Compact NS
Circuit breakers and switch-disconnectors
from 630b to 3200 A
WEB1 cat.2015
Compact NS
Setting the standard,
once again...
The launch of Schneider Electric Compact NS in 1994 revolutionised the world of
moulded-case circuit breakers. Innovative, flexible and attractive, Compact NS rapidly
set the standard in its field.
Equipped with the new generation of Micrologic control units, Compact NS630b to
3200 circuit breakers now offer built-in power and energy metering in addition to
electrical measurement and analysis functions.
Compact NS,
simply a step ahead
I
Compact NS range
More than 10 years of techniques and technologies...
Inventor of the unique system-block concept, Schneider Electric proposes a range of circuit breakers to meet the concerns
of panel builders and contractors. The result of 30 years of experience in the field of electrical distribution,
the Compact NS range is still today the international reference on the moulded case circuit breaker market.
Flexibility Open-
Compact NS adapts endedness
to all your applications: Compact NS
protection of AC evolves together
installations, generator with your installation:
protection, motor interchangeable trip
protection, applications units, standardised
in 1000 V, switch- accessories, changing
disconnectors, source of rating without
IFE
changeover switches. disassembling the device
With Compact NS and addition of indication
you have the choice. and control functions
make Compact NS the
most flexible solution on I/O IFM
the market.
FDM121 FDM128
An answer for
each type of
solutions:
Marine Airports Oil and gas Wind mills
II
ahead quite simply
00
N S16
S1250
00N
S10
kA
N
00
0
2
kA
80
LB
NS
0
15
kA
b
630
70
H
NS
kA
H
50
N
0
320
NS
2 500
NS
2000
kA
NS
85
0b
kA
160
H
70
NS
H
III
Energy management
has never been simpler
Simple-to-install Smart Panels connect your building to real savings
in 3 steps
Measure
Embedded and stand-
alone metering & control
capabilities
Connect Save
> Integrated communication > Data-driven energy efficiency
interfaces actions
> Ready to connect to > Real time monitoring and control
energy management > Access to energy and site
platforms information through on-line
services
IV
Measure
"Smart Panels" mean
visible information
Grouping most of the electrical protection,
command and metering components, the
switchboards are now significant sources
of data locally displayed and sent via
CLOUD communication networks.
connect
and ready to be linked
to expertise
Smart Panels use reliable, simple to install
and use displays, and Ethernet and Modbus
interfaces on the EnerlinX communication
system.
Information is safely transmitted through the
most efficient networks:
Modbus SL inside switchboards, between
components
Ethernet, on cable or WiFi, inside the
building and connecting switchboards,
computers,
Ethernet on DSL or GPRS, for access to
on-line services by Schneider Electric.
Energy experts, wherever they are, are
now able to provide advises based on
permanently updated data of the building.
Save
CLOUD
V
A solution
for all application types:
Compact NS and Compact NSX Source changeover
The Compact range proposes interlocking
solutions between two devices to perform
the source changeover switch function.
As from 100 A, a motor mechanism ensures
automatic replacement of the main source
by a secondary source in order to ensure
permanent availability of energy.
Applications are numerous: operating
theatres, emergency lighting systems,
computer rooms, bank security, etc.
Motor applications
Associated with specific control units,
the Compact range ensures motor protection
functions up to 750 kW, and includes
a dedicated product, Compact NS80H-MA,
for applications up to 37 kW.
DC applications
A specific range from 100 to 630 A with
performance up to 100 kA and 750 V for
battery or traction network type applications.
1000 V / 400 Hz
applications
The Compact range covers 1000 V / 400Hz
applications up to 630 A: road and rail
tunnels, mines, wind turbines (1000 V) and
aircraft facilities (400 Hz).
VI
for an installation
with a longer service life
VII
All the guarantees
of a leading brand
Certification
The reliability of the Compact NS range
circuit breakers must be total.
Such reliability is obtained thanks to faultless
quality at all stages, from design to operation,
in complete compliance with international
standards and local certification.
Environmentally
friendly products
Schneider Electric
commits itself to
an environmental
approach,
manufacturing
products in keeping
Tools Distribution and with the requirements
of European Directive
for easy design service network
RoHS (Restriction
Full documentation, With more than 5000 of Hazardous
CAD software and sales outlets in 130 Substances) in
a library are available countries, you are non-polluting
to assist you guaranteed to find ISO 14001 certified
in all stages of world-wide the range manufacturing units.
installation design. of products complying
with your needs and
satisfying user country
standards perfectly.
VIII
Compact NS630b to 3200 General contents
Presentation 2
1
Presentation Compact NS,
even more applications...
Applications
Protection of LV distribution systems > pages A-2 et A-25
DB403915.eps
5.0 E
Micrologic
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
menu
alarm
time tr 8 12
long
(s) 4 16
Ir .8 .9
2 20
.95
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
transformers
bb distribution systems supplied by engine All circuit breakers in the CompactNS range offer
generator sets positive contact indication and are suitable for
bb long cables in IT and TN systems. isolation in compliance with standards IEC
60947-1 and 2.
DB403916.eps
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
100 % (V) 100
220/240 85
480/690
Icu
CompactNS circuit breakers protect the cables CompactNS circuit breakers automatically
100%
40 % Ics =
menu
alarm
time tr 8 12
long
(s) 4 16
Ir .8 .9
2 20
.95
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
and the starter against short-circuits. ensures type-2 coordination with the motor
Equipped with an electronic trip unit, starter, in compliance with
CompactNS circuit breakers also protect the standard IEC 60947-4-1.
cables, starter and motor against overloads.
Service connection
CompactNS service connection circuit Compact INV switch-disconnectors offering
breakers are specially designed for the visible break (see the corresponding catalogue)
service-connection function: can be combined with CompactNS circuit
Micrologic
5.0 E
bb lead seals and locking systems breakers to constitute the various types of
bb tripping curves certified by utilities service connections and meet the needs of all
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
100 % (V) 100
220/240 85
480/690
Icu
100%
40 % Ics =
menu
alarm
supplied, etc.
5.0 E
Micrologic
circuit breakers exists for circuit control and ranges, see the Compact INS/INV (offering
menu
alarm
time tr 8 12
long
(s) 4 16
Ir .8 .9
2 20
.95
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
N R
electrical installations are connected to two bb manual with mechanical device interlocking
power sources: bb remote controlled with mechanical and/or
Micrologic
5.0 E
H
NS 1200Uimp 12kV
Micrologic
5.0 E
H
NS 1200Uimp 12kV
bb a source "S1" electrical device interlocking
bb a source "S2" to supply the installation when bb automatic by adding a controller to manage
Ui 1000V Ui 1000V
8kV 8kV
Uimp Icu Uimp Icu
Ue (kA) Ue (kA)
100 % (V) 100 100 % (V) 100
220/240 85 220/240 85
480/690 480/690
Icu Icu
100% 100%
40 % Ics = 40 % Ics =
menu menu
alarm alarm
time tr 8 12 time tr 8 12
long long
(s) 4 16 (s) 4 16
Ir .8 .9.95 Ir .8 .9.95
2 20 2 20
.6.7 1 24 .6.7 1 24
.98 .5 at 6 Ir .98 .5 at 6 Ir
.5 1 instantaneous .5 1 instantaneous
.4 x In Ii 8 1012 .4 x In Ii 8 1012
6 6
tsd .4 .4 .3 tsd .4 .4 .3
the source "S1" is not available. switching from one source to the other on the
time time
short
.2 4 15 short
.2 4 15
(s) (s)
Isd3 4 5 .3 .1 3 off Isd3 4 5 .3 .1 3 off
6 2 6 2
2.5
.2 0 x In 2.5
.2 0 x In
8 .1 2 8 .1 2
2 I t 2 I t
10 on 10 on
1.5 delay 1.5 delay
x Ir x Ir
setting setting
2
Presentation
Functions
They can be combined with the FDM121 switchboard display unit to
provide all the functions of a Power Meter as well as operating
assistance.
PB103360.eps
Micrologic control unit that can be changed on site.
Control units are designed to protect Power circuits
and loads. Alarms may be programmed for remote
indications.
In addition to protection functions, Micrologic S/A/E/P
control units offer all the functions of Power Meter
products as well as operating-assistance for the circuit
breaker.
PB106360r-50.eps
Operating-assistance functions
PB111801-19_r.eps
Communication
> page A-28
Compact NS equipped with Micrologic provide
screen 2b.eps
PB103798_9.eps
DB416830.eps
3
Presentation Introduction
General characteristics
for NS630b to 3200 range
Compact Compact NS circuit breakers and auxiliaries comply with the following:
NS630b H bb international recommendations:
Ui 800 V Uimp 8 kV vv IEC 60947-1 - general rules
vv IEC 60947-2 - circuit breakers
Ue (V) Icu(kA) Ics(kA)
vv IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc.
220/240 a 70 35 vv IEC 60947-4 - contactors and motor starters
380/415 a 70 35 vv IEC 60947-5.1 and following - control circuit devices and switching elements;
automatic control components
440 a 65 32
bb European (EN 60947-1 and EN 60947-2) and the corresponding national
500/525 a 50 25 standards:
660/690 a 42 21 vv France NF
Icw 19.2kA / 1s cat B vv Germany VDE
vv U.K. BS
vv Australia AS
vv Italy CEI
bb the specifications of the marine classification companies (Veritas, Lloyds Register
50/60Hz IEC 60947-2 of Shipping, Det Norske Veritas, etc.)
AS UNE CEI BS
UTE VDE NEMA
bb French standard NF C 79-130 and the recommendations issued by the CNOMO
organisation for the protection of machine tools.
For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please
consult us.
Standardised characteristics indicated on the rating plate:
Ui: rated insulation voltage Pollution degree
Uimp: rated impulse withstand voltage Compact NS circuit breakers are certified for operation in pollution-degree 3
Icu: ultimate breaking capacity, for various values environments as defined by IEC standard 60947 (industrial environments).
of the rated operational voltage Ue
cat: utilisation category Tropicalisation
Icw: rated short-time withstand current
Ics: service breaking capacity
Compact NS circuit breakers have successfully passed the tests prescribed by the
In: rated current following standards for extreme atmospheric conditions:
suitable for isolation bb IEC 60068-2-1 - dry cold (-55 C)
bb IEC 60068-2-2 - dry heat (+85 C)
bb IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C)
bb IEC 60068-2-52 - salt mist (severity level 2).
Environmental protection
Compact NS circuit breakers take into account important concerns for environmental
protection. Most components are recyclable and the parts of Compact NS630b to
NS3200 circuit breakers are marked as specified in applicable standards.
Ambient temperature
bb Compact NS circuit breakers may be used between -25 C and +70 C.
For temperatures higher than 40 C (65 C for circuit breakers used to protect motor
feeders), devices must be derated as indicated in the documentation.
bb circuit-breakers should be put into service under normal ambient operating-
temperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 C and -25 C.
the permissible storage-temperature range for Compact NS circuit breakers in the
original packing is -50 C (1) to +85 C.
Discrimination
As standard, the Compact NS range ensures discrimination between two circuit
breakers positioned in series in an installation.
DB128013.eps
CB1
CB2
4
Positive contact indication
DB401831.eps
All Compact NS circuit breakers are suitable for isolation as defined in IEC standard
60947-2:
bb the isolation position corresponds to the O (OFF) position
bb the operating handle cannot indicate the OFF position unless the contacts are
effectively open
bb padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability
of the position-indication system.
The isolation function is certified by tests guaranteeing:
bb the mechanical reliability of the position indication system
bb the absence of leakage currents
bb overvoltage withstand capacity between upstream and downstream connections.
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(IK degree of protection against external mechanical impacts).
standard / VDE
standard / VDE
MCC IP435
CNOMO IP547
tripped
reset
5
Presentation Protection of distribution
systems
Overview of solutions
DB417642.eps
DB417643.eps
G
b systems supplied by a transformer
b systems supplied by an engine generator set
b long cables in IT and TN systems.
Power distribution
DB128023.eps
PB104844_ME.eps
Breaking capacity N 50 50 50 50 50
(kA rms) H 70 70 70 70 70
380/415 V L 150 150 150 - -
LB 200 200 - - -
Rated current (A) 640 800 ... 1000 1250
1600 2000 2500 3200
Compact NS1600b NS2000 NS2500 NS3200
PB104845_ME.eps
Breaking capacity N 70 70 70
(kA rms) H 85 85 85
380/415 V
Accompanying control units up to 3200 A page A-20
Micrologic electronic control units may be used on all Compact NS630b to NS3200 circuit
breakers and can be changed on site.
6
Compact NS630b to 3200 Functions and characteristics
Presentation 2
Protection of distribution systems
Compact NS circuit breakers from 630b up to 3200 A A-2
Micrologic control units
Overview of functions A-6
For Compact NS630b to 3200 A-8
Micrologic A "ammeter" A-10
Micrologic E energy A-12
Micrologic P "power" A-14
Power Meter functions
Micrologic A/E/P control unit with COM option (BCM ULP)
and COM Ethernet gateway A-18
Operating-assistance functions
Micrologic A/E/P control unit with COM option (BCM ULP) A-20
Switchboard-display functions
Micrologic A/E/P control unit with COM option (BCM ULP) A-21
Micrologic A/E/P control unit with COM Ethernet gateway A-23
Protection of distribution systems
Micrologic control units for Compact NS630b to 3200 A-25
EnerlinX communication system
Products overview A-28
Communication
Communication wiring system A-30
Overview of functions A-31
COM option in Compact A-32
Communication architecture A-33
IFE Ethernet interface A-34
IFM Modbus communication interface A-36
Connection of the IFE to a fixed or drawout Compact NS A-38
Connection of the IFM to a fixed or drawout Compact NS A-39
I/O application module A-40
Electrical Asset Manager Configuration Engineering tool A-42
Motor protection
Overview of solutions A-44
Earth-leakage protection
Overview of solutions A-45
Control and isolation
Overview of solutions A-46
Control and disconnection
Compact NS630bNA to 1600NA switch-disconnectors A-48
Compact NS1600bNA to 3200NA switch-disconnectors A-50
Source-changeover systems
Presentation A-52
Manual source-changeover systems A-53
Electrical interlocking
IVE unit A-54
Remote-operated systems A-55
Source-changeover systems
Associated controllers A-56
Electrical and mechanical accessories
Compact NS630b to 1600 (fixed version) A-58
Compact NS630b to 1600 (withdrawable version) A-59
Compact NS630b to 1600 A-60
Compact NS1600b to 3200 (fixed version) A-77
Compact NS1600b to 3200 A-78
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
Additional characteristics E-1
Catalogue numbers and order forms F-1
A-1
Functions and characteristics Protection of distribution
systems
Compact NS circuit breakers
from 630b up to 3200 A
Compact circuit breakers
PB104842.eps
Number of poles
Control manual toggle
direct or extended rotary handle
electric
Type of circuit breaker
Connections fixed front connection
rear connection
front connection with bare cables
withdrawable (on chassis) front connection
rear connection
Electrical characteristics as per Nema AB1
Breaking capacity at 60 Hz (kA) 240 V
480 V
600 V
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Rated current (A) In 50 C
65 C (1)
Compact NS800L. Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
Type of circuit breaker
PB104843.eps
A-2
NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200
3, 4 3, 4 3, 4 3, 4 3, 4
b b b b b
b b b b -
b (except LB) b b b -
N H L LB N H L N H N H N H
b b b - b b b b b b b b b
b b b b b b b b b b b - -
b b - - b b - b b - - - -
b b b b b b b b b b b - -
b b b b b b b b b b b - -
N H L LB N H L N H N H N H
50 65 125 200 50 65 125 50 65 50 65 85 125
35 50 100 200 35 50 100 35 50 35 50 65 85
25 50 - 100 25 50 - 25 50 25 50 50 -
A-3
Functions and characteristics Protection of distribution
systems
Compact NS circuit breakers
from 630b up to 3200 A
A-4
NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200
Micrologic
2.0 5.0 6.0 2.0 A 5.0 A 6.0 A 7.0 A 2.0 E 5.0 E 6.0 E 5.0 P (1) 6.0 P (1) 7.0 P (1)
b b b b b b b b b b b b b
- b b - b b b - b b b b b
b b b b b b b b b b b b b
- - b - - b - - - b - b -
- - - - - - b - - - - - b
- - - b b b b b b b b b b
b b b b b b b b b b b b b
- - - b b b b b b b b b b
- - - - - - - b b b b b b
- - - - - - - - - - b b b
- - - - - - - b b b - - -
b b b b b b b b b b b b b
b b b b b b b b b b b b b
- - - b b b b b b b b b b
- - - b b b b b b b b b b
- - - b b b b b b b b b b
NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200
b b
b b
b -
b b
b b
327 x 210 x 147 350 x 420 x 160
327 x 280 x 147 350 x 535 x 160
14 24
18 36
b -
A-5
Functions and characteristics Micrologic control units
Overview of functions
long time
X Y Z + instantaneous
X: type of protection
bb 2 for basic protection
bb 5 for selective protection
bb 6 for selective + earth-fault protection
bb 7 for selective + earth-leakage protection.
Y: control-unit generation
Identification of the control-unit generation.
Micrologic 5: selective protection
0 signifies the first generation.
Protection:
Z: type of measurement
DB128025.eps
long time
bb A for ammeter + short time
bb E for energy + instantaneous
bb P for power meter
PB100772R-32.eps
PB106351A32.eps
long time
+ short time
+ instantaneous
+ earth fault
DB128045.eps
long time
+ short time
+ instantaneous
+ earth leakage up to 3200A
A-6
Micrologic without Measurements and programmable protection
measurement
A: ammeter
bb I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurements
bb fault indications
bb settings in amperes and in seconds.
