3-8512.090-1
C-6/98
CAUTION!
Remove power to unit before wiring input and output connections.
A. Ground referenced PLC with internal transmitter power supply B. Power connection for display use only
PLC Power
8512 Transmitter supply 8512 Transmitter
4-20 mA Input Fuse** Fuse**
Terminals Terminals
+ Power out 1/8A
+ 4-20 mA - 24* + 1/8A
+ 4-20 mA
VDC
24 VDC
- CH +
-
+
Loop
17-30V *
- Loop
+ 17-30V *
250*
- Gnd
- Gnd
CH - (gnd)
C. 1 to 5 VDC recorder (C1), 4 to 20 mA indicator (C2), or ground referenced PLC (C3) connections without internal transmitter power supply
+ 17-30V *
CH +
- Gnd
*Refer to maximum loop impedance specification for minimum operating voltage requirements (section 10).
**1/8A fuse recommended (customer supplied)
1.2 3-Wire operation (for +GF+ SIGNET 2000, 2507, 2530, 2535, 2540 flow sensors). This wiring is required for powered flow
sensors that consume more than 1.5 mA DC current.
A. Ground referenced PLC with internal transmitter power supply B. Differential input PLC with internal transmitter power supply
8512 Transmitter
PLC PLC Terminals
4-20 mA Input 8512 Transmitter 4-20 mA Input Fuse**
Fuse** + 4-20 mA
+ +
Terminals 1/4A
+ Power out 1/4A
+ 4-20 mA - 24 VDC - Loop
24 VDC - Loop
- + 17-30V *
- CH + + 17-30V * - Gnd
250*
- Gnd
250*
CH +
CH - (gnd) CH -
C. 1 to 5 VDC recorder (C1) and 4 to 20 mA indicator (C2) connections without internal transmitter D. Power connection for display use only
power supply
Recorder Power Indicator Power
1-5 VDC supply 4 -20 mA supply 8512 Transmitter Power 8512 Transmitter
CH - Fuse** CH - Fuse** supply Fuse**
Terminals Terminals
C1 (gnd)
- 24 + 1/4A C2 (gnd)
- 24
+ 1/4A
+ 4-20 mA - 24* + 1/4A
VDC* VDC*
VDC + 4-20 mA
250* CH + -
+
Loop
- Loop
17-30V * + 17-30V *
CH +
- Gnd
- Gnd
*Refer to maximum loop impedance specification for minimum operating voltage requirements (section 10).
**1/4 A fuse recommended (customer supplied).
4. Installation Options
4.1 Standard Panel Mount 4.3 Optional 3-8011 Integral Mounting Kit
Panel cutout template/instructions (included). NPT and DIN conduit port kits available.
Compatible with 3-8510-XX/3-8512-XX flow sensors (only).
Flow sensor and fitting purchased separately (see section 9).
8512 Flow Transmitter
Instrument
+GF+ SIGNET panel
Conduit ports
Blind holes
+GF+ SIGNET +GF+ SIGNET
for DIN conduit
connectors (8) PG13.5 metric 1/2 in. NPT
threaded conduit threaded conduit
ports (2) ports (2)
1 2 3
Choose: Change: Save:
E
A.
Flow rate
2s OPTIONS = OPTIONS =
Press &
hold for B.
access: 1. Press and 1. Press keys in
Resettable total hold 2s sequence
VIEW 2s
2. 2.
C.
2s 5s Press and
CALIBRATE Permanent total To exit without hold 2s
changes:
OPTIONS D. quick 3.
Loop output press
E.
Last cal.
A
7. CALIBRATE (example) 8. OPTIONS (example)
1 2 3 1 2 3
Choose: Change: Save: Choose: Change: Save:
H E
A. A.
Contrast Totalizer VIEW= VIEW=
B. Unit/timebase:
Flow h,m,s,d B. Display low= =700 ms
averging hi= =3 s
off= 100 ms
C.
Flow K-factor Press &
C. hold
Flow display Decimal
D. Units
postion
Totalizer - label only - 2s
Press &
hold D. 4 mA
E. Output adjust
Totalizer K-factor
2s
E. 20 mA
F. 4 mA
Output adjust
Output setpoint A
To return to Return to
VIEW: To restore original value: VIEW before
G. 20 mA removing
Output setpoint quick quick power
press press
H.
Last calibration
A
Technical notes:
Flow and totalizer K-factors are independent of each other. These K-factors
represent the number of pulses generated by the +GF+ SIGNET flow sensor for
each engineering unit measured (published in flow sensor manual).
Environmental
Operating temperature: -15 to 70 C (5 to 158 F) 8512 Flow Transmitter
Electrical Data
107 mm (4.2 in.)
Frequency range: 0.5 Hz to 500 Hz 36 mm (1.4 in.)
Loop/system power: (2-wire mode) 17 to 30 VDC @ 20 mA max.
(3-wire mode) 17 to 30 VDC @ 68 mA max. (front view) (side view)
Sensor power: (2-wire mode) 5 VDC @ 1.5 mA max.
(3-wire mode) 5 VDC @ 20 mA max.
11. Troubleshooting
+GF+ SIGNET
Sales Offices:
USA George Fischer, Inc., 2882 Dow Avenue, Tustin, CA 92780/USA, Tel. (714) 731-8800, Fax (714) 731-6201
Switzerland Georg Fischer Rohrleitungssysteme AG, P.O. Box 671, CH-8201 Schaffhausen/Switzerland, Tel. 052/631 1111, Fax 052/631 2830
Singapore George Fischer Pte. Ltd., 15 Kaki Bukit Road 2, KB Warehouse Complex, Singapore 1441, Tel. 65/747 0611, Fax 65/747 0577
Japan Kubota George Fischer, 2-47 Shikitsuhigashi, 1-Chome, Naniwa-Ku, Osaka, 556-91 Japan, Tel. 816/648 2545, Fax 816/648 2565
China Georg Fischer Ltd., Rm 1503, Business Residence Bldg. of Asia Plaza, 2-3 Bldg. No. 5th Qu Anzhenxili, Chaoyang Qu, Beijing 100029,
P.R. China, Tel. 86/10 6443 0577, Fax 86/10 6443 0578
Australia George Fischer Pty. Ltd., Suite 3, 41 Stamford Road, Oakleigh, Victoria 3166, Australia, Tel. 61/3 9568 0966, Fax 61/3 9568 0988
Signet Scientific Company, 3401 Aerojet Avenue, El Monte, CA 91731-2882 U.S.A., Tel. (626) 571-2770, Fax (626) 573-2057