Liebert XDC User Manual
Liebert XDC User Manual
Liebert XDC User Manual
Liebert XDC
User Manual - 50 and 60 Hz, 130 & 160kW Nominal Cooling Capacity
GENERAL SAFETY GUIDELINES
Before beginning the installation of the Liebert XDC, read all instructions, verify that all the parts are
included, and check the nameplate to be sure the Liebert XDC voltage matches available utility power.
Follow all local codes.
! WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
! WARNING
Risk of unit falling over. Can cause death, injury and equipment damage.
The Liebert XDC is top-heavy. Use extreme caution and care when moving and installing this
unit.
! CAUTION
Risk of piping and component rupture. Can cause injury or equipment damage. Closing
service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do
not close valves without following recommended procedures for repair, maintenance and
replacement of components. Install pressure relief valves in field piping that may become
isolated by service valves.
! WARNING
Risk of refrigerant system explosion or rupture from overpressurization. Can cause injury,
death or equipment damage.
Installer must install a 400 psig pressure relief valve in each of the two R-407C refrigerant
circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and
the pressure relief valves.
For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a
notified body to the EU Pressure Equipment Directive.
! CAUTION
Risk of contact with hot surfaces. Can cause burn injury. The compressors and refrigerant
discharge lines are extremely hot during unit operation. Allow sufficient time for the
compressors and refrigerant discharge lines to cool before working within the unit cabinet.
Use extreme caution and wear protective gloves and arm protection when working on or near
hot compressor and discharge lines.
NOTE
This document shall be used together with site specific documentation and documentation for
other parts of the system (heat rejection devices and cooling modules).
NOTE
Before any action that could cause a disturbance in the XD systems cooling function is begun,
the facility manager MUST be informed. In addition, after the action is taken and the work is
finished, the facility manager MUST be informed.
Figure i Model number nomenclature
Example: XDC160AA *
XD C 160 A A *
Chiller Place holder Place holder Revision
unit level
Liebert Model size A = 460V-3ph-60Hz Place holder
X-treme heat (voltage-phase-frequency)
Density system M = 380/415-3ph-50Hz
TABLE OF CONTENTS
GENERAL SAFETY GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER
1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 General Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.1 Product/System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Equipment Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.1 Handling With Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.2 Removal of Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.3 Removing Piano Jacks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1 Positioning the Liebert XDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.2 Placing the Liebert XDC on a Floor Stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4.3 Positioning the Liebert XDC with Floor Stand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 High Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5.1 Connecting High-Voltage Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Extra Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.0 PIPING AND FILLING WITH REFRIGERANT: R-134A AND R-407C CIRCUITS . . . . . . . . . . . . . 16
2.1 European Union Fluorinated Greenhouse Gas Requirements . . . . . . . . . . . . . . . . . . . . . . . 16
2.2 Recommended Pipe Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Liebert XDC Interconnection With Liebert XD Cooling Module . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Piping Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.4.1 Piping InstallationR-134a Pumped Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5 Filling the Pumped CircuitR-134a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.5.1 Calculating Refrigerant ChargeExample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.5.2 Piping for Direct Expansion (DX) CircuitR-407C Air-Cooled Units . . . . . . . . . . . . . . . . . . 22
2.6 Install Double Discharge Risers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6.1 Air-Cooled Condenser with Liebert Lee-Temp Flooded Condenser Head Pressure
Control SystemR-407C (DX) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.7 Filling the Direct Expansion (DX) CircuitR-407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.0 INSTALLATION CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.0 CHECKLIST FOR LIEBERT XDC STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1 System Refrigerant Charges Over 35 lb. (15.9kg) Require Additional Oil . . . . . . . . . . . . . . 34
4.1.1 Liebert XDC DX R-407C Circuit Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.0 MICROPROCESSOR CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1 Feature Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
i
5.2 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.1 Feature Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.2 Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3 Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3.1 Viewing or Changing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3.2 SETPOINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.3.3 STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.4 ACTIVE ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.5 ALARM HISTORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.6 TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.7 DATE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.8 SETUP OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.3.9 SETPT PASSWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3.10 SETUP PASSWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3.11 CALIBRATE SENSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.12 ALARM ENABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.13 ALARM TIME DELAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3.14 COM ALARM ENABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3.15 CUSTOM ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3.16 CUSTOM TEXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.3.17 DIAGNOSTICS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.0 ALARM DESCRIPTIONS AND SOLUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
6.1 Alarm Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.2 Green and Red Lamp Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3 Enable / Disable Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4 Alarm Time Delays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.5 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.6 View Alarm History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.7 System Shutdown Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.1 Fluorinated Greenhouse Gas Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.2 Air-Cooled Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3 Water/Glycol Floor Stand Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.3.1 Shell and Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.3.2 Regulating Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.3.3 Glycol Solution Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
ii
FIGURES
Figure 1 Liebert XDC components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Moving Liebert XDC with forklift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 3 Remove tie-down brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 4 Remove pallet, insert piano jacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 5 Dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 6 Piping locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 7 Water/glycol Liebert XDC on a floor standpositioning and piping connections. . . . . . . . . . . . . . 7
Figure 8 Piping locationsfloor stand and valve assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 9 Dimensions and clearances for Liebert XDC on floor stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 10 Front view of Liebert XDC and electrical enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 11 Electrical enclosure knockout locations for field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 12 60Hz models, high voltage connectionsprimary disconnect switch . . . . . . . . . . . . . . . . . . . . . . 11
Figure 13 50Hz models high voltage connectionsprimary disconnect switch . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 14 60Hz models high voltage connectionssecondary disconnect switch . . . . . . . . . . . . . . . . . . . . . 12
Figure 15 50Hz models high voltage connectionssecondary disconnect switch . . . . . . . . . . . . . . . . . . . . . 13
Figure 16 Liebert XDC heat rejection connection points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 17 Electrical enclosure knockout locations for Extra Low Voltage connections. . . . . . . . . . . . . . . . . 14
Figure 18 Extra Low Voltage field connections points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 19 Liebert XD system diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 20 Bypass flow controller details, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 21 Bypass flow controller arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 22 Bypass flow controller piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 23 Double discharge riser layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 24 Installation dataLiebert Lee-Temp, one-circuit, four-fan model . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 25 Installation dataLiebert Lee-Temp, one-circuit, high ambient six-fan model . . . . . . . . . . . . . . 25
Figure 26 Liebert XDC piping schematic and Liebert Lee-Temp heater pad wiring. . . . . . . . . . . . . . . . . . . 26
Figure 27 General arrangement air-cooled Liebert XDC Liebert Lee-Temp Control . . . . . . . . . . . . . . . . . . 27
Figure 28 DCSL616 piping connectionstwo refrigerant circuits connected for parallel flow. . . . . . . . . . . 28
Figure 29 DCSL616 piping connectionstwo refrigerant circuits connected for parallel refrigerant
flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 30 Additional oil requirements for refrigerant charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 31 System R-134a liquid level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 32 User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 33 Outdoor fan/condenser configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
iii
TABLES
Table 1 Liebert XDC dimensions, weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 Liebert XDC piping connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 Liebert XDC water/glycol piping connection Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 4 Supply, return pipe sizes for Liebert XD refrigerant loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 5 Bypass flow controllers for a Liebert XDC-based system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 6 System R-134a charge for a Liebert XDC with any model Liebert XDH/Liebert
XDO/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 7 System refrigerant charge for the supply and return mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 R-134a refrigerant charge for Liebert XD Flex Pipe connector lines to and from any
model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 10 Calculating refrigerant chargeexample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 11 Worksheet to calculate refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 12 Receivers and head pressure kits for Liebert Lee-Temp condensers . . . . . . . . . . . . . . . . . . . . . . . 23
Table 13 Recommended refrigerant line sizes, DX R-407C, OD copper . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 14 Recommended refrigerant line sizes for DCSL616 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 15 Indoor unit refrigerant chargeR-407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 16 Outdoor air condenser chargeR-407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 17 Air-cooled systems - liquid line charge - R-407C refrigerant per 100 ft (30 m)
of Type ACR copper tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 18 Indoor water/glycol-cooled module R-407C refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 19 Liebert XDC pump light indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 20 Compressor oil types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 21 User interface keypad functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 22 Setpoint functions, default values and allowable ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 23 Setup operation functions default values and allowable ranges. . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 24 Liebert XDC DIP switches and factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 25 Liebert XDC troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 26 Liebert XDC specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 27 Floor stand specificationswater-cooled Liebert XDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 28 Floor stand specificationsLiebert XDC with 40% propylene glycol . . . . . . . . . . . . . . . . . . . . . . 55
Table 29 Floor stand specificationsLiebert XDC with 40% ethylene glycol . . . . . . . . . . . . . . . . . . . . . . . 56
iv
Product Description
Condenser
Units
Receiver Pumps
Compressor
Heat Exchanger
! WARNING
Risk of unit falling over. Can cause death, injury and equipment damage.