DB128290.eps
DB128302.eps
100 % 100 %
40 % 40 %
menu menu
DB128299.eps
DB128306.eps
DB128308.eps
4260A
N 1 2 3
100
100 % 100 % 50
0
40 % 40 %
menu menu
short time instantaneous short time instantaneous short time instantaneous short time instantaneous
Isd tsd tsd Ii tsd Ii
.4 .4 .3 .4 .4 .3
Ii Isd 4 Isd 4 Isd tsd Ii
3
4
5
(s) .4 .4 .3 6
8
10 3 5 (s) 6
8 10 3 5 (s) 6
8 10
3
4
5 (s) .4 .4 .3 6 8 10
2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12
2 8 .2 .1 3 15 2 8 .2 .1 3 15 2 8 .2 .1 3 15 2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off 1.5 10 .1 2 0 2 off 1.5 10 .1 2 0 2 off 1.5 10 .1 2 0 2 off
x Ir on I t x In on I t on I t x Ir on I t off x In
x Ir x In x Ir x In
setting delay setting delay setting delay setting delay
test
DB128300.eps
DB128307.eps
DB128309.eps
4260A
N 1 2 3
100
100 % 100 % 50
0
40 % 40 %
menu menu
DB128321.eps
4260A
N 1 2 3
100
100 % 50
0
40 %
menu
A-7
Functions and characteristics Micrologic control units
For Compact NS630b to 3200
Micrologic 2.0, 5.0 and 6.0 control units protect power Protection
circuits. Micrologic 5.0 and 6.0 offers time Protection thresholds and delays are set using the adjustment dials.
discrimination for short-circuits as well. Overload protection
True rms long-time protection.
DB414487.eps
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2) or
neutral protection at Ir (4P 4d).
Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
long time
Ir
.7
.8
.9
tr
(s) 4
8
12
alarm
Fault indications (only for micrologic 6.0)
.6
.5
.95 2
.98 1
16
20
LEDs indicate the type of fault:
.4
x In
1 .5 24
at 6 Ir
bb overload (long-time protection Ir)
short time instantaneous bb short-circuit (short-time Isd or instantaneous li protection)
Isd
3
4 5
tsd
(s) . 4 .4 . 3
Ii
6
8 10 bb earth fault or earth leakage (Ig)
2.5 6 .3 .2 4 12 bb internal fault (Ap).
2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off Battery power
on I t x In
x Ir
setting delay
test The fault indication LEDs remain on until the test/reset button is pressed. Under
tg
Ig
D E F (s) . 4 .4 . 3 normal operating conditions, the battery supplying the LEDs has a service life of
.3 .2
C G
.1
approximately 10 years.
B H .2
A I .1 2 0
on I t off
ground fault
A-8
Protection Micrologic 2.0
Long time t
DB128031.eps
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Ir
tripping between 1.05 and 1.20 x Ir other ranges or disable by changing long-time rating plug
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
accuracy: 0 to -20 % 6 x Ir 0.7 (1) 1 2 4 8 12 16 20 24 tr
accuracy: 0 to -20 % 7.2 x Ir 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 % Isd
Instantaneous 0 I
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
accuracy: 10 %
Time delay max. resettable time: 20 ms; max break time: 80 ms
DB128032.eps
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug I2t on
tr
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 I2t off
Isd
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 tsd
Thermal memory 20 minutes before and after tripping Ii
(1) 0 to -40 % - (2) 0 to -60 %
0 I
Short time
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous
Pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault Micrologic 6.0
DB128036.eps
Pick-up (A) Ig = In x A B C D E F G H J
Accuracy: 10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-9
Functions and characteristics Micrologic control units
Micrologic A "ammeter"
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all ammeter measurements
bb tripping causes
bb maximeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
q Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to provide
total discrimination for short-time and earth-fault protection, without a delay before
1 long-time threshold and tripping delay tripping.
2 overload alarm (LED) at 1.125 Ir
3 short-time pick-up and tripping delay Overload alarm
4 instantaneous pick-up A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
5 earth-leakage or earth-fault pick-up and tripping delay
6 earth-leakage or earth-fault test button
7 long-time rating plug screw Fault indications
8 test connector LEDs indicate the type of fault:
9 lamp test, reset and battery test bb overload (long-time protection Ir)
10 indication of tripping cause bb short-circuit (short-time Isd or instantaneous li protection)
11 digital display bb earth fault or earth leakage (Ig or In)
12 three-phase bargraph and ammeter
13 navigation buttons bb internal fault (Ap).
Battery power
The fault indication LEDs remain on until the test/reset button is pressed. Under
normal operating conditions, the battery supplying the LEDs has a service life of
approximately 10 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
A-10
Protection Micrologic 2.0 A
Long time ANSI Code 49 t
DB128031.eps
Current setting (A) 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Ir
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 tr
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping Isd
(1) 0 to -40 % - (2) 0 to -60 % 0 I
Instantaneous ANSI Code 50
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
DB128032.eps
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug I2t on
tr
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 I2t off
Isd
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 tsd
Thermal memory 20 minutes before and after tripping Ii
(1) 0 to -40 % - (2) 0 to -60 %
0 I
Short time ANSI Code 51
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous ANSI Code 50
Pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ANSI Code 51N Micrologic 6.0 A
DB128036.eps
Pick-up (A) Ig = In x A B C D E F G H J
Accuracy: 10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Residual earth leakage (Vigi) ANSI Code 51G Micrologic 7.0 A
DB128037.eps
A-11
Functions and characteristics Micrologic control units
Micrologic E energy
Micrologic E control units protect power circuits. They "Energy meter" measurements
also offer measurements, display, communication and In addition to the ammeter measurements of Micrologic A
current maximeters. Version 6 provides earth-fault Micrologic E control units measure and display:
protection. bb current demand
bb voltages: phase to phase, phase to neutral, average (1) and unbalanced (1)
bb instantaneous power: P, Q, S
DB128038.eps
bb power factor: PF
bb power demand: P demand
bb energy: Ep, Eq (1), Es (1).
Accuracy of active energy Ep is 2 % (including the sensors). The range of
measurement is the same as current with Micrologic A, depending of an external
power supply module (24 V DC).
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all "ammeter" and "energy" measurements
bb enable connection to FDM121
bb tripping causes
bb maximeter / minimeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
14 Thermal memory: thermal image before and after tripping.
15 Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug. Overload protection can be cancelled using a specific LT
rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to provide
total discrimination for short-time and earth-fault protection, without a delay before
tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 long-time threshold and tripping delay Programmable contacts
2 overload alarm (LED) at 1.125 Ir The programmable contacts may be used to signal events
3 short-time pick-up and tripping delay (Ir, Isd, Alarm Ir, Alarm Ig, Ig). They can be programmed using the keypad on the
4 instantaneous pick-up Micrologic E control unit or remotely using the COM option (BCM ULP) and RSU
5 earth-leakage or earth-fault pick-up and tripping delay software.
6 earth-leakage or earth-fault test button
7 long-time rating plug screw Fault indications
8 test connector LEDs indicate the type of fault:
9 lamp test, reset and battery test
10 indication of tripping cause
bb overload (long-time protection Ir)
11 digital display bb short-circuit (short-time Isd or instantaneous li protection)
12 three-phase bargraph and ammeter bb earth fault (Ig)
13 navigation button "quick View" (only with Micrologic E) bb internal fault (Ap).
14 navigation button to view menu contents Trip history
15 navigation button to change menu
The trip history displays the list of the last 10 trips. For each trip, the following
indications are recorded and displayed:
bb the tripping cause: Ir, Isd, li, Ig or Auto-protection (Ap) trips
bb the date and time of the trip (requires communication option).
Battery power
The fault indication LEDs remain on until the test/reset button is pressed. Under
normal operating conditions, the battery supplying the LEDs has a service life of
approximately 10 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
(1) Display on FDM121 only.
front to check circuit-breaker operation. For Micrologic 6.0 E control units, the
Note: Micrologic E control units come with a transparent operation of earth-fault or earth-leakage protection can be checked by pressing the
lead-seal cover as standard. test button located above the test connector.
A-12
Protection Micrologic 2.0 E
Long time ANSI Code 49 t
DB128031.eps
Current setting (A) 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Ir
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 tr
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping Isd
(1) 0 to -40 % - (2) 0 to -60 % 0 I
Instantaneous ANSI Code 50
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
DB128032.eps
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug I2t on
tr
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 I2t off
Isd
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 tsd
Thermal memory 20 minutes before and after tripping Ii
(1) 0 to -40 % - (2) 0 to -60 %
0 I
Short time ANSI Code 51
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous ANSI Code 50
Pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ANSI Code 51N Micrologic 6.0 E
DB128036.eps
Pick-up (A) Ig = In x A B C D E F G H J
Accuracy: 10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Energy Micrologic 2.0 / 5.0 / 6.0 E
Type of measurements Range Accuracy
Instantaneous currents I1, I2, I3, IN 0.2 x In to 1.2 x In 1.5 %
Ig (6.0 E) 0.05 x In to In 10 %
Current maximeters of I1, I2, I3, IN 0.2 x In to 1.2 x In 1.5 %
Demand currents of I1, I2, I3, Ig 0.2 x In to 1.2 x In 1.5 %
Voltages V12, V23, V31, V1N, V2N, V3N 100 to 690 V 0.5 %
Active power P 30 to 2000 kW 2 %
Power factor PF 0 to 1 2 %
Demand power P demand 30 to 2000 kW 2 %
Active energy Ep -1010 GWh to 1010 GWh 2 %
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-13
Functions and characteristics Micrologic control units
Micrologic P "power"
A-14
Protection Micrologic 5.0 / 6.0 / 7.0 P +
Long time (rms) ANSI Code 49 Micrologic 5.0 / 6.0 / 7.0 P
DB128043.eps
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
IDMTL (EIT) Accuracy: 0 to -20 % 6 x Ir 0.7 (1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
IDMTL setting Curve slope SIT VIT EIT HVFuse DT
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Short time (rms) ANSI Code 51
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
Accuracy: 10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous ANSI Code 50
Pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
DB128044.eps
Accuracy: 10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ANSI Code 50N Micrologic 6.0 P
Pick-up (A) Ig = In x A B C D E F G H J
Accuracy: 10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
DB128045.eps
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Residual earth leakage (Vigi) ANSI Code 51G Micrologic 7.0 P
Sensitivity (A) IDn 0.5 1 2 3 5 7 10 20 30
Accuracy: 0 to -20 %
Time delay Dt (ms) Settings 60 140 230 350 800
Dt (max resettable time) 60 140 230 350 800
Dt (max break time) 140 200 320 500 1000
Alarms and other protection Micrologic 5.0 / 6.0 / 7.0 P
Current ANSI Code 46 Threshold Delay DB128046.eps
A-15
Functions and characteristics Micrologic control units
Micrologic P "power"
Measurements..........................................................
DB101133.eps
DB101134.eps The Micrologic P control unit calculates in real time all the electrical values (V, A, W,
VAR, VA, Wh, VARh, VAh, Hz), power factors and cosj factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.
Instantaneous values
The value displayed on the screen is refreshed every second.
Minimum and maximum values of measurements are stored in memory (minimeters
Default display. Display of a maximum and maximeters).
current.
Currents
I rms A 1 2 3 N
A E-fault E-leakage
DB101133.eps
DB101133.eps
I max rms A 1 2 3 N
A E-fault E-leakage
Voltages
U rms V 12 23 31
V rms V 1N 2N 3N
U average rms V (U12 + U23 + U31) / 3
U unbalance %
Power, energy
P active, Q reactive, S apparent W, Var, VA Totals
E active, E reactive, E apparent Wh, VARh, VAh Totals consumed - supplied
Totals consumed
Totals supplied
Display of a voltage. Display of a power. Power factor PF Total
Frequencies
F Hz
DB101137.eps
DB101138.eps
Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum demand
values are systematically stored and time stamped (maximeter).
Currents
I demand A 1 2 3 N
A E-fault E-leakage
I max demand A 1 2 3 N
Display of a frequency. Display of a demand power. A E-fault E-leakage
Power
P, Q, S demand W, Var, VA Totals
P, Q, S max demand W, Var, VA Totals
Only the current and power maximeters may be displayed on the screen.
Time-stamping
Time-stamping is activated as soon as time is set manually or by a supervisor.
No external power supply module is required (max. drift of 1 hour per year).
Reset
An individual reset, via the keypad or remotely, acts on alarms, minimum and
maximum data, peak values, the counters and the indicators.
Additional measurements accessible with the COM option (BCM ULP)
Some measured or calculated values are only accessible with the COM
communication option:
bb I peak / 2, (I1 + I2 + I3)/3, I unbalance
bb load level in % Ir
bb total power factor.
The maximeters and minimeters are available only via the COM option (BCM ULP)
for use with a supervisor.
Additional info
Accuracy of measurements (including sensors):
bb voltage (V) 0.5 %
bb current (A) 1.5 %
bb frequency (Hz) 0.1 %
bb power (W) and energy (Wh) 2 %.
PME software.
A-16
Histories and maintenance indicators....................
DB117041.eps
DB101140.eps
The last ten trips and alarms are recorded in two separate history files that may be
displayed on the screen:
bb tripping history:
vv type of fault
vv date and time
vv values measured at the time of tripping (interrupted current, etc.)
bb alarm history:
vv type of alarm
vv date and time
vv values measured at the time of the alarm.
All the other events are recorded in a third history file which is only accessible
Display of a tripping history. Display after tripping. through the communication network.
bb Event log history (only accessible through the communication network)
vv modifications to settings and parameters
vv counter resets
vv system faults
vv fallback position
vv thermal self-protection
vv loss of time
vv overrun of wear indicators
vv test-kit connections
vv etc.
Note: all the events are time stampled: time-stamping is activated as soon as time is set
manually or by a supervisor. No external power supply module is required (max. drift of 1 hour
per year).
Quick view
20.12.2011 12:00:05
Metering The FDM121 switchboard display unit can be connected to a COM option (BCM
ULP) using a breaker ULP cord to display all measurements on a screen (1). The
S1-1 - Lighting/Level1
Control
Quick view
Open Auto
Alarms Measures
Alarm history
result is a veritable 96 x 96 mm Power Meter.
Services
ESC OK
Control
I
Using an IFE Ethernet interface for LV breakers.
DB414400.eps
I1 310 A I2 315 A
20.12.2011 12:00:05
%
I3 302 A
%
IN 23 A
S1-1 - Lighting/Level1
I1 431 A
screen shows demand, power quality and maximeter/minimeter values along with
histories and maintenance indicators.
Alarm history
% % I2 385 A
ESC
Control
I3 426 A
Maintenance IN 2 A
ESC 1/10
Measurements.......................................................
FDM121 display: current. FDM128 display: current.
Instantaneous rms measurements
The Micrologic continuously display the RMS value of the highest current of the three
phases and neutral (Imax). The navigation buttons can be used to scroll through the
DB112132.eps
V 4/7
DB414401.eps
U3 Alarm history
V12 406 V
V23 415 V
ESC
Control
Maintenance
V31 409 V the measurements provided by Micrologic A.
ESC 1/10 The Micrologic P offer frequency, cos.j in addition to the measurements provided by
Micrologic E.
FDM121 display: voltage. FDM128 display: voltage. Maximeters / minimeters
Every instantaneous measurement provided by Micrologic A or E can be associated
with a maximeter/minimeter. The maximeters for the highest current of the 3 phases
DB112133.eps
PQS
and neutral, the demand current and power can be reset via the FDM display unit or
DB414402.eps
P 64 kW 20.12.2011 12:00:05
Q 38 kVar
the communication system.
S1-1 - Lighting/Level1
S 51 kVA
Energy metering
Quick view I U-V PQS E
PQS
Measures
Alarm history
Ptot 127 kW
ESC
Control
Qtot
Stot
13 kVAr
129 kVA The Micrologic E/P also measures the energy consumed since the last reset of the
meter. The active energy meter can be reset via Micrologic keypad or the FDM
Maintenance
ESC 1/12
FDM121 display: power. FDM128 display: power. Demand and maximum demand values
Micrologic E/P also calculates demand current and power values. These calculations
can be made using a block or sliding interval that can be set from 5 to 60 minutes in
DB112134.eps
E
steps of 1 minute. The window can be synchronised with a signal sent via the
DB414403.eps
Es 13035 kVAh
S1-1 - Lighting/Level1
I U-V PQS E
be recovered on a PC via Modbus communication.
Quick view
Measures
E cumul
ESC 1/3
operations used to adjust consumption to the subscribed power.
A-18
PB104842_24.eps
PB106351A13.eps
PB111801-32_r_1.eps
PB103360_r.eps
Micrologic A/E/P integrated Power Meter functions Type Display
A/E P Micrologic FDM display
LCD
Display of protection settings
Pick-ups (A) and All settings can be displayed Ir, tr, Isd, tsd, Ii, Ig, tg A/E P b -
delays
Measurements
Instantaneous rms measurements
Currents (A) Phases and neutral I1, I2, I3, IN A/E P b b
Average of phases Iavg = (I1 + I2 + I3) / 3 A/E P - b
Highest current of the 3 phases and Imax of I1, I2, I3, IN A/E P b b
neutral
Ground fault (Micrologic 6) % Ig (pick-up setting) A/E P b b
Current unbalance between phases % Iavg - /E P - b
Voltages (V) Phase-to-phase V12, V23, V31 - /E P b b
Phase-to-neutral V1N, V2N, V3N - /E P b b
Average of phase-to-phase voltages Vavg = (V12 + V23 + V31) / 3 - /E P - b
Average of phase-to-neutral Vavg = (V1N + V2N + V3N) / 3 - /E P - b
voltages
Ph-Ph and Ph-N voltage unbalance % Vavg and % Vavg - /E P - b
Phase sequence 1-2-3, 1-3-2 -/- P b b (3)
Frequency (Hz) Power system f -/- P b b
Power Active (kW) P, total - /E P b b
P, per phase - /E P b (2) b
Reactive (kVAR) Q, total - /E P b b
Q, per phase -/- P b b
Apparent (kVA) S, total - /E P b b
S, per phase -/- P b b
Power Factor PF, total - /E P b b
PF, per phase -/- P b b
Cos.j Cos.j, total -/- P b b
Cos.j, per phase -/- P b b
Maximeters / minimeters
Associated with instantaneous rms Reset via FDM display unit and A/E P b b
measurements Micrologic keypad
Energy metering
Energy Active (kW), reactive (kVARh), Total since last reset - /E P b b
apparent (kVAh)
Demand and maximum demand values
Demand current (A) Phases and neutral Present value on the selected - /E P b b
window
Maximum demand since last - /E P b (2) b
reset
Demand power Active (kWh), reactive (kVAR), Present value on the selected - /E P b b
apparent (kVA) window
Maximum demand since last - /E P b (2) b
reset
Calculation window Sliding, fixed or com-synchronised Adjustable from 5 to 60 minutes - /E P - -
in 1 minute steps (1)
(1) Available via the communication system only.
