New 819
Equipment YK Chillers - Mod H, G, F, D, C
Affected: YMC2 Chillers - Mod A and B
Service
Information Retrofit of R-134a YK System to R-513A
• Confirm software version Y.OPT.01.03.308 or Y.OPT.01.00C.308 or greater is loaded into the OptiView
Control panel.
• Select the refrigerant type to R-513A.
2 JOHNSON CONTROLS
SI0389 (819)
WARNING: Do not charge liquid refrigerant into the suction line. This can cause irreversible
damage to the compressor. Use the manifold gauges or a throttling valve to flash the liquid
refrigerant to a vapor prior to entering the suction line.
The chillers will require a similar charge size of R-513A as the original R-134a charge. The optimum charge
will vary depending on the system design and operating conditions. The initial charge should be approximately
85% of the standard charge size for R-134a. After startup and adjustment, the final charge amount will be ap-
proximately 97% of the R-134a charge.
8. Start Up System and Check Operation
Monitor and adjust the liquid level sensor to 50% level of sight glass to achieve the rated discharge superheat
and approach temperature in the evaporator and condenser. Expect the discharge superheat and approach tem-
peratures to be the same as when the unit operated on R-134a.
When the unit is shutdown, the refrigerant charge level must be checked after the pressure and temperature
have equalized between the condenser and evaporator. This may take 4 hours or more after the compressor and
water pumps are stopped. The level should visible in the sight glass. Monitor oil levels in compressor. Add oil
as required to maintain proper levels.
9. Label System with New Refrigerant
Change the chiller nameplate and labelling.
10. Provide customer with new documentation.
(Source: These R-513A Retrofit guidelines were developed by The Chemours Company FC, LLC.)
JOHNSON CONTROLS 3
SI0389 (819)
48
108
36
136-15
LD27114
• Where can I order the Liquid Level Sensor from? Contact your local Johnson Controls service office.
• What is the new Liquid Level Sensor part number that I need to order? 025-48615-006, -008, -009 or
-012. This is based on the original R-134a insertion probe length.
• Where can I order the new nameplate and label kit from? Baltimore Parts. The R-513A label kit part
number is 335-26652-000. These stickers need to replace the R-134a labels with a new labels stating R-513A
wherever applicable on the unit. The nameplate part number can be found on the lower right corner of the
current chiller nameplate. This will come blank and information will have to be added to the new nameplate.
• Do I have to change the software on site? Not always. The software may need to be changed for LDxxxxx units
manufactured before January 1, 2017. The R-513A option is available in software on units manufactured after
January 1, 2017.
4 JOHNSON CONTROLS
SI0389 (819)
• How can I get revised documentation? EG and O1 Manual? Currently the R-513A option is available
as SQ, so the O1 and EG is not updated. Send an email request along with the chiller PIN to BE-ChillerSer-
viceLiterature@jci.com. If you have a project then please contact P&D or Product Management to help you
prepare the documentation update.
• Can R-22 YK units be converted? No. R-513A is not a viable conversion solution. The unit will not meet
performance or capacity.
JOHNSON CONTROLS 5