30RB 23PD
30RB 23PD
30RB 23PD
2
a window into the units operation, Seismic certification considered to determine if corrosion
providing easy-to-read information A seismic kit is available which will re- protection is required.
about chiller performance and over sult in a unit SDS (seismic design accel- Microchannel coils are sturdier than
15 diagnostic functions. Carriers 30 eration parameter) level of 2.0. other coil types; thus, easier to clean
Series chillers ComfortLink controls without causing damage to the coil.
provide features such as chilled water Novation heat exchanger
technology Due to the compact all-aluminum
temperature reset, demand limiting,
design, microchannel coils will reduce
compressor wear minimization and The Novation heat exchanger design overall unit operating weight by 6 to
protection, temperature and pressure with microchannel (MCHX) condenser
7%. The streamlined MCHX coil de-
displays and diagnostic functions. coil is a robust, cost effective alterna- sign reduces refrigerant charge by up
These controls result in higher chiller tive to traditional coil design. These to 30%.
reliability, simplified training and more coils are offered coated or uncoated to
productive service calls with corre- match coil protection to site condi- The coil is designed with rubber iso-
spondingly lower operational and tions. The e-coated version of this coil lation around the powder painted coil
maintenance costs. can withstand an 8000-hour salt spray frame to eliminate galvanic couples,
test in accordance with ASTM B-117 which can cause corrosion due to dis-
Carriers exclusive handheld
Standard. The Carrier Electronic Cata- similar metals.
Navigator display provides conve-
nience and powerful information in the log (E-Cat) can be used to determine Optional integrated heat
palm of your hand. The Navigator whether or not corrosion protection is reclaim package
display helps technicians to quickly recommended for particular applica-
tions in coastal/marine environments. For applications with a simultaneous
diagnose problems and even prevent requirement for chilled water and tem-
them from occurring. Following the input of the requested
data, the E-Cat program output will ad- pered heat water, the heat reclaim
All AquaSnap units are ready to be option is an ideal solution. The produc-
vise the appropriate coil to be used.
used with the Carrier Comfort Net- tion of useful hot water in conjunction
work (CCN) system. Other factors described in "Selection with useful chilled water can lead to
Guide: Environmental Corrosion total COP (coefficient of performance)
A BACnet* communication option is
Protection," catalog number values greater than 6.0.
also available for the i-Vu Open con-
04-581061-01, must also be
trol system or a third-party BACnet
building automation system.
Com
fortL
ink
MODE
Run Status
a30-2187
Service Test
a30-3924 Temperature
MOD
E
Pressures
Run Alarm
Servic
Status Status
Setpoints
e Tes
t
Tem
peratu
Pressu
res Inputs Alarm Status
res
Setpo
ints
Inputs Outputs
Outpu
ESCAPE ENTER
ts
Config
uration Configuration
Time
Clock
ESC
Opera
Alarm
ting
Modes Time Clock
s
Operating Modes
ENTE
R Alarms
a30-3925
MANIFOLD
MICROCHANNELS
RB F 190
Design Series
SEE NEXT PAGE
Nominal Sizes
060 110 170 275 360* FOR REMAINDER
070 120 190 300 390*
080 130 210 315* OF MODEL NUMBER
090 150 225 330*
100 160 250 345* NOMENCLATURE
Voltage
1 575-3-60 5 208/230-3-60
2 380-3-60 6 460-3-60
Cooler Options
- Integral Cooler, CRN (Canada)
0 Integral Cooler, Cooler Heater, CRN (Canada)
Condenser Coil Options 4 Integral Cooler, Microchannel (MCHX), CRN (Canada)
- Aluminum Fin/Copper Tube 5 Integral Cooler, Cooler Heater, Microchannel (MCHX), CRN (Canada)
0 Copper Fin/Copper Tube G Integral Cooler, no CRN
1 Aluminum Pre-Coat Fin/Copper Tube H Integral Cooler, Cooler Heater, no CRN
2 Aluminum E-Coat Fin/Copper Tube K Integral Cooler, Microchannel (MCHX), no CRN
3 Copper E-Coat Fin/Copper Tube L Integral Cooler, Cooler Heater, Microchannel (MCHX), no CRN
4 Microchannel (MCHX) R Integral Cooler, Microchannel (MCHX), Heat Recovery, no CRN
5 E-Coat, Microchannel (MCHX) S Integral Cooler, Cooler Heater, Microchannel (MCHX), Heat Recovery,
no CRN
Hydronics Option T Integral Cooler, Microchannel (MCHX), Heat Recovery, CRN (Canada)
- No Pump Installed V Integral Cooler, Cooler Heater, Microchannel (MCHX), Heat Recovery,
0 Single Pump, 3 HP CRN (Canada)
1 Single Pump, 5 HP
2 Single Pump, 7.5 HP
3 Single Pump, 10 HP
4 Single Pump, 15 HP
6 Dual Pump, 3 HP LEGEND
7 Dual Pump, 5 HP CRN Canadian Registration Number
8 Dual Pump, 7.5 HP, Low Head EMM Energy Management Module
9 Dual Pump, 7.5 HP, High Head GFI-CO Ground Fault Interrupting Convenience Outlet
B Dual Pump, 10 HP LON Local Operating Network
SCCR Short Circuit Current Rating
C Dual Pump, 15 HP VFD Variable Frequency Device
F Single Pump, 3 HP with VFD XL Across-the-Line Start
G Single Pump, 5 HP with VFD
H Single Pump, 7.5 HP with VFD *Refer to the Unit Sizes and Modular Combinations table below.
Hydronic pumps not available on units 30RB060-190 with high SCCR option.
J Single Pump, 10 HP with VFD
K Single Pump, 15 HP with VFD NOTE: A Z in position 11 indicates a special order machine. Digits following
do not correspond to tables.
M Dual Pump, 3 HP with VFD
N Dual Pump, 5 HP with VFD
P Dual Pump, 7.5 HP, Low Head with VFD
T Dual Pump, 7.5 HP, High Head with VFD
Q Dual Pump, 10 HP with VFD
R Dual Pump, 15 HP with VFD
Z Special order designation Quality Assurance
a30-6273
ISO 9001: 2008-certified processes
4
RB F 190 6 -
Packaging/Security Options
L No Packaging
0 Skid
1 Skid, Top Crate, Bag
3 Coil Trim Panels
SEE PREVIOUS PAGE 4 Skid, Coil Trim Panels
5 Skid, Top Crate, Bag, Coil Trim Panels
FOR REMAINDER 7 Coil Trim Panels, Upper and Lower Grilles
8 Skid, Coil Trim Panels, Upper and Lower Grilles
OF MODEL NUMBER 9 Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles
C Trim Panels, Upper and Lower Grilles, Upper Hail Guards
NOMENCLATURE D Skid, Trim Panels, Upper and Lower Grilles, Upper Hail Guards
F Skid, Top Crate, Bag, Trim Panels, Upper and Lower Grilles,
Upper Hail Guards
H Skid, Full End Covers
J Skid, Top Crate, Bag, Full End Covers
K Full End Covers
Refrigeration Circuit Options
- No Suction Line Insulation
0 Suction Insulation Controls/Communication Options
1 Suction Service Valves - None
2 Low Ambient Head Pressure Control Operation 0 EMM
3 Suction Insulation, Suction Service Valves 1 Remote Service Port, GFI-CO
4 Suction Insulation, Low Ambient Head Pressure Control Operation 2 EMM, Remote Service Port, GFI-CO
5 Suction Service Valves, Low Ambient Head Pressure Control Operation 3 BACnet Communication
6 Suction Insulation, Service Valves, Low Ambient Head Pressure 4 BACnet Communication, EMM
Control Operation 5 BACnet Communication, Remote Service Port, GFI-CO
7 Minimum Load Control 6 BACnet Communication, EMM, Remote Service Port, GFI-CO
8 Suction Insulation, Minimum Load Control Operation 7 BACnet/Modbus Translator
9 Suction Service Valves, Minimum Load Control Operation 8 BACnet/Modbus Translator, EMM
B Low Ambient Operation, Minimum Load Control Operation 9 BACnet/Modbus Translator, Remote Service Port, GFI-CO
C Suction Insulation, Suction Service Valves, Minimum Load B BACnet/Modbus Translator, EMM, Remote Service Port, GFI-CO
Control Operation H LON Translator
D Suction Insulation, Low Ambient Head Pressure Control Operation, J LON Translator, EMM
Minimum Load Control Operation K LON Translator, Remote Service Port, GFI-CO
F Suction Service Valves, Low Ambient Head Pressure Control Operation, L LON Translator, EMM, Remote Service Port, GFI-CO
Minimum Load Control Operation
G Suction Insulation, Suction Service Valves, Low Ambient Head Pressure
Control, Operation, Minimum Load Control Operation Electrical/Low Sound/High SCCR Options
H Suction Service Valves, High-Efficiency Variable Condenser Fans - Single Point Power Connections, XL, Terminal Block
J Suction Insulation, Suction Service Valve, High-Efficiency Variable 3 Dual Point Power Connections, XL, Terminal Block
Condenser Fans 7 Single Point Power Connections, XL, Non-Fused Disconnect
K High-Efficiency Variable Condenser Fans 8 Single Point Power Connections, XL, Non-Fused Disconnect, High SCCR
L Suction Insulation, High-Efficiency Variable Condenser Fans C Dual Point Power Connections, XL, Non-Fused Disconnect
M Suction Service Valves, High-Efficiency Variable Condenser Fans, D Dual Point Power Connections, XL, Non-Fused Disconnect, High SCCR
Minimum Load Control Operation G Single Point Power Connections, XL, Terminal Block, Cmpr Blankets
N Suction Insulation, Suction Service Valve, High-Efficiency Variable J Dual Point Power Connections, XL, Terminal Block, Cmpr Blankets
Condenser Fans, Minimum Load Control Operation L Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets
P High-Efficiency Variable Condenser Fans, Minimum Load Control Operation M Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
Q Suction Insulation, High-Efficiency Variable Condenser Fans, High SCCR
Minimum Load Control Operation N Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets
P Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
High SCCR
Q Single Point Power Connections, XL, Terminal Block, Cmpr Blankets,
Cmpr Enclosures
S Dual Point Power Connections, XL, Terminal Block, Cmpr Blankets,
Cmpr Enclosures
V Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
Cmpr Enclosures
W Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
Cmpr Enclosures, High SCCR
X Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
Cmpr Enclosures
Y Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
Cmpr Enclosures, High SCCR
a30-5961
LEGEND
CRN Canadian Registration Number a30-6215
EMM Energy Management Module
GFI-CO Ground Fault Interrupting Convenience Outlet
LON Local Operating Network
SCCR Short Circuit Current Rating
VFD Variable Frequency Device
XL Across-the-Line Start
5
AHRI* capacity ratings
30RB UNITS
30RB CAPACITY COMP FAN TOTAL FULL LOAD IPLV COOLER FLOW COOLER PD
UNIT POWER RATE
SIZE Tons kW kW kW kW EER COP EER COP GPM L/s ft wg kPa
060 57.1 200.6 60.3 10.3 70.6 9.7 2.8 13.1 3.8 136.9 8.6 8.9 26.6
070 66.2 232.8 70.1 10.3 80.4 9.9 2.9 13.4 3.9 158.9 10.0 11.7 34.8
080 76.0 267.3 83.1 10.3 93.4 9.8 2.9 14.3 4.2 182.4 11.5 7.0 21.0
090 86.6 304.6 85.2 15.5 100.7 10.3 3.0 13.7 4.0 207.8 13.1 9.0 26.7
100 92.8 326.5 94.1 15.5 109.6 10.2 3.0 13.5 4.0 222.8 14.1 10.2 30.4
110 106.0 372.8 110.2 15.5 125.7 10.1 3.0 13.9 4.1 254.4 16.1 9.0 26.7
120 118.0 415.0 119.7 18.1 137.7 10.3 3.0 13.8 4.0 283.2 17.9 10.9 32.5
130 127.4 448.1 129.6 20.6 150.2 10.2 3.0 13.8 4.0 305.8 19.3 12.6 37.5
150 140.0 492.4 145.9 20.6 166.6 10.1 3.0 13.6 4.0 336.0 21.2 7.2 21.4
160 152.8 537.5 151.7 25.8 177.5 10.3 3.0 13.6 4.0 366.8 23.1 8.4 25.2
170 164.1 576.9 168.0 25.8 193.8 10.2 3.0 13.6 4.0 393.7 24.8 9.6 28.8
190 186.1 654.7 188.8 31.0 219.7 10.2 3.0 13.4 3.9 446.8 28.2 12.2 36.5
210 195.4 687.3 208.3 31.0 239.3 9.8 2.9 13.3 3.9 469.1 29.6 11.5 34.4
225 206.2 725.0 222.2 31.0 253.1 9.8 2.9 13.4 3.9 494.8 31.2 12.7 38.0
250 227.6 800.3 243.2 36.1 279.4 9.8 2.9 13.4 3.9 546.1 34.5 15.4 45.9
275 250.5 881.0 263.9 41.3 305.2 9.8 2.9 13.3 3.9 601.2 37.9 18.5 55.0
300 271.8 955.8 283.9 46.5 330.4 9.9 2.9 13.2 3.9 652.2 41.1 21.5 64.3
315 305.7 1075.1 303.4 51.6 355.0 10.3 3.0 13.6 4.0 733.7 46.3 10.3 30.7
330 316.9 1114.5 319.7 51.6 371.3 10.2 3.0 13.6 4.0 760.6 48.0 11.8 35.1
345 328.1 1153.9 336.0 51.6 387.6 10.2 3.0 13.6 4.0 787.5 49.7 11.8 35.1
360 350.2 1231.6 356.7 56.8 413.5 10.2 3.0 13.4 4.0 840.5 53.0 14.9 44.5
390 372.3 1309.3 377.5 61.9 439.5 10.2 3.0 13.4 3.9 893.5 56.4 14.9 44.5
LEGEND
COP Coefficient of Performance
EER Energy Efficiency Ratios
IPLV Integrated Part Load Value
PD Pressure Drop
*Air-Conditioning, Heating, and Refrigeration Institute.
All models are compliant with ASHRAE 90.1-2007 and 90.1-2010
standards. Shaded values are compliant with ASHRAE 90.1-
2013 standards.
NOTES:
1. Based on AHRI 550/590 standard rating conditions. Ratings are
for standard chillers only. Ratings do not include options.
2. Data in this table was generated in Packaged Chiller Builder ver-
sion 3.49h. Refer to the most current version of the Packaged
Chiller Builder for the most up-to-date data.
6
30RB UNITS WITH GREENSPEED INTELLIGENCE
CAPACITY COMP FAN TOTAL FULL LOAD IPLV COOLER FLOW COOLER PD
30RB POWER RATE
UNIT SIZE
Tons kW kW kW kW EER COP EER COP GPM L/s ft wg kPa
080 76.0 267.4 83.1 10.3 93.4 9.8 2.9 15.8 4.6 182.5 11.5 7.0 21.0
090 86.6 304.6 85.2 15.5 100.7 10.3 3.0 16.0 4.7 207.8 13.1 9.0 26.7
100 92.8 326.5 94.1 15.5 109.5 10.2 3.0 15.9 4.6 222.8 14.1 10.2 30.4
110 106.0 372.8 110.2 15.5 125.7 10.1 3.0 16.7 4.9 254.4 16.1 9.0 26.7
120 118.0 415.1 119.8 18.1 137.8 10.3 3.0 16.9 4.9 283.3 17.9 10.9 32.5
130 127.4 448.1 129.6 20.6 150.2 10.2 3.0 16.8 4.9 305.8 19.3 12.6 37.5
150 140.0 492.4 146.0 20.6 166.7 10.1 3.0 16.8 4.9 336.0 21.2 7.2 21.4
160 152.8 537.6 151.6 25.8 177.4 10.3 3.0 17.0 5.0 366.8 23.1 8.4 25.2
170 164.0 576.9 167.8 25.8 193.6 10.2 3.0 17.1 5.0 393.7 24.8 9.6 28.8
190 186.1 654.7 188.8 31.0 219.8 10.2 3.0 17.1 5.0 446.8 28.2 12.2 36.5
210 195.4 687.4 208.3 31.0 239.3 9.8 2.9 16.3 4.8 469.1 29.6 11.5 34.4
225 206.1 725.0 222.2 31.0 253.2 9.8 2.9 16.4 4.8 494.8 31.2 12.7 38.0
250 227.6 800.3 243.2 36.1 279.4 9.8 2.9 16.4 4.8 546.1 34.5 15.4 45.9
275 250.5 880.9 263.9 41.3 305.2 9.8 2.9 16.4 4.8 601.2 37.9 18.5 55.0
300 271.8 955.7 283.8 46.5 330.2 9.9 2.9 16.4 4.8 652.2 41.2 21.5 64.3
315 305.7 1075.1 303.2 51.6 354.9 10.3 3.0 17.0 5.0 733.7 46.3 10.3 30.7
330 316.9 1114.5 319.4 51.6 371.1 10.2 3.0 17.1 5.0 760.6 48.0 11.8 35.1
345 328.1 1153.9 335.6 51.6 387.3 10.2 3.0 17.1 5.0 787.4 49.7 11.8 35.1
360 350.2 1231.6 356.6 56.8 413.4 10.2 3.0 17.1 5.0 840.5 53.0 14.9 44.5
390 372.3 1309.3 377.6 61.9 439.6 10.2 3.0 17.1 5.0 893.5 56.4 14.9 44.5
LEGEND
COP Coefficient of Performance
EER Energy Efficiency Ratios
IPLV Integrated Part Load Value
PD Pressure Drop
*Air-Conditioning, Heating, and Refrigeration Institute.
All models are compliant with ASHRAE 90.1-2013 standards.
NOTES:
1. Based on AHRI 550/590 standard rating conditions. Ratings are
for standard chillers only. Ratings do not include options.
2. Data in this table was generated in Packaged Chiller Builder ver-
sion 3.49h. Refer to the most current version of the Packaged
Chiller Builder for the most up-to-date data.
7
Physical data
30RB060-300 ENGLISH
UNIT 30RB 060 070 080 090 100 110 120 130 150
OPERATING WEIGHT (lb)*
Al-Cu Condenser Coil 4,111 4,317 4,600 5,932 6,155 6,519 7,690 8,045 9,174
Cu-Cu Condenser Coil 4,593 4,799 5,082 6,656 6,879 7,243 8,534 9,010 10,139
MCHX Condenser Coil 3,783 3,978 4,267 5,449 5,663 6,027 7,119 7,402 8,517
REFRIGERANT TYPE R-410A, EXV Controlled System
Refrigerant Charge (lb)
Std Coil, Ckt A/Ckt B/Ckt C 89.5/40.5/ 112/40.5/ 68.5/68.5/ 94/76/ 94/96/ 94/106/ 94/133/ 133/106/ 133/133/
MCHX Coil, Ckt A/Ckt B/Ckt C 40/20/ 40/20/ 33/33/ 40/40/ 40/42/ 40/53/ 43/57/ 54/43/ 56/62/
COMPRESSORS Scroll, Hermetic
Quantity 3 3 4 4 4 5 5 6 6
Speed (rpm) 3500
(Qty) Compressor Model Number Ckt A (2) SH240 (2) SH295 (2) SH240 (2) SH295 (2) SH295 (2) SH295 (2) SH295 (3) SH295 (3) SH295
(Qty) Compressor Model Number Ckt B (1) SH240 (1) SH240 (2) SH240 (2) SH240 (2) SH295 (3) SH240 (3) SH295 (3) SH240 (3) SH295
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
Oil Charge (Pt, Ckt A/Ckt B/Ckt C) 26.2/13.1/ 29.2/13.1/ 26.2/26.2/ 29.2/26.2/ 29.2/29.2/ 29.2/39.4/ 29.2/43.8/ 43.8/39.4/ 43.8/43.8/
No. Capacity Steps
Standard 3 3 4 4 4 5 5 6 6
Optional (Maximum) 4 4 5 5 5 6 6 7 7
Minimum Capacity Step (%)
Standard 33 29 25 22 25 18 20 15 17
Optional 22 19 16 14 18 12 14 10 12
Capacity (%)
Ckt A 67 71 50 56 50 45 40 56 50
Ckt B 33 29 50 44 50 55 60 44 50
Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
COOLER Direct Expansion, Shell and Tube Type
Weight (empty, lb) 715 715 856 856 856 970 970 970 1518
Net Fluid Volume (gal) 28.2 28.2 31.3 31.3 31.3 45.8 45.8 45.8 73.5
Maximum Refrigerant Pressure (psig) 445 445 445 445 445 445 445 445 445
Maximum Water-Side Pressure
without Pumps (psig) 300 300 300 300 300 300 300 300 300
Maximum Water-Side Pressure
with Pumps (psig) 150 150 150 150 150 150 150 150 150
COOLER WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 4 4 4 4 4 6 6 6 6
Drain (NPT) 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/
4 4 4 4 4 4 4 4 4
HYDRONIC MODULE (Optional) Pump(s) with pressure/temperature taps and combination valve.
Pump Single or Dual, 1800 or 3600 rpm
CHASSIS DIMENSIONS (ft-in.)
Length 7-11 11-10 15-9
Width 7-425/32
Height 7-67/16
LEGEND
Al-Cu Aluminum Fin/Copper Tube Condenser Coil
Cu-Cu Copper Fin/Copper Tube Condenser Coil
EXV Electronic Expansion Valve
MCHX Microchannel Condenser Coil
N/A Not Applicable
*Operating weight does not include any options.
NOTES:
1. 30RB chillers with Greenspeed intelligence are not available in unit sizes
060 and 070.
2. No pumps are available for unit sizes 210-300 or 060-190 with high SCCR
option.
8
30RB060-300 ENGLISH (cont)
UNIT 30RB 160 170 190 210 225 250 275 300
OPERATING WEIGHT (lb)*
Al-Cu Condenser Coil 10,266 10,601 12,013 13,734 14,067 15,468 16,915 18,306
Cu-Cu Condenser Coil 11,472 11,807 13,460 15,181 15,514 17,157 18,845 20,477
MCHX Condenser Coil 9,475 9,799 11,064 12,772 13,093 14,349 15,647 16,893
REFRIGERANT TYPE R-410A, EXV Controlled System
Refrigerant Charge (lb)
Std Coil, Ckt A/Ckt B/Ckt C 162/106/ 162/130/ 162/162/ 133/106/133 133/133/133 133/133/162 162/162/133 162/162/162
MCHX Coil, Ckt A/Ckt B/Ckt C 83/55/ 83/64/ 83/87/ 59/53/64 59/59/64 59/59/89 83/87/68 83/87/94
COMPRESSORS Scroll, Hermetic
Quantity 7 7 8 9 9 10 11 12
Speed (rpm) 3500
(Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (3) SH295 (3) SH295 (3) SH295 (4) SH295 (4) SH295
(Qty) Compressor Model Number Ckt B (3) SH240 (3) SH295 (4) SH295 (3) SH240 (3) SH295 (3) SH295 (4) SH295 (4) SH295
(Qty) Compressor Model Number Ckt C N/A N/A N/A (3) SH295 (3) SH295 (4) SH295 (3) SH295 (4) SH295
Oil Charge (Pt, Ckt A/Ckt B/Ckt C) 58.4/39.4/ 58.4/43.8/ 58.4/58.4/ 43.8/39.4/43.8 43.8/43.8/43.8 43.8/43.8/58.4 58.4/58.4/43.8 58.4/58.4/58.4
No. Capacity Steps
Standard 7 7 8 9 9 10 11 12
Optional (Maximum) 8 8 9 10 10 11 12 13
Minimum Capacity Step (%)
Standard 13 14 13 10 11 10 9 8
Optional 8 10 9 6 8 7 7 6
Capacity (%)
Ckt A 62 57 50 36 33 30 36 33
Ckt B 38 43 50 28 33 30 36 33
Ckt C N/A N/A N/A 36 33 40 28 33
COOLER Direct Expansion, Shell and Tube Type
Weight (empty, lb) 1518 1518 1518 2382 2382 2382 2382 2382
Net Fluid Volume (gal) 73.5 73.5 73.5 86.6 86.6 86.6 86.6 86.6
Maximum Refrigerant Pressure (psig) 445 445 445 445 445 445 445 445
Maximum Water-Side Pressure
without Pumps (psig) 300 300 300 300 300 300 300 300
Maximum Water-Side Pressure
with Pumps (psig) 150 150 150 150 150 150 150 150
COOLER WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 6 6 6 6 6 6 6 6
Drain (NPT) 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/
4 4 4 4 4 4 4 4
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Standard Low Noise Type
Fan Speed (rpm) Standard 1140 1140 1140 1140 1140 1140 1140 1140
No. Blades...Diameter (in.) 930 930 930 930 930 930 930 930
No. Fans (Ckt A/Ckt B/Ckt C) 6/4/ 6/4/ 6/6/ 4/4/4 4/4/4 4/4/6 6/6/4 6/6/6
Total Airflow (cfm) 124,000 124,000 148,800 148,800 148,800 173,600 198,400 223,200
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C) 6/4/ 6/4/ 6/6/ 4/4/4 4/4/4 4/4/6 6/6/4 6/6/6
Total Face Area (sq ft) 235 235 282 282 282 328 375 422
Max Working Refrigerant Pressure (psig) 656 656 656 656 656 656 656 656
OPTIONAL HEAT RECOVERY CONDENSER Flooded, Shell and Tube Type
Weight (lb) (empty) 1296 1296 1296
Net Fluid Volume (gal) 17.4 17.4 17.4
Maximum Refrigerant Pressure (psig) 656 656 656
Maximum Water-Side Pressure (psig) 300 300 300
Water Connections (in.)
Inlet and Outlet, Victaulic 5 5 5
Drain (NPT) 3/ 3/ 3/
8 8 8
HYDRONIC MODULE (Optional) Pump(s) with pressure/temperature taps
and combination valve.
Pump Single or Dual, 1800 or 3600 rpm Not available
CHASSIS DIMENSIONS (ft-in.)
Length 19-8 23-7 27-6 31-5 35-4
Width 7-425/32
Height 7
7-6 /16
LEGEND
Al-Cu Aluminum Fin/Copper Tube Condenser Coil
Cu-Cu Copper Fin/Copper Tube Condenser Coil
EXV Electronic Expansion Valve
MCHX Microchannel Condenser Coil
N/A Not Applicable
*Operating weight does not include any options.
NOTES:
1. 30RB chillers with Greenspeed intelligence are not available in unit sizes
060 and 070.
2. No pumps are available for unit sizes 210-300 or 060-190 with high SCCR
option.
9
Physical data (cont)
30RB060-300 SI
UNIT 30RB 060 070 080 090 100 110 120 130 150
OPERATING WEIGHT (kg)*
Al-Cu Condenser Coil 1869 1962 2091 2697 2798 2963 3488 3649 4161
Cu-Cu Condenser Coil 2088 2181 2310 3026 3127 3292 3871 4087 4599
MCHX Condenser Coil 1716 1804 1934 2472 2569 2734 3229 3358 3863
REFRIGERANT TYPE R-410A, EXV Controlled System
Refrigerant Charge (kg)
Std Coil, Ckt A/Ckt B/Ckt C 40.6/18.4/ 50.8/18.4/ 31.1/31.1/ 42.6/34.5/ 42.6/43.6/ 42.6/48.1/ 42.6/60.3/ 60.3/48.1/ 60.3/60.3/
MCHX Coil, Ckt A/Ckt B/Ckt C 18.1/9.1/ 18.1/9.1/ 14.9/14.9/ 18.1/18.1/ 18.1/19.1/ 18.1/24.0/ 19.5/25.9/ 24.5/19.5/ 25.4/28.1/
COMPRESSORS Scroll, Hermetic
Quantity 3 3 4 4 4 5 5 6 6
Speed (r/s) 58.3
(Qty) Compressor Model Number Ckt A (2) SH240 (2) SH295 (2) SH240 (2) SH295 (2) SH295 (2) SH295 (2) SH295 (3) SH295 (3) SH295
(Qty) Compressor Model Number Ckt B (1) SH240 (1) SH240 (2) SH240 (2) SH240 (2) SH295 (3) SH240 (3) SH295 (3) SH240 (3) SH295
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
Oil Charge (L, Ckt A/Ckt B/Ckt C) 12.4/6.2/ 13.8/6.2/ 12.4/12.4/ 13.8/12.4/ 13.8/13.8/ 13.8/18.6/ 13.8/20.7/ 20.7/18.6/ 20.7/20.7/
No. Capacity Steps
Standard 3 3 4 4 4 5 5 6 6
Optional (Maximum) 4 4 5 5 5 6 6 7 7
Minimum Capacity Step (%)
Standard 33 29 25 22 25 18 20 15 17
Optional 22 19 16 14 18 12 14 10 12
Capacity (%)
Ckt A 67 71 50 56 50 45 40 56 50
Ckt B 33 29 50 44 50 55 60 44 50
Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
COOLER Direct Expansion, Shell and Tube Type
Weight (empty, kg) 324 324 388 388 388 440 440 440 689
Net Fluid Volume (L) 106 106 118 118 118 173 173 173 278
Maximum Refrigerant Pressure (kPa) 3068 3068 3068 3068 3068 3068 3068 3068 3068
Maximum Water-Side Pressure
without Pumps (kPa) 2068 2068 2068 2068 2068 2068 2068 2068 2068
Maximum Water-Side Pressure
with Pumps (kPa) 1034 1034 1034 1034 1034 1034 1034 1034 1034
WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 4 4 4 4 4 6 6 6 6
Drain (NPT) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
10
30RB060-300 SI (cont)
UNIT 30RB 160 170 190 210 225 250 275 300
OPERATING WEIGHT (kg)*
Al-Cu Condenser Coil 4666 4819 5461 6243 6394 7031 7686 8321
Cu-Cu Condenser Coil 5215 5367 6118 6901 7052 7799 8566 9308
MCHX Condenser Coil 4297 4443 5019 5793 5937 6509 7096 7659
REFRIGERANT TYPE R-410A, EXV Controlled System
Refrigerant Charge (kg)
Std Coil, Ckt A/Ckt B/Ckt C 73.5/48.1/ 73.5/59.0/ 73.5/73.5/ 60.3/48.1/60.3 60.3/60.3/60.3 60.3/60.3/73.5 73.5/73.5/60.3 73.5/73.5/73.5
MCHX Coil, Ckt A/Ckt B/Ckt C 37.6/24.9/ 37.6/29.0/ 37.6/39.5/ 28.8/24.0/29.0 26.8/26.8/29.0 26.8/26.8/40.4 37.6/39.5/30.8 37.6/39.5/42.6
COMPRESSORS Scroll, Hermetic
Quantity 7 7 8 9 9 10 11 12
Speed (r/s) 58.3
(Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (3) SH295 (3) SH295 (3) SH295 (4) SH295 (4) SH295
(Qty) Compressor Model Number Ckt B (3) SH240 (3) SH295 (4) SH295 (3) SH240 (3) SH295 (3) SH295 (4) SH295 (4) SH295
(Qty) Compressor Model Number Ckt C N/A N/A N/A (3) SH295 (3) SH295 (4) SH295 (3) SH295 (4) SH295
Oil Charge (L, Ckt A/Ckt B/Ckt C) 27.6/18.6/ 27.6/20.7/ 27.6/27.6/ 20.7/18.6/20.7 20.7/20.7/20.7 20.7/20.7/27.6 27.6/27.6/20.7 27.6/27.6/27.6
No. Capacity Steps
Standard 7 7 8 9 9 10 11 12
Optional (Maximum) 8 8 9 10 10 11 12 13
Minimum Capacity Step (%)
Standard 13 14 13 10 11 10 9 8
Optional 8 10 9 6 8 7 7 6
Capacity (%)
Ckt A 62 57 50 38 33 30 36 33
Ckt B 38 43 50 28 33 30 36 33
Ckt C N/A N/A N/A 36 33 40 28 33
COOLER Direct Expansion, Shell and Tube Type
Weight (empty, kg) 689 689 689 1080 1080 1080 1080 1080
Net Fluid Volume (L) 278 278 278 327 327 327 327 327
Maximum Refrigerant Pressure (kPa) 3068 3068 3068 3068 3068 3068 3068 3068
Maximum Water-Side Pressure
without Pumps (kPa) 2068 2068 2068 2068 2068 2068 2068 2068
Maximum Water-Side Pressure
with Pumps (kPa) 1034 1034 1034 1034 1034 1034 1034 1034
WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 6 6 6 6 6 6 6 6
Drain (NPT) 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/
4 4 4 4 4 4 4 4
11
Physical data (cont)
30RB315-390 ENGLISH
UNIT 30RB 315 330 345 360 390
OPERATING WEIGHT (Module A/Module B, lb)*
Al-Cu Condenser Coil 10,266/10,266 10,601/10,266 10,601/10,601 12,013/10,601 12,013/12,013
Cu-Cu Condenser Coil 11,472/11,472 11,807/11,472 11,807/11,807 13,460/11,807 13,460/13,460
MCHX Condenser Coil 9,475/9,475 9,799/9,475 9,799/9,799 11,064/9,799 11,064/11,064
REFRIGERANT TYPE R-410A, EXV Controlled System
Circuits Qty 4 4 4 4 4
Refrigerant Charge
Std Coil, Module A Ckt A/Ckt B (lb) 162/106 162/130 162/130 162/162 162/162
Std Coil, Module B Ckt A/Ckt B (lb) 162/106 162/106 162/130 162/130 162/162
MCHX Coil, Module A Ckt A/Ckt B (lb) 83/55 83/64 83/64 83/87 83/87
MCHX Coil, Module B Ckt A/Ckt B (lb) 83/55 83/55 83/64 83/64 83/87
COMPRESSORS Scroll, Hermetic
Total Quantity 14 14 14 15 16
Speed (rpm) 3500
Module A, (Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (4) SH295 (4) SH295
Module A, (Qty) Compressor Model Number Ckt B (3) SH240 (3) SH295 (3) SH295 (4) SH295 (4) SH295
Module B, (Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (4) SH295 (4) SH295
Module B, (Qty) Compressor Model Number Ckt B (3) SH240 (3) SH240 (3) SH295 (3) SH295 (4) SH295
Module A Oil Charge (Pt, Ckt A/Ckt B) 52.5/39.4 52.5/39.4 52.5/39.4 52.5/52.5 52.5/52.5
Module B Oil Charge (Pt, Ckt A/Ckt B) 52.5/39.4 52.5/39.4 52.5/39.4 52.5/39.4 52.5/52.5
No. Capacity Steps
Standard 14 14 14 15 16
Optional (Maximum) 16 16 16 17 18
Minimum Capacity Step (%)
Standard 6 6 7 7 6
Optional 5 4 6 5 5
Capacity (%)
Module A, Ckt A 31 30 29 27 25
Module A, Ckt B 19 22 21 27 25
Module B, Ckt A 31 30 29 27 25
Module B, Ckt B 19 18 21 20 25
COOLER Direct Expansion, Shell and Tube Type
Module A Weight (empty, lb) 1518 1518 1518 1518 1518
Module B Weight (empty, lb) 1518 1518 1518 1518 1518
Net Fluid Volume (gal) Module A/Module B 73.5/73.5 73.5/73.5 73.5/73.5 73.5/73.5 73.5/73.5
Maximum Refrigerant Pressure (psig) 445 445 445 445 445
Maximum Water-Side Pressure (psig) 300 300 300 300 300
WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 6 6 6 6 6
Drain (NPT) 3/ 3/ 3/ 3/ 3/
4 4 4 4 4
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Standard Low Noise Type
Fan Speed (rpm) Standard 1140 1140 1140 1140 1140
Module A No. Blades...Diameter (in.) Ckt A/Ckt B 9...30/9...30 9...30/9...30 9...30/9...30 9...30/9...30 9...30/9...30
Module B No. Blades...Diameter (in.) Ckt A/Ckt B 9...30/9...30 9...30/9...30 9...30/9...30 9...30/9...30 9...30/9...30
Total No. Fans 20 20 20 22 24
Module A No. Fans (Ckt A/Ckt B) 6/4 6/4 6/4 6/6 6/6
Module B No. Fans (Ckt A/Ckt B) 6/4 6/4 6/4 6/4 6/6
Total Airflow (cfm) 248,000 248,000 248,000 272,800 297,600
CONDENSER COILS
Module A No. Coils (Ckt A/Ckt B) 6/4 6/4 6/4 6/6 6/6
Module B No. Coils (Ckt A/Ckt B) 6/4 6/4 6/4 6/4 6/6
Total Face Area (sq ft) 470 470 470 517 564
Max Working Refrigerant Pressure (psig) 656 656 656 656 656
LEGEND
Al-Cu Aluminum Fin/Copper Tube Condenser Coil
Cu-Cu Copper Fin/Copper Tube Condenser Coil
EXV Electronic Expansion Valve
MCHX Microchannel Condenser Coil
*Operating weight does not include any options.
