Established 1855
This guide is intended for reference use only. All final details of design and construction must meet the requirements of federal,
state, and local codes. In cases where plan approval is required, such approval must be obtained from the authority having
jurisdiction before any work is performed.
The equipment presented in the Guide applies only to shop fabricated tanks.
Morrison Bros. Co.
Established 1855
Refer
eferences
erences
NFPA 30 Flammable and Combustible Liquids Code 1996 Edition
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269-9904
API Std 2000 Venting Atmospheric & Low Pressure Storage Tanks
American Petroleum Institute - Fourth Edition, October 1992
1120 L Street, Northwest, Washington DC 20005 Order #822-20000
PEI RP200 Recommended Practices for Installation of Aboveground Storage Systems for Motor
Vehicle Fueling
Petroleum Equipment Institute, P.O. Box 2380, Tulsa, OK 74101, Tel (918) 494-9696
Morrison Bros. Co. P.O. Box 238, Dubuque, IA 52004-0238, Tel (563) 583-5701
Background Information
T he Morrison Venting Guide was created to assist in equipment selection for above-
ground storage tanks. Examples on the next two pages illustrate a vent selection
process. It is best to work through the examples before attempting to use any of the
tables in this book.
Tables include examples for standard sized tanks. The venting capacity charts and
wetted area tables were taken directly from NFPA 30 and UL 142.
The vent selection chapter includes venting capacities of specific Morrison vents. This
data was obtained from results of laboratory testing and engineering calculations.
Catalog pages of the Morrison equipment follow the vent capacity chart.
Definitions
Emergency Venting Venting sufficient to and emergency vents shall be enough to prevent
relieve excessive internal pressure in storage tanks rupture of the shell or bottom of the tank if vertical, or
caused by exposure fires. Venting rate may exceed of the shell or heads if horizontal.
requirements of normal atmospheric and product
transfer effects. In such cases, the construction of Wetted Area Exposed surface or shell area
the tank will determine if additional venting capacity of a tank used in determining the venting require-
must be provided. ments needed for that size tank in event of an
exposure fire. In a horizontal tank, the wetted area
Atmospheric Tank A storage tank that is calculated as 75% of the exposed surface area.
has been designed to operate at pressures from In a vertical tank, the wetted area is calculated as the
atmospheric through 1.0 PSIG (760 mm Hg through first 30 ft. above grade of the exposed shell area of
812 mm Hg) measured at the top of the tank (NFPA the tank.
30 Pg. 30-8). Pressure not to exceed 1.0 PSIG
under normal operation, and 2.5 PSIG under emer- CFH Abbreviation for Cubic Feet of Free Air per
gency conditions (PEI RP-200). Hour used to quantify or measure the airflow and
degree of pressure relief for venting calculations.
Pressure Relieving Devices Defined
in NFPA 30 2-3.6.4, where entire dependence for Vent Capacity The maximum rate of airflow
emergency relief is placed upon pressure relieving (CFH) recorded under test conditions at a maximum
devices, the total venting capacity of both normal pressure of 2.5 PSI for specific sized emergency
vents. This capacity rating is often required to be
featured as a permanent label on the vent itself.
TANK CAPACITY
10,000 gallons
TANK SIZE
10 ft. dia x 17 ft. long
38,000 = x x
100 (518-500) x = 6,840 CFH
TANK CAPACITY
10,000 gallons
TANK SIZE
10 ft. dia x 17 ft. high
38,000 = x x
100 (534-500) x = 12,920 CFH
TANK CAPACITY
10,000 gallons
TANK SIZE
274"L x 130"W x 65"H
(22'-10"L x 10'-10" W x 5'-5"H)
STEP 2 Calculate Wetted Area Total required venting capacity for this tank example was
determined to be 396,320 CFH. Normal venting and emergency
If the tank size is NOT on the precalculated chart on page 7, venting may be combined to reach this total. Morrison Vent
wetted area can be calculated. For Horizontal Rectangular Capacities are listed on page 12. Since the 6" Emergency Vent
Tanks, wetted area = exposed shell area excluding the top (246,130 CFH) can not provide enough additional capacity to
surface of the tank. meet the requirement, an 8" Emergency Vent (462,000 CFH) is
For a 274"L x 130"W x 65"H tank: selected. In specifying pressure settings, it is recommended
that the Emergency Vent NOT be less than the normal vent.
