160 88-Om1
160 88-Om1
160 88-Om1
Safety symbols
The following symbols are used in this document to alert the reader to specific situations:
DANGER
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not
taken.
WARNING
Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment
if proper care is not taken.
CAUTION
Identifies a hazard which could lead to damage to the machine, damage to other equipment or
environmental pollution if proper care is not taken or instructions and are not followed.
Note: Highlights additional information useful to the technician in completing the work being
performed properly.
External wiring, unless specified as an optional connection in the manufacturer’s product line, is
not to be connected inside the control cabinet. Devices such as relays, switches, transducers and
controls and any external wiring must not be installed inside the micro panel. All wiring must be in
accordance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage or problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warning will
void the manufacturer’s warranty and cause serious damage to property or personal injury.
Revision notes
Revisions made to this document are indicated in the following table. These revisions are to
technical information, and any other changes in spelling, grammar, or formatting are not included.
Table 1: Revision notes
Affected pages Description
8 Updated title of Centrifugal Chiller to Air-Cooled Chiller in Associated literature
section
Associated literature
Table 2: Associated literature
Manual description Form number
Installation and Reassembly 160.88-N1
Unit Installation Checklist and Request for Startup 160.88-CL1
Unit Startup Checklist 160.88-CL2
Field Connections Diagram 160.88-PW1
Field Control, Wiring, and MBC Diagrams 160.88-PW2
Air Cooled Chiller Long Term Storage 50.20-NM7
All Products - Replacement Parts Electrical Connectors 50.20-RP1
All Products - Replacement Parts Fittings 50.20-RP2
Nomenclature
Figure 1: System nomenclature
System components
The YORK Model YVAM Centrifugal Liquid Chiller is completely factory-packaged and includes the
following components:
• Evaporator
• Condenser
• Condenser fans
• Condenser fan variable-speed drives (VSD)
• Compressor
• Motor
• VSD
• Battery power panel
• OptiView™ control center
• All interconnecting unit piping and wiring
See Figure 5, Figure 6, and Figure 7 for YVAM chiller components.
Compressor
The compressor is a single-stage centrifugal type powered by a hermetic electric motor, on a
common shaft with a cast aluminum, fully shrouded impeller. The compressor has no inlet guide
vanes and uses a variable geometry diffuser (VGD) for capacity control.
Heat exchangers
The evaporator shell is fabricated from rolled carbon steel plates with fusion welded seams. Heat
exchanger tubes are internally enhanced type.
Evaporator
The evaporator is a shell and tube, hybrid falling film, and flooded type heat exchanger. A
distributor trough provides uniform distribution of refrigerant over the tubes in the falling film
section. Residual refrigerant floods the tubes in the lower section. Suction baffles are located above
the tube bundle to prevent liquid refrigerant carryover into the compressor. A 2 in. liquid level sight
glass is located on the side of the shell. The evaporator shell contains dual refrigerant relief valves.
Condenser
The 10 condenser sections have a microchannel design and consist of a tube and fin design.
Each condenser section has two cooling fans that are speed controlled from the chiller control
panel and use VSD technology to operate the fans. Refrigerant sub-cooling is accomplished in the
condenser section. Refrigerant relief valves are located on the system discharge piping that feeds
the condenser sections with refrigerant isolation valves as standard options.
Waterboxes
The removable compact waterboxes are fabricated of steel. The design working pressure is 150
psig (1,034 kPa) and the boxes are tested at 225 psig (1,551 kPa). Integral steel water baffles
provide the required pass arrangements. Stub-out water nozzle connections with grooved
connections, which are a standard option, are welded to the waterboxes. These nozzle connections
are suitable for groove type couplings, welding, or flanges, and are capped for shipment. Plugged
3/4 in. drain and vent connections are provided in each waterbox.
Power panel
The power panel includes the uninterrupted power supply and power storage battery. These work
together to feed essential electrical loads if the chiller shuts down due to the loss of main chiller
power.
CAUTION
Isolation of the refrigerant in this system must be performed by a qualified service technician.
Use the ± button to enter negative values and select AM/PM during
time entry.
Capacity control
The major components of a chiller are selected to handle the required refrigerant flow at full load
design conditions. However, most systems are required to deliver full load capacity for a relatively
short time while the unit is in operation. A means exists to modulate capacity for other loads.
The speed at which the compressor rotates establishes the pressure differential that the chiller can
operate against. This is referred to as lift. Speed must always be maintained above the minimum
necessary to create the lift required for the pressure difference between the condenser and
evaporator, regardless of load. Below that speed, gas surge occurs. That pressure difference is a
function of the LCHLT, and the condensing temperature, and the heat transfer between those two
systems and the refrigerant.
Smart Freeze
The Smart Freeze feature prevents nuisance chiller shutdowns due to brief periods of chilled liquid
flow fluctuations or other brief operating conditions that would normally cause Low Evaporator
Pressure Safety shutdowns. With this feature enabled and activated, the chiller can ride through
these temporary conditions. Also, this feature allows the LCHLT setpoint to be set as low as 36.0ºF
(2.2ºC). Smart Freeze protection can be enabled or disabled at the keypad by a service technician. It
cannot be used in brine cooling mode.
Smart Freeze protection uses the Evaporator Refrigerant Temperature as one of the variables to
determine when freezing is imminent. The basis of this feature is that the chilled liquid contains an
amount of heat that cannot be eliminated immediately. As a result, it requires a certain amount of
time for the liquid to change to a solid. During this period of time, those parameters that determine
when solidification occurs are evaluated and the shutdown is based on the accumulated time below
the freeze temperature.
Pre-starting
Before starting the chiller, make sure that the display shows the message SYSTEM READY TO
START. The panel can only start when line power is available to the VSD transformers and the UPS
battery in the power panel is present and connected with the battery disconnect switch closed.
CAUTION
After periods of waterside maintenance or prolonged shutdown, vent any air from the chiller water
boxes before starting the water pumps. Failure to do so can result in pass baffle damage.
Start-up
If the chilled water pumps are manually operated, start the pump. The Control Center does not
allow the chiller to start unless chilled liquid flow is established through the unit. If the liquid pumps
are wired to the Microcomputer Control Center pump run contacts, the pump automatically starts
instead.
Note: The coolant temperature inside any Johnson Controls-supplied liquid-cooled motor
starter must be maintained above the dewpoint temperature in the equipment room
to prevent condensing water vapor inside the starter cabinet. Therefore, an additional
temperature-controlled throttle valve is needed in the flow path for the starter heat exchanger
to regulate cooling above the equipment room dewpoint for applications using cooling
sources other than evaporative air-exchange methods, such as wells, bodies of water,
and chilled water. The temperature control valve must be the type to open on increasing
drive coolant temperature, fail-closed, and set for a temperature above dewpoint. It can be
requested as factory-supplied on a chiller order by special quotation.
The Start/Stop control depends if the chiller Control Source is set to Local or to one of the Remote
types from the chiller Setup > Operations screen. Start is operated under the following conditions:
• Only the keypad when the chiller is set to local mode
• Remotely through digital inputs in digital or analog remote mode, but the local keypad start
must be pressed initially to enable the run permissive
• By the SC-EQUIP in BAS (ISN) remote mode, but the local keypad start must be pressed
initially to enable the run permissive
To start the chiller, press the Start button on the Home Screen on the display panel. In Local control
source, the chiller then starts. In remote ISN, analog, digital, or modem, a remote start command
must also be provided to the correct input connection.
When the control is changed to local mode from any other source, it will remain in Run if already
running or remain in Stop if already stopped. A hardware Safety Stop button is also located on the
side of the panel.
The chiller will start if the following conditions are met:
• Leaving Chilled Liquid Temperature is above the setpoint
• Chilled liquid flow is established
• Condenser liquid flow is established
Chiller operation
Upon start request, the following occur in sequence:
1. Chiller's system pump run contacts close
2. VSD pre-charges, approximately 12 s
3. VSD pre-regulates, approximately 3 s
4. The motor runs
The chiller varies capacity to maintain the leaving chilled liquid temperature setpoint by a specific
sequencing of optional hot gas bypass, variable geometry diffuser, and compressor speed.
Throughout capacity control, the compressor speed is maintained above the minimum required
for the prevailing head condition, to avoid surge. Otherwise, the device maintaining capacity is
controlled by a proportional-integral-derivative control based on leaving chiller liquid temperature.
Pressure and motor current overrides also apply as necessary to maintain operating limits.
The Input Current limit threshold value is determined from several settings, depending on the
chiller control source selected according to the following table.
Table 5: Input current limit threshold
Control source Active input current limit threshold
Lowest of:
Local • Local Input Current Limit setpoint (% Input Job FLA)
• Pulldown Input Current Limit (when active)
ISN Remote Input Current Limit setpoint (comms)
Lowest of:
• Local Input Current Limit setpoint (% Input Job FLA)
Analog remote
• Analog Remote Input Current Limit setpoint
• Pulldown Input Current Limit (when active)
Lowest of:
• Local Input Current Limit setpoint (% Input Job FLA)
Digital remote
• Digital Remote Input Current Limit setpoint
• Pulldown Input Current Limit (when active)
Regardless of which method is used to select the preferred LCHLT, the chiller controls to its own
Active LCHLT Setpoint. The Active Setpoint is a target to the programmed setpoint. When the
chiller is not running, the Active Setpoint is set to Entering Chilled Liquid Temperature minus a
programmable offset, default 5°F (-15°C), but not adjusted to less than the programmed LCHLT
setpoint. When the compressor motor starts, the Active LCHLT Setpoint is ramped from this value
to the programmed LCHLT Setpoint at the programmable LCHLT Setpoint Ramp Rate, default 0.1°F/
s (-17.7°C/s). This keeps the chiller from undershooting the setpoint excessively during pulldown.
Any time the programmed setpoint is changed during operation, the Active Setpoint is ramped to
the new value at this rate.
1. Press the soft Stop button on the Home screen of the OptiView panel if in Local control or
send a stop command through the remote system if in Remote or BAS control. If the chiller is
in a remote-control source and the local soft Stop button is used to stop the chiller, the Start
button must be pressed before the chiller will again permit starts through the remote source.
In the event of an unusual circumstance requiring immediate stoppage, a safety stop switch
is located on the side of the control panel. Normal stop eases the driveline to stop and must
always be used instead of the safety stop during regular operation.
2. Stop the chilled water or condenser water pumps if they are not wired into the
Microcomputer Control Center, in which case it will shut off automatically. The actual water
pump contact timing operation is dependent upon the selection on the Setup screen.
3. Open the switch to the cooling tower fan motors, if used.
Result
The OptiView Control Center can be programmed to start and stop automatically for a maximum
of once each day whenever required. See Schedule screen in OptiView control center functions and
navigation.
Safety stop
When depressed, the chiller will not run under any condition. For safety reasons, this position is
required for many maintenance tasks to be completed. The safety stop button must be rotated
clockwise to release the stop condition. The safety stop is not intended for normal shutdown of
the chiller. If it is used, an immediate stop occurs, which bypasses the programmed controlled
shutdown.
Operating logs
A permanent daily record of system operating conditions (temperatures and pressures) recorded at
regular intervals throughout each 24-hour operating period must be kept. Automatic data logging
is possible by connecting the optional printer and programming the Data Logging function. An
optional status printer is available for this purpose. Figure 10 shows an example log sheet used by
Johnson Controls Personnel for recording test data on chiller systems. Log sheets are available in
pads of 50 sheets and can be obtained through the nearest Johnson Controls office.
Fault shutdowns
The chiller is programmed to shut down on two kinds of fault conditions:
• A Cycling fault allows the chiller to automatically restart when the condition clears.
• A Safety fault requires the cause for the condition be determined and resolved before
restarting. When a Safety fault occurs, press the Clear Faults button on the panel Home
screen to restart the chiller. When the condition is cleared and the Clear Faults button is
pressed, the chiller restarts unless the local Stop button was pressed, or the remote run
command ceased.
• Test all system joints for refrigerant leaks with a leak detector. If any leaks are found, they
must be repaired before allowing the system to stand for a long period of time. During long
idle periods, check the tightness of the system periodically.
• Power to the chiller must remain energized so that the UPS panel can maintain the battery
health during the prolonged idle period. This prevents battery failure.
WARNING
Failure to follow required freeze protection protocols can void the warranty.
If the YVAM is exposed to subfreezing ambient temperatures at any time during its life, it is critical
to protect against evaporator freeze damage. The YVAM chiller can be equipped with features to
prevent freeze damage to the evaporator. These features require continuous power to the chiller
control panel, chilled fluid circuit pumps, and evaporator heaters to prevent damage from freezing.
