3-Wire RTD Measurement System Reference Design, - 200°C To 850°C
3-Wire RTD Measurement System Reference Design, - 200°C To 850°C
3-Wire RTD Measurement System Reference Design, - 200°C To 850°C
Design Resources
Ask The Analog Experts
Design Archive All Design files WEBENCH Design Center
TINA-TI SPICE Simulator TI Designs Precision Library
ADS1247 Product Folder
TPS7A4901 Product Folder
ADS1247
IDAC
AIN0/IEXC1 Excitation
RI1 CI_CM1
Current
AIN1 Sources
RRTD CI_DIFF AIN2
RI2 AIN3/IEXC2
CI_CM2
MUX PGA
ADC
Reference
Buffer/MUX
REFP REFN
CR_CM1 CR_CM2
CR_DIFF
RR1 RR2
RREF
An IMPORTANT NOTICE at the end of this TI reference design addresses authorized use, intellectual property matters and
other important disclaimers and information.
TINA-TI is a trademark of Texas Instruments
WEBENCH is a registered trademark of Texas Instruments
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 1
Copyright 2013, Texas Instruments Incorporated
www.ti.com
1 Design Summary
The design requirements are as follows:
The design goals and performance are summarized in Table 1. Figure 1 depicts the measurement
accuracy of the design.
0.05
0.0375
0.025
Temperature Error (C)
0.0125
Calibrated Results
-0.0125
-0.025
-0.0375
-0.05
0 50 100 150 200 250 300 350 400
RRTD ()
Figure 1. Measured Temperature Accuracy with Resistive Input Representing -200C to 850C
2 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
2 Theory of Operation
The relationship between resistance and temperature of an RTD is defined by the Callendar-Van Dusen
(CVD) equations which can be found in Appendix A.4.
Compared to a thermocouple, the main disadvantages of RTD sensors are their cost and required
excitation source. The small change in resistance of an RTD over temperature also places demands on
the accuracy of the acquisition circuit requiring a precision signal chain. Thermistors have larger changes
in resistance over temperature but are much less linear, reducing their effectiveness at measuring wider
temperature ranges.
VIN+
GAIN
RRTD VDIFF ADC
VIN-
An ADC requires a reference voltage to convert the input voltage into a digital output. In most applications,
this reference is fixed and either internally generated or externally applied to the ADC. This 3-wire RTD
system uses what is known as a ratiometric configuration to create the reference voltage, increasing
system accuracy.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 3
Copyright 2013, Texas Instruments Incorporated
www.ti.com
In the ratiometric configuration shown in Figure 3, the excitation current that flows through the RTD returns
to ground through a low-side reference resistor, RREF. The voltage potential developed across RREF, VREF,
is fed into the positive and negative reference pins (REFP and REFN) of the ADC. VREF serves three
purposes in this design: it sets the input common-mode voltage (VCM), the differential ADC input range
(typically VREF), and it is also used to convert the input voltage into digital output codes. See Equations
( 2 ) ( 6 ).
Setting VREF to mid-supply results in optimal input circuit performance for the ADC. R REF should be
selected with low tolerance and low drift since errors in the reference voltage will directly translate into
errors in the conversion result.
I1
VIN+
RRTD VDIFF GAIN
ADC
RREF
VREF VREF
VDIFF (3)
Gain Gain
The voltage drop across the RTD and RREF resistors is produced by the same excitation source in a
ratiometric configuration as shown in Equations ( 4 ) - ( 5 ). Therefore, any changes in the excitation
source are reflected in both the RTD differential voltage and the reference voltage. Since the ADC output
code is a relationship between the input voltage and the reference voltage, the final conversion result is
simply a ratio of the RTD and RREF resistances as shown in Equation ( 6 ). Consequently, inaccuracies due
to magnitude, temperature drift, and noise of the current source cancel without affecting the final
conversion result. The ratiometric configuration also helps reduce the effects of external noise that
appears common to both the inputs and the reference because it should cancel as well.
4 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Two precision current sources are typically used in 3-wire RTD applications to provide an easy way to
cancel the RTD lead resistances (RLEAD) as shown in Figure 4. This technique works best when the two
current sources are well-matched, both in initial accuracy and temperature drift. For additional information
on other RTD configurations, refer to Reference 2.
Equations ( 7 ) ( 10 ) derive the final differential input voltage and prove that RLEAD is excluded from the
final result.
I1
RLEAD VIN+
I1
RRTD VDIFF GAIN
ADC
RLEAD
REFP REFN
I2 VIN-
I1 + I2
RLEAD I2
RREF
I1 I2 I (7)
With two current sources flowing through RREF in this 3-wire RTD system, the VREF voltage doubles as
shown in Equation ( 11 ). Therefore, the final conversion result transfer function also changes as shown in
Equation ( 12 ).
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 5
Copyright 2013, Texas Instruments Incorporated
www.ti.com
VREF 2 I RREF ( 11 )
R Gain
CodeOUTPUT CodesTOTAL RTD ( 12 )
4 RREF
The magnitude of the current sources directly affects the magnitude of the RTD voltage. While maximizing
the magnitude of the excitation current would seem desirable, higher excitation currents create a concern
for violating the compliance voltage of the current source as well as errors due to self-heating.
The current sources will have a compliance voltage limitation based on the topology and supply voltage.
The voltage on the positive input (VIN+) must be limited to a level below the compliance voltage for the
current sources as defined by Equation ( 13 ).