Wetted area = (L x W) + 2(L x H) + 2(W x H) Therefore, the vent specification for this example is as follows:
144 Normal Vent - 2" Fig 548 ........................... 20,200 CFH
(8 oz pressure - 1 oz vacuum)
L = length, W = width, H = height
Emergency Vent - 8" Fig 244 ................... 462,000 CFH
(274 x 130) + 2(274 x 65) + 2(130 x 65) (16 oz pressure)
144 Total Venting Provided ............................. 482,200 CFH
36,000 = x x
100 (612 - 600) x = 4,320 CFH
TANK
WETTED REQ'D VENT EMERGENCY
CAPACITY LENGTH WIDTH HEIGHT AREA CAPACITY VENT SIZE
(Gallons) (Ft-In) (Ft-In) (Ft-In) (Sq Ft) (CFH) (Inches)
125 6'-8" 2'-9" 1'-0" 37 38,950 3
186 2'-8" 2'-8" 3'-6" 44 46,340 3
250 4'-4" 4'-0" 1'-11" 49 51,640 3
250 6'-8" 2'-9" 1'-11" 54 56,900 3
500 7'-6" 3'-0" 3'-0" 86 90,560 4
500 10'-0" 3'-6" 2'-0" 89 93,740 4
1,000 9'-8" 4'-8" 3'-0" 131 137,550 6
1,000 10'-0" 4'-7" 3'-0" 133 139,650 6
2,000 10'-2" 6'-11" 3'-10" 201 211,560 6
2,000 10'-8" 6'-4" 4'-0" 204 213,240 6
2,500 10'-2" 6'-11" 4'-9" 233 229,480 6
3,000 8'-6" 6'-10" 7'-2" 278 253,560 6H
3,000 13'-9" 5'-5" 5'-5" 282 255,640 6H
4,000 11'-4" 6'-10" 7'-2" 338 282,480 6H
4,000 18'-2" 5'-5" 5'-5" 354 289,920 6H
5,000 22'-9" 5'-5" 5'-5" 428 323,760 8
6,000 13'-8" 10'-10" 5'-5" 413 317,460 8
6,000 16'-5" 6'-10" 7'-2" 445 330,900 8
6,000 27'-4" 5'-5" 5'-5" 503 355,140 8
8,000 18'-2" 10'-10" 5'-5" 511 358,180 8
8,000 21'-11" 6'-10" 7'-2" 562 377,560 8
10,000 22'-10" 10'-10" 5'-5" 612 396,320 8
10,000 27'-5" 6'-10" 7'-2" 678 420,080 8
12,000 27'-4" 10'-10" 5'-5" 710 431,400 8
12,000 32'-11" 6'-10" 7'-2" 795 460,300 8 FL
TABLE 1
Tank 3 Ft 4 Ft 5 Ft 6 Ft 7 Ft 8 Ft 9 Ft 10 Ft 11 Ft 12 Ft Tank 3 Ft 4 Ft 5 Ft 6 Ft 7 Ft 8 Ft 9 Ft 10 Ft 11 Ft 12 Ft
Diameter Diameter
Tank Approximate Wetted Area of Tanks With Flat Heads, Tank Approximate Wetted Area of Tanks With Flat Heads,
Length Square Feet Length Square Feet
3 Ft 32 38 Ft 685 791 902 1013 1129 1244
4 Ft 39 55 39 Ft 701 810 923 1036 1155 1272
5 Ft 46 65 88 40 Ft 718 828 944 1060 1181 1301
6 Ft 53 74 100 128 41 Ft 734 847 966 1083 1207 1329
7 Ft 60 84 112 142 173 42 Ft 751 866 987 1107 1233 1357
8 Ft 67 93 124 156 190 226 43 Ft 767 885 1008 1130 1259 1385
9 Ft 74 102 136 170 206 245 286 44 Ft 904 1029 1154 1284 1414
10 Ft 81 112 147 184 223 264 308 353 45 Ft 923 1051 1178 1310 1442
11 Ft 88 121 159 198 239 283 329 377 428 46 Ft 941 1072 1201 1336 1470
12 Ft 95 131 171 213 256 301 350 400 454 509 47 Ft 960 1093 1225 1362 1498
13 Ft 102 140 183 227 272 320 371 424 480 537 48 Ft 979 1114 1248 1388 1527
14 Ft 109 150 194 241 289 339 393 447 506 565 49 Ft 998 1135 1272 1414 1555
15 Ft 116 159 206 255 305 358 414 471 532 594 50 Ft 1157 1295 1440 1583
16 Ft 123 169 218 269 322 377 435 495 558 622 51 Ft 1178 1319 1466 1612
17 Ft 130 178 230 283 338 395 456 518 584 650 52 Ft 1199 1342 1492 1640
18 Ft 137 188 242 298 355 414 477 542 610 678 53 Ft 1220 1366 1518 1668
19 Ft 197 253 312 371 433 499 565 636 707 54 Ft 1246 1389 1544 1696
20 Ft 206 265 326 388 452 520 589 662 735 55 Ft 1263 1413 1570 1725
21 Ft 216 277 340 404 471 541 612 688 763 56 Ft 1437 1593 1753
22 Ft 225 289 354 421 490 562 636 714 792 57 Ft 1460 1622 1781
23 Ft 235 300 368 437 508 584 659 740 820 58 Ft 1484 1648 1809
24 Ft 244 312 383 454 527 605 683 765 848 59 Ft 1507 1674 1839
25 Ft 324 397 470 546 626 706 791 876 60 Ft 1531 1700 1866
26 Ft 336 411 487 565 647 730 817 905 61 Ft 1726 1894