NOTE: No pumps are available for unit sizes 315-390 or 060-190 with high SCCR option.
12
30RB315-390 SI
UNIT 30RB 315 330 345 360 390
OPERATING WEIGHT (Module A/Module B, kg)*
Al-Cu Condenser Coil 4656/4656 4808/4656 4808/4808 5448/4808 5448/5448
Cu-Cu Condenser Coil 5203/5203 5354/5203 5354/5354 6104/5354 6104/6104
MCHX Condenser Coil 4297/4297 4444/4297 4444/4444 5018/4444 5018/5018
REFRIGERANT TYPE R-410A, EXV Controlled System
Circuits Qty 4 4 4 4 4
Refrigerant Charge
Std Coil, Module A Ckt A/Ckt B (kg) 73.5/48.1 73.5/59.0 73.5/59.0 73.5/73.5 73.5/73.5
Std Coil, Module B Ckt A/Ckt B (kg) 73.5/48.1 73.5/48.1 73.5/59.0 73.5/59.0 73.5/73.5
MCHX Coil, Module A Ckt A/Ckt B (kg) 37.6/24.9 37.6/29.0 37.6/29.0 37.6/39.5 37.6/39.5
MCHX Coil, Module B Ckt A/Ckt B (kg) 37.6/24.9 37.6/24.9 37.6/29.0 37.6/29.0 376/39.5
COMPRESSORS Scroll, Hermetic
Total Quantity 14 14 14 15 16
Speed (r/s) 58.3
Module A, (Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (4) SH295 (4) SH295
Module A, (Qty) Compressor Model Number Ckt B (3) SH240 (3) SH295 (3) SH295 (4) SH295 (4) SH295
Module B, (Qty) Compressor Model Number Ckt A (4) SH295 (4) SH295 (4) SH295 (4) SH295 (4) SH295
Module B, (Qty) Compressor Model Number Ckt B (3) SH240 (3) SH240 (3) SH295 (3) SH295 (4) SH295
Module A Oil Charge (L, Ckt A/Ckt B) 24.8/18.6 24.8/18.6 24.8/18.6 24.8/24.8 24.8/24.8
Module B Oil Charge (L, Ckt A/Ckt B) 24.8/18.6 24.8/18.6 24.8/18.6 24.8/18.6 24.8/24.8
No. Capacity Steps
Standard 14 14 14 15 16
Optional (Maximum) 16 16 16 17 18
Minimum Capacity Step (%)
Standard 6 6 7 7 6
Optional 5 4 6 5 5
Capacity (%)
Module A, Ckt A 31 30 29 27 25
Module A, Ckt B 19 22 21 27 25
Module B, Ckt A 31 30 29 27 25
Module B, Ckt B 19 18 21 20 25
COOLER Direct Expansion, Shell and Tube Type
Module A Weight (empty, kg) 689 689 689 689 689
Module B Weight (empty, kg) 689 689 689 689 689
Net Fluid Volume (L) Module A/Module B 278/278 278/278 278/278 278/278 278/278
Maximum Refrigerant Pressure (kPa) 3068 3068 3068 3068 3068
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068
WATER CONNECTIONS (in.)
Inlet and Outlet, Victaulic 6 6 6 6 6
Drain (NPT) 3/ 3/ 3/ 3/ 3/
4 4 4 4 4
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Standard Low Noise Type
Fan Speed (r/s) Standard 19 19 19 19 19
Module A No. Blades...Diameter (mm) Ckt A/Ckt B 9...762/9...762 9...762/9...762 9...762/9...762 9...762/9...762 9...762/9...762
Module B No. Blades...Diameter (mm) Ckt A/Ckt B 9...762/9...762 9...762/9...762 9...762/9...762 9...762/9...762 9...762/9...762
Total No. Fans 20 20 20 22 24
Module A No. Fans (Ckt A/Ckt B) 6/4 6/4 6/4 6/6 6/6
Module B No. Fans (Ckt A/Ckt B) 6/4 6/4 6/4 6/4 6/6
Total Airflow (L/s) 117 042 117 042 117 042 128 747 140 452
CONDENSER COILS
Module A No. Coils (Ckt A/Ckt B) 6/4 6/4 6/4 6/6 6/6
Module B No. Coils (Ckt A/Ckt B) 6/4 6/4 6/4 6/4 6/6
Total Face Area (sq m) 43.66 43.66 43.66 48.03 52.4
Max Working Refrigerant Pressure (kPa) 4522 4522 4522 4522 4522
LEGEND
Al-Cu Aluminum Fin/Copper Tube Condenser Coil
Cu-Cu Copper Fin/Copper Tube Condenser Coil
EXV Electronic Expansion Valve
MCHX Microchannel Condenser Coil
*Operating weight does not include any options.
NOTE: No pumps are available for unit sizes 315-390 or 060-190 with high SCCR option.
13
Physical data (cont)
UNIT WEIGHTS STANDARD UNITS
AL/CU COIL UNITS WITHOUT PUMP ENGLISH AL/CU COIL UNITS WITHOUT PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT No Pump Al/Cu* UNIT No Pump Al/Cu*
30RB 30RB
A B C D Total A B C D Total
060 869 913 1193 1136 4111 060 395 415 542 516 1869
070 891 936 1275 1215 4317 070 405 425 580 552 1962
080 982 958 1313 1346 4600 080 447 436 597 612 2091
090 1159 1397 1845 1531 5932 090 527 635 839 696 2697
100 1173 1431 1952 1600 6155 100 533 650 887 727 2798
110 1319 1448 1964 1788 6519 110 600 658 893 813 2963
UNIT MOUNTING WEIGHT (lb) No Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) No Pump Al/Cu*
30RB A B C D E F Total 30RB A B C D E F Total
120 731 1762 809 985 2347 1056 7,690 120 332 799 367 447 1065 479 3488
130 728 1850 818 1168 2531 949 8,045 130 330 839 371 530 1148 431 3649
150 893 2085 888 1228 2864 1217 9,174 150 405 946 403 557 1299 552 4161
160 1106 2189 1104 1483 2923 1463 10,266 160 503 995 502 674 1328 665 4666
170 1142 2220 1108 1487 3039 1606 10,601 170 519 1009 503 676 1381 730 4819
UNIT MOUNTING WEIGHT (lb) No Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) No Pump Al/Cu*
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1094 1388 1484 1101 1479 2004 1938 1526 12,013 190 497 631 674 500 672 911 881 694 5461
210 916 1804 2139 853 1311 3044 2440 1228 13,734 210 416 820 972 388 596 1384 1109 558 6243
225 947 1836 2144 855 1313 3049 2569 1354 14,067 225 431 835 975 389 597 1386 1168 615 6394
250 1122 2271 2133 850 1307 3035 3166 1584 15,468 250 510 1032 970 386 594 1380 1439 720 7031
275 627 2269 2805 1292 1866 3808 3169 1080 16,915 275 285 1032 1275 587 848 1731 1440 491 7689
300 899 2602 2792 1284 1859 3795 3640 1435 18,306 300 409 1183 1269 584 845 1725 1654 652 8321
CU/CU COIL UNITS WITHOUT PUMP ENGLISH CU/CU COIL UNITS WITHOUT PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT No Pump Cu/Cu UNIT No Pump Cu/Cu
30RB 30RB
A B C D Total A B C D Total
060 992 1037 1311 1254 4,593 060 451 471 596 570 2088
070 1014 1059 1393 1333 4,799 070 461 481 633 606 2181
080 1106 1081 1431 1464 5,082 080 503 491 651 665 2310
090 1342 1584 2020 1711 6,656 090 610 720 918 778 3026
100 1355 1619 2126 1780 6,879 100 616 736 966 809 3127
110 1503 1635 2139 1967 7,243 110 683 743 972 894 3292
UNIT MOUNTING WEIGHT (lb) No Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) No Pump Cu/Cu
30RB A B C D E F Total 30RB A B C D E F Total
120 837 1980 917 1088 2551 1161 8,534 120 380 898 416 494 1157 527 3871
130 850 2100 940 1288 2764 1069 9,010 130 386 952 426 584 1254 485 4087
150 1015 2334 1009 1348 3097 1336 10,139 150 461 1059 458 611 1405 606 4599
160 1252 2497 1266 1642 3218 1599 11,472 160 569 1135 575 746 1463 727 5215
170 1289 2528 1270 1645 3334 1742 11,807 170 586 1149 577 748 1516 792 5367
UNIT MOUNTING WEIGHT (lb) No Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) No Pump Cu/Cu
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1257 1595 1691 1263 1638 2199 2133 1684 13,460 190 571 725 769 574 744 1000 970 765 6118
210 1018 2045 2410 978 1427 3297 2681 1326 15,181 210 463 930 1095 445 649 1498 1219 603 6901
225 1049 2078 2415 981 1429 3301 2810 1452 15,514 225 477 944 1098 446 650 1501 1277 660 7052
250 1283 2577 2404 976 1423 3288 3463 1744 17,157 250 583 1171 1093 444 647 1494 1574 793 7799
275 732 2554 3193 1501 2059 4185 3446 1175 18,845 275 333 1161 1451 682 936 1902 1566 534 8566
300 1064 2950 3179 1494 2053 4172 3974 1591 20,477 300 484 1341 1445 679 933 1896 1807 723 9308
MCHX COIL UNITS WITHOUT PUMP ENGLISH MCHX COIL UNITS WITHOUT PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT No Pump MCHX** UNIT No Pump MCHX**
30RB 30RB
A B C D Total A B C D Total
060 800 840 1098 1045 3,783 060 363 381 498 474 1716
070 821 862 1175 1120 3,978 070 372 391 533 508 1804
080 911 889 1218 1249 4,267 080 413 403 552 566 1934
090 1065 1283 1695 1406 5,449 090 483 582 769 638 2472
100 1079 1316 1796 1472 5,663 100 489 597 815 668 2569
110 1219 1339 1816 1653 6,027 110 553 607 824 750 2734
UNIT MOUNTING WEIGHT (lb) No Pump MCHX** UNIT MOUNTING WEIGHT (kg) No Pump MCHX**
30RB A B C D E F Total 30RB A B C D E F Total
120 660 1614 737 915 2210 985 7,119 120 299 732 334 415 1002 447 3229
130 648 1683 738 1088 2377 870 7,402 130 294 763 335 493 1078 394 3358
150 810 1914 805 1146 2706 1136 8,517 150 367 868 365 520 1227 515 3863
160 1020 2020 1019 1368 2698 1350 9,475 160 463 916 492 620 1224 612 4297
170 1055 2052 1024 1374 2809 1485 9,799 170 478 931 464 623 1274 673 4443
UNIT MOUNTING WEIGHT (lb) No Pump MCHX** UNIT MOUNTING WEIGHT (kg) No Pump MCHX**
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1007 1278 1367 1014 1362 1846 1785 1405 11,064 190 457 580 620 460 618 837 810 637 5019
210 852 1677 1989 793 1219 2831 2269 1142 12,772 210 386 761 902 360 553 1284 1029 518 5793
225 881 1709 1996 796 1222 2838 2391 1260 13,093 225 400 775 905 361 554 1287 1084 571 5937
250 1041 2107 1979 789 1212 2815 2937 1469 14,349 250 472 956 898 358 550 1277 1332 666 6509
275 580 2099 2594 1195 1726 3523 2931 999 15,647 275 263 952 1176 542 783 1598 1329 453 7096
300 830 2401 2576 1185 1716 3502 3359 1324 16,893 300 376 1089 1168 537 778 1588 1523 600 7659
*Condenser Coil: Aluminum Fins/Copper Tubing. NOTE: 30RB chillers with Greenspeed intelligence are not available in
Condenser Coil: Copper Fins/Copper Tubing. size 060 and 070.
** Condenser Coil: Microchannel Design.
14
UNIT WEIGHTS SINGLE PUMP UNITS
AL/CU COIL UNITS WITH SINGLE PUMP ENGLISH AL/CU COIL UNITS WITH SINGLE PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Single Pump Al/Cu* UNIT Single Pump Al/Cu*
30RB 30RB
A B C D Total A B C D Total
060 1085 1127 1230 1184 4626 060 493 512 559 538 2103
070 1107 1150 1312 1263 4832 070 503 523 597 574 2196
080 1193 1164 1354 1388 5100 080 542 529 616 631 2318
090 1353 1620 1885 1575 6432 090 615 736 857 716 2924
100 1366 1655 1991 1644 6655 100 621 752 905 747 3025
110 1565 1653 1974 1868 7059 110 711 751 897 849 3209
UNIT MOUNTING WEIGHT (lb) Single Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) Single Pump Al/Cu*
30RB A B C D E F Total 30RB A B C D E F Total
120 731 2062 960 961 2460 1056 8,230 120 332 935 435 436 1116 479 3733
130 728 2149 969 1144 2645 949 8,585 130 330 975 440 519 1200 431 3894
150 893 2486 1031 1165 3035 1217 9,827 150 405 1128 468 528 1377 552 4458
160 1238 2583 1104 1483 3155 1357 10,919 160 563 1174 502 674 1434 617 4963
170 1279 2609 1108 1487 3276 1495 11,254 170 582 1186 503 676 1489 679 5116
UNIT MOUNTING WEIGHT (lb) Single Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) Single Pump Al/Cu*
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1094 1510 1889 1101 1479 2178 1890 1526 12,666 190 497 686 858 500 672 990 859 694 5757
CU/CU COIL UNITS WITH SINGLE PUMP ENGLISH CU/CU COIL UNITS WITH SINGLE PUMP ENGLISH
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Single Pump Cu/Cu UNIT Single Pump Cu/Cu
30RB 30RB
A B C D Total A B C D Total
060 1208 1250 1348 1302 5,108 060 549 568 613 592 2322
070 1230 1273 1430 1381 5,314 070 559 579 650 628 2415
080 1317 1287 1472 1506 5,582 080 599 585 669 684 2537
090 1537 1806 2060 1753 7,156 090 699 821 937 797 3253
100 1549 1841 2166 1823 7,379 100 704 837 985 828 3354
110 1749 1839 2150 2045 7,783 110 795 836 977 930 3538
UNIT MOUNTING WEIGHT (lb) Single Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) Single Pump Cu/Cu
30RB A B C D E F Total 30RB A B C D E F Total
120 837 2280 1068 1065 2664 1161 9,074 120 380 1034 484 483 1209 527 4116
130 850 2399 1091 1264 2877 1069 9,550 130 386 1088 495 573 1305 485 4332
150 1015 2735 1153 1284 3269 1336 10,792 150 461 1241 523 583 1483 606 4895
160 1382 2894 1266 1642 3447 1495 12,125 160 628 1315 575 746 1567 680 5511
170 1424 2920 1270 1645 3569 1633 12,460 170 647 1327 577 748 1622 742 5664
UNIT MOUNTING WEIGHT (lb) Single Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) Single Pump Cu/Cu
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1257 1718 2095 1263 1638 2374 2084 1684 14,113 190 571 781 952 574 744 1079 947 765 6415
MCHX COIL UNITS WITH SINGLE PUMP ENGLISH MCHX COIL UNITS WITH SINGLE PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Single Pump MCHX** UNIT Single Pump MCHX**
30RB 30RB
A B C D Total A B C D Total
060 1008 1047 1143 1100 4298 060 457 475 518 499 1949
070 1030 1069 1220 1174 4493 070 467 485 553 532 2037
080 1115 1088 1266 1298 4767 080 506 493 574 589 2162
090 1251 1498 1743 1457 5949 090 567 679 790 661 2697
100 1265 1532 1844 1522 6163 100 574 695 836 690 2795
110 1456 1537 1836 1738 6567 110 660 697 833 788 2978
UNIT MOUNTING WEIGHT (lb) Single Pump MCHX** UNIT MOUNTING WEIGHT (kg) Single Pump MCHX**
30RB A B C D E F Total 30RB A B C D E F Total
120 660 1914 887 891 2322 985 7,659 120 299 868 402 404 1053 447 3474
130 648 1982 888 1064 2490 870 7,942 130 294 899 403 483 1129 394 3603
150 810 2316 948 1083 2877 1136 9,170 150 367 1051 430 491 1305 515 4160
160 1148 2395 1024 1376 2926 1259 10,128 160 521 1086 464 624 1327 571 4593
170 1188 2423 1029 1381 3043 1388 10,452 170 539 1099 467 626 1380 629 4740
UNIT MOUNTING WEIGHT (lb) Single Pump MCHX** UNIT MOUNTING WEIGHT (kg) Single Pump MCHX**
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1012 1396 1747 1019 1368 2015 1748 1412 11,717 190 459 633 792 462 620 914 763 640 5313
*Condenser Coil: Aluminum Fins/Copper Tubing. NOTE: 30RB chillers with Greenspeed intelligence are not available in
Condenser Coil: Copper Fins/Copper Tubing. size 060 and 070.
** Condenser Coil: Microchannel Design.
15
Physical data (cont)
UNIT WEIGHTS DUAL PUMP UNITS
AL/CU COIL UNITS WITH DUAL PUMP ENGLISH AL/CU COIL UNITS WITH DUAL PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Dual Pump Al/Cu* UNIT Dual Pump Al/Cu*
30RB 30RB
A B C D Total A B C D Total
060 1218 1259 1254 1213 4,944 060 554 572 570 552 2247
070 1240 1281 1336 1293 5,150 070 564 582 607 588 2341
080 1372 1339 1389 1424 5,523 080 624 609 631 647 2511
090 1518 1808 1919 1611 6,855 090 690 822 872 732 3116
100 1530 1843 2025 1680 7,078 100 695 838 920 764 3217
110 1741 1796 1983 1922 7,442 110 791 817 901 874 3383
UNIT MOUNTING WEIGHT (lb) Dual Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) Dual Pump Al/Cu*
30RB A B C D E F Total 30RB A B C D E F Total
120 731 2281 1061 951 2534 1056 8,613 120 332 1035 481 431 1149 479 3907
130 728 2367 1071 1133 2719 949 8,968 130 330 1074 486 514 1233 431 4068
150 893 2864 1147 1122 3177 1217 10,419 150 405 1299 520 509 1441 552 4726
160 1336 2962 1104 1483 3344 1282 11,511 160 607 1347 502 674 1520 583 5232
170 1383 2983 1108 1487 3471 1415 11,846 170 629 1356 503 676 1578 643 5385
UNIT MOUNTING WEIGHT (lb) Dual Pump Al/Cu* UNIT MOUNTING WEIGHT (kg) Dual Pump Al/Cu*
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1094 1588 2288 1101 1479 2303 1879 1526 13,258 190 497 722 1040 500 672 1047 854 1526 6014
CU/CU COIL UNITS WITH DUAL PUMP ENGLISH CU/CU COIL UNITS WITH DUAL PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Dual Pump Cu/Cu UNIT Dual Pump Cu/Cu
30RB 30RB
A B C D Total A B C D Total
060 1341 1382 1371 1331 5,426 060 610 628 623 605 2466
070 1363 1405 1453 1411 5,632 070 620 638 661 641 2560
080 1495 1462 1507 1541 6,005 080 680 665 685 701 2730
090 1702 1994 2095 1788 7,579 090 774 906 952 813 3445
100 1714 2030 2201 1858 7,802 100 779 923 1000 845 3547
110 1926 1982 2160 2099 8,166 110 875 901 982 954 3712
UNIT MOUNTING WEIGHT (lb) Dual Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) Dual Pump Cu/Cu
30RB A B C D E F Total 30RB A B C D E F Total
120 837 2498 1169 1054 2739 1161 9,457 120 380 1133 530 478 1242 527 4290
130 850 2616 1193 1252 2953 1069 9,933 130 386 1187 541 568 1339 485 4506
150 1015 3112 1270 1240 3411 1336 11,384 150 461 1412 576 562 1547 606 5164
160 1481 3273 1266 1642 3637 1420 12,717 160 673 1488 575 746 1653 646 5781
170 1527 3294 1270 1645 3763 1553 13,052 170 694 1497 577 748 1710 706 5933
UNIT MOUNTING WEIGHT (lb) Dual Pump Cu/Cu UNIT MOUNTING WEIGHT (kg) Dual Pump Cu/Cu
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1257 1799 2492 1263 1638 2502 2071 1684 14,705 190 571 818 1133 574 744 1137 941 1684 6669
MCHX COIL UNITS WITH DUAL PUMP ENGLISH MCHX COIL UNITS WITH DUAL PUMP SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Dual Pump MCHX** UNIT Dual Pump MCHX**
30RB 30RB
A B C D Total A B C D Total
060 1137 1175 1171 1133 4,616 060 516 533 531 514 2094
070 1158 1197 1248 1208 4,811 070 525 543 566 548 2182
080 1289 1258 1305 1338 5,190 080 585 571 592 607 2355
090 1411 1680 1784 1497 6,372 090 640 762 809 679 2890
100 1424 1715 1884 1563 6,586 100 646 778 854 709 2987
110 1626 1677 1852 1795 6,950 110 737 761 840 814 3152
UNIT MOUNTING WEIGHT (lb) Dual Pump MCHX** UNIT MOUNTING WEIGHT (kg) Dual Pump MCHX**
30RB A B C D E F Total 30RB A B C D E F Total
120 660 2134 987 882 2396 985 8,042 120 299 968 448 400 1087 447 3648
130 648 2201 989 1054 2564 870 8,325 130 294 998 449 478 1163 394 3776
150 810 2695 1063 1041 3017 1136 9,762 150 367 1223 482 472 1368 515 4428
160 1244 2759 1028 1381 3114 1194 10,720 160 564 1251 466 626 1412 541 4860
170 1289 2781 1033 1386 3236 1319 11,044 170 585 1261 468 629 1468 598 5009
UNIT MOUNTING WEIGHT (lb) Dual Pump MCHX** UNIT MOUNTING WEIGHT (kg) Dual Pump MCHX**
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 1016 1474 2124 1022 1373 2138 1745 1417 12,309 190 461 668 963 463 623 970 791 643 5582
*Condenser Coil: Aluminum Fins/Copper Tubing. NOTE: 30RB chillers with Greenspeed intelligence are not available in
Condenser Coil: Copper Fins/Copper Tubing. size 060 and 070.
** Condenser Coil: Microchannel Design.
16
UNIT WEIGHTS UNITS WITH OPTIONAL HEAT RECLAIM
MCHX COIL UNITS WITH HEAT RECLAIM ENGLISH MCHX COIL UNITS WITH HEAT RECLAIM SI
MOUNTING WEIGHT (lb) MOUNTING WEIGHT (kg)
UNIT Heat Reclaim MCHX** UNIT Heat Reclaim MCHX**
30RB 30RB
A B C D Total A B C D Total
060 1185 1175 1166 1176 4703 060 538 533 529 533 2133
070 1204 1196 1245 1253 4898 070 546 542 565 568 2222
080 1302 1215 1289 1381 5187 080 590 551 585 627 2353
090 1507 1689 1776 1584 6555 090 683 766 805 718 2974
100 1516 1723 1878 1652 6769 100 688 782 852 749 3071
110 1671 1732 1899 1832 7133 110 758 786 861 831 3236
UNIT MOUNTING WEIGHT (lb) Heat Reclaim MCHX** UNIT MOUNTING WEIGHT (kg) Heat Reclaim MCHX**
30RB A B C D E F Total 30RB A B C D E F Total
120 842 2353 889 863 2492 966 8405 120 382 1067 403 391 1130 438 3813
130 846 2497 905 1027 2685 854 8814 130 384 1133 411 466 1218 387 3998
150 1017 2723 969 1089 3019 1111 9929 150 462 1235 440 494 1370 504 4504
160 1229 2841 1168 1314 3127 1312 10991 160 557 1289 530 596 1419 595 4986
170 1268 2865 1171 1316 3245 1450 11315 170 575 1300 531 597 1472 658 5133
UNIT MOUNTING WEIGHT (lb) Heat Reclaim MCHX** UNIT MOUNTING WEIGHT (kg) Heat Reclaim MCHX**
30RB A B C D E F G H Total 30RB A B C D E F G H Total
190 962 1311 1461 937 1519 2620 2296 1474 12580 190 436 595 663 425 689 1188 1041 669 5706
*Condenser Coil: Aluminum Fins/Copper Tubing. NOTE: 30RB chillers with Greenspeed intelligence are not available in
Condenser Coil: Copper Fins/Copper Tubing. size 060 and 070.
** Condenser Coil: Microchannel Design.
30RB060-110* 30RB120-150
B A C B A
cooler
cooler
Compressors Compressors
a30-3963
C D D E F
30RB160, 170, 315A, 315B, 330A, 330B, 30RB190-300, 360A, 390A, 390B
345A, 345B, 360B
C B A
D C B A
cooler cooler
Compressors Compressors
a30-3964 a30-3965
D E F E F G H
*30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
NOTE: Mounting weights are calculated at mounting locations. Refer to certified drawings starting on page 21 for mounting locations.
17
Options and accessories
FACTORY-INSTALLED FIELD-INSTALLED
ITEM
OPTION ACCESSORY
Condenser Coil Options
MCHX E-Coated X
Aluminum Fin/Copper Tube X
Aluminum Fin/Copper Tube, Pre-Coated X
Aluminum Fin/Copper Tube, E-Coated X
Copper Fin/Copper Tube, E-Coated X
Copper Fin/Copper Tube Condenser Coils X
Heat Reclaim Condenser X
Controls/Communication Options
BACnet Communication X
BACnet/Modbus Translator Control X X
Chillervisor System Manager III Multi-Unit Control X
Energy Management Module (EMM) X X
LON (Local Operating Network) Translator Control X X
Navigator Display X
Remote Service Port X
Remote Enhanced Display X
Service Option X
Touch Pilot Display X
Dual Chiller Accessory Kit X
Cooler Options
Freeze Protection Cooler Heaters X
Remote Cooler X
CRN Cooler (Canada Only) X
Electrical/Low Sound Options
Unit-Mounted Main Disconnect, Non-Fused X
Convenience Outlet (not available at 380 v) X
High SCCR (includes non-fused disconnect)(460 v only) X
Low Sound - Compressor Sound Reduction Blankets X
Ultra Low Sound - Compressor Sound Reduction Enclosures X
Hydronics Option
Hydronic Pump Package (with or without VFD)(not available on unit sizes 060-190
X
with high SCCR or on sizes 210-390 with or without high SCCR option)
Refrigeration Circuit Options
High-Efficiency Variable Condenser Fans (not available on unit sizes 060 and 070) X
Compressor Suction Service Valve X
Low Ambient Temperature Head Pressure Control (not available with high-
X X
efficiency variable condenser fans)
Minimum Load Control (not available with Leaving Fluid Temperature < 38 F [< 3.3 C]) X X
Suction Line Insulation X
Security/Packaging Options
Condenser Coil Trim Panels X X
Security Grilles X X
Full Hail Guard X
Upper Hail Guard X
Full End Screen X
LEGEND
E-Coated Epoxy Coating Applied to Entire Coil Assembly NOTES:
EMM Energy Management Module 1. Std SCCR (short circuit current rating) (5 kA).
LON Local Operating Network 2. High SCCR 460 v (65 kA).
MCHX Microchannel Heat Exchanger
18
areas of high dewpoints where condensation may be a unloading (down to 6% of the full load unit capacity,
concern. depending on unit size). Minimum load control is also
Hydronic pump package option adds circulating available as a field-installed accessory. This option is not
pumps, a combination valve (isolation, modulation and available on applications with leaving fluid temperature less
check), strainer, Victaulic field piping connections, insula- than 38 F (3.3 C).
tion and heaters, and pressure/temperature taps (3). The Security grilles protect the condenser coil from damage
pumps are available in single or dual (lead/lag controlled) with coated wire grilles with openings of 1 by 4 in. (25 mm
cooler pump versions with total dynamic head external to x 102 mm). The security grille option requires the
the chiller from approximately 20 to 140 ft (6.1 m to condenser coil trim panel option. Security grilles are also
42.7 m). This package is available with or without a VFD. available as a field-installed accessory.
Also includes heater and insulation for freeze protection to Condenser coil trim panels provide an aesthetic, fin-
20 F (29 C) with the freeze protection option. The ished appearance for the condenser coil ends of the
hydronic pump package is available for sizes 060-190 and cooler/pump connection side of the unit. Condenser coil
cannot be used in conjunction with the heat reclaim option trim panels are also available as a field-installed accessory.
or on units with high SCCR option.
Upper hail guard consists of louvered panels on the ends
High-efficiency variable condenser fans control the of the machine, which firmly fasten to the machine frame
speed of all fans for improvement in part load efficiency and provide coverage from the top of the unit to the bot-
and sound levels. Additionally, high-efficiency variable con- tom of the coil. A hinged accessory hail guard is also
denser fans maintain head pressure control down to 20 F available. The accessory covers the entire unit end (both
(29 C) ambient temperature with the use of glycol and ends), and, with its hinged design, is not identical to this
wind baffles. Varying the speed of all fans on a circuit to a option.
prescribed speed provides accurate head pressure control
Full end screen consists of louvered panels on the ends
to the most efficient point while achieving optimum usage
of the machine, providing complete coverage from the top
of the coils to accomplish excellent part load efficiency.
to the bottom of the unit. This option functions as both a
These fans are the key component of the 30RB chiller with
privacy screen and a hail guard. For hail protection, an
Greenspeed intelligence. This option is not available on
accessory hail guard is also available. The accessory covers
unit sizes 060 and 070.
the entire unit end (both ends), and, with its hinged design,
Freeze protection with cooler heaters provides protec- is not identical to this option.
tion from cooler freeze-up to 20 F (29 C).
High SCCR (short circuit current rating) devices allow the
Energy management module provides energy manage- chiller to tolerate a 65 kA short circuit current for a brief
ment capabilities to minimize chiller energy consumption. period of time while protecting downstream components.
Several features are provided with this module including The high SCCR provides a higher level of protection than
leaving fluid temperature reset, cooling set point reset or the standard chiller components. This option is not avail-
demand limit control from a 4 to 20 mA signal, 2-step able on 30RB250-300 with single-point power or on
demand limit control (from 0 to 100%) activated by a 30RB060-120 with dual-point power. It is available only at
remote contact closure, and discrete input for Ice Done 460 v and includes the unit-mounted non-fused disconnect
indication for ice storage system interface. option. The standard SCCR rating for all models is 5 kA.
Service option provides a remote service port for Low sound - compressor sound blankets reduce unit
Navigator display connection and a factory-installed conve- sound levels by providing an acoustic blanket on each com-
nience outlet includes 4-amp GFI (ground fault interrupt) pressor.
receptacle with independent fuse protection. Convenience
Ultra low sound - compressor sound enclosures
outlet is 115-v female receptacle. Service option not avail-
provide enclosures which encase compressors that are cov-
able with 380 v.
ered with acoustic blankets.
Low ambient temperature head pressure control
BACnet communication option provides pre-pro-
permits operation of the 30RB units to 20 F (29 C) out-
grammed factory-installed communication capability with a
door ambient temperature. The control is also available as
BACnet MS/TP network. Allows integration with i-Vu
a field-installed accessory and requires field-installed wind
baffles. (This option or accessory is neither required nor Open control system or a third-party BACnet building
available with the high-efficiency variable condenser fan automation system. No field programming is required.
option.) BACnet/Modbus translator control provides an inter-
CRN cooler (Canada only) provides minor cooler modi- face between the chiller and a BACnet Local Area Net-
fications to meet Canadian code. work (LAN, i.e., MS/TP EIA-485). BACnet/Modbus*
translator control is also available as a field-installed acces-
Unit-mounted non-fused disconnect option provides sory. Field programming is required.
non-fused disconnect capability for power and control
located at the unit. On dual point power applications, this LON translator control interfaces between the chiller
and a Local Operating Network (LON, i.e., LonWorks
option is not available on 30RB060-120. This option is
included with the high SCCR option. FT-10A ANSI/EIA-709.1). LON translator control is also
available as a field-installed accessory. Field programming
Minimum load control option allows additional capacity is required.
reduction for unit operation below the minimum step of
* Modbus is a registered trademark of Schneider Electric.
LonWorks is a registered trademark of Echelon Corporation.
19
Options and accessories (cont)
Field-installed accessories demand limit control from a 4 to 20 mA signal, 2-step
Minimum load control accessory allows additional demand limit control (from 0 to 100%) activated by a
capacity reduction for unit operation below the minimum remote contact closure (one-step demand limit does not
step of unloading (down to 6% of the minimum unit capac- require the energy management module), and discrete
ity, depending on unit size) via hot gas bypass. This acces- input for Ice Done indication for ice stage system
sory is not available on applications with leaving fluid interface.
temperature less than 38 F (3.3 C). Remote service port consists of a receptacle for Naviga-
Full hail guard consists of hinged, louvered panels, tor connection. The port is housed in a waterproof enclo-
which cover both ends of the unit. This accessory provides sure conveniently located for easy access to information
complete protection from hail and flying debris. For hail during operation and maintenance routines.
protection, two factory options are also available. These Convenience outlet includes a 4-amp GFI (ground fault
options directly fasten to the end of the chillers (are not interrupt) receptacle with independent fuse protection.
hinged), and therefore are not identical to this accessory. Convenience outlet is a 115-v female receptacle. It is not
Navigator display accessory provides a portable hand- available with 380 v.
held display for convenient access to unit status, operation, Remote cooler accessory provides the additional hard-
configuration and troubleshooting diagnostics capability. ware required to remotely mount the cooler from the unit.