The power-dissipation in the RTD leads to self-heating errors that cannot be easily corrected and should
be kept lower than 25% of the total error budget as a general practice. Keeping the excitation current small
will also minimize the heat produced in other signal path components, reducing drift and other additional
measurement errors. Figure 5 displays the self-heating errors in degrees Celsius versus applied excitation
current for both small and large RTD elements. The typical range of RTD self-heating coefficients is 2.5
mW/C for small, thin-film elements (shown in blue) and 65 mW/C for larger, wire-wound elements
(shown in red).
Self-Heating Error of an RTD vs. Exc itation Current
10
0.1
Temperature (C)
0.01
Error65mW( I)
3
110
Error2.5mW( I)
4
110
5
110
6
110
7
110
5 4 3
110 110 110 0.01
I
Figure 5. RTD Self-Heating vs. Excitation Current for Different RTD Types
6 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The effects of self-heating on measurement accuracy are also based on the placement of the RTD in the
application. The effects of self-heating are reduced if the RTD is placed in a moving fluid medium because
the moving fluid will keep the RTD close to the temperature of the fluid. However, in open-air temperature
measurements, or other applications where the RTD is surrounded by an insulator, the RTD will self-heat
and cause errors.
The full-scale input range of an ADC is bounded by the reference voltage, VREF. By choosing a smaller
value for the excitation current to reduce self-heating, the RTD produces a smaller change in voltage over
the span of the temperature measurement that will not use the full ADC input range. Therefore, a gain
stage is required to amplify the RTD voltage to a level that utilizes more of the range of the full-scale ADC
input, VIN_ADC, and maximizes the measurement resolution.
The gain must be selected such that neither the full-scale input voltage nor the common-mode input
voltage is violated. Both limitations are typically found in the device specifications section of the data
converter datasheet.
Using differential and common-mode low-pass filters at the input and reference paths improves the
cancellation of excitation and environmental noise. However, it is important to note that the corner
frequency of the two differential filters must be well-matched as stated in Reference 1. The input and
reference filters are shown in Figure 6.
I1
RI1 CI_CM1
RRTD CI_DIFF GAIN
RI2 ADC
RR1 RR2
RREF
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 7
Copyright 2013, Texas Instruments Incorporated
www.ti.com
3 Component Selection
The ADS1247 is a 24-bit, delta-sigma () ADC that offers a complete front-end solution for RTD
applications. It comes from a product family of highly integrated precision data converters, featuring a low-
noise programmable gain amplifier (PGA), a precision modulator, a digital filter, an internal oscillator,
and two digitally controlled precision current sources (IDACs). It is a popular industry choice for precision
temperature measurement applications. Other popular choices listed in Table 10 and Table 11 showcase
similar functionality and performance.
ADS1247
IDAC
AIN0/IEXC1 Excitation
RI1 CI_CM1
Current
AIN1 Sources
RRTD CI_DIFF AIN2
RI2 AIN3/IEXC2
CI_CM2
MUX PGA
ADC
Reference
Buffer/MUX
REFP REFN
CR_CM1 CR_CM2
CR_DIFF
RR1 RR2
RREF
The ADS1247 features two IDAC current sources capable of outputting currents from 50 A to 1.5 mA.
Based on Figure 5, the excitation currents will be set to 1 mA to maximize the RTD sensor output while
keeping the errors due to self-heating less than the desired goal of 0.05C.
The internal reference voltage must be on while using the IDACs, even if an external ratiometric reference
is used for ADC conversions. Table 2 displays the required register settings to set the IDACs to 1 mA and
configure them for the proper output channels.
8 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
As the equations in Section 2.2.2 show, the two current sources must be exactly matched to successfully
cancel the lead resistances of the RTD wires. While initial matching of the current sources is important,
any remaining mismatch in the two sources can be minimized by using a multiplexer to swap, or chop,
the two current sources between the two inputs. Taking measurements in both configurations and
averaging the readings will greatly reduce the effects of mismatched current sources. This design uses the
digitally-controlled multiplexer in the ADS1247 to realize this technique. The multiplexer also affords the
user some additional flexibility when routing the input voltage signals and excitation current sources on
their printed circuit board (PCB) layout.
In this application, the ADC uses a 3.3 V supply for both the analog (AVDD) and digital (DVDD) power
supplies. The excitation currents and RREF have been selected to produce a 1.64 V reference, allowing for
a differential input signal range of 1.64 V into the modulator. The maximum allowable PGA gain
setting is based on the reference voltage, the RTD resistance change, and the excitation current as shown
in Equations ( 15 ) ( 17 ).
VREF 1.64 V V
GainMAX 4.2 ( 17 )
VIN _ MAX 0.39048 V V
The PGA gain is set to the closest ADS1247 PGA gain that is below the maximum value calculated in
Equation ( 17 ). The PGA will be set to 4 V/V, as shown in Table 3.
3.2.1 RREF
The value of RREF is selected based on the IDAC setting and the desired VREF voltage of 1.64 V, as shown
in Equations ( 18 ) ( 19 ).
VREF
RREF ( 18 )
2 IIDAC
1.64 V
RREF 820 ( 19 )
2 1 mA
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 9
Copyright 2013, Texas Instruments Incorporated
www.ti.com
An 820 RREF resistor was chosen based on the results of Equation ( 19 ). Since the voltage across the
RREF sets the reference voltage for the ADC, the tolerance and temperature drift of R REF directly affect the
measurement gain error as shown in Section 4.2.2.1 and Appendix A.5.1. To meet the un-calibrated
accuracy requirement of 0.1 (or 0.027% of the full-scale resistance range), a resistor with 0.02%
maximum tolerance was selected.
