Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Symmetra PX 48kW - Guide Specification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11
At a glance
Powered by AI
The document discusses specifications for a Schneider Electric UPS system including its components, design requirements, submittals and factory assistance.

The main components of the UPS system include power modules, a bypass static switch module, battery modules, control modules, and an LCD interface display.

The UPS system is designed and built in accordance with international standards including IEC, EN and FCC standards for electromagnetic compatibility and safety.

Schneider Electric

Symmetra PX 48kW
16-48 kW, 3x400/230V Solutions
Uninterruptible Power System
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS
INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE
ARCHITECT OR THE ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION
WITH OTHER SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO PROVIDE, INSTALL, SUBMIT, ETC., IT SHALL
MEAN THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL PROVIDE,
INSTALL, SUBMIT, ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS.
WHERE APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED,
THE FIRST CHOICE APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995
MASTERFORMAT.

SECTION [26 33 63] [16611]

SOLID STATE UNINTERRUPTIBLE POWER SUPPLY

PART 1 - GENERAL

1.1 SUMMARY

A. This specification describes the operation and functionality of a continuous duty,


three-phase, solid-state, static Uninterruptible Power System (UPS) hereafter
referred to as the UPS. The UPS shall utilize rack-mounted redundant, scalable
array architecture. The system power train shall be comprised of swappable/trained
user-replaceable 16 kVA/16 kW power modules, which shall operate in parallel.
Each 16 kVA/16 kW power module contains a full rated input rectifier/boost
converter (hereafter referred to as Input Converter), full rated output inverter, and
battery charging circuit. The system shall also comprise of a continuous duty
swappable bypass static switch module, swappable/trained user-replaceable battery
modules, redundant control modules, redundant logic power supplies, and LCD
interface display. All of the above system components are housed in a standard, 600
mm wide, 1070 mm deep, and 2000 mm high equipment rack.

B. In addition, this specification describes the performance, functionality, and design of


the Maintenance Bypass Panel, Power Distribution board and extended Runtime
cabinet, the Battery System, and connectivity solutions.

C. The UPS and associated equipment shall operate in conjunction with a primary
power supply and an output distribution system to provide quality uninterrupted
power for mission critical, electronic equipment load.

D. All programming and miscellaneous components for a fully operational system as


described in this specification shall be available as part of the UPS.

1.2 SUBMITTALS
A. Proposal submittals:
1. As bid system bill of materials.
2. Product catalogue sheets or equipment brochures.
3. Product guide specifications.
4. System single-line operation diagram.

24/11/2014
5. Installation information, including weights and dimensions.
6. Information about terminal locations for power and control connections.
7. Drawings for requested optional accessories.

B. Delivery Submittals:
1. Installation manual, which includes instructions for storage, handling,
examination, preparation, installation, and start-up of UPS.
2. User manual, which includes operating instructions.
3. As built equipment drawings for the standard solution.

PART 2 - PRODUCTS

2.1 DESIGN REQUIREMENTS

A. The UPS shall be sized for _____ kVA and _____ kW load.

B. The UPS battery shall be sized for _____ at a Power Factor of_____ for _____
minutes.

C. Short Circuit Withstand Rating: 30 kA Symmetrical with gL/gG fuse in front of


system.

2.2 SYSTEM CHARACTERISTICS

A. System Capacity: The system shall be rated for full kW output in the following frame
sizes:
1. 48 kVA/kW - Can be configured with up to 3 power modules 16 kW for no fault
tolerance.

B. Input:
1. AC Input Nominal Voltage: 3x380 V/220 V, 3x400 V/230 V or 3x415 V/240 V with
L1,L2,L3,N, PE
2. AC Input Voltage Window: 340 - 477 at 100% load and 200 - 477 at 50% load
3. Maximum Frequency Range: 40-70Hz (autosensing)
4. Input Power Factor: > .99 at load greater than 25%.
5. Input Current Distortion with no additional filters:.< 5% at 100% load
6. Soft-Start: Shall be linear from 0-100% input current and shall not exhibit inrush.
This shall take place over a 10 seconds time period

C. Battery:
1. Nominal Battery voltage: +/-192 VDC (296 cells at 2 V)
2. Float voltage: +/-218 VDC (296 cells at 2.27 V)
3. End of discharge voltage (full load): +/-154 VDC (296 cells at 1.6 V)
4. End of discharge voltage (no load): +/-168 VDC (296 cells at 1.75 V)
5. Battery Design Life: 5-8 years
6. Battery Service Life: 3-5 years

D. Battery Charging
1. 10% of output power at low input voltage and 100% load.
2. 20% of output power at nominal voltage and 100% load (optional).

