NIT & NS

HRCII/CANADIAN FUSES

canadian HRCII fuses


The Ferraz Shawmut Canadian NIT fuses
series has offset contacts with British
standard (BS88) dimensions. The NS
series has diagonally offset contacts with
British standard dimensions. Neither fuse
is dimensionally interchangeable with
other North American fuses. They are for
short-circuit protection only, in motor
controllers, for example, where overload
protection is provided by an overload
relay.

HIGHLIGHTS: APPLICATIONS: Ratings Approvals


➤ NIT ➤ HRCII-MISC
➤ ‰BS88 Dimensions ➤ ‰Motor Circuits
AC: 2 to 20A
550VAC, 80kA I.R.
➤ IEC269-2-1 F
DC: 2 to 20A
250VDC, 40kA I.R.
➤ NS
AC: 2 to 32A
440VAC, 80kA I.R.
DC: 2 to 32A
250VDC, 40kA I.R.

NIT – Catalog Numbers & Dimensions


AMPERE CATALOG DIMENSIONS in mm
RATING NUMBER A B D E F G H K
2 NIT2
4 NIT4
6 NIT6 36.5 14.1 55.6 11.1 0.80 44.5 4.70 14.3
10 NIT10
16 NIT16
20 NIT20

NS – Catalog Numbers & Dimensions


NIT & NS – I2t at 80kA
AMPERE CATALOG DIMENSIONS in mm
AMPERE
2
I t (A Secs.)
2 RATING NUMBER A B D E F N
2 NS2
NUMBER PRE-ARC @ 415V @ 550V
4 NS4
2 2.2 5.4 31 6 NS6
4 7.2 18 75 10 NS10 35.5 14.5 62.0 11.0 0.80 3.60
6 22 60 400 16 NS16
10 100 280 1000 20 NS20
16 300 850 2000 25 NS25
20 540 1000 2500 32 NS32

F 37
NIT & NS HRCII/CANADIAN FUSES

Peak Let-Thru Current Data – NIT2-20, NS2-32

Maximum Instantaneous Peak Let-Thru Amperes

Available Current in RMS Symmetrical Amperes

Melting Time - Current Data – NIT2-20, NS2-32


Time in Seconds

Current in Amperes