Note that, as with any amplifier, it is necessary to ensure that the input voltage stays within the specified
common-mode input range listed in the device datasheet specification table. The common-mode input
voltage (VCM) to the PGA must stay within the range shown in Equation ( 20 ) based on the maximum RTD
voltage.
For the IDACs to remain operational, the AIN0 and AIN3 inputs of the ADS1247 must satisfy the IDAC
compliance voltage found in the ADS1247 datasheet (see Equation ( 21 )). The largest voltage will be
seen at AIN0 as it equals the sum of the common-mode voltage and the maximum RTD voltage shown in
Equation ( 22 ).
In this ratiometric configuration, VREF sets the input common-mode voltage at 1.64 V, satisfying the
requirements for both the input common-mode voltage and the IDAC compliance voltage of the ADS1247.
The differential filters chosen for this application were designed to have a -3 dB corner frequency at least
10 times larger than the bandwidth of the ADC. The selected ADS1247 sampling rate of 20 SPS results in
a -3dB bandwidth of 14.8 Hz. The -3dB filter corner frequency was set to be roughly 250 Hz at mid-scale
measurement resistance. For proper operation, the differential cutoff frequencies of the reference and
input low-pass filters must be well matched. This can be difficult because as the resistance of the RTD
changes over the span of the measurement, the filter cutoff frequency changes as well. To mitigate this
effect, the two resistors used in the input filter (RI1 and RI2) were chosen to be two orders of magnitude
larger than the RTD. Input bias currents of the ADC will cause a voltage drop across the filter resistors that
will show up as a differential offset error if the bias currents and/or filter resistors are not equal. Limiting the
resistors to at most 20 k will reduce dc offset errors due to input bias current.
The input filter differential capacitor (CI_DIFF) can be calculated as shown in Equation ( 24 ).
10 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
1
f 3dB _ DIFF
2 CI _ DIFF (RI1 RRTD RI2 )
( 24 )
CI _ DIFF 33 nF
To ensure that mismatch of the common-mode filtering capacitors is not translated to a differential voltage,
the common-mode capacitors (CI_CM1 and CI_CM2) were chosen to be ten times smaller than the differential
capacitor, making them 3.3 nF each. This results in a common-mode cutoff frequency that is roughly
twenty times larger than the differential filter, making the matching of the common-mode cutoff frequencies
less critical.
1
f 3dB _ CM
2 CI _ CM1 (RI1 RRTD RREF )
( 26 )
1
f 3dB _ CM
2 CIN _ CM2 (RI2 RREF )
( 27 )
The differential reference filter is designed to have a -3 dB corner frequency of 250 Hz to match the
differential input filter. The two reference filter resistors were selected to be 20 k, several times larger
than the value of RREF. The reference filter resistors should not be sized larger than 20 k or dc bias errors
will become significant.
RR1 RR2 20 k ( 28 )
The differential capacitor for the reference filter can be calculated as shown in Equation ( 29 ).
1
f 3dB _ DIFF
2 CR _ DIFF (RR1 RREF RR2 )
( 29 )
CR _ DIFF 15 nF
To ensure that mismatch of the common-mode filtering capacitors is not translated to a differential voltage,
the reference common-mode capacitors (CR_CM1 and CR_CM2) were chosen to be ten times smaller than the
reference differential capacitor, making them 1.5 nF each. Again, the resulting cutoff frequency for the
common-mode filters is roughly twenty times larger than the differential filter, making the matching of the
cutoff frequencies less critical.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 11
Copyright 2013, Texas Instruments Incorporated
www.ti.com
1
f 3dB _ CM
2 CR _ CM1 (RR1 RREF )
( 31 )
1
f 3dB _ CM
2 CR _ CM2 RR2
( 32 )
The TPS7A4901 comes from a series of high-voltage, ultra-low noise LDOs that are ideal for precision
applications. A resistor divider at the LDO output sets the output voltage (V LDO_OUT) proportional to the
LDOs internal reference voltage (VLDO_REF). For this device, VLDO_REF = 1.188 V. In order to set VLDO_OUT to
the desired output voltage of 3.3 V, the resistor divider components are selected using Equation ( 33 ).
R1
VLDO _ OUT VLDO _ REF 1
R2
( 33 )
R1 140 k
R2 78.7 k
VDUT VOUT
IN OUT
10F 0.1F 0.01F 140k
EN TPS7A4901 FB
0.1F 10F
78.7k
NR/SS GND
0.01F
12 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
4.1 Simulation
Figure 9 shows the TINA-TI circuit used to simulate the behavior of the RTD, input filtering, and PGA in
this system. The RTD has been modeled with a Pt100 macromodel that converts an input voltage
representative of the RTD temperature into the correct output resistance using the CVD equations. The
simplified ADS1247 PGA does not accurately represent the internal circuitry to the ADC; however, it does
represent the ideal behavior of the internal PGA.