24/11/2014
E. UPS Output:
1. AC Output Nominal Output: 3x380 V/220 V, 3x400 V/230 V or 3x415 V/240 V
with L1, L2, L3, N, PE
2. Output frequency regulation: Frequency is synchronized to bypass input when
available over the standard range of 47 to 53 Hz. Optional +/-0.1 Hz and
+/-10 Hz setting from front panel.
3. At no bypass input present output frequency is 50 Hz.
4. AC Output Voltage Regulation: +/- 1%. For 100% linear load
+/- 3% for 100% non-linear load.
5. Voltage Transient Response: +/- 5% maximum for 100% load step
6. Voltage Transient Recovery within <50 milliseconds
7. Output Voltage Harmonic Distortion:
i. <2% THD maximum for a 100% linear load
ii. <5% THD maximum for a 100% non-linear load as defined by EN50091-
3/IEC 62040-3
8. Overload Rating:
i. Normal and battery Operation:
a. 150% for 60 seconds in normal and battery operation
b. 125% for 10 minutes in normal and battery operation
ii. Bypass Operation:
a. 125% continuous
b. 1000% for 100 milliseconds
9. System AC-AC Efficiency: >95% at 35 - 100% load
10. Output Power Factor Rating: For loads exhibiting a power factor of 0.5 leading to
0.5 lagging no derating of the UPS shall be required.

2.3 OPERATING PRINCIPLES

A. Normal operation: The input converter and output inverter shall operate in an on-line
manner to continuously regulate power to the critical load. The input and output
converters shall be capable of full battery recharge while simultaneously providing
regulated power to the load for all line and load conditions within the range of the
UPS specifications.

B. Battery: Upon failure of the AC input source, the critical load shall continue being
supplied by the output inverter, which shall derive its power from the battery system.
There shall be no interruption in power to the critical load during both transfers to
battery operation and retransfers from battery to normal operation.

C. Recharge: Upon restoration of the AC input source, the input converter and output
inverter shall simultaneously recharge the battery and provide regulated power to
the critical load.

D. Static Bypass: The static bypass shall be used to provide transfer of critical load
from the Inverter output to the bypass source. This transfer, along with its retransfer,
shall take place with no power interruption to the critical load. In the event of an
emergency, this transfer shall be an automatic function.

E. Maintenance Bypass: The system shall be equipped with a Maintenance Bypass


Panel (MBP) used to electrically isolate the UPS and supply the load directly from
the mains supply, if the UPS system has to undergo maintenance or service.

24/11/2014
2.4 ELECTRICAL CHARACTERISTICS

A. Input power converter:


1. The input power converters of the system are housed within the parallel
connected, removable power modules, and shall constantly control the power
imported from the mains input of the system, to provide the necessary UPS
power for precise regulation of the DC bus voltage, battery charging, and Main
Inverter regulated output power.

2. Input Current Total Harmonic Distortion: The input current THDI shall be held to
5% or less at full system, while providing conditioned power to the critical load
bus, and charging the batteries under steady-state operating conditions. This
shall be true while supporting loads of both a linear or non-linear type. This shall
be accomplished with no additional filters, magnetic devices, or other
components.

3. Soft-Start Operation: As a standard feature, the UPS shall contain soft-start


functionality, capable of limiting the input current from 0-100% of the nominal
input over a default 10 seconds period, when returning to the AC utility source
from battery operation. The change in current over the change in time shall take
place in a linear manner throughout the entire operation. (di/dt= constant)

4. Magnetization Inrush Current: The UPS shall exhibit 0 inrush current as a


standard product.

5. Input Current Limit:


i. The input converter shall control and limit the input current draw from utility
to 135% of the UPS output. During conditions where input current limit is
active, the UPS shall be able to support 100% load, charge batteries, and
provide voltage regulation.
ii. In cases where the source voltage to the UPS is nominal and the applied
UPS load is equal to or less than 100% of UPS capacity, input current shall
not exceed 110% of UPS output current, while charging the batteries.

