Broad X User Manual 0814 Revised PDF
Broad X User Manual 0814 Revised PDF
Broad X User Manual 0814 Revised PDF
USERS MANUAL
Aug, 2012 EN
Please read this manual carefully to ensure proper operation
and maintenance of the chiller.
1. Only those who have been trained by BROAD and obtained
operator qualifications can operate BROAD chillers.
2. This manual should be kept for the duration of the chillers life.
3. If there are any technical improvements to this product, we will inform
you in a timely manner so as to facilitate upgrading the technology of the
chiller.
4. It is prohibited to change the chillers component, structure and
wiring diagram without BROADs approval.
5. Chiller operation environment requirements:
Machine room temperature: 4~110 F
Relative humidity: < 85%
Environment: The chiller should be kept away from dust, corrosive gases,
especially brines, and strong acid or alkaline environments. Vibration
should also be avoided inside and around the machine room.
6. Do not install the touch screen in a place where the temperature or
humidity varies more than the recommended ratings, so as to avoid
condensation and freezing.
CONTENTS
General Information 01
Operation 04
DFA Chiller Safety Regulations 13
Product Overview 15
Part List 17
Working Principle 21
Periodic Check 23
Faults and Trouble-shooting 31
Maintenance 43
Energy-saving Management 54
Water Treatment Devices 57
Service Information 63
IFA Main Interface 65
IFA Safety Regulations 66
IFA Trouble-shootings 68
Saturated Steam Pressure 69
Saturated Steam Pressure for LiBr Solution 70
LiBr Solution Specification Curve 71
The Mission of Service Engineers 72
1
GENERAL INFORMATION
TOUCH SCREEN
Turn on the main interface of the
chiller. Directly enter monitor main
interface.
START
Press the ON start, which will turn
green after confirmation, the A/
C water pump and cooling water
pump will start automatically
according to procedures. The chiller
starts operation with automatic
cooling load regulation and safety
protection after chilled water
and cooling water flow rate are
acceptable.
SHUT-OFF
Press OFF Dilution , the burner
steam valve will close and the chiller
enters automatic dilution cycle.
HTG temperature will drop gradually
while the chilled water temperature
rises. The dilution stops and chiller
shuts off when shut-off requirement
is met, the process normally lasts 30-
60 minutes.
NOTE:
1. Nails or other sharp objects shall
not touch the screen surface.
2. Clean the surface with a wet
cloth. Alcohol or other organic
solvent are not allowed.
3. The professional interface is
only open to BROAD service
engineers
2
GENERAL INFORMATION
ALARM NOTICE
If fault notice or alarm notice shows on the main interface, press the blinking icon, and then enter
the Fault Record interface. Then you can check the time of fault, reset time, the name of the fault,
the fault alarm and abnormal reminders. Press the fault name and check the fault reasons and other
informations. Then troubleshoot the fault according to the hints.
The Fault Record interface is also accessible by pressing Fault Record on the Check interface. Please
refer to the next page.
Please refer to page 31 for the different fault types and troubleshooting methods.
3
OPERATION
CHECK
4
OPERATION
5
OPERATION
6
OPERATION
The setting target temperature of the chilled water outlet, cooling water inlet and HTG can be adjusted
on the main screen. Input the target number and confirm in the TENKEY numerical keyboard (Appear
while pressing the background part). The chiller will automatically adjust the load according to the
target temperature setting. For example, if the chilled water target temperature is set at 45 F, the
chiller will automatically keep it around 45 F.
Chilled/Heating W. Outlet temperature: Setting range is 42~77 F, by default at 46 F. By increasing
the target temperature properly when the ambient temperature is low, the user can save energy. But
increasing the target temperature too much will influence the effectiveness of the air conditioning
effect. At the same time, when the ambient temperature is high, it is suited to decrease the target
temperature properly, but it will dramatically increase energy consumption if the target temperature is
too low.
Cooling-water inlet temperature: Settings range is 73~93 F, by default at 83 F. Properly decreasing
the setting helps improve the chillers performance.
HTG temperature: Settings range is 248~315 F, by default at 295 F. The HTG temperature can be set
at a lower value when chiller load is low and vice versa. When the need for cooling is met, try to set the
HTG temperature to a lower setting. As the HTG temperature lowers, the chiller becomes more energy
efficient and safer to operate.
7
OPERATION
TIMING
8
OPERATION
ENERGY-SAVING SETTING
Press Energy-saving setting on the Setting screen to enter the Energy screen.
Select an energy-saving mode according to the ambient temperature and cooling
load: top, high, medium or low energy-saving. The chiller will run automatically
according to the ambient temperature and chosen energy-saving mode.
Note: After the chiller stops automatically at shutdown temperature, it can automatically restart
when the ambient temperature increases (while cooling)/reduces (while heating) by a certain
temperature difference this is called restarting the temperature difference. For example, in
medium energy-saving cooling operation, the chiller will stop when the ambient temperature is 72
F and restart at 75 F. In high energy-saving heating operation, the chiller will stop when ambient
temperature is 60. F and restart when it is 57 F.
OTHER CHOICES
10
OPERATION
INFORMATION
11
OPERATION
ENERGY COST
Press Expense to check the fuel, water, electricity consumption and operation cost
(Fan coils excluded).
12
DFA SAFETY REGULATIONS
1. When the chiller starts cooling operation, the chilled/heating water pump must be started
before to the cooling water pump. When chiller shuts down, the cooling water pump must be
OPERATION
stopped prior to the chilled/heating water pump; otherwise, copper tubes will get frozen.
Although the On/Off sequence of Auto Control mode is set out in the above mentioned
requirements, a reconfirmation is needed once every 3 months in case of any accidents like
incorrectt connection of cables or software viruses.
2. In cooling operation, heating water drain valve must be opened and its handle be removed.
Otherwise the piping system for heating water will be heated and expanded, wasting a
great deal of energy. The handle must be well kept for future use.
3. Random adjustment of solution concentration regulating valves is prohibited.
Otherwise it will cause crystallization, reduce cooling capacity and waste energy.
4. Angle valves must be 100% closed when the chiller is switched from cooling to heating operation.
Start the chiller and when the HTG temperature rises to 212 F, check the temperature of the valve pipe
on the main shell side to see if it rises. A loose shut-off of angle valves will result in high temperature and
damage the HTG.
1. Ensure good ventilation conditions in machine room.
BURNING
Otherwise, the chiller will erode, which will damage electrical insulation and affect combustion , even injure
people due to oxygen shortage in machine room.
2. Make sure there is no gas leakage.
Gas-fired chillers are not allowed to work if the gas leakage detection device and force fan linkage are not in
operation.
3. Make sure there is no exhaust leakage.
In case of exhaust leakage in machine room, the operator will suffer from CO posioning.
4. The fuel filter should be cleaned or replaced regularly.
Otherwise, the burning will not work properly. Smoke will be produced , which can damage the solenoid
valve or even cause deflagration. The oil pump will also be damaged for oil-fired type.
5. Burner operating with black smoke is prohibited.
Excessive Air Coefficient should be within a range of 1.18~1.25 for gas-fired types
and1.13~1.20 for oil-fired types. Otherwise, even a small amount of smoke will increase fuel
consumption dramatically, pollute the environment and even cause fire. If the Excessive Air
Coefficient is too large, it will cause deflagration and even stop the burner, and waste fuel.
6. Gas pressure and fuel heating values must be stable and fuel quality must meet the local standards.
Otherwise it will cause soot in the fire tubes, increase energy consumption, affect cooling
capacity. The burner might be damaged, even cause deflagration if it is serious.
7. The exhaust damper must be full open before chiller start and full close when the chiller
stopped for long time.
1. Confirm the vacuum conditions and proper operation of the auto purge and vent device.
2. Prevent others from handling the vacuum valve randomly.
VACUUM LIFE-SPAN
The handle of the vacuum valve must be removed and well kept after operation to avoid
unauthorized access.
3. Conduct heating and chiller shut-off management with care.
The main shell should be maintained in vacuum condition during heating operation. If the
expected shut-off period is over 8 months, it should be charged with 0.01 MPa~0.02 MPa
high-purity nitrogen (purity>99.995%).
4. Use only BROAD solution; it is forbidden to use solution regenerated by others.
It is required to sample the solution and test it once a year on the machine room site, and solution should be
fully circulated and diluted before sampling. If result cant be confirmed or more details are needed, sample the
solution with special bottle, and send it to BROAD lab with a label on the bottle correctly. BROAD will confirm
the vacuum, rust condition of the copper tubes and steel to ensure 25-year life span. The solution needs not be
taken out for regeneration. If it is too feculent, it can be filtered with the BROAD filter without stopping the unit.
If the solution is regenerated by others, BROAD will not be responsible for the damage to the system.