The four-line, 80-character LCD display provides clear The cooler-unit separation is limited to 75 equivalent feet.
language information in English, French, Spanish, or The remote cooler accessory cannot be used with MCHX
Portuguese. The weatherproof enclosure and industrial condenser coils or in brine applications. Never bury refrig-
grade extension cord enables the Navigator display to be erant piping on these or any other applications.
ideally suited for outdoor applications. Magnets located on BACnet/Modbus translator control provides an inter-
the back of the module allow attachment to any sheet face between the chiller and a BACnet Local Area Net-
metal component for hands-free operation. work (LAN, i.e., MS/TP EIA-485). BACnet/Modbus
Remote enhanced display accessory kit contains a translator control is also available as a factory-installed
remotely mounted indoor 40-character per line, 16-line option. Field programming is required.
display panel for unit diagnostics. LON translator control provides an interface between
Touch Pilot display used as an accessory is a cost- the chiller and a Local Operating Network (LON, i.e.,
effective, touch-screen, remote-mount device that can be LonWorks FT-10A ANSI/EIA-709.1). LON Translator
used in lieu of the remote enhanced display. control is also available as a factory-installed option. Field
Chillervisor System Manager III multi-unit control programming is required.
accessory allows sequencing of between two and eight Security grilles protect the condenser coil from damage
chillers in parallel. Pump control is also provided. with coated wire grilles and openings of 1 by 4 in. (25 mm
Low ambient temperature head pressure control x 102 mm). The security grille accessory requires the
permits operation of the 30RB units to 20 F (29 C) out- condenser coil trim panel accessory. Security grilles are
door ambient temperature. The control is also available as also available as a factory-installed option.
a factory-installed option and requires field-installed wind Condenser coil trim panels provide an aesthetic, fin-
baffles. (This option or accessory is neither required nor ished appearance for the condenser coil ends of the
available with the high-efficiency variable speed fan cooler/pump connection side of the unit. Condenser coil
option.) trim panels are also available as a factory-installed option.
Energy management module provides energy manage- Dual chiller accessory kit provides the additional hard-
ment capabilities to minimize chiller energy consumption. ware (thermistors, wells, connectors) required for applica-
Several features are provided with this module including tions with 2 chillers running in parallel.
leaving fluid temperature reset, cooling set point reset or
20
30RB060, 070 AIR-COOLED CHILLER
1447.8[57.0]
CIRCUIT CIRCUIT
B A
COMPRESSORS COMPRESSOR
CG
y
RIGGING HOLE
38.00
[1.50 ]
COOLER TUBE
Dimensions
40.00
[1.57 ]
NOTES: PD
Z
1. Unit must have clearances as follows:
Top Do not restrict. 804.35
[31.67 ]
Sides and End 6 (1.8 m) from solid surface for air-
flow.
Side 8 (2.4 m) required for coil service area. 100.00
[3.94 ] 22.2[.87]
2. All pumps have drains located at the bottom of volute PS MOUNTING HOLE
Z CG 200.00
x
for draining. [7.87 ]
281.03 1697.58 PIPING ENTRANCE AREA 414.47
3. Temperature relief devices located on suction line, liq- [11.06 ] [66.83 ] [16.32 ]
DETAIL A
uid line and filter drier of each circuit and have 1/4 AIR FLOW
SCALE 1:2
flare connection. COIL SERVICE AREA
4. Units without a pump package have the same leaving 2438.40
water connection, Y and Z dimensions (entering [96.00]
water), and Pump Discharge X dimensions as units
with a pump package. COIL SERVICE AREA
2281.37
[89.82 ]
PUMP PACKAGE
LEAVING WATER CONTROL/POWER BOX
4" VICTAULIC ALL VOLTAGES
190.00
376.01 [7.48 ]
[14.80 ]
a30-5176
SEE DETAIL A OPTION KNOCKOUT
PD 298.45 38.09
x 518.30 FOR 1/2" CONDUIT [1.50 ]
[11.75 ] [20.41 ] 949.14
[37.37 ]
408.89 1575.30 UNIT MOUNTING 408.89
[16.10 ] [62.02 ] [16.10 ]
2159.89
PS 1714.90 [85.04 ]
x
[67.52 ]
2393.08
PUMP SUCTION (PS) PUMP DISCHARGE (PD) [94.22 ]
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
4111 4944 4593 5426 3783 4616 1164 1038 675.6 309.9 353.1 381.0 482.6 188.0
30RB-060
1869 2247 2088 2466 1716 2094 [45.82] [40.86] [26.6] [12.2] [13.9] [15.0] [19.0] [7.4]
4317 5150 4799 5632 3978 4811 1165 1013 675.6 309.9 353.1 381.0 482.6 188.0
30RB-070
1932 2641 2181 2560 1804 2182 [45.86] [39.88] [26.6] [12.2] [13.9] [15.0] [19.0] [7.4]
21
22
30RB080 AIR-COOLED CHILLER
CIRCUIT CIRCUIT
B A
COMPRESSORS COMPRESSORS
CG RIGGING HOLE
1447.8 [57.00] y 19.00
[0.75 ]
NOTES:
COOLER TUBE
1. Unit must have clearances as follows: SERVICE AREA 2236.08
Top Do not restrict. [88.03 ]
Sides and End 6 (1.8 m) from solid surface for air-
flow. 45.00
[1.77 ]
Side 8 (2.4 m) required for coil service area. PD
z
Dimensions (cont)
788.34
2. All pumps have drains located at the bottom of volute [31.04 ] DETAIL A 100.00
for draining. SCALE 11:32 [3.94 ]
3. Temperature relief devices located on suction line, liq- 200.00 22.2[.87]
[7.87 ] MOUNTING HOLE
uid line and filter drier of each circuit and have 1/4
PS CG
flare connection. z x
4. Units without a pump package have the same leaving 296.47 1692.75 403.76
[11.67 ] [66.64 ] [15.90 ]
water connection, Y and Z dimensions (entering PIPING ENTRANCE AREA
water), and Pump Discharge X dimensions as units
with a pump package. COIL SERVICE AREA
5. Dimensions are in mm [inches]. AIR FLOW
2438.40
[96.00]
SCROLLING MARQUEE
DISPLAY
COOLER VENT
1/4" NTP
NO PUMP PACKAGE FAN ELECTRICAL BOX POWER BOX 230V
FIELD CONTROL WIRING (230V ONLY)
2281.37 ENTERING WATER CONTROL/POWER BOX
(FEB)
[89.82 ] PUMP PACKAGE 4" VICTAULIC 380V,460V,575V
LEAVING WATER (SEE NOTE 4)
4" VICTAULIC 7/8" KNOCKOUT TO BE
USED FOR LOCATING
COOLER DRAIN FIELD POWER WIRING
3/4" NPT SEE DETAIL A
864.00 190.00
[34.02 ] [7.48 ]
a30-5177
PS
y 215.73
PD [8.49 ] 246.36 336.50
y
386.88 [9.70 ] [13.25 ]
BACnet COMMUNICATION
PD [15.23 ]
x PUMP PACKAGE OPTION KNOCKOUT
38.09
ENTERING WATER FOR 1/2" CONDUIT
[1.50 ]
4" VICTAULIC 521.16 949.14
PS [20.52 ] [37.37 ]
x
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
4600 5523 5082 6005 4267 5190 1206 1012 675.6 309.9 353.1 381.0 497.8 170.2
30RB-080
2091 2511 2310 2730 1934 2355 [47.48] [39.84] [26.6] [12.2] [13.9] [15.0] [19.6] [6.7]
CG
x
CIRCUIT B CIRCUIT A
1447.8[57.0] COMPRESSORS COMPRESSORS
CG
y
COOLER TUBE
SERVICE AREA
2236.08 DETAIL B RIGGING HOLE
[88.03 ] 38.00
SCALE 3:16
[1.50 ]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
788.35
Sides and End 6 (1.8 m) from solid surface for air- [31.04 ] 100.00 45.00
flow. [3.94 ] [1.77 ]
Side 8 (2.4 m) required for coil service area. 22.2[.87]
200.00 MOUNTING HOLE
2. All pumps have drains located at the bottom of volute PD PS
z [7.87 ]
z
for draining.
1017.46 1632.07 937.55
3. Temperature relief devices located on suction line, liq- [40.06 ] [64.25 ] [36.91 ]
uid line and filter drier of each circuit and have 1/4 PIPING ENTRANCE AREA
flare connection.
4. Units without a pump package have the same leaving AIR FLOW
COIL SERVICE AREA
water connection, Y and Z dimensions (entering
water), and Pump Discharge X dimensions as units 2438.40
[96.00]
with a pump package.
5. Dimensions are in mm [inches]. COIL SERVICE AREA
SCROLLING MARQUEE
PUMP PACKAGE DISPLAY
LEAVING WATER POWER BOX 230V
4" VICTAULIC FIELD CONTROL WIRING FAN ELECTRICAL BOX CONTROL/POWER BOX
(230V ONLY) 380V,460V,575V
2281.37 (FEB)
[89.82 ]
a30-5178
[16.10 ] [109.03 ] FOR 1/2" CONDUIT
UNIT MOUNTING 938.35
[36.94 ]
PD 292.20 992.44
x
[11.50 ] [39.07 ]
2156.30
PS 2195.16
x [84.89 ]
[86.42 ]
3587.08 UNIT MOUNTING
[141.22 ]
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
5932 6855 6656 7579 5449 6372 1625 1017 1389.4 309.9 353.1 1097.3 497.8 170.2
30RB-090
2697 3116 3026 3445 2472 2890 [64.0] [40.0] [54.7] [12.2] [13.9] [43.2] [19.6] [6.7]
6155 7078 6879 7802 5663 6586 1614 999 1389.4 309.9 353.1 1097.3 497.8 170.2
30RB-100
2798 3217 3127 3547 2569 2987 [63.5] [39.3] [54.7] [12.2] [13.9] [43.2] [19.6] [6.7]
23
24
30RB110 AIR-COOLED CHILLER
CIRCUIT B CIRCUIT A
COMPRESSORS COMPRESSORS
1447.8[57.0] CG RIGGING HOLE
y 38.00
[1.50 ]
45.00
COOLER TUBE 2236.08 [1.77 ]
SERVICE AREA [88.03 ]
100.00
NOTES: [3.94 ]
1. Unit must have clearances as follows: 22.2[.87]
761.94 200.00 MOUNTING HOLE
Top Do not restrict. [30.00 ] [7.87 ]
PD PS
Sides and End 6 (1.8 m) from solid surface for z z
airflow. DETAIL B
Dimensions (cont)
flare connection.
4. Units without a pump package have the same leav-
ing water connection, Y and Z dimensions (entering COIL SERVICE AREA AIR FLOW
water), and Pump Discharge X dimensions as units
with a pump package. 2438.40
5. Dimensions are in mm [inches]. [96.00]
a30-5179
OPTION KNOCKOUT 39.89
408.89 2769.30 UNIT MOUNTING 408.89 FOR 1/2" CONDUIT [1.57 ]
[16.10 ] [109.03 ] [16.10 ]
938.35
PS 2728.56 [36.94 ]
x
[107.42 ]
2156.30
[84.89 ]
3587.08
UNIT MOUNTING
[141.22 ]
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
6519 7442 7243 8166 6027 6950 1713 997 856.0 281.9 60.9 340.4 391.2 233.7
30RB-110
2963 3383 3292 3712 2734 3152 [67.44] [39.25] [33.7] [11.1] [2.4] [13.4] [15.4] [9.2]
30RB120,130 AIR-COOLED CHILLER
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface for airflow.
Side 8 (2.4 m) required for coil service area.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter
drier of each circuit and have 1/4flare connection.
4. Units without a pump package have the same leaving water connec-
tion, Y and Z dimensions (entering water), and Pump Discharge X
dimensions as units with a pump package.
5. Dimensions are in mm [inches].
a30-5180
MCHX Microchannel Condenser Coil
25
26
30RB150 AIR-COOLED CHILLER
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
a30-5181
Sides and End 6 (1.8 m) from solid surface for airflow.
Side 8 (2.4 m) required for coil service area.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have 1/4flare connection.
4. Units without a pump package have the same leaving water connection, Y
and Z dimensions (entering water), and Pump Discharge X dimensions as
units with a pump package.
5. Dimensions are in mm [inches].
Dimensions (cont)
240.00
[9.45 ]
CIRCUIT B CIRCUIT A
COMPRESSORS COMPRESSORS
1447.8 CG
[57.00] y
200.00 400.00 SEE DETAIL B
[7.87 ] [15.75 ]
COOLER TUBE
SERVICE AREA
2236.08 RIGGING HOLE
[88.03 ] 38.00
[1.50 ]
DETAIL B
SCALE 3:16
755.58
[29.75 ]
PS PD
z z
100.00
[3.94 ] 22.2 [.87]
MOUNTING HOLE
200.00
769.51 1483.83 1456.33 [7.87 ]
[30.30 ] [58.42 ] [57.34 ]
3212.33 PIPING ENTRANCE AREA 1993.25
[126.47 ] [78.47 ]
AIR FLOW
COIL SERVICE AREA
2438.40
[96.00]
SCROLLING MARQUEE
DISPLAY 7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD CONTROL WIRING FAN ELECTRICAL BOX FIELD POWER WIRING
PUMP PACKAGE (FEB) (DUAL POINT 230V ONLY)
2281.37 LEAVING WATER ALL VOLTAGES (DUAL POWER NFD
[89.82 ] 6" VICTAULIC CIRCUIT B 380,460,575V
ONLY)
NO PUMP PACKAGE
COOLER DRAIN COOLER VENT 1/4" NPT ENTERING WATER
3/4" NPT} 6" VICTAULIC
(SEE NOTE 4) 215.73
864.00 [8.49 ]
[34.02 ] 190.00
PD PS
y y [7.48 ]
a30-5182
[16.10 ] [94.016 ] [109.03 ] [16.10 ]
UNIT MOUNTING UNIT MOUNTING BACnet COMMUNICATION 246.36
PS 4164.06 OPTION KNOCKOUT [9.70 ]
x
[163.94 ] FOR 1/2" CONDUIT
5975.08 938.35
[235.24 ] [36.94 ]
PUMP SUCTION (PS) PUMP DISCHARGE (PD) POWER BOX 230V ONLY (CKT A)
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
30RB-160 10266 11511 11472 12717 9475 10720 3065 994 1808.48 381 297.2 883.92 421.64 231.14
315A/B,330B 4666 5232 5215 5781 4297 4860 [120.66] [39.13] [71.2] [15.0] [11.7] [34.8] [16.6] [9.1]
30RB-170 10601 11846 11807 13052 9799 11044 3114 978 1808.48 381 297.2 883.92 421.64 231.14
330A,345A/B,360B 4819 5385 5367 5933 4443 5009 [122.59] [30.5] [71.2] [15.0] [11.7] [34.8] [16.6] [9.1]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface for airflow.
Side 8 (2.4 m) required for coil service area.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter drier of each circuit and have 1/4
flare connection.
4. Units without a pump package have the same leaving water connection, Y and Z dimensions (entering
water), and Pump Discharge X dimensions as units with a pump package. MCHX Microchannel Condenser Coil
5. Dimensions are in mm [inches].
27
28
30RB190, 360A, 390A/B AIR-COOLED CHILLER
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
2. All pumps have drains located at the bottom of volute for draining.
A A 3. Temperature relief devices located on suction line, liquid line and
3208.00 800.00 filter drier of each circuit and have 1/4flare connection.
[126.30 ] [31.50 ]
CG 4. Dimensions are in mm [inches].
x
CIRCUIT B CIRCUIT A
960.40 COMPRESSORS COMPRESSORS CG
y POWER BOX 230V (CKT B)
[37.81 ]
POWER BOX
380V,460V,575V (CKT A,B)
COOLER TUBE 2236.08
SERVICE AREA [88.03 ]
7/8" KNOCKOUT TO BE
Dimensions (cont)
SEE DETAIL B
USED FOR LOCATING
FIELD POWER WIRING
(DUAL AND SINGLE POINT) 240.00
[9.45 ]
755.58
[29.75 ]
PD 200.00
z 200.00
[7.87 ]
[7.87 ] RIGGING HOLE
400.00
38.00
PS [15.75 ]
z VIEW A-A [1.50 ]
1345.70 1297.44 SCALE 1:16
[52.98 ] [51.08 ]
1963.74 3208.06 1997.28
[77.31 ] [126.30 ] [78.63 ] DETAIL B
PIPING ENTRANCE AREA SCALE 1:4
100.00
[3.94 ]
COIL SERVICE AREA 200.00
AIR FLOW [7.87 ] 22.2 [.87]
MOUNTING HOLE
2438.40
[96.00]
COOLER VENT
1/4" NTP SCROLLING MARQUEE
DISPLAY
2281.37
FIELD CONTROL WIRING
[89.82 ] FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
PUMP PACKAGE 7/8" KNOCKOUT TO BE
LEAVING WATER NO PUMP PACKAGE USED FOR LOCATING
6" VICTAULIC ENTERING WATER FIELD POWER WIRING
6" VICTAULIC (DUAL POINT 230V ONLY)
(SEE NOTE 4) 931.93 (DUAL POWER NFD
[36.69 ] CIRCUIT B 380,460,575V
ONLY)
PD PS
y y 215.71
[8.49 ]
a30-5183
x [1.57 ]
[36.35 ] [81.64 ] 246.36
408.89 2769.30 UNIT MOUNTING 812.70 2769.30 UNIT MOUNTING 408.89 BACnet COMMUNICATION [9.70 ]
[16.10 ] [109.03 ] [32.00 ] [109.03 ] [16.10 ] OPTION KNOCKOUT
FOR 1/2" CONDUIT 938.35
PS 4164.26 [36.94 ]
x
[163.95 ] POWER BOX 230V ONLY (CKT A)
7169.08
[282.25 ]
WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT WEIGHT MAX WEIGHT CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CU/AL CU/AL PUMP CU/CU CU/CU PUMP MCHX MCHX PUMP CGx CGy X Y Z X Y Z
lb/kg lb/kg lb/kg lb/kg lb/kg lb/kg MM [INCH] MM [INCH] .25 .25 .25 .25 .25 .25
30RB-190, 12013 13258 13460 14705 11064 12309 3578 974 3002 381 297.2 2080.3 421.6 231.1
360A,390A/B 5461 6014 6118 14705 5019 5582 [140.87] [38.35] [118.2] [15.0] [11.7] [81.9] [16.6] [9.1]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
a30-5184
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have 1/4flare connection.
3. Dimensions are in mm [inches].
A A
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
800.00 1990.54
[31.50 ] [78.37 ]
2016.54 800.00 CG VIEW-A-A
[79.39 ] [31.50 ] x
DETAIL B
SCALE 1:4
930.95 1885.22
[36.652 ] [74.221 ]
POWER BOX
230V ONLY (CKT A)
SCROLLING MARQUEE
DISPLAY
437.86 215.73
[17.24 ] 437.86 39.89 938.35 [8.49 ]
[17.24 ] ENTERING WATER [1.57 ] BACnet COMMUNICATION [36.94 ]
6" VICTAULIC OPTION KNOCKOUT
FOR 1/2" CONDUIT
408.89 1575.30 2794.35 1981.65 408.89
[16.10 ] [62.02 ] [110.01 ] [78.02 ] [16.10 ]
UNIT MOUNTING UNIT MOUNTING UNIT MOUNTING 2156.30
1348.58 [84.89 ]
2806.54
[53.09 ] UNIT MOUNTING
[110.49 ]
7169.08
[282.25 ]
WEIGHT WEIGHT WEIGHT CENTER OF GRAVITY
CU/AL CU/CU MCHX CGx CGy
lb/kg lb/kg lb/kg MM [INCH] MM [INCH]
13734 15181 12772 3528 917
30RB-210
6243 6901 5793 [138.90] [36.10]
14067 15514 13093 3588 906
30RB-225
6394 7052 5937 [141.26] [35.67]
29
30
30RB250 AIR-COOLED CHILLER
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
a30-5185
2. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have 1/4flare connection.
3. Dimensions are in mm [inches].
A A
VIEW A - A
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT 800.00 SCALE 1:16
1990.54
3154.63 800.00 [31.50 ] [78.37 ]
[124.20 ] 101.20 [31.50 ] CGx
[3.98 ]
SEE DETAIL B
POWER BOX 2 POWER BOX 1
380V,460V,575V 380V,460V,575V 240.00
CKT C CKT A,B CIRCUIT A [9.45 ]
CIRCUIT C COMPRESSORS
1447.8 CIRCUIT B
Dimensions (cont)
COMPRESSORS CGy
[57.00] COMPRESSORS
RIGGING HOLE
38.00
761.93 [1.50 ]
761.93 [30.00 ] DETAIL B
[30.00 ] SCALE 3:16
1020.13
1941.86 100.00
[40.16 ] 22.2 [.87]
[76.45 ] [3.94 ]
MOUNTING HOLE
2416.18 3253.173 PIPING ENTRANCE AREA 2693.73
[95.13 ] [128.0777 ] [106.05 ] 200.00
[7.87 ]
2281.37
[89.82 ]
LEAVING WATER
6" VICTAULIC 964.00
[37.95 ]
215.75
[8.49 ]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
a30-5186
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and filter
drier of each circuit and have 1/4flare connection.
3. Dimensions are in mm [inches].
VIEW A - A
A A SCALE 9:160
100.00
2097.41 3227.88 PIPING ENTRANCE AREA 4231.79
[3.94 ]
[82.58 ] [127.08 ] [166.61 ] 200.00
[7.87 ] 22.2[.87]
MOUNTING HOLE
2438.40
[96.00]
SCROLLING MARQUEE
2281.37 DISPLAY
[89.82 ]
FIELD CONTROL WIRING FAN ELECTRICAL BOX
COOLER VENT (FEB)
1/4" NPT
437.86
COOLER DRAIN 3/4" NPT 437.86 39.89
[17.24 ] ENTERING WATER 215.73
[17.24 ] [1.57 ]
6" VICTAULIC [8.49 ]
938.35
408.89 1575.30 3582.00 3582.00 408.89 BACnet COMMUNICATION
[36.94 ]
[16.10 ] [62.02 ] [141.02 ] [141.02 ] [16.10 ] OPTION KNOCKOUT
UNIT MOUNTING UNIT MOUNTING UNIT MOUNTING FOR 1/2" CONDUIT
2223.58 4319.54
[87.54 ] [170.06 ] 2156.30
9557.08 [84.89 ]
[376.26 ] UNIT MOUNTING
WEIGHT WEIGHT WEIGHT CENTER OF GRAVITY
CU/AL CU/CU MCHX CGx CGy
lb/kg lb/kg lb/kg MM [INCH] MM [INCH]
16915 18845 15647 4857 914
30RB-275
7689 8566 7096 [191.22] [35.98]
31
32
30RB300 AIR-COOLED CHILLER
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and fil-
a30-5187
ter drier of each circuit and have 1/4flare connection.
3. Dimensions are in mm [inches].
VIEW A-A
SCALE 1:10
POWER BOX 2 POWER BOX 1
380V,460V,575V 380V,460V,575V POWER ELECTRICAL BOX (PEB)
CKT C
A A CKT A,B
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT 800.00 3158.54
[31.50 ] [124.35 ]
3210.54 800.00 CGx
[126.40 ] [31.50 ]
1447.8
[57.00] CIRCUIT C CIRCUIT B CIRCUIT A
Dimensions (cont)
100.00
COIL SERVICE AREA [3.94 ]
22.2[.87]
200.00
[7.87 ]
DETAIL B
SCALE 1:5
SCROLLING MARQUEE
DISPLAY
2281.37 FIELD CONTROL WIRING FAN ELECTRICAL BOX
(FEB)
[89.82 ]
215.73
[8.49 ]
864.00
[34.02 ]
ENTERING WATER
437.86 437.86
COOLER DRAIN 6" VICTAULIC 39.89
[17.24 ] [17.24 ] BACnet COMMUNICATION
3/4" NPT [1.57 ]
OPTION KNOCKOUT
408.89 2769.30 3582.00 3582.00 408.89 FOR 1/2" CONDUIT
938.35
[16.10 ] [109.03 ] [141.024 ] [141.024 ] [16.10 ]
[36.94 ]
UNIT MOUNTING} UNIT MOUNTING UNIT MOUNTING
3417.58 2156.30
4319.54
[134.55 ] [84.894 ]
[170.06 ]
UNIT MOUNTING
10751.08
[423.27 ]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liq-
uid line and filter drier of each circuit and have 1/4
flare connection.
3. Chillers with heat reclaim option do not have a pump
package.
4. Dimensions are in mm [inches].
a30-4734
LEGEND
HR Heat Reclaim
MCHX Microchannel Condenser Coil
33
34
30RB090-110 AIR-COOLED CHILLER WITH OPTIONAL HEAT RECLAIM
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line,
liquid line and filter drier of each circuit and have 1/4
flare connection.
3. Chillers with heat reclaim option do not have a pump
package.
4. Dimensions are in mm [inches].
Dimensions (cont)
NOTES:
a30-5963
LEGEND
HR Heat Reclaim
MCHX Microchannel Condenser Coil
30RB120 AIR-COOLED CHILLER WITH HEAT RECLAIM OPTION
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict.
Sides and End 6 (1.8 m) from solid
surface.
Side 8 (2.4 m) required for coil service
area.
2. Temperature relief devices located on
suction line, liquid line and filter drier of
each circuit and have 1/4 flare connec-
tion.
3. Chillers with heat reclaim option do not
have a pump package.
4. Dimensions are in mm [inches].
LEGEND
HR Heat Reclaim
MCHX Microchannel Condenser Coil
a30-4736
35
36
30RB130 AIR-COOLED CHILLER WITH HEAT RECLAIM OPTION
a30-4737
Dimensions (cont)
NOTES: LEGEND
1. Unit must have clearances as follows:
Top Do not restrict. HR Heat Reclaim
Sides and End 6 (1.8 m) from solid surface. MCHX Microchannel Condenser Coil
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have 1/4flare connection.
3. Chillers with heat reclaim option do not have a pump package.
4. Dimensions are in mm [inches].
30RB150 AIR-COOLED CHILLER WITH HEAT RECLAIM OPTION
a30-4738
NOTES: LEGEND
1. Unit must have clearances as follows:
Top Do not restrict. HR Heat Reclaim
Sides and End 6 (1.8 m) from solid surface. MCHX Microchannel Condenser Coil
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have 1/4flare connection.
3. Chillers with heat reclaim option do not have a pump package.
4. Dimensions are in mm [inches].
37
38
30RB160,170 AIR-COOLED CHILLER WITH HEAT RECLAIM OPTION
Dimensions (cont)
a30-4739
NOTES: LEGEND
1. Unit must have clearances as follows: HR Heat Reclaim
Top Do not restrict. MCHX Microchannel Condenser Coil
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have 1/4flare connection.
3. Chillers with heat reclaim option do not have a pump package.
4. Dimensions are in mm [inches].
30RB190 AIR-COOLED CHILLER WITH HEAT RECLAIM OPTION
a30-4740
NOTES: LEGEND
1. Unit must have clearances as follows: HR Heat Reclaim
Top Do not restrict. MCHX Microchannel Condenser Coil
Sides and End 6 (1.8 m) from solid surface.
Side 8 (2.4 m) required for coil service area.
2. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have 1/4flare connection.
3. Chillers with heat reclaim option do not have a pump package.
4. Dimensions are in mm [inches].
39
Selection procedure
Carriers NACO (North American Commercial Operations) Consider the remote cooler option. Do not bury refrig-
Packaged Chiller Builder Program provides quick, easy erant piping.
selection of Carriers air-cooled liquid chillers. The pro- Chiller idle below 32 F (0 C)
gram considers specific temperature, fluid and flow
Loop freeze protection with glycol is strongly recom-
requirements among other factors such as fouling and
mended to a minimum of 15 F (8 C) below lowest antic-
altitude corrections.
ipated ambient temperature.
Before selecting a chiller, consider the following points: Cooler heater option is required if no glycol is used.
Leaving water (fluid) temperature (LWT) Chilled water pump control is strongly recommended;
If the LWT is less than 40 F (4.4 C), loop freeze protec- otherwise override capability is required.
tion to a minimum of 30 F (16.6 C) below the LWT set Drain the cooler This will require a small amount of
point is required. glycol for residual water. Cooler heaters (if provided) will
If the LWT is to be between 15 F and 30 F (9.4 C and need to be disconnected.
1.1 C) and the unit size is 30RB060-100, then both Consider the remote cooler option. Never bury refriger-
suction line insulation and low ambient head pressure ant lines.
control (or 30RB chiller with Greenspeed intelligence) Ambient temperature
must be included. For unit sizes 30RB110-390, opera- Highest allowable ambient air temperature is 125 F
tion below 30 F (1.1 C) is not available. (52 C) for all unit sizes.
If the LWT requirement is greater than 60 F (16 C), a Lowest allowable ambient temperature for the standard
mixing loop is required. unit to start and operate is 32 F (0 C). With the inclu-
Entering water temperature (EWT) sion of wind baffles (field fabricated and installed) and
If the EWT requirement is greater than 70 F (21.1 C), a low ambient head pressure control (low ambient control
mixing loop is required. The EWT cannot exceed 70 F is not required on units with Greenspeed intelligence),
(21.1 C) for extended operation. Pulldown can be the unit is capable to start as low as 13 F (25 C) and
accomplished from 95 F (35 C). to operate as low as 20 F (29 C) ambient tempera-
ture.
Cooler flow rate or cooler delta-T
Cooling capacity requirements
The cooler delta-T must fall between 3 and 20 F (1.7
and 11 C) while still meeting both the fluid min/max Do not oversize the chillers by more than 15% at design
temperature requirements as well as the fluid min/max conditions.
flow requirements. If close capacity control is required below the standard
For larger or smaller delta-T applications, a mixing loop minimum step of unloading, the minimum load control
is required. option should be employed.
If the cooler flow is variable, then the rate of change of Coil corrosion requirements
flow should not exceed 10% per minute. A loop volume Coastal application
of greater than 3 gallons per ton (3.25 L per kW) is rec- Industrial application
ommended. Coastal/industrial application
Cooler pressure drop Urban application
A high cooler pressure drop can be expected when the Farming
cooler delta-T is low. A mixing loop can help to alleviate NOTE: See NACO Packaged Chiller Builder and appropri-
this situation. ate selection guides for more information.
Water quality, fouling factor Chilled water pump external head requirement
Poor water quality can increase the cooler fouling. Capacity control
Higher than standard fouling factors lead to lower Temperature reset
capacity and higher input kW from a given chiller size Return water reset
compared to running the same application with better Outside air temperature reset
quality water (and lower fouling factors). Space temperature reset
Operation below 32 F (0 C) 4 to 20 mA temperature reset (requires an energy man-
Low ambient head pressure control (or 30RB chiller agement module)
with Greenspeed intelligence) is required. Demand limit
Wind baffles are required. 2-step (requires an energy management module)
Consider higher loop volumes, 6 to 10 gallons per 4 to 20 mA (requires an energy management module)
nominal ton (6.5 to 10.75 L per kW). CCN loadshed
Loop freeze protection with glycol is strongly recom-
To select a chiller, use the Packaged Chiller Builder
mended to a minimum of 15 F (8 C) below lowest antic-
Program or follow one of the procedures starting on
ipated ambient temperature.
page 41.
Cooler heater option is required if no glycol is used.
Chilled water pump control is strongly recommended;
otherwise override capability is required.
40
Optional heat reclaim checklist (project SI Example
suitability for heat reclaim) I Determine unit size and operating conditions
There must be a simultaneous requirement for chilled required to meet given capacity at given
water and hot water. conditions.
Hot water temperatures from the heating system must Given:
be in the range of 68 to 120 F (20 to 49 C), with hot
Capacity. . . . . . . . . . . . . . . . . . . . . . . . . 270 kW
water flow in the range of 2 to 4 gpm (0.13 to
Leaving Chilled Water Temp (LCWT) . . . . . . . 7 C
0.25 L per minute) per heating ton.
Cooler Water Temp Rise . . . . . . . . . . . . . . 5.6 C
The chilled water load must be in the range of 60 to
Condenser Entering Air Temp . . . . . . . . . . . 35 C
190 tons (211.2 to 668.8 kW).
Fouling Factor (Cooler) . . . . . . . . . . . . . . . .0.018
The hot water load must fall in the range of 770 to
2,650 MBH (1000 Btu per hour) (812 to 2795 nM/hr) NOTE: For other than approximately 5 to 6 C
per chiller. temperature rise, unit selection must be made using
the chiller program in the electronic catalog.
NOTE: There is minimal impact on chiller cooling perfor-
mance and efficiency when the heat reclaim option is II From Chiller Ratings table on page 59 and
selected. As in all cases, performance data associated with pressure drop curves on page 42, determine
the 30RB heat reclaim chiller is to be determined from the operating data for selected unit.
current version of the chiller selection program. Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 30RB080
Capacity. . . . . . . . . . . . . . . . . . . . . . . .270.5 kW
English Example Power Input . . . . . . . . . . . . . . . . . . . . . .93.8 kW
I Determine 30RB unit size and operating Cooler Water Flow . . . . . . . . . . . . . . . . .11.6 L/s
conditions required to meet given capacity at Pressure Drop. . . . . . . . . . . . . . . . . . . . 21.2 kPa
given conditions.
Given: AquaSnap pump selection
Several pump sizes are available for each AquaSnap chiller
Capacity. . . . . . . . . . . . . . . . . . . . . . . . 126 Tons
Leaving Chilled Water Temp (LCWT) . . . . . . .44 F size to provide flexibility in matching water system require-
Cooler Water Temp Rise . . . . . . . . . . . . . . . 10 F ments. A dual pump option is also available for primary/
Condenser Entering Air Temp . . . . . . . . . . . .95 F standby operation. The Carrier Packaged Chiller Builder
Fouling Factor (Cooler) . . . . . . . . . . . . . .0.00010 Program must be used for pump selection. Pump packages
are available in both constant speed and VFD configura-
NOTE: For other than 10 F (5.6 C) temperature tions.
rise, unit selection must be made using the chiller
program in the electronic catalog. NOTE: The pump option is not available with units with
optional heat reclaim.
II From Chiller Ratings table on page 56 and
pressure drop curves on page 42, determine Proper water system design is critical; cooling loads,
operating data for selected unit. water pressure drops and proper water line sizing must be
accounted for in order to ensure proper system operation.
Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 30RB130 Incorrect or incomplete analysis/design of the water loop
Capacity. . . . . . . . . . . . . . . . . . . . . . 127.4 Tons could lead to low water flow, loss of water temperature
Power Input . . . . . . . . . . . . . . . . . . . . .150.2 kW control, and excessive cycling of chiller compressors.