(2) Available for Micrologic P only.
(3) FDM121 only.
A-19
Functions and characteristics Operating-assistance functions
Micrologic A/E/P control unit
with COM option (BCM ULP)
Histories.................................................................
bb Trip indications in clear text in a number of user-selectable languages.
bb Time-stamping: date and time of trip.
Maintenance indicators.........................................
Micrologic control unit have indicators for, among others, the number of operating
cycles, contact wear P, load profile and operating times (operating hours counter) of
the Masterpact circuit breaker.
It is possible to assign an alarm to the operating cycle counter to plan maintenance.
The various indicators can be used together with the trip histories to analyse the
level of stresses the device has been subjected to.
A-20
Switchboard-display functions
Micrologic A/E/P control unit
with COM option (BCM ULP)
PB103807-32.eps
DB112138.eps
Produit Id
Micrologic 5.3A
Metering
I Screens
Serial number: P07451
U-V
Main menu
Part number: LU432091
PQS
When powered up, the FDM121 screen automatically displays the ON/OFF status of
Firmware: 1.02
E
the device.
F - PF - cos
ESC ESC OK
Metering Services.
Product identification. Metering: sub-menu.
Control
DB112140.eps
DB125912.eps
EpOut 12345678 kWh 50...79% 15 H When not in use, the screen is not backlit. Backlighting can be activated by pressing
80..89% 360 H
one of the buttons. It goes off after 3 minutes.
90..100% 3H
Fast access to essential information
ESC ESC bb Quick view provides access to five screens that display a summary of essential
operating information (I, U, f, P, E, THD, circuit breaker On / Off).
Access to detailed information
Metering: meter. Services.
bb "Metering" can be used to display the measurement data (I, U-V, f, P, Q, S, E,
THD, PF) with the corresponding min/max values.
bb Alarms displays active alarms and the alarm history.
bb Services provides access to the operation counters, energy and maximeter reset
bb function, maintenance indicators, identification of modules connected to the
internal bus and FDM121 internal settings (language, contrast, etc.).
D0 = A / Rx-, A / Tx-
D1 = B / Rx+, B / Tx+
24VDC
ETH1 ETH2
IFM D IFE D
OR
E E
F F
C C
Red Black White Blue Red Black White Blue
E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
24 V
0V
A / Tx- D0
24 V
A / Tx- D0
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
0V
A-22
Switchboard-display functions
Micrologic A/E/P control unit
with COM Ethernet gateway
PB111802-32_r.eps
Connection
The FDM128 is equipped with:
bb a 24 V DC terminal block:
vv power supply range of 24 V DC (limit 20.4 - 28.8 V DC). The FDM128 display unit
has a 2-point screw connector on the rear panel of the module for this purpose.
bb One RJ45 Ethernet jacks.
The Micrologic connects to the internal communication terminal block on the
Masterpact via the breaker ULP cord and Ethernet connection through IFE.
A-23
Functions and characteristics Switchboard-display functions
Micrologic A/E/P control unit
with COM Ethernet gateway
Navigation
DB414405.eps
DB414407.eps
Touch screen is used for intuitive and fast navigation.
20.12.2011 12:00:05 20.12.2011 12:00:05
S1-1 - Lighting/Level1
Operation xxx
Measures
Ep 11 318 kWh Italian, Portuguese, Spanish, etc.).
Alarm history
Trip SDE xxx
Alarm history
Eq 257 kVArh
Control Control
Es 13 815 kVAh
Screens
Close command xxx
Maintenance Maintenance
Main menu
Product identification. Metering: meter.
20.12.2011 12:00:05
S1-1 - Lighting/Level1
Alarm history
0 to 49%
Control
50 to 79%
80 to 89% Control
Maintenance 90 to 100%
ESC 2/3
A-24
Protection of distribution
systems
Micrologic control units
for Compact NS630b to 3200
External sensors
DB128050.eps
The external power-supply module makes it possible to use the display even if the
circuit breaker is open or not supplied (for the exact conditions of use, see the
electrical diagrams part of this catalogue).
This module powers both the control unit (100 mA) and the M2C and M6C
programmable contacts (100 mA).
With the Micrologic A/E control unit, this module makes it possible to display currents
of less than 20 % of In.
With the Micrologic P and H, it can be used to display fault currents after tripping.
External 24 V DC power power supply module.
If the COM option is used, a second dedicated power supply shall be used.
We recommend to use the AD power supply due to its low stray primary secondary
capacitance. Good operation of the Micrologic trip unit in noisy environment is not
guaranteed with other power supplies.
Characteristics
bb Power supply:
vv 110/130, 200/240, 380/415 V AC, 50/60 Hz (+10 % -15 %)
vv 24/30, 48/60, 100/125 V DC (+20 % -20 %).
bb Output voltage: 24 V DC 5 %, 1 A.
bb Ripple < 1 %.
bb Dielectric withstand : 3.5 kV rms between input/output, for 1 minute.
bb Overvoltage category: as per IEC 60947-1 cat. 4.
A-25
Functions and characteristics Protection of distribution
systems
Micrologic control units
for Compact NS630b to 3200
Battery module
PB100771-24.eps
The battery module maintains display operation and communication with the
supervisor if the power supply to the Micrologic control unit is interrupted.
It is installed in series between the Micrologic control unit and the AD module.
Characteristics
bb Battery run-time: 4 hours (approximately).
bb Mounted on vertical backplate or symmetrical rail.
Battery module.
M6C programmable contacts
These contacts are optional equipment for the Micrologic P control units.
PB100781-32_SE.eps
They are described with the indication contacts for the circuit breakers.
Micrologic Type P
Characteristics M6C
Minimum load 100 mA/24 V
Breaking capacity (A) V AC 240 5
p.f.: 0.7 380 3
V DC 24 1.8
M6C. 48 1.5
125 0.4
250 0.15
M6C: external 24 V DC power supply required (consumption 100 mA).
Spare parts
PB100775-32.eps
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
bb it is impossible to modify settings using the keypad unless the settings lockout pin
on the cover is removed
bb the test connector remains accessible
bb the test button for the earth-fault and earth-leakage protection function remains
accessible.
Characteristics
bb Transparent cover for basic Micrologic and Micrologic A, E control units.
bb Non-transparent cover for Micrologic P control units.
Lead-seal cover.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes. Battery service
life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
A-26
Test equipment
PB100837-68.eps
A-27
Functions and characteristics EnerlinX communication system
Products overview
Enerlin'X communication system provides access Ethernet has become the universal link between switchboards, computers and
to status, electrical values and devices control using communication devices inside the building. The large amount of information which
Ethernet and Modbus SL communication protocols. can be transferred makes the connection of Enerlin'X digital system to hosted web
services of Schneider Electric a reality. More advantages are offered to integrators
thanks to configuration web pages available remotely or on the local Ethernet network.
G G
G G
H D
F
B
Ethernet
Modbus SL ULP is a fast communication link dedicated
ULP to circuit breaker monitoring and control.
A-28
Enerlin'X communication devices and displays
Name Function Port Bin. Analog. Bin. Cial. Ref.
Input Input Output
(to device) (to server)
D
gateway
E Smartlink
Ethernet
with Input/Output
functions &
Master
Gateway
(1) Gateway: transfers data from a network to another (ie.: Modbus to Ethernet).
(2) Interface: transfers data from an equipment to a network.(ie.: ULP to Modbus).
A-29
Functions and characteristics Communication
Communication wiring system
G
A
E
F
C
Q
H
I P
L
K P L N D
A BCM ULP: Breaker Communication Module with ULP port L IFE: Ethernet interface LV434010 or LV434011
B Micrologic control unit M External 24 V DC power supply module
C Breaker ULP cord 0.35 m LV434195 N IFM: Modbus-SL interface TRV00210
1.3 m LV434196
3m LV434197
O Com'X 200
P ULP cable 0.3 m TRV00803
D Modbus cable 0.6 m TRV00806
1m TRV00810
E Ethernet cable 2m TRV00820
3m TRV00830
F FDM121: Front Display Module TRV00121
5m TRV00850
G FDM128: Front Display Module LV434128 0.35 m LV434200
Q NSX cord
H Smartlink A9XMSB11 1.3 m LV434201
3m LV434202
I Acti9 Ethernet
Modbus
J ULP line terminators TRV00880
ULP
K I/O (Input/Output) application module LV434063 24 V DC
A-30
Overview of functions
The manager addresses are automatically derived from the circuit breaker address
@xx entered via the Micrologic control unit (the default address is 47).
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.), the baud rate (19200 is recommended),
the volume of data exchanged and the desired response time. The RS 485 physical
layer offers up to 32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device). A drawout device uses two connection points (communication modules on
the device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).
A-31
Functions and characteristics Communication
COM option in Compact
All the Compact devices can be fitted with the For fixed devices, the COM option is made up of:
communication function thanks to the COM option. bb a BCM ULP module, installed behind the Micrologic control unit and supplied with
Compact uses the Ethernet or Modbus its set of sensors (OF, SDE, PF and CH micro switches) its kit for connection to XF
communications protocol for full compatibility with the and MX1 communicating voltage releases and its COM terminal block (inputs E1 to
supervision management systems. E6)
Eco COM is limited to the transmission of metering bb IFM, this module required for connection to the network, contains the Modbus
data and status. It is not used to communicate controls. address (1 to 99) declared by the user via the two dials in front. It automatically
adapts (baud rate, parity) to the Modbus network in which it is installed.
Or
bb IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a Compact NS circuit breaker to be connected to an Ethernet
network. Each circuit breaker has its own IFE and a corresponding IP address.
E6).
bb IFM, this module required for connection to the network, contains the Modbus
address (1 to 99) declared by the user via the two dials in front. It automatically
adapts (baud rate, parity) to the Modbus network in which it is installed.
Or
bb IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a Compact NS circuit breaker to be connected to an Ethernet
network. Each circuit breaker has its own IFE and a corresponding IP address.
bb I/O (Input/Output) application module for LV breaker, the I/O application module is
BCM ULP. delivered with withdrawable devices ordered with the COM option, for cradle
management. It must be installed on a DIN rail near the device. It must be connected
to the ULP system and to the position contacts (CD, CT, CE) that transmit the
position of the device in the cradle.
BCM ULP module
DB416829.eps
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
XF and MX1 communicating voltage releases
The XF and MX1 communicating voltage releases are equipped for connection to
the device communication module.
The remote-tripping function (MX2 or MN) are independent of the communication
option. They are not equipped for connection to the device communication module.
A-32
Communication architecture
Electrical operated
Fixed device Drawout devices
Ethernet Modbus Ethernet Modbus Ethernet Modbus
DB417121.eps
DB417123.eps
DB417122.eps
C
24VD C
C 24VD
24VD
ETH2
ETH2
ETH
2 ETH2
ETH1 ETH
2
1 ETH
2 ETH1
J
ETH ETH1 1
J
1 ETH
ETH
I J I I
set)
(factory set)
Y.ZZ set) (factory
IFE_
XX.Y (factory XX.Y
Y.ZZ
CT Y.ZZ IFE_
00/A XX.Y CT
10-1 IFE_ 00/A
1 LK/ 00/A
CT 10-1
IFE ETH
00/A
CT 10-1 1 LK/
10-1 1 LK/ IFE ETH
00/A
CT
2 LK/ us IFE ETH
00/A
CT 10-1
ETH 2 LK/
ule Stat 2 LK/
10-1 ETH us
Mod ETH us ule Stat
us ule Stat Mod
k Stat Mod us
Networ us k Stat
bus-SL k Stat Networ
Mod Networ bus-SL
bus-SL Mod
Mod
11
LV4340 11
11 LV4340
LV4340
or or
or
I6
I6 C
ULP system
C I5
I5 I4
I4 C
C I3
I3 I2
I2 C
C I1
I1
I6
I6 C
C I5
I5 I4
I4 C
C I3
I3 I2
I2 C
C I1
I1
+ C
+ C 24VD
24VD
A1
A1
O1
O1 I1
I1 O2
O2 I2
I2 O3
O3 I3
I3 APP
APP I4
I4
I5
I5
I6
I6
dule
dule IO Mo
IO Mo
H A1
A1
H
T2
T2 O3 T1
O3 T1 34
34 O2 33
O2 33 24
24 O1 23
23
F
O1 14
14 13
13
G G
F F
B E
E
A C C
B
B A D
A
Manually operated fixed device Manually operated withdrawable device Electrically operated withdrawable device
A-33
Functions and characteristics IFE Ethernet interface
Introduction
The IFE interface and IFE interface + gateway enable LV circuit breakers
as Masterpact NT/NW, Compact NSX or Powerpact to be connected to an Ethernet
network.
IFE interface: ref. LV434010
Provides an Ethernet access to a single LV circuit breaker.
Function
Interface - one circuit breaker is connected to the IFE interface via its ULP port.
IFE interface + gateway: ref. LV434011
Provides an Ethernet access to one or several LV circuit breakers.
Functions
bb Interface - one circuit breaker is connected to the IFE interface via its ULP port.
bb Gateway: several circuit breakers on a Modbus network are connected via
the IFE interface + gateway master Modbus port.
IFE interface, ref.: LV434010
IFE interface, IFE interface + gateway features
bb Dual 10/100 Mbps Ethernet port for simple daisy chain connection.
bb Device profile web service for discovery of the IFE interface, IFE interface +
DB416830.eps
A-34
General characteristics
DB417466.eps
Environmental characteristics
24VDC
Conforming to standards UL 508, UL 60950, IEC 60950, 60947-6-2
Certification cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 C (-4 to +158 F)
Relative humidity 585 %
ETH1 ETH2 Level of pollution Level 3
Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal vibrations -5 Hz < f < 8.4 Hz
A B Electrical characteristics
Resistance to electromagnetic discharge Conforming to IEC/EN 61000-4-3
I J K Immunity to radiated fields 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
Consumption 120 mA at 24 V input
ETH1 ETH2
Physical characteristics
Dimensions 72 x 105 x 71 mm (2.83 x 4.13 x 2.79 in.)
IFE Mounting DIN rail
IFE-XX.YY.ZZ (factory set)
ETH1 LK/10-100/ACT
Weight 182.5 g (0.41 lb)
ETH2 LK/10-100/ACT
C Degree of protection of the installed IO bb On the front panel (wall mounted enclosure): IP4x
Module Status D bb Connectors: IP2x
Modbus-SL
Network Status
E bb Other parts: IP3x
T LV434011
Connections Screw type terminal blocks
F Technical characteristics - 24 V DC power supply
Power supply type Regulated switch type
R
Rated power 72 W
Input voltage 100120 V AC for single phase
200500 V AC phase-to-phase
PFC filter With IEC 61000-3-2
H G Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
or a class 2 power supply with a 24 V DC, 3 A maximum.
A-35
Functions IFM Modbus communication
and characteristics
interface
Function
PB103798-50.eps
Once connected, the circuit breaker is considered as a slave by the Modbus master.
Its electrical values, alarm status, open/close signals car be monitored or controlled
by a Programmable Logic Controller or any other system.
Characteristics
ULP port
IFM Modbus communication interface. 2 RJ45 sockets, internal parallel wiring.
Ref.: TRV00210. bb Connection of a single circuit breaker (eventually via its I/O application module).
bb A ULP line terminator or an FDM121 display unit must be connected to the second
RJ45 ULP socket.
The RJ45 sockets deliver a 24 VDC supply fed from the Modbus socket.
Built-in test function, for checking the correct connection to the circuit breaker
and FDM121 display unit.
Modbus slave port
bb Top socket for screw-clamp connector, providing terminals for:
vv 24 VDC input supply (0V, +24V)
vv Modbus line (D1, D2, Gnd).
bb Lateral socket, for Din-rail stackable connector.
Both top and lateral sockets are internally parallel wired.
bb Multiple IFM can be stacked, thus sharing a common power supply and Modbus
line without individual wiring.
bb On the front face:
vv Modbus address setting (1 to 99): 2 coded rotary switches
vv Modbus locking pad: enables or disables the circuit breaker remote control
and modification of IFM parameters.
bb Self adjusting communication format (Baud rate, parity).
DB417545.eps
6
5
B
4 7
3 8
2 9
1 0
6
5
4 7
3 8
2 9
1 0
C
D
Test E
I H G
A M
odbus screw clamp E ULP activity LED.
connector.
F Test button.
B M
odbus address
G Mechanical lock.
switches.
H ULP RJ45 connectors.
C Modbus traffic LED.
I Stacking accessory
D Modbus locking pad.
connection.
A-36
Technical characteristics
IFM Modbus communication interface
Dimensions 18 x 72 x 96 mm
Maximum number of stacked IFM 12
Degree of protection Part projecting beyond IP4x
of the installed the escutcheon
module Other module parts IP3x
Connectors IP2x
Operating temperature -25...+70 C
Power supply voltage 24 V DC -20 %/+10 % (19.2...26.4 V DC)
Consumption Typical 21 mA/24 V DC at 20 C
Maximum 30 mA/19.2 V DC at 60 C
Certification
CE IEC/EN 60947-1
UL UL 508 - Industrial Control Equipment
CSA No. 142-M1987 - Process Control
Equipment
bb CAN/CSA C22.2 No. 0-M91 -
General requirements - Canadian Electrical
Code Part
bb CAN/CSA C22.2 No. 14-05 -
Industrial Control Equipment
DB417491.eps
A-37
Functions and characteristics Connection of the IFE to a fixed
or drawout Compact NS
Connect the IFE to a fixed manual operated Connect the IFE to a drawout Compact NS or circuit breaker using the
Compact NS or circuit breaker using the breaker breaker ULP cord
ULP cord
Ethernet Ethernet
DB417259.eps
DB417258.eps
24 Vdc 24 Vdc
24VDC 24VDC
ETH2 ETH2 I6
C
I5
ETH2 ETH2
ETH1 ETH1
I4
C
I3
ETH1 ETH1 C
I2
I1
I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD
A1
O1
O2
O3
K
dule
IO Mo
A T1
A1
T2
O3
34
O2 33
24
O1 23
14
13
A
B
B
J
I
H
D
F
E
G
A IFE Ethernet interface for LV circuit breaker A IFE Ethernet interface for LV circuit breaker
B Breaker ULP cord B ULP cable
C Fixed terminal block C Breaker ULP cord
D BCM ULP communication module D Circuit breaker disconnected position contact (CD)
E Fixed electrically operated circuit breaker E Circuit breaker cradle
F BCM ULP communication module
G Drawout circuit breaker
H Drawout terminal block
I Circuit breaker connected position contact (CE)
J Circuit breaker test position contact (CT)
K I/O (Input/Output) application module for LV circuit breaker
A-38
Connection of the IFM to a fixed
or drawout Compact NS
Functions
A This module, required for connection to the network, contains the Modbus address
(1 to 99) declared by the user via the two dials in front. It automatically adapts (baud
rate, parity) to the Modbus network in which it is installed.
