CONTOH PERHITUNGAN
IMPRESSED CURRENT CATHODIC PROTECTION ( ICCP ) SYSTEM
CALCULATION METHOD
1. Round Piles
A = 2 r x L = x OD x L
Where:
A= perimeter length x L
Ir = A x Id
Where:
The total required protective current is the sum of individual pile protective
current, as below:
It = I r
Then the total protective current required including Nominal Current (NC) is:
It = It x NC
N1 = It / Io
Where :
Wt = It x Lf x Cr/Ut
Where :
Since the wear rate of Mixed Metal Oxide (MMO) is extremely low, the anode
weight calculation is to be neglected
Anodes Installation
The electric current discharged by anodes from this 5 m distance shall cause
a positive change in the potential of water to the steel pile. The magnitude of
this change could be calculated by this formula:
xI
V
2d
Where:
V = change of potential (Volt)
= water resistivity = 35 ohm cm
I = anode max output current = 15 amp
d = distance = 500 cm
35ohmcmx15amp
V 0.167Volt
2 xx500cm
DC Circuit Resistance
The total DC circuit resistance of the ICCP system is the sum of two
components below:
Modified Dwight equation has been used to calculate the resistance of single
vertical anode to electrolyte ( soil ) as follows :
8L
RV x In 1
2L D
Where :
8L 2L
Rn ln 1 ln 0.656 N
2NL d s
Where:
Rn = resistance of multiple vertical anodes to remote earth ( ohms )
= soil resistivity ( ohm-cm )
L = length of anode ( cm )
d = diameter of anode ( cm )
s = anode spacing ( cm )
N = number of anodes
Note that this equation is just Dwights equation divided by N with the
crowding correction factor added
4 L2 4 L S 2 L2
S S 2 L2
RH x ln 1
2L DS
L L
Where:
RH = Resistance of one horizontal anode to electrolyte in ohm
= resistivity of the electrolyte in ohm cm
L = length of MMO anode in cm
D = diameter of MMO anode in cm
S = twice depth of anode in cm
Note:
MMO anodes proposed to be installed individually on selected location
around the piles, therefore interference factor is not considered
DC Cable Resistance
The individual Fe/Si/Cr anode cable tail will be connected to the respective
anode Junction Boxes. From Anode Junction Boxes (AJB), the XLPE/PVC
cables will be connected to Main Anode Junction Box and than terminated to
Transformer Rectifier.
The individual MMO anode cable tail will be connected directly to Anode
Junction Box (AJB). From Anode Junction Box the XLPE/PVC cables will be
connected to Transformer Rectifier.
R 2 = R 1 + ( T 2 T1 )
Where :
R2 = Resistance at T2 ( ohm / m )
R1 = Resistance at T1 ( ohm / m )
T2 = Operating temperature of cable ( C )
T1 = Temperature ambient of cable ( C )
=Temperature coefficient of cooper ( = 0.00393/C )
RC1 = LC x R1
Rt = RHT + R2
Et = ( It x Rt ) + Bemf
Where :
The AC current requirement from the ac power input at 400 V, three phase, 50
Hz can be calculated using the following formula:
E dc I dc
Iac =
E ac 3
Where :