Cooler Water Flow . . . . . . . . . . . . . . . 304.7 gpm
Pressure Drop . . . . . . . . . . . . . . . . 12.5 ft of water
41
Selection procedure (cont)
PUMP IMPELLER SIZES
SINGLE PUMP DUAL PUMP
UNIT PUMP
30RB Hp Option Impeller Dia. Pump Option Impeller Dia. Pump
Code* Rpm (in.) Curve Code* Rpm (in.) Curve
3 0,F 1750 6.5 I 6,M 1750 6.5 V
5 1,G 1750 7.3 I 7,N 1750 7.3 V
060
8,P 1750 8.15 V
070 7.5 2,H 1750 8.15 I
9,T 3450 5.25 VI
10 3,J 3450 5.4 II B,Q 3450 5.9 VI
30RB060-130
60
(179.4kPa)
50
(149.5kPa) 080, 090, 100
060, 070
40
(119.6kPa) 110, 120, 130
dP(Feet)
30
(89.7kPa)
20
(59.8kPa)
10
(29.8kPa)
0
0 100 200 300 400 500 600 700
GPM
42
COOLER PRESSURE DROP CURVES (cont)
a30-3966
30RB150-190 and 30RB315A,B; 330A,B; 345A,B; 360A,B; 390A,B
60
(179.4kPa)
50
(149.5kPa)
40
dP(Feet) (119.6kPa)
30
(89.7kPa)
20
(59.8kPa)
10
(29.8kPa)
0
0 200 400 600 800 1000
GPM
0.0 12.6 25.2 37.8 50.5 63.1
L/s
30RB210-300
60.0
(179.4 kPa)
50.0
(149.5 kPa)
40.0
(119.6 kPa)
dP (Feet)
30.0
(89.7 kPa)
20.0
(59.8 kPa)
10.0
(29.8 kPa)
0.0
0 200 400 600 800 1000 1200
GPM
0.0 12.6 25.2 37.8 50.5 63.1 75.7
L/s a30-5962
30RB315-390
60.0
(179.4 kPa)
50.0
(149.5 kPa)
40.0
(119.6 kPa)
dP (Feet)
30.0
(89.7 kPa)
20.0
(59.8 kPa)
10.0
(29.8 kPa)
0.0
0 500 1000 1500 2000
GPM
0.0 31.5 63.1 94.64 162.2
L/s
43
Selection procedure (cont)
OPTIONAL HEAT RECLAIM PRESSURE DROP CURVES
50
(149.5kPa)
40
(119.6 kPa)
ft wg
30
(89.7kPa)
20
(59.8kPa)
10
(29.8kPa)
0
0 100 200 300 400 500 600 700
GPM
0.00 6.31 12.62 18.93 25.24 31.55 37.85 44.16
L/s
a30-4822
40
(119.6 kPa)
30
(89.7kPa)
ft wg
120-150ton
160-190ton
20
(59.8kPa)
10
(29.8kPa)
0
0 100 200 300 400 500 600 700 800 900 1000
GPM
0.00 6.31 12.62 18.93 25.24 31.55 37.85 44.16 50.47 56.78 63.09 a30-4823
L/s
44
PUMP CURVE I FOR HYDRONIC PACKAGE SINGLE PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(21.3) 70 8.19 in 40 54 65
73
1750 RPM
78
80
(18.3) 60 81
7.50 in 80
78
(15.2) 50
7.00 in 73
7.5 hp
(12.2) 40 6.50 in
6.00 in 5 hp
(9.1) 30
65%
(6.1) 20 3 hp
N
P
(3.0) 10 S
H 2 hp
NPSHr
r
(0.0) 0
0 80 160 240 320 400 (gpm)
us
(0.00) (5.05) (10.09) (15.14) (20.19) (25.24) (l/s)
Flow Rate a30-5473
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
Head Pressure
(m) ft of fluid 3450 RPM
(45.7) 150 6.19 in 39
52
62
6.10 in
70
74
(36.6) 120 77
5.40 in
77
77
74
70
(27.4) 90
62
4.50 in
20 hp
(18.3) 60 15 hp
52%
10 hp
N 7.5 hp
(9.1) 30 P
S 5 hp
H 3 hp
r
(0.0) 0 NPSHr
0 100 200 300 400 500 (gpm)
us
(0.00) (6.31) (12.62) (18.93) (25.24) (31.54) (l/s)
Flow Rate
a30-4388
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
45
Selection procedure (cont)
PUMP CURVE IIIA FOR HYDRONIC PACKAGE SINGLE PUMP (Fresh Water)
Head Pressure
8.19 in 35 48
(m) ft of fluid 59
67 1750 RPM
73
(18.3) 60 77
78
77
(14.6) 48
73
6.50 in 67
15 hp
(11.0) 36
6.00 in
59%
10 hp
(7.3) 24 7.5 hp
5 hp
N
(3.7) 12 P 3 hp
S NPSHr
H
r
(0.0) 0
0 160 320 480 640 800 (gpm)
us
(0.00) (10.09) (20.19) (30.28) (40.38) (50.47) (l/s)
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
PUMP CURVE IIIB FOR HYDRONIC PACKAGE SINGLE PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(21.3) 70
1750 RPM
(18.3) 60
(15.2) 50
(12.2) 40
(9.1) 30
(6.1) 20
N
P
(3.0) 10 NPSHr
S
H
r
(0.0) 0
0 200 400 600 800 (gpm)
us
(0.00) (12.62) (25.24) (37.85) (50.47) (l/s)
a30-5466
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
46
PUMP CURVE IVA FOR HYDRONIC PACKAGE SINGLE PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
P
(6.1) 20 S NPSHr
H
r
(0.0) 0
0 200 400 600 800 1000 (gpm)
us a30-5468
(0.00) (12.62) (25.24) (37.85) (50.47) (63.09) (l/s)
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
PUMP CURVE IVB FOR HYDRONIC PACKAGE SINGLE PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
P
(6.1) 20 S NPSHr
H
r
(0.0) 0
0 200 400 600 800 1000 (gpm)
us
(0.00) (12.62) (25.24) (37.85) (50.47) (63.09) (l/s)
a30-5469
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
47
Selection procedure (cont)
PUMP CURVE V FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
8.19 in 39
1750 RPM
53 64
72
(18.3) 60 8.15 in 77
80
80
80
7.30 in 77
(14.6) 48
72
6.50 in 64
(11.0) 36
6.00 in
7.5 hp
53
5 hp
(7.3) 24
3 hp
N 2 hp
(3.7) 12 P
1.5 hp
S
H 1 hp
NPSHr
r
(0.0) 0
0 80 160 240 320 400 (gpm)
us
(0.00) (5.05) (10.09) (15.14) (20.19) (25.24) (l/s)
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
Head Pressure
(m) ft of fluid 6.19 in 31 42 52
60 3450 RPM
65
(45.7) 150 5.90 in 69
70
69
65
(36.6) 120
5.25 in 60
52
15 hp
(27.4) 90
4.50 in
10 hp
7.5 hp
(18.3) 60
5 hp
N 3 hp
(9.1) 30 P
S
H NPSHr
r
(0.0) 0
0 60 120 180 240 (gpm)
us
(0.00) (3.79) (7.57) (11.36) (15.14) (l/s)
Flow Rate a30-4392
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
48
PUMP CURVE VIIA FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid 3450 RPM
(45.7) 150 6.19 in 39
52
6.10 in 62
70
74
(36.6) 120 77
5.40 in 77
77
74
70
(27.4) 90
62
20 hp
(18.3) 60 15 hp
52%
10 hp
N 7.5 hp
(9.1) 30 P
S 5 hp
H
3 hp
r
(0.0) 0 NPSHr
0 100 200 300 400 500 (gpm)
us
(0.00) (6.31) (12.62) (18.93) (25.24) (31.54) (l/s)
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
PUMP CURVE VIIB FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
(6.1) 20 P
S
H NPSHr
r
(0.0) 0
0 100 200 300 400 500 (gpm)
us
(0.00) (6.31) (12.62) (18.93) (25.24) (31.55) (l/s)
a30-5467
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
49
Selection procedure (cont)
PUMP CURVE VIIC FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
P
(6.1) 20 S
H NPSHr
r
(0.0) 0
0 100 200 300 400 500 (gpm)
us
(0.00) (6.31) (12.62) (18.93) (25.24) (31.55) (l/s)
a30-5472
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
PUMP CURVE VIIIA FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
P
(6.1) 20 S NPSHr
H
r
(0.0) 0
0 200 400 600 800 1000 (gpm)
us
(0.00) (12.62) (25.24) (37.85) (50.47) (63.09) (l/s)
a30-5470
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
50
PUMP CURVE VIIIB FOR HYDRONIC PACKAGE DUAL PUMP (Fresh Water)
Head Pressure
(m) ft of fluid
(42.7) 140
3450 RPM
(36.6) 120
(30.5) 100
(24.4) 80
(18.3) 60
(12.2) 40
N
P
(6.1) 20 S NPSHr
H
r
(0.0) 0
0 200 400 600 800 1000 (gpm)
us
(0.00) (12.62) (25.24) (37.85) (50.47) (63.09) (l/s) a30-5471
Flow Rate
LEGEND NOTE: Refer to the 30RB nomenclature on page 4 for option identifi-
NPSHr Net Positive Suction Head (Pressure) Required cation. Refer to the Pump Impeller Sizes table on page 42 for more
information.
51
Selection procedure (cont)
10 0 (30m)
3
90 (27m)
80 (24m)
70 (21m)
Available Head (ft)
60 (18m)
2
50 (15m)
1
40 (12m)
0
30 (9m)
20 (6m)
10 (3m)
a30-3949
30RB080, 090, 100 SINGLE PUMP ENVELOPE CURVES
140 (42m)
4
130 (39m)
120 (36m)
110 (33m)
3
100 (30m)
90 (27m)
Available H ead (ft)
80 (24m)
70 (21m)
2
60 (18m)
50 (15m)
1
40 (12m)
30 (9m)
20 (6m)
10 (3m)
52
30RB110, 120, 130 SINGLE PUMP ENVELOPE CURVES
150 (45m)
14 0 (42m)
4
130 (39m)
12 0 (36m)
110 (33m)
3
10 0 (30m)
Available H ead (ft)
90 (27m)
80 (24m)
70 (21m)
2
60 (18m)
50 (15m)
1
40 (12m)
30 (9m)
20 (6m)
10 (3m)
0
0 50 100 150 2 00 250 300 350 400 450 5 00
FLOW RATE (GPM)
0.00 3.15 6.31 9.46 12.62 15.77 18.93 22.08 25.24 28.39 31.55
FLOW RATE (L/s)
a30-3951
12 0 (36m)
110 (33m)
4
10 0 (30m)
90 (27m)
3
80 (24m)
Available H ead (ft)
70 (21m)
2
60 (18m)
50 (15m)
40 (12m)
1
30 (9m)
20 (6m)
10 (3m)
0
0 100 200 300 400 500 600 700 800
FLOW RATE (GPM)
0.00 6.31 12.62 18.93 25.24 31.55 37.85 44.16 50.47
FLOW RATE (L/s)
NOTE: Refer to the 30RB nomenclature on page 4 for pump envelope curve option identification.
53
Selection procedure (cont)
150
15 0 (45m)
14 0 (42m)
140
B
130 (39m)
13
120
12 0 (36m)
110
110 (33m)
9
100
10 0 (30m)
90 (27m)
ailable H ead (ft)
80 (24m)
70 (21m)
A vailable
60 (18m)
8
50 (15m)
40 (12m) 7
30 (9m) 6
20 (6m)
10 (3m)
0
0 50 100 15
150 200
00 250
25 300
00 350
FLOW RATE (GPM)
0.00 3.15 6.31 9.46 12.62 15.77 18.93 22.08
FLOW RATE (L/s)
a30-3953
150 (45m)
150
14 0 (42m)
140
C
130 (39m)
13
120
12 0 (36m)
110
110 (33m)
B
100
10 0 (30m)
ailable H ead (ft)
90 (27m)
80 (24m)
Available
70 (21m)
8
60 (18m)
50 (15m)
7
40 (12m)
30 (9m)
20 (6m)
10 (3m)
NOTE: Refer to the 30RB nomenclature on page 4 for pump envelope curve option identification.
54
30RB110, 120, 130 DUAL PUMP ENVELOPE CURVES
150 (45m)
14 0 (42m)
13 0 (39m)
C
12 0 (36m)
110 (33m)
B
10 0 (30m)
Available H ead (ft)
90 (27m)
80 (24m)
70 (21m)
8
60 (18m)
50 (15m)
7
40 (12m)
30 (9m)
20 (6m)
10 (3m)
0
0 50 100 150 200 250 300 350 400 450 500
FLOW RATE (GPM)
0.00 3.15 6.31 9.46 12.62 15.77 18.93 22.08 25.24 28.39 31.55
FLOW RATE (L/s)
a30-3955
12 0 (36m)
110 (33m)
C
10 0 (30m)
90 (27m)
B
80 (24m)
Available H ead (ft)
70 (21m)
9
60 (18m)
50 (15m)
40 (12m)
30 (9m)
20 (6m)
10 (3m)
0
0 100 200 300 400 500 600 700 800 900
FLOW RATE (GPM)
0.00 6.31 12.62 18.93 25.24 31.55 37.85 44.16 50.47 56.78
FLOW RATE (L/s)
NOTE: Refer to the 30RB nomenclature on page 4 for pump envelope curve option identification.
55
Performance data
30RB PACKAGED AIR-COOLED CHILLER RATINGS TABLE ENGLISH
CONDENSER ENTERING AIR TEMPERATURE (F)
85 95 105 115 120
LCWT UNIT
(F) SIZE Cooler Cooler Cooler Cooler Cooler
Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate
(Tons) kW (gpm) (Tons) kW (gpm) (Tons) kW (gpm) (Tons) kW (gpm) (Tons) kW (gpm)
060 55.6 63.3 132.7 51.8 69.1 123.7 48.0 75.6 114.7 43.9 83.0 105.1 41.8 87.0 99.9
070 65.6 72.3 156.7 61.6 78.9 147.2 57.4 86.2 137.1 52.7 94.3 126.0 50.3 98.7 120.1
080 74.3 83.2 177.4 69.3 90.9 165.4 63.9 99.6 152.6 58.2 109.3 139.0 55.1 114.6 131.8
090 85.2 90.8 203.5 80.0 98.9 191.1 74.4 107.9 177.6 68.2 117.9 162.9 65.0 123.3 155.2
100 92.0 99.0 219.8 86.5 107.7 206.6 80.7 117.5 192.8 74.4 128.3 177.7 71.0 134.1 169.6
110 105.0 112.9 250.9 98.5 123.4 235.1 91.5 135.3 218.6 84.1 148.4 200.8 80.1 155.5 191.3
120 116.9 124.2 279.2 109.9 135.3 262.4 102.3 147.8 244.4 94.0 161.5 224.6 89.6 168.8 214.1
130 126.1 135.4 301.3 118.4 147.5 282.9 110.2 161.0 263.2 101.1 176.0 241.6 96.2 184.0 229.9
150 138.5 150.0 330.7 130.1 163.2 310.6 121.0 177.9 288.9 111.1 194.1 265.2 105.7 202.8 252.4
160 150.2 160.0 358.9 141.3 174.3 337.5 131.6 190.2 314.3 121.0 207.8 288.9 115.4 217.3 275.5
170 161.8 174.7 386.5 152.2 190.1 363.5 141.7 207.4 338.4 130.2 226.3 311.0 124.0 236.4 296.3
40
190 183.6 198.4 438.6 172.8 215.8 412.8 161.2 235.4 385.1 148.6 256.9 354.8 141.7 268.4 338.1
210 192.9 215.3 460.6 181.4 234.7 433.3 168.9 256.3 403.5 155.2 280.2 370.7 147.7 292.9 352.9
225 203.7 227.7 486.3 191.6 248.1 457.7 178.5 270.8 426.4 164.1 295.7 391.9 156.3 309.0 373.2
250 224.9 251.8 537.1 211.5 274.1 505.3 197.1 299.0 471.1 181.2 326.4 432.9 172.6 341.0 412.3
275 247.7 275.5 591.6 233.3 300.0 557.3 217.7 327.3 519.9 200.4 357.4 478.2 191.1 373.5 456.5
300 268.7 298.6 641.8 253.1 324.9 604.5 236.2 354.4 564.2 217.7 386.9 520.0 207.7 404.3 495.4
315 300.5 320.0 717.7 282.6 348.5 675.0 263.2 380.4 628.7 242.1 415.7 577.8 230.7 434.6 551.0
330 312.1 334.7 745.3 293.5 364.4 701.0 273.3 397.6 652.7 251.3 434.2 600.0 239.4 453.7 571.8
345 323.7 349.3 773.0 304.4 380.2 727.1 283.4 414.7 676.8 260.4 452.6 622.1 248.1 472.9 592.6
360 345.5 373.0 825.1 325.1 405.9 776.4 302.9 442.7 723.5 278.8 483.2 665.9 265.7 504.8 634.4
390 367.3 396.8 877.1 345.7 431.6 825.7 322.5 470.7 770.2 297.1 513.8 709.6 283.4 536.7 676.2
060 58.5 64.0 139.8 54.8 69.9 131.0 50.8 76.5 121.5 46.5 83.8 111.2 44.1 87.8 105.4
070 68.0 73.0 162.5 63.9 79.6 152.7 59.5 87.0 142.2 54.8 95.2 130.9 52.2 99.5 124.9
080 78.0 84.4 186.4 72.7 92.2 173.9 67.1 101.0 160.4 61.1 110.7 146.0 57.8 115.9 138.2
090 88.9 91.7 212.4 83.5 99.7 199.7 77.7 108.8 185.8 71.3 118.9 170.5 67.9 124.3 162.4
100 95.3 99.9 227.8 89.6 108.6 214.3 83.6 118.5 199.9 77.2 129.3 184.5 73.7 135.1 176.2
110 108.9 114.0 260.4 102.2 124.6 244.3 95.0 136.4 227.1 87.3 149.6 208.7 83.2 156.7 198.8
120 121.1 125.3 289.5 113.9 136.5 272.3 106.2 149.0 253.7 97.6 162.8 233.6 93.1 170.1 222.5
130 130.8 136.7 312.6 122.9 148.8 293.7 114.3 162.4 273.3 105.1 177.4 251.2 100.0 185.5 239.2
150 143.7 151.6 343.4 135.0 164.8 322.6 125.6 179.7 300.2 115.3 195.9 275.7 109.8 204.6 262.4
160 156.2 161.6 373.4 147.0 175.8 351.3 136.9 191.8 327.3 125.9 209.5 300.8 120.0 219.0 286.9
170 168.0 176.5 401.6 158.1 191.9 377.8 147.3 209.2 351.9 135.4 228.2 323.3 129.0 238.4 308.3
42
190 190.6 200.3 455.5 179.4 217.6 428.7 167.4 237.2 400.0 154.3 258.9 368.8 147.2 270.4 351.5
210 200.2 217.5 478.3 188.4 236.9 450.2 175.5 258.7 419.4 161.3 282.6 385.5 153.6 295.4 367.1
225 211.3 230.2 505.3 198.9 250.6 475.1 185.3 273.4 443.0 170.4 298.4 407.4 162.3 311.8 388.0
250 233.2 254.3 557.2 219.5 276.7 524.7 204.6 301.7 488.7 188.2 329.3 449.9 179.3 343.9 428.6
275 256.6 278.0 613.4 241.8 302.5 578.0 225.8 330.0 539.6 208.0 360.2 496.7 198.4 376.4 474.0
300 278.4 301.2 665.4 262.3 327.6 627.0 244.9 357.2 585.4 225.9 389.9 540.0 215.5 407.3 515.2
315 312.4 323.2 746.8 294.0 351.6 702.6 273.8 383.6 654.5 251.9 419.0 601.7 240.1 438.0 573.9
330 324.2 338.0 775.0 305.1 367.7 729.1 284.2 401.0 679.2 261.3 437.7 624.2 249.0 457.4 595.2
345 336.1 352.9 803.2 316.2 383.8 755.7 294.5 418.4 703.9 270.8 456.5 646.7 258.0 476.8 616.6
360 358.6 376.8 857.1 337.5 409.6 806.6 314.6 446.4 752.0 289.7 487.1 692.2 276.2 508.8 659.8
390 381.2 400.6 911.0 358.7 435.3 857.4 334.7 474.5 800.0 308.6 517.7 737.6 294.4 540.8 702.9
060 60.8 64.9 145.3 57.1 70.6 136.5 52.9 77.1 126.6 48.5 84.5 116.0 46.1 88.5 110.4
070 70.4 73.8 168.5 66.2 80.4 158.3 61.7 87.8 147.6 56.8 96.0 135.9 54.2 100.4 129.6
080 81.3 85.5 194.5 76.0 93.4 181.8 70.2 102.2 167.9 64.0 112.0 153.0 60.6 117.3 145.0
090 92.1 92.7 220.3 86.6 100.7 207.1 80.7 109.7 193.1 74.2 119.8 177.6 70.8 125.2 169.2
100 98.7 100.8 236.1 92.8 109.6 222.0 86.6 119.4 207.2 80.0 130.3 191.3 76.4 136.1 182.8
110 112.8 115.3 269.8 106.0 125.7 253.4 98.6 137.6 235.8 90.6 150.8 216.7 86.3 158.0 206.5
120 125.4 126.8 299.8 118.0 137.7 282.2 110.0 150.3 263.3 101.3 164.1 242.4 96.6 171.4 231.0
130 135.6 138.1 324.3 127.4 150.2 304.7 118.6 163.9 283.7 109.1 179.0 261.0 103.9 187.0 248.6
150 149.0 153.3 356.3 140.0 166.6 334.9 130.3 181.4 311.7 119.7 197.8 286.3 114.0 206.4 272.6
160 162.3 163.2 388.2 152.9 177.5 365.6 142.4 193.5 340.6 131.0 211.2 313.1 124.9 220.7 298.7
170 174.4 178.4 417.0 164.1 193.8 392.4 152.9 211.1 365.8 140.6 230.2 336.4 134.0 240.4 320.5
44
190 197.8 202.5 473.2 186.2 219.7 445.2 173.6 239.2 415.3 160.1 260.8 382.9 152.8 272.4 365.5
210 207.7 219.8 496.5 195.5 239.3 467.5 182.1 261.1 435.6 167.5 285.1 400.6 159.6 298.0 381.6
225 219.0 232.7 523.8 206.2 253.1 492.9 192.2 276.0 459.7 176.8 301.2 423.0 168.5 314.5 403.0
250 241.5 256.9 577.7 227.6 279.4 544.3 212.2 304.5 507.5 195.3 332.1 467.2 186.1 346.9 445.2
275 265.9 280.8 635.5 250.5 305.2 599.2 234.0 332.7 559.5 215.7 363.1 515.9 205.7 379.3 491.5
300 288.5 304.2 689.6 271.8 330.4 649.6 253.8 360.0 607.1 234.2 392.8 560.2 223.6 410.3 534.4
315 324.6 326.5 776.4 305.7 355.0 731.1 284.8 386.9 681.1 262.0 422.4 626.3 249.8 441.4 597.4
330 336.7 341.6 805.2 316.9 371.3 758.0 295.3 404.6 706.3 271.7 441.4 649.5 258.9 461.1 619.2
345 348.8 356.7 834.1 328.1 387.6 784.8 305.9 422.2 731.6 281.3 460.4 672.8 268.0 480.8 641.1
360 372.2 380.8 890.2 350.2 413.5 837.6 326.6 450.3 781.1 300.8 491.1 719.3 286.8 512.8 686.0
390 395.7 404.9 946.3 372.3 439.5 890.5 347.3 478.3 830.6 320.2 521.7 765.9 305.7 544.9 731.0
LEGEND NOTE: Ratings are for standard chillers with no options. Some options will have
LCWT Leaving Chilled Water Temperature an effect on unit performance, such as Greenspeed intelligence, coil configura-
tion, etc.
56
30RB PACKAGED AIR-COOLED CHILLER RATINGS TABLE ENGLISH (cont)
CONDENSER ENTERING AIR TEMPERATURE (F)
85 95 105 115 120
LCWT UNIT
(F) SIZE Cooler Cooler Cooler Cooler Cooler
Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Rate Flow Rate Flow Rate (Tons) Flow Rate Flow Rate
(Tons) kW (Tons) kW (Tons) kW kW (Tons) kW
(gpm) (gpm) (gpm) (gpm) (gpm)
060 63.1 65.8 151.2 59.3 71.5 142.0 55.2 77.9 132.0 50.6 85.2 121.1 48.1 89.2 115.1
070 72.9 74.7 174.5 68.5 81.2 164.0 63.9 88.7 153.0 58.9 96.9 141.0 56.2 101.3 134.6
080 84.7 86.7 202.7 79.2 94.6 189.6 73.2 103.5 175.2 66.7 113.3 159.7 63.2 118.6 151.4
090 95.5 93.9 228.7 89.9 101.8 215.1 83.8 110.7 200.5 77.2 120.7 184.6 73.5 126.1 176.0
100 102.1 101.8 244.4 96.1 110.5 230.0 89.7 120.4 214.7 82.8 131.4 198.3 79.1 137.2 189.5
110 116.8 117.1 279.4 109.8 127.2 262.7 102.2 138.8 244.7 94.0 152.1 224.9 89.6 159.2 214.3
120 129.7 128.3 310.4 122.1 139.3 292.2 114.0 151.5 272.8 105.1 165.4 251.5 100.2 172.8 239.7
130 140.5 139.5 336.2 132.1 151.7 316.1 123.0 165.4 294.4 113.2 180.5 270.9 107.9 188.6 258.2
150 154.6 155.1 370.0 145.3 168.4 347.8 135.3 183.3 323.8 124.3 199.7 297.6 118.4 208.4 283.1
160 168.5 164.9 403.2 158.7 179.3 379.8 148.0 195.2 354.1 136.2 212.9 325.9 129.8 222.5 310.7
170 180.8 180.3 432.7 170.2 195.8 407.2 158.7 213.1 379.7 146.0 232.2 349.4 139.2 242.4 332.7
46
190 205.0 204.6 490.3 193.0 221.9 461.8 180.0 241.3 430.8 166.0 262.9 397.2 158.5 274.5 379.2
210 215.4 222.2 515.5 202.8 241.7 485.2 189.1 263.6 452.5 173.9 287.7 416.3 165.7 300.6 396.6
225 227.1 235.3 543.6 213.9 255.9 512.0 199.4 278.8 477.0 183.6 304.0 439.3 174.9 317.5 418.6
250 250.3 259.7 599.1 235.9 282.2 564.6 220.2 307.4 527.0 202.7 335.2 484.8 193.2 349.9 462.5
275 275.5 283.8 659.3 259.6 308.2 621.3 242.4 335.6 580.1 223.7 366.0 535.2 213.4 382.3 510.7
300 298.8 307.3 714.8 281.6 333.5 673.9 263.0 363.0 629.3 242.7 395.8 580.9 231.8 413.4 554.7
315 337.0 329.8 806.4 317.4 358.5 759.6 295.9 390.5 708.2 272.3 425.8 651.7 259.6 444.9 621.4
330 349.3 345.2 835.9 328.9 375.1 787.0 306.6 408.4 733.8 282.2 445.2 675.3 269.0 464.9 643.4
345 361.6 360.7 865.4 340.3 391.6 814.4 317.3 426.3 759.4 292.0 464.5 698.9 278.3 484.9 665.5
360 385.8 384.9 923.0 363.1 417.7 869.0 338.7 454.5 810.5 312.0 495.1 746.6 297.6 516.9 712.0
390 410.0 409.2 980.7 385.9 443.8 923.7 360.0 482.6 861.6 331.9 525.7 794.4 316.9 549.0 758.4
060 65.6 66.7 157.0 61.6 72.5 147.5 57.3 79.0 137.3 52.7 86.0 126.1 50.1 90.0 120.1
070 75.4 75.7 180.6 70.9 82.2 169.8 66.2 89.5 158.4 61.0 97.8 146.1 58.2 102.3 139.5
080 88.0 88.1 210.6 82.5 95.9 197.5 76.4 104.8 182.8 69.6 114.7 166.7 66.0 119.9 158.0
090 99.0 95.2 237.0 93.1 103.1 223.0 86.9 111.9 208.0 80.1 121.7 191.8 76.4 127.0 183.1
100 105.6 103.1 253.0 99.5 111.6 238.1 92.9 121.5 222.4 85.8 132.4 205.5 82.0 138.3 196.3
110 120.8 119.0 289.3 113.6 129.1 272.0 105.9 140.4 253.6 97.4 153.4 233.5 92.9 160.6 222.4
120 134.1 129.8 321.2 126.3 140.9 302.4 117.9 153.2 282.4 108.9 166.8 260.8 103.9 174.2 248.8
130 145.6 140.9 348.6 136.9 153.2 327.7 127.5 166.9 305.4 117.4 182.1 281.2 111.9 190.2 268.0
150 160.4 156.9 384.0 150.9 170.4 361.3 140.5 185.3 336.4 129.1 201.7 309.2 123.0 210.5 294.5
160 174.9 166.7 418.8 164.8 181.1 394.5 153.7 197.1 368.1 141.5 214.8 338.8 134.9 224.3 323.0
170 187.4 182.4 448.8 176.4 197.9 422.4 164.5 215.3 394.0 151.5 234.4 362.5 144.4 244.5 345.9
48
190 212.4 206.8 508.6 200.0 224.2 478.5 186.6 243.6 446.8 172.0 265.1 412.0 164.2 276.6 393.2
210 223.5 224.6 535.1 210.4 244.3 503.8 196.2 266.3 470.2 180.6 290.5 432.5 172.1 303.4 412.1
225 235.5 238.1 563.4 221.9 258.7 531.4 207.0 281.7 495.4 190.6 307.1 456.3 181.6 320.5 434.9
250 259.4 262.6 621.2 244.5 285.2 585.6 228.4 310.5 546.9 210.4 338.3 503.8 200.6 353.1 479.9
275 285.4 286.9 683.4 269.0 311.4 644.2 251.2 338.8 601.6 231.8 369.0 555.0 221.3 385.4 529.8
300 309.5 310.5 741.2 291.8 336.9 698.7 272.5 366.4 652.6 251.5 399.0 602.3 240.2 416.6 575.2
315 349.7 333.4 837.5 329.5 362.1 789.0 307.5 394.3 736.3 283.0 429.6 677.6 269.8 448.5 646.1
330 362.3 349.0 867.6 341.2 379.0 817.0 318.3 412.4 762.2 293.0 449.2 701.4 279.3 468.8 668.9
345 374.8 364.7 897.6 352.8 395.8 844.9 329.1 430.6 788.0 303.1 468.8 725.1 288.9 489.1 691.7
360 399.8 389.2 957.4 376.4 422.1 900.9 351.1 458.9 840.8 323.6 499.5 774.5 308.6 521.1 739.1
390 424.8 413.6 1017.2 399.9 448.4 956.9 373.2 487.3 893.7 344.1 530.2 823.9 328.4 553.2 786.4
060 67.9 67.6 162.7 63.8 73.5 152.9 59.4 80.0 142.4 54.7 87.1 131.0 52.1 90.9 124.9
070 78.0 76.8 186.9 73.3 83.3 175.8 68.4 90.6 164.1 63.1 98.7 151.4 60.3 103.2 144.6
080 91.0 89.5 218.1 85.4 97.4 204.5 79.3 106.2 190.1 72.5 116.0 173.7 68.7 121.3 164.7
090 102.4 96.6 245.5 96.4 104.5 230.9 89.9 113.2 215.5 83.0 123.0 198.8 79.2 128.2 189.8
100 109.2 104.5 261.8 102.9 113.0 246.5 96.1 122.5 230.3 88.8 133.5 212.8 84.8 139.4 203.3
110 125.0 120.9 299.5 117.5 131.2 281.5 109.6 142.5 262.5 100.9 155.0 241.8 96.3 161.9 230.6
120 138.6 131.4 332.2 130.6 142.5 312.8 122.0 154.9 292.3 112.6 168.5 270.0 107.6 175.7 258.0
130 150.7 142.4 361.2 141.8 154.7 339.7 132.2 168.5 316.7 121.7 183.7 291.6 116.1 191.9 278.1
150 166.3 158.9 398.4 156.5 172.3 375.0 145.8 187.4 349.4 134.1 203.8 321.2 127.7 212.6 306.0
160 181.5 168.5 434.9 171.0 183.0 409.7 159.6 199.1 382.4 147.0 216.8 352.3 140.2 226.3 335.9
170 194.3 184.5 465.5 182.9 200.1 438.1 170.6 217.5 408.7 157.2 236.7 376.6 149.9 246.8 359.1
50
190 220.0 209.1 526.7 207.2 226.5 496.1 193.4 246.1 463.4 178.3 267.6 427.2 170.2 279.0 407.8
210 231.7 227.2 555.1 218.3 247.0 523.0 203.6 269.0 487.6 187.5 293.3 449.1 178.7 306.2 428.1
225 244.1 240.9 584.4 230.1 261.7 551.3 214.7 284.8 514.5 197.7 310.2 473.5 188.5 323.7 451.6
250 268.8 265.7 643.7 253.5 288.3 607.3 236.8 313.7 567.2 218.3 341.6 523.0 208.2 356.5 498.5
275 295.7 290.1 708.2 278.8 314.7 667.6 260.4 342.2 623.5 240.3 372.5 575.7 229.4 388.6 549.5
300 320.8 314.0 768.2 302.3 340.4 724.1 282.5 370.0 676.4 260.7 402.6 624.4 249.0 420.0 596.5
315 363.0 337.0 869.7 342.0 365.9 819.5 319.2 398.2 764.8 294.0 433.7 704.5 280.3 452.6 671.7
330 375.8 353.0 900.3 353.9 383.0 847.9 330.2 416.6 791.1 304.2 453.5 728.8 290.0 473.1 694.9
345 388.5 369.0 930.9 365.7 400.1 876.3 341.2 435.0 817.5 314.4 473.3 753.2 299.7 493.7 718.2
360 414.3 393.6 992.2 390.1 426.6 934.2 364.0 463.6 872.1 335.5 504.2 803.8 320.1 525.8 766.8
390 440.1 418.3 1053.5 414.4 453.1 992.2 386.7 492.1 926.7 356.6 535.1 854.5 340.4 558.0 815.5
LEGEND NOTE: Ratings are for standard chillers with no options. Some options will have
LCWT Leaving Chilled Water Temperature an effect on unit performance, such as Greenspeed intelligence, coil configura-
tion, etc.