5. It is forbidden to clean the copper tubes with chemicals without BROAD written permission.
If the chemicals are not property used, the cleaning is not strictly controlled or the chemicals
are not drained completely, it will seriously corrode the copper tubes, which will reduce the
life-span or even destroy the chiller.
6. Strengthen water quality management.
Auto water quality stabilizer charging device should be installed (auto dosing of biocide and
anti-sludging agent). The water should be tested at least once every 3 months and select the
appropriate anti-sludging agent according to this result. Quality of make-up cooling water should
meet the quality standard of city water. Poor water quality will cause more energy consumption,
reduce cooling capacity and corrosion of copper tubes, or even destroy the chiller.
13
DFA SAFETY REGULATIONS
1. Anti-freezing protection for the chilled water tubes must be strictly carried out.
BROADs requirement of the 3-stage protection and interlock electrical diagram of the chilled/heating water
CONTROL
system must be followed to avoid poor operation, otherwise tubes may become frozen.
The 3-stage protection should be checked every quarter.
2. The chiller must be started in Auto Control.
There are some protection procedures under Commissioning Mode, but it can be used
only under the supervision of professionals, otherwise serious failure will occur.
3. The safety devices cannot be by passed nor can their settings be changed at will.
Before the cooling period begins, all the safely devices must be calibrated, especially the
chilled water flow switch, temperature sensor and HTG pressure control. Otherwise the
copper tubes may become frozen or serious personal injuries may occur.
4. Power supply must be correct and voltage must be stable.
The fluctuation of the voltage must be within 10% of the rated value. A dedicated grounding
wire must be available in the machine room. At least a 6.0 mm2 wire must be used as the
grounding wire, and the grounding resistance should be 4, otherwise it will damage the
electrical components and control system or even cause personal injury.
5. If the electric wire is damaged, it should be replaced only by manufacturer, service agent or
qualified personnel.
Otherwise personnel and equipments will be in danger.
6. The chiller must be on line 24/7/365.
To ensure collecting the data and monitoring the chiller, the chiller must be on line 24/7/365.
Otherwise BROAD Monitoring Center will not know if the chiller is working normally or not. If
the chiller is to be put into idle for more than 3 months, BROAD Monitoring Center must be
informed before power-off.
7. Computing data must be set correctly.
If the data are wrong, it will cause unexpected chiller shut-off and affect the users energy
management.
1. Do not place heavy objects on or near the automatic pressure escape.
OTHERS
14
PRODUCT OVERVIEW
Cooling
W. outlet
Chilled
W. outlet
Absorber
Evaporator
Cooling
W. inlet
Rear flue Hot W. Hot W. Heating Hot W. Heating Steam angle Auto purge/
chamber heater outlet W. inlet inlet W. heater valve vent system
Chiller
control
cabinet
Flame
sight-glass
Hot W.
relief
valve
Heating
W. relief
valve
Inverter
Heating cabinet
W. drain
valve
Diluted
Hot W. HTHE Concentrated solution
drain Diluted solution sampling solution angle angle
valve sampling valve valve valve valve
15
PRODUCT OVERVIEW
Hot W. Heating W.
thermostatic thermostatic Heating W.
valve valve check valve
Rupture disc
Softener
Chilled W. brine tank
Hot W. Softener
AC W. cooling/ pump control
heating switch valve
valve
Softener
resin tank
AC W. check
valve header
AC W. pump
AC W. check
valve header
Cooling pump
A/C W. 0
resistance
filter Hot W.
flow meter
Cooling W. 0
resistance filter Hot W.
AC W. flow
meter
VALVE LIST
NO. Type Name Function Remark
1 Steam angle valve (F3) Separates main shell with HTG Open in cooling,
Cooling/heating
refrigerant
7 LTHE sampling valve (F10) LTG concentrated solution sampling
8 HTHE sampling valve (F11) HTG concentrated solution
sampling
9 Diluted solution sampling Solution charging/discharging or
valve (F12) diluted solution sampling
10 Main purge valve (F13) Purge the chiller or oil interceptor Purge only
11 Direct purge valve (F14) Purge the chiller directly
12 HTG purge valve (F15) Purge the HTG directly through this Open only while purging
valve HTG
13 Sampling purge valve Purge the sampling bottle or check Open only for sampling
(F16) the vacuum with the vacuum meter or checking vacuum with
vacuum meter
17
PART LIST
cont.
NO. Type Name Function Remark
14 Main shell pressure Checks main shell pressure Closed in operation,
detecting valve (F18) open while checking HTG
low regulating valve
pressure
15 HTG pressure valve (F19) Checks HTG pressure Closed in operation,
open while checking
main shell pressure
16 Auto air vent valve & Non-condensable gases are vented Manual valve is open in
manual valve (F20) out of the chiller through this valve operation, closed while
during auto purge. It can also charging nitrogenor or in
prevent air into leaking in the chiller. maintenance.
17 Nitrogen charging valve Port used for charging nitrogen into Open only for nitrogen
(F21) the chiller or purging the collection charging
chamber when necessary.
18 Auto purging valve (F22) Switches the purge/venting of chiller
19 Refrigerant motor valve Bypasses refrigerant to absorber Automatic, opens only
(F24) during refrigerant bypass
20 Hot water thermostatic Stabilizes hot water temperature Auto-trace and regulate
valve (F25)** hot water load
21 Heating water Stabilizes heating water temperature Auto-trace and regulate
thermostatic valve (F26)** heating water load
22 A/C W. switch valve (F1)* Switches between chilled W. and A/c W. goes through
Heating W. system evaporator in cooling,
and heater in heating.
Other vacuum valves
18
PART LIST
SENSOR LIST
NO. Name Function
1 Chilled water inlet temperature sensor Detect chilled water inlet temperature, for calculating cooling capacity
(T1) and COP
2 Chilled water outlet temperature Detect chilled water outlet temperature to perform cooling load
sensor (T2) regulation to avoid frozen tubes in evaporator and calculate COP
3 Chilled water calibrating temperature Calibrate chilled water outlet temperature to avoid frozen tubes in
sensor (T2A) evaporator caused by chilled water outlet temperature deviation
4 Cooling water inlet temperature Detect cooling water inlet temperature and realize cooling tower fan
sensor (T3) frequency control to avoid excessively higher or lower than the setting
5 Cooling water outlet temperature Detect cooling water outlet temperature to control cooling water
sensor (T4) frequency control
6 HTG temperature sensor (T5)(connect Detect HTG temperature and send signal to PLC to avoid HTG solution
PLC) over-temperature and crystallization
7 HTG temperature control (T5A) Perform HTG temperature limit protection by shutting off burner directly
(connect burner)
8 Exhaust temperature sensor (T6) Detect exhaust temperature to prevent over-temperature
9 Ambient temperature sensor (T9) Detect ambient temperature to save energy; install outside
10 HTG crystallization temperature sensor Detect HTG concentrated solution outlet temperature to judge HTHE
(T10) (HTG) crystallization
11 LTHE inlet temperature sensor (T11) Detect LTHE diluted solution inlet temperature to judge LTHE crystallization
12 LTG crystallization temperature sensor Detect LTHE diluted solution outlet temperature to judge LTHE (LTG)
(T12) crystallization
13 Control cabinet temperature sensor Detect temperature inside control cabinet, auto start/stop the
(T13) ventilation fan to avoid high temperature affecting the reliability, safety
and life-span of electrical components
14 Heating water inlet temperature Detect heating water inlet temperature and calculate heating water
sensor(T14)** capacity
15 Heating water outlet temperature Detect heating water outlet temperature. Adjust the heating load, and
sensor (T15)* calculate heating capacity
16 Hot water inlet temperature sensor (T16)* Detect hot water inlet temperature and calculate hot water capacity
17 Hot water outlet temperature Detect hot water outlet temperature, adjust the hot water load, send an
sensor(T17)** alarm if temperature is too high and calculate hot water capacity
18 Chilled water flow switch (B1,B1A) Detect chilled water flow rate to prevent frozen tubes in the evaporator
(Connected to PLC)
19 Cooling water flow switch (B2) Detect cooling water flow rate to ensure chiller capacity
20 Chilled water flow switch (B3) (Directly Detect chilled water flow rate to perform 3-stage protection
connected to cooling water pump)
21 Pressure control (GY) HTG overpressure protection. When overpressure occurs, a signal will be
sent directly to PLC to the PLC to stop the burner
22 HTG solution level probe (YK1) Detect HTG solution level, perform solution cycling regulation and HTG
low solution level protection and detect the signal of tube cracks
23 Refrigerant level probe (YK2) Detect refrigerant level and send signal to PLC to control the On/Off
function of the of burner and refrigerant pump, perform load regulation
and prevent refrigerant overflowing
24 Non-condensable probe (YK3) Detect solution level in separation canister of auto-purge system
and send signal to PLC. If no solution level is detected, the chiller will
automatically vent out the non-condensable gases in from the chamber
25 Auto vent sensor(YK4) When the solution level in chamber is detected, the auto vent process
will stop
26 A/C water flow rate meter(V1) Detect A/C water flow rate to calculate cooling/heating capacity and COP
27 Cooling water flow rate meter(V2) Detect cooling water flow rate to calculate exhaust heating capacity
28 Gas flow rate meter(V3) Detect gas flow rate to calculate gas consumption, energy cost and COP
29 Hot water flow rate meter(V4)** Detect hot water flow rate to calculate hot water capacity
30 Conductance rate sensor(S) Detect cooling water quality, control water draining time and add inhibitor
31 Different pressure detector(P) Detect A/C water pressure difference, control A/C water pump energy
saving operation
32 Burner gas leakage detector (SG1) Stop burner when gas leakage is detected to avoid safety accident
33 Gas leakage detector in machine Equipped by the user, for detecting integrity of gas pipe in machine room.
room (SG2) Draft fan will be started if gas leakage is detected to avoid accidents
NOTE: parts with ** are not for heating-cooling type; parts with ** and *are not for cooling-only type.