The Liebert XDC is top-heavy. Use extreme caution and care when moving and installing this
unit.
1
Product Description
! CAUTION
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard
doorway. Any attempt to move the unit, while skidded, through a standard doorway will
cause damage to the unit and to the building.
! CAUTION
Risk of unit damage. Ensure the forklift tines are level and not angled in an upward direction.
Improper positioning may cause damage to the bottom of the unit. Ensure the forks are
positioned in a manner as to have the Center of Gravity label, located on the unit, centered
between the tines. Ensure the tines extend beyond the opposite side of the unit.
3. Drive the forklift forward, sliding the forks under the base of the unit (see Figure 2).
2
Product Description
! WARNING
Risk of unit falling over. Can cause death, injury and equipment damage.
The Liebert XDC is top-heavy. Use extreme caution and care when moving and installing this
unit.
5. Remove all lag bolts from the four (4) corner tie-down brackets. Remove the tie-down brackets
from the unit. (see Figure 3).
6. Lift the Liebert XDC about an inch and remove the shipping pallet.
Figure 4 Remove pallet, insert piano jacks
7. Place piano jacks at either end of the Liebert XDC and lower it until it is supported by the piano
jacks. Secure the Liebert XDC to the jacks (see Figure 4 for arrangement).
! CAUTION
Risk of overtightening securing strips. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit.
Ensure that the straps are not tightened to a point of damaging panels.
8. Back the forklift away from the Liebert XDC until the forks are no longer under the unit.
9. Using the piano jacks, maneuver the Liebert XDC into its installation positionthis requires at
least two people.
3
Product Description
NOTE
During installation of the Liebert XDC, the top, bottom, front and left side of the unit
must be accessible.
C
78"
1981mm
1" Recommended
(25.4mm) Minimum Hot Gas
Supply & Liquid Return
17" Piping Opening
5"
D (432mm)
(127mm)
2"
(51mm) Floor Cutout Dimensions
D E Shaded areas indicate a
Unit Unit Base recommended clearance DPN000768
Base of 34" (864mm) for
Pg. 2, Rev. 6
Unit Dimensional Data component access.
4
Product Description
* Orientation determined
by installer.
F - Return From Cooling Units
6" (152mm)
23"
(584.2mm)
Dimensions are
approximate and
subject to change
without notice.
A - Hot Gas
B - Liquid
Refrigerant Lines
Refrigerant Lines
* Allow 8" (204mm) of clearance for filter replacement
** To ensure all refrigerant flow is filtered, install the filter dryer assembly
between the discharge line of the Liebert XDC and the first bypass DPN000768
flow controller or the first cooling module. Pg. 3, Rev. 6
Table 2 Liebert XDC piping connection sizes
Air-Cooled Model Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz A B C D E F G
XDC160 1-3/8 7/8 - - - 2-1/8 1-1/8
5
Product Description
! WARNING
Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or
death.
Read all of the following instructions before attempting to move, lift, remove packaging from
or preparing unit for installation.
! CAUTION
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for
installation.
The water/glycol floor stand can be located beneath the Liebert XDC unit or can be installed nearby.
NOTE
Consult the factory if the Liebert XDC is not installed on the water/glycol condenser floor
stand to prevent exceeding maximum the piping distances.
Refer to the floor stand installation sheet shipped inside the water regulating valve package.
1. Move the floor stand assembly to its installation area and uncrate the unit.
2. Position the floor stand in its final location.
3. Insert leveler pads into each floor stand leg.
4. Level the top of the floor stand to the specified height with the flanged adjusting nut.
5. Tighten jam nuts on all legs against flanged adjusting nuts.
6. Using an appropriate lifting device or method, raise the Liebert XDC and move it above the floor
stand.
7. Align the welded tabs on top of the floor stand with the inside of the unit frame base (see Detail A
in Figure 7).
8. Maintaining the alignment of the Liebert XDC and the floor stand, lower the Liebert XDC onto
the floor stand.
9. Connect the hot gas refrigerant lines from the Liebert XDC to the floor stand with 1-3/8" tubing
(see Figures 7 and 8).
10. Connect the liquid refrigerant lines as shown from the Liebert XDC unit to the floor stand with
7/8" tubing (see Figures 7 and 8).
11. Connect the water lines as shown with the provided valving (see Figures 7 and 8).
12. Connect capillary lines from each water regulating valve to condensers in the floor stand (see
Figures 7 and 8).
Capillary length is limited to 48" (1219mm).
13. Check the pipes for leaks and evacuate air from all pipes.
14. Insulate all water/glycol lines.
15. Charge each condenser loop with R-407C (see Table 18).
6
Product Description
6"
(153mm)
23"
(584mm)
Welded Tab
C - Hot Gas
Refrigerant Lines A
D - Liquid
Refrigerant Lines DETAIL A
Customer
E - Threaded Water
Female Supply
Connections
Customer
Water
Return F - Cup Fitting
Capillary Lines are 48" (1220mm)
Limit Valve Distance from Condensers
Customer Provided Piping DPN001419
Pg. 1, Rev. 1
50/60Hz A B C D E* F**
7
Product Description
33"
72" (838mm)
(1828mm)
24" Nominal
(609mm)
Water-Regulating
Valve Assembly
Capillary Tubes
20-1/4"
(514mm)
10-1/2"
(267mm)
6-1/2"
(165mm)
8
Product Description
78"
(1981mm)
102"
(2591mm)
24" Nominal
610 mm
9
Product Description
! WARNING
Risk of electric shock. Can cause death or injury.