It is equipped with a lock-out switch to enable or disable operations involving writing
to Micrologic, i.e. reset, counter reset, setting modifications, device opening and
B closing commands, etc.
There is a built-in test function to check the connections of the Modbus interface
C
module with the Micrologic and FDM121 display unit.
D
E Mounting
F The module is mounted on a DIN rail. A number of modules may be clipped one next
G to the other. For this, a stacking accessory is available for fast clip-connection of
both the Modbus link and the 24 V DC supply.
A Five-point Modbus and 24 V DC connector The Modbus interface module supplies 24 V DC to the corresponding Micrologic,
B Two Modbus address dials (1 to 99) FDM121 display and BSCM module. Module consumption is 60 mA / 24 V DC.
C Modbus traffic LED
DB112084.eps
Connect the IFM to a fixed manual operated Connect the IFM to a drawout Compact NS or circuit breaker using the
Compact NS or circuit breaker using the breaker breaker ULP cord
ULP cord Modbus
DB417257.eps
Modbus
DB417256.eps
I6
C
I5
I4
C
I3
I2
C
I1
I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD
A1
O1
O2
O3
K
dul e
IO Mo
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
A
A
B
B
C
J
I
H
D
E
D
F
G
E
A IFM Ethernet interface for LV circuit F BCM ULP communication module
breaker G Drawout circuit breaker
A IFM Ethernet interface for LV circuit breaker B ULP cable H Drawout terminal block
B Breaker ULP cord C Breaker ULP cord I Circuit breaker connected position
C Fixed terminal block D Circuit breaker disconnected position contact (CE)
D BCM ULP communication module contact (CD) J Circuit breaker test positioncontact(CT)
E Fixed electrically operated circuit breaker E Circuit breaker cradle K I/O (Input/Output) application module
for LV circuit breaker
A-39
Functions and characteristics I/O application module
Description
DB416829.eps
The I/O (Input/Output) application module for LV breaker is part of an ULP system
with built-in functionalities and applications to enhance the application needs. The
ULP system architecture can be built without any restrictions using the wide range of
circuit breakers.
The I/O application module is compliant with the ULP system specifications.
Two I/O application module can be connected in the same ULP network.
The ranges of LV circuit breakers enhanced by the I/O application module are:
bb Masterpact NW
bb Masterpact NT
bb Compact NS1600b-3200
bb Compact NS630b-1600
bb Compact NSX100-630 A.
Pre-defined applications
Pre-defined application adds new functions to the IMU in a simple way:
bb selection by the application rotary switch on the I/O application module, defining
the application with pre-defined input/output assignment and wiring diagram.
bb no additional setting with the customer engineering tool required.
The resources not assigned to the pre-defined application are free for additional
user-defined applications:
bb cradle management
bb breaker operation
bb light and load control
bb custom.
User-defined applications
User-defined applications are processed by the I/O application module in addition to
the pre-defined application selected.
The user-defined applications are available depending on:
bb the pre-defined application selected
bb the I/O application module resources (inputs and outputs) not used by the
application.
The resources required by user-defined applications are assigned using the
customer engineering tool:
bb protection
bb control
bb energy management
bb monitoring.
Mounting
The I/O application module is a DIN rail mounting device.
4 6
The application rotary switch enables the selection of the pre-defined application.
3 7
It has 9 positions and each position is assigned to a pre-defined application.
2 8 The factory set position of the switch is pre-defined application 1.
1 9
DB416828.eps
the setting of the I/O application module by the customer engineering tool.
A-40
General characteristics
DB417467.eps
Environmental characteristics
Conforming to standards UL 508, UL 60950, IED 60950, 60947-6-2
Certification cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 C (-4 to +158 F)
Relative humidity 585 %
Level of pollution Level 3
I1 C I2 I3 C I4 I5 C I6 Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal -5 Hz < f < 8.4 Hz
vibrations
Electrical characteristics
A B Resistance to electromagnetic Conforming to IEC/EN 61000-4-3
discharge
Immunity to radiated fields 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
Consumption 165 mA
24VDC I1 C I2 I3 C I4 I5 C I6
Physical characteristics
Dimensions 71.7 x 116 x 70.6 mm (2.83 x 4.56 x 2.78 in.)
C Mounting DIN rail
4 5 6 Weight 229.5 g (0.51 lb)
M 3
2
7
8
I1
AI D Degree of protection of the bb On the front panel (wall mounted enclosure): IP4x
1 9 I2
APP
I3 O1
installed I/O application module bb IO parts: IP3x
L I4 O2 E bb Connectors: IP2x
I5
O3
Connections Screw type terminal blocks
I6 F
K T Technical characteristics - 24 V DC power supply
G
Power supply type Regulated switch type
J IO LV434063
Rated power 72 W
Input voltage 100120 V AC for single phase
200500 V AC phase-to-phase
PFC filter With IEC 61000-3-2
O1 O2 O3 A1
13 14 23 24 33 34 T1 T2
Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
or a class 2 power supply with a 24 V DC, 3 A maximum.
I H
Digital inputs
Digital input type Self powered digital input with current limitations as per
IEC 61131-2 type 2 standards (7 mA)
Input limit values at state 1 19.825.2 V DC, 6.18.8 mA
(close)
13 14 23 24 33 34 T1 T2
Input limit values at state 0 019.8 V DC, 0 mA
(open)
Maximum cable length 10 m (33 ft)
Note: for a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to use a
shielded twisted cable. The shield cable is connected to the I/O functional ground of the I/O
1
2
application module.
Digital outputs
Digital output type Bistable relay
Rated load 5 A at 250 V AC
A-41
Functions and characteristics Electrical Asset Manager
Configuration Engineering tool
Introduction
Capture1b.eps
Electrical Asset Manager is a software application that helps the user to manage a
project as part of designing, testing, site commissioning, and maintenance of the
project life cycle.
It enables the user to prepare the settings of the devices offline (without connecting
to the device) and configure them when connected with the devices.
Also it provides lot of other value added features for the user to manage the project
such as, safe repository in cloud, attach artifacts to each device or at the project
level, organize devices in switchboard wise, manage a hierarchical structure of the
installation etc.
References:
Electrical Asset Manager software package can be downloaded from our website
www.schneider-electric.com.
Capture3b.eps
Features
Electrical Asset Manager supersedes the Schneider Electric customer engineering
tools such as Remote setting Utility (RSU) and Remote Control Utility (RCU) with
additional features.
Electrical Asset Manager supports the connection of Schneider Electric
communicable devices to:
bb create projects by device discovery, selection of devices, and import Bill of
Material (BOM)
bb monitor the status of protection and I/O status
bb read information (alarms, measurements, parameters)
bb check protection discrimination between two devices
bb upload and download of configuration or settings in batch mode to multiple
Capture4b.eps
devices.
bb carry out commands and tests
bb generate and print device settings report and communication test report
bb manage multiple devices with electrical and communication hierarchy model
bb manage artifacts (project documents)
bb check consistency in settings between devices on a communication network
bb compare configuration settings between PC and device (online)
bb download latest firmware.
Electrical Asset Manager enables the user to avail the advanced features of the
software once the project is saved in Schneider Electric cloud.
A-42
Functions
Capture5b.eps
Offline Mode
A project can be built in offline mode through 2 different ways:
bb through BOM file import
bb through Device Selection.
Additionally, the user can open an existing project and modify the settings offline.
The user can do the discrimination curve check and firmware compatibility check for
devices in the project.
Online Mode
A project can be built in online mode through device discovery also other than the
methods possible through offline method.
Once the project is built, the following functions can be performed in addition to the
functions available in offline mode:
Capture6b.eps
to transfer the device settings ; to view the tripping curves; to attach device artifacts
and to download the latest firmware, to do the communication test for all the devices
and generate the test report.
bb Monitoring: this allows the user to monitor the real time values of different devices
through different sub tabs namely Monitoring, Logs and Control.
bb Reports: report tab allows you to generate and print a report of the project settings
from the report tab. The user details and project characteristics are automatically
filled with the details entered in the Project page.
Capture8b.eps
A-43
Functions and characteristics Motor protection
Overview of solutions
The circuit breakers presented here provide protection Motor protection up to 750 kW
against short circuits and are suitable for isolation as
Motor rating (kW) 160750
defined by standard IEC 60947-2.
Compact NS630b to 1600
For complete protection of the motor and its control
device, overload protection may be provided by either
PB104839_ME.eps
the circuit breaker or a separate Schneider Electric
thermal relay.
The control device may be of the direct on-line type
(with or without reversing) or of the star-delta type.
Combinations are governed by standard IEC 60947-4.1.
Breaking N 50
DB128055.eps
Ir (A) 1.5 2.5 12 40 50 80 100 160 200 220 320 500 800 1000 1350
A-44
Earth-leakage protection
Overview of solutions
Earth-leakage protection is obtained by: Circuit breakers equipped with a control unit offering integrated
b installing a Micrologic 7.0 A control unit earth-leakage protection and an external rectangular sensor
(Compact NS630b to 3200).
b using a Vigirex relay and separate sensors Rated current (A) 630 3200
(all Compact circuit breakers). Compact NS630b to 1000 N/L NS1600b to 3200
NS1250 and 1600 N
PB104844_ME.eps
PB104845_ME.eps
General circuit breaker characteristics page A-12
Compact NS630b to 3200 circuit breakers are presented in the Protection of
distribution systems section.
Accompanying control units page A-22
Micrologic 7.0 A electronic control units offer earth-leakage protection as standard.
051352_32_SE.eps
06133779A.eps
A-45
Functions and characteristics Control and isolation
Overview of solutions
Circuit
Switch-
breaker-
disconnector
disconnector
Standardised symbols
DB414486.eps
Final
distribution
enclosure
for
commercial
applications
LV devices
Acti 9 NG125 Easypact Compact NS Masterpact NT Micrologic Compact INS Compact INV Fupact INF
A-46
Control and isolation
Overview of solutions
PB104837.eps
isolate electrical distribution circuits. In addition to
these basic functions, other functions for safety, remote
control and convenience include:
b earth-leakage protection
b auxiliary MN/MX releases
b remote operation.
Compact switch-disconnectors may be interlocked with
another Compact switch-disconnector or circuit
breaker to constitute a source-changeover system.
A-47
Functions and characteristics Control and disconnection
Compact NS630bNA to 1600NA
switch-disconnectors
A-48
NS630bNA NS800NA NS1000NA NS1250NA NS1600NA
3, 4 3, 4 3, 4 3, 4 3, 4
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b
b
b
b
b
b
b
b
327 x 210 x 147
327 x 280 x 147
14
18
A-49
Functions and characteristics Control and disconnection
Compact NS1600bNA to 3200NA
switch-disconnectors
A-50
NS1600bNA NS2000NA NS2500NA NS3200NA
3, 4 3, 4 3, 4 3, 4
b b b b
- - - -
- - - -
b b b b
- - - -
- - - -
- - - -
b
b
b
b
350 x 420 x 160
350 x 535 x 160
23
36
A-51
Functions and characteristics Source-changeover systems
Presentation
Some installations use two supply sources to counter the temporary loss of the main
PB191613-50.eps
supply.
A source-changeover system is required to safely switch between the two sources.
The replacement source can be a generator set or another network.
System
2 or 3 mechanically interlocked circuit breakers or
2 switch-disconnectors.
Applications
Small commercial buildings and small and medium industrial activities where the
need for continuity of service is significant but not a priority.
System
2 or 3 circuit breakers linked by an electrical interlocking system. A mechanical
interlocking system protects also against incorrect manual operations, with an
automatic control system (dedicated controllers).
Applications
Large infrastructures, industry, critical buildings & process where the continuity of
service is a priority.
System
2 or 3 circuit breakers linked by an electrical interlocking system. A mechanical
interlocking system protects also against incorrect manual operations. In this case is
necessary to add a PLC controller not dedicated for source-changeover application.
Applications
Industry & Infrastructure where continuity of service requirements are meaningful but
not a priority.
A-52
Manual source-changeover systems
A manual source-changeover system can be installed Interlocking of two devices with rotary handles
on two to three manually-operated circuit breakers The rotary handles are padlocked with the devices in the OFF position.
or switch-disconnectors. Interlocking is mechanical. The mechanism inhibits the two devices being closed at the same time, but does
Interlocks prevent connection to both sources at allow for both to be open (OFF) at the same time.
the same time, even momentarily.
Combinations of "Normal" and "Replacement" devices
All Compact NS630b to 1600 circuit breakers and switch-disconnectors with rotary
handles can be interlocked.
PB113831.eps
DB417641.eps
NO h
I I
NO h
sup sup
FFO
O FFO
O
degr degr
using cables
ahcs ahcs
id id
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
Installation
O
FFO
hsup
NO h
I
sup
O
FFO
hsup
I
NO h
sup
This function requires:
bb an adaptation fixture on the right side of each device
FFO
O FFO
O
degr degr
ahcs ahcs
id id
Source S1 Source S2
NS630b to NT06 to NT16 NW08 to NW40b to
NS1600 NW40 NW63
NS630b to NS1600
Ratings 250... 1600 A bb - - -
It is not possible to combine Compact NS630b to 1600 and Masterpact (NT or NW)
devices.
A-53
Functions and characteristics Electrical interlocking
IVE unit
Electrical interlocking is used with a mechanical Electrical interlocking is carried out by an electrical control device.
interlocking system. For Compact NS630b to NS1600, this function can be implemented
in one of two ways:
Morover, the relays controlling the closing bb using the IVE unit
order to the S1 and S2 circuit breakers bb by an electrician based on the diagrams in accordance with the chapter "Electric
must be mechanically and/or electrically diagrams" source-changeover system.
interlocked to prevent them from giving
simultaneous closing commands. Characteristics of the IVE unit
bb External connection terminal block:
vv inputs: circuit breaker control signals
vv outputs: status of the SDE contacts on the S1 and S2 source circuit breakers.
bb 2 connectors for the two S1 and S2 source circuit breakers:
vv inputs:
- status of the OF contacts on each circuit breaker (ON or OFF)
- status of the SDE contacts on the S1 and S2 source circuit breakers
vv outputs: power supply for operating mechanisms.
bb Control voltage:
vv 24 to 250 V DC
vv 48 to 415 V 50/60 Hz - 440 V 60 Hz.
The IVE unit control voltage must be same as that of the circuit breaker operating
mechanisms.
PG134060_L50.eps
IVE unit.
For Compact NS630b to NS1600, each circuit breaker must be equipped with:
bb a motor mechanism
bb an available OF contact
bb a CE connected-position contact (carriage switch) on withdrawable circuit breakers
bb an SDE contact.
A-54
Remote-operated systems
DB417641.eps
In this case, changeovers between the "Normal" and "Replacement" sources under
predefined conditions are initiated by a Schneider Electric controller.
O
FFO
O
h sup FFO
h sup
NO h
I I
NO h
sup sup
FFO
O FFO
O
degr degr
ahcs ahcs
id id
PB100857_16_SE.eps
DB403810R.eps
O
FFO
O
hsup FFO
B
hsup
A
NO h
I I
NO h
sup sup
FFO
O FFO
O
degr degr
ahcs ahcs
id id
Interlocking by rods. Interlocking by cables. Switching between sources can be automated by adding:
A ACP control plate
B BA or UA controller, or an electrical system provided by the installer for NS630b to 1600.
Electrical system example: part no. 51156904 and 51156904 in the source-changeover
system catalogue.
