Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

3VL 1706-1dd36-0aa0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Product data sheet 3VL1706-1DD36-0AA0

CIRCUIT-BREAKER VL160X N STANDARD BREAKING


CAPACITY ICU=55KA / 415 V AC 3 POLE,
LINE PROTECTION OVERCURRENT RELEASE TM,
LI IN=63A, RATED CURRENT IR=50-63A,
OVERLOAD II=600A,
SHORT-CIRCUIT WITH SCREW CONNECTION

Similar to image

General technical data:


Number of poles 3

Design of the overcurrent release TM

Acceptability for application system protection

Electrical operating cycles as operating time / typical 10,000

Mechanical operating cycles as operating time / typical 20,000

Active power loss / maximum W 70

Product component

auxiliary switch No

Voltage trigger No

undervoltage release mechanism No

undervoltage release with leading contact No

Product function

of the thermal overload release adjustable

ground-fault protection No

for zero conductors / short-circuit and overload protection No

overload protection Yes

Operating cycles / maximum 1/s 120

Protection class IP IP20

3VL1706-1DD36-0AA0 subject to modifications


Page 1/ 4 11/24/2013 Copyright Siemens AG 2013
Protective function of the overcurrent release LI

Impulse voltage resistance / rated value kV 8

Ambient temperature

during operating C 0 70

during storage C -40 +80

Main circuit:
Insulation voltage / for AC / rated value V 800

Operating frequency

1 / rated value Hz 50

2 / rated value Hz 60

Item designation

according to DIN 40719 extendable after IEC 204-2 / according Q


to IEC 750

according to DIN EN 61346-2 Q

Operating voltage / for main circuit

at 50 Hz / with AC

maximum V 690

at 60 Hz / with AC

maximum V 690

Operating voltage / for main current circuit / for DC

maximum V 500

Operating current

at 40 C / rated value A 63

at 50 C / rated value A 63

at 60 C / rated value A 58.6

at 70 C / rated value A 54.2

Continuous current / rated value A 63

Derating temperature / for the rated value of the continuous C 50


current

Auxiliary circuit:
Number of NC contacts / for auxiliary contacts 0

Number of NO contacts / for auxiliary contacts 0

Short-circuit:
Adjustable response current

of the current-dependent overload release A 50 63

of the non-delayed short-circuit release A 600 600

Breaking capacity limit short-circuit current (lcu) / at 415 V / kA 55


rated value

3VL1706-1DD36-0AA0 subject to modifications


Page 2/ 4 11/24/2013 Copyright Siemens AG 2013
Installation/mounting/dimensions:
Type of mounting fixed mounting

Height mm 157.5

Width mm 104.5

Depth mm 106.5

Connections:
Arrangement of electrical connectors / for main current circuit front side

Design of the electrical connection / for main current circuit screw-type terminals

Type of the connectable conductor cross-section

for main contacts

solid 2.5 ... 95 mm

stranded 2.5 ... 95 mm

for auxiliary contacts

solid 0.75 ... 1.5 mm

finely stranded / with conductor end processing 0,75 ... 1.0 mm

Certificates/approvals:
General Product Declaration of Conformity
Approval

TSE

Shipping Approval

other

Confirmation other Environmental


Confirmations

Further information:
Information- and Downloadcenter (Catalogs, Brochures,)
http://www.siemens.com/lowvoltage/catalogs

Industry Mall (Online ordering system)


http://www.siemens.com/lowvoltage/mall

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)


http://support.automation.siemens.com/WW/view/en/3VL1706-1DD36-0AA0/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VL1706-1DD36-0AA0

CAx-Online-Generator
http://www.siemens.com/cax

3VL1706-1DD36-0AA0 subject to modifications


Page 3/ 4 11/24/2013 Copyright Siemens AG 2013
Tender specifications
Datanorm GAEB81 GAEB83 RTF TXT

last change: Aug 12, 2013

3VL1706-1DD36-0AA0 subject to modifications


Page 4/ 4 11/24/2013 Copyright Siemens AG 2013