57
Performance data (cont)
30RB PACKAGED AIR-COOLED CHILLER RATINGS TABLE ENGLISH (cont)
CONDENSER ENTERING AIR TEMPERATURE (F)
85 95 105 115 120
LCWT UNIT
(F) SIZE Cooler Cooler Cooler Cooler Cooler
Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate Cap. Input Flow Rate
(Tons) kW (Tons) kW (Tons) kW (Tons) kW (Tons) kW (gpm)
(gpm) (gpm) (gpm) (gpm)
060 73.9 70.1 177.4 69.5 76.0 166.8 64.7 82.7 155.3 59.5 89.9 142.7 56.6 93.7 135.9
070 84.7 79.5 203.2 79.7 86.2 191.1 74.4 93.6 178.4 68.6 101.7 164.8 65.6 106.0 157.4
080 98.9 93.2 237.3 92.8 101.2 222.7 86.2 110.1 206.9 78.9 119.7 189.3 75.0 124.7 179.9
090 111.4 100.1 267.4 104.9 108.1 251.5 97.7 117.0 234.4 90.0 126.6 215.8 85.9 131.7 206.0
100 118.6 108.3 284.7 111.7 116.9 267.9 104.4 126.5 250.5 96.6 137.0 231.7 92.4 142.6 221.6
110 135.7 126.1 325.5 127.6 136.6 306.1 119.1 148.2 285.7 109.7 160.8 263.2 104.6 167.3 251.0
120 150.4 135.7 360.7 141.7 146.9 339.9 132.3 159.4 317.4 122.0 173.0 292.7 116.5 180.2 279.5
130 163.9 146.6 393.2 154.5 158.8 370.7 144.2 172.7 345.9 132.9 188.1 319.0 126.9 196.3 304.4
150 180.9 165.8 434.0 171.1 178.0 410.5 159.8 192.8 383.3 146.2 209.3 350.8 138.9 218.0 333.2
160 198.7 173.4 476.6 186.7 187.9 447.9 173.9 204.0 417.1 160.0 221.9 383.8 152.5 231.4 366.0
170 211.4 191.4 507.1 199.5 206.4 478.3 186.3 223.4 446.8 171.3 242.6 410.9 163.3 252.8 391.7
55
190 240.1 215.4 575.8 226.2 232.9 542.5 211.2 252.5 507.1 194.9 274.2 467.7 186.1 285.7 446.4
210 252.3 235.4 605.4 238.7 254.0 572.6 222.7 276.3 534.3 204.6 300.6 490.7 194.6 313.6 467.0
225 265.9 250.2 637.5 251.5 269.5 603.4 235.0 292.9 563.7 216.7 318.5 519.8 206.2 332.1 494.5
250 293.1 274.8 703.1 276.9 296.7 664.1 258.8 322.3 620.9 233.3 348.1 559.4 227.5 365.3 545.9
275 322.6 299.7 773.6 304.5 323.6 730.3 284.6 351.3 682.7 262.5 381.7 629.8 250.5 397.9 600.7
300 350.2 323.2 840.1 330.2 349.8 792.0 308.6 379.5 740.2 285.1 412.4 683.5 272.3 429.8 652.8
315 397.5 346.8 953.2 373.4 375.7 895.9 347.7 408.1 834.2 320.0 443.7 767.7 305.1 462.8 732.0
330 410.1 364.8 983.7 386.2 394.3 926.3 360.1 427.4 863.9 331.3 464.4 794.8 315.8 484.2 757.7
345 422.8 382.8 1014.3 398.9 412.9 956.7 372.5 446.8 893.7 342.6 485.2 821.9 326.6 505.6 783.4
360 451.5 406.8 1083.0 425.7 439.3 1020.8 397.5 475.9 953.9 366.2 516.7 878.7 349.4 538.4 838.1
390 480.3 430.8 1151.6 452.5 465.8 1084.9 422.5 505.1 1014.2 389.8 548.3 935.5 372.1 571.3 892.8
LEGEND NOTE: Ratings are for standard chillers with no options. Some options will have
LCWT Leaving Chilled Water Temperature an effect on unit performance, such as Greenspeed intelligence, coil configura-
tion, etc.
58
30RB PACKAGED AIR-COOLED CHILLER RATINGS TABLE SI
CONDENSER ENTERING AIR TEMPERATURE (C)
LCWT UNIT 30.0 35.0 40.0 45.0 50.0
(C) SIZE Cooler Cooler Cooler Cooler Cooler
Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Rate Flow Rate Flow Rate Flow Rate Flow Rate
(kW) kW (L/s) (kW) kW (L/s) (kW) kW (L/s) (kW) kW (L/s) (kW) kW (L/s)
060 200.5 64.3 8.6 188.7 69.5 8.1 175.7 75.4 7.5 161.7 81.8 6.9 147.0 89.0 6.3
070 233.5 73.3 10.0 220.6 79.2 9.5 207.0 85.8 8.9 192.4 93.1 8.3 176.5 100.9 7.6
080 266.0 84.5 11.4 249.7 91.6 10.7 232.4 99.4 10.0 213.9 108.0 9.2 193.8 117.4 8.3
090 304.5 92.0 13.1 287.7 99.3 12.3 269.6 107.4 11.6 250.0 116.3 10.7 228.8 126.0 9.8
100 327.4 100.2 14.0 309.7 108.2 13.3 291.1 117.0 12.5 271.1 126.6 11.6 249.3 137.0 10.7
110 374.0 114.5 16.0 352.9 124.0 15.1 330.6 134.6 14.2 306.8 146.3 13.1 281.1 159.1 12.1
120 416.1 125.8 17.8 393.5 135.9 16.9 369.4 147.1 15.8 343.2 159.3 14.7 314.6 172.4 13.5
130 449.0 137.2 19.2 424.2 148.2 18.2 397.8 160.3 17.1 369.3 173.6 15.8 337.7 188.0 14.5
150 493.2 152.0 21.1 466.1 164.0 20.0 437.0 177.2 18.7 405.5 191.7 17.4 370.8 207.2 15.9
160 535.7 162.1 23.0 506.8 175.0 21.7 475.7 189.3 20.4 442.1 205.0 18.9 405.4 222.0 17.4
170 576.6 177.0 24.7 545.6 191.0 23.4 511.9 206.5 21.9 475.5 223.3 20.4 435.7 241.6 18.7
5.0
190 654.1 200.9 28.0 619.3 216.7 26.5 582.0 234.2 24.9 542.0 253.4 23.2 497.7 274.1 21.3
210 687.2 218.3 29.5 650.2 235.8 27.9 610.2 255.2 26.2 566.7 276.4 24.3 518.7 299.4 22.2
225 725.5 230.9 31.1 686.6 249.3 29.4 644.6 269.7 27.6 598.9 291.9 25.7 548.4 315.8 23.5
250 800.8 255.1 34.3 757.9 275.4 32.5 711.6 297.7 30.5 661.4 322.1 28.3 606.0 348.5 26.0
275 881.8 279.1 37.8 835.4 301.2 35.8 785.6 325.8 33.7 730.9 352.6 31.3 671.0 381.6 28.8
300 956.5 302.4 41.0 906.2 326.2 38.8 852.2 352.7 36.5 793.9 381.6 34.0 729.0 412.9 31.2
315 1071.5 324.3 45.9 1013.7 350.1 43.4 951.4 378.7 40.8 884.2 410.0 37.9 810.7 444.1 34.7
330 1112.3 339.1 47.7 1052.4 366.0 45.1 987.6 395.8 42.3 917.6 428.3 39.3 841.1 463.6 36.0
345 1153.2 354.0 49.4 1091.2 382.0 46.8 1023.8 412.9 43.9 951.0 446.7 40.8 871.4 483.1 37.4
360 1230.7 377.9 52.7 1164.9 407.7 49.9 1093.9 440.7 46.9 1017.5 476.7 43.6 933.4 515.7 40.0
390 1308.2 401.9 56.1 1238.5 433.4 53.1 1164.1 468.5 49.9 1084.0 506.8 46.5 995.3 548.2 42.7
060 207.6 64.9 8.9 195.9 70.1 8.4 183.2 76.0 7.9 169.6 82.6 7.3 154.8 89.7 6.6
070 241.1 74.0 10.3 227.9 79.9 9.8 213.9 86.6 9.2 199.0 93.8 8.5 182.6 101.7 7.8
080 277.3 85.6 11.9 260.5 92.7 11.2 242.7 100.6 10.4 223.4 109.2 9.6 202.5 118.6 8.7
090 315.2 92.9 13.5 298.1 100.0 12.8 279.8 108.2 12.0 259.9 117.2 11.1 238.1 126.9 10.2
100 337.9 101.1 14.5 319.7 109.0 13.7 300.5 117.8 12.9 280.1 127.5 12.0 257.6 137.9 11.0
110 386.3 115.5 16.6 364.8 125.0 15.6 341.8 135.6 14.7 317.3 147.4 13.6 290.8 160.2 12.5
120 429.4 126.9 18.4 406.3 137.0 17.4 381.6 148.2 16.4 354.8 160.4 15.2 325.4 173.6 14.0
130 463.9 138.4 19.9 438.4 149.4 18.8 411.3 161.6 17.6 382.0 174.9 16.4 349.6 189.4 15.0
150 509.5 153.5 21.9 481.6 165.5 20.7 451.7 178.8 19.4 419.3 193.3 18.0 383.7 208.9 16.5
160 554.8 163.6 23.8 525.1 176.5 22.5 492.9 190.8 21.1 458.1 206.5 19.6 420.1 223.6 18.0
170 596.3 178.7 25.6 564.3 192.6 24.2 529.8 208.2 22.7 492.3 225.1 21.1 451.1 243.4 19.3
6.0
190 676.5 202.8 29.0 640.2 218.4 27.5 601.8 235.9 25.8 560.4 255.2 24.0 514.9 275.9 22.1
210 710.4 220.3 30.5 672.4 237.9 28.8 631.2 257.3 27.1 586.5 278.6 25.2 537.0 301.7 23.0
225 749.6 233.1 32.2 709.6 251.6 30.4 666.4 272.0 28.6 619.4 294.3 26.6 567.4 318.3 24.3
250 827.0 257.4 35.5 783.4 277.8 33.6 735.7 300.2 31.5 684.0 324.7 29.3 627.0 351.1 26.9
275 910.3 281.4 39.0 862.6 303.6 37.0 811.4 328.2 34.8 755.4 355.1 32.4 693.7 384.2 29.8
300 987.6 304.8 42.3 935.8 328.7 40.1 880.3 355.2 37.8 820.3 384.2 35.2 753.8 415.7 32.3
315 1109.6 327.2 47.6 1050.2 352.9 45.0 985.8 381.6 42.3 916.3 413.0 39.3 840.3 447.1 36.0
330 1151.1 342.3 49.4 1089.4 369.1 46.7 1022.7 398.9 43.9 950.4 431.6 40.8 871.3 466.9 37.3
345 1192.7 357.4 51.2 1128.6 385.3 48.4 1059.7 416.3 45.4 984.5 450.2 42.2 902.3 486.7 38.7
360 1272.9 381.5 54.6 1204.5 411.1 51.7 1131.6 444.1 48.5 1052.7 480.2 45.1 966.1 519.3 41.4
390 1353.1 405.6 58.0 1280.5 436.8 54.9 1203.5 471.9 51.6 1120.9 510.3 48.1 1029.9 551.9 44.2
060 214.9 65.7 9.2 203.0 70.9 8.7 190.1 76.6 8.2 175.9 83.2 7.5 160.6 90.4 6.9
070 248.8 74.7 10.7 235.3 80.6 10.1 220.9 87.3 9.5 205.5 94.6 8.8 188.8 102.5 8.1
080 287.7 86.6 12.3 270.5 93.8 11.6 252.2 101.7 10.8 232.5 110.4 10.0 211.0 119.8 9.1
090 325.5 93.8 14.0 308.0 101.0 13.2 289.3 108.9 12.4 268.9 117.9 11.5 246.5 127.7 10.6
100 348.6 101.9 15.0 329.9 109.8 14.2 310.2 118.7 13.3 289.1 128.4 12.4 266.2 138.9 11.4
110 398.5 116.7 17.1 376.8 126.1 16.2 353.2 136.7 15.2 328.0 148.5 14.1 300.7 161.3 12.9
120 442.9 128.3 19.0 419.3 138.2 18.0 394.1 149.3 16.9 366.7 161.6 15.7 336.4 174.9 14.4
130 479.2 139.6 20.6 452.9 150.7 19.4 425.0 162.9 18.2 394.9 176.3 17.0 361.8 190.8 15.5
150 526.7 155.1 22.6 498.0 167.1 21.4 467.1 180.4 20.0 433.6 194.9 18.6 396.9 210.6 17.0
160 574.1 165.1 24.6 543.7 178.0 23.3 510.4 192.3 21.9 474.5 208.0 20.4 435.3 225.1 18.7
170 616.5 180.4 26.5 583.4 194.4 25.0 548.0 209.9 23.5 509.3 226.9 21.8 466.9 245.2 20.0
7.0
190 699.2 204.7 30.0 661.8 220.4 28.4 621.9 237.7 26.7 579.3 256.9 24.9 532.6 277.8 22.9
210 734.2 222.3 31.5 695.0 240.0 29.8 652.7 259.5 28.0 606.6 280.9 26.0 555.7 304.0 23.8
225 774.3 235.4 33.2 733.0 253.9 31.4 688.6 274.4 29.6 640.2 296.8 27.5 586.7 320.9 25.2
250 853.8 259.9 36.6 809.1 280.2 34.7 760.3 302.7 32.6 707.0 327.3 30.3 648.3 353.8 27.8
275 939.9 284.0 40.3 890.6 306.1 38.2 837.7 330.7 35.9 780.5 357.7 33.5 716.8 386.8 30.7
300 1019.6 307.6 43.7 966.1 331.3 41.5 908.9 357.8 39.0 847.1 386.9 36.4 779.1 418.4 33.4
315 1148.1 330.2 49.3 1087.4 356.1 46.7 1020.8 384.6 43.8 949.1 416.0 40.7 870.6 450.3 37.3
330 1190.5 345.5 51.1 1127.1 372.4 48.4 1058.4 402.2 45.4 983.9 434.9 42.2 902.2 470.3 38.7
345 1233.0 360.8 52.9 1166.8 388.8 50.1 1096.0 419.8 47.0 1018.6 453.7 43.7 933.8 490.4 40.0
360 1315.7 385.1 56.5 1245.3 414.8 53.4 1169.9 447.6 50.2 1088.6 483.8 46.7 999.5 523.0 42.9
390 1398.5 409.4 60.0 1323.7 440.8 56.8 1243.7 475.4 53.4 1158.5 513.9 49.7 1065.2 555.6 45.7
LEGEND NOTE: Ratings are for standard chillers with no options. Some options will have
LCWT Leaving Chilled Water Temperature an effect on unit performance, such as Greenspeed intelligence, coil configura-
tion, etc.
59
Performance data (cont)
30RB PACKAGED AIR-COOLED CHILLER RATINGS TABLE SI (cont)
CONDENSER ENTERING AIR TEMPERATURE (C)
30.0 35.0 40.0 45.0 50.0
LCWT UNIT
(C) SIZE Cooler Cooler Cooler Cooler Cooler
Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Rate Flow Rate Flow Rate Flow Rate
(kW) kW (kW) kW (kW) kW (kW) kW (kW) kW
Rate (L/s) (L/s) (L/s) (L/s) (L/s)
060 222.5 66.5 9.6 210.2 71.7 9.0 197.1 77.5 8.5 182.7 83.8 7.9 166.8 91.0 7.2
070 256.6 75.5 11.0 242.7 81.4 10.4 228.0 88.1 9.8 212.2 95.4 9.1 195.1 103.3 8.4
080 298.3 87.7 12.8 280.9 94.9 12.1 261.9 102.8 11.2 241.4 111.5 10.4 219.2 121.0 9.4
090 336.5 94.9 14.5 318.3 102.0 13.7 299.1 110.0 12.8 278.4 118.7 12.0 255.3 128.5 11.0
100 359.5 102.8 15.4 340.3 110.7 14.6 320.0 119.6 13.7 298.4 129.3 12.8 274.9 139.8 11.8
110 411.0 118.4 17.6 388.7 127.5 16.7 364.9 137.9 15.7 338.9 149.6 14.6 310.8 162.4 13.3
120 456.6 129.6 19.6 432.3 139.6 18.6 406.6 150.6 17.5 378.7 162.8 16.3 347.7 176.1 14.9
130 494.7 140.9 21.2 467.8 152.0 20.1 439.1 164.2 18.9 408.2 177.7 17.5 374.3 192.3 16.1
150 544.6 156.7 23.4 515.0 168.8 22.1 483.2 182.2 20.7 448.7 196.7 19.3 410.8 212.4 17.6
160 593.6 166.6 25.5 562.3 179.6 24.1 528.3 193.9 22.7 491.2 209.6 21.1 450.7 226.7 19.3
170 636.8 182.2 27.3 602.7 196.2 25.9 566.3 211.7 24.3 526.6 228.7 22.6 483.0 247.1 20.7
8.0
190 722.0 206.7 31.0 683.5 222.4 29.4 642.4 239.7 27.6 598.1 258.7 25.7 550.2 279.7 23.6
210 758.9 224.5 32.6 718.5 242.2 30.8 675.0 261.8 29.0 627.5 283.3 26.9 575.1 306.5 24.7
225 800.2 237.8 34.4 757.8 256.4 32.5 712.0 277.0 30.6 662.1 299.4 28.4 607.0 323.6 26.1
250 881.7 262.4 37.9 835.7 282.8 35.9 786.0 305.4 33.7 731.1 330.0 31.4 670.7 356.6 28.8
275 970.3 286.7 41.7 919.5 308.8 39.5 864.9 333.3 37.1 806.0 360.3 34.6 740.7 389.6 31.8
300 1052.4 310.4 45.2 997.3 334.2 42.8 938.3 360.6 40.3 874.7 389.6 37.6 804.9 421.3 34.6
315 1187.3 333.3 51.0 1124.7 359.2 48.3 1056.7 387.9 45.4 982.4 419.2 42.2 901.4 453.5 38.7
330 1230.4 348.8 52.8 1165.1 375.8 50.0 1094.6 405.7 47.0 1017.8 438.2 43.7 933.7 473.8 40.1
345 1273.6 364.4 54.7 1205.5 392.5 51.8 1132.5 423.5 48.6 1053.3 457.3 45.2 965.9 494.1 41.4
360 1358.7 388.9 58.3 1286.2 418.6 55.2 1208.6 451.5 51.9 1124.7 487.4 48.3 1033.2 526.7 44.3
390 1443.9 413.3 62.0 1367.0 444.7 58.7 1284.7 479.5 55.2 1196.2 517.5 51.4 1100.4 559.4 47.2
060 237.4 68.2 10.2 224.3 73.5 9.6 210.5 79.3 9.1 195.7 85.6 8.4 179.5 92.5 7.7
070 272.7 77.4 11.7 258.0 83.3 11.1 242.5 89.9 10.4 225.9 97.0 9.7 208.0 105.0 8.9
080 318.1 90.2 13.7 300.3 97.4 12.9 281.2 105.2 12.1 259.9 114.0 11.2 236.3 123.5 10.2
090 358.1 97.3 15.4 339.0 104.5 14.6 318.6 112.3 13.7 296.9 120.9 12.8 273.2 130.4 11.7
100 382.0 105.3 16.4 361.8 113.0 15.6 340.5 121.5 14.6 317.5 131.2 13.7 292.7 141.8 12.6
110 437.0 121.9 18.8 413.3 131.2 17.8 388.2 141.3 16.7 361.2 152.3 15.5 331.7 164.9 14.3
120 484.8 132.5 20.8 459.2 142.5 19.7 432.0 153.6 18.6 402.9 165.7 17.3 371.0 178.7 16.0
130 527.1 143.6 22.7 498.6 154.7 21.4 468.3 167.1 20.1 435.6 180.6 18.7 399.9 195.2 17.2
150 581.5 160.2 25.0 550.5 172.3 23.7 516.8 185.8 22.2 480.1 200.4 20.6 439.8 216.2 18.9
160 634.7 169.9 27.3 601.4 183.0 25.9 565.5 197.4 24.3 526.3 213.2 22.6 482.9 230.2 20.8
170 679.3 186.0 29.2 643.1 200.1 27.6 604.4 215.7 26.0 562.6 232.7 24.2 516.2 251.0 22.2
10.0
190 769.5 210.8 33.1 728.7 226.5 31.3 685.1 244.0 29.5 638.1 263.1 27.4 586.6 283.7 25.2
210 810.3 229.1 34.8 767.7 247.0 33.0 721.4 266.7 31.0 671.1 288.2 28.8 615.5 311.5 26.5
225 853.7 242.9 36.7 809.3 261.7 34.8 760.8 282.4 32.7 707.8 304.9 30.4 649.2 329.2 27.9
250 940.3 267.8 40.4 891.4 288.3 38.3 838.7 311.1 36.1 781.4 335.9 33.6 717.2 362.5 30.8
275 1034.3 292.5 44.4 980.4 314.7 42.1 922.5 339.3 39.6 859.8 366.2 37.0 790.6 395.3 34.0
300 1121.8 316.5 48.2 1063.3 340.4 45.7 1000.6 366.9 43.0 932.8 395.8 40.1 858.3 427.2 36.9
315 1269.5 339.8 54.6 1202.9 365.9 51.7 1131.0 394.8 48.6 1052.6 426.3 45.2 965.9 460.4 41.5
330 1314.0 355.9 56.5 1244.6 383.0 53.5 1169.9 413.1 50.3 1088.9 445.9 46.8 999.2 481.2 42.9
345 1358.6 372.0 58.4 1286.3 400.1 55.3 1208.8 431.4 52.0 1125.1 465.4 48.4 1032.5 502.0 44.3
360 1448.8 396.8 62.3 1371.8 426.6 58.9 1289.5 459.7 55.4 1200.7 495.8 51.6 1102.8 534.7 47.4
390 1539.0 421.6 66.1 1457.3 453.1 62.6 1370.2 488.0 58.9 1276.2 526.2 54.9 1173.2 567.4 50.4
LEGEND NOTE: Ratings are for standard chillers with no options. Some options will have
LCWT Leaving Chilled Water Temperature an effect on unit performance, such as Greenspeed intelligence, coil configura-
tion, etc.
60
Typical piping and wiring
30RB UNITS WITHOUT HYDRONIC PACKAGE
AIR FLOW
LEGEND
FIELD
POWER
SUPPLY Airflow Through Condenser
Power Wiring
Chilled Water Piping
NOTES:
1. Chiller must be installed level
to maintain proper compres-
TO sor oil return.
EXPANSION 2. Piping shown are general
TANK points-of-connection guides
only and are not intended for a
specific installation. Wiring and
piping shown are for a quick
overview of system and are not
in accordance with recognized
standards.
3. All wiring must comply with
applicable local and national
VALVE VIBRATION codes.
PRESSURE ELIMINATOR 4. All piping must follow standard
GAGE STRAINER piping techniques. Refer to
SEE NOTE 5 Carrier System Design Manual
or appropriate ASHRAE
GATE (American Society of Heating,
VALVE Refrigerating, and Air-Condi-
tioning Engineers) handbook
for details.
5. A 20-mesh strainer must be
field-supplied and installed
within 10 ft (3 m) of the cooler
SHUT OFF FLOW inlet.
VALVES BALANCING VALVE
PUMP
DRAIN
a30-4373
LEGEND
Power Wiring
Chilled Water Piping
NOTES:
1. Chiller must be installed level to
maintain proper compressor oil
return.
2. Wiring and piping shown are gen-
eral points-of-connection guides
only and are not intended for a spe-
cific installation. Wiring and piping
shown are for a quick overview of
system and are not in accordance
with recognized standards.
3. All wiring must comply with applica-
ble local and national codes.
4. All piping must follow standard pip-
ing techniques. Refer to Carrier
System Design Manual or appropri-
ate ASHRAE (American Society of
STRAINER Heating, Refrigerating, and Air-Con-
SEE NOTE 6 ditioning Engineers) handbook for
details.
5. Air separator required as close to
chiller as possible (except primary/
secondary systems).
6. Additional 20 mesh strainer required
for open loop systems.
COMBINATION 7. A field-installed expansion tank is
VALVE required.
a30-4374
61
Typical piping and wiring (cont)
30RB UNITS WITH HEAT RECLAIM OPTION SIZES 060-110
LEGEND
Power Wiring
Chilled Water Piping
NOTES:
1. Chiller must be installed level to
maintain proper compressor oil
return.
2. Piping shown are general points-
of-connection guides only and are
not intended for a specific installa-
tion. Wiring and piping shown are
for a quick overview of system and
are not in accordance with recog-
nized standards.
3. All wiring must comply with appli-
cable local and national codes.
4. All piping must follow standard pip-
ing techniques. Refer to Carrier
System Design Manual or appro-
priate ASHRAE (American Soci-
ety of Heating, Refrigerating, and
Air-Conditioning Engineers) hand-
book for details.
STRAINER
(20 MESH)
RETURN
STRAINER
(20 MESH)
a30-4731
Power Wiring
Chilled Water Piping
NOTES:
1. Chiller must be installed level
to maintain proper compres-
sor oil return.
2. Wiring and piping shown are
general points-of-connection
guides only and are not
intended for a specific instal-
lation. Wiring and piping
shown are for a quick over-
view of system and are not in
accordance with recognized
standards.
3. All wiring must comply with
applicable local and national
codes.
4. All piping must follow stan-
dard piping techniques. Refer
to Carrier System Design
Manual or appropriate
ASHRAE (American Society
of Heating, Refrigerating, and
Air-Conditioning Engineers)
handbook for details.
STRAINER
(20 MESH)
a30-4730
62
TYPICAL PIPING DIAGRAM FOR 30RB UNITS WITHOUT HYDRONIC PACKAGE
D V
Heater (Optional)
T1 FS PP PP T2
LEGEND
D Drain, 3/4-in. NPT
FS Flow Switch
PP Pipe Plug, 1/4-in. NPT
T1 Leaving Water Thermistor Chilled Water Chilled Water
T2 Entering Water Thermistor Out In
V Vent, 1/4-in. NPT a30-5302
D V
Heater (Optional)
T1 FS PP PP T2
LEGEND
D Drain, 3/4-in. NPT
D Drain, 1/4-in. NPT Strainer/Suction Guide
E Expansion Tank Connection, 3/4-in. NPT
FS Flow Switch
PP Pipe Plug, 1/4-in. NPT
PT Pressure/Temperature Tap Chilled
T1 Leaving Water Thermistor Water In
T2 Entering Water Thermistor Pump
V Vent, 1/4-in. NPT
Indicates items provided with the
optional hydronic pump package. Combination Valve
*Field-supplied and installed.
The strainer supplied with the optional hydronic Pressure Relief*
pump package is 1/8 in. perforated. Isolation Valve*
**Required for open loop systems.
Flexible Connections*
20 Mesh Strainer**
Pressure Reducing
Fill Valve* a30-5303
63
Typical piping and wiring (cont)
D V
Heater (Optional)
T1 FS PP PP T2
Heater
Strainer/Suction Guide
LEGEND
D Drain, 3/4-in. NPT
D Drain, 1/4-in. NPT Reverse Flow Check
E Expansion Tank Connection, 3/4-in. NPT Valve/Service Valve
FS Flow Switch
PP Pipe Plug, 1/4-in. NPT Service Valve
PT Pressure/Temperature Tap
T1 Leaving Water Thermistor
T2 Entering Water Thermistor Pump
V Vent, 1/4-in. NPT
Indicates items provided with the
optional hydronic pump package. Combination Valve
*Field-supplied and installed. Pressure Relief*
The strainer supplied with the optional hydronic
pump package is 1/8 in. perforated.
**Required for open loop systems. Flexible Connections* Isolation Valve*
Pressure Reducing
Fill Valve* 20 Mesh Strainer**
64
TYPICAL PIPING DIAGRAM FOR 30RB UNITS WITH HEAT RECLAIM OPTION
V T1 FS PP
Flexible Connections*
HEAT
RECLAIM
RETURN Pump*
Isolation Valve*
65
Electrical data
30RB060-190 ELECTRICAL DATA SINGLE POINT UNITS
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
UNIT SIZE Supplied MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse
V-Hz (3 Ph)
Min Max XL XL XL Size XL XL XL Size XL XL XL Size
208/230-60 187 253 291.5 350 682.8 350 300.6 350 693.6 350 306.9 350 700.5 350
380-60 342 418 150.9 175 362.9 175 156.0 175 368.8 175 159.0 175 372.6 175
060 460-60 414 506 127.9 150 302.0 150 132.1 150 306.9 150 135.0 150 310.0 150
575-60 518 633 102.4 125 244.7 110 105.7 125 248.6 125 107.8 125 251.1 125
208/230-60 187 253 334.7 400 777.0 400 343.8 400 787.8 400 350.1 400 794.7 400
380-60 342 418 175.5 200 428.8 200 180.8 225 434.7 200 183.6 225 438.5 200
070 460-60 414 506 147.9 175 355.9 175 152.1 175 360.8 175 155.0 175 363.9 175
575-60 518 633 119.8 150 287.4 150 123.1 150 291.3 150 125.2 150 293.8 150
208/230-60 187 253 366.5 400 757.8 400 381.9 450 775.5 450
380-60 342 418 189.3 225 401.3 200 197.4 225 411.0 225
080 460-60 414 506 160.6 175 334.7 175 167.7 200 342.7 200
575-60 518 633 128.6 150 270.9 150 134.0 150 277.3 150
208/230-60 187 253 433.6 500 875.9 500 449.0 500 893.6 500
380-60 342 418 226.9 250 480.3 250 235.0 250 490.0 250
090 460-60 414 506 191.4 225 399.4 225 198.5 225 407.4 225
575-60 518 633 154.6 175 322.2 175 160.0 175 328.6 175
208/230-60 187 253 472.0 500 914.3 500 487.4 500 932.0 500
380-60 342 418 248.7 250 502.1 250 256.8 300 511.8 300
100 460-60 414 506 209.2 250 417.2 225 216.3 250 425.2 250
575-60 518 633 170.0 200 337.6 200 175.4 200 344.0 200
208/230-60 187 253 508.6 600 950.9 600 524.0 600 968.6 600
380-60 342 418 265.3 300 518.7 300 273.4 300 528.4 300
110 460-60 414 506 224.1 250 432.1 250 231.2 250 440.1 250
575-60 518 633 180.8 200 348.4 200 186.2 200 354.8 200
208/230-60 187 253 578.1 600 1020.4 600 593.5 600 1038.1 700
380-60 342 418 304.6 350 538.0 350 312.7 350 567.6 350
120 460-60 414 506 256.2 300 464.2 300 263.3 300 472.2 300
575-60 518 633 208.2 225 325.8 225 213.6 225 382.2 225
208/230-60 187 253 626.7 700 1068.9 700 642.1 700 1086.6 700
380-60 342 418 327.7 350 581.1 350 335.8 350 590.8 350
130 460-60 414 506 276.5 300 484.5 300 283.6 300 492.5 300
575-60 518 633 223.3 250 391.0 250 228.7 250 397.4 250
208/230-60 187 253 684.3 700 1126.5 700 699.7 700 1144.2 800
380-60 342 418 360.4 400 613.8 400 368.5 400 623.5 400
150 460-60 414 506 303.2 350 511.2 350 310.3 350 519.2 350
575-60 518 633 246.4 250 414.1 250 251.8 300 420.5 300
208/230-60 187 253 744.8 800 1187.0 800 760.2 800 1204.7 800
380-60 342 418 390.1 400 643.5 400 398.2 400 653.2 400
160 460-60 414 506 328.9 350 536.9 350 336.0 350 544.9 350
575-60 518 633 265.9 300 433.5 300 271.3 300 439.9 300
208/230-60 187 253 802.4 1000 1244.6 1000 817.8 1000 1262.3 1000
380-60 342 418 422.8 450 676.2 450 430.9 450 685.9 450
170 460-60 414 506 355.6 400 563.6 400 362.7 400 571.6 400
575-60 518 633 289.0 300 456.6 300 294.4 300 463.0 300
208/230-60 187 253 920.5 1000 1362.7 1000 935.9 1000 1380.4 1000
380-60 342 418 485.2 500 738.5 500 493.3 500 748.2 500
190 460-60 414 506 408.0 450 616.0 450 415.1 450 624.0 450
575-60 518 633 331.5 350 499.1 350 336.9 350 505.5 350
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
MCA Minimum Circuit Amps XL Across-the-Line Start 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
NOTES: 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 1/0 to 500 kcmil.
is not below or above the listed minimum and maximum limits. Maximum allowable phase d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
imbalance is: voltage, 2%; amps 10%. 250 kcmil to 500 kcmil.
2. All units or modules have single point primary power connection. (Each unit or module 6. Hydronic pump packages are not available as a factory-installed option for units
requires its own power supply.) Main power must be supplied from a field-supplied 30RB210-390 and 30RB060-190 with high SCCR option.
disconnect.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
3. Cooler heater is wired into the control circuit so it is always operable as long as the power pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
supply disconnect is on, even if any safety device is open. cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
66
30RB060-190 ELECTRICAL DATA SINGLE POINT UNITS (cont)
UNIT VOLTAGE 7.5 HP PUMP, 1750/3450 RPM 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM
UNIT SIZE Supplied MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse
V-Hz (3 Ph)
Min Max XL XL XL Size XL XL XL Size XL XL XL Size
208/230-60 187 253 313.5 350 708.5 350 316.5 350 716.4 350
380-60 342 418 163.2 200 376.9 175 164.9 200 381.3 175
060 460-60 414 506 138.0 150 313.6 150 139.4 150 317.2 150
575-60 518 633 110.5 125 254.0 125 111.6 125 256.9 125
208/230-60 187 253 356.7 450 802.7 400 359.7 450 810.6 400
380-60 342 418 187.8 225 442.8 225 189.5 225 447.2 225
070 460-60 414 506 158.0 175 367.5 175 159.4 200 371.1 175
575-60 518 633 127.9 150 296.7 150 129.0 150 299.6 150
208/230-60 187 253 388.5 450 783.5 450 391.5 450 791.4 450 403.2 450 807.6 450
380-60 342 418 201.6 225 415.3 225 203.3 225 419.7 225 210.3 225 428.5 225
080 460-60 414 506 170.7 200 346.3 200 172.1 200 349.9 200 177.6 200 357.2 200
575-60 518 633 136.7 150 280.2 150 137.8 150 283.1 150 142.6 150 288.9 150
208/230-60 187 253 455.6 500 901.6 500 458.6 500 909.5 500 470.3 500 925.7 500
380-60 342 418 239.2 250 494.3 250 240.9 250 498.7 250 247.9 250 507.5 300
090 460-60 414 506 201.5 225 411.0 225 202.9 225 414.6 225 208.4 250 421.9 225
575-60 518 633 162.7 175 331.5 175 163.8 175 334.4 175 168.6 200 340.2 200
208/230-60 187 253 494.0 500 940.0 500 497.0 500 947.9 600 508.7 600 964.1 600
380-60 342 418 261.0 300 516.1 300 262.7 300 520.5 300 269.7 300 529.3 300
100 460-60 414 506 219.3 250 428.8 250 220.7 250 432.4 250 226.2 250 439.7 250
575-60 518 633 178.1 200 346.9 200 179.2 200 349.8 200 184.0 200 355.6 200
208/230-60 187 253 530.6 600 976.6 600 533.6 600 984.5 600 545.3 600 1000.7 600
380-60 342 418 277.6 300 532.7 300 279.3 300 537.1 300 286.3 300 545.9 300
110 460-60 414 506 234.2 250 443.7 250 235.6 250 447.3 250 241.1 250 454.6 250
575-60 518 633 188.9 200 357.7 200 190.0 200 360.6 200 194.8 225 366.4 225
208/230-60 187 253 600.1 700 1046.1 700 603.1 700 1054.0 700 614.8 700 1070.2 700
380-60 342 418 316.9 350 572.0 350 318.6 350 576.4 350 325.6 350 585.2 350
120 460-60 414 506 266.3 300 425.8 300 267.7 300 479.4 300 273.2 300 486.7 300
575-60 518 633 216.3 225 385.1 250 217.4 250 392.4 250 222.2 250 393.8 250
208/230-60 187 253 648.7 700 1094.6 700 651.7 700 1102.5 700 663.4 700 1118.7 700
380-60 342 418 340.0 350 595.1 350 341.7 350 599.5 350 348.7 350 608.3 400
130 460-60 414 506 286.6 300 496.1 300 288.0 300 499.7 300 293.5 300 507.0 300
575-60 518 633 231.4 250 400.3 250 232.5 250 403.2 250 237.3 250 409.0 250
208/230-60 187 253 706.3 800 1152.2 800 709.3 800 1160.1 800 721.0 800 1176.3 800
380-60 342 418 372.7 400 627.8 400 374.4 400 632.2 400 381.4 400 641.0 400
150 460-60 414 506 313.3 350 522.8 350 314.7 350 526.4 350 320.2 350 533.7 350
575-60 518 633 254.5 300 423.4 300 255.6 300 426.3 300 260.4 300 432.1 300
208/230-60 187 253 766.8 800 1212.7 800 769.8 800 1220.6 800 781.5 800 1236.8 800
380-60 342 418 402.4 450 657.5 450 404.1 450 661.9 450 411.1 450 670.7 450
160 460-60 414 506 339.0 350 548.5 350 340.4 350 552.1 350 345.9 350 559.4 400
575-60 518 633 274.0 300 442.8 300 275.1 300 445.7 300 279.9 300 451.5 300
208/230-60 187 253 824.4 1000 1270.3 1000 827.4 1000 1278.2 1000 839.1 1000 1294.4 1000
380-60 342 418 435.1 450 690.2 450 436.8 450 694.6 450 443.8 450 703.4 500
170 460-60 414 506 365.7 400 575.2 400 367.1 400 578.8 400 372.6 400 586.1 400
575-60 518 633 297.1 300 465.9 300 298.2 300 468.8 350 303.0 350 474.6 350
208/230-60 187 253 942.5 1000 1388.4 1000 945.5 1000 1396.3 1000 957.2 1000 1412.5 1000
380-60 342 418 497.5 500 752.5 500 499.2 500 756.9 600 506.2 600 765.7 600
190 460-60 414 506 418.1 450 627.6 450 419.5 450 631.2 450 425.0 450 638.5 450
575-60 518 633 339.6 350 508.4 350 340.7 350 511.3 350 345.5 350 517.1 350
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
MCA Minimum Circuit Amps XL Across-the-Line Start 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
NOTES: 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 1/0 to 500 kcmil.
is not below or above the listed minimum and maximum limits. Maximum allowable phase d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
imbalance is: voltage, 2%; amps 10%. 250 kcmil to 500 kcmil.