27 Ft 347 425 503 584 668 754 843 933 62 Ft 1752 1923
28 Ft 359 440 520 603 690 777 869 961 63 Ft 1778 1951
29 Ft 371 454 536 621 711 801 895 989 64 Ft 1803 1979
30 Ft 383 468 553 640 732 824 921 1018 65 Ft 1829 2007
31 Ft 395 482 569 659 753 848 947 1046 66 Ft 1855 2036
32 Ft 496 586 678 775 871 973 1074 67 Ft 2064
33 Ft 510 602 697 796 895 999 1103 68 Ft 2092
34 Ft 524 619 715 817 918 1025 1131 69 Ft 2120
35 Ft 539 635 734 838 942 1051 1159 70 Ft 2149
36 Ft 553 652 753 860 966 1077 1187 71 Ft 2177
37 Ft 567 668 772 881 989 1103 1216 72 Ft 2205
TABLE 2
Tank 3 Ft 4 Ft 5 Ft 6 Ft 7 Ft 8 Ft 9 Ft 10 Ft 11 Ft 12 Ft
Diameter
Tank
Wetted Area, Square Feet
Length
3 Ft 28
4 Ft 38 50
5 Ft 47 63 79
6 Ft 56 76 94 113
7 Ft 66 88 110 132 154
8 Ft 75 101 127 151 176 201
9 Ft 85 113 141 170 198 226 255
10 Ft 94 126 157 189 220 251 283 314
11 Ft 103 139 173 208 242 276 311 345 381
12 Ft 113 151 188 227 264 301 340 377 415 452
13 Ft 164 204 246 286 326 368 408 450 490
14 Ft 176 220 265 308 351 396 440 484 528
15 Ft 189 236 284 330 377 424 471 519 566
16 Ft 202 251 302 352 402 453 502 554 603
17 Ft 267 321 374 427 481 534 588 641
18 Ft 283 340 396 452 510 565 623 679
19 Ft 298 359 418 477 538 597 657 716
20 Ft 314 378 440 502 566 628 692 754
21 Ft 397 462 527 594 659 727 792
22 Ft 416 484 552 623 691 761 829
23 Ft 435 506 577 651 722 796 867
24 Ft 454 528 602 679 757 830 905
25 Ft 550 628 708 785 865 943
26 Ft 572 653 736 816 900 980
27 Ft 594 678 764 848 934 1018
28 Ft 616 703 792 879 969 1056
29 Ft 728 821 911 1003 1093
30 Ft 753 849 942 1038 1131
NFPA 30 1996
2-3.5.2 Normal vents shall be sized to be at least as large as the
filling or withdrawal connection, whichever is larger, but in no case
less than 1-1/4 in. (3 cm) nominal inside diameter.
2" 148ALT P res s ure Vacuum Vent 8 14,200 T es ted at Iowa S tate Univ. by P . Kavanagh, 1960
2" 148ALT P res s ure Vacuum Vent 16 10,500 T es ted at Iowa S tate Univ. by P . Kavanagh, 1960
2" 351S F lame Arres ter 22,000 T es ted at Ohio S tate Univ. by O. E . B uxton Jr. 1967
2" 351S /548-748 F lame Arres ter/Vent 2 15,500 B as ed on IS U T es t of 2" 351S /548-748 - 8 oz by Kavanagh, 1990
2" 351S /548-748 F lame Arres ter/Vent 4 15,500 B as ed on IS U T es t of 2" 351S /548-748 - 8 oz by Kavanagh, 1990
2" 351S /548-748 F lame Arres ter/Vent 6 15,500 B as ed on IS U T es t of 2" 351S /548-748 - 8 oz by Kavanagh, 1990
2" 351S /548-748 F lame Arres ter/Vent 8 15,500 T es ted at Iowa S tate Univ. by P . Kavanagh, 1990
2" 351S /548-748 F lame Arres ter/Vent 12 13,000 B as ed on IS U T es t of 2" 351S /548-748 - 16 oz by Kavanagh, 1990
2" 351S /548-748 F lame Arres ter/Vent 16 13,000 T es ted at Iowa S tate Univ. by P . Kavanagh, 1990
2" 354 Updraft Vent 27,650 T es ted at Univ. Wis cons in P latteville by L. Lee, 1988
3" 354 Updraft Vent 59,000 T es ted at Univ. Wis cons in P latteville by L. Lee, 1996
4" 354 Updraft Vent 116,900 T es ted at Continental Dis c Corp, 1997
2" 548-748 P res s ure Vacuum Vent 2 20,200 B as ed on IS U T es t of 2" 548 - 8 oz by Kavanagh, 1960
2" 548-748 P res s ure Vacuum Vent 4 20,200 B as ed on IS U T es t of 2" 548 - 8 oz by Kavanagh, 1960
2" 548-748 P res s ure Vacuum Vent 6 20,200 B as ed on IS U T es t of 2" 548 - 8 oz by Kavanagh, 1960
2" 548-748 P res s ure Vacuum Vent 8 20,200 T es ted at Iowa S tate Univ. by P . Kavanagh, 1960
2" 548-748 P res s ure Vacuum Vent 12 18,600 Approx. Calculated C.F .H .
