
198
Pmax
9 bar
KSt =226 bar ml
Pstat = 0.1 beir
'd
x
d
"'(j
QJ
'0..
--
40 , - - - - - - - - r - - - - - - , - - - - ,
VJ
'-
30
20
L\
"'(:f
_ 10
"
~
:3 0
\,,
~-6 _
1
venting area A
_ _ b.
[m 2 j 2
25
Fig. 228. Direct filling of corn starch: Influence of the dust dispersion procedure and
the vessel shape upon the reduced maximum explosion indices relative to vent
size A
199
If the product is fed from a cyclone through a rotary air lock into the silo
(Fig. 229), then there will be a pronounced reduction in the reduced maximum explosion indices, in comparison with direct pneumatic filling.
Therefore, it is possible to show the influence the dust dispersion procedure has
upon the occurrence of an explosion (Fig. 230).
The figure documents the already-stated differences between the VDI dust dispersion procedure and direct pneumatic filling. The first-mentioned procedure
has some inherent reserves, provided that the air volume Q given in Fig. 226 and
227 is not exceeded. But it also shows the major reduction in explosion violence
once the product is fed from a cyclone through a rotary air lock into the silo. The
resulting measured reduced explosion indices correspond approximately to the
ones obtained in a cubic vessel of equal size (V = 20-m3) with the same relief area
(A = 1.27-m2 ) [Pred.rnax = 0.22 bar; (dpfdt)red,rnax = 3 barfs]. In using the outlined
system instead of direct pneumatic filling, the required explosion resistance for the
silo can be substantially lowered and costs saved. This is also confirmed by observations made on silos after dust explosions.
In this context, reference is to be made to yet unpublished test results for the
determination of the lowest minimum ignition energy (LMIE) of hard-to-ignite
granules with a few weight percent of fine particles in the 20-m3 silo. The minimum
ignition energy required by the dust cloud generated by direct pneumatic filling is
ten times the value of the LMIE of the fine dust because of extreme turbulence. If
the product is filled into the silo from the cyclone through the rotary air lock, however, the minimum ignition energy of the dust cloud is identical with the LMIE of
the fine dust because of the low turbulence.
1.2 , - - - - - - - - - ,
24.-----------~
Pmax
KSt
A
Pstot
VI
::
d
..0
..0
" 9 bar
=226 bor,mis
=1.27m 2
=0,1 bar
0.6
x
d
-0
~
CL
O~~-iLL-LLL------
CAB
__~
C
A = VOl- procedure
B = pneumatic conveying
C= filling via a cyclone
Fig.230. Influence of the dust dispersion procedure upon the reduced maximum explosion
indices (20-m3 silo, corn starch)
200
In summarizing, the following can be stated: The dust cloud generated by direct
pneumatic filling of the silo will be much harder to ignite with an extended capacitor discharge, and the reduced maximum explosion indices will be higher than the
ones obtained when filling from a cyclone through an air lock.
Fig. 231. Wood dust explosion in pressure-vented pipeline (vent openings closed with safety
membranes)
201
0.2
L
Cl
.D
X
Cl
E_ 0.1
u
~
0.
0 ~--------~--------~--~
..8
12 [ otd =0.55 [
<.:
+-]-
:!2
.g-
.-/fi'
.td =0. 35
6-
':~ ~
~-
1
I
o~------~---------L--~
10
20
22.5
202
Fig. 234. Element for a bucket elevator with explosion panel: Corn starch dust explosion
203
204
~----------------------------.
~~------------------------~ CMU
equipment
possibly be the reason why such a protective measure is only slowly being adopted
by industry, regardless of its often-proven effectiveness in practice. Explosion suppression systems (Fig. 236) consist of a detector system which senses the start of an
explosion, the pressurized container with the extinguishing media and a valve
which is activated by the pressure sensor through a control-monitoring unit. The
extinguishing media are dispersed into the protected vessel in as short a time as
possible in order to reduce the expected maximum explosion pressure to a substantially lower level (Fig. 237). Explosion suppression systems have a built-in monitoring system and maintain their function for a given time after power failure.
The control and monitoring unit has the following assignment:
- start-up of the total explosion suppression system
- safety shut-down of the process equipment protected by the suppression system
in case of an explosion
- power supply, either from main system or emergency battery
- monitoring charging current for emergency battery
check of external wiring inclusive of ground fault monitoring
- automatic fault annunciating
- optical and acoustical alarm at activation of the explosion suppression system
- monitoring the pressure sensors for proper function.
The detectors which trigger the explosion suppression have to be capable of following the starting explosion sufficiently rapidly and without too much inertia.
There are three types of detectors:
thermoelectric detectors
- optical detectors
- pressure sensors
The first two types are unsuited for use with explosion suppression systems on vessels because they have to be installed close by the ignition source or else the dust
205
p =activation pressure of
a suppression system
'd
..0
c::
o
Vi
D..
x
OJ
course of
suppressed explosion
time
[ms]
Fig. 237. Pressure behavior versus time for a normal and "suppressed" dust explosion
cloud which appears between the detector and the ignition source will absorb some
of the radiation. Such action will delay the signal and result in too late an activation
of the suppression system.
Since the explosion pressure of a starting explosion propagates uniformly at the
velocity of sound in the vessel, the pressure sensor is the most suitable device. Such
sensors (Fig. 238) register with ample safety a starting explosion at a pre-set pressure and can trigger via the control unit the ignition impulse for the valve of the extinguishing container. They have proven themselves amply in industrial practice.
The pressure sensors which activate the explosion suppression must be insensitive to the vessel contents and especially to external influences (shock, vibration).
Therefore, they are normally used in pairs, i.e., two sensors offset by 90 have to
206
reach simultaneously the activation pressure for the system. This should also be
verifiable. The pressure sensors have to be deactivated before a vessel entry takes
place and they must be secured against accidental tripping. The extinguishing containers must fulfill all rules and regulations applicable for the user and be designed
in accordance with the technical guidelines.
The containers are equipped with fast-acting valves which will open the full
cross section within milliseconds after the activation signal is given. They are designed in such a way that the whole content of extinguishing medium will be uniformly distributed in the protected vessel within as short a time as possible. Such
requirements are met by the extinguishing containers shown in Fig. 239 and 240,
which can be described as:
- 5-1 container with rise pipe and two 3/4" valves activated by blasting detonators
- 5-1 container with a 3" valve activated by a line-cutting charge.
Both containers are filled with 4 kg of extinguishing medium. The large amount of
driving medium (nitrogen) provides an optimum dispersion of the extinguishing
medium inside the protected vessel.
The pressure of the driving medium is as follows:
3/4" system PN 2 = 120 bar
3" system PN 2
60 bar
207
Fig. 240 alb. 5-1 extinguisher with a 3" valve a) container b) hemispherical nozzle for dispersion of the extinguishing medium
208
Through the special arrangement of the nozzles (Fig. 239 and 240), a uniform distribution of the extinguishing medium is guaranteed. Special attention has to be
given to the proper functioning of the hemispherical nozzles, which must not be
affected by operating conditions, especially product accumulations.
The hemispherical nozzles which distribute the extinguishing medium penetrate into the protected vessel in the suppression arrangements described so far.
This is often unacceptable for practical applications, especially if the equipment
which processes combustible dusts is subjected to frequent product changes. For
such cases, movable hemispherical nozzles or so-called telescopic nozzles
(Fig. 241) are to be recommended. At first, the hemispherical nozzle is outside the
vessel to be protected and separated by a membrane. In case of an explosion, i.e.,
once the fast-acting valve of the extinguisher is activated, the nozzle is propelled
forward by the pressure of the driving medium, destroying the membrane and initiating the extinguishing action. The mechanical process results in a delayed start
of the extinguishing, which in turn causes an increased reduced maximum explosion pressure in the vessel (which generally is within an acceptablerange). The connecting lines between the valve of the extinguisher and the hemispherical nozzle
which disperses the extinguishing medium has to be as short as possible and sufficiently pressure shock-resistant.
In case longer lines are needed because of technical reasons (especially in conjunction with the 3/4" systems), then the length should not exceed SOO-mm, otherwise the extinguishing efficiency will be reduced.
Both explosion suppression systems have practically the same extinguishing efficiency using a powdery extinguishing medium for incipient dust explosions. For
130 mm
209
a given combustible dust, there exists basically a correlation between the activation pressure of the suppression system and the reduced maximum explosion pressure prod,max, as shown in Fig. 242. The reduced maximum explosion pressure is the
pressure at optimum combustible dust concentration which will exist in the protected vessel after the activation of the extinguishing system. A rising activation pressure pa results also in an increased reduced maximum explosion pressure Pred,max'
An extinguishing medium will be classified as "very good" if an increase in the activation pressure will result in a minimal rise in the reduced maximum explosion
pressure. Only extinguishing agents with the best effectiveness fulfill such a requirement.
In general, a dust explosion may be considered successfully suppressed if the
maximum explosion pressure pmax is lowered to a reduced maximum explosion
pressure pred,max = 1 bar, with an activation pressure Pa = 0.1 bar. This means that
the vessel and the equipment which are protected by explosion suppression have to
be built explosion-resistant for a 1 bar range in accordance with paragraph 5.3.1.