If continuous power cannot be guaranteed or chilled fluid flow cannot be provided during periods
Note:
The minimum chilled water flow rate is for full load selections. Variable primary flow ratings
(1)
as low as 50% of the minimum are permitted. Glycol limits are higher. Contact your Johnson
Controls sales office for ratings and further information.
Shipping and operating weights are shown for the base unit. Selected options can add
(2)
weight. Contact your nearest Johnson Controls sales office for weight data.
Display only
Values in this group are read-only parameters of information about the chiller operation. This
type of information may be represented by a numerical value, a text string, or an LED image. For
numerical values, if the monitored parameter is above the normal operating range, the high limit
value is displayed along with the greater than (>) symbol. If it is below the normal operating range,
the low limit value is displayed along with the less than (<) symbol. In some cases, the value may be
rendered invalid by other conditions and the display uses Xs to indicate this.
Programmable
Values in this group can be changed by the user. In order to program any setpoints on the system,
the user must first be logged in with the appropriate access level. Each of the programmable values
requires a specific access level that is indicated beside the specified value. All of the programmable
controls in the system fall into one of the categories described in the following sections.
Access level
The OptiView panel restricts certain operations based on password entry by the operator. Three
different access levels are provided as follows:
• View: The panel defaults to the lowest access level, which is termed View. In this mode, the
chiller operating values and setpoints can be observed, but no changes can be made.
• Operator: The second access level is termed Operator and this allows the customer to
change all of the setpoints required to operate the chiller system. In order to gain standard
operator level access, the Home screen logon password is entered as 9 6 7 5, using the
numeric keypad.
• Service: In case advanced diagnostics are necessary, a Service access level is provided. Only
qualified service personnel use this access level. This level provides advanced control over
many of the chiller functions and allows calibration of many of the chiller controls. The access
levels are listed above in hierarchical order beginning with the lowest level and proceeding
to the highest level. Users logged in under the higher access levels can perform any actions
available at the lower access levels.
The operator access level has a 10 minute timeout. After 10 successive minutes without a keypress,
the panel reverts to the View access level. This prevents unauthorized changes to the chiller if a
user was logged on at a higher access level and failed to log off. After making necessary setpoint
adjustments, return to the Home Screen and log off.
Change setpoints
On screens that contain setpoints that are programmable at the operator access level, a button
with this label is visible if the present access level is View. This button brings up the Access Level
Programming setpoints
About this task:
The control center uses the setpoint values to control the chiller and other devices that are
connected to the chiller system. Setpoints can fall into several categories. They could be numeric
values, such as 45.0°F for the Leaving Chilled Liquid Temperature, or they could enable or disable
a feature or function. Regardless of which setpoint is being programmed, use the following
procedure:
1. Press the setpoint button. A dialog box appears displaying the present value, the upper and
lower limits of the programmable range, and the default value.
2. If the dialog box begins with the word ENTER, use the numeric keys to enter the required
value. Leading zeroes are not necessary. If a decimal point is necessary, press the decimal (•)
button, for example, 45.0.
To set the entry value to the default for that setpoint, press the ▲ button. To clear the
present entry, press the ▼ button. The ◄ button is a backspace key and causes the entry
point to move back one space. If the dialog box begins with SELECT, use the ◄ and ►
buttons to select the preferred value.
If the previously defined setpoint is required, press the X (Cancel) button to dismiss the
dialog box.
3. Press the Enter (✓) button.
If the value is within range, it is accepted and the dialog box disappears. The chiller begins to
operate based on the new programmed value. If out of range, the value is not accepted and
the user is prompted to try again.
Manual controls
Some buttons are used to perform manual control functions. These may involve manual control
of items such as the compressor speed or valve actuators. These are mostly restricted to qualified
technicians in Service access. Other buttons in this category are used to initiate and terminate
processes such as calibrations or reports.
Free cursor
On screens that contain many setpoints, a specific button might not be assigned to each setpoint
value. A soft key is assigned to enable the cursor arrow buttons below the numeric keypad, which
are used to highlight the setpoint field. At this point, the Enter (✓) button is pressed to bring up a
dialog, which prompts the user to enter a new setpoint value. The X button cancels cursor mode.
See the Schedule screen for an example.
Navigation
To maximize the amount of values that the panel can display to the user, and in order to place
those values in context, multiple screens have been designed to describe the chiller operation. In
order to move from one screen to the next, navigation buttons have been defined. These buttons
allow the user to either move forward to a subscreen of the present screen, or move backward to
the previous screen. Except when viewing the Home screen display, the upper-right soft button
always returns the user to the Home screen. Navigating is as simple as pressing the button next
to the label containing the name of the preferred screen. The system immediately refreshes the
display with the graphics for that screen. The following figure is a layout of all the screens and how
they are connected.
Languages
The screens can be displayed in various languages. Language selection is performed on the User
screen. The preferred language is selected from those available. Not all languages are available.
English is the default language. If a language other than English is displayed, an English-speaking
person must navigate to the User screen using the preceding Navigation chart and select English.
Note:
The saturation temperatures are calculated values. They display XXX if the pressure used for
(1)
When the chiller system is powered on, the default display in Figure 12 appears. The Home screen
display depicts a visual representation of the chiller itself. The animation indicates the chilled liquid
flow and condenser cooling liquid flow when the flow switch inputs are satisfied.
Table 11: Display only fields
Field/LED name Description
Chilled Liquid Temperature - Leaving Displays the temperature of the liquid as it leaves the evaporator.
Chilled Liquid Temperature - Displays the temperature of the liquid as it enters the evaporator.
Entering
Outside Ambient Air Temperature Displays the outside ambient air temperature
Input % Full Load Amps This displays the percentage of full load amps used by the system.
Input Power (kW) This displays the total input power used by the system.
Operating Hours Displays the cumulative operating hours of the chiller.
Motor Run (LED) This LED is on when the digital output that gives the VSD a motor run command is on.
This screen gives a general overview of common chiller parameters for both shells.
Table 14: Display only fields
Field/LED name Description
Discharge Temperature Displays the temperature of the refrigerant in its gaseous state at discharge of the
compressor as it travels to the condenser.
Input % Full Load Amps This displays the percentage of full load amps utilized by the system.
Outside Ambient Temperature Displays the outside ambient air temperature.
Chilled Liquid Temperature - Leaving Displays the temperature of the liquid as it leaves the evaporator.
Chilled Liquid Temperature - Displays the temperature of the liquid as it enters the evaporator.
Entering
Chilled Liquid Temperature - Displays the programmed temperature setpoint for leaving chilled liquid. It is the local
Setpoint value or remote reset value depending on control source.
Condenser Pressure Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature Displays the saturation temperature in the condenser calculated from condenser
pressure.
Evaporator Pressure Displays the present refrigerant pressure in the evaporator.
Evaporator Saturation Temperature Displays the present saturation temperature in the evaporator calculated from
evaporator pressure.
Programmable
There are no programmable fields on this screen.
Table 15: Navigation
Button Description
Home Causes an instant return to the Home screen.
This screen displays a cutaway view of the chiller evaporator. All setpoints relating to the
evaporator side of the chiller are maintained on this screen. Animation of the evaporation process
indicates whether the chiller is presently in a run condition. Animation of the liquid flow indicates
chilled liquid flow.
Table 16: Display only fields
Field/LED name Description
Leaving Chilled Liquid Temperature Displays the temperature of the liquid as it leaves the evaporator.
Entering Chilled Liquid TemperatureDisplays the temperature of the liquid as it enters the evaporator.
Evaporator Small Temperature Displays the difference between the Leaving Chilled Liquid temperature and the
Difference Evaporator Refrigerant temperature. The Evaporator Refrigerant temperature is
represented by the Refrigerant Temperature sensor input if the sensor is enabled.
Otherwise it is represented by the Evaporator Saturation temperature.
Evaporator Pressure Displays the present refrigerant pressure in the evaporator.
Leaving Chilled Liquid Temperature Displays the present setpoint to which the chiller is operating, whether controlled
Setpoints–Setpoint locally or remotely.
Leaving Chilled Liquid Temperature Displays the Leaving Chilled Liquid Temperature at which the chiller restarts after it
Setpoints–Restart shuts down on LEAVING CHILLED LIQUID – LOW TEMPERATURE cycling shutdown.
This temperature is set as an offset using the Leaving Chilled Liquid Temperature
Cycling Offset –Restart setpoint.
Leaving Chilled Liquid Temperature Displays the present value of the leaving chilled liquid temperature shutdown offset in
Setpoints (Shutdown) – Effective effect, limited by the chiller minimum temperature.
Offset
Leaving Chilled Liquid Temperature Displays the value set for leaving chilled liquid temperature restart offset.
Setpoints (Restart) – Offset
Evaporator Saturation Temperature Displays the present saturation temperature in the evaporator, determined from the
evaporator pressure.
Chilled Liquid Flow Switch (Open/ Displays whether the liquid flow switch input indicates flow is present in the
Closed) evaporator.
Chilled Liquid Pump Displays the command presently sent by the control center to the Chilled Liquid Pump
run contacts: Run or Stop.
This screen displays the air-cooled condenser with an animation of heat ejection out of the fan
deck.
Table 19: Display only fields
Field/LED name Description
Condenser Saturation Temperature Displays the saturation temperature in the condenser.
Condenser Small Temperature Displays the condenser small temperature difference.
Difference
Condenser Pressure Displays the refrigerant pressure in the condenser.
Condenser Liquid Temperature Displays the temperature of the refrigerant in the drop leg between the condenser
and evaporator shells.
Subcooling Temperature Displays the difference between the Condenser Refrigerant temperature and the Drop
Leg Refrigerant temperature. The Condenser Refrigerant temperature is represented
by the Condenser Saturation temperature.
High Pressure Switch (Open/Closed) Displays the present position of the high-pressure switch. This indicates open when a
high-pressure fault is present.
Condenser Fan Speed Command 1 Displays command signal to condenser fan speed.
Condenser Fan Speed Command 2 Displays command signal to condenser fan speed.
Active Subcooling Setpoint Displays the active subcooling setpoint.
Condenser Drain Valve Command Displays the position command to the condenser drain control valve in percent of
travel with 0% full closed to 100% full open.
This screen displays a cutaway view of the chiller compressor, revealing the impeller, and shows
all conditions associated with the compressor. Animation of the compressor impeller indicates
whether the chiller is presently in a Run condition. This screen also serves as a gateway to
subscreens for navigating to capacity control and displaying MBC, surge, and VGD and power panel
detail.
Table 21: Display only fields
Field/LED name Description
Discharge Temperature Displays the temperature of the refrigerant in its gaseous state at discharge of the
compressor as it travels to the condenser.
Discharge Superheat Displays the discharge superheat, calculated as Discharge Temperature –
Condenser Saturation temperature.
Motor Run (LED) Indicates ON when the digital output run command to the VSD is on.
Input % Full Load Amps Displays the chiller current as a percentage of the job input Full Load Amps (FLA)
value.
Motor % Full Load Amps Displays the current to the motor as a percentage of the motor maximum current.
VSD Output Frequency Displays the VSD frequency.
Programmable
There are no programmable fields on this screen.
Table 22: Navigation
Button Description
Home Causes an instant return to the Home screen.
Capacity Control Causes an instant transfer to the Capacity Control screen.
MBC Moves to the subscreen allowing view of the MBC parameters and event log.
Surge Moves to the subscreen that allows viewing and programming of the surge protection
feature.
This screen displays the orientation of the magnetic bearing axes relative to the compressor
driveline. Pertinent parameters transmitted to the control panel from the Magnetic Bearing
Controller (MBC) are displayed on this screen. Many parameters are shown in the diagram in the
locations they represent. The left end of the motor shaft graphic represents the low stage, a single
stage, impeller end bearing. The right end of the motor shaft graphic represents the opposite end
bearing.
Table 23: Display only fields
Field/LED name Description
V13 Position Displays the shaft position in micrometers from center along the radial axis designated “V”
for the Impeller End Bearing.
W13 Position Displays the shaft position in micrometers from center along the radial axis designated “W”
for the Impeller End Bearing.
W1 (Current) Displays the magnetizing current to the upper bearing on the radial axis designated “W” for
the Impeller End.
W3 (Current) Displays the magnetizing current to the lower bearing on the radial axis designated “W” for
the Impeller End.
V1 (Current) Displays the magnetizing current to the upper bearing on the radial axis designated “V” for
the Impeller End.
V3 (Current) Displays the magnetizing current to the lower bearing on the radial axis designated “V” for
the Impeller End.
Z1 (Current) Displays the magnetizing current to the axial bearing at the Impeller End.