2. All units and modules have single point primary power connection. (Each unit or module 6. Hydronic pump packages are not available as a factory-installed option for units
requires its own power supply.) Main power must be supplied from a field-supplied 30RB210-390 and 30RB060-190 with high SCCR option.
disconnect.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
3. Cooler heater is wired into the control circuit so it is always operable as long as the power pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
supply disconnect is on, even if any safety device is open. cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
67
Electrical data (cont)
30RB210-390 ELECTRICAL DATA SINGLE POINT UNITS
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
UNIT SIZE Supplied MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse MCA MOCP ICF Rec Fuse
V-Hz (3 Ph)
Min Max XL XL XL Size XL XL XL Size XL XL XL Size
208/230-60 187 253
380-60 342 418 501.8 600 755.1 600
210 460-60 414 506 422.9 450 630.9 450
575-60 518 633 342.3 350 509.9 350
208/230-60 187 253
380-60 342 418 534.5 600 787.8 600
225 460-60 414 506 449.6 450 657.6 450
575-60 518 633 365.4 400 533.0 400
208/230-60 187 253
380-60 342 418 596.8 600 850.2 600
250 460-60 414 506 502.0 600 710.0 600
575-60 518 633 408.0 450 575.6 450
208/230-60 187 253
380-60 342 418 659.2 700 912.6 700
275 460-60 414 506 554.4 600 762.4 600
575-60 518 633 450.5 500 618.1 500
208/230-60 187 253
380-60 342 418 721.6 800 975.0 800
300 460-60 414 506 606.8 700 814.8 700
575-60 518 633 493.0 500 660.7 500
208/230-60 187 253 744.8 800 1187.0 800
380-60 342 418 390.1 400 643.5 400
315A 460-60 414 506 328.9 350 536.9 350
575-60 518 633 265.9 300 433.5 300
208/230-60 187 253 744.8 800 1187.0 800
315B 380-60 342 418 390.1 400 643.5 400
460-60 414 506 328.9 350 536.9 350
575-60 518 633 265.9 300 433.5 300
208/230-60 187 253 802.4 1000 1244.6 1000
380-60 342 418 422.8 450 676.2 450
330A 460-60 414 506 355.6 400 563.6 400
575-60 518 633 289.0 300 456.6 300
208/230-60 187 253 744.8 800 1187.0 800
330B 380-60 342 418 390.1 400 643.5 400
460-60 414 506 328.9 350 536.9 350
575-60 518 633 265.9 300 433.5 300
208/230-60 187 253 802.4 1000 1244.6 1000
380-60 342 418 422.8 450 676.2 450
345A 460-60 414 506 355.6 400 563.6 400
575-60 518 633 289.0 300 456.6 300
208/230-60 187 253 802.4 1000 1244.6 1000
345B 380-60 342 418 422.8 450 676.2 450
460-60 414 506 355.6 400 563.6 400
575-60 518 633 289.0 300 456.6 300
208/230-60 187 253 920.5 1000 1362.7 1000
380-60 342 418 485.2 500 738.5 500
360A 460-60 414 506 408.0 450 616.0 450
575-60 518 633 331.5 350 499.1 350
208/230-60 187 253 802.4 1000 1244.6 1000
360B 380-60 342 418 422.8 450 676.2 450
460-60 414 506 355.6 400 563.6 400
575-60 518 633 289.0 300 456.6 300
208/230-60 187 253 920.5 1000 1362.7 1000
380-60 342 418 485.2 500 738.5 500
390A 460-60 414 506 408.0 450 616.0 450
575-60 518 633 331.5 350 499.1 350
208/230-60 187 253 920.5 1000 1362.7 1000
390B 380-60 342 418 485.2 500 738.5 500
460-60 414 506 408.0 450 616.0 450
575-60 518 633 331.5 350 499.1 350
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
MCA Minimum Circuit Amps XL Across-the-Line Start 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
NOTES: 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 1/0 to 500 kcmil.
is not below or above the listed minimum and maximum limits. Maximum allowable phase d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
imbalance is: voltage, 2%; amps 10%. 250 kcmil to 500 kcmil.
2. All units or modules have single point primary power connection. (Each unit or module 6. Hydronic pump packages are not available as a factory-installed option for units
requires its own power supply.) Main power must be supplied from a field-supplied 30RB210-390 and 30RB060-190 with high SCCR option.
disconnect.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
3. Cooler heater is wired into the control circuit so it is always operable as long as the power pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
supply disconnect is on, even if any safety device is open. cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
68
30RB060-190 ELECTRICAL DATA DUAL POINT UNITS
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
UNIT SIZE Supplied MCA MOCP ICF Rec MCA MOCP ICF Rec MCA MOCP ICF Rec
V-Hz Fuse Fuse Fuse
(3 Ph) Min Max XL XL XL XL XL XL XL XL XL
Size Size Size
208/230-60 187 253 168.8/141.5 225/200 560.0/532.8 200/175 177.9/141.5 250/200 570.8/532.8 200/175 184.2/141.5 250/200 577.7/532.8 225/175
380-60 342 418 86.4/ 74.1 110/110 298.4/286.1 100/ 90 91.5/ 74.1 125/110 304.3/286.1 110/ 90 94.5/ 74.1 125/110 308.1/286.1 110/ 90
060 460-60 414 506 73.6/ 62.5 100/ 90 247.7/236.6 90/ 80 77.8/ 62.5 110/ 90 252.6/236.6 90/ 80 80.7/ 62.5 110/ 90 255.7/236.6 90/ 80
575-60 518 633 59.0/ 50.0 80/ 70 201.2/192.3 70/ 60 62.3/ 50.0 80/ 70 205.1/192.3 70/ 60 64.4/ 50.0 90/ 70 207.6/192.3 80/ 60
208/230-60 187 253 212.0/141.5 300/200 654.2/532.8 250/175 221.1/141.5 300/200 665.0/532.8 250/175 227.4/141.5 300/200 671.9/532.8 300/175
380-60 342 418 110.9/ 74.1 150/110 364.3/286.1 125/ 90 116.0/ 74.1 150/110 370.2/286.1 150/ 90 119.0/ 74.1 150/110 374.0/286.1 150/ 90
070 460-60 414 506 93.6/ 62.5 125/ 90 301.6/236.6 110/ 80 97.8/ 62.5 125/ 90 306.5/236.6 110/ 80 100.7/ 62.5 125/ 90 309.6/236.6 125/ 80
575-60 518 633 76.3/ 50.0 110/ 70 243.9/192.3 90/ 60 79.6/ 50.0 110/ 70 247.8/192.3 90/ 60 81.7/ 50.0 110/ 70 250.3/192.3 100/ 60
208/230-60 187 253 216.5/168.8 250/225 607.8/560.0 250/200 231.9/168.8 300/225 625.5/560.0 300/200
380-60 342 418 112.5/ 86.4 150/110 324.5/298.4 125/100 120.6/ 86.4 150/110 334.2/298.4 150/100
080 460-60 414 506 95.2/ 73.6 125/100 269.3/247.7 110/ 90 102.3/ 73.6 125/100 277.3/247.7 125/ 90
575-60 518 633 76.2/ 59.0 100/ 80 218.5/201.2 90/ 70 81.6/ 59.0 100/ 80 224.9/201.2 90/ 70
208/230-60 187 253 283.6/168.8 350/225 725.9/560.0 350/200 299.0/168.8 350/225 743.5/560.0 350/200
380-60 342 418 150.1/ 86.4 175/110 403.5/298.4 175/100 158.2/ 86.4 200/110 413.2/298.4 175/100
090 460-60 414 506 126.0/ 73.6 150/100 334.0/247.7 150/ 90 133.1/ 73.6 150/100 342.0/247.7 150/ 90
575-60 518 633 102.2/ 59.0 125/ 80 269.8/201.2 125/ 70 107.6/ 59.0 125/ 80 276.2/201.2 125/ 70
208/230-60 187 253 283.6/212.0 350/300 725.9/654.2 350/250 299.0/212.0 350/300 743.5/654.2 350/250
380-60 342 418 150.1/110.9 175/150 403.5/364.3 175/125 158.2/110.9 200/150 413.2/364.3 175/125
100 460-60 414 506 126.0/ 93.6 150/125 334.0/301.6 150/110 133.1/ 93.6 150/125 342.0/301.6 150/110
575-60 518 633 102.2/ 76.3 125/110 269.8/243.9 125/ 90 107.6/ 76.3 125/110 276.2/243.9 125/ 90
208/230-60 187 253 283.6/243.8 350/300 725.9/635.0 350/300 299.0/243.8 350/300 743.5/635.0 350/300
380-60 342 418 150.1/124.8 175/150 403.5/336.8 175/150 158.2/124.8 200/150 413.2/336.8 175/150
110 460-60 414 506 126.0/106.3 150/125 334.0/280.4 150/125 133.1/106.3 150/125 342.0/280.4 150/125
575-60 518 633 102.2/ 85.2 125/110 269.8/227.4 125/100 107.6/ 85.2 125/110 276.2/227.4 125/100
208/230-60 187 253 295.5/306.2 350/400 737.8/748.4 350/350 310.9/306.2 400/400 755.5/748.4 350/350
380-60 342 418 156.7/160.2 200/200 410.1/413.6 175/175 164.8/160.2 200/200 419.7/413.6 200/175
120 460-60 414 506 131.4/135.2 150/175 339.4/343.2 150/150 138.5/135.2 175/175 347.4/343.2 150/150
575-60 518 633 106.5/110.2 125/125 274.1/277.8 125/125 111.9/110.2 125/125 280.5/277.8 125/125
208/230-60 187 253 401.7/243.8 450/300 843.9/635.0 450/300 417.1/243.8 500/300 861.6/635.0 450/300
380-60 342 418 212.5/124.8 250/150 465.9/336.8 225/150 220.6/124.8 250/150 475.6/336.8 250/150
130 460-60 414 506 178.4/106.3 200/125 386.4/280.4 200/125 185.5/106.3 225/125 394.4/280.4 200/125
575-60 518 633 144.7/ 85.2 175/110 312.4/227.4 175/100 150.1/ 85.2 175/110 318.8/227.4 175/100
208/230-60 187 253 401.7/306.2 450/400 843.9/748.4 450/350 417.1/306.2 500/400 861.6/748.4 450/350
380-60 342 418 212.5/160.2 250/200 465.9/413.6 225/175 220.6/160.2 250/200 475.6/413.6 250/175
150 460-60 414 506 178.4/135.2 200/175 386.4/343.2 200/150 185.5/135.2 225/175 394.4/343.2 200/150
575-60 518 633 144.7/110.2 175/125 312.4/277.8 175/125 150.1/110.2 175/125 318.8/277.8 175/125
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300 535.2/243.8 600/300 979.7/635.0 600/300
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150 283.0/124.8 300/150 538.0/336.8 300/150
160 460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125 237.9/106.3 250/125 446.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100 192.7/ 85.2 225/110 361.3/227.4 225/100
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350 535.2/306.2 600/400 979.7/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175 283.0/160.2 300/200 538.0/413.6 300/175
170 460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150 237.9/135.2 250/175 446.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125 192.7/110.2 225/125 361.3/277.8 225/125
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450 559.1/400.4 600/450 1003.6/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225 296.1/209.5 300/250 551.0/462.9 300/225
190 460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200 248.7/176.8 250/200 457.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175 201.3/144.1 225/175 369.9/311.7 225/175
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
(Ckt1/Ckt2) (Ckt1/Ckt2) 500 kcmil.
MCA Minimum Circuit Amps XL Across-the-Line Start b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
(Ckt1/Ckt2) 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
NOTES: 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 250 kcmil to 500 kcmil.
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%. 6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390 and 30RB060-190 with high SCCR option.
2. Control power is derived from main power. No separate control power connection is
required. 7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
3. Cooler heater is wired into the control circuit so it is always operable as long as the power cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
supply disconnect is on, even if any safety device is open. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
69
Electrical data (cont)
30RB060-190 ELECTRICAL DATA DUAL POINT UNITS (cont)
UNIT VOLTAGE 7.5 HP PUMP, 1750/3450 RPM 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM
UNIT Supplied MCA MOCP ICF MCA MOCP ICF MCA MOCP ICF
SIZE Rec Fuse Rec Fuse Rec Fuse
V-Hz (3 Ph)
Min Max XL XL XL Size XL XL XL Size XL XL XL Size
208/230-60 187 253 190.8/141.5 250/200 585.7/532.8 225/175 193.8/141.5 250/200 593.6/532.8 225/175
380-60 342 418 98.7/ 74.1 125/110 312.4/286.1 110/ 90 100.4/ 74.1 125/110 316.8/286.1 110/ 90
060 460-60 414 506 83.7/ 62.5 110/ 90 259.3/236.6 100/ 80 85.1/ 62.5 110/ 90 262.9/236.6 100/ 80
575-60 518 633 67.1/ 50.0 90/ 70 210.5/192.3 80/ 60 68.2/ 50.0 90/ 70 213.4/192.3 80/ 60
208/230-60 187 253 234.0/141.5 300/200 679.9/532.8 300/175 237.0/141.5 300/200 687.8/532.8 300/175
380-60 342 418 123.2/ 74.1 150/110 378.3/286.1 150/ 90 124.9/ 74.1 150/110 382.7/286.1 150/ 90
070 460-60 414 506 103.7/ 62.5 125/ 90 313.2/236.6 125/ 80 105.1/ 62.5 125/ 90 316.8/236.6 125/ 80
575-60 518 633 84.4/ 50.0 110/ 70 253.2/192.3 100/ 60 85.5/ 50.0 110/ 70 256.1/192.3 100/ 60
208/230-60 187 253 238.5/168.8 300/225 633.4/560.0 300/200 241.5/168.8 300/225 641.4/560.0 300/200 253.2/168.8 300/225 657.5/560.0 300/200
380-60 342 418 124.8/ 86.4 150/110 338.6/298.4 150/100 126.5/ 86.4 150/110 342.9/298.4 150/100 133.5/ 86.4 150/110 351.8/298.4 150/100
080 460-60 414 506 105.3/ 73.6 125/100 280.9/247.7 125/ 90 106.7/ 73.6 125/100 284.5/247.7 125/ 90 112.2/ 73.6 125/100 291.8/247.7 125/ 90
575-60 518 633 84.3/ 59.0 110/ 80 227.8/201.2 100/ 70 85.4/ 59.0 110/ 80 230.6/201.2 100/ 70 90.2/ 59.0 110/ 80 236.5/201.2 100/ 70
208/230-60 187 253 305.6/168.8 350/225 751.5/560.0 350/200 308.6/168.8 400/225 759.5/560.0 350/200 320.3/168.8 400/225 775.6/560.0 350/200
380-60 342 418 162.4/ 86.4 200/110 417.6/298.4 175/100 164.1/ 86.4 200/110 421.9/298.4 200/100 171.1/ 86.4 200/110 430.8/298.4 200/100
090 460-60 414 506 136.1/ 73.6 175/100 345.6/247.7 150/ 90 137.5/ 73.6 175/100 349.2/247.7 150/ 90 143.0/ 73.6 175/100 356.5/247.7 175/ 90
575-60 518 633 110.3/ 59.0 125/ 80 279.1/201.2 125/ 70 111.4/ 59.0 125/ 80 282.0/201.2 125/ 70 116.2/ 59.0 150/ 80 287.8/201.2 125/ 70
208/230-60 187 253 305.6/212.0 350/300 751.5/654.2 350/250 308.6/212.0 400/300 759.5/654.2 350/250 320.3/212.0 400/300 775.6/654.2 350/250
380-60 342 418 162.4/110.9 200/150 417.6/364.3 175/125 164.1/110.9 200/150 421.9/364.3 200/125 171.1/110.9 200/150 430.8/364.3 200/125
100 460-60 414 506 136.1/ 93.6 175/125 345.6/301.6 150/110 137.5/ 93.6 175/125 349.2/301.6 150/110 143.0/ 93.6 175/125 356.5/301.6 175/110
575-60 518 633 110.3/ 76.3 125/110 279.1/243.9 125/ 90 111.4/ 76.3 125/110 282.0/243.9 125/ 90 116.2/ 76.3 150/110 287.8/243.9 125/ 90
208/230-60 187 253 305.6/243.8 350/300 751.5/635.0 350/300 308.6/243.8 400/300 759.5/635.0 350/300 320.3/243.8 400/300 775.6/635.0 350/300
380-60 342 418 162.4/124.8 200/150 417.6/336.8 175/150 164.1/124.8 200/150 421.9/336.8 200/150 171.1/124.8 200/150 430.8/336.8 200/150
110 460-60 414 506 136.1/106.3 175/125 345.6/280.4 150/125 137.5/106.3 175/125 349.2/280.4 150/125 143.0/106.3 175/125 356.5/280.4 175/125
575-60 518 633 110.3/ 85.2 125/110 279.1/227.4 125/100 111.4/ 85.2 125/110 282.0/227.4 125/100 116.2/ 85.2 150/110 287.8/227.4 125/100
208/230-60 187 253 317.5/306.2 400/400 763.5/748.4 350/350 320.5/306.2 400/400 771.4/748.4 350/350 332.2/306.2 400/400 787.6/748.4 400/350
380-60 342 418 169.0/160.2 200/200 424.1/413.6 200/175 170.7/160.2 200/200 428.5/413.6 200/175 177.7/160.2 225/200 437.3/413.6 200/175
120 460-60 414 506 141.5/135.2 175/175 351.0/343.2 175/150 142.9/135.2 175/175 354.6/343.2 175/150 148.4/135.2 175/175 361.9/343.2 175/150
575-60 518 633 114.6/110.2 125/125 283.4/277.8 125/125 115.7/110.2 125/125 286.3/277.8 125/125 120.5/110.2 150/125 292.1/277.8 150/125
208/230-60 187 253 423.7/243.8 500/300 869.6/635.0 450/300 426.7/243.8 500/300 877.6/635.0 500/300 438.4/243.8 500/300 893.7/635.0 500/300
380-60 342 418 224.8/124.8 250/150 479.9/336.8 250/150 226.5/124.8 250/150 484.3/336.8 250/150 233.5/124.8 250/150 493.1/336.8 250/150
130 460-60 414 506 188.5/106.3 225/125 398.0/280.4 200/125 189.9/106.3 225/125 401.6/280.4 225/125 195.4/106.3 225/125 408.9/280.4 225/125
575-60 518 633 152.8/ 85.2 175/110 321.6/227.4 175/100 153.9/ 85.2 175/110 324.5/227.4 175/100 158.7/ 85.2 175/110 330.4/227.4 175/100
208/230-60 187 253 423.7/306.2 500/400 869.6/748.4 450/350 426.7/306.2 500/400 877.6/748.4 500/350 438.4/306.2 500/400 893.7/748.4 500/350
380-60 342 418 224.8/160.2 250/200 479.9/413.6 250/175 226.5/160.2 250/200 484.3/413.6 250/175 233.5/160.2 250/200 493.1/413.6 250/175
150 460-60 414 506 188.5/135.2 225/175 398.0/343.2 200/150 189.9/135.2 225/175 401.6/343.2 225/150 195.4/135.2 225/175 408.9/343.2 225/150
575-60 518 633 152.8/110.2 175/125 321.6/277.8 175/125 153.9/110.2 175/125 324.5/277.8 175/125 158.7/110.2 175/125 330.4/277.8 175/125
208/230-60 187 253 541.8/243.8 600/300 987.7/635.0 600/300 544.8/243.8 600/300 995.6/635.0 600/300 556.5/243.8 600/300 1011.8/635.0 600/300
380-60 342 418 287.2/124.8 300/150 542.3/336.8 300/150 288.9/124.8 300/150 546.7/336.8 300/150 295.9/124.8 300/150 555.5/336.8 350/150
160 460-60 414 506 240.9/106.3 250/125 450.4/280.4 250/125 242.3/106.3 250/125 454.0/280.4 250/125 247.8/106.3 250/125 461.3/280.4 300/125
575-60 518 633 195.4/ 85.2 225/110 364.2/227.4 225/100 196.5/ 85.2 225/110 367.1/227.4 225/100 201.3/ 85.2 225/110 372.9/227.4 225/100
208/230-60 187 253 541.8/306.2 600/400 987.7/748.4 600/350 544.8/306.2 600/400 995.6/748.4 600/350 556.5/306.2 600/400 1011.8/748.4 600/350
380-60 342 418 287.2/160.2 300/200 542.3/413.6 300/175 288.9/160.2 300/200 546.7/413.6 300/175 295.9/160.2 350/200 555.5/413.6 350/175
170 460-60 414 506 240.9/135.2 250/175 450.4/343.2 250/150 242.3/135.2 250/175 454.0/343.2 250/150 247.8/135.2 250/175 461.3/343.2 300/150
575-60 518 633 195.4/110.2 225/125 364.2/277.8 225/125 196.5/110.2 225/125 367.1/277.8 225/125 201.3/110.2 225/125 372.9/277.8 225/125
208/230-60 187 253 565.7/400.4 600/450 1011.6/842.6 600/450 568.7/400.4 600/450 1019.5/842.6 600/450 580.4/400.4 600/450 1035.7/842.6 600/450
380-60 342 418 300.3/209.5 350/250 555.4/462.9 350/225 302.0/209.5 350/250 559.7/462.9 350/225 309.0/209.5 350/250 568.6/462.9 350/225
190 460-60 414 506 251.7/176.8 300/200 461.2/384.8 300/200 253.1/176.8 300/200 464.8/384.8 300/200 258.6/176.8 300/200 472.1/384.8 300/200
575-60 518 633 204.0/144.1 225/175 372.8/311.7 225/175 205.1/144.1 225/175 375.7/311.7 225/175 209.9/144.1 225/175 381.5/311.7 225/175
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
(Ckt1/Ckt2) (Ckt1/Ckt2) 500 kcmil.
MCA Minimum Circuit Amps XL Across-the-Line Start b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
(Ckt1/Ckt2) 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
NOTES: 1/0 to 500 kcmil.
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
is not below or above the listed minimum and maximum limits. Maximum allowable phase 250 kcmil to 500 kcmil.
imbalance is: voltage, 2%; amps 10%. 6. Hydronic pump packages are not available as a factory-installed option for units
2. Control power is derived from main power. No separate control power connection is 30RB210-390 and 30RB060-190 with high SCCR option.
required. 7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
3. Cooler heater is wired into the control circuit so it is always operable as long as the power cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
supply disconnect is on, even if any safety device is open. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
70
30RB210-390 ELECTRICAL DATA DUAL POINT UNITS
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
UNIT SIZE Supplied MCA MOCP ICF MCA MOCP ICF Rec MCA MOCP ICF Rec
Rec Fuse
V-Hz (3 Ph) Fuse Fuse
Min Max XL XL XL Size XL XL XL XL XL XL
Size Size
208/230-60 187 253 626.7/353.9 700/400 1068.9/796.2 700/400
380-60 342 418 327.7/186.4 350/225 581.1/439.7 350/200
210 460-60 414 506 233.3/200.0 250/225 441.3/408.0 250/225
575-60 518 633 188.8/162.0 200/175 356.4/329.6 200/175
208/230-60 187 253 684.3/353.9 700/400 1126.5/796.2 700/400
380-60 342 418 360.4/186.4 400/225 613.8/439.7 400/200
225 460-60 414 506 260.0/200.0 300/225 468.0/408.0 300/225
575-60 518 633 211.9/162.0 225/175 379.5/329.6 225/175
208/230-60 187 253 684.3/472.0 700/500 1126.5/914.3 700/500
380-60 342 418 360.4/248.7 400/250 613.8/502.1 400/250
250 460-60 414 506 303.2/209.2 350/250 511.2/417.2 350/225
575-60 518 633 246.4/170.0 250/200 414.1/337.6 250/200
208/230-60 187 253 920.5/353.9 1000/400 1362.7/796.2 1000/400
380-60 342 418 485.2/186.4 500/225 738.5/439.7 500/200
275 460-60 414 506 408.0/156.8 450/175 616.0/364.8 450/175
575-60 518 633 331.5/127.5 350/150 499.1/295.1 350/150
208/230-60 187 253 920.5/472.0 1000/500 1362.7/914.3 1000/500
380-60 342 418 485.2/248.7 500/250 738.5/502.1 500/250
300 460-60 414 506 408.0/209.2 450/250 616.0/417.2 450/225
575-60 518 633 331.5/170.0 350/200 499.1/337.6 350/200
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
315A 460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
315B 575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
330A 460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
330B 380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
345A 460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
345B 380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
360A 460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
360B 380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
390A 460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
390B 380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
LEGEND 5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
ICF Instantaneous Current Flow MOCP Maximum Overcurrent Protection a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
(Ckt1/Ckt2) (Ckt1/Ckt2) 500 kcmil.
MCA Minimum Circuit Amps XL Across-the-Line Start b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
(Ckt1/Ckt2) 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
NOTES: 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 250 kcmil to 500 kcmil.
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%. 6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390 and 30RB060-190 with high SCCR option.
2. Control power is derived from main power. No separate control power connection is
required. 7. Power draw includes both crankcase heaters and cooler heaters (where used). Each com-
pressor has a crankcase heater which draws 56 watts of power. Units ordered with the
3. Cooler heater is wired into the control circuit so it is always operable as long as the power cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts each.
supply disconnect is on, even if any safety device is open. 8. 30RB chillers with Greenspeed intelligence are not available in size 060 and 070.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
208/230
460
575 v only
71
Electrical data (cont)
30RB ELECTRICAL DATA POWER ENTRY
UNIT SIZE VOLTAGE ELECTRICAL OPTION CONNECTIONS MAIN POWER ENTRANCE CONTROL BOX
Single Point Circuit 1 Combination
208/230, 380, Standard (Terminal Block) Circuit 1 Combination
060,070 Dual Point
460, 575 Circuit 2 Combination
Non-Fused Disconnect Option* Single Point Circuit 1 Combination
Single Point Circuit 1 Power-L
Standard (Terminal Block) Circuit 1 Power-L
208/230 Dual Point
Circuit 2 Power-L
Non-Fused Disconnect Option* Single Point Circuit 1 Power-L
080-120
Single Point Circuit 1 Combination
Standard (Terminal Block) Circuit 1 Combination
380, 460, 575 Dual Point
Circuit 2 Combination
Non-Fused Disconnect Option* Single Point Circuit 1 Combination
Single Point Circuit 1 Power-L
Standard (Terminal Block) Circuit 1 Power-L
Dual Point
Circuit 2 PEB1
208/230
Single Point Circuit 1 Power-L
Non-Fused Disconnect Option Circuit 1 Power-L
130-190, Dual Point
Circuit 2 PEB1
315A-390A,
315B-390B Single Point Circuit 1 PEB1
Standard (Terminal Block) Circuit 1 PEB1
Dual Point
Circuit 2 PEB1
380, 460, 575
Single Point Circuit 1 PEB1
Non-Fused Disconnect Option Circuit 1 PEB1
Dual Point
Circuit 2 Power-L
Circuit 1 Power-L
Standard (Terminal Block) Dual Point
Circuit 2 PEB2
208/230
Circuit 1 Power-L
Non-Fused Disconnect Option Dual Point
Circuit 2 PEB2
Single Point Circuit 1 PEB1
210, 225
Standard (Terminal Block) Circuit 1 PEB1
Dual Point
Circuit 2 PEB1
380, 460, 575
Single Point Circuit 1 PEB1
Non-Fused Disconnect Option Circuit 1 PEB1
Dual Point
Circuit 2 Power-L
Circuit 1 Power-L
Standard (Terminal Block) Dual Point
Circuit 2 PEB2
208/230
Circuit 1 Power-L
Non-Fused Disconnect Option Dual Point
Circuit 2 PEB2
Single Point Circuit 1 PEB1
250-300
Standard (Terminal Block) Circuit 1 PEB1
Dual Point
Circuit 2 PEB2
380, 460, 575
Single Point Circuit 1 PEB1
Non-Fused Disconnect Circuit 1 PEB1
Dual Point
Circuit 2 PEB2
LEGEND NOTE: 30RB chillers with Greenspeed intelligence are not available in size 060
PEB Power Electrical Box and 070.
72
CONDENSER FAN ELECTRICAL DATA
73
Electrical data (cont)
COMPRESSOR ELECTRICAL DATA
COMPRESSOR COMPRESSOR COMPRESSOR
UNIT UNIT VOLTAGE A1 A2 A3 A4 B1 B2 B3 B4 C1 C2 C3 C4
SIZE V-Hz (3 Ph)
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
208/230-60 75.0 485 75.0 485 75.0 485
380-60 38.4 260 38.4 260 38.4 260
060 460-60 32.7 215 32.7 215 32.7 215
575-60 26.2 175 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 75.0 485
380-60 49.3 315 49.3 315 38.4 260
070
460-60 41.6 260 41.6 260 32.7 215
575-60 33.9 210 33.9 210 26.2 175
208/230-60 75.0 485 75.0 485 75.0 485 75.0 485
380-60 38.4 260 38.4 260 38.4 260 38.4 260
080 460-60 32.7 215 32.7 215 32.7 215 32.7 215
575-60 26.2 175 26.2 175 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 75.0 485 75.0 485
380-60 49.3 315 49.3 315 38.4 260 38.4 260
090 460-60 41.6 260 41.6 260 32.7 215 32.7 215
575-60 33.9 210 33.9 210 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315
100 460-60 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 75.0 485 75.0 485 75.0 485
380-60 49.3 315 49.3 315 38.4 260 38.4 260 38.4 260
110 460-60 41.6 260 41.6 260 32.7 215 32.7 215 32.7 215
575-60 33.9 210 33.9 210 26.2 175 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
120 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 75.0 485 75.0 485 75.0 485
380-60 49.3 315 49.3 315 49.3 315 38.4 260 38.4 260 38.4 260
130 460-60 41.6 260 41.6 260 41.6 260 32.7 215 32.7 215 32.7 215
575-60 33.9 210 33.9 210 33.9 210 26.2 175 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
150 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 75.0 485 75.0 485 75.0 485
380-60 49.3 315 49.3 315 49.3 315 49.3 315 38.4 260 38.4 260 38.4 260
160, 315A, 315B, 330B 460-60 41.6 260 41.6 260 41.6 260 41.6 260 32.7 215 32.7 215 32.7 215
575-60 33.9 210 33.9 210 33.9 210 33.9 210 26.2 175 26.2 175 26.2 175
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
170, 330A, 345A, 345B, 360B 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
190, 360A, 390A, 390B 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 75.0 485 75.0 485 75.0 485 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 38.4 260 38.4 260 38.4 260 49.3 315 49.3 315 49.3 315
210 460-60 41.6 260 41.6 260 41.6 260 32.7 215 32.7 215 32.7 215 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 26.2 175 26.2 175 26.2 175 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
225 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
250 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
275 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
208/230-60 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560 94.2 560
380-60 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315 49.3 315
300 460-60 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260 41.6 260
575-60 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210 33.9 210
LEGEND NOTE: 30RB chillers with Greenspeed intelligence are not available in size 060
LRA Locked Rotor Amps and 070.
RLA Rated Load Amps
74
Controls
Microprocessor microprocessor uses these inputs to control capacity and
The ComfortLink microprocessor controls overall unit oper- fan cycling.
ation. Its central executive routine controls a number of pro- Saturated condensing temperature
cesses simultaneously. These include internal timers, reading Cooler saturation temperature
inputs, analog to digital conversions, fan control, display
control, diagnostic control, output relay control, demand Control sequence
limit, capacity control, head pressure control, and tempera- Off cycle If ambient temperature is below 36 F (2 C),
ture reset. Some processes are updated almost continuously, cooler heaters (if equipped) are also energized.
others every 2 to 3 seconds, and some every 30 seconds. Start-up After the control circuit switches on, the pre-
The microprocessor routine is started by switching the start process takes place, then microprocessor checks
Emergency ON-OFF switch to ON position. Pump control itself, starts pump (if configured) and waits for temperature
of external pumps (where so configured) or optional internal to stabilize. The controlled pulldown feature limits com-
pump, will energize the cooler pump to the internal (or pressor loading on start-up to reduce demand on start-up
CCN) time schedule (or input occupied signal from external and unnecessary compressor usage. The microprocessor
system). limits supply-fluid temperature decrease (start-up only) to
Where dual pumps are utilized only one pump will be 1 F (0.6 C) per minute.
operated at a time. The control will start the pump with the Capacity control On first call for cooling, micropro-
least hours. When the unit receives a call for cooling (based cessor starts initial compressor and fan stage on lead
on a deviation from chilled water set point), the unit stages circuit.
up in capacity to maintain the cooler fluid set point. The As additional cooling is required, additional compressors
first compressor starts 1 to 3 minutes after the call for cool- are energized.
ing. The ComfortLink microprocessor controls the capac-
ity of the chiller by cycling compressors at a rate to satisfy Speed at which capacity is added or reduced is con-
actual dynamic load conditions. The control maintains trolled by temperature deviation from set point and rate of
leaving-fluid temperature set point shown on the scrolling temperature change of chilled fluid.
marquee display board through intelligent cycling. Accu- The Main Base Board (MBB) responds to the supply
racy depends on loop volume, loop flow rate, load, chilled water temperature to cycle the compressors to
outdoor-air temperature, number of stages, and particular match cooling load requirements.
stage being cycled off. No adjustment for cooling range or Minimum load control valve is energized by the MBB.
cooler flow rate is required, because the control automati- Valve allows hot gas to pass directly into the cooler circuit
cally compensates for cooling range by measuring both on the final step of unloading, permitting the unit to oper-
return-fluid temperature and leaving-fluid temperature. ate at lower loads with less compressor cycling.