19
PART LIST
C hilled w ater7/14
A uto chem icalclosing device
Hotw ater80/60
C ooling w aterpum p
C hilled w aterpum p
Hotw aterpum p
W .softner
Absorber
High tem perature
Evaporator heat exchanger
Heat source orfuel
C hilled w ater65/55
Hotw ater80/60
C hilled w aterpum p
Hotw aterpum p
Heatsource orfuel
23
PERIODIC CHECK
24
PERIODIC CHECK
25
PERIODIC CHECK
26
PERIODIC CHECK
Rubber cork
Vacuum rubber
hose Purge nozzle
Sampling bottle
Concentration meter
Hydrometer
Mercury thermometer
27
PERIODIC CHECK
29
PERIODIC CHECK
30
FAULT AND TROUBLESHOOTING
FAULT TYPE
There are four different types of faults: screen to correct the fault. The PLC will store
fault stop, fault alarm, abnormal the record for the service engineers review
reminding and abnormal record. The and reference for maintenance.
touch screen will indicate when the first Any fault should be solved in a timely
three types occurred. manner, even though some faults or
abnormalities will not immediately
a. Fault Atop cause the chiller to stop.
Emergency repair is needed when fault stop If not solved in time, a fault will cause the
occurs during chiller operation. The chiller chiller to stop. In addition, the chiller running
will enter dilution shut off cycle immediately, with a fault will waste energy, shorten life
and this type of fault must be dealt with in span and increase the complexity and
a timely manner otherwise it will lead to difficulty of repair. For these reasons every
chiller stoppage and possibly cause a safety fault should be solved immediately.
accident. The chiller can be started only by
manual reset after all faults are cleared.
b. Fault Alarm
The alarm is sent out and the chiller
remains in operation, but the fault
should be solved and reset within 24
hours or the chiller will upgrade to
fault stop. When such faults appear,
the chiller will remain in operation
and continuously alarming. Some
fault alarms (such as burner, chilled w.
Pump, cooling w. Pump and so on) will
reset automatically at intervals, then
upgrade to fault stop if reset fails. All
fault alarms will upgrade to fault stop if
faults are not solved within 24 hours.
c. Abnormal Reminding
A reminder prompt appears and the chiller
remains in operation. These types of faults
have to be repaired within 10 days, otherwise
the chiller will upgrade to fault stop.
Although the chiller will remain in operation
and continue reminding under such a fault,
some functions will be disabled when
something abnormal appears. Some other
abnormalities will upgrade the chiller to fault
alarm if several attempted automatic resets
fail. All abnormal reminding will upgrade to
fault stop if they are not solved in 10 days.
d. Abnormal Record
The abnormal record alarm will not affect
chiller operation. The chiller will record the
fault, but not remind the user on the touch
31
FAULT AND TROUBLESHOOTING
CHILLER
a. Fault stop
NO. Fault Cause Keys
1 Chilled water a. Wrong wiring or short circuit a. Check and connect the wires correctly
flow switch b. Flow switch(es) damaged or b. Readjust or replace the switch(es)
fault improperly adjusted c. Check to verify why water flow is taking place
c. Before starting the chiller, there through the chilled water circuit of the chiller and
is water passing by the chilled rectify situation *
water side
2 Copper tube a. Abnormally low /insufficient a. Stop the pumps and cut off power supply
cracks chilled water flow rate, when the immediately*
chilled water 3-stage protection b. Close water system inlet valves *
failed or improperly adjusted c. Close the 3 angle valves (for vapor, diluted
simultaneously,which can cause solution and concentrated solution) *
evaporator copper tube(s)to d. Inform service engineer immediately *
crack e. Take sample from the drain valve and
Possible reasons: check the specific gravity. If the gravity
1. Some valves in chilled water is over 1.1, water between the inlet and
system damaged outlet valves of the chiller should be
2. Chilled water pump fault collected for regeneration in the future
3. Filters on chilled water system are f. Drain the LiBr solution into a clean vessel
seriously clogged g. Open the water box cover, plug one end
4. Air is not totally vented out of of the copper tubes tightly with a cone
the chilled water system rubber plug, spot the leaking tubes with
b. Chilled water outlet temperature the positive pressure bubble detection
too low, while the chilled water method
3-stage protection failed or h. Leaking tubes can be clogged with cone
improperly adjusted, which can copper blocks when less than 3% of tubes
cause evaporator copper tube are leaking. Replacement is required
to crack when the quantity is more than 3%
c. Possible reasons: i. Check the chilled water flow switches to
1. Too much deviation of the chilled see if they work. Recalibrate or replace
water outlet temperature them
2. Chilled water outlet j. Replace the chilled water temperature sensor if its
Temperature set too low deviation is 2 F
c. Improper cleaning within the k. Solution regeneration required
water system results in copper l. Chiller re-commissioning
tube erosion m. Thoroughly analyze the reasons for the
d. Bad water quality causes pitting; fault, and take steps to make sure the
scaling can cause under deposit fault does not happen again.
corrosion and penetration of NOTES:
tube 1. The chemical cleaning method of the
e. Corrosive gas gets in to the water side copper tubes is subject to
cooling water system causing BROAD approval. It is forbidden to use a
erosion on absorber and metal brush for cleaning
condenser copper tubes 2. The cooling tower should be away from
f. Chiller vibration causes copper the chimney so as to avoid exhaust
tubes to crack entering into cooling tower. Chimney
g. Improper maintenance in winter. (Anti- should be down-wind side from of the
freeze was not added in the water cooling tower
system or water was not drained 3. Improve the machine room anti-freezing
out in the copper tubes when the condition. If the temperature is lower than 32
temperature in machine room was less F, antifreeze must be added or the water in the
than 32 F) copper tubes be completely drained
32
FAULT AND TROUBLESHOOTING
cont.
NO. Fault Cause Keys
3 Chilled a. Chilled water pumps stop a. Check chilled w. pumps power
water off b. Chilled water system lacks water or filter supply and reset it *
severely clogged b. Add water (vent air from pipes)
c. Chilled water outlet/inlet valves closed or or clear the filters *
damaged c. Check and open valves or
d. Flow switch(s) improperly adjusted or replace them *
damaged d. Readjust or replace switch(es)
4 Insufficient a. Actuating value of flow switch is improperly a. Readjust
chilled water adjusted b. Replace
flow b. Flow switch damaged c. Check the wiring
c. Open circuit or loose contact with flow d. Regain the chilled water flow
switch(es) by following methods *
d. Insufficient water flow 1. Repair or replace
1. Chilled water valve damaged 2. Repair
2. Chilled water pump fault 3. Clean filter
3. Chilled water system filters seriously blocked 4. Refill the water and vent air out
4. Air is not totally vented out of the chilled
water system
5 Chilled w. a. Incorrect temperature sensor wiring; open/ a. Check and connect the wires
outlet, HTG short circuit correctly
temperature b. Temperature module(s) damaged b. Replace temperature
sensor fault c. Temperature sensor(s) damaged module(s)
c. Replace temperature sensor(s)
6 Temperature a. Incorrect communication lines wiring; open/ a. Check and connect the wires
Detecting short circuit correctly
Module fault b. Temperature detecting module damaged b. Replace temperature module(s)
7 S-pump a. Inverter damaged a. Refer to the inverter manual
Inverter fault b. Incorrect fault feedback wiring; open circuit b. Check and connect the wires
c. Communication circuit fault or strong correctly
electromagnetic interference c. Check communication circuit
and eliminate source of
electromagnetic interference
8 No solution a. Solution pump filter clogged, wrong rotation, a. Clean filter, repair or replace
level in HTG not started or stopped by fault solution pump
(during b. S-pumps setting of maximum frequency is b. Reset s-pump frequency.