The following extinguishing agents are used in practice:
- halogenated hydrocarbons
water
- extinguishing powders, and most recently
- hybrid extinguishers.
Basically, it is also possible to use halons in conjunction with explosion suppression
systems for fighting dust explosions. They are liquid extinguishers which will evaporate in the protected vessel once discharged from the container. The prerequisite
for halon use is that the extinguishing agent be dispersed very quickly after the start
of ignition. This calls for a relatively low activation pressure (Pa <0.1 bar) in order
to have a successful explosion suppression. This unfortunately may lead to accidental triggering because of pressure fluctuations in the ongoing process. Also, some
shortcomings became known which may make the application of halon suppression systems problematical. If, for instance, halon is dispersed too late into the ves-
c
o
o
'Vi
D..L
x
d
ClJ.n
-0
QJ
0..'-
-oQJ
QJ'u~
~ ~
'1:JQJ
QJ''- 0..
4-
'x
d
5'--'1--~1---'-1-'1---1'--'1--'
3-
./
effective
extinguishing
agents-
r----T"~: ~------
2 '-
//
less effective
extinguishing / agenfs
./
~-----
OL-~I
0,1
___IL-_L-I~I___L-I~I__~
Q4
0,2
0,6
OS
07
OJ
210
number of 5-1J
extinguishers
OJ
211
100 ,----,---,--,-----,--,----,
50
.~
::J
D1
C
-+-
25
10~--+_~~_+--~~_+~
z
L
QJ
f--+----+~.rr--+-__t-,---I
2. 5 t-----bo'~-.
.0
::J
C
Fig. 243. Suppressant requirements for the explosion suppression of propane and dusts
2.5
10
25
50
100
volume of vessel V [m 3]
Table 22 gives the minimum number of 5-1 extinguishers required for the protection
of a vessel size V 2.
The number of extinguishers which is calculated from Table 22 has to be rounded to the next higher figure. The extinguishers also have to be distributed as evenly
as possible on the surface of the vessel to be protected. The figures in Table 22 indicate some limitation for the use of an explosion suppression system for dust explosions. This limit is set by the dispersion velocity of the extinguishing agent of a multiple of 10 mls. Based on present knowledge, suppressant systems can be effectively used for the protection of vessels against dust explosions, if the Kscvalue does
not exceed 300 bar mls. Dusts having a greater explosion violence (aluminum dust
K st >300 barmls) may not be effectively suppressed in vessels over the whole
range of concentration. At the most, the protective system may restrict the explosion limits up to a dust concentration which will result in explosion indices which
remain below the stated limit for application.
Table 22. Minimum requirements of suppressants for an explosion suppressant system (Pa
~
Dust
explosion
class
Number of
5-1 extinguishers
N2
Minimum explosion
resistance of the vessel
[bar]
St1
1.08 V?3
0.5
St2
1.40 Vl
1.0
l3
212
In applying the above-outlined system with 5-1 extinguishers for the protection
of 100-m3 or 200-m3 vessels, between 23 and 48 containers are required, depending
upon vessel size and dust explosion class. Not only the number of extinguishers but
also their installation will cost considerably. Therefore, systematic tests were made
in vessels of 1O_m3 , 25-m3 , and 250-m3 in order to improve the effectiveness of the
original suppression system [127]. The size of the container as well as the diameter
of the valve with the line-cutting charge were increased systematically (Fig. 240).
Such a developement culminated in a 45-1 extinguisher with a 5-inch valve
(Fig. 244). The capacity is 35 kg of extinguishing agent on the basis of ammonium
phosphate, which uses nitrogen as the driving medium at a pressure of PN2 = 60 bar.
The explosion suppression tests were successfully concluded in a 250-m 3 vessel
(Fig. 245). The results are shown in Fig. 246.
Also, the large vessel shows the expected correlation of activation pressure pa
of the improved suppression system with the reduced maximum explosion indices
(Pred,max; (dp/dt )red,max> respectively). A successful suppression of a dust explosion
requires 7-10 45-1 extinguishers, depending upon the dust explosion class. The reduced maximum explosion pressure remains below Pred,max = 1 bar even with a relatively high activation pressure Pa = 0.2 bar. In using the original suppression system, at least 43-56 5-1 extinguishers would have been required for the same suppression result. The new, improved explosion suppression system allows a substan-
213
10
0.8
I-
'-
B
x
06
I-
0.4
I-
02
I-
,:f
QJ
'-
D..
x
d
E
-0-
/.
"Xl extinguishers
I-
6 l-
41-
D..
"0
2100
QJ
'-'-
10
.0
.~o~
~~~
0
Vl
.......
'-
.st2d", P=':~'k
___
7extinguishers
o~tingUishers
____6
-
6---01
I
02
activation pressure Pa
03
[bar]
214
tial decrease in extinguishers for the fighting of dust explosions. As shown also in
Fig. 246, the suppression of a propane explosion requires less extinguishers than a
dust explosion. This is due to the course of the explosion. In the large vessel, the
explosion pressure of the ignited, turbulent dust/air mixture increases at first
slowly and then reaches the final pressure quite rapidly.
For the propane/air mixture, however, which is ignited in a quiescent state, at
least 600 ms pass until a noticeable pressure is detected which will trigger the suppression. If this does not happen, then another 400 ms pass until a rapid pressure
rise occurs towards the end of the combustion, which will result in the high gas-specific Ka-value.
The results from these systematic explosion suppression tests in vessels having
varying sizes again show that the well-known cubic law determines the extinguisher
requirements per vessel size. Figure247 documents that the improved explosion
suppression system allows a 80 % reduction in the number of extinguishers needed, based on the customary system to successfully fight dust explosions. Thus, the
application of the explosion suppression system is not only made easier, especially
for larger vessels (V~10-m3), but also the installation cost is reduced.
60
40
t>.
Vl
<-
5.41_extlngUIShe/r
with 3" - valve
OJ
..c:.
Vl
5
en
20
J: :
:.;::
~ 10
z:
Z 9~ t>.
1'1'
1
with
/-
iLA
10
I
100
'" Propane
5'~valve
: N =1.0SV3
1000
[m3 ]
A Propane
. N=0.13-V3
o St1-dusts : N=1.0SV3
St1-dusts: N=0.1SV3
o St2-dusls : N= 1.40.V3
SIZ-dusls . N= 0.25V3
215
216
flame
d~tector
valve activated by
detonator
amplifier
\
:--------0---------
container for
extinguishing medium
fan haped nozzle
/
toIon source
/
Ignl
pressure drop in pipelines. The effectiveness of the barrier hinges upon the detection of the dust explosion in the pipeline with a suitable detector. Its signal is amplified by the control unit (Fig. 236), which will open the fast-acting valves of the extinguishers, thereby freeing the path for the extinguishing agent, which will be dispersed inside the pipeline through a nozzle arrangement. An optical flame detector
(Fig. 251) is the most suitable device for such a barrier arrangement since the propagating flame from the explosion has to be detected and extinguished. Due to the
intense flame which is generally found in dust explosions, one can use daylight-insensitive flame detectors. A possible penetration of daylight into the pipe will
therefore not cause a false activation.
It is necessary to flush the optical lens with gas in order to keep it dust-free.
Pressure detectors are not suited for the case on hand because there is no distinct
separation between the pressure and flame fronts for explosions in pipelines.
217
To store the extinguishing agent, the same containers are used as for explosion
suppression (Fig. 239):
- 5-1 extinguisher with one 3/4" valve, filled with 2 kg of the most suitable agent;
used in pipelines with smaller cross sections (DN :::;400 mm)
- 5-1 extinguisher with two 3/4" valves , filled with 4 kg of the most suitable agent;
used for pipes with larger cross sections (DN ::::::500 mm)
As extinguishing agent, a powder based on ammonium phosphate is preferred.
The containers are pressurized with nitrogen as the driving medium at PNZ = 120
bar. The use of halons gives the same adverse effects as described in conjunction
with the safety measure explosion suppression. Vertically arranged fan-shaped
nozzles are used for the dispersion of the extinguishing agent (Fig. 252).
Intensive studies have shown (Fig. 253) that the suppressant requirement at the
barrier location must be adjusted linearly with the flame velocity. Especially at
high velocities, the extinguishers with the 4 kg content are more effective than the
ones with 2 kg. For a given flame velocity, the required amount of extinguishing
agent per cross section (m 2) is constant in order to force the disruption ofthe explosion, independent of the pipe diameter. Based upon this, the figures for Table 23
have been generated giving the required number of extinguishers per flame velocity Vex and nominal pipe diameter DN.
218
-0
~~
150
5.41 extinguisher
dusts
.S<'!
o-E
1 3/4' valve
2kg powder
PN =120 bar
2
QJ-'--en
'--~
QJ~
~c
0.2
CL.....
U
100
/
i~/
+
enQJ
cV)
LV)
.!!1
III
CL
:::::10
en'--
:..&::QJ
QJ.o..