This is referred to as leaving-fluid temperature control with
return-fluid temperature compensation. Additional information
The basic logic for determining when to add or remove a Detailed information on controls and operation is available
stage is a time band integration of deviation from set point in the Controls, Start-Up, Operation and Troubleshooting
plus rate of change of leaving-fluid temperature. When guide included with each unit. Packaged Service Training
leaving-fluid temperature is close to set point and slowly programs are also available. Contact your Carrier repre-
moving closer, logic prevents addition of another stage. sentative for more information.
If 1 F per minute (0.6 C per minute) pulldown control has High-efficiency variable condenser fans (30RB
been selected (adjustable setting), no additional steps of chillers with Greenspeed intelligence only) All
capacity are added as long as the difference between leaving- fans on a circuit run at the same speed and are controlled
fluid temperature and set point is greater than 4 F (2.2 C) by a VFD with special CCN software to maintain SCT (sat-
and rate of change in leaving-fluid temperature is greater than urated condensing temperature) set point. The set point is
the selected pulldown control rate. If it has been less than calculated from operating conditions and adjusted to the
90 seconds since the last capacity change, compressors will most efficient operating point. The high-efficiency variable
continue to run unless a safety device trips. This prevents condenser fan option uses Danfoss VLT 102 variable fre-
rapid cycling and also helps return oil during short on periods. quency drives, each with a display. Drives are connected to
the LEN communication bus. Fan speed is determined by
Sensors the chiller controller and communicated to the drive to pro-
Thermistors are used to control temperature-sensing inputs to vide excellent part load efficiency and reduced sound level
microprocessor. Additional thermistor sensors may be used as operation over the life of the chiller.
remote temperature sensors for optional LCWT (leaving Dual chiller control The ComfortLink controller
chilled fluid temperature) reset. allows 2 chillers (piped in parallel) to operate as a single
Cooler leaving chilled fluid temperature (T1) chilled water plant with standard control functions coordi-
Cooler entering fluid (return) temperature (T2) nated through the master chiller controller. This standard
Outside-air temperature (T9) ComfortLink feature requires a communication link
Two refrigerant pressure transducers are used in each between the 2 chillers and, in the case of parallel chillers,
circuit for sensing suction and discharge pressure. The requires an additional thermistor and well for each chiller.
75
Controls (cont)
Dynamic ComfortLink controls Dynamic Com- safety mode until reset. It then reverts to normal control
fortLinkcontrols keep the chiller on line during periods of when unit is reset.
extreme operating conditions. If the entering fluid tem- Low-pressure safety Safety cuts out if system pres-
perature is 85 F (29 C) or higher and the saturated suction sure drops below minimum.
temperature is 50 F (10 C) or higher the maximum
High-pressure cutout Switch shuts down compres-
operating pressure (MOP) feature limits the suction to keep
sors if compressor discharge pressure increases to
the chiller online. The control automatically starts the
641 psig (4420 kPa).
chiller in the unloaded state to eliminate the potential of
compressor overload due to high head pressure or low suc- Compressor anti-cycling This feature limits com-
tion pressure. The controller will equalize run time on each pressor cycling.
circuit through the lead/lag feature. If a circuit becomes Loss of flow protection Proof of flow switches are
disabled, the control will automatically set the active circuit standard and installed on all 30RB chillers.
to lead, keeping the chiller online at a reduced capacity. Sensor failures Failures are detected by the
microprocessor.
CAPACITY CONTROL STEPS*
UNIT 30RB STANDARD CAPACITY STEPS (%)
Temperature reset
060 0, 33, 67, 100 The energy management module (EMM) is required for 4
070 0, 29, 64, 100 to 20 mA reset of LCWT in constant fluid systems. Reset
080 0, 25, 50, 75, 100 by return fluid, outdoor-air temperature, or space tempera-
090 0, 22, 50, 72,100
100 0, 25, 50, 75, 100
ture does not require this option. Reset reduces compres-
110 0, 18, 41, 59, 82, 100 sor power usage at part load when design LCWT is not
120 0, 20, 40, 60, 80, 100 necessary. Humidity control should be considered since
130 0, 15, 33, 48, 67, 81, 100 higher coil temperatures resulting from reset will reduce
150 0, 17, 33, 50, 67, 83, 100
latent heat capacity. Three reset options are offered, based
160 0, 13, 28, 41, 56, 69, 84, 100
170 0, 14, 29, 43, 57, 71, 86, 100 on the following:
190 0, 13, 25, 38, 50, 63, 75, 88, 100 Return-fluid temperature Increases LCWT set point
210 0, 10, 21, 33, 43, 55, 67, 76, 88, 100
as return (or entering) fluid temperature decreases (indicat-
225 0, 11, 22, 33, 44, 56, 67, 78, 89, 100
250 0, 10, 20, 30, 40, 50, 60, 70, 80, 90, 100 ing load decrease). Option may be used in any application
275 0, 9, 18, 27, 36, 45, 55, 64, 73, 82, 91, 100 where return fluid provides accurate load indication. Lim-
300 0, 8, 17, 25, 33, 42, 50, 58, 67, 75, 83, 92, 100 itation of return fluid reset is that LCWT may only be reset
315 0, 6, 14, 20, 28, 34, 42, 50, 56, 64, 70, 78, 84, 92, 100 to value of design return fluid temperature.
330 0, 6, 13, 19, 27, 33, 40, 48, 55, 63, 70, 78, 85, 93, 100
345 0, 7, 14, 21, 29, 36, 43, 50, 57, 64, 71, 79, 86, 93, 100 Outdoor-air temperature Increases LCWT as out-
360 0, 7, 13, 20, 27, 33, 40, 47, 53, 60, 67, 73, 80, 87, 93, 100 door ambient temperature decreases (indicating load
390 0, 6, 13, 19, 25, 31, 38, 44, 50, 56, 63, 69, 75, 81, 88, 94, 100 decrease). This reset should be applied only where outdoor
*Capacity control steps may vary due to compressor sequencing. ambient temperature is an accurate indication of load. An
accessory thermistor is required.
Standard ComfortLink controls with scrolling Space temperature Increases LCWT as space tem-
marquee display A four-digit alphanumeric display
perature decreases (indicating load decrease). This reset
shows all of the ComfortLink control codes (with 60-char- should be applied only where space temperature is an
acter expandable clear language), plus set points, time of
accurate indication of load. An accessory thermistor and
day, temperatures, pressures, and superheat. Additional the energy management module accessory is required.
information can be displayed all at once with the accessory
Navigator display. For details on applying a reset option, refer to unit
Controls and Troubleshooting literature. Obtain ordering
Navigator display An optional 4-line, 20-character part numbers for reset option from the Packaged
per line display an also available as a field-installed Chiller Builder program or contact your local Carrier
accessory.
representative.
Low-temperature override This feature prevents
LCWT from overshooting the set point and possibly caus- Accessory controls
ing a nuisance trip-out by the freeze protection. Demand can be limited by controlling the chiller capacity
High-temperature override This feature allows through the demand limit control (the energy management
chiller to add capacity quickly during rapid load variations. module is required for this function). This factory-installed
option or accessory interfaces with microprocessor to con-
Abnormal conditions All control safeties in chiller
trol unit so that chillers kW demand does not exceed its
operate through compressor protection board or control
setting. It is activated from an external switch or a 4 to
relay and microprocessor.
20 mA signal.
Loss of feedback signal to the MBB will cause the com-
pressor(s) to shut down. For other safeties, microprocessor The standard ComfortLink controller is programmed to
makes appropriate decision to shut down a compressor accept various accessory temperature reset options (based
on outdoor-air temperature [standard], return-fluid tem-
due to a safety trip or bad sensor reading and displays
appropriate failure code on the display. Chiller remains in perature, or space temperature), that reset the LCWT. An
accessory thermistor (T10) is required if outdoor-air
76
temperature or space temperature reset is selected. The thermal storage system may potentially reduce the size of
energy management module (EMM) is only required for the chiller plant required to meet demand loads.
temperature reset that is initiated by a 4 to 20 mA signal.
Heat reclaim option
Demand limit The heat reclaim option is available for 30RB060-190
If applied, this limits the total power draw of unit to chiller applications in which the customer has a simultane-
selected point by controlling number of operational com- ous need for chilled water and tempered hot water.
pressors during periods of peak electrical demand. The Whether or not the heat reclaim mode is in operation, the
energy management module is required for either 2-step or chiller always controls the leaving chilled water tempera-
4 to 20 mA demand limit. ture set point. When in the heat reclaim mode, the two
refrigerant circuits are independently controlled, which
Electronic expansion valve (EXV) means that one circuit can be in the standard cooling mode
The EXV controls refrigerant flow to the cooler for differ- while the other circuit is in the heat reclaim mode. This
ent operating conditions by moving an orifice to increase permits two heat reclaim control stages (100% heat
or decrease the flow area through the valve based on reclaim if both circuits are in heat reclaim mode and
microprocessor input. The orifice is positioned by a step- approximately 50% heat reclaim based upon the size of
per motor through approximately 3,600 discrete steps and the operating circuit). The intermediate stages are obtained
is monitored every three seconds. The EXV maintains an by cycling between the cooling-only mode and the heat
approximate 8 F (5 C) refrigerant superheat entering the reclaim mode.
compressor. When the heat reclaim mode is enabled (local mode, cus-
Diagnostics tomer remote contact or CCN control), and the return
The microprocessor may be put through a service test (see (entering) hot-water temperature is below the customer-
Controls, Start-Up, Operation, Service, and Troubleshoot- adjustable set point, one circuit is switched to the heat
ing literature). Service test confirms microprocessor is reclaim mode. In this mode, the chiller is operating with a
functional, informs observer through display the condition water-cooled condenser on one circuit and an air-cooled
of each sensor and switch in chiller, and allows observer to condenser on the other circuit. Depending upon hot-water
check for proper operation of fans and compressors. temperature requirements, the second circuit may also be
switched to the heat reclaim mode (providing full heat
Default settings recovery in this mode of operation). The hot water tem-
To facilitate quick start-ups, 30RB chillers with perature is controlled by the cycling of each refrigerant cir-
ComfortLink controls are pre-configured with a default cuit between the air-cooled and heat reclaim modes. When
setting that assumes stand-alone operation supplying 44 F the hot water set point is satisfied, the chiller will transition
(6.7 C) chilled water. back to the cooling-only mode and operate as a conven-
Configuration settings will be based on any options tional air-cooled chiller.
or accessories included with the unit at the time of The heat reclaim option is provided with an additional
manufacturing. factory-installed board. The functions controlled by this
Date and time are set to U.S.A. Eastern Time zone and board include control of:
will need reconfiguring based on location and local time a customer-supplied heat reclaim condenser pump
zone. If operation based on occupancy scheduling is a customer-supplied 3-way valve
desired, this will also need to be set during installation. a factory-supplied heat reclaim condenser heater
a series of solenoid valves.
Ice duty
Changeover from the cooling-only mode to the heat
ComfortLink controls have the capability of reduced leav- reclaim mode involves the generation of a signal to start
ing fluid temperature operation for thermal storage, or ice the heat reclaim condenser pump and pump flow verifica-
duty. On unit sizes 060-100 the optional energy manage-
tion via the condenser water flow switch. If the condenser
ment module includes input contacts for the ice done sig- water flow switch contacts remain open for more than a
nal generated by the thermal storage control system. The minute after the signal has been sent to the pumps, the cir-
ice duty feature may be configured to start on an external
cuit remains in the cooling mode; an alarm is generated.
input command or by the ComfortLink standard internal
scheduling function. Ice duty may be used in combination When operating in the heat reclaim mode, proper head
with any other standard features offered by the energy pressure must be maintained. In order to accomplish this, a
management module and ComfortLink controls. 3-way water valve must be field-installed and located within
40 ft (12.2 m) of the heat reclaim condenser. This valve
The production of ice, which is stored for peak cooling will facilitate cold water start-up (water temperatures below
demands, can significantly decrease energy costs. The unit
59 F [15 C]), and it also will be able to maintain proper
produces ice (normally at night) by supplying ice storage head pressure during heat reclaim operation. The mini-
tanks with low temperature cooling fluid. The chiller takes mum position of this water valve must be set at 20%, and
advantage of reduced ambient conditions at night for ice-
the maximum position of the valve must be set at 100%. A
making mode, so the capacity suffers a lower penalty for 0 to 10 vdc control signal from the heat reclaim board will
the low leaving fluid temperatures. be used to control the position of the valve.
At peak cooling demands the chiller and the stored ice
may share the cooling load to reduce operating costs. The
77
78
NOTES:
+
THE MAXIMUM LOAD ALLOWED FOR THE CHILLED WATER PUMP RELAY IS 5 VA SEALED, 10 VA EQUIP
11 12 13
INRUSH AT 24V. FIELD POWER SUPPLY IS NOT REQUIRED. GND
6. FOR CONTROL OF CHILLED WATER PUMPS, A SET OF NORMALLY OPEN CONTACTS RATED FOR DRY CIRCUIT APPLICATION GROUND-FAULT
MUST BE SUPPLIED FROM FIELD SUPPLIED PUMP STARTER RELAY. CONNECT CONTACTS TO VIOLET AND PINK WIRES IN CIRCUIT-INTERRUPTER
SHLD - COM
HARNESS FROM MAIN BASE BOARD CHANNEL 18. WIRES IN HARNESS ARE MARKED PMP1-13 AND PMP1-14. OUTLET
7. TERMINALS 12 AND 13 OF TB5 ARE FOR A ALARM RELAY. THE MAXIMUM LOAD ALLOWED FOR THE
(4 AMPS MAX.)
ALARM RELAY IS 10 VA SEALED, 25 VA INRUSH AT 24V. FIELD POWER SUPPLY IS NOT REQUIRED.
8. MAKE APPROPRIATE CONNECTIONS TO TB6 AS SHOWN FOR ENERGY MANAGEMENT BOARD OPTIONS. THE
CONTACTS FOR OCCUPANCY OVERRIDE, DEMAND LIMIT AND ICE DONE OPTIONS MUST BE RATED FOR
DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 24VAC LOAD UP TO 50 MA.
9. J3 - 24 AND 25 OF EMM BOARD ARE FOR RUN RELAY AND SHUTDOWN RELAY. THE MAXIMUM EMM BOARD
LOAD ALLOWED FOR THE RUN AND SHUTDOWN RELAY IS 10 VA SEALED, 25 VA INRUSH AT 24V.
FIELD POWER SUPPLY IS NOT REQUIRED.
J3
J6
J4
J4
J4
J4
J7B
J7A
LEGEND: CH CH CH CH CH CH CH CH CH
TRAN2 10 2 11A 8 9 24 25
SECONDARY 5 6
A - ALARM 115V DATA COM PORT
R
+
+
+
X1
+
WHT X3 FU4 +
R
S
R
+
S
5V
5V
PMPI- CHILLED WATER PUMP INTERLOCK
XF FIELD POWER SUPPLY
3
1
5
5
4
2
6
6
3
2
1
3
4
4
CWP - CHILLED WATER PUMP EMM
GROUND
VIO
RED
GRA
GRA
RED
GRN
BLK
GRN
ORN
BLU
BLK
VIO
BLU
ACCESSORY
ORN
FIOP/ACCESSORY DISCONNECT/BRANCH CIRCUIT
MLV - MINIMUM LOAD VALVE
LINE PROTECTION PER NEC
TB - TERMINAL BLOCK
FIELD POWER WIRING TB6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 (SEE NOTE #2)
FIELD CONTROL WIRING BRASS SCREW
FACTORY INSTALLED WIRING SILVER SCREW RESET
R
R
GRN-YEL
BAS Port
SHD
RUN
315A,B
160 CB1A ((STANDARD DISCONNECT POWER ENTRY)
+
-
+
-
CB1B (OPTIONAL DUAL POWER ENTRY POINT FOR DISCONNECT)
8
A
330A Net+ Net- SHIELD UPC 1 2 3
345A,B 170
ICE DONE
13
360B Open
TB5
SIGNAL
SIGNAL
T8
4-20 MA
4-20 MA
SW2 C
GENERATOR
GENERATOR
360A
ON/OFF
OCCUPANCY OVERRIDE
DEMAND LIMIT STEP 2
390A,B
Typical control wiring schematic
RESET
LIMIT
TEMP
SETPOINT
CAPACITY
SPACE
(10K)
Network
Wiring
EQUIP
080-300 230V GND
130-300 380/460/575V
TB5
DISPLAY LOCATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FIELD CONTROL
WIRING ENTRY
PMPI
FEB REMOTE A
ON/OFF
MLV-A
PEB2 SEE
NOTE 3 PMP2
COMBI DUAL SETPOINT
060,070 230V OR
MLV-B
MLV-C
a30-5188
OPTIONAL HEAT RECLAIM CONTROL TYPICAL FIELD WIRING
() (+)
LEGEND NOTES:
Field Control Wiring 1. Terminals 1 and 2 of TB7 are for external connection of heat
Factory Installed Wiring reclaim condenser water valve. a30-4742
2. Terminals 3 and 4 of TB7 are for external connection of field-
supplied heat reclaim water pump control relay.
3. The maximum load allowed for the condenser pump relay is
5 va sealed, 10 va inrush at 24 v.
4. Terminals 14 and 15 of TB7 are for external connection of
heat reclaim remote enable switch.
5. Terminals 5 through 13 of TB7 are for the connection of
factory-installed solenoid valve control wiring.
79
Application data
Chiller location and clearances given consideration where substantial operating time is
The 30RB unit must be installed outdoors. anticipated below the minimum unloading step.
Do not locate near sound sensitive areas without proper Piping duplex units The 30RB duplex chillers (sizes
acoustic consideration. For applications requiring mount- 315 - 390) are shipped and rigged as 2 separate units. The
ing a chiller on a building rooftop, consideration should be units must be piped in parallel. If units are to be aligned
given to using rubber-in-shear or spring isolators to mini- end-to-end, minimum spacing of 42 to 48-in. (depending
mize structure-borne transmission. Unit must be level when on local codes) between chillers is recommended to provide
installed to ensure proper oil return to the compressors. adequate service access and piping clearance.
Clearances must be provided around chillers for airflow, Multiple chillers
service and local code requirements. See dimensional
drawings for specific unit clearance requirements. Ensure Where chiller capacities greater than can be supplied by a
single 30RB chiller are required, or where standby capabil-
adequate clearance between adjacent chillers is main-
tained. A minimum of 10 ft (3048 mm) is recommended. ity is desired, chillers may be installed in parallel. Units may
Chiller fan discharge must be at least as high as adjacent be of the same or different sizes with this piping arrange-
ment. However, cooler flow rates must be balanced to en-
solid walls. Installation in pits is not recommended.
sure proper flow to each chiller.
Minimum clearances Unit software is capable of controlling two parallel units
The recommended minimum clearance to ensure proper as a single plant by making use of the dual chiller control
airflow through the condenser coils and to allow fan main- feature. Refer to the Controls, Start-up, Operation, Service
tenance is as shown below. and Troubleshooting guide for further details. The accesso-
Acceptable clearance on the cooler connection side or ry Chillervisor System Manager can be used to ensure
end opposite the control box of the unit can be reduced to proper staging sequence of up to 8 chillers arranged in a
3 ft (1 m) without sacrificing performance as long as the parallel configuration. Refer to the accessory Chillervisor
remaining three sides are unrestricted. Acceptable clear- System Manager installation instructions for further details.
ance on the side with a control box can be reduced to 4 ft If the dual chiller algorithm is used, and the machines are
(1.3 m) due to NEC (National Electric Code) regulations, installed in parallel, an additional chilled water sensor must
without sacrificing performance as long as the remaining be installed for each module. For 30RB315-390, where it
three sides are unrestricted. Clearances between chillers in is understood that these are duplex chillers comprised of 2
dual chiller applications may be reduced to 6 ft (1.8 m) chillers to be installed in parallel, two factory-supplied
without sacrificing performance provided the remaining thermistors and wells are shipped in the control box of one
sides are unrestricted. For acceptable clearance with layout of the modules (for other 30RB chiller sizes which will be
involving more than 2 chillers, please contact application installed in a parallel piping configuration, a dual chiller ac-
engineering. cessory kit is available). Install one thermistor and well per
chiller in the common leaving water header.
MULTIPLE UNIT SEPARATION
Parallel chiller control with dedicated pumps is recom-
6 ft (1.8 m)
a30-4904 MINIMUM mended. The chiller must start and stop its own water
pump located in its own piping. Check valves are required
at the discharge of each pump (when the factory hydronic
10 ft package option is chosen, and dual pumps are select-
(3 m)*
MINIMUM ed, the check valves are automatically supplied). If
pumps are not dedicated for each chiller, then isolation
valves are required. Each chiller must open and close its
own isolation valve through the unit control (the valve must
* 12 ft (3.7m) required for unit sizes 275 and 300. For applications be connected to the pump outputs). Refer to the chiller
with higher than 115 F (46.1 C) ambient, contact application
engineering. piping configuration shown on the next page.
If a series application is required, the master/slave con-
Oversizing chillers trol feature cannot be used. Hydronic pump packages may
Oversizing chillers by more than 15% at design conditions not be applied in series applications.
must be avoided as the system operating efficiency is
adversely affected (resulting in greater or excessive electri-
cal demand). When future expansion of equipment is
anticipated, install a single chiller to meet present load
requirements and add a second chiller to meet the addi-
tional load demand. It is also recommended that 2 smaller
chillers be installed where operation at minimum load is
critical. The operation of a smaller chiller loaded to a
greater percentage over minimum is preferred to operating
a single chiller at or near its minimum recommended value.
Minimum load control should not be used as a means to
allow oversizing chillers. Minimum load control should be
80
PARALLEL DUAL CHILLER OPERATION
CONTROL
BOX
OR ISOLATION VALVE
CONTROL
BOX LEGEND
SLAVE CHILLER LWT Leaving Water Temperature
PUMP & CHECK VALVE
Field-Installed Communication Bus
Field-Installed Wiring
OR ISOLATION VALVE
a30-4453
DUAL CHILLER
LWT SENSORS
& WELLS
81
Application data (cont)
Minimum cooler flow (maximum cooler tempera- than 10% per minute. Apply a minimum of 6 gallons per
ture rise) The minimum cooler flow for standard units ton (6.5 L per kW) water loop volume if the flow rate
is shown in Minimum and Maximum Cooler Fluid Flow changes more rapidly.
Rates table on page 83. When system design conditions The 30RB chiller is available without a hydronic pump-
require a lower flow (or higher rise) than the minimum ing package or with either of 2 variations of a hydronic
allowable cooler flow, follow the recommendations below. pumping package. One of these hydronic options offers a
a. Multiple smaller chillers may be applied in series, each constant-speed pumping package, and the other offers a
providing a portion of the design temperature rise. variable-speed drive. Traditional pumping systems incorpo-
b. Cooler fluid may be recirculated to raise the flow rate to rate constant speed drives and waste energy by relying
the chiller. The mixed temperature entering the cooler upon throttling valves as the only means to control flow. A
must be maintained to a minimum of at least 3 F more energy-efficient approach to this issue is use a vari-
(1.7 C) above the LCWT and to a maximum of no able-speed drive. The 30RB chiller is now available with an
more than 20 F (11.1 C) above the LCWT. optional variable-speed hydronic package with sensorless
technology to meet this market requirement.
NOTE: Recirculation flow is shown below.
The major cost of a pump over its lifetime will be energy
RECIRCULATION FLOW consumption and maintenance, and both of these factors
will be reduced using variable-speed pumping. Energy is
saved by the combination of lowering the pump speed in
conjunction with the resulting lowering of pumping system
resistance when conditions permit. Maintenance benefits
from the sensorless pumping system include the lack of the
need to maintain remote sensors as well as the beneficial
effects of lower speed/pressure on the pump and pump
bearings.
a30-4042 Another advantage associated with variable-speed
pumping is reduced system noise in part load operation
when the pump is running at lower speeds. The variable-
Maximum cooler flow The maximum cooler flow speed pump package offered on the 30RB chiller is offered
(see the Minimum and Maximum Cooler Flow Rates table both in single and dual-pump designs. In the dual pump
on page 83) results in a practical maximum pressure drop case, in which one pump is the back-up of the other, each
through cooler. pump connection is fitted with an isolation valve which
Return fluid may bypass the cooler to keep the pressure allows one pump to be isolated for service with the other
drop through the cooler within acceptable limits. This per- pump still operating.
mits a higher delta T with lower fluid flow through cooler As already mentioned, the 30RB variable-speed
and mixing after the cooler. The mixed temperature enter- hydronic package employs sensorless technology. The
ing the cooler must be maintained to a minimum of at least term sensorless means that no remote sensors are
3 F (1.7 C) above the LCWT and to a maximum of no required for pump operation. The sensorless pump control
more than 20 F (11.1 C) above the LCWT. monitors system requirements from pump speed and
NOTE: Bypass flow is shown below. power. The hydronic unit is provided with a pre-defined
control curve to automatically adjust speed at all operating
BYPASS FLOW conditions. Pump performance and characteristic curves
for multiple speeds are programmed into the speed-con-
troller memory. The pre-programmed information includes
power, pressure and flow throughout the entire range of
the pump. During chiller operation, the power and speed
of the pump are monitored. This enables the controller to
establish the hydraulic performance, and to position the
pump's head-flow characteristic. Although this curve is pre-
defined, it is also fully field adjustable. The pump has a
a30-533 graphical user interface, and the graphic keypad can also
be used to allow manual pump speed control.
Variable cooler flow rates This variable-speed pumping system easily connects to
Variable flow rates may be applied to a standard chiller. BMS (Building Management System) systems (BACnet is
The unit will, however, attempt to maintain a constant standard, and LON can be obtained via special order). The
leaving chilled water temperature. In such cases, the mini- pumps may be controlled directly by the BMS system. The
mum flow must be in excess of the minimum flow given in sensorless feature can also be switched off to allow the use
the Minimum and Maximum Cooler Fluid Flow Rates table of either a 0 to 10 VDC signal or a 0 to 20 mA signal.
(page 83), adjusted for glycol in the system, and the mini- For multiple chiller applications employing the variable-
mum fluid volume must be in excess of 3 gallons per ton speed pumping package, such as chillers operated in a par-
(3.2 L per kW). The flow rate must change at a rate less allel arrangement, the drives must be connected by control
82
wiring and set up to run the same speed. This is to prevent As a specific example, let us say the schedule calls for a
surging or hunting of the speed set point. One drive will 100-ton, fresh-water chiller, and it is desired to have a con-
act as the master while the other slave drive will run at the stant 10-degree temperature difference in part load opera-
same speed. The master drive may be controlled by a 0 to tion (say 54 to 44 F). The schedule calls for 240 gpm at full
10 VDC signal, a 0 to 20 mA signal, or a BMS. The drive load based upon the desired capacity and the fluid tem-
must be configured to not use the sensorless function in perature difference. A constant temperature difference in
this arrangement. part load operation is essentially the same as providing
A typical example of a chiller operating with a variable- flow in direct proportion to chiller load. In the present
speed pumping system would be the case when the user example, this means that 100% load will run at the sched-
requires the chiller to operate with a constant fluid tem- uled 240 gpm, 90% load will be 216 gpm, etc. down to
perature difference as the load is reduced. This can be the minimum allowable flow for this unit size, which, in the
accomplished with the 30RB variable-speed pumping case of a 30RB100, is 120 gpm. The chiller in this exam-
package with the understanding that the minimum allow- ple will therefore be able to run down to 50% load while
able flow for the chiller must be respected. Once that limit approximately maintaining a constant 10 degree fluid tem-
is reached, the flow cannot be further reduced. To accom- perature difference, and then the flow will be held constant
plish this purpose, the minimum speed of the drive is pre- for all lower loads. Throughout the range in which flow is
set based upon the chiller size that is being employed. reduced (down to minimum allowable flow), the pump
speed is proportionally reduced, resulting in pump energy
savings.
30RB315-390
MINIMUM COOLER MAXIMUM COOLER MINIMUM COOLER MAXIMUM COOLER
UNIT FLOW RATE (gpm) FLOW RATE (gpm) MINIMUM LOOP FLOW RATE (l/s) FLOW RATE (l/s) MINIMUM LOOP
SIZE VOLUME (gal.) VOLUME (liters)
Module A Module B Module A Module B Module A Module B Module A Module B
315 192 192 768 768 945 12 12 48 48 3577
330 204 192 816 768 990 13 12 51 48 3748
345 204 204 816 816 1035 13 13 51 51 3918
360 228 204 912 816 1080 14 13 58 51 4088
390 228 228 912 912 1170 14 14 58 58 4429
*30RB chillers with Greenspeed intelligence are not available in size
060 and 070.
For minimum cooler flow rate with brine applications, refer to E-cat
software performance.
83
Application data (cont)
Fluid loop volume FOULING FACTORS
The volume in circulation must equal or exceed 3 gal. per
FOULING
nominal ton (3.25 L per kW) of cooling for temperature FOULING FACTOR
FACTOR CAPACITY
COMPRESSOR
(English) POWER
stability and accuracy in normal air conditioning applica- (ft2hrF/Btu) (SI) MULTIPLIER MULTIPLIER
(m2C/W)
tions. In process cooling applications, or for operation at
0.00025 0.000044 0.991 0.995
ambient temperature below 32 F (0 C) with low loading 0.00050 0.000088 0.977 0.987
conditions, there should be from 6 to 10 gal. per ton (6.5 0.00075 0.000132 0.955 0.979
to 10.8 L per kW). To achieve this volume, it is often nec- 0.00175 0.000308 0.910 0.952
essary to install a tank in the loop.
Tank should be baffled to ensure there is no stratification Cooler and hydronic system freeze protection
and that water (or brine) entering tank is adequately mixed Freeze protection for down to 20 F (28.9 C) for the
with liquid in the tank. cooler and hydronic package is available as a factory-
installed option. Since power is sometimes lost for extend-
TANK INSTALLATION ed periods during winter storms, freeze protection provid-
ed by heater tapes will be effective only if a back-up power
supply can be assured for the units control circuit, heater
and cooler pump. If not protected with an antifreeze solu-
tion, draining the cooler and outdoor piping is recom-
mended if the system will not be used during freezing
weather conditions.
BAD GOOD Two conditions that must be considered when determin-
ing antifreeze concentration are leaving water set point
and ambient freeze conditions. Both of these parameters
can help determine the recommended concentration level.
Higher concentration must be used to adequately protect
the machine.
NOTE: Use only antifreeze solutions approved for heat ex-
BAD GOOD changer duty.
a30-3185
For applications in which the leaving water temperature
The piping between the chiller and the fluid loop volume set point is less than 40 F (4.4 C), a suitable inhibited anti-
tank can be done to allow the tank to be on the return side freeze solution must be used. The solution concentration
of the chiller (tank piped to chiller inlet) or the supply side must be sufficient to protect the chilled water loop to a
of the chiller (tank piped to the chiller outlet). However, it is freeze protection (first crystals) concentration of at least
recommended that the tank be piped to the return side of 15 F (8.3 C) below the leaving water temperature set
the chiller to buffer any changes in load to allow more sta- point.
ble chiller operation. If the chiller refrigerant or fluid lines are in an area where
ambient conditions fall below 34 F (1 C), it is required that
Minimum time to power chiller before
start-up an antifreeze solution be added to protect the unit and fluid
piping to a temperature of 15 F (8.3 C) below the lowest
In order to ensure that the crankcase heaters are provided
anticipated ambient temperature.
sufficient time to raise the crankcase temperature to the
required operating point, power must be applied to the Select concentration based on either burst or freeze pro-
control circuit a minimum or 24 hours prior to chiller start- tection as dictated by the application. If the chiller does not
up. On 30RB chillers, the control circuit obtains its power operate during the winter, nor is a start-up expected, a
via a control transformer off the main 3-phase power sup- burst protection concentration is recommended. This con-
ply. Therefore, the main (3-phase) power is to be supplied centration may not be high enough to pump the fluid
at least 24 hours prior to chiller start-up unless there are through the unit. Burst protection is typically a lower con-
special means for providing control power. centration that will provide better performance from the
machine. If the chiller does operate during winter, a freeze
Cooler fouling factor protection concentration is recommended. This concentra-
The fouling factor used to calculate tabulated ratings is tion will be high enough to keep the fluid in a condition
0.00010 ft2 hr F/Btu (0.000018 m2 C/W). As foul- that it can be pumped at low ambient conditions.
ing factor is increased, unit capacity decreases and com-
pressor power increases. Corrections to published ratings IMPORTANT: Glycol anti-freeze solutions are highly
can be approximated by using the multipliers in the fouling recommended since heater tapes provide no protec-
factors table. tion in the event of a power failure.
84
High ambient temperature operation external static restrictions up to 0.2 in. wg (50 Pa) are as
High outdoor ambient chiller start-up and operation is pos- follows:
sible for standard 30RB chillers at ambient temperatures EXTERNAL STATIC CAPACITY COMPRESSOR
up to 125 F (52 C) at nominal voltage. In some cases, in. wg Pa MULTIPLIER POWER MULTIPLIER
where return water temperature is expected to exceed 0.0 0.0 1.000 1.00
60 F (15.5 C), an accessory kit may be required. 0.1 25 0.986 1.01
Low ambient temperature operation 0.2 50 0.968 1.03
Units will start and operate down to 32 F (0 C) as Condenser coil protection (Enviro-Shield)
standard. Refer to the environmental selection guides for more infor-
NOTE: Minimum load on chiller must be above the mini- mation. If the standard Novation (microchannel) coil does
mum step of unloading. not meet the corrosion requirements for a given applica-
With the inclusion of wind baffles (field-fabricated and tion, additional coil options are available. For specific geo-
installed) and low ambient head pressure control (low ambi- graphical recommendations, please refer to the NACO
ent control is not required on units with Greenspeed intel- (North American Commercial Operations) Packaged
ligence) the unit is capable to start as low as 13 F (25 C) Chiller Builder program.
and be operational to as low as 20 F (29 C) ambient Aluminum fin/copper tube coils are constructed of
temperature. Inhibited propylene glycol or other suitable seamless copper tubes mechanically bonded to aluminum
corrosion-resistant anti-freeze solution must be field sup- fins. The fins have wavy enhancements. These condenser
plied and installed in all units for unit operation below 34 F coils are recommended with remote cooler applications.
(1.1 C). Solution must be added to fluid loop to protect These coils are not recommended for corrosive environ-
loop down to 15 F (8.3 C) below minimum operating ments.
ambient temperature. Concentration should be based on Pre-coated aluminum-fin coils have a durable epoxy-
expected minimum temperature and either Burst or phenolic coating applied to the fin prior to the fin stamping
Freeze protection levels. At least 6 gal. per ton (6.5 L process to provide protection in mildly corrosive coastal
per kW) of water volume is the recommended minimum for environments. Pre-coated coils have an inert barrier
a moderate system load. between the aluminum fin and copper tube. This barrier
High-efficiency variable condenser fans electrically disconnects the dissimilar metals to minimize
the potential for galvanic corrosion. This economical
Highly efficient part load performance is available with option provides substantial corrosion protection beyond
variable speed condenser fan motors controlled by variable the standard uncoated coil construction.
speed drives. In most applications, the chiller will run at
part load conditions the vast majority of the time, and this Copper-fin coils provide increased corrosion resistance
is particularly the case if the application has a 24/7 duty compared to aluminum fin coils. All-copper coils eliminate
cycle. This option will lower utility costs while producing a bimetallic construction to eliminate the potential for gal-
scroll compressor design that provides excellent part load vanic corrosion. Application in industrial environments is
efficiency. This is the essence of 30RB chillers with Green- not recommended due to potential attack from sulfur, sul-
speed intelligence. (High-efficiency variable condenser fur oxide, nitrogen oxides, carbon and several other indus-
fans are not available with sizes 060 and 070.) trial airborne contaminants.