Disconnect all local and electric remote power supplies before working within.
! CAUTION
Risk of sharp edges and heavy parts. May cause personal injury or equipment damage.
Wear gloves to prevent injury to hands.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.
NOTE
Before beginning to install the Liebert XDC, read all instructions, verify that all the parts are
included and check the nameplate to be sure the Liebert XDC voltage matches available utility
power.
Follow all local codes.
Enclosure Cover
Latch
Enclosure Cover
Latches
10
Product Description
2. Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 11).
Enclosure Cover
Not Shown for Clarity
3. Route the input hazardous voltage electrical power wiring through the top right knockout on the
primary electrical enclosure (see Figure 11) to the disconnect switch L1, L2 and L3 (see
Figure 12). Observe proper phasing.
4. Connect the ground wire to the ground lug (see Figures 12 and 14 for 60Hz models and
Figures 13 and 15 for 50Hz models).
Ground
Lug
Primary
Disconnect
Switch
11
Product Description
Compressor Customer
Circuit Breakers Power
Busbar Primary Power Block Connection
Wire
Raceway
Ground
Lug
Primary
Disconnect
Switch
Power Connection
From Primary
Power Block
Ground Lug
Transformer 2
Secondary Disconnect Secondary
Switch Power Block
Pump Fuse
Blocks
Transformer
Fuse Block
Transformer 1
Pump Contactors
12
Product Description
13
Product Description
Figure 17 Electrical enclosure knockout locations for Extra Low Voltage connections
User Interface Liebert XD Module Condensate
(Wall Box) Wiring Connections (optional;
depends on features
Temperature/Humidity supplied with Liebert XD Module)
Sensor Wiring
Alternate Knockout
for Temperature/Humidity
Sensor Wiring
14
Product Description
Factory-Wired
TS-3
TS-4 Temperature
TS-5 Sensor(s)
TS-6
H2O (24)
RAD1 (50)
XDOC (51)
K3COM
K3NO
K3NCL
37
38
77
78
15
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
2.0 PIPING AND FILLING WITH REFRIGERANT: R-134A AND R-407C CIRCUITS
Liebert XDC supply line, from Liebert XDC 1-1/8" OD (1.025" ID) for lengths up to 60 feet
supply to farthest Liebert XD cooling module 1-3/8" OD (1.265" ID) for lengths over 60 but less than 175 feet
Liebert XDC return line, from farthest 2-1/8" OD (1.985" ID) for lengths up to 60 feet
cooling module to Liebert XDC return 2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet
From any model Liebert XDO/Liebert XDH 1/2" OD (0.430" ID) for lengths up to 10 feet
supply to supply line of Liebert XDC 7/8" OD (0.785" ID) for lengths over 10 but less than 25 feet
From any model Liebert XDO/Liebert XDH 7/8" OD (0.785" ID) for lengths up to 10 feet
return to return line of Liebert XDC 1-1/8" OD (1.025" ID) for lengths over 10 but less than 25 feet
From any model Liebert XDV/Liebert XDCF 1/2" OD (0.430" ID) for lengths up to 10 feet
supply to supply line of Liebert XDC 5/8" OD (0.545" ID) for lengths over 10 but less than 35
From any model Liebert XDV/Liebert XDCF 5/8" OD (0.545" ID) for lengths up to 10 feet
return to return line of Liebert XDC 7/8" OD (0.785" ID) for lengths over 10 but less than 35 feet
16
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Liebert XDP/ SLOPEThe main supply and return lines to and from the Liebert XDC must be sloped downward
Liebert XDC toward the Liebert XDC at a rate of 1-2" for every 20 feet (25.4-51mm per 6m) of pipe run.
Horizontal connector lines should also be sloped downward from the cooling modules toward the
main supply and return lines.
17
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
4" (102mm)
7/8"
(22mm) ID
Flow Direction
18
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Liebert XD Liebert XD
Cooling Cooling
Module #1 Module #2
Bypass Flow
Controllers
Coolant
Supply
Filter Dryer
Coolant Assembly
Return
Liebert XDP
or
Liebert XDC
! CAUTION
Risk of overpressurization. Can cause equipment damage.
Do not exceed 150 psig (1034 kPa; 10.34 bars) in the R-134a circuit.
Insulation
NOTE
Piping should not be insulated before it has been checked for leaks. Applying good insulation to
pipes before checking for leaks would prevent easy detection of leaks.
Insulate all piping between the Liebert XDC and cooling modules to prevent condensation where the
piping passes through non-conditioned areas.
19
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
NOTE
System refrigerant volume calculations derived from Tables 6, 7, 8 and 9 are based on a fully
loaded system. Additional charge may be required for lightly loaded systems.
Table 6 System R-134a charge for a Liebert XDC with any model Liebert XDH/Liebert
XDO/Liebert XDV/Liebert XDCF
Per Liebert XD Unit
Refrigerant Charge, (Excludes Connector Lines
lb (kg) to and from Liebert XD Cooling Module)
157 lb. (65.7kg) Liebert XDC
3.55 lb. (1.61kg) Liebert XDO
2.32 lb. (1.05kg) Liebert XDV
5.32 lb. (2.41kg) Liebert XDH
1.41 lb. (0.64kg) Liebert XDCF
Table 7 System refrigerant charge for the supply and return mains
Refrigerant Charge,
lb/foot (kg/m) Supply/Return Main Length and Diameter
0.45 (0.67) Main supply actual length per 1-1/8" OD copper tubing
0.68 (1.01) Main supply actual length per 1-3/8" OD copper tubing
0.28 (0.42) Main return actual length per 2-1/8" OD copper tubing
0.43 (0.64) Main return actual length per 2-5/8" OD copper tubing
Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb/foot (kg/m) Hard-Piped Connector Length and Diameter
0.08 (0.12) 1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF supply connector actual length
0.13 (0.19) 5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length
0.26 (0.39) 7/8" OD Liebert XDO/Liebert XDH supply connector actual length
0.02 (0.03) 5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length
0.07 (0.1) 1-1/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length
20
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Table 9 R-134a refrigerant charge for Liebert XD Flex Pipe connector lines to and from any
model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb. (kg) Metal Liebert XD Flex Pipe Connector Length
Supply Line Diameter 1/2"
0.3 lb. (0.14) 4 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.5 lb. (0.23) 6 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.7 lb. (0.32) 8 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.8 lb. (0.36) 10 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
Return Line Diameter 5/8"
0.01 lb. (0.01) 4 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.02 lb. (0.01) 6 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.03 lb. (0.01) 8 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.03 lb. (0.01) 10 ft. Liebert XD Flex Pipe existing Liebert XDV systems
Return Line Diameter 1"
0.13 lb. (0.06) 4 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.2 lb. (0.096) 6 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.27 lb. (0.126) 8 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.33 lb. (0.15) 10 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
2.5.1 Calculating Refrigerant ChargeExample
Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert
XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant
required for one system combining a Liebert XDC with Liebert XD cooling modules (Liebert XD
CoolFrame, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert
XDC with 20 Liebert XDV8 cooling modules.