2" 548-748 P res s ure Vacuum Vent 16 18,000 T es ted at Iowa S tate Univ. by P . Kavanagh, 1960
2" 749 P res s ure Vacuum Vent 8 8,500 T es ted at Univ. Wis cons in P latteville by L. Lee, 1988
2" 749 P res s ure Vacuum Vent 12 8,500 T es ted at Univ. Wis cons in P latteville by L. Lee, 1988
2" 749 CR B P res s ure Vacuum Vent 1.70 11,000 T es ted at Univ. Wis cons in P latteville by L. Lee, 1996
3" 548 P res s ure Vacuum Vent 2 43,000 B as ed on IS U T es t of 3" 548 - 8 oz by Kavanagh, 1990
3" 548 P res s ure Vacuum Vent 4 43,000 B as ed on IS U T es t of 3" 548 - 8 oz by Kavanagh, 1990
3' 548 P res s ure Vacuum Vent 6 43,000 B as ed on IS U T es t of 3" 548 - 8 oz by Kavanagh, 1990
3" 548 P res s ure Vacuum Vent 8 43,000 T es ted at Iowa S tate Univers ity by P . Kavanagh, 1990
3" 548 P res s ure Vacuum Vent 12 40,000 B as ed on IS U T es t of 3" 548 - 16 oz by P . Kavanagh, 1990
3" 548 P res s ure Vacuum Vent 16 40,000 T es ted at Iowa S tate Univers ity by P . Kavanagh, 1990
3" 244 S eries E mergency Vent 8 59,900 T es ted at Continental Dis c Corp, 1997
4" 244 S eries E mergency Vent 8 119,750 B as ed on Continental Dis c Corp T es t of 4" 16 oz 244, 1997
4" 244 S eries E mergency Vent 12 119,750 B as ed on Continental Dis c Corp T es t of 4" 16 oz 244, 1997
4" 244 S eries E mergency Vent 16 119,750 T es ted at Continental Dis c Corp, 1997
6" 143 P res s ure Vacuum Vent 8 246,130 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
6" 143 P res s ure Vacuum Vent 10 246,130 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
6" 143 P res s ure Vacuum Vent 16 246,130 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
6" 244 S eries E mergency Vent 8 246,130 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
6" 244 S eries E mergency Vent 10 246,130 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
6" 244 S eries E mergency Vent 16 246,130 T es ted at Continental Dis c Corp, 1997
6" 244H S eries E mergency Vent 8 298,750 B as ed on Continental Dis c Corp T es t of 6" 16 oz 244, 1997
8" 143 P res s ure Vacuum Vent 8 462,000 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
8" 143 P res s ure Vacuum Vent 16 462,000 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
8" 143A F lngd P res s ure Vacuum Vent 8 509,550 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
8" 143A F lngd P res s ure Vacuum Vent 16 509,550 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
8" 244M Male E mergency Vent 8 453,300 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
8" 244M Male E mergency Vent 16 453,300 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
8" 244 F emale E mergency Vent 8 462,000 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
8" 244 F emale E mergency Vent 16 462,000 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
8" 244F F langed E mergency Vent 8 509,550 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
8" 244F F langed E mergency Vent 16 509,550 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
10" 143A F lngd P res s ure Vacuum Vent 2.5 808,350 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
10" 143A F lngd P res s ure Vacuum Vent 8 808,350 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
10" 143A F lngd P res s ure Vacuum Vent 16 808,350 B as ed on UL Calc from Cont. Dis c Corp. T es t of 244 S eries , 1997
10" 244F S eries F langed E mergency Vent 2.5 808,350 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
10" 244F S eries F langed E mergency Vent 8 808,350 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
10" 244F S eries F langed E mergency Vent 16 808,350 UL Calc bas ed on Continental Dis c Corp. T es t of 244 S eries , 1997
2" 922 Vent/Overfill Alarm 8 24,656 T es ted at Continental Dis c Corp, 1997