IOP4
R8 4k
CI_CM1 3.3n -
Pt100 RTD RI1 9.09k AINP
U1 RTD3 +
R7 1k
VT+ RTD+ +
+ +
TEMP 100 V 2_V_RTD
CIN_DIFF 33n VIN_PGA VIN_ADC+
VT- RTD-
-
Mon+ Mon- AINN -
RI2 9.09k IOP1
+
Temp (C)
+ R9 1k
(Volts = degrees C) V -
CI_CM2 3.3n IOP3
1_R_RTD R10 4k
RTD Resistance
IDAC2 VREF_INT +
(Volts = Ohms) 3_VIN_ADC
-
IDAC2 1m
4_VREF
VREF
- IOP2
RR1 20k CR_CM1 1.5n
VREFP VIN_ADC-
+
+
RREF 820 CR_DIFF 15n VREF_ADC
VREFN -
RR2 20k +
CR_CM2 1.5n
- IOP5
TM
Figure 9. TINA-TI Simulation Circuit for the RTD and ADS1247 Inputs
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 13
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Figure 10 displays the RTD resistance, RTD voltage, ADC input voltage, and the V REF voltage as the RTD
temperature is swept from -200C to 850C. The results are displayed on the image for the minimum, mid-
scale, and maximum temperatures. The RTD voltage spans from 18.51 mV to 390.48 mV and with the
PGA set to 4 V/V, the differential ADC input is from 74.03 mV to 1.56 V. The VREF voltage is also displayed
and is the expected value of 1.64 V.
T 400
RTD ( )
0
-200 -50 100 250 400 550 700 850
o
Temperature ( C)
14 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The frequency response of the input and reference filters was tested using an ac current generator in
place of the IDAC1 source and is shown in Figure 11. The -3 dB cutoff frequency of the filters is roughly 20
Hz different when the RTD is at the maximum value near 390 . The dc magnitude of the results is based
on the current-to-voltage transfer function (I*R) as the excitation currents pass through the passive
resistors in the signal chain.
T
60.00
VIN_PGA
VREF_ADC
-3dB = 246.11 Hz
40.00 -3dB = 246.24 Hz
Gain (dB)
20.00
0.00
-20.00
1.00 10.00 100.00 1.00k 10.00k 100.00k 1.00M
Frequency (Hz)
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 15
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The smallest signal an n-bit data converter can theoretically resolve is given by its LSB size (least-
significant bit). An increase in input voltage by one LSB will increment the ADC output by one code.
Equation ( 34 ) calculates the weight of one LSB referred to the input of the PGA using VREF, Gain, and the
number of codes.
2 VREF 2 1.64 V
LSB ( V ) 48.88 nV
Gain 2 n
4
V
224
( 34 )
To calculate the theoretical achievable code step size in terms of resistance, divide the LSB size by the
excitation current used to excite the RTD, as shown in Equation ( 35 ).
LSB( V ) 48.88 nV
LSB() 48.88 ( 35 )
IIDAC 1 mA
Since the input-referred peak-to-peak noise of the ADS1247 at 20 SPS and Gain = 4 V/V is greater than
one LSB, a more appropriate resolution calculation replaces the converter LSB weight with the input-
referred noise specification. The ADC datasheet will typically provide the input-referred noise (in VPP or
VRMS) for different supply voltages, reference voltages, data rates, and gain settings.
The ADS1247 input-referred noise specification for the closest configuration to this system is 5.94 VPP
(see Table 5 in the ADS1247 datasheet). Equation ( 36 ) calculates the ADC resistance measurement
resolution based on the input-referred peak-to-peak noise (NoiseRTI_pp). The NoiseRTI_pp value is divided by
factor of two to show the resolution as a deviation from the mean value.
The expected temperature resolution in degrees Celsius can be calculated by dividing the expected
resistance resolution by the RTD sensitivity () as shown in Equation ( 37 ). Appendix A.4 explains how
the value of changes over the RTD measurement temperature, ranging from 0.4323 /C at -200C to
0.2927 /C at 850C. Therefore, the temperature resolution will vary over the RTD temperature range,
even though the resistance measurement resolution will remain constant.
Equation ( 37 ) calculates the ADC resolution in degrees Celsius using the Pt100 sensitivity at 0C.
ADCRES () 2.97 m
ADCRES @ 0C (C) 0.0076C
@ 0C ( 37 )
0.39083
C
The expected accuracy of the design can be calculated using the specifications of the components
selected in Section 3. The units associated with these specifications range from volts, to percent full-scale
range (%FSR), to parts-per-million of full-scale (ppm). In order to calculate the total error, these different
errors sources must be converted to a common unit of measurement. In the following calculations, all
specifications will be converted to volts referred to the input (RTI) of the ADS1247.
16 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Gain errors will be referenced to the maximum differential input voltage, VIN_MAX = 390.48 mV (calculated in
Equation ( 16 ) in Section 3.1.3), to properly calculate the input-referred voltage errors.
The tolerance of RREF will produce gain errors in the ADC transfer function as derived in Appendix A.6.
Assuming the tolerance is specified as a percentage, the transfer function gain error from the R REF
tolerance can be calculated from Equations ( 38 ) ( 39 ).
The error in volts due to the RREF tolerance can be calculated from the gain error and the maximum input
voltage.
0.019996
Gain ErrorR REF Tol( V ) 390.48mV 78.0804 V
100
The ADS1247 will cause errors due to the offset voltage, offset voltage drift, gain error, gain error drift,
integral nonlinearity (INL), and IDAC matching.
Offset voltage error and offset voltage error drift are commonly specified in an input-referred voltage and
can be directly entered from the device performance datasheet, if provided.
Offset ErrorADC( V ) 15 V ( 41 )
Gain errors are usually specified as a percentage of the full-scale ADC input range (%FSR), so the input-
referred voltage error can be calculated by multiplying by VIN_MAX. Equation ( 42 ) uses the typical gain
error of the ADS1247, but similar errors can be calculated using the maximum specifications as well.