A-55
Functions and characteristics Source-changeover systems
Associated controllers
Communication option b
Power supply
Control voltages (2) 110 V b b
220 to 240 V 50/60 Hz b b
380 to 415 V 50/60 Hz b b
440 V 60 Hz b b
Operating thresholds
Undervoltage 0.35 Un y voltage y 0.7 Un b b
Phase failure 0.5 Un y voltage y 0.7 Un b
Voltage presence voltage u 0.85 Un b b
UA controller
A-56
Controller BA UA
IP degree of protection (EN 60529) and IK degree of protection against
external mechanical impacts (EN 50102)
Front IP40 b b
Side IP30 b b
Connectors IP20 b b
Front IK07 b b
Characteristics of output contacts (dry, volt-free contacts)
Rated thermal current (A) 8
Minimum load 10 mA at 12 V
Output contacts: b b
Position of the Auto/Stop switch
Load shedding and reconnection order b
Generator set start order b
AC DC
Utilisation category (IEC 60947-5-1) AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A) 24 V 8 7 5 6 8 2
48 V 8 7 5 5 2 -
110 V 8 6 4 4 0.6 -
220/240 V 8 6 4 3 - -
250 V - - - - 0.4 -
380/415 V 5 - - - - -
440 V 4 - - - - -
660/690 V - - - - - -
A-57
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
(fixed version)
DB417254.eps
Spreader
Vertical connection Connection kit
adapter for connectors
Rear connectors
Auxiliary contact
Spreader
5.0 E
Micr ologic
push
O OFF
I
push
ON
H
NS 1200Uimp 12kV
Ui 1000V
Voltage release
8kV
Uimp Icu
Ue (kA)
arged 100 % (V) 100
disch 40 85
220/2
90
480/6
O OFF 40 % Ics =
100%
Icu
menu
alar m
tim e tr 8 12
long
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 at 6 Ir eous
.5 1 instantan
.4 x In Ii 8 10
6 12
tsd .4 .4 .3
e
t tim
shor
.2 4 15
(s)
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
53
012
Electrical control with Manual control with Manual control with Communications
mixed connection rear connection front connection module
Phase IFE
barriers
Phase
barriers
Escutcheon
ed ed
tripp tripp
t t
r es e r es e
F F
0 OF 0 OF
tripped
reset
A-58
Compact NS630b to 1600
(withdrawable version)
DB417425.eps
Interphase barriers
IFE
Vertical connection
Spreader adapter
Spreader
FDM121 FDM128
Auxiliary contact
5.0 E
Micr ologic
rear connection
Ue (kA)
100 % (V) 100
40 85
220/2
90
480/6
Voltage release
Icu
100%
40 % Ics =
menu
alar m
tim e tr 8 12
long
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 at 6 Ir eous
.5 1 instantan
.4 x In Ii 8 10
6 12
tsd .4 .4 .3
e
t tim
shor
.2 4 15
(s)
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
Manual operation
Communications
module
5.0 E
Micr ologic
I ON
push
O
push
OFF H
NS 1200Uimp 12kV
Ui 1000V
Uimp
8kV
Icu I on I on
Ue (kA)
100 % arged (V) 100
disch 40 85
220/2
90
480/6
O
Icu
OFF 100%
40 % Ics =
menu
ed ed
alar m
Ir
long
.8 .9
tim e tr
(s) 4
2
8 12
16
20
tripp tripp
.7 .95
.6 1 24
.98 .5 at 6 Ir eous
.5 1 instantan
.4 x In Ii 8 10
6 12
tsd .4 .4 .3
e
t tim
shor
.2 4 15
(s)
Isd3 4 5 .3 .1 3 off
6 2
.2
t t
r es e r es e
2.5 8 0 x In
2
.1 2
I t
10 on
1.5 delay
x Ir
setting
F F
012
53 0 OF 0 OF
tripped
reset
A-59
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
Installation
PB106360r-50_r.eps
Fixed configuration
Compact NS630b to 1600 circuit breakers may be installed vertically, horizontally or
flat on their back.
DB128063.eps
DB128064.eps
Fixed Compact NS800.
Withdrawable configuration
Compact NS630b to 1600 circuit breakers should be installed vertically only.
DB128066.eps
b extract and/or rapidly replace the circuit breaker
without having to touch connections;
b allow for the addition of future circuits at a later date.
DB128067.eps
DB128068.eps
A-60
The device may be in one of four positions on the
DB128070.eps
chassis:
b connected position. The power circuits and auxiliary
contacts are all connected
b test position. The power circuits are disconnected.
The auxiliary contacts are still connected and the
Connected Test Disconnected Removed
device can be operated electrically
b disconnected position. The power circuits and The multifunctional chassis for Compact NS630b to 1600 devices is particularly
auxiliary contacts are all disconnected, however the suited for incoming circuit breakers. Features include:
device is still mounted on the chassis. It can be bb device connection and disconnection through a door, using a crank that can be
operated manually (ON, OFF, "push to trip"). stored in the chassis
b removed position. All circuits are disconnected. The bb three positions (connected, test and disconnected) that are indicated:
device simply rests on the chassis rails and can be vv locally by a position indicator
removed. vv remotely by carriage switches (3 for the connected position, 2 for the disconnected
position and 1 for the test position)
bb circuit breaker ON/OFF commands through a switchboard front panel.
Locking
There are extensive locking possibilities:
bb chassis locking in connected, disconnected and test positions using three
padlocks and two keylocks, on the switchboard front panel
bb door interlock (inhibits door opening with breaker in connected position)
bb racking interlock (inhibits racking with door open)
bb locking in each of the connected, disconnected and test positions during device
connection or disconnection. Continuation to the next position requires pressing a
release button to free the crank.
Other safety function
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics.
DB128071.eps
3
4
5
6
7
8
1
9
10
2
1 mismatch protection
2 door interlock
3 racking interlock
4 keylock locking
5 padlock locking
6 position indicator
7 chassis front plate (accessible with cubicle door closed)
8 crank entry
9 reset button
10 crank storage
A-61
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
Types of connection
Fixed device
Front connections (N, L) Connection by:
bars bare cables (except L) cables with lugs
DB128077.eps
DB128072.eps
DB128073.eps
DB128074.eps
DB128075.eps
DB128076.eps
Rear connections (N, L, LB) Connection by:
Horizontal: Vertical: bars cables with lugs
DB128078.eps
DB128079.eps
DB128072.eps
DB128074.eps
DB128080.eps
DB128082.eps
DB128072.eps
DB128073.eps
DB128074.eps
DB128075.eps
DB128076.eps
Withdrawable device
Front connections Connection by:
bars cables with lugs
DB128083.eps
DB128072.eps
DB128074.eps
DB128076.eps
DB128072.eps
DB128074.eps
DB128080.eps
A-62
To ensure performance and isolation, depending on Connections accessories
the type of circuit breaker (N, H, L, LB) and type of
connection, certain isolation accessories
are mandatory.
Type of accessories For Compact NS630b to NS1600
Fixed: Withdrawable:
Front connection Rear connection Front connection Rear connection
Vertical-connection adapters N, H, L - N, L, LB -
DB128085.eps
Spreaders N, H, L N, H, L, LB N, H, L, LB N, H, L, LB
DB128089.eps
Connection shield N, H, L - - -
DB128090.eps
(1) (2)
(1) Mandatory for voltages u 500 V unless using the bare-cable connector + terminal shield kit.
(2) Mandatory for fixed devices with L and LB performance levels, whatever the voltage.
(3) The interphase barriers are not compatible with the spreaders.
A-63
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
DB128094.eps
Bars
Fixed, front-connection Compact NS630b to 1600
DB128097.eps
devices are equipped with terminals comprising captive
screws for direct connection of bars.
Other connection possibilities for bars include
vertical-connection adapters for edgewise bars and
spreaders to increase the pole pitch to 95 mm.
If the vertical connection adapters are front oriented, Vertical-connection adapters.
then it is mandatory to install the arc chute screen in
order to comply with the safety clearances.
DB128098.eps
DB128100.eps
DB128099.eps
Spreaders.
DB128101.eps
DB128102.eps
Bare cables
DB128095.eps
DB128103.eps
Special sets of connectors and terminal shields may be
used to connect up to four 240 mm2 copper or
aluminium cables for each phase. Bare cable
connection is possible for ratings up to and including
1250 A.
DB128104.eps
DB128096.eps
4-cable connectors.
DB128107.eps
DB403911.eps
A-64
Rear connection of fixed devices
DB128109.eps
DB403912.eps
Bars
DB128100.eps
Fixed, rear-connection Compact NS630b to 1600
devices equipped with horizontal or vertical connectors
may be directly connected to flat or edgewise bars,
depending on the position of the connectors.
Spreaders are available to increase the pole pitch
to 95 mm.
Spreaders.
DB128110.eps
DB128111.eps
DB128112.eps
A-65
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
DB128094.eps
DB128097.eps
Other connection possibilities for bars include
vertical-connection adapters for edgewise bars and
spreaders to increase the pole pitch to 95 mm.
Vertical-connection adapters.
DB128115.eps
DB128116.eps
DB128100.eps
Spreaders.
DB128117.eps
DB128105.eps
Cables with lugs
DB128096.eps
DB128119.eps
A-66
Rear connection of withdrawable devices
Bars
DB128121.eps
DB128094.eps
DB128100.eps
Withdrawable, rear-connection Compact NS630b to
1600 devices equipped with horizontal or vertical
connectors may be directly connected to flat or
edge-wise bars, depending on the position of the
connectors.
Spreaders are available to increase the pole pitch to Spreaders.
95mm.
DB128122.eps
DB128123.eps
DB128124.eps
DB128105.eps
DB128126.eps
A-67
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
DB128127.eps
PB104833_ME.eps
DB128128.eps
reinforce isolation of connection points in installations
with busbars, whether insulated or not.
Barriers are installed vertically between front or rear
connection terminals.
They are mandatory for voltages u 500 V for both fixed
and withdrawable products and for L and LB types,
whatever the voltage.
DB128129.eps
A-68
CAF1
Connection of electrical auxiliaries
DB417647.eps
CAF2
CAO1
CAO2 Fixed devices
OF1 Connections are made directly to the auxiliaries once the front has been removed.
OF2 Wires exit the circuit breaker through a knock-out in the top.
OF3
SD
MN or MX
DB128133.eps
SDE
COM
Manually operated device.
DB417648.eps
Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the
SDE
OF3 chassis.
OF2 The auxiliary terminal block is made up of a fixed and moving part. The two parts are
OF1
in contact when the device is in the test and connected positions.
MN or MX
COM
CT1
CE3
CE2
CE1
CD2
CD1
Withdrawable device.
A-69
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
Functions
bb OF (ON/OFF) - indicates the position of the main circuit breaker contacts
bb SD (trip indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
vv operation of a voltage release
vv operation of the "push to trip" button
vv disconnection when the device is ON.
OF, SD and SDE changeover contacts. Returns to de-energised state when the circuit breaker is reset.
bb SDE (fault indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
bb CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit breaker closing (early make).
Installation
bb OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker
bb CAF / CAO function - the contact fits into the rotary-handle unit (direct or
extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 100 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 6 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.6 0.05 5 2.5 0.6 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 2 - - 5 1.5 - -
480 V 6 1.5 - - 5 1 - -
660/690 V 6 0.1 - - - - - -
Connected, disconnected, test position carriage switches
056456.eps
A-70
M6C programmable contacts
PB100781-32_SE.eps
These contacts, used with the Micrologic P control units, may be programmed via
the control unit keypad or via a supervisory station with the COM communication
option. They require an external power supply module.
They indicate:
bb the type of fault
bb instantaneous or delayed threshold overruns.
They may be programmed:
M6C programmable contacts: bb with instantaneous return to the initial state
circuit breaker external relay with six independent changeover bb without return to the initial state
contacts controlled from the circuit breaker via a three-wire
connection (maximum length is 10 meters). bb with return to the initial state following a delay.
Characteristics M6C
Minimum load 100 mA/24 V
Breaking capacity (A) V AC 240 5
p.f.: 0.7 380 3
V DC 24 1.8
48 1.5
125 0.4
250 0.15
1 3 7 9 6 4 12 10 18 16 24 22
DB101170.eps
5 11 2 8 14 20
Rotary handles
PB104828_ME.eps
A-71
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
DB128139.eps
DB128138.eps
DB128137.eps
Opening Opening Delayed
order order opening
order 10 12
Delay
unit
3 6
056421.eps
C2 D2 Instantaneous
opening D2
order
MX MN MN
C1 D1 D1
A-72
Electrically operated circuit breakers are equipped as
standard with a motor mechanism module.
Electrically operated circuit breaker
The motor mechanism module is used to remotely open and close the circuit
Two solutions are available for electrical operation:
breaker. It is made up of a spring-charging motor equipped with an opening release
b a point-to-point solution and a closing release.
b a bus solution with the COM communication option. An electrical operation function is generally combined with:
bb device ON/OFF indication OF
bb "fault-trip" indication SDE.
Motor mechanism module
Power supply V AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277 - 380/415
V DC 24/30 - 48/60 - 100/125 - 200/250
Operating threshold 0.85 to 1.1 Un
Consumption (VA or W) 180
PB104831_ME.eps
DB128141.eps
A1 A1 81 11
COM
DB417155.eps
Supervisor 200 ms
OF min.
for MX
SDE
A-73
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
Locking in ON position does not prevent the device from tripping in the event of a
fault or remote tripping order.
Locking on electrically operated devices
1 reset of mechanical
DB128142.eps
trip indicator
2 OFF pushbutton
3 OFF position locking
3 4 ON pushbutton
5 springs charged
Rotary handle locked by a indication
keylock. 6 pushbutton locking
1 7 contact position indication
4 8 operation counter
I
5
ON
push
O OFF
push
ed
harg
disc
2 O OFF
6
7
53
012
PB100810A-32.eps
The transparent cover blocks access to the pushbuttons used to open and close the
device.
It is possible to independently lock the opening OFF button and the closing ON
button.
The pushbuttons may be locked using either:
bb padlocks (not supplied), 5 to 8 mm
bb lead seal
Access to pushbuttons bb two screws.
protected by transparent
cover. Pushbutton locking using a
padlock.
PB104365A-32.eps
A-74
Chassis locking
1 mismatch protection
DB128071.eps
2 door interlock
3 racking interlock
4 keylock locking
5 padlock locking
3 6 position indicator
7 chassis front plate
4 (accessible with cubicle
door closed)
5 8 crank entry
9 reset button
6 10 crank storage
7
8
1
9
10
2
PB104367A34.eps
mechanically indexed.
The racking crank blocks when the exact position is obtained.
A release button is used to free it.
As standard, the circuit breaker can be locked only in "disconnected position". On
request, the locking system may be modified to lock the circuit breaker in any of the
three positions: "connected", "disconnected" or "test".
Mismatch protection.
A-75
Functions and characteristics Electrical and mechanical
accessories
Compact NS630b to 1600
Other accessories
PB104740-32.eps
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with electrically operated devices.
Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40. It is available in fixed and withdrawable versions.
Operation counter.
Transparent cover (CCP) for escutcheon
DB128144.eps
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54 and the degree of protection
against mechanical impacts to IK10. It may be used for withdrawable devices only.
Escutcheon.
DB128145.eps
Transparent cover.
DB128146.eps
Blanking plate.
A-76
Electrical and mechanical
accessories
Compact NS1600b to 3200
(fixed version)
DB417253.eps
Vertical-connection adapters
Interphase barriers
Auxiliary contact
E
ic 5.0
Micr olog
OF F
100 % OF F
40 %
menu
Voltage release
alar m
tim e tr 8 12
long
(s ) 4 16
Ir .8 .9
.7 2 20
.9 5
.6 1 24
.9 8 .5 at 6 Ir neous
.5 1 instanta
.4 x In Ii 8 10
6 12
ts d . 4 . 4 . 3
e
t tim
shor
.2 4 15
(s )
Is d3 4 5 .3 .1 3 off
6 2
2. 5
.2 0 x In
8 .1 2
2 I t
10 on
1. 5 delay
x Ir
setting
E
ic 5.0
Micr olog
OF F
100 %
OF F
40 %
Circuit breaker
Ir
menu
long
.7
.8 .9
tim e tr
(s ) 4
2
8 12
16
20
alar m NS1600b / 2500A
.9 5
Communications
.6 1 24
.9 8 .5 at 6 Ir neous
.5 1 instanta
.4 x In Ii 8 10
6 12
shor
t tim
e
ts d . 4 .4 .3 4
(s ) .2 15
Is d3 4 5 .3 .1 3 off
6 2
2. 5
.2 0 x In
8
module
2
.1 2
I t
10 on
1. 5 delay
x Ir
setting
Circuit breaker
NS3200
Interphase barriers
I/O IFM
Escutcheon
FDM121 FDM128
A-77
Functions and characteristics Electrical and mechanical
accessories
Compact NS1600b to 3200
Installation
PB106366.eps
DB128151.eps
OFF
OFF
Mounting on rails.
DB128153.eps
DB128154.eps
OFF
OFF
OFF
OFF
Bars
DB128155.eps
Bars may be directly connected to the terminals of Compact NS1600b to 3200 circuit
breakers.
NS1600b to 2500
DB128156.eps
OFF
OFF
DB128158.eps
DB128159.eps
OFF
OFF
OFF
OFF
A-78
All the auxiliary contacts opposite are also available Indication contacts
in "low-level" versions capable of switching very low
loads (e.g. for the control of PLCs or electronic Contacts installed in the device
circuits). Changeover contacts are used to remote circuit breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
054549-18.eps
Functions
bb OF (ON/OFF) - indicates the position of the main circuit breaker contacts
bb SD (trip indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault
vv operation of a voltage release
vv operation of the "push to trip" button
OF, SD and SDE changeover contacts.
bb Returns to de-energised state when the circuit breaker is reset.
SDE (fault indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
Installation
bb OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on the position where it is inserted in the device.
The contacts clip into slots behind the front cover of the circuit breaker.
Electrical characteristics of the OF/SD/SDE auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 100 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 6 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.6 0.05 5 2.5 0.6 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 2 - - 5 1.5 - -
480 V 6 1.5 - - 5 1 - -
660/690 V 6 0.1 - - - - - -
A-79
Functions and characteristics Electrical and mechanical
accessories
Compact NS1600b to 3200
DB128138.eps
DB128139.eps
DB128137.eps
Opening Opening Delayed
order order opening
order 10 12
MX voltage release Delay
unit
3 6
C2 D2 Instantaneous
opening D2
order
MX MN MN
C1 D1 D1
MN delay units
To eliminate circuit breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply non-adjustable 100/130 - 200/250
V AC 50-60 Hz /DC adjustable 48/60 - 100/130 - 200/250 - 380/480
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption of delay pick-up: 200 (200 ms) hold: 4.5
unit alone (VA or W)
Circuit breaker response non-adjustable 0.25 s
time at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s
A-80
Device locking
PB104836_ME.eps
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40.
Interphase barriers.
DB128161.eps
Escutcheon.
A-81
A-82
Compact NS630b to 3200 Installation recommendations
Presentation 2
Functions and characteristics A-1
B-1
Installation Operating conditions
recommendations
2000
Altitude (m) 2000 3000 4000 5000
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 800 710 635 560
Maximum rated operationnal voltage 50/60 Hz Ue (V) 690 690 635 560
Rated current 40 C 1 x In 0.99 x In 0.96 x In 0.94 x In
Intermediate values may be obtained by interpolation.
Vibrations
Compact NS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
bb 2 V 13.2 Hz: amplitude 1 mm
bb 13.2 V 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Electromagnetic disturbances
DB128163.eps
B-2
Installation in switchboards
Power supply and weights
Power supply
DB128165.eps
Compact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when
installed in a switchboard.
Weights
Circuit breaker Chassis
NS630b to 1600 manual operation 3P 14 14
4P 18 18
NS630b to 1600 electrical operation 3P 14 16
4P 18 21
NS1600b to 3200 3P 24 -
4P 36 -
The table above presents the weights (in kg) of the circuit breakers and the main accesories,
which must be summed to obtain the total weight of complete configurations.
