Air Conditioning
Air Conditioning
Air Conditioning
Three Zones
The air conditioning operation is automatic.
In addition to supplying fresh air, the system maintains a constant
selected temperature that is independently controlled for each of
the three zones.
The three zones are the Cockpit, Forward Cabin, and Aft Cabin.
Mixing Unit
The mixing unit mixes the conditioned air from the packs with
recirculated air from the cabin that is pulled by the Cabin Fans.
The mixing unit then distributes the air mixture to the three zones.
CAB FANS pb
The fans are controlled by the CAB FANS pushbutton on the
Ventilation panel.
The normal position of this switch is ON, however the switch can
be used to select the fans to OFF during abnormal conditions as
required by an ECAM procedure.
Pack Controllers
The Pack Controllers control the output flow and temperature of air
from each pack, to maintain the temperature of the coldest zone
temperature setting(s) on the COCKPIT, FWD CABIN, and AFT
CABIN Zone Temperature Selectors on the AIR COND panel.
Zone Controller
Trim Air is then added and modulated as necessary by the Zone
Controller to add hot air from the respective Trim Air Valves to the
air from the mixing unit to maintain the temperature demanded by
the respective warmer Zone Temperature Selector settings for the
affected Zone(s).
HOT AIR pb
The hot airflow to all Trim Air Valves is controlled by the Hot Air
Pressure Regulator Valve, that is normally on but can be selected
OFF by the crew or when commanded to close automatically for
abnormal conditions.
Zone Selectors
The Regulator Valve regulates the Trim Air temperature to meet the
requirements for the normal ranges of the Zone Temperature
Selectors.
Outflow Valve
When Ram Air is selected on and the Outflow Valve is operating
under automatic control, the Outflow Valve will open about 50% as
long as the differential pressure is less than 1 psi.
Avionics Ventilation
AVIONICS VENTILATION INTRODUCTION:
An automatic ventilation system provides cooling for the electronic
and electrical components in the flight deck and the avionics
compartment.
This system is controlled by the Avionic Equipment Ventilation
Computer (AEVC).
Battery Ventilation
BATTERY VENTILATION:
A Venturi in the skin of the aircraft draws air from the space around
the batteries and vents it overboard.
This provides ventilation for the batteries.
No control or indication of this system operation is provided to the
flight crew.
Pack Introduction
The two Air Conditioning packs operate automatically and
independently of each other.
Lets follow the flow of bleed air as it enters and flows through a
single pack.
PACK pb
The Pack pb normally remains in the ON position.
During engine start, the Pack Flow Control Valves will automatically
close as soon as the MODE selector is set to IGN (Ignition) or CRK
(Crank) for start.
During engine start, the Pack Flow Control Valves remain closed
when the MASTER switch is set to ON (or the MAN START pb is set
to ON), and the start valve is open and N2 < 50%.
After Start
After engine start, the Pack Flow Control Valves automatically
open; however on the ground, reopening of the valves is delayed
for 30 seconds after the first engine start.
This delay avoids cycling of the valves before the second engine
start
If the second engine is not started within 30 seconds, the Pack
Flow Control Valves will open until the second engine MASTER
switch is set to ON.
Pack FCV on Bleed Page
The operation of the Pack Flow Control Valve is displayed on the
ECAM BLEED page.
The amount of flow that is provided by the Pack Flow Control Valve
is also displayed.
When the valve is closed, the flow indicates on the LO side and is
amber.
At other times, the flow line displays in green and to the right of the
LO position.
Read the pop-up information about this display.
Compressor Section
The cooled bleed air enters the compressor section of the air-cycle
machine and is compressed to a higher pressure and temperature.
The temperature of the air that exits the compressor section is
displayed above the Pack Flow.
It normally displays green, but displays amber for temperatures
above 230 degrees C.
Water Separator
A water separator system dries the air before it enters the turbine
section.
Turbine
After the main heat exchanger, the air flows through the turbine
section, where it expands, and heat is removed from the air.
This expansion generates power to drive the compressor and
cooling air fan.
The removal of heat energy during this process reduces the
temperature of the air, resulting in very low air temperature at
turbine discharge.
