Data Sl. No. Description Data Unit Remarks: Battery Sizing Calculation For E&M Ups-1

This document provides battery sizing calculations for two uninterruptible power supply (UPS) systems. For the 80KVA UPS, the calculations determine that 208 battery cells are needed, each providing 490 watts, for a total battery capacity of 550 amp-hours. For the 120KVA UPS, the same process is followed determining again that 208 cells at 490 watts each are required, resulting in a total battery capacity to support the UPS for 120 minutes of backup time.

Uploaded by

Manglesh Singh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views

Data Sl. No. Description Data Unit Remarks: Battery Sizing Calculation For E&M Ups-1

This document provides battery sizing calculations for two uninterruptible power supply (UPS) systems. For the 80KVA UPS, the calculations determine that 208 battery cells are needed, each providing 490 watts, for a total battery capacity of 550 amp-hours. For the 120KVA UPS, the same process is followed determining again that 208 cells at 490 watts each are required, resulting in a total battery capacity to support the UPS for 120 minutes of backup time.

Uploaded by

Manglesh Singh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Battery sizing Calculations JKC-GCC-MEP-SVN-180002-A6

BATTERY SIZING CALCULATION FOR E&M UPS-1

DATA
Sl. No. Description Data Unit Remarks

1 Rating of UPS 80 KVA

Voltage level as Per Section VIII OCS Sub


2 415+15%-20% Volts division 4 Clause 4.4.5.4 (7)

Power factor as Per Section VIII OCS Sub


3 0.8
division 4 Clause 4.4.5.4 (7)

4 Inverter efficiency 0.95

Back up time as Per Section VIII OCS Sub


5 120 Minutes
division 4 Clause 4.4.5.5.8

End cell voltage as Per Section VIII OCS Sub


6 1.75 Volt
division 4 Clause 4.4.5.5.8

7 Charging voltage 2.3 Volt

Operating temperature
8 35.9 deg. C

CALCULATIONS

Choice of no of cell-
A) Min no of cells Min. DC voltage/End cell voltage
1) Min. DC voltage(=415*0.8) 332 V
Min no of cells 189.71 V
Say 190

2) Max no of cells Max. DC voltage/Charging voltage


Max. DC voltage(=415*1.1) 477.25
Max no of cells 207.50
Say 208 Cells
Let Selected no of cell 208 Cells

B) Power required for UPS in KW KVA*P.F.


= 64 KW

C) Power required form battery KW/Inverter efficiency


= 67.37 KW

Total wattages
D) Power required form each cell
required from
= 323.89 Watt/Cell

E) Considering temperation correction factor for operating temperature of 25°C

1.00

Power required from each cell 323.89 Watt/Cell

F) Considering aging factor 0.8


Power required form each cell 404.9 Watt/Cell
= 490 Watt/Cell

G) Load Current IDC MAX = 185.0780798 Amps

H) K Factor for 120 mins. = 2.82

I) Calculated Battery Capacity I DC MAX x K factor = 521.9201851 AH

I) Selected Battery Capacity = 550 AH

MMRC / UGC-05 1
Battery sizing Calculations JKC-GCC-MEP-SVN-180002-A6

BATTERY SIZING CALCULATION FOR E&M UPS-2

DATA
Sl. No. Description Data Unit Remarks

1 Rating of UPS 120 KVA

Voltage level as Per Section VIII OCS Sub


2 415+15%-20% Volts division 4 Clause 4.4.5.4 (7)

Power factor as Per Section VIII OCS Sub


3 0.8
division 4 Clause 4.4.5.4 (7)

4 Inverter efficiency 0.95

Back up time as Per Section VIII OCS Sub


5 120 Minutes
division 4 Clause 4.4.5.5.8

End cell voltage as Per Section VIII OCS Sub


6 1.75 Volt
division 4 Clause 4.4.5.5.8

7 Charging voltage 2.3 Volt

Operating temperature
8 35.9 deg. C

CALCULATIONS

Choice of no of cell-
A) Min no of cells Min. DC voltage/End cell voltage
1) Min. DC voltage(=415*0.8) 332 V
Min no of cells 189.71 V
Say 190

2) Max no of cells Max. DC voltage/Charging voltage


Max. DC voltage(=415*1.1) 477.25
Max no of cells 207.50
Say 208 Cells
Let Selected no of cell 208 Cells

B) Power required for UPS in KW KVA*P.F.


= 96 KW

C) Power required form battery KW/Inverter efficiency


= 101.05 KW

Total wattages
D) Power required form each cell
required from
= 485.83 Watt/Cell

Considering temperation correction factor for operating temperature of 25°C


E)
1.00

Power required from each cell 485.83 Watt/Cell

F) Considering aging factor 0.8


Power required form each cell 607.3 Watt/Cell
= 490 Watt/Cell

G) Load Current IDC MAX = 277.6171197 Amps

H) K Factor for 120 mins. = 2.82

I) Calculated Battery Capacity I DC MAX x K factor = 782.8802776 AH

I) Selected Battery Capacity = 850 AH

MMRC / UGC-05 2