The INL is typically specified in either number of ADC codes or in ppm FSR. Because INL is not a gain
error, it must be multiplied by the full-scale input voltage of the ADC rather than VIN_MAX, as shown in
Equation ( 43 ).
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 17
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The final errors considered for this system are caused by the mismatching of the IDAC current sources
which introduce a gain error in the transfer function as derived in Appendix A.7.
The errors from the mismatch of the IDAC sources are the largest errors in the system. This reinforces the
importance of chopping the two IDAC current sources to remove these errors as described in Section
3.1.2.
With all of the input-referred errors calculated in volts, the total error can be calculated by taking the root-
sum-of-square of all of the uncorrelated error terms. A similar calculation can be performed for the
maximum error by replacing the typical specifications with the maximum specifications. For cases where a
typical specification is not available, the maximum specification is used.
2 2 2
Gain ErrorR REF Tol Offset ErrorADC Gain ErrorADC
ErrorTotal( V )
2 2
INL ErrorADC Gain ErrorIDAC ( 46 )
ErrorTotal( V ) 303.903 V
The system errors and their resulting input-referred error in V are summarized in Table 4.
After removing the IDAC mismatch errors with chopping, a two-point gain and offset calibration can
remove the errors from the RREF tolerance, offset voltage, and gain error, leaving only the error from INL.
Table 5 compares the original unadjusted error with the errors after IDAC chopping and a two-point
calibration.
18 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The magnitude of the IDAC source can be used to convert the calculated voltage error into a calculated
resistance error as shown in Equation ( 47 ). The results from Table 5 have been converted to resistance
accuracy in Table 6.
Error (V )
Error () ( 47 )
IIDAC (A )
The temperature accuracy can be calculated by dividing the resistance accuracy by the RTD sensitivity ()
at the desired calibration temperature. The RTD sensitivity is worst at 850C (see Appendix A.4). The
results in Table 7 display the Total Error in degrees Celsius at 0C.
Error ()
Error (C) ( 48 )
@ 0C
Table 8 compares the calculated performance with the design goals from Table 1. It is necessary to chop
the IDAC sources to meet the desired un-calibrated precision resistance measurement accuracy.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 19
Copyright 2013, Texas Instruments Incorporated
www.ti.com
5 PCB Design
Providing proper power supply decoupling, grounding, and minimizing cross-over between the analog and
digital circuitry return currents is required to achieve optimal performance in all mixed-signal PCB designs.
In addition to standard practices, minimizing or balancing PCB trace resistance is a primary concern
because the design is based on accurately measuring the resistance of the RTD. Implementing a 4-wire
Kelvin connection at the RTD and RREF resistors help to minimize PCB resistance in series with the sense
elements by separating the measurement sense and excitation current paths.
As discussed in Section 2.2.2, the lead resistances of the 3-wire RTD are effectively cancelled when they
are equal and the magnitude of the excitation current sources are also equal. The same theory applies to
PCB trace resistance in series with the three RTD leads. Therefore, the PCB trace resistances connecting
the IDAC and ADS1247 inputs to the RTD must be balanced, otherwise additional differential signals will
be formed. The resistance of the trace between the terminal block and the R REF resistor is common to both
the positive and negative inputs and is cancelled by taking a differential measurement. Balancing the RTD
trace resistance is accomplished by creating traces of equal length between the terminal block and the
ADS1247connection points. Figure 12 displays these critical PCB layout areas. The full PCB layout is
shown in Figure 13.
RREF Kelvin
Connection
RR1
CR_CM1
CR_DIFF
RREF
CR_CM2
RTD Terminal Block
RR2
RI1
CI_CM1
CI_DIFF
CI_CM2
RI2
RTD Kelvin
Connection
20 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 21
Copyright 2013, Texas Instruments Incorporated
www.ti.com
0.12
Resistance Measurement Error ()
0.1
0.08
0.06
Results
0.04
Linear (Results)
y = 0.0002719x - 0.0064178
0.02
-0.02
0 50 100 150 200 250 300 350 400
RRTD ()
Figure 14. Resistance Measurement Results with Precision Resistors Before Calibration
22 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Precision temperature measurement applications are typically calibrated to remove the effects of gain and
offset errors, which generally dominate the total system error. The simplest calibration method is a linear,
or two-point, calibration which applies an equal and opposite gain and offset term to cancel the measured
system gain and offset errors. Applying a gain and offset calibration yields the calibrated results shown in
Figure 15. More information regarding calibration can be found in Reference 5.
0.01
Resistance Measurement Error ()
0.005
Calibrated Results
-0.005
-0.01
0 50 100 150 200 250 300 350 400
RRTD ()
Figure 15. Resistance Measurement Results with Precision Resistors after Calibration
The results in Figure 15 can be converted to temperature accuracy by dividing the results by the RTD
sensitivity () at the measured resistance. Over the full resistance input range, the maximum total
measured error is 0.00415 . Equation ( 49 ) uses this measurement and the RTD sensitivity at 0C to
calculate the measured temperature accuracy.
Error () 0.00415
Error (C) 0.0106C
@ 0C ( 49 )
0.39083
C
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 23
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Figure 16 displays the calculated temperature accuracy of the circuit, not including any linearization related
errors of the RTD.