Anti-Ice Valve
This valve automatically opens when icing conditions are sensed at
the output of the turbine section.
The purpose of this valve is to allow warm air to bypass the cooling
process and stop the formation of ice. It can provide a backup
method of temperature control in abnormal conditions.
Bypass Valve
A Bypass Valve is also installed. It is automatically modulated by
the pack controller to provide control of the output temperature of
the air from this pack.
Without the operation of the Bypass Valve, the pack would always
provide the coldest possible output.
With the operation of the Bypass Valve, the output temperature of
air from each pack can be controlled.
HOT AIR pb
It is pneumatically-operated and electrically-controlled from the
HOT AIR pushbutton on the AIR COND panel.
This pushbutton normally remains ON for automatic operation
of Trim Air.
In the absence of air, a spring keeps the Hot-Air Pressure-
Regulating Valve closed.
Pack Controller
Each Pack Controller regulates the temperature of its associated
pack, in accordance with a demand signal from the Zone Controller,
by modulating the bypass valve and the Ram Air Inlet Flap.
The Pack Controllers also regulate flow by modulating the
associated pack flow control valve.
Temperature Sensors
The zone controller computes a temperature demand from the
selected temperature and the sensed actual temperature.
The actual temperature is measured by sensors located:
- in the cockpit, for the cockpit zone, or
- in the lavatory extraction circuit and galley ventilation system, for
the cabin.
LO Flow
LO flow might be selected when there are light passenger loads
(below 115) and minimal need for temperature change in the
cabin. This mode demands less bleed air and therefore increases
fuel efficiency. Note: The system delivers normal flow if the crew
selects LO flow and the temperature demand cannot be satisfied.
NORM is selected to provide the normal flow rates.
HI flow should be selected when there is hot and humid
conditions.
Various Configurations
Depending on the skin temperature, the cooling air is provided by
outside air, circulated air in the pressurized portion of the aircraft,
or by the air conditioning system.
Open Circuit - Normal Ground
The Open-Circuit Configuration is the NORMAL GROUND
CONFIGURATION and operates only if the thrust levers are not at
Takeoff and the skin temperature is above the on-ground
threshold.
We would expect to see this configuration during mildly cool,
warm, or hot ground operations and it is not available in flight.
The AEVC will select the configuration to the closed circuit
configuration on the ground if the skin temprature is very cool or
cold.
Intermediate Configuration
The Intermediate Configuration provides ventilation when the
aircraft is on the ground (with takeoff power) or during in-flight, if
the skin temperature is above the in-flight threshold.
The only difference between this and the Closed-Circuit
Configuration is that a smaller internal door flap opens on the Skin
Air Extract Valve to allow some of the air to flow overboard. This
completes the normal configurations of the Avionics Ventilation
system. Now we will describe the two abnormal configurations for
this system.
Blower FAULT
An abnormal configuration that is very similar to the Closed-Circuit
Configuration operates if the Blower Fan or Extract Fan is shut
down.
This configuration will be set by the crew as a result of an ECAM
Procedure.
With only the Blower pb in OVRD, the Blower Fan stops and the Air
Conditioning Inlet valve opens to supply cooling air.
Extract FAULT
With only the Extract pb in OVRD, both fans continue to run and the
Skin Exchanger Inlet Bypass valve closes to force all recirculating
air over the Skin Heat Exchanger.
Smoke Configuration
The Smoke configuration is set by the crew as a result of selecting
both BLOWER and EXTRACT pbs to OVRD. The Blower Fan stops,
but the Extract Fan continues to operate.
All valves close except the Air Conditioning Inlet Valve and a
smaller door flap opens on the Skin Air Extract Valve. This
configuration purges smoke from the system by using conditioned
air to blow through the avionics equipment and then overboard
through the smaller internal door flap on the Skin Air Extract Valve.
AEVC Failure
Finally, a variation of the smoke configuration is set if the Avionics
Equipment Ventilation Computer fails.
However, the Skin Exchange Isolation valve remains open, the Inlet
Valve and Skin Exchange Inlet Bypass Valve remain in their last
position, and the Extract Fan continues to operate.