Table 10 Calculating refrigerant chargeexample
Number of Units
or Piping Length, Pounds
Components feet Per Component Total, lb.
Liebert XDC 1 157 157
Liebert XDV8 Cooling Modules 20 2.32 46.4
Supply Main, 1-1/8" 100 0.45 45
Return Main, 2-1/8" 100 0.28 28
Liebert XDV 1/2" supply Liebert XD Flex Pipes 20 0.8 16
Liebert XDV 5/8" return Liebert XD Flex Pipes 20 0.03 0.6
Total 293
Total
21
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
! WARNING
Risk of refrigerant system explosion or rupture from overpressurization. Can cause death,
injury and equipment damage.
Installer must install a 400 psig pressure relief valve in each of the two R-407C refrigerant
circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and
the pressure relief valves.
For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a
notified body to the EU Pressure Equipment Directive.
22
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
For Air-Cooled Liebert Lee-Temp / Flood Back Head Pressure Control Units Only
NOTE
Proper safety equipment and proper refrigeration tools are required. Check unit nameplate for
correct refrigerant type before topping off or recharging a system.
NOTE
Refrigerant R-407C is a blend of three components and must be introduced and charged from
the cylinder only as a liquid.
Refrigerant R-407C uses a POE (polyolester) lubricant. Do not open the compressor unit piping
to the atmosphere for more than 15 minutes. The compressors contain POE oil that is very
hygroscopic; it quickly absorbs water from the atmosphere. The longer the compressor piping is
open to the atmosphere, the harder it will be to fully evacuate. If left open too long, the POE oil
may need to be replaced before achieving the required vacuum level.
POE oils also have a property that makes them act as a solvent in a refrigeration system.
Maintaining system cleanliness is extremely important because the oil will tend to bring any
foreign matter back to the compressor. Refer to the ASHRAE refrigeration handbook for
general good-practice refrigeration piping.
Table 12 Receivers and head pressure kits for Liebert Lee-Temp condensers
Ambient Temp 35 to 105 -30 to 105
Range, F (C) (2 to 41) (-34 to 41)
Condenser for
2 x DCSL616 2 x DCSL616
Each XDC160A
Receiver Kit for 2 x 181610G2 1 x 179713G1 1
Each XDC160A 2 x 181610G4 1 x 179713G3 2
Head Pressure
Kit for Each 2 x 179711G1 2 x 179711G2
XDC160A
1. 120V heater or
2. 230V heater
23
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
4
6
See
See
Note 14
Note 12
* Hot Gas Line
From Unit
(Circuit 1)
24
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
B
* Hot gas line
from unit
(Circuit 1)
5
Liebert Lee-Temp
heater pad electric
box this end C
(See DPN000937,Pg. 3)
* Hot gas line to
condenser (Circuit 1) Electrical service
5 Hot gas line
96" (2438mm) receiver 7 by others
(Circuit 1)
shown; some systems Liquid return Ensure piping stays
See Note 14
use smaller receivers A D line to unit Liquid line below electrical box
Position elbow to direct (Circuit 1) (Circuit 1) See Note 14 and does not protrude
relief valve downward Metal
Clamp Isolator See Page 5 for piping connection details
Mounting Instructions
Note 14
1. Uncrate carton and inspect for damage to
condenser and condenser control panel. Materials Supplied by Liebert
2. Assemble legs per instructions as shown. 1 Built-in condenser control box. See electrical drawing
3. When piping long, vertical rises, oil traps are for details and field wiring.
recommended on hot gas line every 25 ft. (7.6m) 2 Air-cooled condenser.
(see 2.6 Install Double Discharge Risers). 3 Piping access cover to be reinstalled when piping is completed.
4. Wire according to electrical diagram on inside 4 3/8"-16 x 3/4" long bolts - (20 total) attaches legs to
of condenser control box and in accordance with condenser frame.
all local codes. 5 3/8"-16 x 1-1/4" long bolts - (10 total) attaches legs to
5. All condenser locations more than 200 ft. (61m) of receiver. 3/8" nuts (10 total). 3/8" washers (20 total)
equivalent piping length away from Liebert XDC unit 6 Terminal block for 2 wire 24 volt interlock connection between
must consult factory for special piping considerations. Liebert XDC unit and Liebert condenser.
6. Field to size refrigerant lines so as not to exceed 7 Condenser legs - (5) fivelegs for (6) six-fan models.
2F (1.1C) saturation loss for total equivalent length 8 Lee-Temp:
(do not use connection sizes to determine line sizes). a. Insulated storage receiver - storage
7. Condenser installation is limited to a maximum of receiver (1) per circuit. Receiver size varies.
15 ft. (4.6m) location below Liebert XDC unit. b. Dual head pressure control valve assembly
8. Do not run piping or wiring in the path of air flow with integral check valve(s) - (1) one per circuit (See Note 14)
as this will hamper the system performance. c. Rotalock valve - (1) one per circuit, field-installed.
9. Install field-supplied inverted traps on hot d. Pressure relief valve - (1) one per circuit, field-installed.
gas lines between condenser and field piping. e. Liquid level indicator - (1) per circuit
10. All other piping field-supplied and field-connected. factory-installed on receiver.
11. Inverted traps must be installed to allow proper
clearance to fully open condenser control box door DPN000937
and in accordance with local electric codes. Pg. 2, Rev. 9
12. Secure Lee-Temp receiver assembly and each leg to
condenser frame using hardware provided. Receiver
can be mounted on either side of condenser.
13. Lee-Temp Item B is shipped as a pre-piped
assembly shipped loose for field installation. See Figure 29 for details on piping connections.
Item C is shipped loose for field installation.
14. Fasten liquid and hot gas lines using flat
surface clamps with isolators (field provided).
Support field piping separately to avoid coil
damage and loss of charge.
15. Relieve pressure at access port. Replace access port
fitting with relief valve before charging system.