0.05
0.0375
0.025
Temperature Error (C)
0.0125
Calibrated Results
-0.0125
-0.025
-0.0375
-0.05
0 50 100 150 200 250 300 350 400
RRTD ()
24 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Histogram
70
60
50
Frequency
40
30
ADC Readings
20
10
0
220043.349
220043.944
220044.538
220045.133
220045.727
220046.322
220046.916
220047.511
220048.105
220048.700
220049.294
220043.646
220044.241
220044.835
220045.430
220046.024
220046.619
220047.214
220047.808
220048.403
220048.997
Enter the measured input-referred noise into Equation ( 50 ) to determine the measured resolution in
Ohms.
The expected temperature resolution in degrees Celsius can be calculated by dividing the expected
resistance resolution by the RTD sensitivity () at 0C as shown in Equation ( 51 ).
ADCRES () 1.725 m
ADCRES @ 0C (C) 0.0044C
@ 0C ( 51 )
0.39083
C
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 25
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The temperature resolution falls well within the accuracy goal of 0.05C and can be observed in the
results in Figure 16. The noise can be further reduced by applying additional averaging or filtering in
software.
Table 9 compares the measured performance with the calculated performance and design goals from
Table 8. It is necessary to chop the IDAC sources to meet the desired un-calibrated precision resistance
measurement accuracy.
7 Modifications
This design can be easily modified for other RTD types and temperature ranges by changing the IDAC,
PGA, and RREF selections using the equations shown in the theory and component selection sections.
There are a few other fully integrated products available from TI that offer the same required building
blocks as the ADS1247 but feature different performance, channel count, and cost. Several of these
devices are listed in Table 10.
(1) AVDD = 3.3 V, AVSS = 0 V, Internal Reference = 2.048 V, Data Rate = 20 SPS, PGA = 4 V/V
(2) AVDD = 3 V, AVSS = 0 V, Internal Reference = 3 V, Data Rate = 13.42 SPS, PGA = 4 V/V
Table 11 features other suitable ADC solutions that offer integrated PGAs.
(1) AVDD = 3.3 V, AVSS = 0 V, Internal Reference = 2.048 V, Data Rate = 20 SPS, PGA = 4 V/V
(2) AVDD = 3 V, AVSS = 0 V, Internal Reference = 3 V, Data Rate = 13.42 SPS, PGA = 4 V/V
Discrete current sources could be comprised of an integrated device such as the REF200 or a circuit such
as the designs featured in TIPD101 or TIPD107.
26 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Collin Wells is an applications engineer in the Precision Linear group at Texas Instruments where he
supports industrial products and applications. Collin received his BSEE from the University of Texas,
Dallas.
3. Collin Wells, Signal Conditioning and Linearization of RTD Sensors 2011 Texas Instruments
Technology Day Presentation.
TM
4. Omega , The Omega Temperature Measurement Handbook and Encyclopedia, Vol
TM th
MMXIV , 7 Edition.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 27
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Appendix A.
28 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 29
Copyright 2013, Texas Instruments Incorporated
www.ti.com
01h VBIAS 00
02h MUX1 20
03h SYS0 22
04h OFC0 xx
05h OFC1 xx
06h OFC2 xx
07h FSC0 xx
08h FSC1 xx
09h FSC2 xx
0Ah IDAC0 96
0Bh IDAC1 03
0Ch GPIOCFG 00
0Dh GPIODIR 00
0Eh GPIODAT 00
30 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Class-A RTDs are a good choice for this application to provide good pre-calibration accuracy and long-
term stability. A Class-A RTD will have less than 0.5C of error at 100C without calibration and the long-
term stability makes accurate infrequent calibration possible. Table 13 displays the tolerance, initial
accuracy and resulting error at 100C for the five main classes of RTDs.
(1) AAA is not included in the DIN-IEC 60751 specification but is an industry accepted tolerance for performance demanding applications.
nd
For positive temperatures the CVD equations is a 2 -order polynomial Equation ( 52 ).
For negative temperatures from -200C to 0C, the CVD equation expands to a 4th-order polynomial
shown in Equation ( 53 ).
The coefficients in the Calendar Van-Dusen equations are defined by the IEC-60751 standard. R0 is the
resistance of the RTD at 0C. For a European standard Pt100 RTD the coefficients are:
R 0 100
A 3.9083 10- 3 C ( 54 )
B -5.775 10 -7
C
C -4.183 10 -12
C
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 31
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The change in resistance of a Pt100 RTD from -200C to 850C is displayed in Figure 20.
360
320
280
Resistance (Ohms)
240
160
120
80
40
0
200 95 10 115 220 325 430 535 640 745 850
Temp
Temperature (C)
While the change in RTD resistance is fairly linear over small temperature ranges, Figure 21 displays the
resulting non-linearity if an end-point fit is made to the curve shown in Figure 20. The results show almost
4.5% non-linearity, or greater than 16C, illustrating the need for digital calibration.
18 4.5
16 4
14 3.5
12 3
8 2
6 1.5
4 1
2 0.5
0 0
200 95 10 115 220 325 430 535 640 745 850
Temp
Temperature (C)
32 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
Figure 22 displays the change in the sensitivity () of the RTD over the full temperature measurement
range.
Plot Difference Between RTD Resistance and a Linear Endpoint Fit vs. Temperature
0.5
0.47
0.44
0.41
RTD Sensitivity (Ohms/C)
0.38
( Temp) 0.35
0.32
0.29
0.26
0.23
0.2
200 95 10 115 220 325 430 535 640 745 850
Temp
Temperature (C)
The sensitivity of the RTD at a few selected temperatures over the full operating range is listed in Table
14.