B-3
Installation Installation in switchboards
recommendations Safety clearances
and minimum distances
General rules
When installing a circuit breaker, minimum distances (safety clearances) must be
maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
bb use insulated bars for circuit-breaker connections
bb block off the busbars using insulating screens.
DB417671.eps
146.5
F
(*) An overhead clearance of 50 mm is
required to remove the arc chutes.
DB128169.eps
C C
40
180
F
F Datum
B-4
Installation example
Painted sheetmetal
DB404158.eps
B-5
Installation Door interlock
recommendations
for Compact NS630b to 1600
DB418148.eps
this locking device prevents opening of the door if the
circuit breaker is in the connected or test positions. If
the circuit breaker was connected with the door open,
the door may be closed without having to disconnect
the circuit breaker.
X
61
11.5
(1) (2)
2
Dimensions (mm)
Type (1) (2)
NS630b to 1600 (3P) 135 168
NS630b to 1600 (4P) 205 168
Door
F
5
23
B-6
Control wiring
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+)
bb It is recommended to use the AD power supply due to its low stray primary-
secondary capacitance. Good operation of the Micrologic Trip Unit in noisy
environment is not guaranteed with other power supplies.
bb The dedicated AD power supplies shall be used only for the Micrologic trip units. If
the COM option is used, a second dedicated power supply shall be used.
bb M2C and M6C modules can be supplied by Micrologic external AD power supply.
bb The consumption of a Micrologic Trip Unit is approximately 100mA.
bb The consumption of M2C and M6C modules is approximately 100mA.
bb A number of 5 devices (Micrologic control units with M2C or M6C) can be
connected to the same AD power supply. Add other AD power supply for more than 5
devices.
bb For Micrologics control units alone, a number of 10 devices can be connected to
the same AD power supply. Add other AD power supply for more than 10 Micrologics.
bb If the installation is shared between several panels, one AD power supply shall be
added for each panel.
bb AD power supply dedicated to Micrologics trip units shall not be connected to
earth. (F1-, F2+).
External 24 V DC power supply for Communication bus
bb A dedicated 24 V DC power supply shall be used for the communication devices.
bb Do not connect the positive terminal (E1) to earth.
bb The negative terminal (E2) can be connected to earth.
bb A number of communication modules (BCM, IFE, IFM, I/O, FDM) can be
connected to the same 24 V DC power supply. Refer bellow the devices
consumption table to avoid exceeding the maximum current delivered by the
24 V DC power supply.
ULP module consumption
The table below lists the ULP module consumption.
Module Typical Consumption Maximum Consumption
(24 V DC at 20 C / 68 F) (19.2 V DC at 60 C / 140 F)
BCM ULP for Masterpact and 40 mA 65 mA
Compact NS
Micrologic 5 or 6 trip unit for 30 mA 55 mA
CompactNSX circuit breakers
BSCM for Compact NSX circuit 9 mA 15 mA
breakers
2-wire RS 485 isolated repeater 15 mA 19 mA
FDM121 display for LV circuit breaker 21 mA 30 mA
IFM Modbus-SL interface for LV 21 mA 30 mA
circuit breaker
IFE Ethernet interface for LV circuit 120 mA 3 A (with gateway)
breaker
I/O input/output interface module 165 mA 420 mA
for LV circuit breaker
Maintenance module 0 mA (the maintenance 0 mA (the maintenance
module has its own power module has its own power
supply) supply)
Installation recommendation
bb The 24 V DC wires (output of the 24 V DC power supply) shall be twist together.
bb The 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly.
bb The technical characteristics of the external 24 V DC power-supply module for
Micrologic control units are indicated on page A-28.
Note: wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be
connected to earth at both ends.
B-7
Installation Temperature derating
recommendations Compact NS devices equipped
with electronic trip units
B-8
Power dissipation / Resistance
Compact NS devices equipped
with electronic trip units
The values indicated in the tables opposite are Compact NS630b to 1600
typical values. Version Fixed device
Power dissipated per pole (P/pole) in Watts (W) N L LB
The value indicated in the table is the power R/pole P/pole R/pole P/pole R/pole P/pole
NS630b 0.026 10 0.039 15 0.056 15
dissipated at IN, 50/60 Hz, for a three-pole or
NS800 0.026 15 0.039 20 0.056 20
four-pole circuit breaker (these values can be higher
NS1000 0.026 22 0.039 34
than the power calculated on the basis of the pole NS1250 0.026 44
resistance). Measurement and calculation of the NS1600 0.026 74
dissipated power are carried out in compliance with
the recommendations of Annex G of standard Version Withdrawable device
IEC 60947-2. N L LB
R/pole P/pole R/pole P/pole R/pole P/pole
Resistance per pole (R/pole) in milliohms (m)
NS630b 0.038 19 0.072 34 0.086 34
The value of the resistance per pole is provided as
NS800 0.038 30 0.072 40 0.086 40
a general indication for a new device. NS1000 0.038 50 0.072 77
The value of the contact resistance must be NS1250 0.036 84
determined on the basis of the measured voltage NS1600 0.036 154
drop, in accordance with the manufacturers test
procedure (expert card ABT no. FE 05e).
Compact NS1600b to 3200
Note: this measurement is not sufficient to determine Version Fixed device
the quality of the contacts, i.e. the capacity of the circuit N
breaker to carry its rated current. R/pole P/pole
NS1600b 0.019 84
NS2000 0.013 84
NS2500 0.008 100
NS3200 0.008 227
B-9
B-10
Compact NS630b to 3200 Dimensions and connection
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
C-1
Dimensions Compact NS630b to 1600
and connection
(fixed version)
Dimensions
Manual control
Front connection (N, L)
DB128173.eps
DB128174.eps
(1)
254
163.5
X 327 X
508 200
100
DB128176.eps
105
175 (4P)
188
94
105 123
X X
234 210
113
92.5 117 123
F
107.5 35
140.5 70
146.5 Y
205 14
Z
Electrical control
Front and rear connection (N, L, LB)
105 (3P)
DB128178.eps
DB417646.eps
123
105
X X
210 234 200
117 100
123
107.5 35
175.5 70
182 99.5 (3P)
99.5
F 169.5 (4P)
Z Y F : Datum.
Note: Dimensions for front and rear
connection on electrically operated
devices are identical to those for
manually operated devices.
C-2
Mounting
Front connection
On backplate On rails
Y
DB128179.eps
DB128180.eps
Y 4 6.5
4 6.5
X X
200 200
100 100
99.5 (3P)
99.5
169.5 (4P)
99.5 (3P)
99.5
169.5 (4P)
Rear connection
On backplate On rails
Y
DB414750.eps
DB414751.eps
Y 4 6.5 (3P)
6 6.5 (4P)
4 5.5
4 R30
60 107
75
X 200 X 234
75
60 100 107 117
70 70
200 (3P) (4P)
270 (4P)
Note: Mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.
C-3
Dimensions Compact NS630b to 1600
and connection
(fixed version)
Front-panel cutouts
Toggle control
DB128183.eps
DB128184.eps
DB128185.eps
(C) 150 194 mini (3P) 194 mini (3P)
(2) 194 mini 194 mini
264 mini (4P) 264 mini (4P)
201(1)
X 216 (1) X
X
266 (2)
F : Datum. Y
DB128186.eps
119 (1)
144 (2)
95.5 (1)
108 (2)
35.5 (1)
71 (1) 60.5 (2)
121 (2)
Electrical control
Door cutout
A
Y
DB128187.eps
DB128184.eps
X X 216 (1)
266 (2)
108 (1)
133 (2)
F : Datum.
(1) Without escutcheon.
(2) With escutcheon.
C-4
Rotary handle
DB128190.eps
DB128189.eps
(1) (2)
(B)
(D) 180 mini Y
(2)
60
R80
X X
195
24
60
107.5 25
140.5
146.6
175.5
229.5
F
Z
Door cutout
A B D
Y Y Y
DB128184.eps
DB128192.eps
DB128193.eps
194 mini (3P) 194 mini (3P)
194 mini 194 mini 194 mini
264 mini (4P) 264 mini (4P)
201 (1)
216 (1) 201 (1)
X X X
266 (2)
108 (1)
133 (2)
90.5 (1) 90.5 (1)
194 (1) 97 (1)
181 (1) 130 (1)
244 (2) 122 (2)
DB128196.eps
DB128195.eps
Y
Y
60
R100
X X
X
24
60
212.5 25
231.5 mini
605.5 maxi F
Z
C-5
Dimensions Compact NS630b to 1600
and connection
(withdrawableversion)
Dimensions, mounting and cutouts
Dimensions
Manual control Electrical control
127.5 (3P)
DB128198.eps
DB128199.eps
160.5
DB128197.eps
70 (*) 46 (*)
199
X X X
45.5
69 123
5 5
90 (3P)
60 mini 60 mini 160 (4P)
90
F F Y
Mounting
Bottom mounting on base plate or rails Vertical on uprights or backplate
Y
DB128200.eps
DB128201.eps
DB128202.eps
Y
X
X
24 25
100
216
231
F
F
Cutouts
Door cutout Rear panel cutout
Y
DB128203.eps
DB128204.eps
259 (1)
X 303 (2) X
234
117
109 (1)
130.8 (2) 102.5 (3P)
161 (1) 102.5
183 (2) 172.5 (4P)
259 (1)
307 (2)
C-6
Rotary handle
DB128206.eps
DB128205.eps
mini
Y
136 (*)
60
R80
X X
93 24
60
5
60 mini F 25
Door cutout
170 mini (3P)
230 mini
DB128207.eps
259 (1)
303 (2)
X
109 (1)
130.8 (2)
161 (1)
259 (1) 183 (2) (1) Without escutcheon.
307 (2) (2) With escutcheon.
Extended rotary handle
Dimensions Door cutout
DB128208.eps
DB128209.eps
DB128210.eps
60
E47966A
R200
X X X
24
60
207 mini 17 25
447 maxi
F
C-7
Dimensions Compact NS1600b to 3200
and connection
(fixed version)
Dimensions
Dimensions
DB128212.eps
DB128211.eps
165
X X
330
18.5
38.5
132
162.5
168.5
222.5
F
368
Z
Y Y
DB128213.eps
DB128214.eps
X 216 (1) X
267 (2) 201
108 (1) 100.5
133.5 (2)
173 (1)
198.5 (2) 166
346 (1) 332
397 (2)
C Mounting on rails
Y Y
DB128215.eps
DB128216.eps
4 12
X
X 150
119
75
95.9
73 195 (3P)
310 (4P) 195
146
F : Datum.
(1) Without escutcheon. Note: X and Y are the symmetry planes for a 3-pole device
(2) With escutcheon.
C-8
Compact NS630b to 3200
External modules
DB128217.eps
DB128218.eps
8
S : 0.6 mm
S : 2.5 mm
3.5
DB128220.eps
88
90
105
59 88
105
DB128222.eps
H4
73 60
H3 Input C +
24VD
t
24V OutpuC
BAT + 24VD H1
H2
112
75
++ 90
Network
45
Rseau
us
modb
CCM
shield
Fault
A A
B B
A A
B B
Com.
Breaker
Disjoncteur
ss
Addre
+
.
sync
CE
CD
CT
58
54
C-9
Dimensions Compact NS630b to 3200
and connection External modules
DB416700.eps
24VDC I1 C I2 I3 C I4 I5 C I6
I1 A1
I2
I3 O1
I4 O2
I5 O3 45 92
I6
84.8 115
IO LV434063
O1 O2 O3 A1
13 14 23 24 33 34 T1 T2
72 63.6
71
DB416702.eps
45 92
85 105
18 66
73
DB416698.eps
ETH1 ETH2
IFE
IFE-XX.YY.ZZ (factory set)
ETH1 LK/10-100/ACT
45 92
ETH2 LK/10-100/ACT
Module Status
84.8 105
Modbus-SL
Network Status
T LV434011
72 63.6
71
ComX 200
DB417076.eps
DB417077.eps
90 45 85 106
144 63
69
C-10
External sensor for neutral
400/1600 A (NS630b to 1600)
4 14
DB128228.eps
35 76
177
208
127
44
44 174 44
295
Installation
400/1600 (NS630b to NS1600) 1000/4000 A (NS1600b to NS3200)
DB128230.eps
DB128231.eps
C-11
Dimensions Compact NS630b to 3200
and connection External modules
DB128233.eps
DB128232.eps
197
233
115 216
280 71
362
381
242 281
146
160 263
456 72
470
552
572
Busbars path
280 x 115 mm window 470 x 160 mm window
Busbars spaced 70 mm centre-to-centre Busbars spaced 115 mm centre-to-centre
DB128236.eps
DB128237.eps
M1 M2 M3
2 bars 50 x 10
4 bars 100 x 5
DB128238.eps
DB128239.eps
M1 M2 M3
2 bars 100 x 5
4 bars 125 x 5
C-12
FDM121 switchboard display
Dimensions
DB114991.eps
DB114992.eps
96
X
96
Y
Mounting
Through panel
DB114993.eps
DB416963.eps
DB118545.eps + 0.8
X 92 0
X
+ 0.8
10.6 92 0
20.7 23
Y
Z
On panel
DB114996.eps
DB115121.eps
DB115122.eps
DB115270.eps
2 22.5
16.5
X 99.3
+ X
- 0.5
32
19
+0.3
15 37 20 13 2 22.5
-
+
- 1.5
33
Z
17
99.3
Y
Connector (optional).
C-13
Dimensions FDM128 switchboard display
and connection
Dimensions
DB416703.eps
DB416736.eps
129
X
163
Mounting
On panel
1.5...6
DB416704.eps
DB416737.eps
DB416738.eps
100
X
30.6
17.5
39
+0
DB416739.eps
DB416740.eps
22,5 -0,30
100
100 100
100
+0
30 -0,20
C-14
Accessories NS630b to 3200
Escutcheon
NS630b to NS1600 (fixed control)
A C
DB128241.eps
DB128242.eps
DB128240.eps
(A)
Y
(C)
Y
X X X
275 154
27
27 27
131
27
253
DB128244.eps
X X 313
27
27 13 27
317
DB128246.eps
Y
27
X 275 X
137.5
27 202.5
405
C-15
Dimensions Compact NS630b to 1600
and connection
(fixed version)
Bars
DB128248.eps
DB128041.eps
DB128247.eps
15
123
E47904A
67.5 N Y
X
67.5 44
DB128249.eps
25 9.5 12.5
123
15 60
12.5
31
F 2 11
Z
DB128251.eps
DB128051.eps
15
View A
97
X
N Y
97
60
DB128252.eps
12.5
12.5 9.5
31
44
F
Z
25
2 11
View A detail.
Front connection
70 70 70
DB128253.eps
DB128254.eps
DB128255.eps
30
163.5
129
N Y
X View A
163.5 9.5
25 15
15
16.5 15
15 25
9.5
F 2 screws M10 44
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-16
Front connection with spreaders
70 70
DB128258.eps
DB128259.eps
DB128257.eps
25 25
196
181
15
Y
View A
X
95 95 95
DB128260.eps
70 70 70
181
196 12.5 12.5
N Y 15
31.5 View A
F
Z
Rear connection with spreaders
98 95 95
DB128261.eps
DB128262.eps
DB128263.eps
70 70
123
15
82.5
X
15 52.5
Y
123
95 95 95
DB128264.eps
70 70 70
83
F 12.5 12.5
Z
N
Y
Spreader detail
Middle left or middle right Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
spreader for 4P
DB128266.eps
DB128268.eps
DB128267.eps
DB128265.eps
View A detail.
C-17
Dimensions Compact NS630b to 1600
and connection
(fixed version)
Bars
DB128270.eps
DB128152.eps
DB128269.eps
15
View A
200
X N
430 Y
DB128271.eps
200
10
62.5
F View A detail.
Z
F : Datum.
Note: (1) two mounting possibilities for vertical-connection adapters (pitch 21 mm).
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-18
Compact NS630b to 1600
(fixed version)
Cables with lugs and bare cables
DB128273.eps
DB128274.eps
View A
250 N Y
200 15
X 530
DB128275.eps
200
250
View A detail.
15
10
150
F
Z
Lugs
20.5 : 240 mm
DB128276.eps
DB128277.eps
DB128278.eps
23 : 300 mm
89.5
10
11.5
25
31
DB128281.eps
DB128279.eps
199 206.5
N
Y
X
398 413
199 206.5
DB128282.eps
16.5
35
61
F
Z
F : Datum.
C-19
Dimensions Compact NS630b to 1600
and connection
(plug-in and withdrawable
versions)
Bars
Horizontal rear connection
70 70 70
DB128284.eps
DB128285.eps
DB128283.eps
49
15
67.5
X
228
N
67.5 Y
114
44
DB128249.eps
25 9.5 12.5
267.5 15
F 60
12.5
2 11
DB128288.eps
DB128289.eps
49 15
View A
97
X
97 N
Y
60
DB128252.eps
267.5 12.5
F 12.5 9.5
44
25
2 11
View A detail.
Front connection
15 12.5 View A
DB128292.eps
DB128293.eps
DB128291.eps
70 70 70
171
N Y
X 336
Top terminal Bottom terminal
DB128294.eps
140
235 12.5
F
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-20
Front connection with spreaders
95 95
DB128296.eps
DB128297.eps
DB128295.eps
View A
70 70
238
223
X Y
95 95 95
DB128298.eps
207 70 70 70
192 View A
12.5 12.5
250
F
N Y
Spreader detail
Middle left or middle right Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
spreader for 4P
DB128266.eps
DB128267.eps
DB128268.eps
DB128265.eps
View A detail.
F : Datum.
C-21
Dimensions Compact NS630b to 1600
and connection
(plug-in and withdrawable
versions)
Cables with lugs
Front connection with vertical-connection adapters and cable-lug adapters
15 70 70 70
DB128304.eps
DB128305.eps
DB128303.eps
15 View A
50
71
292
21 N
Y 15
171
DB128275.eps
X 583
140
21
261
71
View A detail.
50
193.5 15
F
Lugs
20.5 : 240 mm
DB128276.eps
DB128277.eps
DB128278.eps
23 : 300 mm
89.5
10
11.5
25
31
F : Datum.