1. 2" Fig. 548 - 4 oz P ............................ 20,200 8. 3" Fig. 548 - 4 oz P ............................ 43,000
4" Fig. 244 - 8 oz P ........................ 119,750 4" Fig. 244 - 8 oz P ........................ 119,750
139,950 162,750
2. 2" Fig. 548 - 8 oz P ............................ 20,200 9. 3" Fig. 548 - 8 oz P ............................ 43,000
6" Fig. 244 - 16 oz P ...................... 246,130 6" Fig. 244 - 16 oz P ...................... 246,130
266,330 289,130
3. 2" Fig. 548 - 8 oz P ............................ 20,200 10. 3" Fig. 548 - 8 oz P ............................ 43,000
8" Fig. 244 - 16 oz P ...................... 462,000 8" Fig. 244 - 16 oz P ...................... 462,000
482,200 505,000
4. 2" Fig. 548 - 8 oz P ............................ 20,200 11. 3" Fig. 548 - 8 oz P ............................ 43,000
10" Fig. 244 - 16 oz P ...................... 808,350 10" Fig. 244F - 16 oz P .................... 808,350
828,550 851,350
5. 2" Fig. 548 - 8 oz P ............................ 20,200 12. 3" Fig. 548 - 8 oz P ............................ 43,000
10" Fig. 244F - 8 oz P ...................... 808,350 10" Fig. 244F - 8 oz P ...................... 808,350
828,550 851,350
6. 2" Fig. 548 - 8 oz P ............................ 20,200 13. 3" Fig. 548 - 8 oz P ............................ 43,000
10" Fig. 244F - 2.5 oz P ................... 808,350 10" Fig. 244F - 2.5 oz P ................... 808,350
828,550 851,350
7. 2" Fig. 548 - 8 oz P ............................ 20,200 14. 3" Fig. 548 - 8 oz P ............................ 43,000
2" Fig. 922 - 8 oz P .......................... 24,656 2" Fig. 922 - 8 oz P .......................... 24,656
44,856 67,650
Emergency Vent
Emergency vent (pressure relief
only) used on aboveground
storage tanks, as a code require-
ment that helps prevent the tanks
from becoming over-pressurized
and rupturing if exposed to fire. Fig.244 Fig.244F
UL listed. Fig.244M
WARNING! WARNING!
The 244 emergency vent is for emergency pressure
The 244 emergency vent must be properly sized and
relief only and must be used in conjunction with
selected for each specific tank application in order to
a normal vent or pressure vacuum vent such
meet the proper venting capacity requirements.
as a Morrison Fig. 354, 548, 748, or 749.
Description
The 244 emergency vent consists of a body and cover that Material and Configuration Options
moves up and down on a center pin. Pressure inside the 1. Aluminum Body or Iron Bodysuffix (I) indicates iron.
tank forces the cover to lift up off the vent seat, allowing
2. Metal-to-Metal Seat (brass) or Soft Seat (Viton)suffix
air to exhaust. The center pin guides the movement. When
(O) indicates o-ring.
pressure falls the cover lowers back down onto seat and
the vent is automatically reset. 3. Male Threads/Female Threads/Flanged Mounting
Connectionsuffix (M) indicates male, and suffix (F)
Code Compliance indicates flanged.
When properly sized for the tank, this vent will conform to 4. Opening Pressure Settingsettings indicated are
the requirements of NFPA 30, 30A, UL 142, UL 2244, API approximate.
2000, and PEI RP200.
Emergency vent should be set higher than the
normal vent so the normal vent operates first.
Aluminum Body Style(O) indicates Viton o-ring seat
Opening 5. Screened Opening(all 4" and 6", and 8" female
Pressure Ship Venting Mounting threaded body only) specify "WITH SCREEN", #3 mesh
Fig. No. Size Setting Weight Capacity Connection stainless steel screen used for theft control. Screen is
(oz/sq in) (lbs) (CFH)
(@ 2.5 PSI)
NOT intended to function as a flame arrester.
244 &
244O 4" 8.0 10.65 119,750 Female NPT Use 16 oz. o-ring to comply with pressure decay test.
12.0 16.00 119,750 Female NPT Contact factory for assistance.