25
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Figure 26 Liebert XDC piping schematic and Liebert Lee-Temp heater pad wiring
Rotalock Valve Combination
Inverted Trap Head Pressure Control
(By Others) & Check Valve
Condenser
Pressure Relief Valve Control Box
Solenoid Valve
Dehydrator Expansion Valve
Liquid Level
Indicator External Equalizer
Hand Shutoff
Valve By Others
Sensing Bulb
Sight Hot Gas Bypass Valve
Glass Service Valves
Discharge Line Suction Line
Separate Continuous
L1 Electical Source
By Others
GND Volts
115
Circuit 1 & 2 Optional Model With 3 Heater Pads Per Receiver 200/208/230
L2 Total Watts Per Receiver
Standard 300 Watt (2 Heater Pads)
Optional 450 Watt (3 Heater Pads)
L1 1 Phase 50/60 Hz
GND
DPN000937
Lee-Temp Heater Pad Wiring Pg. 3, Rev. 6
26
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Condenser Coil
Rotalock
Valve **
Check
Head Pressure Valve
Control with 1/4" (6.4mm)
Integral Check Pressure Relief
Liebert Valve **
Valve Lee-Temp
Receiver Sight Glass
Some Models
Traps * every 25 ft. Have 2 Sight Glasses
n
(7.6m) of rise on hot e tur ser
R n Standard Piping
gas line only i q u i d on d e
L C Assembly **
m
fro
Single Liebert XDC Circuit Shown
Factory-Supplied Piping
Field-Supplied Piping
* Components are not supplied by
Liebert but are recommended
for proper circuit operation and
maintenance.
Liquid/Return * * Components supplied by
DPN000937
Hot Gas/Discharge Liebert and must be
Pg. 4, Rev. 6
field-installed.
Table 13 Recommended refrigerant line sizes, DX R-407C, OD copper
Liebert XDC 160
Equivalent * Hot Gas Line,
Length, ft., (m) in. Liquid Line, in.
50 (15) 1-1/8 7/8
100 (30) 1-1/8 1-1/8
150 (45) 1-3/8 1-1/8
200 (60) 1-3/8 1-1/8
* Double risers are required when hot gas vertical rise is 15 feet or
more (see 2.6 - Install Double Discharge Risers).
27
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Figure 28 DCSL616 piping connectionstwo refrigerant circuits connected for parallel flow
Condenser
Coil (Circuit 2)
Condenser Coil
(Circuit 1)
Inverted Trap * on discharge
line to extend above base of Additional
coil by a minimum of Piping
7-1/2" (190mm) Assembly **
Rotalock
Valve **
Check
Head Pressure Valve
1/4" (6.4mm)
Control with Pressure Relief
Integral Check Valve **
Liebert
Valve
Lee-Temp
Receiver Sight Glass
Some Models Have
2 Sight Glasses
Traps * every 25 ft Standard
om
(7.6m) of rise on hot i q uid n Fr r Piping
L tur nse Assembly **
gas line only R e nd e
Co
28
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Figure 29 DCSL616 piping connectionstwo refrigerant circuits connected for parallel refrigerant flow
29
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
2.6.1 Air-Cooled Condenser with Liebert Lee-Temp Flooded Condenser Head Pressure
Control SystemR-407C (DX) Circuit
The Liebert Lee-Temp system consists of a modulating type head pressure control valves and insu-
lated receivers with heater pads to ensure operation at ambient temperatures as low as -30F (-
34.4C).
NOTE
Liebert Lee-Temp heater pads require a separate, continuous electrical source. See nameplate
on unit for proper voltage.
Evacuation and Leak CheckR-407C (DX) Circuit (Air and Water/Glycol Systems)
1. Make sure the unit is Off. Open all disconnects and pull all fuses except the control fuses. On
units supplied with circuit breakers, open all breakers except for the transformer.
2. Energize the liquid line solenoid valves via 24VAC or through Diagnostics under Test Outputs,
select DEHYDRATION to be On (see 5.3.17 - DIAGNOSTICS). This will energize the solenoids
and hot gas valves to open simultaneously on Circuit 1 and Circuit 2.
NOTE
The procedures above allow the technician to use 24VAC power and controls to open liquid line
solenoid valve(s) for the dehydration process. If no power is at the unit disconnect, the
technician is to use a separate 24VAC source rated at 75 VA and connect to the system liquid
line solenoid valve(s) directly.
3. Attach refrigerant gauges to the suction and discharge service valves of the compressor.
4. Open all compressor service valves, including those located outside the Liebert XDC.
5. Connect the tank of dry nitrogen to the Schrader valves on the liquid lines and the hot gas lines.
6. Pressurize the system circuit(s) to 150 PSIG (1034 kPa; 10.34 bars) with dry nitrogen with a trace
of refrigerant. Check the system for leaks with a suitable leak finder.
7. After completion of leak testing, release the test pressure (per local code) and connect to vacuum
pump(s) at the Schrader valves on the liquid lines and on the hot gas lines.
8. After 4 hours of pulling a deep vacuum, check the vacuum levels and, if they have not changed,
break the vacuum with dry nitrogen.
9. Pull a second and third vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.
30
Piping and Filling with Refrigerant: R-134a and R-407C Circuits
Table 17 Air-cooled systems - liquid line charge - R-407C refrigerant per 100 ft (30 m) of Type
ACR copper tube
O.D., inches Liquid Line, lb (kg) Hot Gas Line, lb (kg)
3/8 3.7 (1.7) -
1/2 6.9 (3.1) -
5/8 11.0 (5.0 2.2 (1.0)
3/4 15.7 (7.1) 3.1 (1.4)
7/8 23.0 (10.4) 4.5 (2.0)
1-1/8 39.3 (17.8) 7.8 (3.5)
1-3/8 59.8 (27.1 11.8 (5.4)
1-5/8 - 16.7 (7.6)
Table 18 Indoor water/glycol-cooled module R-407C refrigerant charge
Model 60 Hz Charge / Circuit, lb (kg)
Liebert XDC 160 30.0 (13.2) per circuit
31
Installation Checklist
32
Checklist for Liebert XDC Startup
! WARNING
Risk of piping and component rupture. May cause injury or equipment damage. Closing
service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do
not close valves without following recommended procedures for repair, maintenance and
replacement of components. Install pressure relief valves in field piping that may become
isolated by service valves.
NOTE
Before any action that could cause a disturbance in the Liebert XD systems cooling function
is begun, the facility manager MUST be informed. In addition, after the action is taken and
the work is finished, the facility manager MUST be informed
1. Verify that bypass flow controllers were installed (if applicable), see Table 5:
2. Check all isolation ball valves in the Liebert XDC and Liebert XD cooling module and verify that
all are open.
3. Check rotation of Liebert XDC pumps.
Use the rotation device provided with 460V models of the Liebert XDCthis device must be held
against the pump
housingat the inspection screw prior to energizing the pumpsGreen indicates proper rotation;
Green and Red indicate incorrect rotation.
Table 19 Liebert XDC pump light indicator
Indicator Lights
Description
Green Red
The electricity supply has been switched off or the pump has
Off Off
been cut out by the thermal switch.
On Off The electricity supply has been switched on. Normal operation.
The electricity supply has been switched on. The direction of
On On
rotation is wrong.
4. Check rotation of fans on Liebert XD cooling modules.
5. Verify that air is being discharged in the cold aisle.
6. Check rotation of fans on condenser(s) of Liebert XDC (air-cooled units only)Verify that air is
being discharged out to the atmosphere.
7. Confirm that the total calculated refrigerant R-134a amount has been properly charged into the
system [see 2.5 - Filling the Pumped CircuitR-134a].