Note: X and Y are the symmetry planes for a 3-pole device.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-22
Compact NS1600b to 3200
(fixed version)
DB128311.eps
DB128312.eps
DB128310.eps
165
150
X Y
N
View A
OFF
OFF
150
165
DB128313.eps
20
F
Z
View A detail.
Front connection with vertical-connection adapters (NS1600b to 2500)
115 115 115
DB128315.eps
DB418147.eps
DB418145.eps
80 80 80 80
230
142.5
X Y
N
View A
142.5
OFF
OFF
230
DB128317.eps
25
F
40
Z
View A detail.
Front connection (NS3200)
115 115 115
DB128319.eps
DB128320.eps
DB418146.eps
230
142.5
N Y
X View A
DB128317.eps
OFF
OFF
142.5
230
25
F
40
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-23
Dimensions Power connections for
and connection
Compact NS630b to 1600
Recommended drilling dimensions
DB128324.eps
DB128325.eps
DB128322.eps
Middle left or middle right Middle spreader for 3P Left or right spreader Left or right spreader
spreader for 4P for 4P for 3P
44
DB128327.eps
DB128328.eps
DB128329.eps
DB128330.eps
DB128326.eps
25 9.5 12.5
60
12.5
2 11
DB128333.eps
DB128334.eps
DB128335.eps
DB128331.eps
60
DB128336.eps
12.5
12.5 9.5
44
25
2 11
DB128324.eps
DB128325.eps
DB128322.eps
DB128342.eps
15 25 15
2 M10 screws 9.5
44
C-24
Power connections for
CompactNS1600b to 3200
Recommended drilling dimensions
DB128324.eps
DB128325.eps
DB128322.eps
DB128346.eps
DB128349.eps
DB128347.eps
DB128350.eps
DB128351.eps
DB128350.eps
DB128351.eps
C-25
Dimensions Power connections for
and connection
Compact NS630b to 3200
DB128357.eps C
E E
B Connection of bars
DB128358.eps
Bars must be adjusted to ensure correct positioning on the terminals before bolting (B).
Bars must rest on a support firmly attached to the switchboard frame, such that the
circuit breaker terminals do not bear any weight (C).
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is calculated
to resist the electrodynamic stresses exerted between the bars of each phase during
a short-circuit.
B C
DB128359.eps
DB128360.eps
C-26
1 2 3 4 5 Connections
DB128361.eps
The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
The correct tightening torques for the connection of bars to the circuit breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and bolts
(class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
Examples of bar connections
DB128362.eps
DB128363.eps
DB128364.eps
6
Bar drilling
Examples
DB128365.eps
DB128366.eps
DB128367.eps
Insulation distance
DB128368.eps
Dimensions (mm)
Utilisation voltage X minimum
Ui y 600 V 8 mm
Ui y 1000 V 14 mm
Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.
DB128369.eps
Dimensions (mm)
e Radius r
Minimum Recommended
5 5 7.5
10 15 18 to 20
C-27
Dimensions Power connections for
and connection
Compact NS630b to 3200
Sizing of bars
Note: The values presented in the tables are the result of trials and theoretical calculations on
the basis of the assumptions mentioned above.
These tables are intended as an aid in designing connections, however, the actual values must
be confirmed by tests on the installation.
DB128370.eps
C-28
Vertical rear connections
DB128371.eps
C-29
C-30
Compact NS630b to 3200 Electrical diagrams
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
D-1
Electrical diagrams Compact NS630b to 1600
Fixed circuit breakers
DB128373.eps
N L1 L2 L3
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT BPO BPF
M6C
D2
C2
B4
A4
A2
Q1
Q2
Q3
VN
Z1
Z2
Z3
Z4
Z5
Q
MN MX Motor-mechanism
module
Micrologic
or
D1
A1
C1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
24 V DC
9 11
power supply
R
b b VN external voltage connector
(must be connected to the neutral A4 A2 B4
with a 3P circuit breaker)
A1
CN2 a - 440/480 V
D-2
Electrical diagrams Compact NS630b to 1600
Fixed circuit breakers
Yellow
Brown
DB128375.eps
DB128376.eps
White
Black
Blue
Red
Open Closed Fault Fault Closed Open
E6 E5 E4 E3 E2 E1
MN/MX
OF1
11 12 14
M1M2M3 F1 F2 D1/C1
542
544
532
534
524
522
514
512
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
32
34
22
24
12
14
82
84
92
94
D2/C2 OF2
21 22 24
OF3
31 32 34
SD
OF3 OF2 OF1 CAO2 CAO1 91 92 94
SDE SD CAF2 CAF1
541
531
521
511
31
21
11
81
91
White
Black
Blue
Red
SDE :
fault-trip indication contact
(short-circuit, overload, earth fault) E6 E5 E4 E3 E2 E1
MN/MX
SD :
trip indication contact M1M2M3 F1 F2 D1/C1
(manual operation) Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2
CAF2/CAF1 * : early-make contact
(rotary handle)
82 32 22 12
84 34 24 14
B4 A4 A2 A1
D-3
Electrical diagrams Compact NS630b to 1600
Plug-in / withdrawable circuit breakers
DB128379.eps
N L1 L2 L3
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
M6C AT BPO BPF
Q1
Q2
Q3
VN
D2
C2
B4
A4
A2
Z1
Z2
Z3
Z4
Z5
Q
Motor-mechanism
MN MX module
Micrologic
or
F2+
M1
M2
T2
T3
T1/M3
D1
C1
A1
T4/F1
24 V DC
E3 E4 Z3 Z4 T3 T4 VN Q2 542 B4
/
E1 E2 Z1 Z2 T1 T2 F1 Q1 541 D1 C1 A1
9 11
power supply
R
b b VN external voltage connector
(must be connected to the neutral A4 A2 B4
with a 3P circuit breaker)
A1
CN2 a - 440/480 V
D-4
Electrical diagrams Compact NS630b to 1600
Plug-in / withdrawable circuit breakers
DB128150.eps
DB128382.eps
DB128188.eps
Open Closed Fault Fault Closed Open Disconnected Connected Test
822
824
812
814
332
334
322
324
312
314
542
544
532
534
524
522
514
512
914
912
32
34
22
24
12
14
82
84
92
94
331
321
311
821
811
911
541
531
521
511
31
21
11
81
91
Q3 544 534 84 94 524 514 34 24 14 824 814 334 324 314 914
Q2 542 532 82 92 522 512 32 22 12 822 812 332 322 312 912
Q1 541 531 81 91 521 511 31 21 11 821 811 331 321 311 911
Legend
Connected
* CAF2 option is not compatible with M6C option. (only one wire per connection point).
D-5
Electrical diagrams Compact NS1600b to 3200
Fixed circuit breakers
DB128391.eps
N L1 L2 L3
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT
D2
C2
Z1
Z2
Z3
Z4
Z5
Q
MN MX
Micrologic
or
D1
C1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
24 V DC
D-6
Electrical diagrams Compact NS1600b to 3200
Fixed circuit breakers
DB128393.eps
E6 E5 E4 E3 E2 E1
MN/MX
OF1
Open Closed Fault Fault 11 12 14
M1M2M3 F1 F2 D1/C1
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2 OF2
21 22 24
32
34
22
24
12
14
82
84
92
94
OF3
31 32 34
SD
91 92 94
21
11
81
91
81
82
84
SDE
Indication contacts
OF3 / OF2 / OF1 : ON / OFF indication contacts
D-7
Electrical diagrams Compact NS630b to 3200
Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking
DB414726.eps
circuit for external neutral
Compact equipped with a Micrologic 6 A/E/P (1):
bb shielded cable with 2 twisted pairs
bb T1 twisted with T2
bb maximum length 4 meters
bb cable cross-sectional area 0.4 to 1.5 mm2
bb recommended cable: Belden 9552 or equivalent.
For proper wiring of neutral CT, refer to instruction
Bulletin 48041-082-03 shipped with it.
Do not remove Micrologic factory-installed jumper
between T1 and T2 unless neutral CT is connected.
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical; for
the power wiring, H1 is connected to the source side,
H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external Shield Drain
neutral is not necessary.
Connection for signal VN is required only for power
measurements (3 , 4 wires, 4CTs).
Micrologic 6
F2+
T1/M3
M1
M2
T2
T3
T4/F1
12 5 6 7 10 11
H1 X1
1 MiDGF module 9
H2 X2 3 8
PE 13 14
D-8
Electrical diagrams Compact NS630b to 3200
Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking
Earth-leakage protection
N L1 L2 L3
Connection of the rectangular-sensor secondary
DB128388.eps
circuit
Compact equipped with a Micrologic 7 A/P:
Z1
Z2
Z3
Z4
Z5
use the cable shipped with the rectangular sensor.
Q
I
Micrologic 7
U
F2+
T1/M3
M1
M2
T2
T3
T4/F1
M1
M2
M3
Neutral protection
D-9
Electrical diagrams Compact NS630b to 3200
Communication
Ethernet
J
24 V DC
Modbus
A A N A
24 V DC
24 V DC B
+24V
0V
I I I
K Eth2
C Eth1
C +24V
0V
D
K +24V
0V
Eth1
Eth2
Eth2
Eth1
I
I I
I6
C
I5
I4
C
I3
I2
C
I1
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
A1
K
K O1
O2
O3
K dule
IO Mo
E
I6
C
I5
I4
C
I3
I2
C A1
I1
T2
O3 T1
34
I6 I6 O2 33
C C 24
I5 23
O1
I3 14
I2 13
C I2
C
I1 I1
+
DC
24V
I6
C
I5
I3
I2
C
I1
+
DC
24V
A1
T2
T1
O2
24
O1 23
14
13
A1
T2
T1
M
O2
24
O1 23
14
13
F
L L L M
F G H H
K ULP cable
A FDM121 (TRV00121) E I/O application module (LV434063) I ULP termination (TRV00880)
L Breaker ULP cord
B IFE master (LV434011) F Masterpact NT/NW J FDM128 (LV434128)
M NSX cord
N Modbus Termination
(1)
C IFE (LV434010) G Compact NS630b-3200
(VW3A8306DRC) Ethernet
D IFM (TRV00210) H Compact NSX
Modbus
(1) Modbus termination is mandatory, see ULP system user guide TRV99101.
D-10
Electrical diagrams Fixed, electrically operated
Compact NS630b to 3200
Connection to the communication
interface module
DB416707.eps
121
FDM
Color
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP
cord
E1 E2 E3 E4 E5 E6
A / Tx- D0
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
24 V
0V
D0 = A / Rx-, A / Tx-
ULP cable D1 = B / Rx+, B / Tx+
24VDC
ETH1 ETH2
IFE IFM
OR
D-11
Electrical diagrams Withdrawable
Compact NS630b to 3200
Connection to the I/O application module
and communication interface module
DB417695.eps
121
FDM
24VDC
I/O
application
Color module
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP ULP cable
cord
Red Black White Blue
E1 E2 E3 E4 E5 E6
A / Tx- D0
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
24 V
0V
Modbus-SL Ethernet
24 V DC 24 V DC
24VDC
ETH1 ETH2
IFM IFE
D-12
Electrical diagrams Compact NS630b to 3200
Connection of the 24 V DC
external power supply AD module
bb The 24 V DC external power-supply (AD module) for the Micrologic control unit
DB417452.eps
Note: in case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The BAT battery module, mounted in series upstream of the AD module, ensures
an uninterrupted supply of power if the AD module power supply fails.
The internal voltage taps are connected to the botton side of the circuit breaker.
With Micrologic P/H, external voltage taps are possible using the PTE option.
With this option, the internal voltage taps are disconnected and the voltage taps are connected
to terminals VN, V1, V2, V3.
The PTE option is required for voltages less than 220 V and greater than 690 V (in which case
a voltage transformer is compulsory). For three-pole devices, the system is supplied with
terminal VN connected only to the control unit (Micrologic P).
When the PTE option is implemented, the voltage measurement input must be protected against
short-circuits. Installed as close as possible to the busbars, this protection function is ensured
by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
This voltage measurement input is reserved exclusively for the control unit and must not ever be
used to supply other circuits outside the switchboard.
Connection
The maximum length for each conductor supplying power to the trip unit or M6C
module is 10 m.
Do not ground F2+, F1-, or power supply output:
bb the positive terminal (F2+) on the trip unit must not be connected to earth ground
bb the negative terminal (F1-) on the trip unit must not be connected to earth ground
bb the output terminals (- and +) of the 24 V DC power supply must not be grounded.
Reduce electromagnetic interference:
bb the input and output wires of the 24 V DC power supply must be physically
separated as much as possible
bb the 24 V DC wires (output of the 24 V DC power supply) shall be twisted together.
bb the 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly
bb power supply conductors must be cut to length. Do not loop excess conductor.
D-13
D-14
Compact NS630b to 3200 Additional characteristics
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
E-1
Additional characteristics Tripping curves
Compact NS630b to 3200
DB128396.eps
It ON
0.4
0.3
0.2
It OFF 0.1
0
(1)
Ig = In x A B C D E F G H J
In < 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A y In y 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In > 1200 A 500 640 720 800 880 960 1040 1120 1200
E-2
Additional characteristics Current-limiting curves
The limiting capacity of a circuit breaker is its aptitude Ics = 100 % Icu
to limit short-circuit currents. The exceptional limiting capacity of the Compact NS range greatly reduces the
forces created by fault currents in devices.
(Isc)
DB128398.eps
Prospective The result is a major increase in breaking performance. In particular, the service
Isc peak breaking capacity Ics is equal to 100 % of Icu.
Prospective The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
current the following operations:
bb break three times consecutively a fault current equal to 100 % of Icu
Prospective bb check that the device continues to function normally:
Isc vv it conducts the rated current without abnormal temperature rise
Limited Isc
vv protection functions perform within the limits specified by the standard
peak vv suitability for isolation is not impaired.
Actual
current Longer service life of electrical installations
Limited Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
Isc
on installations.
(t) Thermal effects
The exceptional limiting capacity of the Compact NS range is Less temperature rise in conductors, therefore longer service life for cables.
due to the rotating double-break technique (very rapid natural Mechanical effects
repulsion of contacts and the appearance of two arc voltages
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
in-series with a very steep wave front).
being deformed or broken.
Electromagnetic effects
Less disturbances for measuring devices located near electrical circuits.
Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which
are a function of the prospective short-circuit current (the current which would flow if
no protection devices were installed):
bb the actual peak current (limited current),
bb thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .
Example
What is the real value of a 200 kA rms prospective short-circuit (i.e. 440 kA peak)
limited by an NS630bLB upstream ?
Answer: 70 kA peak (see next page).
E-3
Additional characteristics Current-limiting curves
Current-limiting curves
Voltage 400/440 V AC (1) Voltage 660/690 V AC
Limited short-circuit current (k peak) Limited short-circuit current (k peak)
DB128400.eps
DB128399.eps
NS630bH
NS800H
NS1000H NS1600bN
NS630bH NS2000N
NS1250H NS800H
NS630bN NS1600H NS2500N
NS1000H NS3200N
NS800N NS1250H
NS1000N NS630bL NS630bN NS1600H
NS1250N NS800L NS630bLB NS800N
NS1600N NS1000L NS800LB NS1000N
NS1250N
L NSX630 NS1600N NS630bLB
S NS630bL NS800LB
H NSX400
N NS800L L
k F k NS1000L S NSX630
L NSX250 H
S NSX400
H NSX100
N
F NSX160 L
F, N S NSX250
B
NSX100
NSX160
N, H
F
Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
Thermal-stress curves
Voltage 400/440 V AC (1) Voltage 660/690 V AC
Limited energy Limited energy
DB128401.eps
DB128402.eps
NS630bH NS1600bN
NS630bN NS800H NS630bH NS2000N
NS800N NS1000H NS800H NS2500N
NS1000N NS1250H NS1000H NS3200N
NS1250N NS1600H NS1250H
NS1600N NS1600H
NS630bN
NS800N
NS1000N
NS1000L NS1250N
NS630bL NS1600N
NS800L
NS630bLB NS630bL
NS800L NS630bLB
NS800LB NS800LB
NS1000L L
S L S NSX630
F N H NSX630 H
NSX400 NSX400
F, N
L
B F N H S L S NSX250
NSX250 N, H
NSX100 F NSX100
NSX160 NSX160
Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
E-4
Compact NS630b to 3200 Catalogue numbers
and order forms
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
Additional characteristics E-1
F-1
Catalogue numbers NS630b to NS1600 fixed
manuallyoperated
Complete device
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33460 33463
NS800 33466 33469
NS1000 33472 33475
NS1250 33478 33480
NS1600 33482 33484
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33461 33464
NS800 33467 33470
NS1000 33473 33476
NS1250 33479 33481
NS1600 33483 33485
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33462 33465
NS800 33468 33471
NS1000 33474 33477
Front-connected circuit breaker with Micrologic 5.0 control unit
Compact NS type N
DB128405.eps
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33546 33549
NS800 33552 33555
NS1000 33558 33561
NS1250 33564 33566
NS1600 33568 33570
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33547 33550
NS800 33553 33556
NS1000 33559 33562
NS1250 33565 33567
NS1600 33569 33571
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33548 33551
NS800 33554 33557
NS1000 33560 33563
Front-connected circuit breaker with Micrologic 6.0 A control unit
Compact NS type N
DB128403.eps
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33886 33888
NS800 33893 33896
NS1000 33909 33917
NS1250 33919 33923
NS1600 33925 33927
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33887 33889
NS800 33894 33901
NS1000 33916 33918
NS1250 33922 33924
NS1600 33926 33928
F-2
Catalogue numbers NS630b to NS1600 fixed
manuallyoperated
Complete device
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33223 33227
NS800 33233 33237
NS1000 33243 33247
NS1250 33253 33257
NS1600 33263 33267
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33228 33229
NS800 33238 33239
NS1000 33248 33249
NS1250 33258 33259
NS1600 33268 33269
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33497 33500
NS800 33498 33501
NS1000 33499 33502
Front-connected circuit breaker with Micrologic 5.0 A control unit
Compact NS type N
DB128403.eps
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33323 33327
NS800 33333 33337
NS1000 33343 33347
NS1250 33353 33357
NS1600 33363 33367
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33328 33329
NS800 33338 33339
NS1000 33348 33349
NS1250 33358 33359
NS1600 33368 33369
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33516 33519
NS800 33517 33520
NS1000 33518 33521
Fixed front connected Micrologic 2.0 E
Compact NS type N
3P 4P
NS630b 34400 34402
NS800 34404 34406
NS1000 34408 34410
NS1250 34412 34414
NS1600 34416 34418
Compact NS type H
3P 4P
NS630b 34401 34403
NS800 34405 34407
NS1000 34409 34411
NS1250 34413 34415
NS1600 34417 34419
Fixed front connected Micrologic 5.0 E
Compact NS type N
3P 4P
NS630b 34420 34422
NS800 34424 34426
NS1000 34428 34430
NS1250 34432 34434
NS1600 34436 34438
Compact NS type H
3P 4P
NS630b 34421 34423
NS800 34425 34427
NS1000 34429 34431
NS1250 34433 34435
NS1600 34437 34439
Front-connected switch-disconnector
3P 4P
DB128404.eps
Note: select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.