-100 0.40531
0 0.39083
100 0.37928
200 0.36773
400 0.34463
600 0.32153
850 0.29266
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 33
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The RREF drift specification must be multiplied by the temperature change and converted to a percentage
before performing the same calculations used for the RREF tolerance.
ppm ppm
RREF Drift 2 ( 56 )
C C
ppm ppm
RREF Drift (ppm) RREF Drift TMAX 2 65C 130 ppm ( 57 )
C C
The error in volts due to the RREF drift can be calculated by multiplying the gain error in percent by VIN_MAX.
As the ambient temperature changes, the ADS1247 will produce errors due to offset drift, gain error drift,
and IDAC mismatch drift.
Offset error drift is commonly specified as an input-referred voltage and can be directly entered from the
device performance datasheet. The largest offset drift error will be at a system ambient temperature of
-40C (See Figure 15 in the ADS1247 datasheet).
34 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
If offset drift is specified in V/C then it will first be multiplied by TMAX to determine the final offset voltage
due to temperature drift.
Like gain error, gain error drift in the ADS1247 datasheet is specified as %FSR. The largest gain drift error
will be at a system ambient temperature of -40C (See Figure 23 in the ADS1247 datasheet).
If gain error drift is specified in ppm/C, then it must first be converted into Gain ErrorADC Drift (%) similar to
the conversion performed in Equations ( 56 ) ( 58 ).
The IDAC mismatch drift is commonly specified in ppm/C. First, calculate the IDAC mismatch in %FSR
based on the drift specification and TMAX.
10
IIDAC Mismatch Drift (%) 65C 100 0.065%
1,000,000C
The gain error caused by the IDAC mismatch drift can be calculated in %FSR using the same calculations
shown in Appendix A.7 and then converted to volts.
The error from the IDAC mismatch drift can be removed if the IDAC sources are chopped as described in
Section 3.1.2.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 35
Copyright 2013, Texas Instruments Incorporated
www.ti.com
With all of the input-referred errors calculated in volts, the total error can be calculated by taking the root-
sum-of-square of all of the uncorrelated ambient temperature and temperature drift error terms.
2 2 2
Gain ErrorR REF Tol Gain ErrorR REF Tol Drift Offset ErrorADC
2 2 2
ErrorTotal( V ) Offset ErrorADC Drift Gain ErrorADC Gain ErrorADC Drift
2 2 2 ( 66 )
INL ErrorADC Gain ErrorIDAC Gain ErrorIDAC Mismatch Drift
ErrorTotal( V ) 303.9 V
The system errors over temperature and their resulting input-referred errors in V are summarized in
Table 15.
Table 15. Summary of Error Sources and Resulting Voltage Error RTI over Temperature
Value Input-Referred Error (V)
Error Source
Typ Max Typ Max
RREF Errors
RREF Tolerance - 0.02% - 164
RREF Drift - 2 ppm/C - 106.6
ADS1247 Errors
Integrated Nonlinearity (INL) 6 ppm 15 ppm 4.92 12.3
Offset Voltage - 15 V - 15
Offset Voltage Drift 1 V 1
Gain Error 0.005% 0.02% 19.52 78.1
Gain Error Drift 0.01% 0.015% 39.05 58.57
IDAC Mismatch - 0.15% - 292.6
IDAC Mismatch Drift - 10 ppm/C - 126.9
The IDAC mismatch errors can be removed by chopping the IDAC sources as described in Section 3.1.2.
A two-point gain and offset calibration can remove the errors from the R REF tolerance, offset voltage, gain
error, and IDAC mismatch leaving only the error from INL and temperature drift errors. Table 16 compares
the unadjusted error with the error after chopping the IDAC sources and performing a two-point gain and
offset calibration at 25C and over temperature.
36 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
www.ti.com
The magnitude of the IDAC source can be used to convert the calculated voltage error into a calculated
resistance error in Ohms as shown in Equation ( 47 ). The results from Table 16 have been converted to
resistance accuracy in Table 17.
With the resistance accuracy known, the final temperature accuracy can be calculated by dividing the
resistance accuracy by the change in the RTD resistance per degree Celsius. The results in Table 18 use
the sensitivity at 0C of 0.3908/C.
RRTD
CodeIDEAL CodesTOTAL ( 67 )
4 RREF
If RREF is substituted with (RREF+RREF*) in the ideal transfer function, then it simplifies to Equation ( 68 ).
RRTD
CodeRREF Error CodesTOTAL
4 RREF RREF
( 68 )
Equation ( 69 ) calculates the gain error caused by the RREF tolerance by comparing the calculated error
transfer function to the ideal transfer function.
SLAU520A-December 2013-Revised November 2014 3-Wire RTD Measurement System Reference Design, -200C to 850C 37
Copyright 2013, Texas Instruments Incorporated
www.ti.com
If RREF is substituted with RREF-RREF* to calculate the effects of a decrease in RREF, the polarity of the gain
error will be positive.
Assuming the tolerance is specified in %, the gain error can be calculated as shown:
RREF Tol(%)
Gain ErrorRREF Tol(%) ( 70 )
RREF Tol(%) 100
RRTD
CodeIDEAL CodesTOTAL ( 71 )
4 RREF
However, if I2 is set equal to (I1+ I1*) in Equation ( 7 ), the transfer function simplifies to Equation ( 72 ).
RRTD
CodeIDAC Mismatch Error CodesTOTAL ( 72 )
4 RREF 2
Equation ( 73 ) calculates the gain error caused by the IDAC mismatch by comparing the calculated error
transfer function to the ideal transfer function.