~O
'+a'+-
>,0
4--C'J
-----.,>
~E
el'--
:::::1QJ
O-CL
,e'"
5.41 extinRuisher
2 3/4" va ves
4 kg powder
PN2 =120 bar
"+
;e .
300
600
219
300
5-1 extinguisher
with
400
500
600
200
300
400
1
1
1
1
2
4
2
4
6
2
5
8
500
600
700
2
2
3
2
3
4
3
4
6
4
5
7
For the design of such flame barriers, the following may serve as a guideline: In
a 200-m-Iong pipeline having a 400-mm diameter, the flame velocity at the lO-m
mark, which is the location of the barrier, can be described as follows:
Dust explosion class
St 1 (K st :s 200
bar'm/s)
St 2 (Kst = 201-300 bar'm/s)
St 3 (K st > 300
barmls)
For small pipe areas, the values for the flame velocity move upwards; for large
areas, downwards. Figure 254 shows the explosion indices for combustible dust in
a 20-m-Iong pipeline with 400-mm diameter for an unhindered and an extinguished
explosion. The estinguishing barrier is located at the lO-m mark, with the flame detector at the I-m mark.
As can be seen, the propagation of the explosion flame is not only limited to the
zone between ignition source and barrier, as expected, but very violent explosions
or detonation-like behavior are stopped from occurring downstream of the barrier.
Figure 255 shows an actual installation of an extinguishing barrier in a vent
pipe.
The use of extinguishing barriers is by no means limited to pipes with small
cross sections. Applications with pipelines having diameters of 1400-mm-2500-mm
(Fig. 256) have shown that there are no problems in fighting coal-mine explosions
[methane explosions (Fig.257), coal dust explosions, methane/coal dust explosions1and also explosions with dusts belonging to the dust explosion classes St 1
and St 2.
The above-mentioned tests have shown, on one hand, that the required quantity for the extinguishing agent in large area pipe changes proportionately with the
expected flame velocity. Because of the proportional relationship between the
flame velocity and the explosion pressure (see sect. 4.5), there is, on the other
220
' Vi
.2
0.
'd
LJ
'x
d
E
c
0
OJ
0>
::J
Vl
~
d
~ 0.
E
::::J
E
20
without
extinguish ing
barrier
10
'::::J
.l!!
c
til
til
extinguishing
barrier at a
distance of 10m
0.
o 0.!----'-----:3~OO::-----6-:-:!OO.
K St
[bar,m/s)
Fig. 254. Pipeline DN 400, Ip = 20-m: Effectiveness of an extinguishing barrier against dust
explosions
221
222
The optimum explosion violence was reached once ignition was initiated in the
middle of the feed casing at the lS-m mark. The explosion developed fastest in the
feed direction, i.e., the extinguishing barrier located in the head of the elevator
was actuated first.
Due to their high content of large particles (M = lOOOfLm) and small content of
fines 3 wt% <63 fLm), un ground soybean-extraction grouts are not explosible. But
after conveying the product for several minutes, the fines were liberated and a selfpropagating explosion noticed. The same observations were made by pneumati-
l-
1/1
223
o Methane explosions
o
Cross section:
-
:: 5m2
Flame velocity:
~ 400m/s
51- extinguishers with two
3/4" - valves
ammonium-phosphate powder
224
cally conveying similar products into silos. The explosion violence which resulted
from adding a dust atmosphere to the product in the buckets was always in between
the results gained from the other two conditions. Therefore, these test results will
be excluded from the following discussions.
Optimum explosion characteristics are always reached in the feed casing
(Fig. 261), with an explosible atmosphere present, but without product in the buckets. The existence of the two extinguishing barriers substantially reduces both explosion characteristics, especially the maximum flame velocity in comparison with
the unrestricted course of the explosion. The pressure build-up in the boot is markedly higher than in the head (Fig. 262) because of the longer distance the explosion takes through the return casing. Such pressure again is markedly reduced by
the extinguishing barriers.
In general, the extinguishing barriers performed very well in all explosion tests.
They not only reduced the explosion characteristics in the various parts of the elevator, but also prevented an explosion propagation into the return casing. The test
results lead to the conclusion that bucket elevators which are protected with extinguishing barriers have to be built explosion pressure shock-resistant for 3 bar. This
obviously corresponds to an explosion pressure resistance of 2 bar. If the elevator
height exceeds 30-m, then additional barriers have to be installed every 30-m, with
optical flame detectors upstream and downstream of the barrier. In practice, obvi-
225
s.or-----,-------,
A 0
...Cl
2.5
~D..
o~--------~------~
200r-----.-------I+
226
ously the return casing has to be protected in the same manner. The number of 5-1
containers which is required for the design of extinguishing barriers can be taken
from Fig. 263 in relation to the casing diameter. Figure 264 schematically depicts
the layout of such barriers on a protected belt-and-bucket elevator.
In practice, a structure may be on top of the silo for weather protection. The
floor of said structure must be suitable for pedestrian and vehicular traffic for silo
inspection and cleaning. Therefore, it is generally not possible to route the vent
ducts from the explosion vent in the top of the silo to a safe space (Fig. 7). Tests with
an imitated vented structure on top of a pressure-vented silo (Fig. 265) proved that
such endangering can be eliminated by the use of HRD extinguishers (high rate
discharge) in the proximity of the silo vent (Fig. 266).
Three 10-1 extinguishers have been used, each equipped with two detonator-activated valves. The extinguishers are arranged at 120 positions and are filled with
7 kg of extinguishing agent on the basis of ammonium phosphate (propellant pressure PN2 = 120 bar). The extinguishing agent is again dispersed through fan-type
nozzles. The system is activated by an optical flame detector mounted in the silo
wall. With such an arrangement, which is also some kind of an extinguishing barrier, it was possible to successfully extinguish the flames in the area of the vent and
prevent the explosion from propagating into the structure. The flame originated
from a corn starch explosion inside the silo at optimum dust concentration.
The explosion pressure inside the silo was Pred,max = 0.5 bar, with a flame velocity Vmax = 250 mls. The pressure inside the top structure was only pred,max = 0.060.08 bar. Without extinguishers in service, the structure was destroyed at a pressure
of Prcd,max = 0.3 bar. From this, it was shown that due to the exhaust of unburnt
0
:z:
Vl
'-
~ 10
.~
::J
01
:>=
x
OJ
b
'-
OJ
.D
E
::J
:z:
o0
J
0.5
10
1000
400 600
800
diameter of the casing
[mm]
Fig. 263. Requirements for extinguishing barriers as a function of casing diameter (St 1 dusts,
explosion pressure shock resistance: 3 bar)
227
detectors
__________
-L-~_~L
228
dust/air mixture into the structure ahead of the flame front, a larger silo height will
be simulated . Figures 267 and 268 convey an impression of these tests .
The above statements have shown that extinguishing barriers have an outstanding effectiveness when used in pipelines (especially with large cross sections), in
229
elevators, and when used to prevent a silo explosion from propagating into a structure. Such a barrier not only limits the course and effects of an explosion, but also
markedly restricts the flame propagation.
ment or a vessel protected with design measures, then such a lock may act as a mechanical flame barrier against dust explosions, provided certain design features are
incorporated.
Early information about the propagation of ignition through narrow gaps
comes from the recent, not yet concluded tests made by Schuber [133]. He is using
a 42-1 ignition chamber for the start of a dust explosion. A circular gap with a given
length 19 and width w connects the ignition chamber with the surrounding free area
of a second I-m3 housing. The dust/air mixtures required for the tests are generated
in both housings by rapidly discharging the dust from pressurized dust storage
chambers (Fig. 270).
230
Fig. 270. Test arrangement for the determination of the ignition propagation of dust/air mixtures through narrow gaps
231
In a double logarithmic plot, the gap width w is a linear function of the product
lowest minimum ignition energy (LMIE) times reduced ignition temperature TI
(Fig. 271). This means that both characteristics which influence the ignition behavior of extended capacitor discharges and hot surfaces also affect the ignition propagation of dust/air mixtures. Dusts having a low ignition temperature and LMIE
(e. g., Lycopodium) also require a small maximum experimental safe gap w. If said
characteristics have a large value (e. g., coal) then the maximum experimental safe
gap will be accordingly large.
Figure 272 shows the influence of the gap length 19 upon the maximum experimental safe gap w. Obviously, such a value does not change proportionately with
the gap length, as with flammable gases and solvent vapors. Therefore, the maximum experimental safe gap cannot be increased with increased gap length. A maximum is reached, however, at a gap length of 19 = 40-50-mm, which depends upon
the type of dust and cannot be exceeded. This maximum is generally called the
"quenching distance". It also follows the same correlation shown in Fig. 271. For
gap sizes below the quenching distance but above the maximum experimental safe
gap, there is an explosion halt or stop in the gap area, while there is also a re-ignition of the exterior mixture by the hot gases. For gap widths larger than the
quenching distance, there will be an independent explosion propagation through
the gap.
With this, Schuber confirmed the present knowledge, which originated from
practical testing.