V24 Position Displays the shaft position in micrometers from center along the radial axis designated “V”
for the Opposite Impeller End Bearing.
W24 Position Displays the shaft position in micrometers from center along the radial axis designated “W”
for the Opposite Impeller End Bearing.
W2 (Current) Displays the magnetizing current to the upper bearing on the radial axis designated “W” for
the Opposite Impeller End.
W4 (Current) Displays the magnetizing current to the lower bearing on the radial axis designated “W” for
the Opposite Impeller End.
V2 (Current) Displays the magnetizing current to the upper bearing on the radial axis designated “V” for
the Opposite Impeller End.
This screen displays the orientation of the magnetic bearing axes relative to the compressor
driveline similar to the MBC screen. Additional pertinent parameters transmitted to the control
panel from the MBC are displayed on this screen. Many parameters are shown in the diagram in
the locations they represent. The left end of the motor shaft graphic represents the low stage,
a single stage, impeller end bearing. The right end of the motor shaft graphic represents the
opposite end bearing.
Table 25: Display only fields
Field/LED name Description
Z1 Temperature Displays the temperature measured at the impeller end bearing assembly.
A13 Unbalance / B13 Unbalance Magnitude of motion at 1x rotation in each of two vectors at the 1-stage impeller end.
A24 Unbalance / B24 Unbalance Magnitude of motion at 1x rotation in each of two vectors at the opposite 1-stage
impeller end.
Z2 Temperature Displays the temperature measured at the opposite impeller end bearing assembly.
Z12 Vibration Displays the vibration amplitude for specific frequencies measured axially by the
position sensors.
Magnetic bearing currents as described for the MBC screen are repeated on this
screen:
• W1 (Current)
• V1 (Current)
• Z1 (Current)
• V3 (Current)
• W3 (Current)
• W2 (Current)
• V2 (Current)
• Z2 (Current)
• V4 (Current)
• W4 (Current)
[MBC Status] AVR (LED) Indicates the MBC is reporting its automatic vibration reduction feature is active
through Modbus Data.
Programmable
There are no programmable fields on this screen.
Table 26: Navigation
Button Description
Home Causes immediate return to the Home screen.
Compressor Causes immediate transfer to the Compressor screen.
MBC Causes immediate return to the MBC screen.
This screen displays the chiller compressor and all parameters relating to the surge protection
feature. All setpoints relating to this screen are maintained on this screen.
Table 27: Display only fields
Field/LED name Description
Delta P/P A parameter that represents the system differential or head pressure. It is calculated as
condenser pressure – evaporator pressure) / evaporator pressure.
Surge Window Time When the chiller enters run mode, this value counts up to the time programmed as the
Count Window setpoint. When it reaches the Count Window minutes, the number of surge
events in the oldest minute is discarded and the number of surge events in the most recent
minute is added. This provides a rolling count of the total surge events that have occurred in
the last Count Window minutes. This value is reset when the chiller shuts down.
Surge Window Count Displays the number of surge events that have occurred in the last 1 to 5 minutes as
programmed with the Count Window setpoint. If the chiller has been running for less than
the Count Window minutes, it is the number of surge events that have occurred within the
last number of minutes displayed as the Surge Window Time. The count is cleared when the
chiller shuts down.
Surge Detected (LED) Illuminates momentarily when a surge is detected by the surge protection feature.
Surge Count Total number of surges accumulated by the surge protection feature.
Use the surge protection feature to define how many surges are excessive and how the control
reacts to an excess surge condition. When excess surging is detected, you can configure the chiller
to shut down. The sensitivity of this surge detection is set by the Sensitivity setpoint on this screen.
This screen displays information pertaining to the power panel, which includes the uninterruptable
power supply (UPS) and storage battery for essential loads necessary for shutdown during a line
power loss.
Table 32: Display only fields
Field/LED name Description
Control Voltage (LED) Indicates the OptiView control voltage digital input voltage is present, indicating line power
is available.
Power Loss Time Indicates the time in seconds while the OptiView control voltage digital input is low,
indicating time without line power for the present outage.
Motor Speed Indicates the motor speed as reported from the MBC.
UPS Line / Charging (LED) Indicates the UPS is in charging mode, using line power to supply loads and any necessary
current to the power storage battery.
UPS Inverter (LED) Indicates the UPS is providing power from the storage battery.
UPS Fault (LED) Indicates the UPS has faulted.
UPS Battery V+ (LED) Indicates the UPS senses battery present.
UPS Battery Voltage Indicates the UPS battery voltage from available to the UPS input.
UPS Inverter Enable (LED) Indicates the presence of the signal from OptiView™ to the UPS permitting the UPS to supply
power from the battery as needed upon loss of line power.
Power Panel Temperature Indicates the ambient temperature inside the power panel.
Power Panel Cooling System Indicates the power panel coolant pump and coil fan are commanded to run.
Run (LED)
Line Low Battery Voltage These are control setpoints for battery health fault logic.
Offset, Inverter Low Battery
Voltage Threshold, Line Low
Battery Voltage Threshold
This screen displays the pertinent parameters associated with capacity control in relation to Leaving
Chilled Liquid temperature, current and pressure overrides, and anti-surge control. This screen also
provides a means for a service technician to control VGD, speed, and optional hot gas bypass valve
manually for maintenance or service.
Table 34: Display only fields
Field/LED name Description
Evaporator Pressure Displays the pressure in the evaporator.
[Evaporator Pressure] Displays the evaporator pressure setpoint below which the low evaporator pressure capacity
Override Threshold control override takes effect.
Condenser Pressure Displays the pressure in the condenser.
[Condenser Pressure] Displays the condenser pressure setpoint above which the high condenser pressure capacity
Override Threshold control override takes effect.
Input Current % FLA Displays the percent of useful job full load current presently supplied to the chiller,
determined from the highest of the three-phase Input Currents/(Input Job FLA setting/0.9).
[Input Current % FLA] Displays the active input current percent limit, which is the minimum of Local Input Current
Override Threshold Limit, Remote Input Current Limit, and Pulldown Current Limit or BAS (ISN) current limit.
Motor Current % FLA Displays the percentage of maximum motor current delivered to the motor, determined
from the highest of the three phase Motor Currents/Maximum Motor Current Limit.
[Motor Current % FLA] Displays the active motor current percent limit, which is a percentage of the minimum of VSD
Override Threshold and motor maximum current limits.
Entering Chilled Liquid Displays the temperature of the chilled liquid as it enters the evaporator.
Leaving Chilled Liquid Displays the temperature of the chilled liquid as it leaves the evaporator.
Active LCHLT setpoint Displays the active temperature setpoint to which the chiller is set to control liquid leaving
the evaporator. The active setpoint is a target to the Local, Remote, or BAS (ISN) LCHLT
programmed setpoint, depending on the control source selected. When the chiller is not
running, the Active setpoint is set to Entering Chilled Liquid Temperature - LCHLT setpoint
Start Offset. When the VSD starts, the Active LCHLT setpoint is ramped to the programmed
LCHLT setpoint at the programmable LCHLT setpoint ramp rate. When the chiller is running,
performing capacity control, any change to the programmed LCHLT setpoint results in a
ramp from the old Active setpoint value to the new LCHLT setpoint value at the programmed
LCHLT setpoint Ramp Rate.
This screen displays more detailed parameters associated with the VSD. This screen also provides a
means for a service technician to access setpoints or control the DC Bus manually for maintenance
or service.
Table 39: Display only fields
Field/LED name Description
Motor Run (LED) Indicates the digital output from the controls is commanding the motor to RUN.
DC Bus Regulating (LED) Indicates the VSD is regulating the DC Bus.
Precharge Complete (LED) Indicates the drive DC Bus has been pre-charged.
Input Current Limit (LED) Indicates the chiller input current is at the Job FLA limit.
Cooling System (LED) Indicates the relay controlling the drive water pump output is energized.
Precharge Active (LED) Indicates the VSD is pre-charging the DC Bus.
Output Current Rating Indicates the VSD size reported from VSD.
Phase Rotation Displays the phase rotation sequencing.
DC Bus Voltage Displays the DC Bus voltage.
Input kVA Displays the total kilovolt-Amps measured by the VSD.
VSD Command The command from OptiView control to the VSD. Commands are as follows:
• 1 = Pre-Regulate
• 2 = Run
• 3 = Manual Precharge
• 4 = Manual Pre-Regulate
• 5 = Soft Shutdown
• 0 = Idle
• 1 = Precharge
• 2 = Pre-Regulate
• 3 = Waiting for Run
• 4 = Run
• 5 = Stop
• 6 = Unit trip
• 7 = Water Pump
• 8 = Test Mode
• 9 = Manual Precharge
• 10 = Man Pre-Regulate
• 11 = Soft Shutdown
• 12 = Precharge Re-init
• 13 = Check DCCT
VSD Inverter State Displays the inverter state of the VSD. States are as follows:
• 0 = Stop
• 1 = Dwell
• 2 = Run
• 3 = Run Voltage Control
• 4 = Test Mode
• 5 = Faulted
• 6 = Check DCCT
VSD Output Frequency Displays the present output frequency to the motor.
Input Voltage Peak (L1, L2, L3) Displays the three-phase input peak voltages measured by the VSD (Neutral to Line).
Input Voltage RMS (L1, L2, L3) Displays the three-phase input RMS voltages across each line.
Input Current RMS (L1, L2, L3) Displays the three-phase input current values measured by the VSD.
Output Voltage RMS (Phase A, Displays the three-phase output RMS voltages across each line.
B, C)
Output Current RMS (Phase A, Displays the three-phase output current values measured by the VSD.
B, C)
Rectifier Baseplate Displays the drive input rectifier baseplate temperatures at each phase.
Temperature (L1, L2, L3)
Inverter Baseplate Displays the drive output inverter baseplate temperatures at each phase.
Temperature (Phase A, B, C)
Internal Ambient Temperature Displays the ambient temperature inside the drive cabinet from two sensors as reported by
the VSD.
This screen displays information pertinent to the motor temperature monitoring feature. The
feature consists of motor winding temperature and motor housing temperature. The individual
winding temperature sensors can be disabled on this screen.
Table 43: Display only fields
Field/LED name Description
Motor Run (LED) Illuminates when the OptiView control center is commanding the motor to run.
% Input Full Load Amps Displays the input current as a percentage of chiller full load amps.
VSD Output Frequency Displays the frequency at which the VSD is operating the motor. This value is returned from
the drive logic board.
VGD Position Displays the present variable geometry diffuser position as a value between 0% (closed) and
100% (full open).
Motor Temperatures Displays the enabled motor winding temperatures for phase A, B and C. Individual
temperatures can be disabled using the Temperature Disable setpoint. The software
prevents more than 2 of the 3 sensors at either end of the motor to be disabled. When an
individual temperature is disabled, the temperature data box does not appear. Any input
that registers as open displays the minimum temperature 32°F.
Average Winding This value is calculated as the average of all enabled and valid motor winding temperatures.
Temperature Any winding temperature that registers as open, out of range or disabled is not used in the
calculation. A maximum of six temperatures is used to calculate the average.
Rotor Elongation Displays the calculated change in distance from the two axial position sensors for the rotor
shaft versus the shutdown baseline set at the factory. This indicates thermal growth and
torque effect.
Estimated Rotor Temperature Displays the temperature derived from physical parameters, elongation, and housing
temperature.
Motor Housing Temperature Display the temperature of the motor housing sensed at the thermistor on the motor
externally.
Motor Housing Temperature Displays the target temperature for the motor cooling control. It is equal to entering
Setpoint condenser water temperature plus the programmable setpoint offset.
This screen provides a convenient location for programming the most common setpoints involved
in the chiller control. This screen also serves as a gateway to the Setup screen for defining the setup
of general system parameters.
Table 45: Display only fields
Field/LED name Description
LCHLT - Setpoint Displays the present Active setpoint to which the chiller is operating whether controlled
remotely or locally.
LCHLT Cycling - Shutdown Displays the LCHLT at which the chiller will shut down to avoid over-cooling LCHLT below
setpoint in low load situations.
LCHLT Cycling – Restart Displays the LCHLT at which the chiller will restart after it has shut down due to over-cooling
temperature.
Input Current Limit Setpoint Displays the active Input Current Limit setpoint. This is the minimum of the locally or remote
(received via 0 VDC to 10 VDC, 2 VDC to 10 VDC, 0 mA to 20 mA, or 4 mA to 20 mA input or
PWM) programmed Current Limit setpoint or pulldown limit. In BAS (ISN) remote mode, the
remote setpoint is received from the SC-Equip Gateway interface.
This screen allows the user to use remote control status and change certain setpoints.