If I1 is substituted with I2+ I2*, the polarity of the gain error will be positive.
Assuming the IDAC mismatch is specified in %FSR, the gain error can be calculated as shown in Equation
( 74 ).
38 3-Wire RTD Measurement System Reference Design, -200C to 850C SLAU520A-December 2013-Revised November 2014
Copyright 2013, Texas Instruments Incorporated
IMPORTANT NOTICE FOR TI REFERENCE DESIGNS
Texas Instruments Incorporated ("TI") reference designs are solely intended to assist designers (Buyers) who are developing systems that
incorporate TI semiconductor products (also referred to herein as components). Buyer understands and agrees that Buyer remains
responsible for using its independent analysis, evaluation and judgment in designing Buyers systems and products.
TI reference designs have been created using standard laboratory conditions and engineering practices. TI has not conducted any
testing other than that specifically described in the published documentation for a particular reference design. TI may make
corrections, enhancements, improvements and other changes to its reference designs.
Buyers are authorized to use TI reference designs with the TI component(s) identified in each particular reference design and to modify the
reference design in the development of their end products. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL
OR OTHERWISE TO ANY OTHER TI INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY
OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN, including but not limited to any patent right, copyright, mask work right,
or other intellectual property right relating to any combination, machine, or process in which TI components or services are used.
Information published by TI regarding third-party products or services does not constitute a license to use such products or services, or a
warranty or endorsement thereof. Use of such information may require a license from a third party under the patents or other intellectual
property of the third party, or a license from TI under the patents or other intellectual property of TI.
TI REFERENCE DESIGNS ARE PROVIDED "AS IS". TI MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE
REFERENCE DESIGNS OR USE OF THE REFERENCE DESIGNS, EXPRESS, IMPLIED OR STATUTORY, INCLUDING ACCURACY OR
COMPLETENESS. TI DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS
FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY
INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO TI REFERENCE DESIGNS OR USE THEREOF. TI SHALL NOT BE LIABLE
FOR AND SHALL NOT DEFEND OR INDEMNIFY BUYERS AGAINST ANY THIRD PARTY INFRINGEMENT CLAIM THAT RELATES TO
OR IS BASED ON A COMBINATION OF COMPONENTS PROVIDED IN A TI REFERENCE DESIGN. IN NO EVENT SHALL TI BE
LIABLE FOR ANY ACTUAL, SPECIAL, INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES, HOWEVER CAUSED, ON ANY
THEORY OF LIABILITY AND WHETHER OR NOT TI HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES, ARISING IN
ANY WAY OUT OF TI REFERENCE DESIGNS OR BUYERS USE OF TI REFERENCE DESIGNS.
TI reserves the right to make corrections, enhancements, improvements and other changes to its semiconductor products and services per
JESD46, latest issue, and to discontinue any product or service per JESD48, latest issue. Buyers should obtain the latest relevant
information before placing orders and should verify that such information is current and complete. All semiconductor products are sold
subject to TIs terms and conditions of sale supplied at the time of order acknowledgment.
TI warrants performance of its components to the specifications applicable at the time of sale, in accordance with the warranty in TIs terms
and conditions of sale of semiconductor products. Testing and other quality control techniques for TI components are used to the extent TI
deems necessary to support this warranty. Except where mandated by applicable law, testing of all parameters of each component is not
necessarily performed.
TI assumes no liability for applications assistance or the design of Buyers products. Buyers are responsible for their products and
applications using TI components. To minimize the risks associated with Buyers products and applications, Buyers should provide
adequate design and operating safeguards.
Reproduction of significant portions of TI information in TI data books, data sheets or reference designs is permissible only if reproduction is
without alteration and is accompanied by all associated warranties, conditions, limitations, and notices. TI is not responsible or liable for
such altered documentation. Information of third parties may be subject to additional restrictions.
Buyer acknowledges and agrees that it is solely responsible for compliance with all legal, regulatory and safety-related requirements
concerning its products, and any use of TI components in its applications, notwithstanding any applications-related information or support
that may be provided by TI. Buyer represents and agrees that it has all the necessary expertise to create and implement safeguards that
anticipate dangerous failures, monitor failures and their consequences, lessen the likelihood of dangerous failures and take appropriate
remedial actions. Buyer will fully indemnify TI and its representatives against any damages arising out of the use of any TI components in
Buyers safety-critical applications.
In some cases, TI components may be promoted specifically to facilitate safety-related applications. With such components, TIs goal is to
help enable customers to design and create their own end-product solutions that meet applicable functional safety standards and
requirements. Nonetheless, such components are subject to these terms.
No TI components are authorized for use in FDA Class III (or similar life-critical medical equipment) unless authorized officers of the parties
have executed an agreement specifically governing such use.
Only those TI components that TI has specifically designated as military grade or enhanced plastic are designed and intended for use in
military/aerospace applications or environments. Buyer acknowledges and agrees that any military or aerospace use of TI components that
have not been so designated is solely at Buyer's risk, and Buyer is solely responsible for compliance with all legal and regulatory
requirements in connection with such use.
TI has specifically designated certain components as meeting ISO/TS16949 requirements, mainly for automotive use. In any case of use of
non-designated products, TI will not be responsible for any failure to meet ISO/TS16949.
Mailing Address: Texas Instruments, Post Office Box 655303, Dallas, Texas 75265
Copyright 2014, Texas Instruments Incorporated