16.0 21.00 119,750 Female NPT
6" 8.0 15.50 246,130 Female NPT Iron Body Style(O) indicates Viton o-ring seat
10.0 21.50 246,130 Female NPT
16.0 33.15 246,130 Female NPT Opening
8" 8.0 34.70 462,000 Female NPT Pressure Ship Venting Mounting
16.0 68.00 462,000 Female NPT Fig. No. Size Setting Weight Capacity Connection
244& (oz/sq in) (lbs) (CFH)
244OF 8" 8.0 387.50 509,550 Flanged (@ 2.5 PSI)
16.0 71.50 509,550 Flanged 244I &
10" 2.5 32.00 808,350 Flanged 244OI 4" 8.0 13.65 119,750 Female NPT
8.0 71.00 808,350 Flanged 12.0 19.00 119,750 Female NPT
16.0 125.00 808,350 Flanged 16.0 24.00 119,750 Female NPT
6" 8.0 20.63 246,130 Female NPT
244M & (3" OM only) 10.0 26.63 246,130 Female NPT
244OM 3" 8.0 5.75 59,900 Male NPT 16.0 38.28 246,130 Female NPT
8" 8.0 44.33 462,000 Female NPT
4" 8.0 11.55 119,750 Male NPT 16.0 77.63 462,000 Female NPT
12.0 16.30 119,750 Male NPT
16.0 21.25 119,750 Male NPT 244MI & (3" OMI only)
6" 8.0 19.45 246,130 Male NPT 244OMI 3" 8.0 8.00 59,900 Male NPT
10.0 24.00 246,130 Male NPT 4" 8.0 16.36 119,750 Male NPT
16.0 35.00 246,130 Male NPT 12.0 21.11 119,750 Male NPT
8" 8.0 34.00 453,300 Male NPT 16.0 26.06 119,750 Male NPT
16.0 68.00 453,300 Male NPT 6" 8.0 27.76 246,130 Male NPT
10.0 32.31 246,130 Male NPT
244OH 6" 8.0 21.50 298,750 Female NPT 16.0 43.31 246,130 Male NPT
16.0 41.40 298,750 Female NPT 8" 8.0 34.63 453,300 Male NPT
16.0 75.36 453,300 Male NPT
244OMH 6" 8.0 23.00 298,750 Male NPT
16.0 42.9 298,750 Male NPT
Pressure/Vacuum
Emergency Vent
Emergency vent with both
pressure and vacuum relief for
use on aboveground storage
tanks. Pressure relief is handled
in same manner as with the
Morrison Fig. 244. Emergency
vacuum relief can be utilized as
a backup to the normal vent.
6" Fig. 143 8" Fig. 143 8"/10" Fig. 143A
Opening pressure and vacuum
settings are approximate. Opening
Pressure Ship Venting Mounting Vacuum
Construction Details Fig. No. Size Setting Weight Capacity Connection Setting
(oz/in2) (lbs) (CFH) (oz/in2)
Bodyaluminum (@ 2.5 PSI)
Covercast iron (except 10"2.5 oz 143A is 143 6" 8.0 22.50 246,130 Female NPT 1.0
aluminum) 16.0 35.00 246,130 Female NPT 1.0
VacuumAssembly and Seat Ringbrass
Vacuum Screentype 304 stainless steel 8" 8.0 37.00 462,000 Female NPT 1.0
16.0 69.00 462,000 Female NPT 1.0
NOTEThe 143 and 143A emergency vents
should always be used in conjunction with a 143A 8" 8.0 44.00 509,550 Flanged 1.0
16.0 74.00 509,550 Flanged 1.0
"normal vent" such as Morrison Fig. 548 or 548A.
10" 8.0 84.00 808,350 Flanged 1.0
16.0 124.00 808,350 Flanged 1.0
WARNING!
WARNING!
The 244 and 143 Series emergency vents are for
The 244 and 143 series emergency vents must be properly
emergency pressure relief only and must be used in
sized and selected for each specific tank application in order
conjunction with a normal vent or pressure vacuum vent,
to meet the proper venting capacity requirements.
such as a Morrison Fig. 354, 548, 748, OR 749.
244A 244C
The 244A can be used with The 244C can be used with
either Fig. 244F or Fig. 143A. either Fig. 244F or Fig. 143A.
Construction Details
Construction Details
Carbon steel welded rim and skirt.
Fig. 244C
Cast iron with NPT center port
Fig. 244A
I.D.
8" (eight 7/8" holes on 11" B.C.) 19.0 lbs 8" (eight 7/8" holes on 11" B.C. w/8" NPT I.D.) 26.5 lbs
10" (twelve 1" holes on 14" B.C.) 21.5 lbs 10" (twelve 1" holes on 14" B.C. w/10" NPT I.D.) 36.0 lbs
548 and 548A 748 and 748A
Pressure/Vacuum Vent Pressure/Vacuum Vent
With Gauge Hatchfor normal For normal venting of
venting of aboveground aboveground storage tanks.
storage tanks. Allows tank to Allows tank to breathe
breathe during filling and during filling and discharging
discharging operations. operations. Pressure/vacuum
Pressure/vacuum poppets seal poppets seal vapors in the tank
vapors in the tank when when pressure is equalized. This
pressure is equalized. This vent vent must be used in conjunc-
must be used in conjunction tion with an emergency vent
with an emergency vent and it and it is RECOMMENDED that
is RECOMMENDED that the the opening pressure setting is
opening pressure setting is set Fig. 548 set below that of the emergency
vent so the normal vent
below that of the emergency vent so Fig. 748
the normal vent operates first. operates first.
Construction Details Construction Details
seats/poppets.
hood.