6. Charging
i. The battery charging circuit shall contain a temperature compensation
circuit, which will regulate the battery charging to optimize battery life.
ii. The battery charging circuit shall remain active when in requested Static
Bypass and in Normal Operation.
iii. Back-feed Protection: The above-mentioned logic controlled contactor also
provides the back-feed protection.

B. Output inverter
1. The UPS output inverter shall constantly recreate the UPS output voltage
waveform by converting the DC bus voltage to AC voltage through a set of IGBT
driven bi-directional power converters. In both normal operation and battery
operation, the output inverters shall create an output voltage independent of the
mains input voltage. Input voltage anomalies such as brown-outs, spikes,
surges, sags, and outages shall not affect the amplitude or sinusoidal nature of
the recreated output voltage sine wave of the output inverters.

2. Overload Capability: Steady-state overload conditions, of up to 150% of system


capacity, shall be sustained by the inverter for 60 seconds in normal and battery
operation. Should overloads persist past the outlined time limitation the critical
load will be switched to the automatic static bypass output of the UPS.

24/11/2014
3. Output Contactor: The output inverter shall be provided with an output
mechanical contactor to provide physical isolation of the inverter from the critical
bus. With this feature a failed inverter shall be removed from the critical bus.
4. Battery Protection: The inverter shall be provided with monitoring and control
circuits to limit the level of discharge on the battery system.
5. Redundancy: The UPS shall be configured with redundant output inverters, each
with semiconductor fusing, and logic controlled contactors to remove a failed
component from the critical bus.

C. Static bypass:
1. As part of the UPS, a system static bypass switch shall be provided. The system
static bypass shall provide no break transfer of the critical load from the Inverter
output to the static bypass input source during times where maintenance is
required, or the inverter cannot support the critical bus. Such times may be due
to prolonged or severe overloads, or UPS failure. The UPS and static bypass
switch shall constantly monitor the auxiliary contacts of their respective circuit
breakers, as well as the bypass source voltage, and inhibit potentially
unsuccessful transfers to static bypass from taking place.

2. The design of the static switch power path shall consist of Silicon Controlled
Rectifiers (SCR) with a continuous duty rating of 125% of the UPS output rating.

3. Automatic Transfers: An automatic transfer of load to static bypass shall take


place whenever the load on the critical bus exceeds the overload rating of the
UPS. Automatic transfers of the critical load from static bypass back to normal
operation shall take place when the overload condition is removed from the
critical bus output of the system. Automatic transfers of load to static bypass
shall also take place if for any reason the UPS cannot support the critical bus.

4. Manual Transfers: Manually initiated transfers to and from static bypass shall be
initiated through the UPS display interface.

5. Overloads: The static bypass shall be rated and capable of handling overloads
equal to or less than 125% of the rated system output continuously. For
instantaneous overloads caused by inrush current from magnetic devices, or
short circuit conditions, the static bypass shall be capable of sustaining
overloads of 1000% of system capacity for periods of up to 100 milliseconds.

6. Modular: The static bypass switch shall be of a modular design.

7. System Protection: As a requirement, back-feed protection in the static bypass


circuit shall also be incorporated in the system design. To achieve back-feed
protection, a mechanical contactor in series with the bypass SCR(s) shall be
controlled by the UPS/static switch, to open immediately upon sensing a
condition where back-feeding of the static switch by any source connected to the
critical output bus of the system is occurring. One such condition could be a
result of a shorted SCR.

2.5 ENVIRONMENT CONDITIONS

A. Storage Ambient Temperature: -15 C to 40 C.

B. Operating Ambient Temperature: 0 C to 40 C. (25 C is ideal for most battery


types).

24/11/2014
C. Relative Humidity: 0 to 95% non-condensing.