cooling) too low c. Tune down concentration
c. Concentration regulating valve is improperly regulating valve
adjusted d. Check and connect the wires
d. Incorrect level probe wiring or open/short correctly
circuit e. Replace solution level control
e. Level control damaged
b. Fault alarm
NO. Fault Cause Keys
1 Chilled/heating/ a. Incorrect temperature sensor wiring or a. Check and connect the wires
hot w. outlet, open/short circuit correctly
cooling w. Inlet, b. Temperature module damaged b. Replace temperature module
temperature c. Temperature sensor damaged c. Replace temperature sensor(s)
sensor fault
2 HTG super high a. PLC control failure. a. Check PLC control system
temperature b. Excessive deviation in HTG temperature b. Replace
sensor c. Check or replace
c. Temperature control abnormal. d. Check and recover the
d. Inadequate vacuum vacuum
3 HTG solution a. Aging of upper and lower coating of a. Replace solution probes upper
level control solution level probe leads to short circuit and lower cover
fault b. Incorrect solution level control or level b. Check and connect the wires
probe wiring correctly
33
FAULT AND TROUBLESHOOTING
cont.
NO. Fault Cause Keys
4 Cooling water a. Cooling water pumps stop a. Check cooling water pumps
off b. Cooling water system lacks water or filter power supply and reset *
severely clogged b. Add water (vent air from
c. Cooling water outlet/inlet closed or pipes) or clear the filters *
damaged c. Check and open valves or
d. Flow switch(es) improperly set or damaged replace them *
d. Readjust or replace flow(es)
5 Burner fault a. Incorrect fault feedback wiring or open/ a. Check and connect the
short circuit wires correctly
b. Burner fault b. Refer to burner manual
6 Ignition fault a. Incorrect fault feedback wiring or open/ a. Check and connect the
short circuit wires correctly
b. Burner fault b. Refer to burner manual
7 Gas leakage a. Incorrect fault feedback wiring or open/ a. Check and connect the
short circuit wires correctly
b. Interior leakage of the solenoid valve. b. Repair or replace
8 Refrigerant a. Inverter fault a. Refer to inverter manual
pump inverter b. Incorrect fault feedback wiring or open b. Check and connect the
fault circuit wires correctly
c. Communication circuit fault or strong c. Check communication
electromagnetic interference circuit and eliminate
d. Refrigerant pump get stuck or electrical fault source of electromagnetic
interference
d. Restore flexibility or replace
the pump.
9 Absorption a. Incorrect pump wiring or short circuit/ loose a. Check and connect the
pump, vent contact wires correctly
pump fault b. Pump overload, lack of phase, short circuit b. Check or replace pump
or damaged
10 Auto air vent a. Auto purge valve is not switched to vent a. Check auto purge valve
abnormal b. Actuating value setting too large (no b. Check vent valve
operation venting for long time may cause valve c. Reset vent interval
plates sealing elements to stick) d. Check solution level control
c. Vent interval short and vent probe wiring
d. Solution level control or vent probe wiring fault e. Open auto-vent manual
e. Auto-vent manual valve closed check valve (normally open
in operation)
11 AC pump fault a. Incorrect pump wiring or short circuit/ loose a. Check and connect the
contact wires correctly
b. Pump overload, lack of phase or short circuit b. Check or replace pump
c. Soft starter fault c. Check or replace soft starter
12 Cooling water a. Chilled water 3-stage protection act or is a. Check chilled water 3-stage
pump fault wrong wired protection
b. Incorrect pump wiring or short circuit, loose b. Check and connect the
contact wires correctly
c. Pump overload, lack of phase or short circuit c. Check or replace pump
d. Inverter or soft starter fault d. Check or replace inverter,
soft starter
13 Cooling fan a. Incorrect fan wiring or with short circuit, loose a. Check and connect the
fault contact wires correctly
b. Fan overload, lack of phase or short circuit b. Check or replace fan*
c. Inverter (if exists) fault c. Check or replace inverter
14 Hot water a. Incorrect wiring, short circuit or loose contact a. Check and connect the
pump fault b. Pump overload, lack of phase or short circuit wires correctly
b. Check or replace pump
34
FAULT AND TROUBLESHOOTING
c. Abnormal reminding
NO. Fault Cause Keys
1 Chilled w. inlet a. Incorrect temperature sensor wiring a. Check and connect the wires
/cooling w. outlet or open/short circuit correctly
/HTG crystallization b. Temperature module damaged b. Replace temperature module
/LTG crystallization c. Temperature sensor damaged c. Replace temperature sensor(s)
/LTHE diluted solution
inlet/vent/ambient
/control cabinet
temperature sensor
abnormal
2 Large deviation with a. Temperature sensor resistance a. Check and connect the wires
chilled water outlet value drifts correctly or replace
temperature sensor b. Incorrect temperature sensor wiring b. Replace temperature module
c. Temperature module drifting or c. Calibrate or replace
damaged temperature sensor
3 Chilled water outlet a. Chilled water flow rate is too low a. Increase chilled water flow rate *
temperature lower than b. Chilled water outlet temperature b. Increase chilled water outlet
41 F setting is too low temperature setting *
c. Cooling water temperature is too low c. Increase cooling water
temperature
4 Heating/hot water a. Thermostatic valve works abnormally a. Check thermostatic valve wiring
outlet temperature b. Water flow is too low or actuation device
over 203 F c. Large deviation in temperature b. Increase water flow rate *
sensor(s) c. Replace temperature sensor
d. Temperature sensor installation d. Move the temperature sensor to
location is too close to water heater 10m away from the water heater
5 Exhaust over a. Soot in fire tubes a. Clear soot *
temperature b. Excessive combustion b. Adjust combustion amount
c. Exhaust temperature sensor deviation c. Replace temperature sensor
too large
6 High temperature in a. Machine room overheated a. Strengthen ventilation to reduce
control cabinet b. Control cabinet fan damaged machine room temperature *
c. Improper temperature sensor b. Repair or replace
installation location c. Check and reinstall in proper
position
7 HTG over-pressure a. Poor vacuum condition a. Refer to item 13 of Abnormal
b. Cooling water flow rate is too low or Reminding
temperature is too high b. Increase cooling water flow
c. Steam angle valve opening is too rate or reduce cooling water
small temperature *
d. Scaling with cooling water copper c. Check the opening of steam
tubes. angle valve *
e. Too small LTG solution circulation d. De-scale. Plan is subject to
f. Pressure control actuating value is BROAD written confirmation
too low e. Readjust the solution circulation
g. Pressure control damaged f. Reset
h. Low or no flow in heating model g. Replace
h. Check the heating water loop
8 Cooling water flow a. Improper flow switch wiring a. Check and connect the wires
switch abnormal b. Flow switch damaged or improper correctly
setting b. Readjust or replace flow switch
c. Water flow in cooling water side c. Check the reason for the water
before chiller started flow
9 Refrigerant level a. Incorrect refrigerant level probe a. Check and connect the wires
control fault wiring or short circuit correctly
b. Refrigerant level control damaged b. Replace solution level control
c. Refrigerant box gets frozen c. Refer to refrigerant freezing
d. Refrigerant level probe upper and keys
lower covers are aging d. Replace solution level probe
upper and lower cover
35
FAULT AND TROUBLESHOOTING
cont.