Size Setting Setting Weight Weight (CFH) Fig. 748 Fig. 748A Venting
(oz/sq in) (oz/sq in) (lbs) (lbs) (@2.5 PSI) Pressure Vacuum Ship Ship Capacity
2" 2.0 1.0 13.25 7.00 20,200 (oz/sq in) (oz/sq in) (lbs) (lbs) (@2.5 PSI)
6.0 1.0 14.25 8.50 20,200 2" 2.0 1.0 13.25 7.00 20,200
3" 2.0 1.0 26.25 12.25 43,000 16.0 1.0 NA 11.25 18,600
Construction Details
Size2" NPT Option (must
Body and Capaluminum specify)male NPT Fig. 748ALT
PoppetsTeflon coated connection for dryer
alum application
Screensstainless steel Optionpressure discharge
NPT hood
749 Series
Pressure/Vacuum Vent
Vent valve used on underground and low volume
aboveground tanks for motor fueling. Vent allows tank to
breathe during filling and discharging operations.
Construction Details
Poppets seal vapors in the tanks when pressure is equal-
ized. Settings are approximate. Bodyaluminum
Pressure Poppetaluminum
Fig. 7492" NPT Vacuum Poppetbrass
Fig. 749S2" slip-on style Pipe SealBuna-N
Fig. 749CRB2" NPT CARB approval (95-15A) for stage I Screenbrass
and II (8 oz for stage I only).Viton o-rings on pressure Fig. 749
poppet.
Fig. 749CRBS2" slip-on style CARB approval (95-15A)
Pressure Vacuum Ship Venting
for stage I and II (8 oz for stage I only). Viton o-rings Fig. No. Setting Setting Weight Capacity
on pressure poppet. (oz/in2) (oz/in2) (lbs) (CFH)
Fig. 749BSPsame as Fig. 749, but with British pipe (@ 2.5 PSI)
749 &
threads. 749S 8.0 0.5 1.0 8,500
12.0 0.5 1.0 8,500
749CRB &
WARNINGFig. 749 P/V vent must only be used in conjunc- 749CRBS 3"W.C. 8" W.C. 1.2
tion with motor fueling and/or low capacity flow. Fluid handling 8 oz 5 oz 1.2
in lines larger than that used for retail service stations can
749BSP 8.0 0.5 1.0 8,500
cause tank to rupture or implode. 12.0 0.5 1.0 8,500
922
Combination Vent/Overfill
Alarm
For use on aboveground storage tanks. The
922 alerts you when your tank is near full
while also allowing your tank to breathe
during filling and dispensing operations.
This 2" full port pressure/vacuum vent is
equipped with a high intensity, audible
alarm which can be set by adjusting the
cable length to float height. It is fully
mechanical, with no wires or batteries
needed. Fig. 922
Construction Details
Size2" NPT
Bodyanodized aluminum
Screensstainless steel
Rainguardanodized alumi-
num
SealsViton WARNINGAll emergency vents, fill connections, tank
Internalsbrass openings, and piping connections must be airtight. Alarm/vent
Floatstainless steel airway must be free of any obstruction such as dirt or ice
when filling or unloading tank.
351S 351S/748A
Flame Arrester Flame Arrester
Used in conjunction with a With 748A Ventused in
normal vent on above- conjunction with a Fig. 748A
ground storage tanks. pressure/vacuum vent on
Open (non-pressure type) aboveground storage tanks.
flame arrester to help Pressure type flame arrester
prevent the transmission to help prevent the transmis-
of heat and/or an ignition
sion of heat and/or an
source into the tank. ignition source into the tank.
Fig. 748Asame vent
Size Weight
Fig. 351S featured in pressure/vacuum
2" NPT 25 lbs
vent section.
Construction Details Standard Features
Construction Details Fig. 351S w/748A
Bodycast iron 1. Gauge opening cap.
Fig.351SFlame arrester
Covercast iron 2. Vapor relief capacity at
Fig. 748APressure/vacuum
Capbrass 2.5 PSI = 22,000 CFH
vent
Arrester Platesstainless steel
Fig. 748 Venting
Pressure Vacuum Ship Capacity
or hydrogen gases. For use with normal hydrocarbon flames 2" 2.0 1.0 40.0 20,200
and free of debris. Blocked airways can cause structural 12.0 1.0 42.5 18,600
WARNINGObstruction of airflow through vents can result in structural deformation of the tank. Atmospheric conditions and below
freezing temperatures may cause condensation to occur and freeze. Freezing action can restrict movement of poppets and block
screened air passages. Monthly inspection and more frequent inspection in cold weather by someone familiar with the proper
operation of this vent is required to help guard against accidental damage to the tank. For further instructions contact: Morrison Bros.
Co., Dubuque, Iowa (563) 583-5701.
Open Vents
CARB approved (89-12). stainless steel screen keeps debris Fig. 155S
Fig. 354
Bodyaluminum
Size Weight Capacity
" 6 ozs
NOTEopen vents will
1" 9 ozs
WARNING! allow unrestricted
1" 10 ozs
evaporation of product.