This screen is the top level of the general configuration parameters. It allows programming of the
time and date, along with specifications as to whether the time is displayed in the 12 hour or the
24 hour format. In addition, the chiller configuration, as determined by the state of the microboard
program jumpers and program switches is displayed. A qualified service technician, following
instructions in YORK YVAM Service Manual (Form 160.88-M2), establishes this configuration for the
required operation. This screen also serves as a gateway to more subscreens for defining general
system parameters. These subscreens are listed in Table 53.
Table 51: Display only fields
Field/LED name Description
Liquid Type Displays Water or Brine.
Refrigerant Type Shows the refrigerant selected at factory level.
Line Voltage Displays the chiller line voltage setting.
Line Frequency Displays the chiller line frequency setting.
Hot Gas Bypass Displays the Hot Gas Bypass Enable or Disable Setting.
Chilled Liquid Pump Displays the Chiller Liquid Pump Operations Selection Standard or Enhanced.
Operations
Flow Switch Input Displays where the flow switch is terminated on in the OptiView Panel (J14 or TB4).
Power Failure Restart Displays the power failure restart setting, Manual or Auto, start after a power failure.
Condenser Fan Type Display whether the condenser fans are set for standard or enhanced operation.
Variable Water Outlet Control Displays whether the Variable Water Outlet Control is enabled or disabled.
Note: Used for European requirement.
VSD Cooling Protection Displays whether drive cooling protection is enabled or disabled.
VSD Cooling Source Displays the cooling for drive cooling (LCHT or ECHLT).
Auxiliary VSD Cooling Control Displays the auxiliary drive cooling enabled or disabled setting.
Clock (Enabled /Disabled) Operator Allows the user to enable or disable the real-time clock in order to conserve
battery life. The clock will be disabled during manufacturing and must
be enabled at system commissioning. In addition, when preparing for
prolonged shutdown, the clock must once again be disabled.
12/24Hr Operator Allows the user to specify the format in which the time will be presented. This
setpoint affects the display of the time on the chiller panel and on all reports
generated. The 12-Hour time format will include the AM and PM modifiers
and show the range of time between 1:00 and 12:59, while the 24-Hour time
format will show the range of time between 0:00 and 23:59.
Change Settings Operator Used to enter the following setpoints. Pressing this button places a green
selection box around the first changeable setpoint. The access level
determines which setpoints can be changed. Use the ▲ and ▼ buttons
to place the selection box around the required setpoint. With the setpoint
selected, press the ENTER (✓) button. A dialog box appears with the range of
settings.
The schedule screen contains more programmable values than a normal display screen. Each
programmable value is not linked to a specific button. Instead the Select button is used to enable
the cursor arrows, which are used to highlight the day and the start or stop time the user wants to
modify. At this point the user may press the Enter (✓) button to program the start and stop times
for that day.
The user can define a standard set of start and stop times that are used every week. The user
can then specify exception start and stop combinations for any day of the week up to six weeks
in advance. At the end of each week, the schedule for the next week is created by combining the
standard week definition and the next defined exception week. The schedule is then updated as
each of the exception weeks shifts down, leaving a new, blank exception week in the sixth week
slot.
This screen displays the chiller schedule. There are no other display options.
Table 54: Programmable
Button Access Description
Standard Week Start/Stop Operator For each day of the week, the user may specify a time for the chiller to start
Times and a time for the chiller to stop. The times specified in this entry week will
be used as the default for every week of chiller operation.
Exception Start/Stop Times Operator For each day of the week, the user may specify a time for the chiller to start
and a time for the chiller to stop. These start and stop combinations may be
scheduled up to five weeks in advance and also for the present week. As each
week goes by, the new schedule will be created for the present week using
the Exception specification in combination with the Standard week definition,
as described above.
Schedule (Enabled / Disabled) Operator Allows the user to enable or disable the monitoring function which enforces
the scheduled starting and stopping of the chiller.
Repeat Sunday Schedule Operator Duplicates the schedule defined for Sunday for the remainder of the
standard weekdays.
Use this to define custom User IDs and matching passwords. The building administrator can then
assign custom passwords to users who are authorized to maintain the chiller.
This screen displays attributes assigned to User IDs. There are no other display options.
Table 56: Programmable
Button Access Description
Date Display Mode Operator Define the unit system (English or Metric) used by the chiller display.
System Language Operator Allows the user to define the language for all screens. The preferred
language is selected by scrolling through the list of those available. English
is the default language and is selected by pressing the ▲ button when the
dialog box appears during the selection process. The selected language
will not be displayed until after the user navigates from the User screen to
another screen. The selections are: English, French, German, Hungarian,
Italian, Japanese, Portuguese, Simplified Chinese, Spanish, and Traditional
Chinese.
Date Format Operator Allows the user to format the day, month, and year.
This screen allows definition of the necessary communications parameters. See Printing for details
on the printer connections and setup. Presently, there are no COM 2 communications features
available.
This screen displays attributes assigned to COMMS IDs. There are no other display options.
Table 58: Programmable
Button Description
Chiller ID Access level required: Operator
Define the numeric chiller ID when used within an BAS network of chillers. This ID number is
also printed at the top of reports obtained with a local printer.
Printer Setup Access level required: Operator
Pressing either key places a green selection box around the first changeable parameter.
Use the ▲ and ▼ buttons to place the selection box around the parameter to be changed.
With the selection box around the parameter, press the ENTER (✓) button. A dialog box is
displayed permitting data entry.
Printer Baud Rate Define the baud rate for communication between the panel and the printer.
Printer Data Bits Define the number of data bits for communication between the panel and the printer.
Printer Parity Bits Define the number of parity bits for communication between the panel and the printer.
Printer Stop Bits Define the number of stop bits for communication between the panel and the printer.
This screen allows definition of the necessary communications parameters for the printer. See
Printing for details on printer connections and setup.
Table 60: Display only fields
Field/LED name Description
Time Remaining Until Next Displays the time until the next print log will occur, if the function is enabled.
Print
This screen allows definition of the sales order parameters. The commissioning date is entered
by the YORK or Johnson Controls service technician at the time of chiller commissioning. These
values must never be changed or entered by anyone other than a qualified service technician. Entry
instructions are included in the YORK YVAM Service Manual (Form 160.88-M2). The remainder of the
values are entered at the YORK factory during the manufacturing of the chiller.
Table 63: Display only fields
Field/LED name Description
Model Number Factory defined model number of the chiller system.
YORK Order Number Factory defined order number under which the chiller was sold.
Chiller Serial Number Factory defined serial number for the chiller system.
Compressor Model Factory defined model number of the compressor. Critical entry for correct chiller operation.
Technicians see YORK YVAM Service Manual (Form 160.88-M2).
Evaporator Model Factory defined model number of the evaporator.
Condenser Model Factory defined model number of the condenser.
VSD Model Factory defined model number of the VSD.
Condenser and Evaporator Factory defined condenser and evaporator parameters as in the original rating.
Design Load Information
Nameplate Information Factory defined information about the chiller configuration.
Commissioning Date Define the date at which the chiller was commissioned.
Job Name and Location Factory defined job name and location the chiller is destined for.
This screen allows definition of general parameters having to do with the operation of the chiller.
Table 66: Display only fields
Field/LED name Description
Chiller Run Time Displays the amount of time the chiller has been running since the last start signal was
received. Value is reset to zero when the chiller enters coastdown. It remains at zero while
shutdown and during MBC Startup.
Number of Starts Displays the number of the starts the chiller has initiated.
Operating Hours Displays the total accumulated run time of the chiller.
This screen allows the user to browse through the faults. For a more thorough reporting of the
system conditions at the time of the recorded shutdown, use the History details screen.
Table 68: Display only fields
Field/LED name Description
Last Normal Shutdown Displays the date and time and the description of the last normal shutdown. A normal
shutdown is defined as:
• Local (Panel rocker switch)
• Remote (Digital, Analog, or BAS (ISN))
Last Fault While Running Displays the date and time and the description of the last safety or cycling shutdown while
the system was running.
Last Ten Faults Displays a chronological listing (most recent first) of the date, time, and description of the
last 10 safety or cycling shutdowns that occur while the system is running or stopped.
This screen allows the user to see an on-screen printout of all the system parameters at the time of
the selected shutdown. Not all screens are shown as in Figure 37. The number of screens required
to display all of the data varies according to type of motor starter and options applied.
Table 71: Display only fields
Field/LED name Description
History Printout Displays an on-screen printout of the system parameters.
This screen allows the service technician to select up to 10 parameters for display on the Custom
screen.
Table 76: Display only fields
Field/LED name Description
Slot Numbers Lists the available parameters that can be displayed. The required parameters for display are
selected from this list.
The Trend screen displays the graphical trending of the selected parameters and is also a gateway
to the graph setup screens.
You can plot up to six operator selected parameters, or data points, in an X/Y graph format. The
X-axis scales to the selected data collection interval and displays in a time of day or elapsed time
format, as selected with the X-axis toggle button. The Y-axis scales to the selected minimum and
maximum value for each parameter. Analog parameters scale in pressure, temperature, volts,
amps, hertz, or time. Digital on and off parameters scale as 0 (off) and 1 (on). You can display only
one Y-axis label at a time. Use the Y-axis toggle button to toggle the Y-axis labels through the
different parameters. The Y-axis label that is displayed is identified at the top of the graph. For
identification, each plotted parameter and associated Y-axis labeling is color coordinated.
The parameters are sampled at the selected data collection interval and plotted using 450 data
points across the X-axis. If the actual value of the sampled parameter is less than the Y-axis label
minimum for that parameter, the value is plotted at the minimum value. Similarly, if the actual
value is greater than the Y-axis label maximum for that parameter, the value is plotted at the
maximum value.
The screen can display the following chart types:
• One screen
• Continuous
• Triggered
If a power failure occurs while the trending is running, the trending is stopped. When power is
restored, the last screen of data that was collected is displayed on the trending screen. To begin a
new trend screen, press the Start button.
Note: A red screen with the words TREND MAX MUST BE > TREND MIN appears if the Y-axis
minimum has been programmed to a value that is greater than the Y-axis maximum for any
parameter. If this appears, navigate to the Trend setup screen to change the values.
This screen is used to configure the trending screen. The parameters to be trended are selected
from the Common Slots Screen or Common Slots Master list and entered as Slot Numbers for Data
Points 1 through 6. The Y-Axis minimum and maximum values for each parameter are entered
as Data Point Min and Data Point Max for Data Points 1 through 6. The interval at which all the
parameters are sampled is selected as the Data Collection Interval.
This screen displays chiller trend setup fields. There are no display only fields.
Table 81: Programmable
Button Access Description
Select Operator This button is used to enter the slot numbers and the minimum and
maximum Y-axis values of each parameter to be trended. Pressing this
button places a yellow box around Data Point 1 Slot Number. Use the ▲ and
▼ navigation buttons to place the box around the value of data points 1
through 6 to be changed. With the required value selected, press the Enter
(✓) button. A dialog box is displayed for data entry.
Chart Type Operator Selects Continuous, One Screen, or Triggered.
Data Point Slot # (1-6) Operator Use the Select button as described previously and enter the slot number
from the Common Slots Screen or Master Slot Number List of the parameter
that you want to trend. The selected parameter description is displayed for
the data point. If you set this slot number to 0, trending for that particular
data point is disabled. Any or all points can be disabled.
This screen displays the slot numbers of the commonly monitored parameters. The slot numbers
for the remainder of the available parameters are listed on the .
From these lists, you can select up to six parameters to trend. Return to the Trend setup screen and
enter the parameters Slot Numbers into Data Points 1 through 6.
Table 83: Display only fields
Field/LED name Description
Slot Numbers These are the slot numbers of the most commonly used parameters.
Status messages
Table 86: Status messages
Message Description
The chiller is shut down on a Cycling shutdown. The cause of the shutdown is still in effect
CYCLING SHUTDOWN – AUTO
and is displayed on the Details line of the Status Bar. The chiller automatically restarts when
RESTART
the Cycling condition clears.
A chiller start has been initiated. The MBC conditions are verified and transitioned to levitate
MBC STARTUP the driveline rotor (MBC Levitation Mode). The progress of the MBC startup is described in
the Details Line of the Status Bar.
The chiller is shut down on a Safety shutdown. The cause of the shutdown is still in effect and
SAFETY SHUTDOWN –
is displayed on the Details line of the Status Bar. The chiller can be started after the Safety
MANUAL RESTART
condition clears and the Operator presses the Clear Fault button.