NO. Fault Cause Keys
10 Refrigerant a. Poor vacuum a. Refer to poor vacuum eliminating method
overflow b. Refrigerant water polluted b. Refer to polluted refrigerant eliminating
c. Cooling water flow too low or method
temperature too high c. Increase cooling water flow or improve
d. Comprehensive solution cooling tower performance
concentration is too low d. Increase solution concentration
e. Heating capacity is too high e. Decrease heat input
f. Scaling in absorber copper tubes f. Remove scaling in absorber copper
tubes
11 Refrigerant a. Cooling water temperature and a. Increase cooling water temperature and
freezing users load are both low select energy saving operation mode *
b. Chilled water outlet target b. Increase chilled water outlet target
temperature setting is too low temperature *
c. Chilled water flow is too low c. Check the chilled water system and
increase chilled water flow *
12 Crystallization a. Cooling water inlet temperature is a. Check cooling water temperature
too low setting value; keep normal or add
b. Excessive combustion inverter to control
c. Poor vacuum b. Readjust burner and reduce combustion
d. Circulation is improperly adjusted c. Refer to poor vacuum
e. Excessive corrosion inhibitors d. Readjust circulation amount
e. Add corrosion inhibitors strictly according
to the standard
13 Poor vacuum a. Sealing element aging a. Replace
b. External vacuum valve is not closed tightly b. Check and close tightly *
c. Leakage caused during transportation, c. Conduct thorough leakage checking
whereas leakage detection not and repair to the chiller
performed at initial start, or new d. Remove the rust and eliminate the
leakage occurred during operation leakage, then repaint the leaking point
d. Leakage at welding seam caused or the whole chiller (the chiller shall be
by serious outside corrosion in vacuum when paint is applied)
e. Auto purge and air vent device e. Troubleshoot
defective f. Readjust the setting of HTG target
f. The chiller keeps running at high temperature to avoid HTG operating
HTG temperature which generates at high temperature *
non-condensable gases
14 Auto-vent a. Poor vacuum a. Refer to poor vacuum eliminating method
frequently b. Incorrect or broken non-condensable b. Check and wire correctly
probe wiring c. Replace sealing elements
c. Vent valve stuck
15 Lack of anti- a. Anti-scale agent runs out a. Add anti-scale agent *
scale agency b. Level probe fault b. Check or replace level probe
16 Lack of a. Disinfectant runs out a. Add disinfectant *
disinfectant b. Level probe fault b. Check or replace level probe
17 AC/cooling/ a. Incorrect flow meter wiring or a. Check and wire correctly
hot water open/short circuit b. Check or replace flow meter
flow meter b. Flow meter damaged or fault c. Eliminate source of electromagnetic
abnormal c. Electromagnetic interference interference
18 AC water a. Incorrect sensor wiring or open/ a. Check and wire correctly
pressure drop/ short circuit b. Check or replace Sensor
cooling water b. Sensor damaged or fault c. Eliminate source of electromagnetic
conductivity c. Electromagnetic interference interference
sensor fault
19 Internet a. Incorrect wiring or internet cable a. Check and wire correctly
monitoring not connected b. Repair or replace
abnormal b. Communication port failed c. Repair or replace
c. Network gateway abnormal d. Fix the network problem *
d. Internet is abnormal e. Reset networking parameters
e. Internet parameter setting is wrong
20 PLC/touch a. Fail to replace on time a. Replace battery and the replacement
screen low b. Poor battery quality should be done in 2 minutes
battery b. Purchase battery from BROAD
36
FAULT AND TROUBLESHOOTING
d. Abnormal record
NO. Fault Cause Keys
1 Cooling a. Poor performance of cooling tower a. Refer to cooling tower fault and
water inlet b. Lack of water leads to air in the water eliminating method
temperature c. Cooling water target temperature b. Add water (and continuously add
over upper limit setting is too high. water) *
d. Fan blade angle improperly adjusted c. Reset target temperature value *
causes motor strap too loosen d. Adjust fan blade angle or strap
2 Cooling water a. Low outdoor temperature a. Chiller stops, no cooling *
inlet temperature b. Fan actuation temperature is low b. Readjust the setting value *
below the lower c. Cooling tower fan linkage fails c. Find the cause and recover the
limit linkage control
3 HTG over- a. Poor vacuum a. Refer to poor vacuum and eliminating
Temperature b. Excessive combustion method
c. Excessive deviation of HTG b. Readjust burner
temperature sensor c. Replace temperature sensor
4 Vent alarm The same as Vent over temperature The same as Vent over temperature
5 Burner on-off a. Load change is dramatic and the a. Conduct load regulation function
frequently chillers load regulation is abnormal. commissioning accurately
b. Burner is abnormal b. Refer to 5.4 Burner fault and
c. Gas lower limit pressure switch troubleshooting
frequently turns on and off c. Improve gas pressure and stabilize or
adjust pressure switch setting value
6 Inverter a. Inverter communication port a. Replace inverter
communication damaged b. Redo the wiring
abnormal b. Communication cable abnormal. c. Replace
c. Communication converter d. Eliminating source of electromagnetic
damaged interference
d. Electromagnetic interference
7 Instantly power Voltage unstable Negotiate with utility company *
off
8 Sudden power a. Power failure a. Negotiate with utility company *
failure b. Main switch is open b. Check the main switch and restart
c. PLC control circuit fuse is burnt out the chiller *
d. Machine room gas leakage or fire c. Find the cause and replace the fuse
alarm is activated d. Eliminate the gas leakage or fire
alarm *
37
FAULT AND TROUBLESHOOTING
e. others
NO. Fault Phenomenon Causes Keys
1 Cooling Chilled water a. Poor vacuum a. Refer to poor vacuum and eliminating
capacity outlet/inlet b. Insufficient cooling method
lower than temperature water flow b. Vent air out of water system and fulfill
the rated both c. Cooling water inlet the tank with water. Check if valves
value increase and temperature is higher of water system are fully opened and
temperature than the rated value. filters are clogged. Check the pump
difference d. HTG fire off temperature model selection and rectify *
decreases; setting value is too low c. Cooling tower has poor heat dispersion
cooling water e. Chilled water flow effect. Check if cooling fan belt is
radiation or temperature loose or has fallen off. Adjust cooling
decreases measurement is fan blades angle. Check distribution
inaccurate angle and speed of cooling tower
f. Amount of added water distributor. Check if the tower
Octanol is insufficient selection is correct *
g. Chiller heating/cooling d. Reset HTG fire off temperature
switch valves are not e. Calibrate the flow meter and
fully opened thermometer. Calculate accurately
h. Refrigerant water gets chilled water flow and temperature
polluted difference.
i. Refrigerant water f. Increase by 0.3%
spray gets clogged g. Check respectively the 3 heating/
or refrigerant inverter cooling switch valves;, the steam
goes out of control angle valve must be fully open *
j. Refrigerant loss h. Refer to item 4 of this chapter
k. Comprehensive solution i. Backwash or flush R-pump filter,
concentration is too low Wash spray device when necessary.
l. Fouling in copper tubes Conduct accurate commission to
m. Combustion volume is R-pump inverter
too small j. Check and fully close the refrigerant
n. Soot in combustion bypass valve. Make sure the refrigerant
chamber and fire tubes anti-overflow control is reliable
o. Hot water is k. Drain part of the refrigerant water to
overloaded increase comprehensive concentration
l. Clean the copper tube fouling.
Detailed plan is subject to BROAD
written approval
m. Readjust burner and increase
combustion volume
n. Clean the exhaust soot and readjust
the burner using exhaust analyzer
o. Adjust according to specific condition
2 Heating Heating water a. Combustion volume is a. Check for clogged fuel system
capacity (hot water) too small filters. Readjust burner to increase
lower than temperature b. Scaling in water heater combustion rate
the rated cannot be copper tubes. b. Clean the copper tube fouling,
increased. c. Soot in combustion Detailed plan is subject to BROAD
Outlet/inlet chamber or fire tube written approval
temperature d. Poor vacuum c. Clean soot. Find the root cause and
difference e. Level in HTG is too high readjust the burner
becomes small f. Too much octanol d. Check and repair leakage, Purge
injected in HTG. vacuum
e. Lower the solution level
f. Switch to cooling, heat the solution for
2 hours, regenerate after bypassing
the refrigerant water.
38
FAULT AND TROUBLESHOOTING
cont.
NO. Fault Phenomenon Causes Keys
3 Plate heat a. Rated cooling capacity Caused by frequent a. Replace heat exchanger
exchanger drops noticeably power failure or unstable b. Redo the commissioning
mixed flow b. HTG temperature is solution level in HTG of the chiller. Make sure
obviously high and HTG the HTG solution level
pressure is low. S-pump stays long time at zone C
frequency becomes or solution level fluctuates
low and refrigerant level within an allowable range
increases noticeably c. Contact utility company
c. HTG low on solution or or prepare backup
solution level rises frequently generator to tackle the
d. HTHE crystallization is frequent power failure
reported all the time problem *
e. The concentration of HTG
concentrated solution drops
noticeably during operation.
Take the measurement
after the S-pump stops for
1 minute, the result is 3%
higher than normal
f. When in operation, S-pump
frequency changes from
operational to maximum, the
HTG concentrated solution
outlet temperature may drop
by 86 F in a short time
4 Refrigerant Refrigerant water level is a. Cooling water inlet a. Increase the cooling
water increasing. Specific gravity temperature too low water inlet temperature
polluted >1.04. Cooling capacity b. Too much solution properly *
decreases circulation causes b. Readjust the solution
HTG/LTG solution level circulation amount
to become too high c. Take out some refrigerant
and concentration water.
too weak d. Readjust the burner to
c. Comprehensive reduce the combustion
solution concentration e. Avoid sudden increase
too weak of hot water flow. By-pass
d. Excessive combustion refrigerant completely to
e. Hot water flow regenerate in addition to
increases suddenly above measures
5 Unstable HTG solution level is not in a. Improper adjustment Observe 3 times the whole
HTG zone C, or jumps between 2 of frequency process from start to stop for
solution zones frequently to zone E or b. Solution volume is 3 consecutive hours, then:
level zone A, and stays too long insufficient a. Reset S-pump frequency
in zone D or zone B. S-pump c. S-pump fault and redo the chiller
frequency drops over 30% in d. HTG solution level commissioning if
120 seconds control fault necessary
e. Poor vacuum b. Add solution and redo
the chiller commissioning
c. Repair or replace
d. Refer to HTG solution
control fault keys
e. Refer to Poor Vacuum
and Solutions
39
FAULT AND TROUBLESHOOTING
cont.
