071 - Data Sheet Ups
071 - Data Sheet Ups
:1
Edition : 1
DATA SHEET
FOR
UN-INTERRUPTED POWER SUPPLY (UPS)
SYSTEM
(ELECTRICAL SECTION)
MECON LIMITED
DELHI 110 092
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI
ANNEXURE - I
PURCHASER'S DATA FOR UPS
1.0 INPUT POWER SUPPLY
1.1 Voltage/freq./ phase 415 V (+) 10% & (-) 15% TPN, 50 Hz 5% or 230V
AC single phase (voltage range-160V AC to 270V
AC) As per SOR.
1.2 System fault level 10 kA for 1 Sec
2.0 SITE CONDITION
2.1 Design Maximum /Minimum 48C/2C
temperature
2.2 Max. Relative humidity 95%
2.3 Altitude 0.0 M MSL
3.0 OUT PUT REQUIREMENT
3.1 Voltage/ Phase 230V 1% AC, Single phase 2 wire
3.2 Output waveform & frequency Pure Sinusoidal Wave
50 Hz 0.1%
Voltage distortion (THD): Less than 3% for linear
loads & Less than 5% for non linear loads.
4.0 SYSTEM REQUIREMENTS
4.1 Rating (KVA at 0.8 pf.) As per SOR
4.2 The inverter circuit should be IGBT based, fully
Type of inverter microprocessor controlled with PWM Technology or
Latest proven technology
4.3 125% of the rated output for 10 minutes & 150% for
Overload capacity
1 minute.
4.4 Dual/Parallel Redundant with static bypass & Dual
Mode of operation Redundant rectifier as specified in SOR/Design
basis/Block diagram
4.5 >90% for normal load and not below 85% for 25%
Inverter efficiency
of load
4.6 Installation Floor Mounted
4.7 Type of enclosure Minimum IP-31
4.8 External Cable Connection From Bottom
4.9 Internal protection All live parts shrouded
4.10 Doubly Earthed (Two distinct terminals to be made
Earthing
available)
4.11 Cooling Forced ventilation with fans
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI
7.2 i) Battery end cell voltage As per specification (clause no. 3.5)
ii) Battery stand formation
iii) Battery back up time As per battery manufacturer
iv) De-rating factor
As per SOR
(i) Ageing -- 0.8
(ii) State of Charge -- 0.88
(iii) Temp. Correction -- As per min. site
temp. (Ref. 2.1
above)
The rectifier/charger output current & voltage shall be
limited to the battery suppliers recommendation.
8.0 Alarms, Indications and LCD Display
8.1 Single line Power Flow Diagram (Mimic diagram) with LED indications of UPS
status (i.e. Mains present, Battery charging & discharging, Low battery Voltage
and unit on bypass).
8.2 Digital panel Meter with LCD a) Input AC Voltage, current, frequency
display shall be provided for b) Output AC Voltage, current, frequency.
monitoring viz. c) Battery current and voltage
d) Total run time
e) Mains ON/OFF, Mains Over/Under voltage,
Phase fail
f) Inverter ON/OFF, Inverter Over/Under
voltage, inverter overload, over heat & load
in % on inverter.
g) Battery voltage low, battery level in % &
battery fault
h) Battery Operation Boost Charge, Float
Charge with of status - "in charge" or
"discharge"
i) Load on bypass or inverter.
9.3 Battery
Under voltage at battery terminal, Battery over
charge, Battery Over current
9.4 Rectifier & Battery charger Maximum current limiting
Over temp. Trip
Boost charging and float charging current limiting
with back up protection against over charging.
10.0 Distribution boxes
10.1 Distribution Board Details (As per tender drawings/SOR)
(1) ACDB 230 V, Single Phase (1 No.) :
Incomer : DP MCB
Outgoing : 8 Nos, 6A/10A (Combination) DP MCBs
(2) DCDB : 24 V DC (1 No.)