8. Confirm that the total calculated refrigerant R-407C amount has been properly charged into the
system (see 2.7 - Filling the Direct Expansion (DX) CircuitR-407C).
9. Confirm that the remote temperature/humidity sensor provided has been installed in the correct
location.
The correct location is near the return side of a main air mover such as a Liebert Deluxe
System 3. If more than one Liebert XDC is installed, use a different location for each remote sen-
sor for best temperature/humidity calculation.
33
Checklist for Liebert XDC Startup
4.1 System Refrigerant Charges Over 35 lb. (15.9kg) Require Additional Oil
4.1.1 Liebert XDC DX R-407C Circuit Volume
NOTICE
Risk of improper lubrication. May cause equipment damage.
Liebert XDCs refrigerant R-407C circuits with refrigerant charges over 55 lb (24.9kg) require
additional oil. See Figure 30 for the amount required for various charge levels.
Once the system has been fully charged with refrigerant, use a hand pump to add the
additional oil at the suction side of the system while the system is running.
The amount of oil added by field service must be recorded on a tag attached at the tandem,
(the amount added along with the date it was added). This will be documented on a tag
located at the tandem compressor and marked Oil Added Field Service Record. Refer to the
Liebert XDC user manual, SL-16671, available at Lieberts Web site, www.liebert.com
140
130
120
110
100
90
80
70
60
40
50
30
20
10
0
0 100 200 300 400
XDC160 System Refrigerant Field Charge Per Circuit, Pounds
To calculate the oil required, use the following formula:
Additional Oil Required per Circuit = (Refrigerant Charge * 0.4 - 22)
Enter the refrigerant charge in pounds to determine the oil required in ounces
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system
damage.
Failure to use oil types, viscosities and quantities recommended by the compressor
manufacturer may reduce compressor life and void the compressor warranty. See oil types
specified in Table 20.
Do not mix polyol ester (POE) and mineral-based oils.
Do not mix oils of different viscosities.
Consult Emerson or the compressor manufacturer if questions arise.
Table 20 Compressor oil types
Refrigerant Type
Compressor Type R-407C
Copeland Scroll and Digital Scroll POE OIL - ISO 32 Viscosity
Use Copeland POE Oil ULTRA 22 CC, Mobil EAL Arctic 22 CC, Copeland brand Ultra 22 CC, Copeland brand Ultra 32 CC,
Copeland brand Ultra 32-3MAF, Mobil EAL Arctic 22 CC or Uniqema RL32-3MAF or other Copeland-approved oil.
34
Checklist for Liebert XDC Startup
35
Microprocessor Control
Active alarms are displayed on the LCD screen and sound an audible beep. To silence an alarm, press
the Alarm Silence/Help key as prompted on the display.
Setpoints, DIP switch settings and other selections were made during factory testing of the unit based
on typical operating conditions. (Other default selections were made according to options included
with the unit.)
ADJUST THE FACTORY DEFAULTS ONLY IF THEY DO NOT MEET YOUR SPECIFICATIONS.
Allowable ranges are displayed by pressing the Help key. A password will be required (if enabled) to
change setpoints, time delays, etc.
The display normally shown includes the present room temperature, humidity, active status func-
tions and active alarms. More detailed status and alarm information is available from the menu.
5.1.1 Display
To turn the unit On, press the On/Off (I/O) key after power is applied to the Liebert XDC.
To turn the unit Off, press the On/Off (I/O) key before power is disconnected.
Table 21 User interface keypad functions
Keypad Function
On/Off (I/O) Turns the unit On or Off (top far left keypad)
Menu Enables the user to access the program menu to change setpoints, alarms, etc. (top near left)
Raises the value of displayed parameter while in a set mode (set points, time, etc).(arrow, top
Up Arrow Key
near right)
Escape (Esc) Allows user to move back to a previous menu (top far right)
If an alarm is present, press this key to silence the alarm. Help text will appear if this key is
Alarm Silence
pressed when no alarm is present (bottom left)
Down Arrow Lowers the value of displayed parameter while in a set mode (set points, time, etc).(arrow,
Key bottom near right).
After setting a control value, press ENTER to store the information in the microprocessor
Enter
(bottom right).
36
Microprocessor Control
5.2 Controls
The microprocessor control for the Liebert XDC features an easy-to-use, menu-driven liquid crystal
display. The menus, control features and circuit board details are described in this section.
37
Microprocessor Control
5.3.2 SETPOINTS
Selecting SETPOINTS from the Main Menu will reveal the following menu items:
Table 22 Setpoint functions, default values and allowable ranges
Menu Item Function Default Range
MIN TEMP SP * Minimum room temperature setpoint 72 (22) 50-80 (10-27)
HI AIR TEMP High room air temperature alarm 80 (27) 35 to 95 (2-35)
LO AIR TEMP Low room air temperature alarm 55 (13) 35 to 95 (2-35)
* For optimal cooling performance, the minimum temperature setpoint should be at least 1-2 below the expected temperature at
the remote sensor, which may require additional consideration of the remote sensor location or minimum temperature setting.
If the minimum temperature setpoint is set above the typical remote temperature sensor reading, this will reduce the Liebert
XD cooling output and, in extreme cases, cause erratic Liebert XD performance.
MIN TEMP SP
This setpoint is used to keep the room temperature above the setpoint. The Liebert XDC can lower
the room temperature too much depending on the room dew point and load. This setpoint will back off
the cooling to keep the room temperature above this temperature, see 5.3.1 - Viewing or Changing
Settings.
NOTE
This is not a true room temperature setpoint. The Liebert XDC will try to cool as much as
possible. If it is able to cool the room to this setpoint, it will back off its cooling capability to try
to keep the room temperature at or above this setpoint, but the Liebert XDC has no heaters, so it
cannot warm the room.
HI AIR TEMP
This is the temperature at which the HIGH REMOTE TEMP and HIGH LOCAL TEMP alarms will
be activated, see 5.3.1 - Viewing or Changing Settings.
LO AIR TEMP
This is the temperature at which the LOW REMOTE TEMP and LOW LOCAL TEMP alarms will be
activated, see 5.3.1 - Viewing or Changing Settings.
38
Microprocessor Control
5.3.3 STATUS
The user can check the status of cooling percentage, pump and compressor operating status and tem-
perature of the refrigerant.
VALVE OPEN %0-100
COMP 1A, 2A, 1B, 2BOn/Off
PUMP 1On/Off
PUMP 2On/Off
REFRIG TRefrigerant temperature 0-100F
5.3.6 TIME
The controller time clock must be set to allow for time stamping of the alarms for alarm history. To
change the time press ENTER to select the function, then use the up or down arrow key arrow to
change the first character, press Enter to store, then press the up or down arrow key to change the
second character, press Enter to store, etc.
NOTE
The clock uses the 24 hour system (for example: 17:00 would be 5:00 PM). Battery backup
protects the date and time settings.