F-3
Catalogue numbers NS630b to NS1600 fixed
manuallyoperated
Device based on separate components
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33220 33224
NS800 33230 33234
NS1000 33240 33244
NS1250 33250 33254
NS1600 33260 33264
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33221 33225
NS800 33231 33235
NS1000 33241 33245
NS1250 33251 33255
NS1600 33261 33265
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33222 33226
NS800 33232 33236
NS1000 33242 33246
Compact NS type LB
Icu = 200 kA at 400/415 V 3P 4P
NS630b 48952 48955
NS800 48953 48956
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33505
Micrologic 5.0 A selective protection 33512
Micrologic 6.0 A selective + earth-fault protection 33513
Micrologic 7.0 A selective + earth-leakage protection 33514
"energy" E
3P/4P
Micrologic 2.0 E basic protection 33535
Micrologic 5.0 E selective protection 33537
Micrologic 6.0 E selective + earth-fault protection 33539
"power meter" P
3P/4P
(1) In case of an installation 3P + Neutral, please add ENVT Micrologic 5.0 P (1) selective protection 65290
device ref. 65317 (see page F-13). Micrologic 6.0 P (1) selective + earth-fault protection 65291
Micrologic 7.0 P selective + earth-leakage protection 65292
Basic switch-disconnector
Compact NS type NA
DB128408.eps
3P 4P
NS630b 33420 33421
NS800 33422 33423
NS1000 33424 33425
NS1250 33426 33427
NS1600 33428 33429
3P 4P
630-1000 A - NA/N/H Top 33598 33608
Bottom 33599 33609
1250 A - NA/N/H Top 33600 33610
630-1000 A - L Bottom 33601 33611
1600 A - NA/N/H Top 33602 33612
Bottom 33603 33613
Rear connection
3P 4P
Vertical NA/N/H/L/LB Top 33604 33614
Bottom 33605 33615
Horizontal Top 33606 33616
NA/N/H/L/LB Bottom 33607 33617
Note: to order a complete device, order:
b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector. b connections. b accessories (for the device, the connection, the control unit)
and communication option as required.
F-4
Catalogue numbers NS630b to NS1600 fixed
electricallyoperated
Device based on separate components
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33270 33274
NS800 33280 33284
NS1000 33290 33294
NS1250 33300 33304
NS1600 33310 33314
I ON
pus h
OOF F
pus h
dis charged
Compact NS type H
O OFF
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33271 33275
NS800 33281 33285
NS1000 33291 33295
NS1250 33301 33305
Note: the characteristics of the motor mechanism module NS1600 33311 33315
for electrical operation are specified separately by selecting Compact NS type L
a part number from the table at the bottom of this page. Icu = 150 kA at 220/415V 3P 4P
NS630b 33272 33276
NS800 33282 33286
NS1000 33292 33296
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33505
Micrologic 5.0 A selective protection 33512
Micrologic 6.0 A selective + earth-fault protection 33513
Micrologic 7.0 A selective + earth-leakage protection 33514
"energy" E
3P/4P
Micrologic 2.0 E basic protection 33535
Micrologic 5.0 E selective protection 33537
Micrologic 6.0E selective + earth-fault protection 33539
"power meter" P
3P/4P
(1) In case of an installation 3P + Neutral, please add ENVT Micrologic 5.0 P (1) selective protection 65290
device ref. 65317 (see page F-13). Micrologic 6.0 P (1) selective + earth-fault protection 65291
Micrologic 7.0 P selective + earth-leakage protection 65292
Basic switch-disconnector
Compact NS type NA
DB128411.eps
3P 4P
NS630b 33440 33441
NS800 33442 33443
NS1000 33444 33445
NS1250 33446 33447
NS1600 33448 33449
I ON
pus h
OOF F
pus h
dis charged
Note: the characteristics of the motor mechanism module for electrical operation are specified
O OFF
separately by selecting a part number from the table at the bottom of this page.
3P 4P
630-1000 A - NA/N/H Top 33598 33608
Bottom 33599 33609
1250 A - NA/N/H Top 33600 33610
630-1000 A - L Bottom 33601 33611
1600 A - NA/N/H Top 33602 33612
Bottom 33603 33613
Rear connection
Vertical NA/N/H/L Top 33604 33614
Bottom 33605 33615
Horizontal Top 33606 33616
NA/N/H/L Bottom 33607 33617
Motor mechanism module
AC 50/60 Hz DC
U 48 V Standard Communicating Standard Communicating
DB401828.eps
33689 (*)
33696 (*)
200/250 V 33693 (*)
33700 (*)
F-5
Catalogue numbers NS630b to NS1600 manually
operated withdrawable devices
Device based on separate components
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33320 33324
NS800 33330 33334
NS1000 33340 33344
NS1250 33350 33354
NS1600 33360 33364
Compact NS type H
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33321 33325
NS800 33331 33335
NS1000 33341 33345
NS1250 33351 33355
NS1600 33361 33365
Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33322 33326
NS800 33332 33336
NS1000 33342 33346
Compact NS type LB
Icu = 200 kA at 400/415 V 3P 4P
NS630b 48967 48971
NS800 48968 48972
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33525
Micrologic 5.0 A selective protection 33532
Micrologic 6.0 A selective + earth-fault protection 33533
Micrologic 7.0 A selective + earth-leakage protection 33534
"energy" E
3P/4P
Micrologic 2.0 E basic protection 33536
Micrologic 5.0 E selective protection 33538
Micrologic 6.0 E selective + earth-fault protection 33540
"power meter" P
3P/4P
(1) In case of an installation 3P + Neutral, please add ENVT Micrologic 5.0 P (1) selective protection 65293
device ref. 65316 (see page F-13). Micrologic 6.0 P (1) selective + earth-fault protection 65294
Micrologic 7.0 P selective + earth-leakage protection 65295
Basic switch-disconnector
Compact NS type NA
DB128414.eps
3P 4P
NS630b 33430 33431
NS800 33432 33433
NS1000 33434 33435
NS1250 33436 33437
NS1600 33438 33439
3P 4P
630-1250 A - NA/N/H 33722 33725
1600 A - NA/N/H 33723 33726
630/800 A - LB
630-1000 A - L
+ connection
3P 4P
Front connection
DB128416.eps
F-6
Catalogue numbers NS630b to NS1600 electrically
operated withdrawable devices
Device based on separate components
Icu = 50 kA at 220/415 V 3P 4P
NS630b 33370 33374
NS800 33380 33384
NS1000 33390 33394
NS1250 33400 33404
OOF F
pus h
pus h
I ON
NS1600 33410 33414
Compact NS type H
harged
dis c
O OF F
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33371 33375
NS800 33381 33385
NS1000 33391 33395
Note: the characteristics of the motor mechanism module for NS1250 33401 33405
electrical operation are specified separately by selecting a part NS1600 33411 33415
number from the table at the bottom of this page. Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33372 33376
NS800 33382 33386
NS1000 33392 33396
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33525
Micrologic 5.0 A selective protection 33532
Micrologic 6.0 A selective + earth-fault protection 33533
Micrologic 7.0 A selective + earth-leakage protection 33534
"energy" E
3P/4P
Micrologic 2.0 E basic protection 33536
Micrologic 5.0 E selective protection 33538
Micrologic 6.0 E selective + earth-fault protection 33540
"power meter" P
3P/4P
(1) In case of an installation 3P + Neutral, please add ENVT Micrologic 5.0 P (1) selective protection 65293
device ref. 65316 (see page F-13). Micrologic 6.0 P (1) selective + earth-fault protection 65294
Micrologic 7.0 P selective + earth-leakage protection 65295
Basic switch-disconnector
Compact NS type NA
DB128419.eps
3P 4P
NS630b 33450 33451
NS800 33452 33453
NS1000 33454 33455
NS1250 33456 33457
NS1600 33458 33459
I ON
pus h
O OF F
pus h
harged
dis c
O OF F
Note: the characteristics of the motor mechanism module for electrical operation are specified
separately by selecting a part number from the table at the bottom of this page.
Chassis and connections
Chassis
DB128415.eps
3P 4P
630-1250 A - NA/N/H 33722 33725
1600 A - NA/N/H 33723 33726
630-1000 A - L
+ connection
3P 4P
Front connection
DB128416.eps
33829 (*)
33836 (*)
200/250 V 33833 (*)
33840 (*)
4P (4 parts) 33641
4P 33629
Vertical-connection adapters
3P (3 parts) 33642
DB128422.eps
4P (4 parts) 33643
4P 33597
4P 33623 33623
Electrical auxiliaries
Indication contacts
6 A - 240 V Low level
DB128428.eps
DB128431.eps
F-8
Catalogue numbers Accessories for
NS630btoNS1600
withdrawable devices
4P (4 parts) 33643
Spreaders
3P (3 parts) 33622 33622
DB128427.eps
Chassis accessories
Auxiliary terminal shield (CB)
3P 33763
DB128434.eps
4P 33764
4P 33766
Electrical auxiliaries
OF ON/OFF indication contacts
6 A - 240 V Low level
DB128436.eps
F-9
Catalogue numbers Accessories for
NS630btoNS1600
withdrawable devices
Chassis locking
Keylocking in disconnected position
By Profalux keylocks
DB128440.eps
Installation accessories
Escutcheon
33857
DB128430.eps
Blanking plate
33858
DB128432.eps
Spare parts
Toggle extension 46996
DB128447.eps
F-10
Catalogue numbers Accessories for
NS630btoNS1600 fixed and
withdrawable devices
I on
Red handle and yellow front 33864
tripp
ed
Conversion accessory CNOMO 33866
Locking by keylocks Ronis Profalux
reset
0 OFF
I on
Red handle and yellow front 33879
tripp
reset
ed
Telescopic (for chassis-mounted devices) 33880
0 OFF
I
ON
tripped
reset
OFF
0
9
0039
F-11
Catalogue numbers Accessories for
NS630b to 1600 fixed and
withdrawable devices
Mechanical interlocking
Mechanical interlocking for source changeover
Interlocking using connecting rods for Compact electrically operated devices
Complete assembly with 2 adaptation fixtures + rods
DB128465.eps
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-12
Catalogue numbers Communication option for
NS630btoNS1600 fixed and
withdrawable devices
Communication options
IFE Ethernet interface LV434010
DB417415.eps
for LV breaker
Ethernet interface LV434011
for LV breakers and gateway
Ir
.7
long
.8 .9
time
.95
tr
(s)
2
1
4
8 12
16
20
alarm
48/60 V DC 54441
100/125 V DC 54442
110/130 V AC 54443
200/240 V AC 54444
380/415 V AC 54445
Test equipment
Mini test kit
Hand held test kit (HHTK) 33594
DB128463.eps
F-13
Catalogue numbers NS1600b to NS3200 fixed,
front-connected, manually
operated device
Circuit breaker
Compact NS type N
DB128467.eps
3P 4P
NS1600b 34024 34025
NS2000 34027 34028
NS2500 34030 34031
NS3200 34033 34034
OFF
OFF
F-14
Catalogue numbers Accessories for
NS1600btoNS3200
Communication option
IFE Ethernet interface LV434010
DB128462.eps
for LV breaker
Ethernet interface LV434011
for LV breakers and gateway
IFM Modbus-SL interface module TRV00210
I/O application module LV434063
OFF
COM (BCM-ULP)
OFF
33986
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 Ir
@6
48/60 V DC 54441
100/125 V DC 54442
110/130 V AC 54443
200/240 V AC 54444
380/415 V AC 54445
Test equipment
Mini test kit
Hand held test kit (HHTK) 33594
DB128463.eps
Installation accessories
Escutcheon
33929
DB128444.eps
F-15
Order form Order form:
Compact NS630b to NS3200
Circuit breakers and switch-disconnectors
F-16
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixedcircuitbreaker
Connection
3P 4P
630/1000 A - N Top 33598 33608
Bottom 33599 33609
1250 A - N Top 33600 33610
630-1000 A - L Bottom 33601 33611
630/800 A - LB
1600 A - N Top 33602 33612
Bottom 33603 33613
Rear connection / Replacement kit (3 or 4 parts)
3P 4P
DB401442.eps
Connection accessories
Bare-cable connectors + 1 connector shield for 4 cables (240 mm)
3P 33640
DB128420.eps
4P 33641
Installation manual 33148
4P 33629
4P 33643
Installation manual 33148
Cable lug adapters / Replacement kit (3 or 4 parts)
3P 33644
DB128423.eps
4P 33645
Installation manual 33148
4P 33597
Installation manual 33148
Brackets for mounting on a horizontal surface (2 parts)
3P/4P 64908
DB101032.eps
4P 33623
Installation manual 33148
Cable lug kits / Replacement kit (6 or 8 parts)
240 mm 3P (6 lug kit) 33013
DB128424.eps
F-17
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixed circuit breaker
Electrical auxiliaries
Electrical auxiliaries
Indication contact / 1 part
6 A - 240 V Low level
DB128428.eps
F-18
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixed circuit breaker
Installation accessories
F-19
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixed circuit breaker
Micrologic control unit, external sensor
alarm
Battery + cover
Battery (1 part) 33593
DB128353.eps
Communication option
IFE Ethernet interface for LV breaker LV434010
DB417415.eps
48-60 V DC 54441
100-125 V DC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
Test equipments / 1 part
Hand held test kit (HHTK) 33594
DB128464.eps
F-20
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixed circuit breaker
Locking and accessories
9
0039
Installation manual 47103
F-21
Catalogue numbers:
spare parts
Spare parts: NS630b to NS1600
fixed and withdrawable circuit
breaker
Mechanical interlocking for source
changeover
Mechanical interlocking for source changeover
Interlocking using connecting rods for Compact electrically operated devices
Complete assembly with 2 adaptation fixtures + rods
DB128465.eps
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-22
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 withdrawable circuit
breaker
Connection
Connection
3P 4P
DB128416.eps
DB401444.eps
Connection accessories
Vertical connection adapters for front-connected chassis / Replacement kit (3 or 4 parts)
3P 33642
DB128422.eps
4P 33643
Installation manual 33149
4P 33645
Installation manual 33149
4P 33623
Installation manual 33149
4P 33764
Installation manual 33149
4P 33766
Installation manual 47104
Clusters
1 disconnecting contact cluster for chassis (see table below) (1 part) 64906
DB401446.eps
DB418007.eps
F-23
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 withdrawable circuit
breaker
Electrical auxiliaries
Electrical auxiliaries
SD trip indication contact for manually operated devices / 1 part
6 A - 240 V Low level
DB128436.eps
3 wires. 6 wires.
F-24
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 withdrawable circuit
breaker
Installation accessories
Installation accessories
Escutcheon / 1 part
33857
DB128430.eps
F-25
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 withdrawable circuit
breaker
Micrologic control unit, external sensor
Replacement parts for Micrologic control units
Long-time rating plug (limits setting range for higher accuracy) / 1 part
Standard 0.4 at 1 x Ir 33542
DB128458.eps
alarm
Communication option
IFE Ethernet interface for LV breaker LV434010
DB417415.eps
48-60 V DC 54441
100-125 V DC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
Test equipments / 1 part
Hand held test kit (HHTK) 33594
DB128464.eps
F-26
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 withdrawable circuit
breaker
Locking and accessories
Locking for manually operated devices
Removable toggle locking system / 1 part
Locking by 3 padlocks 44936
DB128448.eps
9
0039
Installation manual 47103
F-27
Catalogue numbers: Spare parts: NS630b to NS1600
spare parts withdrawable circuit breaker
Chassis locking and accessories
Mechanical interlocking for source
changeover
Chassis locking
Keylocking in disconnected position / 1 part
By Profalux keylocks
DB128440.eps
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-28
Catalogue numbers: Spare parts: NS630b to
spare parts
NS1600 fixed or withdrawable
circuit breaker
Instructions
Instructions
Chassis accessories 47104
Circuit breaker accessories Manual 33148
Electrical 33149
Fixed and drawout circuit breaker Manual 33148
Electrical 33149
NS630b user manual French 33159
English 33160
Micrologic user manual 20/50 (French) 33076
20/50 (English) 33077
2A/7A (French) 33079
2A/7A (English) 33080
2E/6E (French) 33079
2E/6E (English) 33080
5P/7P (French) 33082
5P/7P (English) 33083
Modbus communication notice for manual 33088
F-29
Catalogue numbers:
spare parts
Spare parts: Communication bus
accessories, monitoring and
control, ethernet gateway
Communication options
IFE Ethernet interface for LV breaker LV434010
DB417415.eps
F-30
Catalogue numbers: Spare parts:
spare parts
Compact NS1600b to 3200
Connection, locking and installation
accessories
Optional vertical connection adaptor / Replacement kit (3 or 4 parts)
1600/2500/3200 A 3P 33975
DB128323.eps
4P 33976
Installation accessories
Escutcheon / 1 part
33929
DB128444.eps
OFF
OFF
F-31
Catalogue numbers: Spare parts:
spare parts
Compact NS1600b to 3200
Micrologic control unit, external sensor
alarm
33543
8 12
External sensors
External sensor for neutral + earth-fault protection (TCE) / 1 part
CT rating: 1000/4000 A 34036
DB128459.eps
48-60 V DC 54441
100-125 V DC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
Test equipments / 1 part
Hand held test kit (HHTK) 33594
DB128464.eps
F-32
0