NO. Fault Phenomenon Causes Keys
6 Rupture Solution flows out a. Incorrect operation Stop the chiller immediately, cut
disk broken from flow duct of during nitrogen charging. off power, stop water pumps,
the rupture disk Nitrogen overcharged close valves and notify local
b. Copper tubes broken BROAD service organization *
c. HTG pressure increases
abnormally due to other
reasons
7 Chilled Chilled water a. Overload a. Add new chiller or reduce the
water outlet outlet temperature b. Chiller cooling capacity is load *
temperature is higher than the below the rated one b. Refer to item 1 of this chapter.
higher than target setting c. Deviation of the c. Calibrate with accurate
the target value and can not temperature sensor(s) thermometer. If deviation 2 F,
value be decreased d. Wrong parameter setting replace the temperature sensor;
deviation < 2 F, readjust the
compensation value
d. Modify the parameter setting
8 Touch No normal display a. Touch screen's power off a. Power on *
screen out on touch screen b. PLC communication failure b. Repair or replace
of order c. Touch screen fault c. Replace
d. Problem with the d. Repair or replace
connection cable e. Replace
between PLC and touch f. Check by programmer and
screen modify
e. 24V DC supply failure g. Re-input the program
f. Wrong configuration on
communication port
g. Wrong operation leads
to touch screen program
being lost
9 Big Touch screen a. Poor grounding of a. Re-ground (to a dedicated
fluctuation chiller parameters communication cable grounding electrode)
with touch display unstable b. Temperature sensor poor b. Overhaul and replace
screen data wiring c. Overhaul and replace
display c. PLC Power module fails d. Shielded wires well grounded
d. Shielded wires are poorly e. Eliminate interference and
grounded ground chiller properly
e. Interference from inverter
or high frequency from
system power
10 Canned Canned pump a. Pump motor overload a. Find the cause and reset
pump fault can not be started protection b. Check the control circuit
after chiller startup b. Control circuit fails c. Repair or replace
c. Pump fails d. Troubleshooting
d. Chiller in auto protection e. Try to notate solution pump
e. Pump is obstructed by in both directions, if it still
solution crystallization cannot be started then de-
f. Power phase absence crystallization is needed
f. Adjust power supply to normal
requirement
40
FAULT AND TROUBLESHOOTING
COOLING TOWER
NO. Fault Phenomenon Causes
1 Abnormal a. Fan improperly balanced a. Check balance
noise and b. Blade end touches the tower body b. Adjust the space between blade and
vibration c. Loose bolts tower body
d. Motor axis abnormal c. Tighten the loose bolt *
e. Pipe vibration d. Add grease and replace axis *
f. Strap is too loose e. Install pipe support frame *
f. Adjust strap
2 Current too a. Fan blades are not at the same angle a. Adjust to the same angle
large b. Motor fault b. Repair or replace
c. Bearing fault c. Replace bearing
d. Too large air output causes overload d. Adjust blade angle
e. Power supply voltage too low e. Recover normal voltage *
f. Lose phase f. Check power supply phase and
recover *
3 Cooling water a. Insufficient air flow a. Check and adjust strap, adjust fan
temperature b. Vented hot air enters tower blade angle
rising c. Absorb less air b. Improve ventilation condition *
d. Dirty filling causes asymmetric c. Improve ventilation condition *
distribution d. Clean *
e. Distribution system abnormal e. Clean sundries *
f. Strap is too loose or broken f. Adjust or replace strap
4 Cooling water a. Water collector level too low a. Check, adjust auto make up and fast
amount b. Filter screen clogged make up system
decreasing c. Insufficient water pump flow rate b. Clean
c. Repair or replace
5 Asymmetric a. Sprayer or distribution pipe broken a. Check damaged parts, clear out
distribution or clogged sundries and clean up water filter
b. Water supply volume too large or screen *
small b. Adjust water supply volume *
6 Water floating a. Cooling water amount too large a. Adjust water rate *
b. Air flow too great b. Adjust fan blade angle, reduce air rate
c. Asymmetric water distribution c. Clean up distributing basin and nozzle *
d. Incorrect installation direction of d. Readjust installation direction
filling material e. Clean up filling material *
e. Filling blocked f. Reinstall as required
f. Incorrect installation of baffle plates
OTHER PARTS
Faults and troubleshooting about burner, inverter, heat source valve, softener, auto
water treatment and other automation equipment, please refer to manuals provided
with the products accordingly.
42
MAINTENANCE
Maintenance should be completed on the following items once every 2 months for high
load, 3 months for medium load and 6 months for low load:
NO. Items Method
1 Check the a. Check the running, fault and energy consumption records of the chiller
record and b. Inquire/analyze the users energy consumption and give energy saving
feel the air suggestions to the user
conditioning c. Check the running status of the chiller and terminals, and feel the air conditioning
effect effect in different areas
2 Observe the a. Whether or not the burner starts and stops frequently
operation b. Observe for at least 30 minutes to check if the HTG solution level fluctuates
and check abnormally and noisily
parameter c. Whether or not the refrigerant level goes up abnormally
setting d. Whether or not the cooling capacity of the chiller decreases and the energy
consumption increases
e. Check whether noise and vibration of the distribution system is normal or not,
the foundation becomes flexible or not.
3 Burner a. Clean off the dust and water on the steel strip to prevent rusting
b. Clean burner fan blades and oil pump filter; check the fan motor bearing
c. Wash the atomization tray, nozzle (oil type), ignition electrode and the residual
carbon on the ion flame detector; make sure they are not damaged and are
in the right position
d. Clean the flame detector and confirm that the photosensitive part is transparent
and not damaged
e. Check the excess air coefficient: gas type 1.18~1.25, oil type 1.13~1.20
4 Solution and a. When the solution pump is running, the solution should be clear and transparent
rust as observed from the sight glass
b. Observe the rust status of the copper tubes and steel plates. The vacuum must
be confirmed when something abnormal is found
5 Vacuum a. Confirm the vacuum of the chiller by bubble comparison method
detection b. Check whether or not the vacuum valve cover, valve cork and the valve
before compound gauge is closed
c. Check the reliability of auto purge/ air vent device
6 Control a. Check heating and aging status of each component in the control cabinet
cabinet b. Check whether or not the touch screen displays the right PLC signal
c. Check whether or not the control cabinet fan runs well; clean rust on the fan filter
7 Canned Check the temperature rise, cavitation and abnormal noise of the motor. Check
pump and whether the inverter works normally
inverter
43
MAINTENANCE
Following maintenance items: For high load every 4 months, medium load every 6
months and low load every 12 months.
NO. Items Method
1 Water side of a. Take out the fouling detector for the cooling/chilled water, open the soft
copper tubes connector for heating/hot water to check the fouling with the copper tubes.
If fouling occurs, clean according to a method officially approved by BROAD
b. Check the reliability of water quality stabilizer charging, water drain, water
makeup devices and their control
2 Fuel filter Clean
3 Action test for a. Adjust the water pump inverter or the outlet valve after the pump starts.
flow switches Check whether the flow switch closes when the flow rate is above 70% of the
rated value and whether it disconnects when the flow rate is below 60% of
the rated value (40% for cooling water)
b. Confirm the start/stop sequence of the cooling and chilled water pumps
4 HTG a. Make sure the pressure control actuating value is set correctly (factory setting)
temperature b. Check if protection is actuated during Nitrogen charging for repair or during
and pressure maintenance
control c. Make sure when HTG temperature >340F, HTG temperature control actuates to shut off the
burner
5 Gas train air a. Check valve train joints leakage by soap solution. Charge Nitrogen to
tightness & maintain pressure at valve train per burner manual instructions
upper/lower b. Check performance of gas valve leakage detecting system
limit pressure c. Ensure that two stages of gas solenoid valves can both open/close reliably
switch d. Test whether the burner is stopped when gas supply pressure is beyond
upper/lower limit
6 Protection test Check the possibility of accidents which may lead to stop fault
7 Rupture disc Replace
and sealing
elements
Following maintenance items: For high load every 2 years, medium load every 3 years
and low load every 5 years.