D. Altitude: Maximum installation with no derating of the UPS output shall be 1000 m
above sea level.
1. 1000 m: 100% load
2. 1500 m: 95% load
3. 2000 m: 91% load
4. 2500 m: 86% load
5. 3000 m: 82% load

E. Audible noise, nominal max at 1 m from surface of unit


1. < 57 dBA at < 70% load
2. < 63 dBA at 100% load

2.6 BATTERY

A. The UPS battery shall be of modular construction made up of trained user-


replaceable, swappable, fused, battery modules. Each battery module shall be
monitored for voltage and temperature for use by the UPS battery diagnostic, and
temperature compensated charger circuitry.

B. The battery block housed within each removable battery module shall be of the
Valve Regulated Lead Acid (VRLA) type.

C. The UPS shall incorporate a battery management system to continuously monitor


the health of each removable battery module. This system shall notify the user in the
event that a failed or weak battery module is found.

2.7 DISPLAY AND CONTROLS

A. Control Logic: The UPS shall be controlled by two fully redundant,


user-replaceable/swappable control modules. These modules shall have separate,
optically isolated, communication paths to the power and static switch modules.
Logic power for the control modules shall be derived from redundant power supplies,
each having a separate AC and DC input and output. The communication of the
control modules shall be of Controller Area Network (CAN Bus).

B. Display Unit: A microprocessor controlled display unit shall be located on a hinged


door in the front of the system. The display shall consist of an alphanumeric display
with backlight, four LEDs for quick status overview, and a keypad consisting of
pushbutton switches.

C. Metered Data: The following metered data, shall be available on the alphanumeric
display:
D.
1. Year, Month, Day, Hour, Minute, Second of occurring events
2. Source Input Voltage
3. Output AC voltage
4. Output AC current
5. Input Frequency
6. Battery voltage

E. Event log: The display unit shall allow the user to display a time and date stamped
log of the most recent status and alarm events.

24/11/2014
F. Alarms: The display unit shall allow the user to display a log of all active alarms. The
following minimum set of alarm conditions shall be available:
1. Input Frequency outside configured range
2. AC adequate for UPS but not for Bypass
3. Low/No AC input, startup on battery
4. Intelligence Module inserted
5. Intelligence Module removed
6. Redundant Intelligence Module inserted
7. Redundant Intelligence Module removed
8. Number of Batteries changed since last ON
9. Number of Power Modules changed since last ON
10. Number of Batteries increased
11. Number of Batteries decreased
12. Number of Power Modules increased
13. Number of Power Modules decreased
14. Number of External Battery Cabinets increased
15. Number of External Battery Cabinets decreased
16. Redundancy Restored
17. Need Battery Replacement
18. The Redundant Intelligence Module is in control
19. On Battery
20. Shutdown or unable to transfer to battery due to overload
21. Load Shutdown from Bypass. Input Frequency Volts outside limits
22. Fault, Internal Temp exceeded system normal limits
23. Input Circuit Breaker Open
24. System level fan failed
25. Bad Battery Module
26. Bad Power Module
27. Intelligence Module is installed and failed
28. Redundant Intelligence Module is installed and failed
29. Redundancy has been lost
30. Redundancy is below alarm threshold
31. Runtime is below alarm threshold
32. Load is above alarm threshold
33. Load is no longer above alarm Threshold
34. Minimum Runtime restored
35. Bypass is not in range (either frequency or voltage)
36. Backfeed contactor stuck in OFF position
37. Backfeed contactor stuck in ON position
38. UPS in Bypass due to Internal Fault
39. UPS in Bypass due to overload
40. System in Forced Bypass
41. Fault, Bypass Relay Malfunction
42. High DC Warning
43. High DC Shutdown
44. Low Battery Shutdown
45. Low Battery Warning

G. Controls: The following controls or programming functions shall be accomplished by


use of the display unit. Pushbutton membrane switches shall facilitate these
operations.
1. Silence audible Alarm
2. Display or set the date and time
3. Enable or disable the automatic restart feature
4. Transfer critical load to and from static bypass
5. Test battery condition on demand

24/11/2014
6. Set intervals for automatic battery tests
7. Adjust set points for different alarms
8. Program the parameters for remote shutdown.

H. Potential Free (Dry) Contacts: The following potential free contacts shall be available
on an optional relay interface board:
1. Normal Operation
2. Battery Operation
3. Bypass Operation
4. Common Fault
5. Low Battery
6. UPS Off

I. Communication Interface Board: A communication interface board shall provide the


following communication port:
1. RS232 Serial Port #1: Enables local access to the UPS for management and
monitoring, and provides UPS data and simple signaling support.