The chiller is performing a Soft Shutdown. Simultaneously, the Hot Gas Bypass Valve is
commanded to 100% open (if Hot Gas Bypass is Enabled), the compressor VGD commanded
to close rapidly. The motor drive speed is slowed from its initial speed to the minimum
required to prevent surge. Then the motor drive speed is ramped to 0 Hz. The chiller then
transitions to coastdown. Soft Shutdown is initiated by the following:
• Leaving Chilled Liquid – Low Temperature
• Local Panel Stop Key
• Remote stop
• Any MBC Fault occurs
SOFT SHUTDOWN • Multi-Unit Cycling – Contacts Open
• System Cycling – Contacts Open
• Control Panel – Schedule
• Condenser – Flow Switch Open fault active
• Chilled Liquid – Flow Switch Open fault active
• Expansion I/O – Serial Communications fault active
If the local panel safety stop switch is pressed or any chiller shutdown faults other than
those listed above occur, Soft Shutdown is immediately terminated and a System Coastdown
occurs.
The chiller is prevented from being started due to the reason displayed on the Details Line of
START INHIBIT
the Status bar.
The chiller has shut down and removed the run signal from the motor VSD. The system is
waiting for confirmation that the driveline has stopped rotating. When the MBC and VSD
SYSTEM COASTDOWN
report drive frequency of 0 Hz for 5 s, coastdown is considered completed. Then, after 60 s
delay, the VSD Precharge command is released.
Run messages
Table 87: Run messages
Message Description
LEAVING CHILLED LIQUID The chiller is running, controlling the Leaving Chilled Liquid to the Leaving Chilled Liquid
CONTROL Temperature Setpoint. Or if the unit is a heat pump and the Control Mode is Cooling.
LEAVING CONDENSER LIQUID The chiller is running, controlling the Leaving Condenser Liquid to the Leaving Condenser
CONTROL Liquid Temperature Setpoint. If the unit is a heat pump and the Control Mode is Heating.
The chiller is running, controlling either the Leaving Chilled Liquid or Leaving Condenser
LEAVING CHILLED &
Liquid Temperature. If the unit is a heat pump and the Control Mode is Cooling and
CONDENSER LIQUID CONTROL
Heating.
This non-annunciating message alerts that the DC Bus is precharged or pre-regulated for
a state outside of chiller run. It is set when the VSD indicates a precharge or pre-regulated
WARNING – VSD DC BUS
state or DC Bus voltage >50 V in the stopped state. A countdown timer shows with this
ACTIVE
message to indicate the time remaining in a precharge or pre-regulate command while
stopped.
The Chiller Input current is greater than or equal to the Active Current Limit Setpoint. The
Current Limit Setpoint is programmed over a range of 30% to 100% of the Chiller Full Load
Amps (FLA). The Active limit is the minimum of the Local, pulldown (if active), and Remote
Current Limit Setpoints in Remote mode or the remote value in BAS (ISN) mode. While this
VSD – HIGH INPUT CURRENT
condition is in effect, chiller capacity control is in override to reduce current. Normal LCHLT
LIMIT
capacity control operation is resumed and this message automatically clears when the
input current decreases below this limit.
The highest of the three-phase input currents divided by the programmed Job Input FLA is
compared to the limit for this override.
VSD – INPUT PULLDOWN The chiller input current will be limited by the pulldown demand limit setpoint. The
LIMIT message clears when the pulldown demand time expires.
SYSTEM RUN - ACTIVE
The chiller is running, and the Optimizer is Active.
OPTIMIZER
SYSTEM RUN - PASSIVE
The chiller is running, and the Optimizer is Passive.
OPTIMIZER
The chiller is running, the Heat Pump is Enabled and the Control Mode is Cooling, and the
SYSTEM RUN - COOLING
Optimizer is off.
SYSTEM RUN - HEATING The chiller is running, the Heat Pump is Enabled and the Control Mode is Heating.
SYSTEM RUN - COOLING and
The chiller is running, Heat Pump is Enabled, and the Control Mode is Cooling and Heating.
HEATING
Warning messages
Table 90: Warning messages
Message Description
While the chiller state is Stopped, the Saturated Condenser Temperature decreased below
WARNING - CONDENSER
35.0°F. The condenser pump run contacts close. The message is automatically reset and
FREEZE THREAT FROM LOW
pump contacts return to the previous state when either the chiller is not in stopped state
PRESSURE
or the Saturated Condenser Temperature is > 40.0°F.
The condenser pressure exceeds the High Pressure Warning Setpoint threshold,
programmed by a service technician logged in at service access level. While this
WARNING – CONDENSER –
condition is in effect, the chiller capacity is in override to reduce pressure. This message
HIGH PRESSURE LIMIT
automatically clears and normal LCHLT capacity control is restored when the condenser
pressure decreases to below the Setpoint.
The Evaporator pressure Transducer is indicating a higher pressure than the condenser
pressure Transducer after the chiller has been running for 10 min. This indicates a
WARNING – CONDENSER OR
Condenser or Evaporator Transducer failure. This message is displayed until the condition
EVAPORATOR XDCR ERROR
clears and the warnig reset button is pressed in operator (or higher) access mode. The
condition is not checked in Brine mode.
The difference between the Discharge Pressure Transducer output and the Condenser
Pressure Transducer output has exceeded 21 psid for 3 min continuous while the chiller
was running. This feature verifies the operation of the transducers. Because both
WARNING – CONDENSER OR
transducers are measuring essentially the same pressure, both outputs must be within
VGD SENSOR FAILURE
the specified tolerance. This message must be manually cleared. It is displayed until the
transducer outputs are within the acceptable range of each other and the warning reset
button is pressed in service access level.
This message automatically clears and normal LCHLT capacity control restored when the
Evaporator pressure increases to the reset value.
This message applies only if Surge Protection shutdown feature is Disabled. The Surge
Window Count has exceeded the Count Limit. The message can be manually cleared after
WARNING – EXCESS SURGE
the Surge Window Count is less than or equal to the Count Limit, or the shutdown feature
DETECTED
is Enabled or the chiller is stopped. To clear the message, press the warning reset button
on Home Screen when logged in at operator (or higher) access level.
The chiller is running and Refrigerant Level > (Refrigerant Level setpoint +15%) OR
Refrigerant Level < (Refrigerant Level setpoint -15%) for 10 min continous. The Warning
WARNING - LIQUID LEVEL
is bypassed for the first 30 min of run to allow stable operation to establish. It is released
SETPOINT NOT ACHIEVED
when the chiller is not running or Refrigerant Level is within ±15% of the setpoint. The
message clears automatically.
The chiller is running greater than 30 min and the Subcooler Effectiveness value decreased
less than 0.400 (admin programmable) at any drop leg refrigerant temperature or
increased greater than 1.50 (admin programmable) when the drop leg refrigerant
WARNING - LOSS OF temperature is at least 0.5°F below or any amount above the Entering Condenser Liquid
SUBCOOLER LIQUID SEAL Temperature. The subcooler effectiveness is (Condenser Sat Temp - Drop leg refrigerant
temp)/(Cond Sat Temp - Entering Condenser Liquid Temp). To clear the message, press the
warning reset button on the Home Screen when logged on at operator (or higher) access
level.
This manual reset warning is set when the internal oscillator that drives the axial position
sensor coil is overloaded for 1 s continuous. This is typically the result of an open in the
WARNING – MBC – HIGH
connection to the shaft position sensor. It could also be a failure of the MBC control board.
AXIAL OSCILLATOR VOLTAGE
To clear this message, press the warning reset button when logged on at operator access
level or higher.
This manual reset warning is set when the internal oscillator that drives the radial position
sensor coil is overloaded for one continuous s. This is typically the result of an opening in
WARNING – MBC – HIGH
the connection to the shaft position sensor. It could also be a failure of the MBC control
RADIAL OSCILLATOR VOLTAGE
board. To clear this message, press the warning reset button when logged on at operator
access level or higher.
This warning appears when the MBC Axial Centering process was never performed, or
WARNING – MBC – CHECKSUM not correctly realized internally. The centering process as found in the calibration section
CENTERING of Form 160.88-M2 must be performed in admin access. To clear this message, press the
warning reset button when logged on at operator access level or higher.
A software reboot has occurred on the control board due to processor problem, but reset
WARNING – MBC – DSP
with the reboot. To clear this message, press the warning reset button when logged on at
WATCHDOG
operator access level or higher.
A software reboot has occurred on the amplifier (power) board due to processor problem,
WARNING – MBC – AMP
but reset with the reboot. To clear this message, press the warning reset button when
WATCHDOG
logged on at operator access level or higher.
The MBC experienced an unsatisfactory condition detected internally to the control
WARNING – MBC – INTERNAL
system. This message clears when the condition is resolved and the warning reset button
ALARM
is pressed in operator (or higher) access mode.
It releases when Battery Voltage > Line Low Battery Voltage Threshold + 0.1 V.
This auto reset warning is set when all of the following are true for 5 s continuous:
Control Voltage digital input is high (indicates line power is available)
• UPS Line / Charging digital input is low (indicates UPS not reporting in charge mode)
WARNING – UPS – NOT
CHARGING
It releases when any of the following are true:
• Control Voltage digital input is low (indicates line power is lost)
• UPS Line / Charging digital input is high (UPS is reporting in charge mode)
Line voltage imbalance is calculated, for every drive communications cycle, as:
where Vab, Vbc and Vca are line-to-line total rms voltages received from the drive, max is the
WARNING – VSD – INPUT function which selects the largest of its arguments, and:
VOLTAGE IMBALANCE
The chiller restarts after the evaporator pressure increases to the restart threshold. If this
shutdown occurs three times in a 90 min period, an EVAPORATOR-LOW PRESSURE safety
shutdown is initiated.
Valid communication between the microboard and the LTC I/O Board have been
EXPANSION I/O – SERIAL
disrupted for three consecutive attempts. The chiller automatically restarts when valid
COMMUNICATIONS
communication is received.
UPS – LINE LOW BATTERY This fault is also set during chiller state Stopped when all of the following are true:
VOLTAGE
• The Battery Voltage Faults setting is Enabled
• The Control Voltage digital input is high (indicates line power is available)
• The Battery Voltage < Line Low Battery Voltage Threshold
This shutdown often occurs when there is a sudden change in the input voltage due to
storms, utility power problems, or site power problems.
The VSD contains two temperature sensors, which monitor the unit’s internal ambient
temperature. This shutdown is generated when the higher of the two ambient
temperatures exceeds a high limit of 158°F (70°C). The unit’s fans and water pumps
VSD – HIGH INTERNAL remain energized until the internal temperature drops below 148°F (64°C), after which
AMBIENT TEMPERATURE they are de-energized and the fault can be cleared. Some potential causes for this
shutdown are internal drive fan failure, drive coolant pump failure, entering condenser
water temperature higher than design, condenser water flow lower than required, fouled
drive heat exchanger, or restriction of condenser water to the drive.
If the safety shutdown occurs, the chiller can be restarted after the Clear Faults button is
pressed.
VSD – HIGH PHASE B INPUT
See the previous message, VSD – HIGH PHASE A INPUT CURRENT.
CURRENT
VSD – HIGH PHASE C INPUT
See the previous message, VSD – HIGH PHASE A INPUT CURRENT.
CURRENT
If the A phase motor current exceeds the value for the given model of drive, then a cycling
shutdown occurs. If three high motor current cycling shutdown faults occur on any phase
within 90 min, the third fault in the 90 min period causes a Safety Shutdown.
VSD – HIGH PHASE A MOTOR Drive model Motor current fault value
CURRENT 0490B 776 A
If the safety shutdown occurs, the chiller can be restarted after the Clear Faults button is
pressed.
VSD – HIGH PHASE B MOTOR
See the previous message, VSD – HIGH PHASE A MOTOR CURRENT.
CURRENT
VSD – HIGH PHASE C MOTOR
See the previous message, VSD – HIGH PHASE A MOTOR CURRENT.
CURRENT
When power is connected, all boards go through the initialization process. At this
time, memory locations are cleared, program jumper positions are checked, and serial
communications links are established. If this process is not completed, the OptiView panel
indicates this fault. There are several causes for an unsuccessful initialization as follows:
• Serial data communications must be established. If communications between
VSD INITIALIZATION FAILED
the drive logic board and control center Microboard does not take place during
initialization, this message will be generated. The Serial communications can be
verified by selecting the VSD Details screen from the Motor screen and observing
the Full Load amps value. A zero displayed for this and other VSD parameters,
indicates a serial communications link problem.
The drive logic board is able to determine which model of drive can run which model of
motor. If the Control Center provides a model of motor that is not compatible with this
model of VSD, then this shutdown is generated. This shutdown is also generated when
VSD – INVALID SETPOINTS
the measured line frequency does not match the programmed input frequency from the
Control Center. When this condition clears, the chiller can be started after the Clear Faults
button is pressed.