Rotary air locks will generally be safe against ignition propagation given the following criteria:
1) two vanes per side are engaged,
2) the vanes or the tips are made out of metal, and
3) the gap between rotor and housing is ::::::O.2-mm.
101 , - - - - - - - , - - - - - - - , 0 - - - - . , - - - - - - - - - , 0 - - - - - - - - ,
E
E
... -..
,..-.",.
A,.,."""-
.."",.-0
....,.,-: . .,..,.,...
.
........
.,."....
,..... .
__ --6~.",.
... _ - - - "",.".........
-'~'
~o
19 = 0 mm
olg= 15 mm
Alg= 50 mm
103
LMIE
TI +273
[mJ 1
273
Fig. 271. Combustible dusts: Maximum experimental safe gap as a function of the product lowest minimum ignition energy (LMIE) times reduced ignition temperature TI
232
~~"OOI dc""
-----1-
~
~~~~
~Lo.-o===o Lycopodium
oI
o
12.5
25
37.5
50
Methane
Fig. 272. Combustible dusts: Influence of the gap length 19 upon the
maximum experimental safe gap
This can be confirmed with information from Fig. 271. Sulfur, for example, has a
very low minimum ignition energy (LMIE = 0.5 mJ) and also a low ignition temperature (TI = 250C).
The product of LMIE times reduced ignition temperatures gives ~ 1 mJ, which
corresponds to a maximum experimental safe gap w = O.4-mm referenced to a gap
length 19 = O-mm (cross section of a circular gap with knife edges).
In case of an explosion, the rotary air lock has to be stopped immediately by a
suitable detector in order not to pass burning or glowing product which may cause
a second fire or explosion. Rotary air locks need not only be tested for their suitability as flame arresters but also must be tested for their pressure rating with appropriate explosion tests.
233
nator which opens the valve of the compressed air cylinder. The propellant
(pressure 10-40 bar), via a cylinder-piston system, closes the gate, which will be
dampened through the plastic deformation of a braking device [135].
The functioning of both valve types can be tested in place. Rapid-action valves
need an external operating device, which requires a suitable detector with control
unit for triggering.
In case a vessel is protected by a design measure:
- explosion-resistant design for the maximum explosion pressure
explosion-resistant design for the reduced maximum explosion pressure in conjunction with explosion pressure venting or explosion suppression,
an explosion can activate the downstream rapid-action valve through the following
means:
- a rupture disc with a sensing device or
- the usual membrane pressure sensor with a corresponding low activation pressure.
If the activation is by an optical flame detector, which is mounted in the wall of the
pipe, then the distance to the rapid-action valve must be in line with the anticipated
flame velocity and the closing time of the valve. The rapid-action valve described
above can be mounted in vertical, horizontal, or slanting pipelines.
Rapid-action valves have to be tested under explosion conditions to determine
their effectiveness as a flame barrier and their pressure ratings before actual use in
practice. Such a test arrangement is shown in Fig. 273.
ignihon source
flame front
Fig. 273. Arrangement for the performance testing of rapid action valves with respect to
flame containment and pressure shock resistance
234
Before the start of the test, the pipeline up- and downstream from the valve is
filled with an explosible fueVair mixture. An optical flame detector senses the starting explosion, and its control unit activates the rapid-action valve, which stops the
explosion analogous to practical applications. During such a test, the flame velocities and the explosion pressure (especially ahead of the valve) are recorded for the
whole system.
The following are used as a test medium:
- very easily ignition-propagating combustible dusts (e. g., Lycopodium or
aluminum fine dust)
- the flammable gas propane in order to cover the range of hybrid mixtures.
For the tests, the fuel concentration is systematically varied. The tests for flame
propagation are carried out with low turbulent mixtures, the ones for pressure
resistance with normal turbulent dust/air mixtures. Propane/air mixtures are basically ignited in a quiescent state. Such a test arrangement can also be modified by
substituting an explosion vessel of, e. g., 2.4-m3 (Fig. 274) for the pipeline ahead of
the rapid-action valve.
The aim of the test is to subject the valve to an explosion pressure of approximately 10 bar gage without allowing a flame propagation.
Figure 275 shows an explosion protection rapid-action valve which fulfills these
requirements. It was developed from a standard gate valve for dust service through
systematic tests [136]. It is manufactured in the nominal sizes DN 50-650 and, depending upon diameter, has closing times between 10 ms (DN 50) and 50 ms (DN
650). It has already been pointed out that the end-flanges of longer pipelines will
be exposed to markedly higher explosion pressures, especially in the case of explosions with dusts of the dust explosion class St 3 (aluminum) or hybrid mixtures
Fig. 274. Test arrangement with an explosion vessel for the testing of rapid-action valves for
flame propagation and explosion pressure shock resistance
235
(Fig. 137). The reason for this is not the development of a detonation, but instead
the acceleration of the explosion flame into the precompressed mixture ahead of
the closed pipe. These amplified effects of an explosion also occur at the location
of a closed rapid-action valve if it is installed in a pipeline more than lO-m away
from a vessel which is protected by design measures. The result is a heavily deformed plate (Fig. 276) and naturally propagating ignition of the fuel/air mixture.
As a remedy, a special venting device was designed (Fig. 277), at first for a pipeline DN 400. It entails a 3-m-Iong pipe section with four equally spaced flanged
venting slots around the pipe circumference. The total vent area corresponds to 4.5
times the cross section of the pipe. The vent openings are closed with lightweight
aluminum plates supported in rubber moldings. Two steel slings prevent the plates
from flying away in case of an explosion.
The venting device is mounted as close as possible to the rapid-action valve in
order to accomplish a decrease in the loading pressure of the valve gate (Fig. 278).
Systematic explosion tests were made to determine the effectiveness of such a
venting device in conjunction with an activated explosion valve DN 400. They
showed that the activation pressure of the venting device is of the utmost importance for the reduction of the explosion pressure at the location of the device. The
lower the pressure is, the more unburnt mixture will be exhausted through the vent
236
Fig 277. Venting device for the explosion protection valve WEY
ahead of the flame front, which will not participate in the combustion. The activation pressure has to be kept positively below pa ~O.5 bar in order to maintain the
pressure loading in the gate area below the design pressure of the valve.
Figure 279 shows the influence of an extremely high and low activation pressure
upon the pressure development and flame velocity of an aluminum-dust explosion.
100
o Pa=Q5 bar
Pa=2.0 bar
t:
250g/m3 At
...Cl
50
ON =400
tp =23m
0..
0
500
Vl
-.
250
>QJ
10
length of pipe
237
238
239
40,--------,--------,--------,--,
30
"
L-
..0
20
OJ
Cl..
10
o_
O- _ _ _
8----'::8==--=-9
o~--------~------~~------~--~
[ml
2500
2000
1500
til
E
----1000
x
>CJ
500
Fig. 282 alb. Influence of the location of the venting device upon the explosion characteristics of fine aluminum dust (375 glm3) (2.4-m 3IDN 400, lp =33-m, without explosion valve)
240
'd
..Cl
10
X
OJ
D-
o~---~----~----~~
1000.-----r---~r--------r--.
x 500
OJ
>
length of pipe
lp [m]
quired pressure rating of a rapid-action valve must be explosion-resistant for a nominal 10 bar pressure and not explosion pressure shock-resistant. It will then remain functional after being exposed to a detonation-like behavior of combustible
dusts, provided that a venting device is installed ahead of the valve and at the lO-m
mark. For longer pipelines, such a venting device has to be installed every 20-m.
Due to the development of flames and pressure, such an installation is limited to
an open air application.
Figure 284 shows a closed explosion valve with an activated venting device.
The test results with an explosion valve show that the problems inherent in the
threat of a violent dust explosion can be mastered and that economical solutions
are possible (no excessive explosion rating for the valve). The stoppage of a dust
explosion in a pipeline may also be accomplished by rapid-acting butterfly valves
which are controlled by detectors.
The make shown in Fig. 285 is pneumatically closed by the escaping air from a
compressed air cylinder which again has a valve actuated by a detonator. The requirements for such a system are the same as for rapid-action gate valves.
241
Fig. 284. Closed explosion valve with activated venting device after a detonation test
242
II
/-h
limit switch to
indicate closed position
reset knob
'I
I
I
hemispherical
nozzle
243
pressure container
amp ifier
flame
Joptical
detector
activated valve
Ventex- valve
Fig. 287. Ventex valve ESI with externally assisted activation (schematic)
triggers, via a control unit, the magnetic lock of the compressed air cylinder. Such
a detector may be a rupture disc with signaling device or a membrane pressure sensor on the protected vessel. For a pipeline, it is an optical flame sensor installed in
the pipe wall. Once the closing action is started, both externally activatedVentextype valves will be maintained in a closed position. The re-setting back to operating
position is done manually.
The externally activatedVentex valves work only in one direction and are only
suited for a horizontal installation in pipelines [128].
Externally activated Vente x valves have the advantage that they remain functional (the uncertain pressure range excluded) even if the triggering detector
should fail.