NO. Items Essentials of the method
1 HTG solution level probe and UDK upper/lower jacket Filter the solution with a precision filter
2 Vacuum sealing elements in high temperature area Replace
3 Sealing materials in front/rear flue chamber Replace
4 Sealing gasket for heating/hot water box cover Replace
5 Burner Replace the nozzle, ion flame detector
and motor bearing
Following maintenance items: For high load every 5 years, medium load every 7 years
and low load every 10 years.
NO. Items Essentials of the method
1 Burner Replace the oil pump, ignition electrode
and solenoid valve coil
2 Inverter Replace
3 Turbulator Replace
4 Cold/heat insulation materials Replace
44
MAINTENANCE
b. Routine maintenance
The maintenance interval of some items has nothing to do with the running load of the
chiller. This maintenance model is called routine maintenance.
Annual maintenance
NO. Items Method
1 Solution analysis Fully dilute the solution inside the chiller, then BROAD service engineer test
the solution at site, and issue a report of Site Testing of LiBr Solution. If the test
cannot be finished at site or the user needs a more detailed and professional
report, sample around 50 ml and send it to BROAD lab for testing by post or
express. The lithium molybdate solution cannot be tested at site, sampling the
solution around 50 ml and sending it to BROAD lab is required
2 Control a. Check for heat radiation inside the components and aging
cabinet(include b. Check whether or not the control cabinet fan runs normally and filters fan dust
the control of c. Make sure the inverter is running normally
water system) d. Check the reliability of the wiring terminal connections inside the control
cabinet. Fasten if they are loose. Clean dust
e. Check and make sure the temperature of the surrounding area is between 41 ~ 110 F,
and well-ventilated
3 Soot in the Open auto pressure escape to check soot in HTG fire tubes. Check if the
fire tubes and condensate drain pipes at front fuel chamber can drain smoothly. If soot
combustion exists, it should be cleaned and the excess air coefficient of the burner should
chamber be readjusted
4 Flue duct and Check and clean
chimney stack
5 Chiller paint Check the chiller for external rust. If there is rust, clean the rust and paint the repaired part
or the whole chiller (note: inside the chiller should be vacuum and normal temperature
when paint is being applied)
6 Water box and Open all the water box covers to check whether there is rust withinthe tube
tube sheet sheet and inside the water box
7 Chilled/heating Analyze the water. Soften it if the quality standard is not met
water quality
8 Oil box Completely clean dirt inside the daily oil tank and oil storage tank. Check
whether the oil level probe works well
9 Grounding Chiller grounding resistance should be 4, all motor insulation resistance (to
earth) should be 0.5M
10 Water pumps a. Check if the pump temperature increase is normal, The pump current must
be less than the rated value.
b. Check the running noise and vibration; also check if there is abnormal
noise, cavitation, and check the foundation to see if it is flexible or not.
c. Make sure the control system works well and flow rate is sufficient.
d. Check the lubricant oil appearance, oil temperature, oil quality. There should
be no oil emulsion and impurities. If necessary, replace or add new lubricants.
e. Check the electrical wiring terminals and their reliability. Make sure the
grounding resistance is 4, and insulation resistance is 0.5M
f. Check whether the water system is full of water and sealing is normal or
not. Check the pressure drop between the inlet/outlet and calibrate the
pressure gauge, check the painting of the pump, repaint if it drops.
h. The ambient temperature may be lower than 34 F. If so, add antifreeze, or drain the
water inside the pumps.
11 Pipes, valves a. Check water leakage at connection joints and the valve seals
and accessories b. Check whether there is any damage in heat and cold insulation or paint.
Check whether the support is strong enough
c. Check whether the valve switch is flexible,
d. Clean the dirt in the pipes, valves and accessories
45
MAINTENANCE
cont.
NO. Items Method
12 Flow meter a. Confirm the displayed data on flow meter is the same as on the touch
screen
b. Clean the surface of flow meter with proper tools (do not use chemical method to wash).
c. Check ambient conditions (air flow, humidity); check if the sealing of the
connections is good or not, and if cable joints and fasteners are loose or not.
d. Check whether or not the grounding is good, whether there is any
interference or anti-interference influence.
13 Filter header Drain water and clean up filter and impurities in the boxes
and outlet box
14 Softener a. Brine level should reach 1 / 3 of the brine tank, otherwise add industrial brine,
lodized brine and powdered brine should not be used, otherwise, they will
affect the performance and life span of the exchange resin
b. Check and clean the filter of the inlet. Make sure that water pressure is not
higher than 0.6MPa
c. Make sure the ambient temperature is above zero and inlet temperature is below 104 F
d. Check the quantity of resin and make up the resin around 5%-10% every year
e. To avoid anti-dehydration, freeze and breeding germ of germen the resin, you should fill
up with brine when the equipment is not in use
15 Automatic a. Inspect records of adding and quantity of the chemicals; add some if
dosing device insufficient. Note: To avoid direct contact with the chemicals, please take
protective measures, such as wearing masks, gloves and safety glasses
b. Check the strainer of the chemicals supply valve on the bottom of tube, and
clean if dirty. Cleaning procedure: disconnect the tube connections which
are connected with the anti-sludging pump or biocide pump, and lift the
tubes with the fixer from the drum, then clean the strainer of valve on the
bottom of the tube with clean water or neutral solution
c. Check if pump head, pipe connections are in working order
16 Cooling tower a. Check and clean the sprayers and strainer of cooling tower
b. Check the shaft of reducer, if necessary, add some lubricating oil (which
tends to use Lithium Grease # 3) from the filling hole. Make sure that oil does
not enter the cooling water; otherwise it will affect heat transfer.
c. Check fan driving belt, and make sure it is not tight or loose. Too tight may
lead to damage of bearings, while too loose may lead to overheating or
sliding. Make sure that oil does not enter the cooling water; otherwise it will
affect heat transfer.
d. Check fan blade damage or corrosion, clean fan blade and make sure
vibration and noise are acceptable. Check the state of filler, clean inside of
the cooling tower
e. Check the electrical wiring terminals and reliability, the grounding resistance
should be 4, and insulation resistance of 0.5M
f. Check and fasten all steel structure, connecting bolts of cooling tower and impellers. Make sure
everything is fastened tightly. This will help decrease the noise and vibration in the cooling
tower. Check whether the make-up water valve, overflow tube, drain valve are normal or not
g. Open all the drain valves and make sure there is no water in the system
during cold winter
17 Expansion tank a. Check automatic make up water valves, signal pipes, overflow pipes, drain valves and
insulation are check that insulation is in good condition
b. Clean and repaint where necessary
46
MAINTENANCE
cont.
NO. Items Method
16 Control cabinet fan Replace
17 Touch screen Replace
18 Actuator of motor valve Replace
19 Actuator of auto purge motor valve Replace
20 Actuator of Refrigerant W. bypassing Replace
valve
21 Actuator of heat source valve Replace (Including steam, hot water, electric gas valve)
22 Actuator of cooling W drain valve Replace
23 HTG pressure control Replace
24 HTG temperature control Replace
25 Cooling tower Replace nozzle, packing, and a ball valve and vent valve
26 Fan control cabinet Replace
27 Inverter fan Replace
28 Soft Starter fan Replace
29 Cold & Heat insulations Replace
30 Auto vent valve Replace
31 Rubber isolator Replace
32 Rubber soft connector Replace
33 Auto dosing device Replace metering pump (except the diaphragm), four-
function valve, brine tank, dosing valve, liquid level probe
34 Softener Replace water pressure gauge, brine safety valve, water
distributor, central tube , brine tank, brine plate, brine
well, cover and plane
35 Atomization tray of burner Replace
49
MAINTENANCE
50
MAINTENANCE
51
MAINTENANCE
NON-OPERATION MAINTENANCE
If the chiller needs to be stop for more b. Cooling water system antifreeze
than 8 months due to some special Completely drain cooling water from the pipes,
reasons, non-operation maintenance cooling towers and copper tubes inside the chiller
should be carried out. and especially, make sure no water remains in the
1. Shut off all inlet/outlet valves, and open the lower positions of system.
water drain valves to drain out the trapped c. Domestic hot water system antifreeze
water inside the copper tubes. 1. Without secondary heating exchange, if the
2. Charge the nitrogen gas of high purity ambient temperature is lower than 34 F, and if
(above 99.995%) into the chiller to domestic hot water is not in use in winter, you
0.01~0.02Mpa and check periodically must open the drain valve to drain all water
(every 1~2 months) for the pressure out of the system. This will help to prevent the
drops. domestic hot water system from freezing.