2.8 SOFTWARE AND CONNECTIVITY

A. Network Adaptor: The Network Management Card shall allow one or more network
management systems (NMS) to monitor and manage the UPS in TCP/IP network
environments. The management information base (MIB) shall be provided in DOS
and UNIX "tar" formats.

B. Unattended Shutdown
1. The UPS, in conjunction with the network adaptor, shall be capable of gracefully
shutting down one or more operating systems.

2.9 ACCESSORIES

A. Battery disconnect breaker: Each UPS system shall have a 250 A 500 VDC rated,
thermal magnetic trip molded case circuit breaker. Each circuit breaker shall be
equipped a shunt trip mechanism and 1A/1B auxiliary contacts (1 AUX contact for
the internal DC circuit breaker). The circuit breakers are to be located within the
UPS enclosure or as part of a line-up-and-match type battery cabinet.

B. Maintenance bypass: The maintenance bypass shall provide power to the critical
load bus from the bypass source, during times where maintenance or service of the
UPS is required.
100 A gL/gG fuse must be in front of the Mains input and for dual mains an 80A gL
fuse on the bypass input must be installed.

C. Maintenance bypass panel (MBP): The maintenance bypass panel is to be housed


within the same UPS cabinet shall enable the UPS system to be transferred to a
maintenance bypass mode and to be isolated for essential maintenance. The
maintenance bypass panel to contain protection of all UPS/external static-switch
feeder and outgoing busbars and all necessary ACB/isolating switch interlocking to
allow fail-safe start-up, shutdown and transfer to maintenance bypass.

D. PDU (Power distribution unit):


1. GENERAL: A 100 A rated Modular Power Distribution Unit shall be contained
within the UPS frame.
The PDU shall have 18 pole positions available for the installation of modular
output distribution breakers. Single or three pole 16 A or 32 A circuit breakers
will provide the feeds to the server racks. The power to the cabinets from the

24/11/2014
PDU will be channeled via overhead power feeds exiting through the top of the
PDU. They will lie across the top of the cabinets via an overhead troughing
system. These troughs will sit on top of the cabinets and will be of tool less
installation. The PDU shall have branch circuit monitoring that links to the
management system interface.

2. ELECTRICAL: The PDU functionality is contained within the same frame as the
UPS, all in a standard 600 mm IT equipment rack.
The PDU shall contain at least (1) 3-phase distribution panel standard. The
panel shall be fed by the output of the 3-phase Symmetra modular UPS system
and shall be shall be rated for 3-phase 3x380 V/220 V, 3x400V/230 V or 3x415
V/240 V, L1,L2,L3,N, PE, 50 Hz. The PDU should be populated with standard
modular distribution breakers either as 1p (18) or 3p (6) or with RCD breakers
either as 1p (9) or 3p (3).
The panel should have Input and Output distribution from the top and power
cables shall be provided by the UPS vendor connecting the distribution breakers
cited above to, Schneider Electric supplied equipment rack. Each cable shall
include an IEC-309 plug that connects to a rack PDU (outlet strip). The layout of
the IT room equipment racks shall determine power cable length.

E. StruxureWare Data Center Expert: A centralized infrastructure management


platform, hereafter referred to as Data Center Expert, shall be sold separately and
shall be available for purposes of complete system monitoring and management of
all components outlined in this specification used as a single solution for small IT or
part of the StruxureWare software stack providing data to systems such as Data
Center Operation.
1. Monitoring - Data Center Expert shall be capable of monitoring a PDU through a
network of Cat 5 cable and a switch supplied by the user. This switch shall relay
information to Data Center Expert, which in turn shall allow access to this
information via the users public network via a single IP address.
2. Monitored Values: Data Center Expert shall be capable of monitoring alarms,
general status parameters, voltage and current of the PDU.
3. Thresholds: For individualized customer needs, Data Center Expert shall allow
for user configurable thresholds for alarm notification. With this feature, Data
Center Expert can notify clients of reaching thresholds for PDU capacity, or
branch circuit breaker capacity. Other custom programmable alarm points for
non-Schneider Electric products shall also be available via dry contact input
signal.
4. Public Network Monitoring: Data Center Expert shall also be capable of
monitoring other Schneider Electric devices that are connected to the clients
public network.