5.3.7 DATE
The controller date must be set to allow for time stamping of the alarms for alarm history. To change
the date press ENTER, then use the up or down arrow key to change the first character, press
ENTER to store, press the up or down arrow key to change the second character, etc.
39
Microprocessor Control
NOTE
None of these setpoints should be changed before consulting a Liebert representative.
Changing any of these setpoints could drastically affect the system.
Selecting Setpoint/Setup from the Main Menu will display the following selections:
Table 23 Setup operation functions default values and allowable ranges.
Menu Item Function Default Range
0 to 9.9 min
RESTART Restart time delay 0.1 min
(0 = manual restart)
C/F DEGREES Celsius or Fahrenheit F C or F
PUMP START TD Pump start time delay 10 sec 3 - 120 sec
PUMP WAIT TD Pump wait time delay 10 sec 3 - 120 sec
PUMP OFF TD Pump off time delay 5 sec 5 - 120 sec
LEAD PUMP Lead Pump Pump 1 Pump 1/Pump 2
DIPSWCH DIP switch status NA NA
RESTART
This is the time delay after which the control will attempt to restart the Liebert XDC after a loss of
power. It is programmable from 0.1-9.9 minutes in 6-second (0.1 minute) increments. The user can
also select NO. If NO is selected, the system WILL NOT automatically restart. The default is 0.1 min-
utes.
C/F DEGREES
The user may select control and alarm parameters in either Celsius or Fahrenheit. The default is
degrees Fahrenheit.
PUMP START TD
The user may set a Pump Start Time Delay to ensure that refrigerant begins flowing when the pump
starts. If refrigerant does not begin flowing before the user-set delay expires, the pump will be turned
off (see PUMP OFF TD).
PUMP WAIT TD
The user may set the pump wait time delay to prevent the pump from continuing to run when refrig-
erant is not flowing. If a pump is running normally and refrigerant flow is lost, the pump will stay on
for the specified amount of time trying to re-establish refrigerant flow. If refrigerant flow resumes
during the specified interval, the pump will continue operating. If the wait time expires and refriger-
ant flow has not resumed, the pump will shut down (see PUMP OFF TD).
40
Microprocessor Control
PUMP OFF TD
The user can set the amount of time a pump will remain off when refrigerant flow is interrupted or stops.
After the time delay has expired, the control will try to restart the pump (see PUMP START TD).
LEAD PUMP
This allows the user to select which pump is the active pump. It can be set to PUMP 1 or PUMP 2.
The control will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF
FLOW condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time
delay has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.
LEAD TANDEM
Not currently used.
DIPSWCH
This allows the user to read the eight-position DIP switch located on the control board. The switches
are numbered according to the numbers on the DIP switch. The numeral 1 indicates the switch is ON
and a 0 indicates the switch is OFF. These switches are factory-set and should not require any user
changes.
Table 24 Liebert XDC DIP switches and factory settings
DIP Switch Factory Setting
1 Off
2 Off
3 Off
4 Off
5 Off
6 Off = Standard, On = Dual Source
7 Off
8 Off
VALVE TIME
Valve travel time is not currently used.
VLV ST OPEN
Valve start open % is not currently used.
VLV START TD
Valve start time delay is not currently used.
MIN VLV SET
Minimum valve setpoint is not currently used.
COMP SEQ ON
When the Liebert XDC is started, this is the time delay before the next compressor comes on when the
control is sequencing on compressors.
COMP OFF TD
This is how long a compressor must be off before the control will turn it back on.
INNERSTAGE TD
This is how long the control must wait between compressor stage changes during normal operation.
WSK1 TD
Compressor winter start kit time delay for all compressors.
WSK2 TD
The winter start kit 2 time delay is not currently used.
100% START TD
This is how long the control will keep the unit at 100% cooling during startup after all compressors
have staged on.
41
Microprocessor Control
42
Microprocessor Control
43
Microprocessor Control
44
Microprocessor Control
5.3.17 DIAGNOSTICS
This allows the user to perform checks on inputs, outputs, and conduct a test of the Liebert XDC con-
trol board from the wall box.
Entering the TEST OUTPUTS will interrupt system operation. Selecting TEST INPUTS or TEST
MICRO will not interrupt system operation. Pressing ENTER and selecting TEST OUTPUTS will
permit the user to toggle the following outputs on and off:
PUMP 1On/Off
PUMP 2On/Off
COMP 1A, 2A, 1B, 2BOn/Off
GREEN LAMPOn/Off
RED LAMPOn/Off
COMMON ALARMOn/Off
LLSV1, LLSV2On/Off
HGSV1, HGSV2On/Off
HGV1, HGV2On/Off
DEHYDRATION1, DEHYDRATION2On/Off
Pressing ENTER and selecting TEST INPUTS will permit the user to read the following inputs:
INPUT POWEROn/Off
CONDENSATIONOn/Off (condensation detection)
DIFF PRESSUREOn/Off (differential pressure switch)
CUSTOMER ALARMOn/Off
Pressing ENTER and selecting TEST MICRO will permit the user to test the microcontroller and
associated circuitry on the Liebert XDC control board.
45
Alarm Descriptions and Solutions
46
Alarm Descriptions and Solutions
SHORT CYCLE C1A Activated when compressor 1A turns On, Off, then back On, 5 times
within 10 minutes, or 10 times within 1 hour.
SHORT CYCLE C1B Activated when compressor 1B turns On, Off, then back On, 5 times
within 10 minutes, or 10 times within 1 hour.
SHORT CYCLE C2A Activated when compressor 2A turns On, Off, then back On, 5 times
within 10 minutes, or 10 times within 1 hour.
SHORT CYCLE C2B Activated when compressor 2B turns On, Off, then back On, 5 times
within 10 minutes, or 10 times within 1 hour.
HIGH REFRIGERANT TEMP 1 Activated when the refrigerant temperature sensed from
refrigerant temperature sensor 1, exceeds the user specified setpoint. See 5.3.2 - SETPOINTS.
Alarm will reset itself when the refrigerant temperature drops below the setpoint.
LOW REFRIGERANT TEMP 1 Activated when the refrigerant temperature sensed from
refrigerant temperature sensor 1, drops 1.5 degrees Fahrenheit below the refrigerant tempera-
ture control point. Alarm will reset itself if the refrigerant temperature raises back up before the
control shuts down because of low refrigerant temperature.
FAILED REFRIGERANT SENSOR 1 Activated when the control stops receiving a signal
from the refrigerant temperature sensor 1. If this alarm becomes active, the control will slowly
back down cooling over a 9-minute period. This alarm will shut down the Liebert XDC, main
power (disconnect switch) must be turned OFF then back ON to clear this alarm.
HIGH CHILLED WATER TEMP not currently used.
LOW CHILLED WATER TEMP not currently used.
FAILED CHILLED WATER SENSOR not currently used.
VALVE FAILURE not currently used.
LOSS OF POWER Activated when the unit is ON and operational, and 24VAC power to the
control is lost to the control. This alarm will be emitted when power is restored to the control
(unit). Unit will restart at a user defined time delay after power is restored. See 5.3.8 - SETUP
OPERATION. Alarm will reset itself after 30 seconds of run time.