3. Check carefully whether all valves 2. With a secondary heating exchange system, if
are closed tightly, screws are properly domestic hot water is not in use in winter, it
mounted, sight glass covers are is not necessary to drain out all water from
covered and fuel supply valves are shut the system. This will help prevent water
off. pipes and copper tubes from corrosion. If
4. Cut off the power supply after informing ambient temperature is lower than 34 F,
BROAD Remote Monitoring Center. antifreeze needs to be added into the first
5. The doors and windows of the heating exchange cycle system, and its
machine room should be steady and freezing point should be lower than the
reliable, and cannot be used for other minimum ambient temperature. However,
construction purposes. Unauthorized water in the secondary cycle system has to
personnels are prohibited to access into be drained out.
the machine room. The burner, tools,
spare parts and documents should be d. Unit antifreeze
well kept. 1. If ambient temperature is lower than 34 F,
6. Keep the humidity and temperature but antifreeze has been added, water in the
of the machine room normal. Some copper tube inside the unit does not need
dehumidification measures shall be to be drained out. If no antifreeze has been
taken for electrical parts, e.g. the added, drain the water to prevent the unit
control cabinet. from freezing.
7. A comprehensive maintenance and 2. When the ambient temperature is lower than
inspection is necessary before restarting 34 F, because of the residual refrigerant
the chiller. water in the refrigerant water pump,
refrigerant water pressure-drop pipe and
condenser pressure-drop pipe, when
ANTIFREEZE IN WINTER the ambient temperature is lower than
Before winter every year, users should 34 F, freeze may occur. In this case, pass
double-check the unit and system to refrigerant water into the absorber and
confirm that they are in accordance with keep the unit in a vacuum state.
antifreeze requirements. If not, take the 3. Long-time-disabled chillers in a
following steps to prevent a unit or system nitrogen state as well as chillers that
from freezing. have not yet been put to use but
a. Air-conditioning water system antifreeze have been previously tested on
When the air-conditioning system is disabled the testing platform and delivered
and if the ambient temperature may be lower with nitrogen in the system, should
than34 F, water in the system pipes needs be charged with some LiBr solution
to be drained out completely. Add antifreeze in refrigerant water box from
to the system, the antifreeze freezing point refrigerant water sample valve. The
should be lower than the minimum ambient best concentration of solution in the
temperature of the system to ensure that the refrigerant water box is 52%.
water system and chiller have no freezing
accident. This step will also help prevent water
pipes and copper tubes from corrosion.
52
MAINTENANCE
53
ENERGY SAVING MANAGEMENT
54
ENERGY SAVING MANAGEMENT
cont.
NO. Item Method Effect
9 Ensure insulation of the Check the insulation periodically Avoids energy loss and
entire system is in good equipment damage from poor
condition insulation performance
10 Avoid leakage of Check the pipes periodically Save water and energy
water pipes
11 Cycling mode of Closed circuit is recommended Reduce electricity
water system consumption, help anticorrosion
and anti-scaling and extend life
span of pipes
12 Distribute cooling The water supplying temperature can be Avoid unreasonable energy
(heating) load lowered and flow rate increased if the waste
reasonably temperature humidity requirement is low in the
room, and vice versa. Adjust the fresh air rate
according to different requirements and clean
the air filters periodically.
13 Divide water pumps Arrange pumps according to different pressure Avoid excessive pressure loss in
into different sections drop areas. For example, separately design closed the low-level area, and reduce
loops for high-level areas and low-level areas. unnecessary water pump use
14 Reasonable air duct Choose reasonable air duct size according to Avoid unreasonable energy loss
system economical air speeds, avoid air leakage of during air transportation
equipment or air ducts, avoid air short-circuit
between supply and return air and clean the
air ducts on time
15 Ensure all equipment Solve equipment problems on time Avoid increased energy
is well maintained consumption
16 Eliminate heat Install air return windows above the lights so Reduces the room load so that
generated by room that the heat of the lights will be taken off by the air supply can be reduced
lights by utilizing a the return air and power for air supply can
return air system also be reduced
17 Manage doors and Prohibit the opening of doors and windows Avoid heat loss
windows strictly when the air conditioning system is working. Use
an infrared ray sensing automatic door, and
also the door curtain
18 Use a cold-light or Install energy efficient lights. Reduce indoor load
natural-light system
19 Improve the Reduce the area of windows. Use vacuum Reduce indoor load
thermodynamic heat-insulated glass or film plated reflecting
performance of the glass in the windows. Use sealing bar and heat
building insulating window curtains. Use a screen on
the building roof. Use heat insulation materials
with good performance on heat reflecting for
outdoor envelope
20 Use 100% automatic The air conditioning system will adjust all Heavy energy waste due to
and intelligent equipment according to load, so that best poor operations will be avoided
control for air performance is achieved at all times
conditioning system
21 Lower indoor Summer: When the indoor temperature is
temperature and No less than 79 F, humidity 40% to 60% adjusted from 79 F to 83 F in
humidity standards Winter: summer, the cooling load can be
No higher than 68 C, humidity 35% reduced by 20% When the indoor
temperature is adjusted from 68 F
to 65 F, the cooling load can be
reduced by 30%
22 Clean all kinds The filters of the cooling water system and fuel Avoid low heat transfer
of filters in the air system should be cleaned at least every 3 efficiency
conditioning system months. The filters of the chilled (heating) water
periodically system, and indoor units should be cleaned
at least every one year or less. The cleaning
interval should be shortened if the system is
new, depending on water quality material of
ducting, etc.
56
SERVICE INFORMATION
57
SERVICE INFORMATION
Contact
Country/District Tel/Fax E-mail
Headquarter 0731-84086139 / 0731-84611356(F) serviceinfo@broad.net
The United States 001-2016783010 / 001-2016783011(F) Yangdezhi@broadusa.com
Europe 0033-134430788 / 0033-134430825 Broadeurope.lh@wanadoo.fr
0033-134430657 / 0033-134430703(F)
58
LIBR SOLUTION PERFORMANCE CURVE
59
MISSION OF BROAD SERVICE ENGINEERS
The mission of service engineers is to ensure there is no downtime to the chiller during its life span,
energy efficiency is not lower than 95% of its design level, and air purification function of BROAD
terminal retains its high level for the lifetime of the chiller.
To achieve this mission, service engineers should love users and cherish the global environment. All
the engineers should understand that if a chiller shuts down, it will cause users a great loss which may
even exceed the cost of the chiller; if the energy consumption exceeds the standard, it will not only
affect the users economic interest, but also increase greenhouse gases as well---8 kilogram oil or 15
m3 natural gas or 19 KWH waste per year equal to cutting down a big tree which absorbs 18.3kg of
CO2 annually. Besides, the disabler of purification function will result in great expenses for users to
buy purification device--which have more value if the investment used to improve the users health. All
these situations will be completely against the users expectations on BROAD.
To achieve this mission, service engineers should love BROAD, deeply appreciate the service essence
of Broad. Every service engineer should understand that if the downtime, energy waste or purification
disablement occurred, not only the BROAD brand which is built by all BROAD staff hardwork will be
ruined, but also the trust from BROAD on them.
To achieve this mission, service engineers have to study hard, to master testing,
maintaining, energy-saving running and air purifying knowledge, and also consolidate
and update these knowledge through annual refresher training.
To achieve this mission, service engineers have to be able to be aware of the defects in
product design and manufacturing and also can report to the production department
in time. Only if each engineer takes an active part in quality improvement, the products
can be developed constantly.
To achieve this mission, service engineers have to work hard rigorously everyday,such
as making regular maintainance plan,managing well tools and repair spare
part,monitoring the operational condition of chiller, ensuring the precise maintainance
and technology upgrade proceed as planned. Avoid any urgent repair after
breakdown of chillershave happened or any maintainance after obvious weakening of
energy efficiency and purifying capability because no matter how speedy the repair
and maintainance is, it cannot make up for the customers' loss.
To achieve this mission, service engineers have to find out any defect in design and
installation of the userssystem timely and precisely, and help users to slove them. They
have to take the responsiblity and be initiative on supervising users to take regular
maintainance of the machine,and to conduct energy-saving management well. We
should always take the users system as our own.
To achieve this mission, service engineers have to build close and deep relationship
with users, to ensure that the more BROAD products they use and longer the life span
of these products, the more trust they have on BROAD. Every engineer has to keep in
faith that if you fulfill your mission, and build good relationship with users, customers will
take BROAD as their first choice, or even most of them will consider BROAD as their only
choice. Hence, the BROAD ideal will be realized.
All the service engineers, the great mission is on your shoulder!
80g
To preserve forest
and water resources,
BROAD Town, Changsha, China please follow us to
Tel: +86-731-84611352 use thin, unlaminated
Fax: +86-731-84611356 printing papers.
Email: serviceinfo@broad.net 2012.08 1st edition No.: 5,000
www.broad.com BY258-12 C 2012