PART 3 - EXECUTION

3.1 REMOTE UPS MONITORING


The following three methods of remote UPS monitoring shall be available:
A. Web Monitoring: Remote monitoring shall be available via a web browser such as
Internet Explorer.

B. Simple Network Management Protocol (SNMP): Remote UPS Monitoring shall be


possible through a standard MIB II compliant platform.

3.2 SOFTWARE COMPATIBILITY


The UPS manufacturer shall have available software to support graceful shutdown and remote

24/11/2014
monitoring with PowerChute Network Shutdown (PCNS) for the following operating system
families for:
A. Windows
B. Hyper-V
C. VMware
D. Linux
E. Unix
F. Mac OS X
The full and updated supported OS compatibility chart can be found here:
http://www.apc.com/whitepaper/?um=200

3.3 STANDARD AND TESTS

A. Standards: All equipment shall be designed and built in accordance with accepted
engineering practice and applicable international standards, in particular the
standards listed below:
1. 89/336/EEC
2. 73/23EEC
3. EN/IEC62040-1-1, EN/IEC/UL60950-1
4. EN50091-2/IEC62040-2 (class A), FCC15A
5. EN/IEC62040-3 (VFI-SS-111)
6. IEC62040-2/EN/IEC 61000-4-2 level 3, performance criteria B
7. IEC62040-2/EN/IEC 61000-4-4 level 2, performance criteria A
8. IEC62040-2/EN/IEC 61000-4-3 level 2, performance criteria A
9. IEC62040-2/EN/IEC 61000-4-5 Level 3, performance criteria A

3.4 FACTORY ASSISTED START-UP


If a factory assisted UPS start-up is requested, factory trained service personnel shall perform
the following inspections, test procedures, and on-site training:

A. Visual Inspection:
1. Inspect equipment for signs of damage.
2. Verify installation per manufacturers instructions.
i. Inspect cabinets for foreign objects.
ii. Inspect Battery Units.
iii. Inspect Power Modules.

B. Mechanical Inspection:
1. Check all UPS and external maintenance bypass cabinet internal control wiring
connections.
2. Check all UPS and external maintenance bypass cabinet internal power wiring
connections.
3. Check all UPS and external maintenance bypass cabinet terminal screws, nuts,
and/or spade lugs for tightness.

C. Electrical Inspection:
1. Verify correct input and bypass voltage.
2. Verify correct phase rotation of all mains connections.
3. Verify correct UPS control wiring and terminations.
4. Verify voltage of all battery modules.
5. Verify neutral and ground conductors are properly landed.
6. Inspect external maintenance bypass switch for proper terminations and phasing.

D. Site Testing:
1. Ensure proper system start-up.

24/11/2014
2. Verify proper firmware control functions.
3. Verify proper firmware bypass operation.
4. Verify proper maintenance bypass switch operation.
5. Verify system set points.
6. Verify proper inverter operation and regulation circuits.
7. Simulate utility power failure.
8. Verify proper charger operation.
9. Document, sign, and date all test results.

E. On-Site Operational Training: During the factory assisted start-up, operational


training for site personnel shall include key pad operation, LED indicators, start-up
and shutdown procedures, maintenance bypass and AC disconnect operation, and
alarm information

3.5 MANUFACTURER FIELD SERVICE

A. Worldwide service: The UPS manufacturer shall have a worldwide service


organization. Available, consisting of factory trained field service personnel to
perform start-up, preventative maintenance, and service of the UPS system and
power equipment. The service organization shall offer 24 hours a day, 7 days a
week, and 365 days a year service support.

B. Replacement parts: Parts shall be available through the worldwide service


organization: 24 hours a day, 7 days a week, and 365 days a year. The worldwide
service organization shall be capable of shipping parts within 4 working hours or on
the next available flight, so that the parts may be delivered to the customer site
within 24 hours.

C. Maintenance contracts: A complete offering of preventative and full service


maintenance contracts for the UPS system and the battery system shall be
available. All contract work shall be performed by Schneider Electric factory trained
service personnel.

END OF SECTION

24/11/2014

You might also like