244
Basket
guard
cover or
rupture
disc
Fig. 288 alb. Explosion diverter (a) schematic presentation, b) actual diverter) [137]
5.3.6 Conclusions
245
5.3.6 Conclusions
In case the preventive explosion protection approach cannot be used for installa-
tions which manufacture, process, and convey combustible dust, a number of "design measures" can be used for their protection. Such measures will not prevent a
dust explosion but will limit the effects to an unobjectionable level. These measures basically require a certain explosion resistance of the vessels, equipment, and
pipelines, which may be built explosion pressure-resistant or explosion pressure
shock-resistant. Whereas explosion pressure-resistant vessels and equipment designed for the full maximum explosion pressure or a reduced maximum explosion
pressure have proven themselves for decades, the pressure shock-resistant design
is considered safe based on today's limited knowledge.
Vessels, equipment, and pipelines can be designed for the full maximum explosion pressure. This is generally feasible for sizes up to a few m3 If the threat of an
explosion comes from non-toxic combustible dust which will not dam3ge the surroundings, then explosion pressure venting is a viable, very effective design measure. In addition, within limits, certain reductions in relief area are possible in comparison with the valid guidelines, provided that the maximum explosion pressure
of the dust does not exceed 9 bar. Such a protective measure can also be used in
pipelines and for silos by incorporating the newer findings.
The effectiveness of explosion suppression systems has been substantially improved so that this proven design measure can be successfully used for large and larger vessels independent of location. Explosion diversion is a flanking measure for
the above-mentioned design measures that is helpful in separating equipment from
the systems which use preventive explosion protection.
Extensive practice-related tests in large pipelines, bucket elevators, and silos
have shown that extinguishing barriers can be used without reservation to halt or
stop an explosion in practice.
The same is true for rotary air locks which have been tested for ignition breakthrough and pressure resistance. Early results are now available pertaining to
flame propagation of dust/air mixtures through narrow gaps, e. g., rotor and housing of an air lock.
The findings pertaining to the use of rapid-action valves for the restriction of
the course of dust explosions have been substantially expanded. Such valves may
now be successfully used in practice, even with the danger of an extreme course of
an explosion (pressure piling, detonation).
Rapid-action valves have been used as flame barriers against dust explosions
for a long time in practice, with a proven record.
Explosion diverters are economical solutions to disengage explosions. They
find more and more use in practical installations, not only for limiting the course of
an explosion, but also to prevent flame jet ignition (maybe at a possible precompression) in vessels or equipment which is protected through design measures.
All in all, there is no problem in explosion technology which cannot be solved with
the above-mentioned safety measures in conjunction with an explosion diverter.
6 Concluding Remarks
In the years following the first two editions of my book "Explosions: Course, Prevention, Protection" in 1978/1981, many problems pertaining to the explosion technology of combustible dusts have been studied and solved. This related not only to
the improvements of the test methods needed to detect the dangers inherent in
dust layers and airborne dust, but also the explosion protection through preventive
and design means. Open gaps were closed through methodical research.
Therefore, I did not honor the request of my publisher to print a third edition
of my book, but decided to undertake a complete revision. Such a revision, however, is limited to combustible dusts, in line with the revisedVDI guideline 2263:
"Dust Fires and Dust Explosions: Hazards-Assessment-Protective Measures",
which has been just issued at the time this book was published.
This book again attempts to survey the present state of the art and starts with a
historical review of the development of the problematic nature of "dust explosions". It is shown that such findings are not of recent date but had already been
known for approximately 200 years.
All organic and metallic dusts are capable of exploding, but not all have to be
considered explosible while being manufactured, processed, and conveyed in practice. The new findings pertaining to the ignition capabilities of electrically and mechanically generated sparks, electrostatic discharges, and hot surfaces in dust/air
mixtures facilitate the use of the preventive safety measure "prevention of effective ignition sources". However, its practical application assumes the knowledge of
the safety characteristics of the fuel plus expert judgement. The presence of an explosible dust/air mixture in part of or in the whole of an installation does not always
present an explosion danger.
Substantial improvements have been made in the field of explosion protection
through design measures and through the flanking explosion diversion measures.
The book was written for the practical user and abstains from theoretical dissertations, which are rare in the field of combustible dusts. The numerous figures were
not only chosen to document for the reader the danger of a dust explosion but also
to visually present solutions for meeting such a danger.
The reader should realize: Dust explosions can be mastered!
7 Acknowledgements
I thank, without exception, all members of the national and international professional organizations and divisions for the numerous, useful discussions with which
they helped to create the image of the safety technology available to control the
dangers of dust explosions. This is especially true for Mr. C. Donat (Farbwerke
HoechstAG), who retired in the meantime.
I extend my thanks to the numerous equipment manufacturers for their unselfish support for the very elaborate and costly tests.
Included in my thanks are the "Bundesministerium fUr Forschung und Technologie", the "Berufsgenossenschaft der chemischen Industrie" and the "Berufsgenossenschaft Nahrungsmittel und GastsHitten", for their financial help in carrying
out various test programs.
I owe special thanks to Mr. A. Schaerli, the previous head of the central safety
department of Ciba-Geigy, Ltd. for the appreciation he always showed for the
work done in the explosion technology group, which formerly reported to him. He
exerted considerably energy and persevered for the improvement of the test conditions and the expansion of the facilities in the laboratory and the open air station
in the Jura, Switzerland. Without his support, a major portion of the tests mentioned in this book, especially the large-scale tests, would not have been possible.
I thank also Mr. G. Zwahlen, the head of the safety test station at Ciba-Geigy,
Ltd. for his contribution and always helpful collaboration.
Included in my thanks are all my former and present colleagues. Their special
effort was decisive for the success of the tests, and their results are used as the basis
of this book.
8 Appendix
b) x V
A= (a+--Pred.max
c
Table 24. Factors for the calculation of the vent area A as a function of vessel size V
(Pmax
Pred,max
[bar]
St1
<0.5
2:0.5
0.04
0.04
0.021
0.021
0.741
0.766
St2
<0.5
2:0.5
0.048
0.048
0.039
0.039
0.686
0.722
Analogous to Fig. 190, the required vent area for dusts belonging to the dust explosion classes St 1 and St 2 can be taken from the newly developed nomograms
(Fig. 290/291) for a given vessel size Vand a known pressure ratio (equivalent to the
reduced maximum explosion pressure Pred,max) [139].
249
Fig. 290. Nomogram based on dust explosion class St 1 (Psta! = 0.1 bar)
I"
I' I'\.
1/:
,-
.r,-
11max =10bor'
I
I
"""
"
0.1
relief area A [m 2 ]
---
i/.
Yh
"
Q25b or
or
\..~\~
~ 11,
'/.~ ~
~
200 tor
111I
Pred max
/..r..
;;"
/ : r.,..-
~~
0.01 1cfJ
VA
101
102
0.1 bar)
250
8 Appendix
13,--------,---------,---,
I
Cornstarch I
g'
1211-
.9
10 -
a
I
EI
9-
'8
/
-
d
E
Wheat.
L.
Light
agent
ProtediV~
Be-
7r---
61-
OJ
E
E
:::J
E
:;:::
D..
5L-------~1--------~1--~
400
500
600
bulk density
[kg 1m 3 ]
There is a linear correlation of air volume Q at the optimum material-to-air ratio with the explosion characteristics independent of the dust type. This is shown in
Fig. 293 for a constant vent area A = 0.5-m2 The pressure-area curve especially
shows a clearly proportional behavior with the dust-specific Kscvalue (Fig. 294).
o Cornstarch
: Pmox =9.01xIr;K~f226bar.m/S
t::. Light protagent: Pnux =8.6bar; t=150 bar. m/s
o Wheat
:I=\nax =B.1bar; St= 7B ~m/s
L.
.0
E
-6
(JJ
L.
D..
Vl
--.
L.
20
.0
X
E
,::f
OJ
L.
10
"'-
--.
D..
-0
-0
10
12
13
14
15
16
251
0:
o 0.6 , - - . I - - . I - - - -Ir - - ,I - - - .I - - - ,
.0
CJ
/4 .
"
0.5 -
~
/ti
~ 0.4 ~4
"E
~
III
0.2
I-
Cornstarch
: test resultsx0.35
Light prot agent: test results xQ.51
Wheat
: test results
E
-0 0.1 I~
Cl.
o1~0--~1~1--~12~~13~~14---1~5--~16
~
I
I
I
I
volume of air Q [m 3/minl
Table 25. Direct pneumatic conveying: Correlation of vent areaAwith reduced maximum
explosion pressure Pred,max for different Kst-values
(V = 20-m3 silo; HID = 6.25; Pmax:5 9 bar; pstat = 0.1 bar; Q = 15-16 m3/min;
optimum material-to-air ratio)
Kst [bar m/s]
50
100
A[m2]
0.2
0.5
1.0
1.5
2.0*
200
300
Pred,max [bar]
0.82
0.46
0.23
0.14
0.10
1.43
0.67
0.38
0.24
0.20
2.67
1.29
0.68
0.48
0.38
3.93
1.91
0.98
0.70
0.56
252
8 Appendix
4rr,-----~~--,---~
<>
"2
d
..0
x
d
E
i
-0
,~
-0
C1J
L.
~~1
D..