Incomer : DP MCB
Outgoing : 6 Nos, 10A/16A DP MCB
(3) DCDB 48 V DC (1 No.)
Incomer : DP MCB,
Outgoing ; 6 Nos, 10A/16ADP MCB
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI
ANNEXURE-II (A)
TECHNICAL DATA FROM MANUFACTURER
(To be filled up by the Tendered)
1.0 INVERTER
10.0 Metering
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI
ANNEXURE- II (B)
TECHNICAL DATA FROM MANUFACTURER
1.2.1 Rectifier
1.4 Power Factor of Rectifier (at all load) 0.6 to 0.7 (lag)
600 V on AC side
1.10 PTRV (Peak Transient reverse voltage)
200 V on DC side
ANNEXURE III
PREFERRED MAKES
1. EMERSON
2. DB POWER
3. APLAB
4. KELTRON
5. HI-REL
ANNEXURE - IV
1. QAP shall be submitted for each of the equipment separately with break up Code Description Code Description Code Description DOCUMENTS:
of assembly/sub-assembly & part/component or for group of equipment
having same specification. 1. Visual 12. Routine test as per relevant IS 23. Short time rating D1. Approved GA drawings
2. Use numerical codes as indicated for extent of inspection & tests and 2. Dimensional other standard 24. Operational & functional D2. Approved single line/
submission of test certificates & documents. Additional codes & description 3. Fitment & Alignment 13. Type test as per relevant IS/ check schematic diagram
for extent of inspection & tests may be added as applicable for the plant and 4. Physical Test (Sample) other standard 25. Over Speed Test D3. Approved
equipment 5. Chemical Test (Sample) 14. Impulse Test 26. Flame Proof Test data sheet
3. Separate identification number with quantity for equipment shall be 6. Ultrasonic Test 15. Partial Discharge Test 27. Clearance and creepage D4. Approved bill of materials
indicated wherever equipment having same specifications belonging to 7. Magnetic Particle Test (MPT) 16. Heat run risc test\tempr. Distance D5. Unpriced P.O. copy
different facilities are grouped together. 8. Radiography Test 17. Enclosure Protection Test 28. Acceptance Test D6. Calibration Certificate
4. Weight in tonnes (T) must be indicated under column 5 for each item. 9. Dye Penetration Test 18. Calibration of all measuring
Estimated weights may be indicated wherever actual weights are not 10. Measurement of IR Value 19. Noise & Vibration instruments and gauges
available. a) Before HV Test 20. Test certificates for bought out
ABBREVIATIONS USED : b) After HV Test components
11. High Voltage test/Dielectric 21. Tank Pressure Test
CONTR : CONTRACTOR test 22. Paint shade verification
MFR : MANUFACTURER
EQUIPMENT DETAILS INSPECTION AND TESTS Test Certificates Acceptance REMARKS /
Sl. Description (With equipment Indentificatuin Quantity Manufacturers Expected schedule of Raw Material and inprocess stage Final Inspection/Test by & documents to Criteria SAMPLING
No. heading, place of use, and No. Name and Address Final Inspection inspection be submitted to Standards /IS/ PLAN
Breif Specifications) No/M T MFR CONTR MECON MFR CONTR MECON MECON / BS/ASME/
ONGC Norms and
Documents
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1. UPS System Set 1,2,3,4, - - 1,2,3,12, 1,2,3,12, 1,2,3,12, D1, D2, D3, D4, Tech. ( * ) 12 hour
24, 27,28 16,22,23 16*, 22, 16*, 22, D5, D6, 20, 12,13 Specification, heat run test
24,27,28 23,24,27, 23,24,27, Approved
28 28 Drawings &
Data Sheets
2. Battery Set Set 1,2,3,4, - - 1,2,3,12, 1,2 - D1, D3, D4, D5, Tech. 12, 13
24,27 13,28 D6, 12,13 Specification, Document to be
reviewed by
Approved MECON
Drawings &
Data Sheets
Test certificates