Battery sizing Calculations JKC-GCC-MEP-SVN-180002-A6

BATTERY SIZING CALCULATION FOR E&M UPS-1

DATA
Sl. No. Description Data Unit Remarks

1 Rating of UPS 80 KVA

Voltage level as Per Section VIII OCS Sub


2 415+15%-20% Volts division 4 Clause 4.4.5.4 (7)

Power factor as Per Section VIII OCS Sub


3 0.8
division 4 Clause 4.4.5.4 (7)

4 Inverter efficiency 0.95

Back up time as Per Section VIII OCS Sub


5 120 Minutes
division 4 Clause 4.4.5.5.8

End cell voltage as Per Section VIII OCS Sub


6 1.75 Volt
division 4 Clause 4.4.5.5.8

7 Charging voltage 2.3 Volt

Operating temperature
8 35.9 deg. C

CALCULATIONS

Choice of no of cell-
A) Min no of cells Min. DC voltage/End cell voltage
1) Min. DC voltage(=415*0.8) 332 V
Min no of cells 189.71 V
Say 190

2) Max no of cells Max. DC voltage/Charging voltage


Max. DC voltage(=415*1.1) 477.25
Max no of cells 207.50
Say 208 Cells
Let Selected no of cell 208 Cells

B) Power required for UPS in KW KVA*P.F.


= 64 KW

C) Power required form battery KW/Inverter efficiency


= 67.37 KW

Total wattages
D) Power required form each cell
required from
= 323.89 Watt/Cell

E) Considering temperation correction factor for operating temperature of 25°C

1.00

Power required from each cell 323.89 Watt/Cell

F) Considering aging factor 0.8


Power required form each cell 404.9 Watt/Cell
= 490 Watt/Cell

G) Load Current IDC MAX = 185.0780798 Amps

H) K Factor for 120 mins. = 2.82

I) Calculated Battery Capacity I DC MAX x K factor = 521.9201851 AH

I) Selected Battery Capacity = 550 AH

MMRC / UGC-05 1
Battery sizing Calculations JKC-GCC-MEP-SVN-180002-A6

BATTERY SIZING CALCULATION FOR E&M UPS-2

DATA
Sl. No. Description Data Unit Remarks

1 Rating of UPS 120 KVA

Voltage level as Per Section VIII OCS Sub


2 415+15%-20% Volts division 4 Clause 4.4.5.4 (7)

Power factor as Per Section VIII OCS Sub


3 0.8
division 4 Clause 4.4.5.4 (7)

4 Inverter efficiency 0.95

Back up time as Per Section VIII OCS Sub


5 120 Minutes
division 4 Clause 4.4.5.5.8

End cell voltage as Per Section VIII OCS Sub


6 1.75 Volt
division 4 Clause 4.4.5.5.8

7 Charging voltage 2.3 Volt

Operating temperature
8 35.9 deg. C

CALCULATIONS

Choice of no of cell-
A) Min no of cells Min. DC voltage/End cell voltage
1) Min. DC voltage(=415*0.8) 332 V
Min no of cells 189.71 V
Say 190

2) Max no of cells Max. DC voltage/Charging voltage


Max. DC voltage(=415*1.1) 477.25
Max no of cells 207.50
Say 208 Cells
Let Selected no of cell 208 Cells

B) Power required for UPS in KW KVA*P.F.


= 96 KW

C) Power required form battery KW/Inverter efficiency


= 101.05 KW

Total wattages
D) Power required form each cell
required from
= 485.83 Watt/Cell

Considering temperation correction factor for operating temperature of 25°C


E)
1.00

Power required from each cell 485.83 Watt/Cell

F) Considering aging factor 0.8


Power required form each cell 607.3 Watt/Cell
= 490 Watt/Cell

G) Load Current IDC MAX = 277.6171197 Amps

H) K Factor for 120 mins. = 2.82

I) Calculated Battery Capacity I DC MAX x K factor = 782.8802776 AH

I) Selected Battery Capacity = 850 AH