<>~
<>D_ _
<>::::::::~-I.
O~_~_--:'-:--_.J-_-.:r
0.5
1.0
1S
2.0
relief area A [m 2 j
Again it is emphasized that the figures in Table 25 are only valid for air volumes
Q :516 m 3/min (see Fig.227) and for an optimum material-to-air ratio (see
Fig. 292). Any deviation from such a ratio lowers the reduced maximum explosion
pressure.
In addition, Fig. 295 indicates that with the full use of the silo top as a vent area
(A = 2.0-m 2 ), only the pressure generated by weakly reacting dusts (Kst :550
barm/s) will be equivalent to the static venting pressure of the relief device. For
more violent reacting dusts, however, the pressure will be higher, requiring a
higher explosion pressure rating so that the silo will not be destroyed in case of explosion.
In adhering to the model developement for cubic vessels, Radandt [138] gives
additional mathematical correlations for the sizing of vent areas A for larger silos
(V >20-m 3). The factors for the equation shown in sect. 8.1.1 can be taken from
Table 26.
Table 26. Factors for the sizing of vent areas A as a function of silo size V
(Pmax = 9 bar, Pstat = 0.1 bar)
Dust explosion class
pred.max [bar1
St 1
:S 2
0.01]
0.069
0.776
St2
:S 2
0.012
0.114
0.720
253
The calculated values from the model giving the correlation of reduced maximum explosion pressure with vent area A coincide nicely with the actual measured
values for the 20-m3 silo (height/diameter ratio = 6.25) (Fig. 295). Based on the
correlation found for cubic vessels, larger volumes will require more vent area than
expected from the cubic law.
In many cases, the venting of a silo is limited by the available top area (see sect.
5.3.3.3).
For a given volume, but increasing height/diameter ratio, such a top area becomes smaller, and, therefore, the required explosion pressure Pred.max, which can
either be interpolated from Table 25 or calculated from the transformed equation
in sect. 8.1.1.
Pred,max =
b .yc
A - a yc
The factors are to be taken from Table 26, andAis the available area at the top of
the silo.
9 References
1. BIA: Dokumentation Staubexplosionen (Analyse und Einzeldarstellung), Berufsgenosenschaftliches Institut flir Arbeitssicherheit - Report 4/82
2. W. Bartknecht: Staubexplosionen - Ein historischer Oberblick, VDI-Berichte 494, Seite
11-24,1984
3. W.H. Geck: Zundfahige Industriestaube, Verlag desVereins DeutscherIngenieure, 1954
4. P. Beyersdorfer: Staubexplosionen, Verlag von Theodor Steinhoff, Dresden und Leipzig, 1925
5. L. Darmstaedter: Handbuch der Geschichte der Naturwissenschaften und Technik, Verlag von J. Springer, 1908
6. Berggewerkschaftliche Versuchsstrecke: 75 Jahre Berggewerkschaftliche Versuchsstrecke, Festschrift 1968
7. G. Pellmont: Explosions- und Zundverhalten von hybriden Gemischen aus brennbaren
Stauben und Brenngasen, Diss. ETH Zurich Nr. 6498, 1979
8. Chemische-Technische Reichsanstalt: Jahresbericht 1933-1935 S. 372-388
9. W. Gliwitzky: Ober Staubexplosionen, ihre Grundlagen undVerfahrenzu ihrer Untersuchung, Elektrotechnische Zeitschrift, 59. Jahrgang, Heft 43, 1938
10. H. Selle: Die chemischen und physikalischen Grundlagen der Verbrennungsvorgange
von Stauben, VDI-Berichte, Band 19,1957
11. G. Leuschke: Licht- undWarmestrahlung, Handbuch der Raumexplosionen v. H. Freytag, Verlag Chemie GmbH, WeinheimlBergsstrasse, 1965
13. B. Howard, H. Essenhigh: Pyrolyses of Coal Particles in Pulverised Fuel Flames, Industrial and Engineering Chemistry, Process, Design and Development, Vol 6. Nr. 1, S. 7484,1967
14. H. Essenhigh, B. Howard: Towards an Unified Combustion Theory, Industrial and Engineering Chemistry, Vol 58, Nr. 1, S. 15-23, 1966
15. Vital: Annales des mines, Ser. 7Vol. 20, S. 180, 1875
16. H. Selle: Die Grundzuge der Experimentierverfahren zur Beurteilung brennbarer Industriestaube, VDI-Berichte, Band 19,1957
17. VDI-Kommission Reinhaltung der Luft: Internationaler Erfahrungsaustausch: "Sichere Handhabung brennbarer Staube" am 20. und 21. 6.1979, Dusseldorf, S. 25 (Ab
Manuskript gedruckt: 1981)
18. B. Mason, S. Taylor: Ind. Engng. Chern. 29, S. 626, 1937
19. H. Selle, J. Zehr: Experimentaluntersuchungen von Staubverbrennungsvorgangen und
ihre Betrachtung vom reaktionsthermodynamischen Standpunkt, VDI-Berichte, Band
19,1957
20. J. Liitolf: Untersuchungen von Stauben auf Brand- und Explosionsgefahr, VDI-Berichte, Band 165, 1971
21. W. Bartknecht: Brenngas- und Staubexplosionen, Forschungsbericht F 45 des Bundesinstitutes flir Arbeitsschutz, 1971
22. J. Zehr: Die physikalische Kennzeichnung der Stoffeigenschaften, VDI-Berichte, Band
19,1957
23. VDI-Kommission Reinhaltung der Luft: Staubbrande und Staubexplosionen: Gefahren
- Beurteilung - Schutzmassnahmen, VDI-Richtlinie 2263, 1986, Beuth-Verlag GmbH,
Berlin und KOln
24. VDI-Fachausschuss "Brennbare Staube": Verhiitung von Staubbranden und Staubex-
9 References
255
256
9 References
53. J. Zehr: Anleitung zu den Berechnungen tiber die Ztindgrenzwerte und die maximale
Explosionsdrticke, VDI-Berichte Nr. 19, S. 63-68, Dtisseldorf: VDI-Verlag 1957
54. J. Schonwald: Vereinfachte Methode zur Berechnung der unteren Explosionsgrenze von
Staub/Luft-Gemischen, Staub-Reinhaltung der Luft 31, Heft 9,1971
55. VDI-Kommission Reinhaltung der Luft: Druckentlastung von Staubexplosionen, VDIRichtlinie 3673, Absatz 12, luni 1979, Beuth-Verlag GmbH, Berlin und Koln
56. International Standard ISO 6184/1: Explosion Protection Systems - Part I: Determination of Explosion Indices of Combustible Dusts in Air, International Organization for
Standardization, 1985
57. R. Siwek: Bericht tiber Versuche zur Entwicklung einer Laborapparatur flir die Bestimmung der Explosionskenngrossen brennbarer Staube, HTL-Winterthur, Semesterarbeit,1976
58. R. Siwek: 20 l-Laborapparatur flir die Bestimmung der Explosionskenngrossen brennbarer Staube, HTL-Winterthur, Diplomarbeit, 1977
59. R. Siwek: Experimental Methods for the Determination of Explosion Characteristics of
Combustible Dusts, 3rd Int. Symposium on Loss Prevention and Safety Promotion in
the Process Industries, Basel, Vol. 2, p. 839-850, 1980
60. Th Glarner: Temperatureinfluss auf das Explosions- und Ztindverhalten brennbarer
Staube, Diss. ETH Ztirich Nr. 7350, 1983
61. BIA: Brenn- und Explosionskenngrossen von Stauben, Forschungsbericht Staubexplosionen des Berufsgenossenschaftlichen Institutes ftir Arbeitssicherheit, Marz 1980