Tank piping must be equal to the vent size, or less to maintain 1" 12 ozs
proper tank design limits. Pumping product through lines larger 2" 1.0 lbs
than the vent size, may cause the tank to rupture or implode. 3" 3.0 lbs
818/818F 918/918F
Clock Gauge Clock Gauge
Alarm
Patent 5144836for measur-
ing liquid level in aboveground Utilizes the Fig. 818
storage tanks. Gauge mounts
style clock gauge with a
on top of tank and is activated built-in high level
by a float connected to a cable. warning alarm.
Readout is on a 12 hour clock Fig. 818 Contains a battery
Fig. 918
face. powered, intrinsically
safe, alarm unit that is mounted remote from gauge.
Small hand = feet, large hand = inches. Gauge can be read
20-30 ft away to within 1/8 ". Maximum measurement is 12 Alarm is set for desired level during installation and can be
ft. reset at any time for a change in alarm level requirements.
Fig. 818SSwith stainless steel parts for some chemicals. Fig. 918SSwith stainless steel parts for some chemicals.
Fig. 918METwith metric face
Fig. 818METwith metric face
Fig. 818MEFwith metric face and female threads Fig. 918MEFwith metric face and female threads
Fig. 818MEBwith metric face and British pipe threads.
Construction Details
Fig. 818Ifloating suction gauge.
Gauge UnitFig. 818 clock gauge style (same standard and
Construction Details
optional features). Fig. 918 gauge has alarm dial and internal
Bodyaluminum with 2" NPT male connection. 2" female
Cablestainless steel
only).
3.
Extension leader for extended mounting above the tank.
1018
Fig. 1018
NOTEInstallation
NOTECylindrical floats will
instructions are included,
pass through a 2" opening.
piping is not included.
SGC89 SGE92
connected to a
measuring tape
Standard Features
12 ft or 50 ft tape
3" pulley
Floatnylon
3" BSP female body
threads
Options
4" NPT 2" pulley 3" NPT female threads 8.0 lbs
threads
FMMASO-91 Series
517 Series 518 Series
7 Gallon AST
3 Gallon AST
Spill Container Spill Container
Installed on above- Installed on aboveground
ground storage tanks storage tanks for the
for the purpose of purpose of containing small
containing small spills Fig. 517 spills and drips from the fill
and drips from the fill nozzle. 3 gallon capacity. nozzle. 7 gallon capacity.
Steel construction. Lockable and white powder Lockable with drain valve
coated. ULC listed. and vented lid. Connects to
4" male (NPT) riser, and is
Fig. 517spill containment. Male (NPT) riser
connection. white powder coated. ULC
listed.
Fig. 517Fspill containment. Female (NPT) riser
connection. Fig. 518CCsame as 518
only with centered opening.
Fig. 517WOwaste oil containmentRemovable
screen on inside of container so used filters, etc. can
Construction Details
be allowed to drain. Size Weight
Body and lid (14 ga.)steel
4" 21.5 lbs
Drain Valvebrass
Size Weight
Drain O-ringViton
515
Fig. 515
28" - 42"
Fig. 78DI
Expansion
Relief Valve
12 Ft.
Minimum Fig. 419
Drop Tube
Electrical
Line
Fig. 636
Emergency
Fig. 128DI Shut-off Valve
Frost-Proof
Drain Valve
Page 23
Morrison Bros. Co. P.O. Box 238 Dubuque, IA 52004 Ph: 563-583-5701 Fax: 563-583-5028
Aboveground Fuel Storage - Pressure System
Page 24
Rectangular double-wall tank with remote fill and side mounted dispenser
Fig. 548
Pressure
Vacuum Vent
Fig. 691B
Locking
Ball Valve Fig. 636
Emergency
Morrison Bros. Co. 8005534840
Shut-off Valve
Fig. 918
Fig. 323 & 323C Overfill
Vapor Recovery Alarm
Adaptor w/ Cap
Morrison Bros. Co. P.O. Box 238 Dubuque, IA 52004 Ph: 563-583-5701 Fax: 563-583-5028
Aboveground Fuel Storage - Suction System
Horizontal cylindrical tank with top fill and top mounted pump
Morrison Bros. Co. 8005534840
12 Ft.
Minimum Fig. 419
Drop Tube
Fig. 157
Suction Pipe
Strainer Fig. 128DI
Frost-Proof
Drain Valve
Page 25
Morrison Bros. Co. P.O. Box 238 Dubuque, IA 52004 Ph: 563-583-5701 Fax: 563-583-5028
Aboveground Fuel Storage - Suction System
Page 26
Electrical
Line
Fig. 246
Check
Valve
Fig. 800A
& 800DC Fig. 419
Adaptor w/ Drop Tube
Dust Cap
Fig. 691B
Locking
Ball Valve
Morrison Bros. Co. 8005534840
Morrison Bros. Co. P.O. Box 238 Dubuque, IA 52004 Ph: 563-583-5701 Fax: 563-583-5028
AST Bulk Storage Normal (P/V) Vent - and with Flame Arrestor
Expansion
Relief feature
allows excess
pressure due to
temperature
gain to bleed
back to tank.
Fig. 535