The input voltage to the drive is not phase rotation sensitive, but the drive must be able to
VSD – LINE VOLTAGE PHASE
determine the correct input phase rotation. If the drive logic board cannot determine the
ROTATION
correct phase rotation, then this shutdown is generated.
This shutdown is generated by the drive logic board and it indicates that the low voltage
VSD – LOGIC BOARD POWER
power supplies for the logic boards have dropped below their allowable operating limits.
SUPPLY
This message usually means the power to the VSD has been removed.
VSD – LOGIC BOARD This shutdown is generated if a communications problem occurs between the two
PROCESSOR microprocessors on the drive logic board.
This shutdown often occurs when there is a sudden change in the input voltage due to
storms, utility power problems, or site power problems.
The temperature of the input baseplate phase A has decreased below the low limit of
VSD – LOW PHASE A INPUT 34°F (1.1°C). All phase temperatures must increase above the fault-reset threshold of 42°F
BASEPLATE TEMPERATURE (5.6°C) for this fault to clear. The cooling fans and pumps turn on while this shutdown is
present. They turn off when the temperature rises above the fault-reset threshold.
VSD – LOW PHASE B INPUT
See the previous message, VSD – LOW PHASE A INPUT BASEPLATE TEMPERATURE.
BASEPLATE TEMPERATURE
VSD – LOW PHASE C INPUT
See the previous message, VSD – LOW PHASE A INPUT BASEPLATE TEMPERATURE.
BASEPLATE TEMPERATURE
The control center determines this fault when the temperature of the motor baseplate
phase A has decreased below the low limit of 34°F (1.1°C). All phase temperatures
VSD – LOW PHASE A MOTOR
must increase above the fault-reset threshold of 42°F (5.6°C) for this fault to clear. The
BASEPLATE TEMPERATURE
cooling fans and pumps turn on while this shutdown is present. They turn off when the
temperature rises above the fault-reset threshold.
VSD – LOW PHASE B MOTOR
See the previous message, VSD – LOW PHASE A MOTOR BASEPLATE TEMPERATURE.
BASEPLATE TEMPERATURE
VSD – LOW PHASE C MOTOR
See the previous message, VSD – LOW PHASE A MOTOR BASEPLATE TEMPERATURE.
BASEPLATE TEMPERATURE
The control center determines this fault when the VSD has not reported run state through
VSD – NOT RUNNING serial communications for 8 s while the microboard issues a VSD run command. The fault
is released when the microboard command is Stopped State.
When the drive begins precharge, the output of the input current Direct Current Current
VSD – PHASE A INPUT DCCT Transformers (DCCT) are evaluated to ensure that they are reading zero current when no
OFFSET current is flowing through the DCCT. If the zero current output value is above a threshold,
then this shutdown is generated.
VSD – PHASE B INPUT DCCT
See the previous message, VSD – PHASE A INPUT DCCT OFFSET.
OFFSET
VSD – PHASE C INPUT DCCT
See the previous message, VSD – PHASE A INPUT DCCT OFFSET.
OFFSET
The gate driver board for the input/rectifier monitors the power supplies within the gate
VSD – PHASE A INPUT GATE driver circuit, and confirms that the input/rectifier can be correctly controlled. If the gate
DRIVER driver monitor determines that the input/rectifier cannot be correctly controlled, then the
drive shuts down and displays this message.
VSD – PHASE B INPUT GATE
See the previous message, VSD – PHASE A INPUT GATE DRIVER.
DRIVER
VSD – PHASE C INPUT GATE
See the previous message, VSD – PHASE A INPUT GATE DRIVER.
DRIVER
The gate driver board for the motor/inverter monitors the power supplies within the gate
VSD – PHASE A MOTOR GATE driver circuit, and confirms that the motor/inverter can be correctly controlled. If the gate
DRIVER driver monitor determines that the motor/inverter cannot be correctly controlled, then the
drive shuts down and displays this message.
VSD – PHASE B MOTOR GATE
See the previous message, VSD – PHASE A MOTOR GATE DRIVER.
DRIVER
VSD – PHASE C MOTOR GATE
See the previous message, VSD – PHASE A MOTOR GATE DRIVER.
DRIVER
The drive must be able to determine the input voltage frequency from the input voltage
VSD – PHASE LOCKED LOOP measurement. If the input voltage frequency is not stable enough for the drive to make
this determination, then this shutdown is generated.
If the input voltage of any one phase drops below the threshold value for the given input
voltage range in the previous table, then this shutdown occurs.
See the previous message, VSD SHUTDOWN – REQUESTING FAULT DATA. If the control
VSD – STOP (FAULT) center does not receive the cause of the Fault over the Serial Link within 20 s, it is assumed
CONTACTS OPEN it is not forthcoming and that message is replaced with VSD – STOP CONTACTS OPEN
message.
The chiller can be started after the evaporator pressure increases to the restart threshold and the
Clear Fault button is pressed.
Smart Freeze protection is activated and has shut down the chiller because the evaporator
temperature has been below the Smart Freeze threshold for greater than the allowable number of
s. If the Evaporator Refrigerant Temperature sensor RT7 is Enabled, using procedure in YORK YVAM
Service Manual (Form 160.88-M2), this parameter is used as the evaporator refrigerant temperature
and the freeze threshold is 32.8°F (0.4°C). If RT7 is not enabled, the evaporator refrigerant
temperature used is the Evaporator Saturation Temperature, derived from the Evaporator Pressure
EVAPORATOR – LOW Transducer and the freeze threshold is 34.0°F (1.1°C).
PRESSURE – SMART The total count is incremented once for every s the evaporator refrigerant temperature is below the
FREEZE freeze threshold, but it is never decremented below zero. The number of s it takes the chilled liquid
to freeze is based on how far the evaporator refrigerant temperature is below the freeze threshold as
follows:
# s to freezing = (4053.7) / (freeze threshold – evap. refrigerant temp.)
Smart Freeze is activated only if the feature has been Enabled by a service technician, following
instructions in YORK YVAM Service Manual (Form 160.88-M2), and the Leaving Chilled Liquid
temperature Setpoint is less than 38.0°F (3.3°C).
A possible defective Evaporator pressure Transducer or Leaving Chilled Liquid temperature
Thermistor has been detected. The pressure and temperature that these devices are indicating are
not in the correct relationship to each other. The control center converts the evaporator pressure to
EVAPORATOR – a Saturated Temperature value and compares this value to the Leaving Chilled Liquid temperature
TRANSDUCER OR (difference = chilled liquid temp – evaporator saturated temp). The difference must
LEAVING LIQUID not be outside the range of –2.5°F (–1.4°C) to +25.0°F (13.9°C). If the Transducer and Thermistor are
PROBE accurate, the Evaporator Saturated temperature must not be greater than 2.5°F (1.4°C) warmer or
greater than 25.0°F (13.9°C) colder than the leaving chilled liquid temperature. In order to initiate a
shutdown, the difference must be outside the acceptable range continuously for 10 min. The chiller
can be started after the Clear Fault button is pressed.
A possible defective evaporator pressure transducer or refrigerant temperature sensor has been
detected. The control center converts the evaporator pressure to a Saturated Temperature value and
compares this value to the optional Evaporator Refrigerant Temperature Sensor. If the difference
between these temperatures is greater than 3.0°F (16.7°C) continuously for 1 min, this shutdown is
performed. This check is only performed under the following conditions:
• Chiller has been running for at least 10 min
EVAPORATOR – • Evaporator refrigerant temperature (RT7) has been enabled by a service technician using
TRANSDUCER OR instructions in YORK YVAM Service Manual (Form 160.88-M2)
TEMPERATURE
• Not in brine cooling mode
SENSOR
• Smart Freeze is enabled
• Evaporator Temperature Sensor (RT7) or Evaporator Saturation Temperature is indicating a
temperature of less than 32.0°F (0°C)
The chiller can be started after the temperatures are within 3.0°F (1.67°C) of one another and the
Clear Fault button is pressed.
INTERNAL ERROR – BRAM is detected to be a size other than 512K. The warning clears when the correct size BRAM is
INVALID BRAM detected on boot up.
The Sales Order - Invalid Compressor Model safety shutdown is set when any of the
following are true:
• Motor is anything other than M2 or M6
• Motor Rev is anything other than C
• Character other than ‘-‘ between position 3 and 4
• SS/LS Imp. Diam. is anything other than 164, 174, 186, 197, 205, 218, 233, 246, 275, 295, or 331
• SS/LS Rotation is anything other than F
• SS/LS Imp. Rev. is anything other than the character A
• SS/LS Flow Rev. is anything other than the character C
• Motor Model is invalid
SALES ORDER • Invalid impeller/motor combination
- INVALID
COMPRESSOR MODEL The following table shows all valid impeller and motor combinations for single stage:
Compressor Motor
197FA M1 M2
205FA M1 M2
218FA M1 M2
233FA M2 M4
246FA M2 M4 M6
275FA M4 M6
295FA M4 M6
331FA M6
The following table shows all valid impeller and motor combinations for two stage:
Compressor Motor
233FA / 205RA M1 M2
275FA / 241RA M2 M4 M6
331FA / 291RA M4 M6
The fault is released when the values have been corrected. The chiller can be restarted after the Clear
Faults button is pressed.
This message applies only if the Surge Protection Shutdown feature is enabled.
SURGE PROTECTION
The Surge Window Count surge events exceeded the Count Limit setpoint. The chiller shuts down as
– EXCESS SURGE
soon as the count exceeds the limit. The chiller can be started after the Clear Fault button is pressed.
The Microboard’s software Watchdog initiated a Microprocessor reset because it detected that a
portion of the chiller operating program was not being executed. The result of this reset is a Safety
WATCHDOG –
shutdown and re-initialization of the program. This is generally indicative of a severe electrical power
SOFTWARE REBOOT
disturbance or impending Microboard failure. The chiller can be started after the compressor switch
is placed in the Stop-Reset (O) position.
UPS – BATTERY NOT This fault is also set during chiller state Stopped when all of the following are true:
CONNECTED • Battery Voltage Faults is Enabled
• Battery Disconnected Counter >= 4
Note: The thresholds for set and release are intended to be different.
The VGD actuator fault digital input has lost voltage either by wiring issue or fault indicated at the
VGD ACTUATOR
actuator. The chiller begins a standard soft shutdown. The fault clears when the digital input detects
FAULT
voltage. When the condition clears, the chiller can be started after the Clear Faults button is pressed.
The VGD Position feedback indicates greater or less than the VGD command by 5% for one min
VGD POSITIONING
continuous. The fault clears when the position is within the command + 5 % over one min. When the
FAULT
condition clears, the chiller can be started after the Clear Faults button is pressed.
VGD FEEDBACK The VGD Feedback voltage is below 0.4 VDC or above 4.6 VDC. It is released when voltage is within the
FAULT range. When the condition clears, the chiller can be started after the Clear Faults button is pressed.
Anytime the chiller is in a non-running condition, the DC Bus voltage is monitored and checked
VSD – DC BUS
against a threshold level of 100 VDC every five min. If the DC Bus voltage is higher than the threshold
LOCKOUT – DO NOT
value, this shutdown is generated. When the condition clears and drive input modules are tested and
CYCLE POWER
determined acceptable the chiller can be started after the Clear Faults button is pressed.
If the drive fails to complete pre-regulation due to VSD – DC BUS PRE-REGULATION fault, it must
repeat pre-charge in order to attempt another pre-regulation. The drive waits 10 s before clearing
VSD – DC BUS the DC Bus voltage pre-regulation fault and allowing another pre-charge to start. The unit’s fans
PRE-REGULATION and water pumps remain energized during this wait time. The drive allows up to three consecutive
LOCKOUT pre-regulation related faults (that is VSD-DC BUS REGULATION) to occur. After the third consecutive
fault, this shutdown is generated. When the condition clears, the chiller can be started after the Clear
Faults button is pressed.
This message is generated when the sum of the three phases of instantaneous input current values
are greater than the shutdown value for a period of 1 s for the given model of drive listed in the
following table.
VSD – GROUND
Drive model Ground current shutdown value
FAULT
0490B 40 A
When the condition clears, the chiller can be started after the Clear Faults button is pressed.
When the condition clears, the chiller can be started after the Clear Faults button is pressed.
VSD – PHASE B
See the previous message, VSD – PHASE A INPUT DCCT.
INPUT DCCT
VSD – PHASE C
See the previous message, VSD – PHASE A INPUT DCCT.