62. E. Schenk: Explosions- und Ztindverhalten von Flockmaterial, VDI-Berichte 494, S.
53-57,1984
63. W. Bartknecht: Untersuchung des Explosions- und Ztindverhaltens brennbarer Staube
und hybrider Gemische, Schriftenreihe: "Humanisierung des Arbeitslebens", Band 64,
Herausgeber: Der Bundesminister flir Forschung und Technologie, VDI-Verlag, Dtisseldorf,1985
64. E. W. Scholl: Loschmittelsperre zurVerhinderung der Fortpflanzung von Schlagwetterund Kohlenstaubexplosionen, Dissertation TH Clausthal, 1968
65. N. Kalkert: Theoretische und experimentelle Untersuchungen der Explosionskenndaten von Mischungen aus mehreren gas- und staubfOrmigen Brennstoffkomponenten und
Luft, Fortschr.-Ber. VDI-Z., Reihe 3, Nr. 64, 1982
66. W. Berthold: Mindestztindenergie - Prtifverfahren VDI-Berichte 494, S. 105-108, 1984
67. BG-Chemie: Richtlinie Nr. 4: "Statische Elektrizitat"
68. AK: "Brennbare Staube": Sicherheitsmassnahmen gegen Staubbrande und Staubexplosionen,Ausgabe 1, Okt. 1973, Abschn. 2.1
69. W. Bartknecht: Untersuchungen tiber das Explosions- und Ztindverhalten von Beschichtungspulvern, Ciba-Geigy AG, Zentraler Sicherheitsdienst, Fachgruppe Explosionstechnik, Bericht vom 19.7.1983 (unveroffentlicht)
70. 1. P. Zeeuwen, G. F. M. van Laar: Ignition Sensitivity of Flammable Dust-Air Mixtures,
Prins Maurits Laboratorium TNO (Holland), 1985
71. W. Bartknecht: Untersuchungen tiber das Explosions- und Ztindverhalten von Flock,
Ciba-Geigy AG, Zentraler Sicherheitsdienst, Fachgruppe Explosionstechnik, Bericht
vom August 1983 (unveroffentlicht)
72. H. Franke: Bestimmung der Mindestztindenergie von Kohlenstaub/Methan/Luft-Gemischen (hybride Gemische), VDI-Berichte 304, S. 69, 1978
73. B. Maurer: Elektrostatische Entladungsvorgange als Ztindquellen, VDI-Berichte 494,
S. 25-33, 1984
75. M. Steinicke: Gasbewegung und Turbulenz bei Explosionen in einer langgestreckten
Bombe, Dissertation TH, Braunschweig, 1943
76. E. Schmidt, H. Steinecke, U. Neubert: Aufnahmen derVerbrennung von Gasgemischen
in Rohren mit dem Eigenlicht der Flamme bei Schlierenbeleuchtung, VDI-Forschungsheft 431, 1951
77. G. Dammkohler: Gasbewegung in einem geschlossenen Verbrennungsraum bei einseitiger Ztindung, lahrbuch der deutschen Luftfahrtforschung, 1938
78. W. Bartknecht: Explosionstechnische Kennzahlen brennbarer Staube in Rohren mit en-
9 References
257
258
9 References
9 References
259
123. DEUGRA: Explosionsunterdrlickung in Industriebetrieben, Gesellschaft flir Brandschutzsysteme mbH, D-4030 Ratingen, 1985
124. D. Schneider: Erfahrungen mit Staubunterdrlickungssystemen in Mahlanlagen, VDIBerichte 494, S. 293-307,1984
125. D. Schneider: Erfahrungen mit Schutzmassnahmen gegen Staubexplosionen, 9. Internationales Kolloquium flir die Verhlitung von Arbeitsunfallen und Berufskrankheiten
in der chemischen Industrie, Luzern, 1984, S. 489-534
126. International Standard ISO 6184/4: Explosion Protection Systems - Part 4: Determination of Efficacy of Explosion Suppression Systems, International Organization for Standardization, 1985
127. P. Moore, W. Bartknecht: Suppression of Gas and Dust Explosions in Large Volumes,
5th International Symposium Loss Prevention and Safety Promotion in the Process Industries, CanneslFrance, September 1986
128. W. Czajor: Explosionstechnische Entkoppelung von Apparaturen, VDI-Berichte, 494,
S.233-238
129. E. W. Scholl: Ein Verfahren zum Loschen von Schlagwetter-, Kohlenstaub- und Methan-Kohlenstaub-Explosionen, Gllickauf-Forschungshefte, 29. Jahrgang, Heft 4,1968
130. W. Bartknecht: Loschmittelsperre, Sonderausgabe des "Ladenburger-Kreises", Oktober 1977, Herausgeber: Total-Foerstner & Co. AG, D-6802 Ladenburg
131. W. Bartknecht: Staubexplosionsversuche in einem verstarkten Gurtelevator der Fa.
Blihler-MIAG GmbH (Braunschweig), Ciba-Geigy AG, Zentraler Sicherheitsdienst,
Fachgruppe Explosionstechnik, 1981
132. F. Kossebau: Explosionsgeschlitzte Elevatoren, Blihler-MIAG-Nachrichten, 219, S.
20-21,1981
133. G. Schuber: Zlinddurchschlagverhalten von Staub/Luft-Gemischen und von hybriden
Gemischen, Jahresbericht 1984/1985 zum BMFT/HdA-Forschungsvorhaben, CibaGeigy AG, Zentraler Sicherheitsdienst, Fachgruppe Explosionstechnik (Veroffentlichung in Vorbereitung)
134. IRS: Prospektblatt: Schnellschuss-Schieber, Industrie-Rationalisierungssysteme, D6100 Darmstadt, 1985
135. SISTAG: Prospektblatt: WEY-Explosionsschutz- Schieber, Typ SLC-Ex, Sidler Stalder
AG, Maschinenfabrik, CH-6274 Eschenbach
136. H. Stalder: Explosionsschutz-Schieber: Massnahmen gegen die Auswirkungen von Explosionen und Detonationen, 10. Internationales Kolloquium fur die Verhlitung vonArbeitsunfallen und Berufskrankheiten in der chemischen Industrie, Frankfurt 1985, S.
525-555
137. Silo-Thorwesten: Prospektblatt: Druck-Entlastungsschlot, Silo-Thorwesten GmbH, D4720 Beckum, 1985
138. S. Radandt: Bestimmung der Explosionsdruck-Entlastungsflachen in Ubereinstimmung mit den am haufigsten angewendeten Richtlinien innerhalb und auBerhalb Europas, Europex-Seminar: "Druckentlastung von Staub explosion en in Behaltern", 1986
139. W. Bartknecht: Druckentlastung von Staubexplosionen in Behaltern. Staub-Reinhaltung in del' Luft, Nr. 9, September 1986, S. 368-373
140. W. Bartknecht: Massnahmen gegen gefahrliche Auswirkungen von Staubexplosionen
in Silos und Behiiltern, Jahresbericht 1985 zum BMF/HdA-Forschungsvorhaben vom
Februar 1986 (unveroffentlicht)
a
A
c
C
abs
AD
AI
BAM
CL
Cr
d
D
D
DIN
DN
dp/dt
(dp/dt)max
(dp/dt)red
(dp/dt)red,max
DR
E
EE
energy
electrical equivalent energy
exempli gratia (for example)
explosion protection guideline
FR
FRG
function
recoil force
Federal Republic of Germany
grams
H
H
h,hrs
Halon
height
product humidity
hour(s)
halogenated hydrocarbons
high rate discharge
I
ID
current
inside diameter
ignition energy
e.g.
Ex-RL
HRD
IE
IEC
IP
i. e.
J
kJ
I
I
L
LEL
LMIE
LOC
Ig
log
Ip
m
MESG
MIE
ML
max
mm
ms
length
liter
inductance
lower explosible limit
lowest minimum ignition energy
limiting oxygen concentration
gap length
common logarithm of
length of pipe
meters
median value
maximum experimental safe gap
minimum ignition energy
material-to-air loading
maximum
millimeters
milliseconds
number of extinguishers
newton
newton meters
nitrogen
oxygen concentration
oxygen
Prod.max
pressure
pneumatic
activation pressure (of suppression systsems)
thrust
atmospheric pressure
polyethylene
explosion pressure
nominal pressure
pressure of the driving medium N2
polyvinyl chloride
initial pressure
maximum explosion pressure
reduced explosion pressure
reduced maximum explosion pressure
volume of air
p
p
Pa
PA
Palm
PE
Pex
PN
PN2
PVC
Pi
Pmax
Pred
261
262
R
RL
resistor
guideline
s
SA
sect.