E-coated Novation coils have an extremely flexible
Altitude correction factors and durable epoxy coating uniformly applied to all coil sur-
Correction factors must be applied to standard ratings faces. Unlike brittle phenolic dip and bake coatings, e-coat
at altitudes above 2000 ft (610 m) using the following provides superior protection with unmatched flexibility,
multipliers: edge coverage, metal adhesion, thermal performance and
ALTITUDE CORRECTION FACTORS most importantly, corrosion resistance. E-coated coils
provide this protection since all coil surfaces are complete-
COMPRESSOR
ALTITUDE ALTITUDE CAPACITY
POWER ly encapsulated from environmental contamination. This
(ft) (m) MULTIPLIER
MULTIPLIER option provides the best protection for Novation coil
2,000 610 0.99 1.01 technology. E-coated aluminum microchannel coils shall be
4,000 1220 0.98 1.02 capable of withstanding an 8000-hour salt spray test in ac-
6,000 1830 0.97 1.03 cordance with the ASTM (American Society for Testing
8,000 2440 0.96 1.04 and Materials) (U.S.A.) B-117 Standard.
10,000 3050 0.95 1.05
E-coated aluminum-fin coils have the same flexible and
Condenser airflow durable epoxy coating as e-coated Novation coils. This op-
Airflow restrictions on units with standard fans will affect tion provides better protection compared to standard or
the unit capacity, condenser head pressure, and compres- pre-coated aluminum-fin coils in many environments.
sor power input. Correction factors to be applied for E-coated copper-fin coils have the same flexible and
durable epoxy coating as other e-coated coils. However,
this option combines the natural salt and environmental re-
sistance of all-copper construction with the highest level of
85
Application data (cont)
corrosion protection within the round-tube, plate-fin type The AquaSnap 30RB chiller will require a field-
of coils. supplied expansion tank when the optional pumping pack-
age is provided.
Electrical/utility interests
The expansion tank is based on fluid type, temperature
Use of energy management practices can significantly range, fluid pressure and loop volume.
reduce operating costs, especially during off-peak modes
of operation. Demand limiting and temperature reset are 2 Parallel chillers with hydronic packages require that
techniques for accomplishing efficient energy manage- pump inlets be equalized to prevent pump cavitation.
ment. See Demand Limiting (also called load shedding) sec- Pump expansion tanks must be removed and located
tion below for further details. together in the common pump suction header. All materi-
als needed for expansion tank relocation are field supplied.
Demand limiting (load shedding) Appropriate measures must be taken for freeze protection.
When a utilitys demand for electricity exceeds a certain NOTE: The hydronic package is not available on units
level, loads are shed to keep electricity demand below a equipped with the heat reclaim option.
prescribed maximum level. Typically, this happens on hot
days when air conditioning is most needed. The energy Air separation
management module (EMM) can be added to accomplish The AquaSnap 30RB chiller will require a field-supplied air
this reduction. Demand may be limited on unit by resetting separation device when the optional pumping package is
fluid temperature, or by unloading the chiller to a given provided.
predetermined percentage of the load. Demand limit may Air must be controlled in a hydronic system if it is to per-
also be driven by an external 4 to 20 mA signal. These fea- form properly. Air can block the flow of chilled water to its
tures require a signal from an intelligent central control. Do destinations and can cause cavitation in the pump, which
not cycle demand limiter for less than 10 minutes on and will aerate the pump and potentially cause pump failure.
5 minutes off. Duty cycling cycles electrical loads at regular The air separator is sized according to the total flow
intervals regardless of need. This reduces the electrical through the system. The air separator should be located
operating costs of building by fooling demand indicating inside the building. There are several types of air separa-
devices. Duty cycling of compressors or fans is not recom- tors to choose from. For more information and product
mended since motor winding and bearing life will suffer selection contact your local manufacturers representative.
from constant cycling.
Heat reclaim
Remote on-off control
Whenever a chiller is operating, the heat removed from the
Remote on-off control may be applied by hard-wired con- cooler fluid as well as the energy associated with the com-
nection (see Controls and Troubleshooting literature) or by pression process must be moved to another location.
connection to a Carrier Comfort Network (CCN) system. Under standard operation, an air-cooled chiller moves and
Optional hydronic system selection releases this heat to the atmosphere. There are times,
Select pump gpm from resulting chiller selection and total however, when it is beneficial to capture this heat and con-
pressure loss in the system plus the chiller internal pressure vert it into useful hot water.
loss. The heat reclaim option has been developed to serve this
NOTE: Maximum gpm (L/s), pressure and pump hp must purpose. Unlike many heat reclaim schemes seen on the
not exceed maximum on pump curve. market, the heat reclaim option that has been developed
for the 30RB chiller is full condensing. This means that this
NOTE: Optional hydronic system is available in both water-cooled condenser, which is in parallel with the
constant-speed and VFD configurations, as described in standard air-cooled condenser, is capable of capturing all of
the Variable Cooler Flow Rates section. the heat available from the chiller condensing process. The
Pump flow can be reduced by using the factory-supplied leaving-water temperature can reach at maximum 131 F
triple-duty valve up to 10%. Beyond that, impeller (55 C) under steady state and constant hot water flow con-
trimming is recommended to reduce energy consumption. ditions with an allowable hot water temperature range
Follow local codes or ASHRAE 90.1 recommendations. from 68 to 131 F (20 to 55 C).
Contact your Carrier representative for specific amount of
trim required.
86
TYPICAL MULTIPLE CHILLER CONFIGURATION WITH AIR ELIMINATOR AND EXPANSION TANK LOCATION
DUAL CHILLER
LVG SENSORS
DISTRIBUTION
T PUMP
CHILLER 1
CHILLER 2
ZONE 1
ZONE 2
ZONE 3
EXPANSION
TANK(S)
AIR ELIMINATOR
WITH VENT
COLD WATER
To operate in the heat reclaim mode, there must be a Chiller Performance at AHRI Conditions with Heat
simultaneous need for chilled water and tempered hot Reclaim (104 F/114 F) in Operation:
water. Just as the chiller operates in standard duty, the Cooling Capacity 96.3 tons (339.0 kW)
chiller always controls the leaving chilled water tempera-
Input Power 121.0 kW
ture. Consequently, the chiller will produce as much hot
water as possible while maintaining the leaving chilled Heating Output 1,548 MBH (453 kW)
water temperature.
To generate hot water, the entering hot water tempera- (453 kW + 339 kW) = 6.5
ture is compared to the hot water set point to determine 121.0 kW
the number of circuits necessary to maintain the entering
hot water temperature. If the entering hot water tempera- COP (TOTAL) = 6.5
ture is below the customer-adjustable set point, one refrig- Head pressure control A form of head pressure con-
eration circuit will automatically be changed over to the trol is required while in the heat reclaim mode. In order to
heat recovery mode to produce tempered hot water. In this meet this requirement, a 3-way control valve must be field-
mode, the chiller is operating as a water-cooled chiller with installed. Since the hot water temperature at start-up may
one circuit and as an air-cooled chiller with the other be very low, the 3-way valve is to be located as close to the
circuit. heating condenser as possible so that this valve can quickly
Depending on the entering hot water requirements, the accomplish its purpose of maintaining the minimum
second circuit may also be switched to the heat recovery required head pressure. In this regard, the 3-way valve is to
mode through the integrated controls. The entering hot be located with 40 ft (12.2 m) of the heating condenser.
water temperature is controlled by the cycling of each The 30RB chiller uses an analog output to control this
refrigerant circuit from the cooling-only to the heat recov- valve. See figure below. A minimum loop volume of 6 gal-
ery modes. When the hot water set point is satisfied, the lons per ton of heating (0.5 to 0.83 gallons [1.9 to 3.1 L]
chiller will transition back to the cooling-only mode as a per MBH of heating) capacity is necessary. In some cases,
conventional air-cooled chiller. The number of cycles is lim- this will require the installation of a hot-water buffer tank.
ited to 4 per hour.
The leaving hot-water temperature is a function of the THREE-WAY HEAD PRESSURE CONTROL VALVE
entering hot water temperature, hot water flow and chiller
capacity. In the heat reclaim mode, the entering hot water MODULATING 3-WAY
CONTROL VALVE
temperature, and not the leaving hot water temperature, is 40 FT MAX
TEMPERED WATER
controlled. As a consequence, these applications are useful TO WATER HEATER
87
Application data (cont)
Operating limits With a properly installed 3-way HEAT RECOVERY OPERATION ENVELOPE (STEADY
water valve, the minimum hot-water inlet temperature can STATE CONDITIONS REQUIRED)
be as low as 40 F (4 C) during system start-up. The hot NORMAL COOLING MODE USING AIR-COOLED
water flow range is from 2 to 4 gpm per heating ton CONDENSERS
(0.13 to 0.25 L per minute). See the Heat Recovery Oper-
COOLING ONLY CONDITIONS
ation Envelope tables on this page for the allowable range
MODE Min Nominal Max
of chiller operating conditions when the heat reclaim
F -20* 95 125
option has been selected. Condenser OAT
C -29* 35 52
Freeze protection The heat reclaim condenser is lo- F 38 (LWT) 54/44 60 (LWT)
cated within the standard chiller envelope. Therefore, this Cooler EWT/LWT
C 3 (LWT) 12/7 16 (LWT)
device, as well as its associated water piping, must be locat-
LEGEND
ed outdoors. A form of freeze protection must be provided.
EWT Entering Water (Fluid) Temperature
The heating condenser is provided with a heater that will LWT Leaving Water (Fluid) Temperature
accomplish freeze protection down to 0 F (17.8 C). If a OAT Outdoor Air Temperature
unit controls the water pump/valves, allowing for flow * With low-ambient option.
through the condenser, the unit is protected from freezing
down to 20 F (28.9 C). In addition, the same guideline HEAT RECOVERY MODE USING WATER-COOLED
CONDENSERS
for cooler freeze protection and preparation for winter
shutdown must be followed. The Carrier warranty does not HEAT RECOVERY CONDITIONS
cover damage due to freezing. The piping, however, must MODE Min Nominal Max
either be provided with heat trace or an antifreeze solution Condenser F 68* (EWT) 104/114 131 (LWT)
must be added to the hot water fluid. EWT/LWT C 20* (EWT) 40/46 55 (LWT)
Adding antifreeze solution is the only certain means of Cooler F 38 (LWT) 54/44 59 (LWT)
protecting the unit from freeze-up if the heater fails or elec- EWT/LWT C 3 (LWT) 12/7 15 (LWT)
trical power is interrupted or lost while temperatures are LEGEND
below 32 F (0 C). EWT Entering Water (Fluid) Temperature
LWT Leaving Water (Fluid) Temperature
General heat reclaim application data The heat
reclaim option may be selected for chiller sizes 30RB060- * Install three-way valve controls as required to ensure 68 F (20 C) min-
imum entering condenser temperature.
190, and exclusively with MCHX coils (either uncoated or Condenser water flow must be maintained such that the maximum
e-coated). No hydronic package option is available in con- heating condenser water temperature rise is no more than 20 F
junction with the heat reclaim option to conserve chiller (11 C) and the minimum heating condenser water temperature rise
is no less than 5 F (3 C).
footprint. As a result, the overall chiller dimensions are un-
changed when this option is selected. The cooler water
piping connections and the additional heating condenser
piping details are shown for this option in the Dimensions
section.
88
Guide specifications
Outdoor Air-Cooled Liquid Chiller B. Materials of Construction:
HVAC Guide Specifications 1. The base rail is industrial-quality, 7ga, zinc-
dipped, galvanized frame (with Magni-coated
Size Range: 60 to 390 Tons screws).
(210 to 1370 kW) Nominal
2. Cabinet shall be galvanized steel casing with a
80 to 390 Tons baked enamel powder or pre-painted finish.
(280 to 1370 kW) Nominal with
Greenspeed Intelligence 3. Cabinet shall be capable of withstanding
500-hour salt spray test in accordance with the
Carrier Model Number: 30RB ASTM (American Society for Testing and Mate-
Part 1 General rials) (U.S.A.) B-117 standard.
1.01 SYSTEM DESCRIPTION C. Fans:
Microprocessor controlled, air-cooled liquid chiller 1. Condenser fans shall be direct-driven (VFD
for outdoor installation, utilizing scroll compressors, [variable frequency drive] controlled on units
low sound fans and optional hydronic pump system. with Greenspeed intelligence), 9-blade airfoil
For units that incorporate Greenspeed intelligence, cross-section, reinforced polymer construction,
all fans are controlled with variable speed fan drive shrouded-axial type, and shall be statically and
motors. Chiller software shall be specifically devel- dynamically balanced with inherent corrosion
oped to coordinate optimal fan speed for applica- resistance.
tion conditions and provide refrigerant circuit 2. The variable speed drives for the condenser
optimization, resulting in higher part-load efficiency fans on 30RB units with Greenspeed intelli-
and reduced acoustic levels. gence shall include a DC link reactor.
NOTE: Hydronic pump packages are only available 3. Air shall be discharged vertically upward.
on 30RB060-190 units. Hydronic pump packages 4. Fans shall be protected by coated steel wire
are not available when optional heat reclaim is safety guards.
selected or on units with high SCCR option.
D. Compressor/Compressor Assembly:
1.02 QUALITY ASSURANCE
1. Fully hermetic scroll type compressors.
A. Unit shall be rated in accordance with AHRI (Air-
Conditioning, Heating and Refrigeration Institute) 2. Direct drive, 3500 rpm (60 Hz), protected by
Standard 550/590, latest edition (U.S.A.) and all motor temperature sensors, suction gas cooled
units shall be in compliance with ASHRAE (Ameri- motor.
can Society of Heating, Refrigeration, and Air-Con- 3. External vibration isolation rubber-in-shear.
ditioning Engineers) 90.1.2007 and ASHRAE 90.1 4. Each compressor shall be equipped with crank-
2010. case heaters to minimize oil dilution.
B. Unit construction shall comply with ASHRAE 15 E. Cooler:
Safety Code, UL (Underwriters Laboratories) latest 1. Shell-and-tube type, direct expansion.
edition, and ASME (American Society of Mechanical
Engineers) applicable codes (U.S.A. codes). 2. Tubes shall be internally enhanced seamless-
copper type rolled into tube sheets.
C. The management system governing the manufac-
ture of this product is ISO 9001: 2008 certified. 3. Shall be equipped with Victaulic-type water
connections.
D. Unit shall be full load run tested at the factory.
4. Shell shall be insulated with 3/4-in. (19-mm)
1.03 DELIVERY, STORAGE AND HANDLING
PVC foam (closed-cell) with a maximum K fac-
A. Unit controls shall be capable of withstanding tor of 0.28.
150 F (66 C) storage temperatures in the control
5. Design shall incorporate a minimum of 2 inde-
compartment.
pendent direct-expansion refrigerant circuits.
B. Unit shall be stored and handled per unit manufac-
6. Cooler shall be tested and stamped in accor-
turer's recommendations.
dance with ASME Code for a refrigerant work-
Part 2 Products ing side pressure of 445 psig (3068 kPa).
2.01 EQUIPMENT Cooler shall have a maximum water-side pres-
A. General: sure of 300 psig (2068 kPa).
Factory assembled, single-piece or factory-matched 7. Cooler shall be provided with a factory-installed
duplex chassis, air-cooled liquid chiller. Contained flow switch.
within the unit cabinet shall be all factory wiring, F. Condenser:
piping, controls, refrigerant charge (R-410A), and 1. Coil shall be air-cooled Novation heat
special features required prior to field start-up. exchanger technology with microchannel
(MCHX) coils and shall have a series of flat
tubes containing a series of multiple, parallel
89
Guide specifications (cont)
flow microchannels layered between the refrig- control and primary/standby sequencing to
erant manifolds. Coils shall consist of a two- ensure equal pump run time.
pass arrangement. Coil construction shall h. Dual chiller control for parallel chiller appli-
consist of aluminum alloys for fins, tubes, and cations without addition of hardware
manifolds in combination with a corrosion-resis- modules and control panels (additional
tant coating. thermistors and wells are required).
2. Tubes shall be cleaned, dehydrated, and sealed. i. Timed maintenance scheduling to signal
3. Assembled condenser coils shall be leak tested maintenance activities for pumps, strainer
and pressure tested at 656 psig (4522 kPa). maintenance and user-defined maintenance
G. Refrigeration Components: activities.
Refrigerant circuit components shall include j. Low ambient protection to energize cooler
replaceable-core filter drier, moisture indicating sight and optional heat reclaim or hydronic sys-
glass, electronic expansion device, discharge service tem heaters.
valve and liquid line service valves, and complete k. Periodic pump start to ensure pump seals
operating charge of both refrigerant R-410A and are properly maintained during off-season
compressor oil. periods.
H. Controls, Safeties, and Diagnostics: l. Single step demand limit control activated by
1. Unit controls shall include the following mini- remote contact closure.
mum components: m. Generation of 0 to 10 vdc signal to control
a. Microprocessor with non-volatile memory. 3-way valve position when optional heat
Battery backup system shall not be accepted. reclaim is employed.
b. Separate terminal block for power and n. Nighttime sound mode to reduce the sound
controls. of the machine by a user-defined schedule.
c. Control transformer to serve all controllers, 3. Diagnostics:
relays, and control components. a. The control panel shall include, as standard,
d. ON/OFF control switch. a scrolling marquee display capable of indi-
cating the safety lockout condition by
e. Replaceable solid-state controllers. displaying a code for which an explanation
f. Pressure sensors shall be installed to mea- may be scrolled at the display with time and
sure suction and discharge pressure. Therm- date stamp.
istors shall be installed to measure cooler b. Information included for display shall be:
entering and leaving fluid temperatures as
well as optional heat reclaim condenser 1) Compressor lockout.
entering and leaving fluid temperatures, and 2) Loss of charge.
refrigerant pump down pressure and 3) Low fluid flow.
temperature. 4) Cooler coil and optional heat reclaim coil
freeze protection.
2. Unit controls shall include the following 5) Cooler set point.
functions:
6) Optional heat reclaim set point.
a. Automatic circuit lead/lag. 7) Chilled water reset parameters.
b. Hermetic scroll compressors are mainte- 8) Thermistor and transducer malfunction.
nance free and protected by an auto-adaptive 9) Entering and leaving-fluid temperature.
control that minimizes compressor wear. 10) Evaporator and condenser pressure.
c. Capacity control based on leaving chilled 11) System refrigerant temperatures.
fluid temperature and compensated by rate 12) Chiller run hours.
of change of return-fluid temperature with 13) Compressor run hours.
temperature set point accuracy to 0.1 F 14) Compressor number of starts.
(0.06 C). 15) Time of day:
a) Display module, in conjunction with
d. Limiting the chilled fluid temperature pull- the microprocessor, must also be
down rate at start-up to an adjustable range capable of displaying the output
of 0.2 F to 2 F (0.11 C to 1.1 C) per (results) of a service test. Service test
minute to prevent excessive demand spikes shall verify operation of every
at start-up. switch, thermistor, fan, and com-
e. Seven-day time schedule. pressor before chiller is started.
f. Leaving chilled fluid temperature reset from b) Diagnostics shall include the ability to
return fluid and outside air temperature. review a list of the 30 most recent
g. Chilled water pump and optional heat alarms with clear language
descriptions of the alarm event. Dis-
reclaim condenser water pump start/stop
play of alarm codes without the
90
ability for clear language descriptions L. Chilled Water Circuit:
shall be prohibited. 1. Chilled water circuit shall be rated for 300 psig
c) An alarm history buffer shall allow (2068 kPa). Units with optional pump package
the user to store no less than 30 are rated for 150 psig (1034 kPa) working
alarm events with clear language pressure.
descriptions, time and date stamp
2. Thermal dispersion proof of flow switch shall be
event entry.
factory installed and wired.
d) The chiller controller shall include
multiple connection ports for com- 3. Optional hydronic package:
municating with the local equipment a. With or without VFD (variable frequency
network, the Carrier Comfort Net- drive) (30RB060-190 units only):
work (CCN) system and access to 1) Field pipe connections shall be Victaulic
chiller control functions from any type.
point on the chiller. 2) Optional single or primary/standby
e) The control system shall allow soft- operation pump systems. Dual pump
ware upgrade without the need for systems shall have a pump discharge
new hardware modules. check valve.
16) Crankcase heater failure. 3) Pumps shall be vertical in-line, single
4. Safeties: stage design, and capable of being ser-
a. Unit shall be equipped with thermistors and viced without disturbing piping connec-
all necessary components in conjunction tions.
with the control system to provide the unit a) Pump casing shall be of class 30 cast
with the following protections: iron.
b) The impeller shall be of cast bronze,
1) Loss of refrigerant charge.
closed type, dynamically balanced,
2) Reverse rotation.
keyed to the shaft and secured by
3) Low chilled fluid temperature.
locking cap screw.
4) Thermal overload.
c) The hydronic kit will be provided with
5) High pressure.
a flush line connection to ensure
6) Electrical overload.
lubrication at the seal face and allow
7) High heat reclaim leaving fluid tempera-
for positive venting of the seal
ture.
chamber.
b. Condenser fan and factory pump motors d) Each port shall be fitted with an isola-
shall have external overcurrent protection. tion valve that allow the units to
I. Operating Characteristics: operate in parallel or standby, yet
1. Unit shall be capable of starting and running at may be used to isolate one pumping
outdoor ambient temperatures from 32 F to unit for servicing or removal with the
125 F (0 to 52 C) for all sizes. other pump still running.
e) Pump shall be rated for 150 psig
2. Unit shall be capable of starting up with 95 F (1034 kPa) working pressure.
(35 C) entering fluid temperature to the cooler. f) The pump case shall have gage tap-
J. Motors: pings at the suction and discharge
Condenser-fan motors shall be totally enclosed nozzles and include drain ports.
single-speed, 3-phase type with permanently lubri- g) Dual pumps shall allow for the servic-
cated bearings and Class F insulation. ing of one pump without draining the
K. Electrical Requirements: chilled water loop.
h) Motors shall be premium efficiency,
1. Unit/module primary electrical power supply totally enclosed fan cooled (TEFC) 3-
shall enter the unit at a single location phase type with grease lubricated ball
(some chiller voltage/size combinations require bearings.
2 power supplies). i) Each pump shall be factory tested per
2. Unit shall operate on 3-phase power at the volt- Hydraulic Institute Standards.
age shown in the equipment schedule. 4) Pressure/temperature taps (3) shall be
3. Control points shall be accessed through termi- factory installed to measure the pressure
nal block. differential across the pump and across
the strainer.
4. Unit shall be shipped with factory control and
5) Combination valve (which includes
power wiring installed.
check, isolation, and modulation) shall
be factory installed. Pressure/tempera-
ture taps (2) shall be factory installed to
91
Guide specifications (cont)
measure the pressure differential across 5) The control shall have the following
the combination valve. additional features: Sensorless override
6) Hydronic assembly shall have factory- for BMS, manual pump control or
supplied electric freeze protection to closed loop PID control; programmable
20 F (29 C). skip frequencies and adjustable switch-
7) Piping shall be Schedule 40 black steel. ing frequency for noise/vibration
8) Cast iron or ductile iron body 1/8-in. control; auto alarm reset; motor pre-
perforated strainer. A factory-installed, heat function; six programmable digital
removable fine mesh start-up strainer inputs; two analog inputs; one
for initial run period shall be included. programmable analog/digital output;
The start-up strainer must be removed two volt-free contacts.
within 24 hours after chiller start-up. 6) The hydronic unit shall be capable of
b. With VFD (these comments are applicable in operating in any of the following control
addition to the comments in section a when modes:
the VFD hydronic package is employed a) Duty pump and standby pumps with
[30RB060-190 units only]): Sensorless control
b) Duty pump and standby pumps with
1) The drive shall be of the VVC-PWM
remote sensor or building system
(voltage vector control - pulse with mod- (BAS) control.
ulation) type, providing near unity dis-
placement power factor without the M. Special Features:
need for external power factor correc- Certain standard features are not applicable
tion capacitors at all loads and speeds. when the features designated by * are specified. For
2) The drive and motor protection shall assistance in amending the specifications, contact
include; motor phase to ground fault, your Carrier representative.
loss of supply phase, over voltage, 1. High-efficiency variable condenser fans:
under voltage, motor over temperature,
All fans on the unit shall have variable speed fan
inverter overload, over current. Over
motors to provide higher part load efficiency
current is not allowed, ensuring
and reduced acoustic levels. Each fan circuit
hydronic units will not overload the
shall have a factory-installed, independent vari-
motor at any point in the operating
able speed drive with display. Variable speed
range of the unit.
drives are rated IP-55 enclosures and UL
3) Sensorless control software shall be
Listed. The use of this option, with the addition
available in the hydronic unit to provide
of antifreeze in the cooler circuit and wind baf-
automatic speed control without the
fles, shall allow running with outdoor ambient
need for pump mounted (internal/exter-
temperatures down to 20 F (28.9 C). This
nal) or remotely mounted differential
option is not available with sizes 060 and 070,
pressure system feedback sensors.
and it is not available in combination with low
Control mode setting and minimum/
ambient head pressure control.
maximum head set points shall be set at
the factory and be user adjustable via * 2. Low Ambient Head Pressure Control:
the programming interface. Unit shall be capable of running at outdoor
4) The integrated control shall incorporate ambient temperatures down to 20 F (29 C)
an integrated graphical user interface with the addition of antifreeze in the cooler cir-
that shall provide running and diagnos- cuit, wind baffles, and field-installed or factory-
tic information and identify faults and installed solid-state head pressure control with
status in clear English language. Faults condenser coil minimum step capacity tempera-
shall be logged/recorded for review at a ture sensor. This option or accessory is neither
later date. It shall be possible to upload required nor available with the high-efficiency
parameters from one drive into the non- variable condenser fan option.
volatile memory of a computer and 3. Unit-Mounted Non-Fused Disconnect:
download the parameters into other
drives requiring the same settings. The Unit shall be supplied with factory-installed,
key pad shall incorporate Hand-Off- non-fused electrical disconnect for main power
Auto pushbuttons to enable switching supply. This option is not available on
between BMS (Building Management 30RB060-120 with dual point power. This
System) and manual control. The drive option is included with the high SCCR option.
shall incorporate a USB port for direct 4. Optional Condenser Coil Materials:
connection to a PC and an RS485 con- a. E-coated microchannel coils:
nection with Modbus RTU protocol. E-coated aluminum microchannel coil shall
Optional protocols available should have a flexible epoxy polymer coating uni-
include BACnet and LonWorks.
formly applied to all coil external surface
92
areas without material bridging between fins including fin edges. Superior hardness char-
or louvers. Coating process shall ensure acteristics of 2H per ASTM D3363-92A
complete coil encapsulation, including all and cross hatch adhesion of 4B-5B per
exposed fin edges. E-coat shall have a thick- ASTM D3359-93. Impact resistance shall be
ness of 0.8 to 1.2 mil with top coat having a up to 160 in./lb (ASTM D2794-93). Humid-
uniform dry film thickness from 1.0 to 2.0 ity and water immersion resistance shall be
mil on all external coil surface areas includ- up to minimum 1000 and 250 hours respec-
ing fin edges. E-coated coils shall have supe- tively (ASTM D2247-92 and ASTM D870-
rior hardness characteristics of 2H per 92). Corrosion durability shall be confirmed
ASTM D3363-00 and cross hatch adhesion through testing to no less than 3000 hours
of 4B-5B per ASTM D3359-02. Impact salt spray per ASTM B117-90. Coil
resistance shall be up to 160 in./lb (ASTM construction shall be aluminum fins mechan-
D2794-93). E-coated coil shall have superior ically bonded to copper tubes.
impact resistance with no cracking, chip- f. E-coated copper-fin coils:
ping, or peeling per NSF/ANSI 51-2002
Coil shall have a flexible epoxy polymer
Method 10.2. E-coated aluminum micro-
coating uniformly applied to all coil surface
channel coils shall be capable of withstand-
areas without material bridging between fins.
ing an 8000-hour salt spray test in accor-
Coating process shall ensure complete coil
dance with the ASTM (American Society
encapsulation. Color shall be high gloss
for Testing and Materials) (U.S.A.) B-117
black with gloss 60 of 65 to 90% per
Standard.
ASTM D523-89. Uniform dry film thickness
b. Aluminum fin/copper tube coils: from 0.8 to 1.2 mil on all surface areas
Coil shall be constructed of seamless copper including fin edges. Superior hardness
tubes mechanically bonded to aluminum fins. characteristics of 2H per ASTM D3363-
Fins shall have wavy enhancements. These 92A and cross hatch adhesion of 4B-5B per
condenser coils are recommended with ASTM D3359-93. Impact resistance shall be
remote cooler applications. These coils are up to 160 in./lb (ASTM D2794-93).
not recommended for corrosive environ- Humidity and water immersion resistance
ments. shall be up to minimum 1000 and 250
c. Pre-coated aluminum-fin coils: hours respectively (ASTM D2247-92 and
ASTM D870-92). Corrosion durability shall
Coil shall have a durable epoxy-phenolic
be confirmed through testing to no less than
coating to provide protection in mildly corro- 3000 hours salt spray per ASTM B117-90.
sive coastal environments. Coating shall be Coil construction shall be copper-fins
applied to the aluminum fin stock prior to
mechanically bonded to copper tube sheets.
the fin stamping process to create an inert Galvanized steel tube sheets shall not be
barrier between the aluminum fin and cop- acceptable. A polymer strip shall prevent
per tube. Epoxy-phenolic barrier shall mini-
coil assembly from contacting sheet metal
mize galvanic action between dissimilar coil pan to maintain coating integrity and
metals. minimize corrosion potential between the
d. Copper-fin coils: coil and pan.
Coil shall be constructed of copper fins 5. Optional Heat Reclaim Condenser:
mechanically bonded to copper tubes and a. Condenser shall be capable of full heat
copper tube sheets. Galvanized steel tube
recovery.
sheets shall not be acceptable. A polymer
strip shall prevent coil assembly from b. Condenser shall be water cooled, with
contacting sheet metal coil pan to minimize Victaulic piping connections.
potential for galvanic corrosion between the c. Condenser shall be flooded, shell and tube
coil and pan. All-copper construction shall type, with mechanically cleanable tubes and
provide protection in moderate coastal removable heads.
applications. d. Shell shall be insulated with 3/4 in. (19 mm)
e. E-coated aluminum-fin coils: PVC foam (closed cell) with a maximum K
Coil shall have a flexible epoxy polymer factor of 0.28.
coating uniformly applied to all coil surface e. Tubes shall be internally enhanced, seamless
areas without material bridging between fins. copper type, rolled into tube sheets.
Coating process shall ensure complete coil f. Condenser shall be tested and stamped in
encapsulation. Color shall be high gloss accordance with ASME Code for a refriger-
black with gloss 60 of 65 to 90% per ant working pressure of 656 psig
ASTM ID523-89. Uniform dry film thick- (4522 kPa). The condenser shall have a
ness from 0.8 to 1.2 mil on all surface areas
93
Guide specifications (cont)
maximum water-side pressure of 300 psig 11. Upper Hail Guard:
(2068 kPa). Unit shall be equipped with a factory-installed
g. Condenser shall be leak and pressure tested option consisting of louvered panels on the
at 722 psig (4977 kPa). ends of the machine which firmly fasten to the
h. Condenser design shall incorporate 2 inde- machine frame. These panels shall cover the
pendent refrigerant circuits. unit from the top to the bottom of the coils,
i. Condenser shall have a factory-installed and thus providing protection of the coils from hail
wired thermistor in both the entering and damage.
leaving nozzles, as well as a factory-installed 12. Full Hail Guard:
and wired flow switch.
Unit shall be equipped with field-installed acces-
j. Condenser shall be equipped with a heater
sory consisting of hinged, louvered panels,
which is controlled by the chiller.
which cover both ends of the unit. This acces-
k. Condenser shall control the return (entering) sory provides complete protection from hail.
hot water temperature.
13. Full End Screen:
l. Condenser shall have a vent and drain.
Unit shall be equipped with a factory-installed
m. Condenser shall have a relief valve per cir- option consisting of louvered panels that cover
cuit (2 total). the machine ends from top to bottom and
NOTE: When a heat reclaim condenser is spec- firmly fasten to the machine frame. These end
ified, the air-cooled condenser coils must be screens function as a privacy screen and also
either MCHX or e-coated MCHX type. provide hail protection.
6. Remote Enhanced Display: 14. BACnet* Communication Option:
Unit shall be supplied with indoor-mounted, Shall provide pre-programmed factory-installed
remote, 40-character per line, 16-line display communication capability with a BACnet MS/
panel for field installation. TP network. Allows integration with i-Vu
7. Chillervisor System Manager Multi-Unit Open control system or a third-party BACnet
Control: building automation system. No field program-
ming shall be required.
Field-installed control shall sequence between 2
and 8 chillers in parallel in a single system. 15. BACnet/Modbus Translator Control:
8. Minimum Load Control: Unit shall be supplied with factory or field-
installed interface between the chiller and a
Unit shall be equipped with factory (or field)
BACnet Local Area Network (LAN, i.e., MS/
installed, microprocessor-controlled, minimum
TP EIA-485). Field programming shall be
load control that shall permit unit operation
required.
down to a minimum of 6% capacity (varies with
unit size). This option/accessory is not available 16. LON Translator Control:
on applications with leaving fluid temperature Unit shall be supplied with factory or field-
less than 38 F (3.3 C). installed interface between the chiller and a
9. Energy Management Control Module: Local Operating Network (LON, i.e., Lon-
Works** FT-10A ANSI/EIA-709.1). Field pro-
A factory or field-installed module shall provide
gramming is required.
the following energy management capabilities:
4 to 20 mA signals for leaving fluid temperature 17. Navigator Hand Held Display:
reset, cooling set point reset or demand limit a. Portable hand held display module with a
control; 2-step demand limit control (from 0% minimum of 4 lines and 20 characters per
to 100%) activated by a remote contact closure; line, of clear English, Spanish, Portuguese or
and discrete input for Ice Done indication for French language.
ice storage system interface. b. Display menus shall provide clear language
10. Condenser Coil Trim Panels and Security descriptions of all menu items, operating
Grilles: modes, configuration points and alarm
Unit shall be supplied with factory or field- diagnostics. Reference to factory codes shall
installed coil covers and painted grilles to not be accepted.
protect the condenser coil and internal chiller c. RJ-14 connection plug shall allow display
components from physical damage. module to be connected to factory-installed
receptacle.
95
Carrier Corporation Syracuse, New York 13221 1-17
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Pg 96 Catalog No. 04-52300089-01 Printed in U.S.A. Form: 30RB-23PD
Replaces: 30RB-22PD