INPUT DCCT
The motor current in each phase of the drive is measured at the beginning of the run command. The
motor current at this time must measure very low. This low value is used as the zero current value
VSD – PHASE A for the rest of this run time. The motor current is then monitored for the next 1.5 s to ensure that a
MOTOR DCCT minimum amount of current is flowing to the motor. After 1.5 s, if the motor current is less than 25 A
on any phase, then this shutdown is generated. When the condition clears, the chiller can be started
after the Clear Faults button is pressed.
VSD – PHASE B
See the previous message, VSD – PHASE A MOTOR DCCT.
MOTOR DCCT
VSD – PHASE C
See the previous message, VSD – PHASE A MOTOR DCCT.
MOTOR DCCT
A tripped circuit breaker is an indication of a serious fault condition, and must never be reset without
an inspection of the drive by certified technician.
Callout Description
A Smart sensor board mounted behind door rail
B Smart sensors
Check the condenser coils and VSD cooling coils for dirt and debris, and X
clean if necessary.
Check the condenser coils for dirt and debris, and clean if necessary. X
Verify the VSD heat exchanger coolant level and add coolant if necessary. X
Review the operating data for trends that indicate increasing vibration or X
power consumption. The MBC data includes 1 x rotational speed vibration
in displacement.
Clean the evaporator tubes. X (2)
Check all enclosure door gaskets for any signs of leakage or damage that X
might cause a leak. This includeS the VGD actuator shaft bellows.
Check the OptiView panel cooler condensate drain tube for any blockage. X
Replace all vapor emitters in the VSD and any other locations where they X
are present.
Verify the operation of the Smart Sensor System. X
Verify the VSD coolant concentration is 44% propylene glycol (PG) using a X
refractometer.
Replace the VSD starter coolant. 5 years
Note:
This procedure must be performed at the specified time interval by an Industry Certified
(1)
Technician who has been trained and qualified to work on this type of YORK equipment. A
record of this procedure being successfully carried out must be maintained on file by the
equipment owner if proof of adequate maintenance is required at a later date for warranty
validation purposes.
For operating and maintenance requirements listed above, refer to appropriate service literature,
Form 160.88-MR1, or contact your local Johnson Controls Service Office.
Electrical isolation
1. Isolate electrical power supply to the chiller from the facility.
2. Isolate the power panel battery from the uninterrupted power supply (UPS) by opening the
power panel disconnect switch.
3. Isolate plant fluid flow to the chiller at appropriate valves or have refrigerant isolated to
prevent free-wheeling the driveline and generating electrical energy from the permanent
magnet rotor.
Renewal parts
For any required renewal parts, refer to Solution Navigator at Parts Navigator
(solutionnavigator.com).
Operating inspections
By following a regular inspection using the display readings of the OptiView Control Center and a
maintenance procedure, the operator can avoid serious operating difficulty. Use the following list of
inspections and procedures as a guide for maintenance.
Weekly
1. Check the OptiView™ Control Center displays.
2. Check the entering and leaving chilled liquid temperatures and evaporator pressure for
comparison with the job design conditions. Chilled liquid temperatures can be checked on
the System screen.
3. Check the condenser saturation temperature on the System screen. The condenser
saturation temperature is based on condenser pressure sensed by the condenser transducer.
4. Check the compressor discharge temperature on the System screen. During normal
operation, make sure that the discharge temperature does not exceed 220°F (104°C).
5. Check the compressor motor current on the System screen.
6. Check for any signs of dirty or fouled condenser coils. Make sure that the temperature
difference between air temperature leaving condenser and the saturated condensing
temperature does not exceed the difference recorded for a new unit by more than 4°F (2.2°C).
Monthly
1. Leak check the entire chiller.
2. Check the condenser coils and VSD cooling coils for any evidence of dirt or debris that might
block air flow.
Semi-annually
Check the controls semi-annually, or more often, as required.
WARNING
Care must be taken not to exceed the rated pressure of the unit refrigerant pressure relief valves.
- When using a refrigerant-based trace gas, you must always charge with vapor only to
reach the initial 10 psig (69 kPa) pressure.
- The use of trace gas must adhere to local policies in regard to venting or recovery of
the gas. This is dependent on the gas that is selected.
- Important: Use a suitable gas detection device that can detect the trace gas that
is selected.
- Set the gas detection limit for 10% R-134a based trace gas to 0.078 oz/year R-143a.
4. Add dry nitrogen into the chiller until the pressure reaches 100 psig (69 kPa).
5. To make sure that the concentration of trace gas has reached all parts of the system,
complete the following steps:
a. Slightly open the condenser service at the liquid drain connection into the evaporator
service valve.
b. Test for the presence of the trace gas with a leak detector.
c. Continue to vent in this manner until the trace gas is detected and close the service
valve.
6. Before beginning the trace gas testing, ensure that any vented gas has been adequately
vented from the chiller area so that there are no false positive indications. It might be
necessary to reset the test probe in an outside space.
7. Test around each joint and factory weld carefully and thoroughly.
8. To check for tube or tube joint leaks, complete the following steps:
a. Isolate and drain the evaporator waterboxes.
b. Purge the waterboxes and tubes with dry nitrogen through the vents or drains until the
detector does not indicate any evidence of refrigerant.
c. Close the vents and drains. Wait an hour.
d. Open a drain and insert the leak detector.
9. If a tube leak is suspected, complete the following steps:
a. Remove the waterboxes to facilitate application of the soap solution to the tubesheets.
b. To test for tube wall leaks, insert a rubber cork in both ends of each tube, and leave
pressurized for at least 8 hours.
System evacuation
WARNING
Ensure that power is removed from the input side of the VSD at all times when the chiller is under
vacuum (less than atmospheric pressure). The VSD maintains voltage to ground on the motor when
the chiller is off while voltage is available to the VSD. Insulating properties in the motor are reduced in
vacuum and may not insulate this voltage sufficiently.
Vacuum dehydration
Before you perform the final evacuation and system charging, it is necessary to obtain a sufficiently
dry system. The following instructions have been assembled to provide an effective method
for evacuating and dehydrating a system in the field. Although there are several methods of
dehydrating a system, the following method produces one of the best results and provides
accurate readings of the extent of dehydration. The equipment required to follow this method of
dehydration consists of the following items:
• High resolution vacuum gauge (microns below 500)
• Chart that shows the relationship between dew point temperature and pressure in microns
(vacuum), see Table 95
• Vacuum pump that can pump a suitable vacuum on the system
Follow the dehydration steps as closely as possible to prevent moisture from becoming trapped
in the system. If you apply too deep of a vacuum, any trapped moisture might freeze and not be
exhausted as vapor. Failure to remove all of the moisture can create acids in the refrigerant circuit.
These acids can damage internal system components over time and cause premature failure of
items such as the compressor, motor, and any other devices sensitive to acid contact.
Note:
• One standard atmosphere = 14.696 psia = 760 mm Hg absolute pressure at 32°F = 29.921
in. Hg absolute at 32°F
• psig = pound per square inch gauge pressure = pressure above atmosphere
• psia = pound per square inch absolute pressure = sum of gauge plus atmospheric
pressure
• Shell volume = L*π * r2= (Length in feet)*( 3.1416)*(radius squared) = cubic feet
To keep the units consistent, round the length and radius to the nearest tenth of a foot.
• μm = Micron
When this point is reached, practically all of the air has been evacuated from the system, but a small
amount of moisture still remains. In order to provide a medium for carrying this residual moisture
to the vacuum pump, nitrogen must be introduced into the system to bring it to atmospheric
pressure and the indicator temperature will return to approximately ambient temperature. Close
off the system again, and start the second evacuation. The relatively small amount of moisture left
1. Connect a high capacity vacuum pump, with indicator, to the system charging valve as shown
in Figure 50.
- If the pressure rise goes to 0 psig (0 kPa), it indicates that a leak is present.
- During the hold period, if moisture is present, the pressure stabilizes at some level
below atmosphere and must correspond to the room ambient temperature or the
heat being applied to the vessel. See Table 95 for values.
7. An acceptable vacuum pressure rise is 150 μm (150 micron) in 60 min.
- 1000TR 1,000 μm (1,000 micron)
- See factory standard
8. If the vacuum does not hold within the limits defined in Step 7, you must find and repair the
leak. For cases where leaks cannot be identified while pressurized but vacuum hold tests
indicate that there is a leak, in most cases this can be traced to an elastomeric or O-ring
sealing issue.
Result
When the 500 μm (500 micron) hold test is successful, you can charge the system using the steps in
Refrigerant charging.
Refrigerant charging
Before beginning, it is critical to establish that the vapor portion of the refrigerant container or
cylinder has not been contaminated with other gases that are not R-134a, including air. Use the
appropriate saturation property R-134a. See Table 96 to determine if the saturation pressure and
ambient temperature of the refrigerant in the container indicates that the gas pressure coincides
with the corresponding temperature.
To prevent liquid freezing within any of the chiller tubes when charging an evacuated system, make
sure that only the refrigerant vapor from the top of the drum or cylinder is admitted to the system
until the system pressure is raised above the corresponding saturation pressure at the freezing
point of the chilled liquids. For all other liquids, establish the freeze point temperature and vapor
charge to an appropriate pressure that is 5°F (2.78°C) higher than that freeze point. For water with
R-134a at 32°F (0°C), that pressure is 28 psig (193 kPa). See Table 96.
Before charging, establish that starting weight for the refrigerant cylinder. When the chiller has
been vapor charged to the appropriate saturation pressure, you might need to use a refrigerant
pump to draw vapor from the chiller and discharge it to the vapor connection of the refrigerant
cylinder. This helps to create a pressure differential for pushing the refrigerant liquid from the
cylinder to the chiller.
While charging, take every precaution to prevent air from entering the system. Create a suitable
charging connection from new copper tubing or correctly selected flexible charging hoses. Fit this
charging connection between the system charging valve and the fitting on the charging drum.
This connection must be as short as possible but long enough to provide sufficient flexibility for
changing drums. It must also contain a tee fitting with a valve that can serve as a connection point
to a vacuum pump to evacuate the charging lines.
The charging connection must be evacuated each time the lines are disconnected for changing
cylinders or any of the components of the charging process.
The charging line must also contain a sight glass. When liquid charging is performed, the sight
glass can be monitored to determine when the liquid is no longer being transferred to the chiller.
The refrigerant charge is specified for each chiller model on the unit data plate or in the factory
order form (FOF) that is provided for every new sale. Charge the chiller based on the amount
specified in the FOF less 10%. For example, for a chiller that requires 500# of refrigerant, the
initial refrigerant charge is 450#, 500 - 50 = 450. This allows room to trim the charge as outlined in
Checking and trimming the refrigerant charge.
WARNING
To avoid the possibility of freezing liquid within any the chiller tubes when removing refrigerant from a
charged system, the required method is to run the chilled water pumps during this process to eliminate
the risk of tube freezing during the recovery process. The chilled liquid flow must remain present for
the entire refrigerant recovery process. If water flow cannot be maintained, it is imperative that the
chilled liquid be completely drained from the chiller and the waterbox vents and drains are all open
before beginning this process.
Before the removal of any charge into the containers, for optimal performance, use an empty, fully
evacuated refrigerant container. This ensures that the container is not contaminated and aids in
the efficient removal of refrigerant.
Before removing any refrigerant, establish the starting weight (tare weight) for the refrigerant
cylinder and log the final weight for each container that is used for the recovery. This ensures that
the correct weights are noted for determining the chiller refrigerant charge amount.
While handling refrigerant into or out of any chiller, every precaution must be taken to prevent air
from entering the system when handling the charging lines. Create a suitable charging connection
from new copper tubing or correctly selected flexible charging hoses. Fit this charging connection
between the system service or charging valves and the fitting on the refrigerant container. This
connection must be as short as possible but long enough to provide sufficient flexibility for
changing containers. It must also contain a tee fitting with a valve that can serve as a connection
point to a vacuum pump to evacuate the charging lines.
The charging connection must be evacuated each time the lines are disconnected for changing
cylinders or any of the components of the charging process. The charging line for the refrigerant
liquid must also contain a sight glass. When liquid refrigerant is being handled, the sight glass can
be monitored to determine when the liquid is no longer being transferred to or from the chiller.
1. Navigate to Condenser/Drain Control screen and manually set the drain valve to 100% open.
This ensures that any condensed liquid drains to the evaporator.
2. Connect the liquid refrigerant charging connection on the bottom of the evaporator to the
refrigerant container liquid connection only.
3. To help move the liquid refrigerant, you must use a push and pull method to lower the
pressure in the recovery container and raise the chiller system vapor pressure. This method
draws vapor suction from the recovery container vapor connection and discharges into the
condenser vapor connections. This allows all liquid refrigerant to be pushed to the recovery
container.