St
seconds
surface area
Section
dust explosion class
t2min
time
temperature
autoignition temperature
ignition delay time
grinding time
glowing wire temperature
ignition temperature
induction time
oven temperature
optimum temperature
rubbing time
reduced time
duration of combustion
minimum duration of combustion
induction time
minimum induction time
V
VEL
voltage
upper explosible limit
v
V
vol
vr
vs
velocity
volume of vessel
Verb and Deutscher Elektrotechniker
Verein Deutscher Ingenieure
(German Society of Engineers)
flame velocity
maximal flame velocity
volume
speed of rotation
versus
wt
weight
TA
td
tg
TOI
TI
ti
to
Topt
tr
t red
tl
tlmin
t2
VDE
VDI
Vex
Vex,max; Vmax
dynamic coefficient
temperature difference
micron; 10- 6 m
ohm
percent
degrees Celsius
11 Conversion Factors
1mm
1cm
1m
lkm
=
=
=
=
0.0394"
0.3937"
3.2808'
0.6214 st.mi
linch
1 foot
1 status mile
1cm2
1m2
1m2
1m2
=
=
=
=
=
=
=
2.5400 em
0.3048m
1.6093 km
0.1550 sq.in
10.7639 sq.ft
1.1960 sq. yd
15.499 sq.in
1 square inch
1 square foot
1 square yard
1 square inch
=
=
=
=
6.4516cm2
0.0929m2
0.8361 m2
6.452 . 10-4 m2
1cm3
11
1m3
1m3
=
=
=
=
0.06102 cu.in
0.03531 cu.ft
35.31 cu.ft
1.308 cu.yd
1 cubic inch
1cubicfoot
1 cubic foot
1 cubic yard
=
=
=
=
16.387 cm3
28.3141
0.02832m3
0.7646m3
11
11
1 (USA) gallon
1 (Brit) gallon
= 3.78541
= 4.54611
19
1kg
= 15.4323 grain
= 2.2046 pounds
1 grain
1 pound
= 0.0648g
= 0.4536 kg
1bar
1bar
1Pa
= 14.504 psi
= 105 Pa
= 0.000145 psi
264
11 Conversion Factors
1 pound-force/inch2
1 pascal
1 pound-force/inch 2
=
=
=
0.06895 bar
0.00001 bar
6894.8 Pa
xOC
1.8x + 32F
xOF
5/9 (x-32}"C
12 Subject Index
A
Autocatalytic decomposition 42, 43
Autoignition 36
-, induction time 39
-, - -, dependency of storage temperature
and test volume 39
-, heat balance 36
-, heat generation 36
-, heat transmission 37
-, storage temperature 36
-, surrounding temperature 36
-, temperature 36
--, determination 37
- -, method dependency 36
--, volume dependency 36,37
--, -, EC-method 37
- -, - as per Grever 37
--, -, hot storage test in a wire mesh
basket 39
B
Blow off pipes, see relief pipes
Brush discharge 157
Burning behavior 28,29
--,burnoffvelocity 29,31
--, ---, determination 31
Burning rate, see Burning behavior
C
Calculation model, explosion pressure
venting
--, silos 251
- -, vessels 248
Carbonization gases, see decomposition
gases
Chemical ignitors, see pyrotechnical
ignitors
Coal pulverizer 182
Combustibility test 29
- - at elevated temperature 30
- - at reduced pressure 32
- - at room temperature 29
--, appearance 29,30
- -, Combustion class 29,30
--, --, temperature dependency 30
--, under vacuum 32
Combustible dusts 51
--, explosible limits 54
--, explosion indices 56-80
--, ignition temperature 115-119
- -, minimum ignition energy 96-109
Combustion time, see duration of
combustion
Conical pile discharge 158, 159
Constructive explosion protection 161
- - -, design for the maximum explosion
pressure 163
- - -, diverting 215
---, explosion pressure venting 166
---, explosion suppression 203
Cubic Law 61
--, validity 61,64,65
D
Decomposition energy 44, 45
Decomposition gases 32,40,43,45,50
Decomposition temperature,
see exothermic decomposition
Deflagration 32
-, ashes 32
-, -, combustibility 32
-, avoidance 32
-, decomposition gases 32
-, -, explosion hazard 32
-, -, pressure build-up 32
-, initiated 32
-, stoppage 32
-, temperature 32
-, test 32, 33
-, -, laboratory test 33
-, -, -, laboratory test at elevated
temperature 33
-, -, laboratory test at room
temperature 33
-, -, laboratory test inerting 33
-, -, screening test 32
-, -, screening test, test under vacuum 32
-, -, screening test, Witt scher pot 33
-, velocity 33
Dependency on volume, see volume
dependency
Detector for explosion suppression 205
266
Subject Index
Diversion 215
-, diverter 243
-, extinguishing barrier 215
-, rapid action valve: butterfly type 241
-, rapid action valve: float type 241
-, rapid action valve: gate typ 232
-, rotary air locks 229
Diverter 243
Duration of combustion 107, 108
Dust
-, airborne dust 51
-, definition 25
-, dust layers 28
-, settling velocity 25,26
Dust accumulation
--, acceptable 12
--, -, cubically-shaped 13
--, -, not cubically-shaped 13
Dust explosions
--, bakeries 10
--, coal dust 4
--, combines 3
--, frequency 4,7
--, -, types of equipment 7
--, -, dust types 7
- -, -, types of ignition sources 8
--, grain/flour 2,5
--, mechanics 14
--, number 2,4
--, silos 4,7
--, sugar 4,10,11
Dust explosion class 78
---, frequency 79
- - -, increasing 90
Dust investigations 23
--, apparatus 15,56,62
--, dispersal procedure 22,23,56,62
Dust layers 28
Dust temperature 28, 30, 31, 33
E
- -, - -, pressure build-up 40
- -, - -, explosion hazard 40,44
--, --, type oftest 40
--, --, quantity 43
--, decomposition temperature 40
--, --, dependency on determination
method 40
--, heat accumulation 40
--, --, adiabatic condition 40,45
--, --,critical temperature 40,45
- -, - -, heat elimination 44
- -, - -, heat elimination, capacity of heat
elimination 44
--, --, heating efficiency 44
--, heat production 44
- -, - -, rate of heat production 44
--, self-heating 40,46
--, -, induction time 45,46
--, thermal explosion 40,44,45
--, type oftest
--, ---, differential thermal analysis 44
- -, - - -, DTA, see differential thermal
analysis
--, ---, as per Liitolf 40
--, ---, with nitrogen, Grever-Oven 44
--, ---, hot storage test in the
Dewar-tube 45
- -, -, hot storage test under pressure
build-up 46
--, -, hot storage test with temperature
programmed conditions 46
Explosibility 11,27, 47
-, definition 53
-, friction sensitivity 47
-, - -, test type 49
-, --, test type, apparatus as per BAM 49
-, impact sensitivity 48
-, --, test type 48
-, - -, test type, drop weight as per
Koenen 48
-, - -, test type, drop weight as per
Liitolf 48
-, thermal sensitivity 50
-, - -, test type 50
-, --, test type, steel tube test 50
-, --, test type, steel tube test, limiting
diameter 51
Explosion characteristics, see explosion
indices
Explosion doors, see explosion flaps
Explosion flaps
--, bucket elevator 201
- -, - -, influence of weight of the
flaps 201
--, pipes 203
--, silos 194
--, -, venting efficacy 196
Subject Index
--, vessels 174
--, -, venting efficacy 175
Explosion hazard, see explosibility
Explosion indices
--, combustible dusts 56-80
--, flock 84-86
--, hybrid mixtures 88-91
Explosion limits 54
--, combustible dusts 54
- -, - -, influence of temperature 56
- -, - -, influence of ignition energy 55
--, --, lower 54
--, --, upper 54
--, flock 82
- - ,-, influence of ignition energy 83
--, hybrid mixtures 87
--, --, influence of flammable gases 87
--, --, influence of type of flammable
gases 88
Explosion pressure 56
--, combustible dusts 56
--, --, influence of humidity 72
- -, - -, influence of filling ratio 69
- -, - -, influence of ignition energy 77
- -, - -, influence of initial pressure 73
- -, - -, influence of particle size 69
- -, - -, influence of solvents 72
--, --, influence of temperature 73
- -, - -, influence of turbulence 58
- -, - -, influence of volume 61
- -, - -, influence of water 71
--, flock 84
--, -, influence of fiber 84
- -, -, influence of ignition energy 86
--, frequency 79
--, hybrid mixtures 88
- -, - -, influence of flammable gases 89
--, --, influence of type of flammable
gases 91
--, optimum dust concentration 91
Explosion pressure venting 166
- - -, belt elevator 201
---, coal pulverizer 181
---, fluidized bed driers 177
- - -, - - -, explosion pressure,
reduced 167
---, ---, explosion pressure,
maximum 168
---, large vessels 183
---, pipelines 200
- - -, -, detonation 239
---, -, explosion 200
- - -, silos 187
---, -, explosion velocity 192
- - -, -, influence of arrangement 190
- - -, -, influence of partial filling 191
---, -, pneumatic conveying 194,249-253
267
268
Subject Index
F
Fan-shaped nozzle 218
Fiber 26
-, flock 26
Flame jet ignition 215
Flammability 28
-. test 28
-, - at e\cvated temperature 28
-, - at room temperature 28
-, -, ignition sources 28
-. -, lighter with flintstone 28
-, -, lighter with flintstone, sparks 28
-, -, lighter with flintstone, gas flames 28
-, -, lighter with flintstone, mechanical
sparks 28
-, -, lighter with flintstone, matches 28
-, of deposited combustible dusts 28
Flintstone friction sparks 147
Flock 81
-, explosion indices 84-86
-, explosion limits 82, 83
-, minimum ignition energy 109-112
Fluidized bed driers 177-180
Foreign particle 32, 48
Friction sensitivity, see explosibility
Friction sparks 150
G
Gap, maximum experimental safe 230
Glowing temperature 154
Glowing wire coil 117
---, comparison with minimum ignition
energy 118
---, ignitability 118
GrewerTh. 37,38
H
SUbject Index
Limiting inert dust concentration 141
Limiting oxygen concentration 129
---, combustible dusts 130
- - -, hybrid mixtures 137
Localization of heat, see exothermic
decomposition Uitolf J. 40,48
M
Partial filling 68
Particle size 11,24,34-36
--, median value 52,53,69
Particle size distribution 52, 53
---, median value 52,53
Pipelines
269
270
Subject Index
Radiation 14
Rapid action valve
---,butterflytype 241
---,floattype 241
---, --, activated with a device 243
---, --, explosion pressure activated 242
---, gate type 232
---, --, venting elements for 238
Recoil forces, explosion pressure
venting 175
Relief pipes for pressure venting 172
-----, nomogram 173
Resistance of apparatus 162
Rotary air locks, rotary locks 229
S
Silo
-, course of explosion
191, 192