NOTE
Alarms MUST BE ACKNOWLEDGED before they can be RESET. To acknowledge / silence
alarms press the Alarm Silence / ? key.
47
Alarm Descriptions and Solutions
48
Alarm Descriptions and Solutions
49
Troubleshooting
7.0 TROUBLESHOOTING
Table 25 Liebert XDC troubleshooting
Symptom Possible Cause Check or Remedy
No main power Check L1, L2, and L3 for rated voltage.
Loose electrical connections Tighten connections.
Pump/compressor
Overloads tripped Allow pump to cool. Check amp draw.
will not energize
Tripped circuit breaker Check circuit breaker to pump(s).
Incorrect phase wiring See Table 19.
Isolation valve(s) on pump suction
Open all isolation valves completely during normal operation.
and/or discharge is closed.
Check Liebert XD cooling modules to make sure that they are
Liebert XD cooling modules are Off.
ON prior to starting the Liebert XDC
Check alarm(s) history on Liebert XDC. The Liebert XDC was
operating below the dew point for a significant amount of
Low Refrigerant Temperature time. Check humidity in conditioned space; lower humidity if
(high dew point) necessary to allow Liebert XDC to operate at a lower
temperature. (Disconnect must be switched to Off then back
Pump will not run to On to allow Liebert XDC to reset.)
Place the sensor on the return air side of the primary air
Incorrect location of
mover (I.e., Liebert Deluxe System 3). Do not install the
temperature-humidity senors
sensor near unsealed doors, windows and similar areas.
Check both differential pressure settings. If not within 6 psi,
Pressure switch not making contact 1 psi (41 kPa, 7kPa; 0.41 bars, 0.07 bars) then manually
change accordingly.
See 2.7 - Filling the Direct Expansion (DX) CircuitR-
Not enough charge
407C.
Check for adequate charge in system, refer to the user
Cavitation due to vapor in pump manual. 2.7 - Filling the Direct Expansion (DX) CircuitR-
407C
Pump noisy
Pump is rotating in reverse See Table 19
Worn motor bearings Replace pump
Check humidity of room along with location of remote
Low Refrigerant Temperature
sensors. Make sure that the sensors are not located in a cold
(high dew point)
area where there is a lack of sufficient air flow.
Liebert XDC (Pump) When power is restored, the Liebert XDC will automatically
Loss of power
suddenly stops restart.
Clogged filter/dryer and/or impeller Clean out debris.
Check the entire system for leaks with a refrigerant sniffer.
Leak in system - loss of charge
Repair as necessary.
If there is no cooling required, turn the Liebert XDC off at the
Lack of load in the room
I/O button.
Minimum room temperature setpoint Check the setpoint by following instructions in 5.3.2 -
Room becomes
is too low. SETPOINTS.
too cold
Place the sensor on the return air side of the primary air
Incorrect location of temperature-
mover (i.e., Liebert Deluxe System 3). Do not install the
humidity senors.
sensor near unsealed doors, windows, and similar areas.
Check control panel for welded
Motor burnout contactor contacts or welded Replace defective components.
overload contacts
Main 24VAC Shorts or loose connections Check the wiring connections of the 24VAC circuit.
fuse trips Faulty circuit board Replace the circuit board.
Unstable pump While pump is running R-134a receiver level must be within
R-134a pump loop is overcharged
operation recommended levels (see Figure 31).
50
Troubleshooting
51
Maintenance
8.0 MAINTENANCE
The Liebert XD system components require little maintenance when proper fluid levels are main-
tained and proper startup and operation procedures are followed. The following tasks should be per-
formed at the intervals stated:
1. Check sight glass level of receiver on all circuits every 4-6 weeks. During normal operation, the
level should be at or above the first sight glass.
2. Check system for leaks every 4-6 weeks
Electric Service
Supplied by Others
Liebert Lee-Temp Heater Pad Liquid Line
Connection Boxes
52
Maintenance
53
Specifications
9.0 SPECIFICATIONS
Table 26 Liebert XDC specifications
XDC160 Water /
XDC160 Air Glycol
189192G3
Models XDC160AA XDC160AM 189192G5
See Tables 27, 28
and 29 for
Cooling Capacity, tons (kW) 46 (160) 37 (130)
Water/Glycol
performance data
The Liebert XDCs minimum recommended operating load is 40% of
system nominal capacity. For example, a Liebert XDC160 60Hz
Minimum Load systems minimum load would be 64kW. Loading below this value
can unfavorably affect system operation. Consult factory for any
loading below this recommendation.
Electrical Requirements
Input 460V-3ph-60Hz 380/415V-3ph-50Hz 460V-3ph-60Hz
Full Load Amps 79A
Minimum supply wire sizing ampacity 84A
Maximum fuse or circuit breaker size 100A
Dimensions, inches (mm)
Height - Main unit only 78 (1981)
Height - Main unit only, as shipped 83 (2108)
Width - Main unit 74 (1879)
Depth - Main unit 34-5/8 (879)
Height - Water / Glycol-cooled condenser stand N/A 24 (607)
Width - Water / Glycol-cooled condenser stand N/A 72 (1829)
Depth - Water / Glycol-cooled condenser stand N/A 33 (839)
Weight, lb (kg)
Main unit only 1800 (817)
Main unit only, as shipped Domestic: 1945 (882); Export: 2093 (949)
Water / Glycol-cooled condenser stand N/A 1075 (488)
Water / Glycol-cooled condenser stand, as shipped N/A 1150 (521)
Pipe Connections, inches, O.D., Cu
Refrigerant supply to Liebert XD cooling modules 1-1/8
Refrigerant return from Liebert XD cooling modules 2-1/8
Liquid line, DX circuit 7/8
Hot gas line, DX circuit 1-3/8
Heat Rejection Equipment
95F ambient air-cooled condenser 2-DCSL415 N/A
100-105F ambient air-cooled condenser 2-DCSL616 N/A
Number of XD Cooling Units Connected, Maximum (Minimum)
Liebert XDCF10 16 (6)
Liebert XDH20 8 (4)
Liebert XDH32 5 (2)
Liebert XDO16 10 (4)
Liebert XDO20 8 (4)
Liebert XDV8 20 (8)
Liebert XDV10 16 (7)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Maximum Ambient Operating Temperature, F (C) 86 (30)
Agency
Approvals CSA CE CSA
54
Specifications
55
Specifications
56
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologiesincluding Liebert power and cooling www.liebert.com
technologiesthat protect and support business-critical systems. Monitoring
Liebert solutions employ an adaptive architecture that responds liebert.monitoring@emerson.com
to changes in criticality, density and capacity. Enterprises benefit 800-222-5877
Outside North America: +00800 1155 4499
from greater IT system availability, operational flexibility and
Single-Phase UPS & Server Cabinets
reduced capital equipment and operating costs.
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
2007 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-16671_REV11_02-10
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
2007 Emerson Electric Co.