Note:
• The refrigerant weight is based on a maximum tube bundle.
• The water weight is the total water in the evaporator shell and for 150 psi, two-pass,
compact waterbox.
Evaporator maintenance
Maintenance of the evaporator shell is important to provide trouble-free operation of the chiller.
The water side of the tubes in the shell must be kept clean and free from scale.
The major portion of maintenance on the evaporator involves maintaining the water side of the
evaporator in a clean condition.
The use of untreated water in closed water systems and similar environments frequently results in
one or more of the following issues:
• Scale formation
• Corrosion or rusting
• Slime and algae formation
As a result, to ensure a longer and more economical life of the equipment, it is beneficial for the
user to provide for correct water treatment. To determine the condition of the water side of the
evaporator tubes, use the following guidance:
• The evaporator tubes under normal circumstances do not require cleaning. However, if the
temperature difference between the refrigerant and the chilled water increases slowly over
the operating season, it can indicate the following issues:
- The evaporator tubes are fouling
- A water bypass in the waterbox requires gasket replacement
- Refrigerant has leaked from the chiller
Tube fouling
Fouling of the tubes can occur due to the following types of deposits:
• Rust or sludge: This can enter the tubes and accumulate there. This material usually does not
build up on the inner tube surfaces as scale, but does interfere with the heat transfer. Rust or
sludge can generally be removed from the tubes by a thorough brushing process.
• Scale: This develops due to mineral deposits. These deposits, even though very thin and
scarcely detectable on physical inspection, are highly resistant to heat transfer. They can
be removed most effectively by circulating an acid solution through the tubes using skilled
experts as described in the following section.
WARNING
Acid cleaning must only be performed by an expert. Consult your local water treatment representative
for assistance in removing scale buildup and for preventative maintenance programs to eliminate
future problems.
1. Remove the heads and listen at each section of tubes for a hissing sound that might indicate
gas leakage. This can help identify the section of tubes that requires further investigation.
- If you can determine the probable location of the leaky tubes, go to Step 2 to treat
that section.
- If the location is not definite, you must investigate all of the tubes.
2. Wash off both tube heads and the ends of all tubes with water.
3. To clear the tubes of traces of refrigerant-laden moisture from the circulation water, blow out
the tubes with nitrogen or dry air.
4. As soon as the tubes are clear, insert a cork into each end of the tube.
5. Pressurize the dry system with 50 psig to 100 psig (345 kPa to 690 kPa) of nitrogen.
6. Repeat Step 3 to Step 5 with all of the other tubes in the suspected section or, if necessary,
with all the tubes in the evaporator.
7. Keep the cork inserted in the evaporator tubes for 12 to 24 h before proceeding.
- Depending upon the amount of leakage, the corks may blow from the end of a tube,
indicating the location of the leakage. Go to Step 9.
- If the corks remain inserted, go to Step 8 to conduct a thorough test with the leak
detector.
8. If the corks remain inserted after 12 to 24 h, two people working at both ends of the
evaporator must carefully test each tube. One person removes the corks at one end of the
tube and the s person removes corks from the opposite end and handles the leak detector.
a. Begin with the top row of tubes in the section being investigated and remove the corks
at the ends of one tube simultaneously.
b. Insert the exploring tube for 5 s. This is the amount of time required to draw any
refrigerant gas that might have leaked through the tube walls into the detector. A fan
placed at the end of the evaporator opposite the detector can ensure that any leakage
travels through the tube to the detector.
9. Mark any leaking tubes for later identification.
What to do next:
If any of the tube sheet joints are leaking, the leak can be indicated by a leak detector. If a tube
sheet leak is suspected, its exact location can be found by using a soap solution. A continuous
buildup of bubbles around a tube indicates a tube sheet leak.
Standard and Environment Guard microchannel coils must be cleaned following this procedure at
least once every quarter or every 3 months to ensure that the integrity of the coils and the warranty
of the coils are maintained. In environments where coils can become heavily fouled, a monthly
frequency of cleaning is recommended.
1. Use a vacuum cleaner with a soft brush attachment to remove surface debris such as dirt,
leaves, insects, or fibers. When brushing debris off the face of the coil, you can also use a
soft bristle brush. Do not use a wire brush. Do not scrape the coil with the vacuum nozzle, air
nozzle, or any other hard tool.
2. Rinse the coil with potable tap water. Use a gentle spray from a spray nozzle with a plastic
end. Do not contact the coil with the hose nozzle. Rinse the coil by running water through
every passage in the heat exchanger surface until it is clean.
3. It is important to remove any excess water trapped in the coils immediately after the final
water rinse.
a. To fully dry the coils, run the condenser fans on the chiller after the final water rinse.
b. To remove any excess water, blow air through the coils with a hand-held blower or
vacuum.
Environment Guard Premium microchannel coils must be cleaned following this procedure at least
once every quarter or every 3 months to ensure that the integrity of the coils and the warranty
of the coils are maintained. In environments where there are high levels of pollution or corrosive
elements, use a monthly cleaning procedure to remove debris, rinse with water, and dry, in
addition to the quarterly cleaning using approved cleaning solutions.
1. Use a vacuum cleaner with a soft brush attachment to remove surface debris such as dirt,
leaves, insects, or fibers. When brushing debris off the face of the coil, you can also use a
soft bristle brush. Do not use a wire brush. Do not scrape the coil with the vacuum nozzle, air
nozzle, or any other hard tool.
2. Rinse the coil with potable tap water. Use a gentle spray from a spray nozzle with a plastic
end. Do not contact the coil with the hose nozzle. Rinse the coil by running water through
every passage in the heat exchanger surface until it is clean.
3. Apply a coil cleaning solution approved by Johnson Controls. Details of solutions approved for
use are documented in product manuals.
4. To remove the cleaning solution, repeat the water rinse.
5. Apply a salt reducer solution approved by Johnson Controls. Details of solutions approved for
use are documented in product manuals.
6. To remove the salt reducer solution, repeat the water rinse. The final rinse must be thorough
to ensure that all cleaning solution and salt reducer solution is removed from the coils.
7. It is important to remove any excess water trapped in the coils immediately after the final
water rinse.
a. To fully dry the coils, run the condenser fans on the chiller after the final water rinse.
b. To remove any excess water, blow air through the coils with a hand-held blower or
vacuum.
Electrical controls
Perform annual checks to ensure that all electrical connections are tight and that connectors are
secure.
Important: Do not change the factory settings of operation and safety controls. If the settings
are changed without Johnson Controls approval, the warranty will be jeopardized.
All appropriate electrical safety measures must be followed when testing these heaters because these
circuits will be energized.
CAUTION
The evaporator water loop must be filled before conducting the following tests to prevent damage to
the heaters for the evaporator related components.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize the heater.
2. At the HTR DIST panel, use wires 131 and 131A to measure the current to the heaters. The
nominal current for each one is 3 A. However, it might read lower values based on the load at
the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize heaters.
2. At the auxiliary power panel, use wires 325 and 325 A to measure the current to the heaters.
The nominal current for each one is 1 A. However, it may read lower values based on the load
at the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize the heater.
2. At the HTR DIST panel, use wires 131 and 131A to measure the current to the heaters. The
nominal current for each one is 2 A. However, it may read lower values based on the load at
the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2.
2. Use an electronics safe freeze spray to lower the temperature of the metal portion of the
heater switch to energize the heater. The spray can be purchased at most supply houses. See
Figure 54 for the switch image.
3. Record the value in 160.88-CL2.
Callout Component
A Fans
B Control panel cooler thermostat control
C Control panel heater thermostat control
1. To operate the cooler, set the value of the control panel cooler thermostat knob to a
temperature lower than ambient. See Figure 56.
2. When the cooler is running, check for cool air flowing from the top of the cooler unit.
3. After confirming operation, set the thermostat back to 90°F (32.2°C).
To verify that the heating and cooling circuit is functioning, use the OptiView panel to navigate to
the appropriate screens for manually operating the coolant pumps for each cabinet.
1. Navigate to Home > VSD > VSD Details > Manual Cooling and select Enabled.
2. Verify that the VSD coolant pump is operating.
3. Navigate to Home > VSD > Power Panel > Manual Power Panel Cooling and select Enabled.
4. Verify that the power panel coolant pump is operating.
5. Disable the manual operation of both pumps.
6. Note the correct operation of the pumps in 160.88-CL2.
Acceptable printers
The following printers can be used. Printers must be equipped with an RS- 232 Serial interface.
• OKI Data OKIPOS 441
• Brecknell CP130
The Control Center provides the required formatting control codes for the printers above when the
printer is selected on the printer screen. These codes are transmitted through the serial interface to
the printer to provide a correct print format.
Different printers require different formatting control codes. Other printers might provide correct
operation when connected to the Control Center. However, the print format may not be correct or
as required.
OKI Data
Models: OKIPOS 441
• Dimensions: 5.98 in. x 6.90 in. x 9.64 in. (H x W x D)
• Paper: 3.0 in. wide
• Type: Dot Matrix Impact
• Purchase: 800-OKI Data Spare printer Ribbon Okidata 52119001 Black
• P/N Charcoal P/N 62113901 Beige P/N 62113601
Printer connections
Connect the printer to the Control Center Microboard as follows. Only one printer can be connected
at a time.
Table 99: Okidata OkiPos 441
Microboard Printer Function
J2-4 pin 3 Tx (data to printer)
J2-2 pin 20 DSR (busy signal from printer)
J2-9 pin 7 Gnd
Cabinet Shield
1. With the printer power off, remove the two screws that hold the RS232 Interface Module.
2. Pull the RS232 Interface Module out of the printer.
3. Set DIP switch SW2-2 to OFF to select 19200 BPS. Do not change any other switch settings.
4. Re-install the RS232 Interface Module and two mounting screws.
5. Load paper and install the printer ribbon into the printer.
6. Connect the printer cable to the printer and the microboard.
7. Connect the printer power cable to the printer and plug into a 100 to 240VAC power source.
Brecknell
Models: Brecknell CP130
• Dimensions: 2.50 in x 3.75 in. x 5.25 in. (H x W x D)
• Paper: Thermal 57 mm (2.25 in.)
• Type: Dot Matrix
• Purchase: 800-637-0529 (North America), +44 (0) 845-246-6717 (Europe and ME)
• P/N AWT 05-505788 (printer, cable, 1 roll of paper)
• P/N AWT 05-505594 (power supply)
• P/N AWT 05-505671 (case, 20 rolls of paper)
Printer connections
Connect the printer to the Control Center Microboard as follows. Only one printer can be connected
at a time. Modify the cable and connect as shown in the following table.
Table 100: Printer connections
Microboard Printer Function
J2-4 Pin 3 TX Data to the printer
J2-2 Pin 5 Busy signal from the printer
J2-9 Pin 6 Signal Common
1. Connect the laptop computer to the OptiView™ as shown in the following table.
Table 101: Laptop connections
Laptop (RS-232 Serial Port) OptiView (Com 1)
PIN Description Connector Terminal
2 RX to J2 4 (TXD1)
4 DTR to J2 2 (DSR1)
5 GND to J2 9 GND
2. On the OptiView™ Printer screen, select PC. This allows faster data download than the
printer selections.
3. Navigate to the Setpoints > Setup > Comms screen and check that the printer settings match
the port settings listed in Substep h in the following step.
4. Set up the HyperTerminal as follows:
a. Go to the Start menu.
b. Select All Programs.
c. Select Accessories.
d. Select Communications.
e. Select HyperTerminal.
f. In the box displayed, it requires a name and icon for the connection. Select a name that
is descriptive and select an icon. Select OK.
g. In the box labeled Connect, select the com port that will connect to the YVAM unit. This
port is usually labeled Com 1. Click OK.
h. Enter the port settings as follows:
The connector on the PC has male pins. As a result, the mating cable needs to terminate DB9/F
(female pin) connector.
Table 103: RS-232 pin assignments (DB9 PC signal set) for most laptops
Pin Description
Received line Signal Detector
Pin 1
(Data Carrier Detect)
Pin 2 Received Data
Pin 3 Transmit Data
Pin 4 Data Terminal Ready
Pin 5 Signal Ground
Pin 6 Data Set Ready
Pin 7 Request To Send
Pin 8 Clear To Send
Pin 9 Ring Indicator
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius (°C), subtract 32° and multiply by 5/9 or
0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (for example, a range of 10°F) from Fahrenheit to Celsius, multiply
by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6°C range
© 2022 Johnson Controls. 5000 Renaissance Drive, New Freedom, York, PA 17349, USA. Subject to change without notice. All
rights reserved.