Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Solar Power Factor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4
At a glance
Powered by AI
The key takeaways are that power factor is a measure of the phase difference between voltage and current in an AC system, and non-unity power factor is caused by capacitive and inductive loads which leads to reactive power. This impacts the grid and can be improved by grid-connected PV systems with reactive power control.

A non-unity power factor means a load is consuming both active and reactive power. Reactive power does no useful work but is needed to maintain voltage in the system. A poor power factor requires the grid to generate and transmit more current than is actually needed by the load, increasing costs.

Capacitive and inductive loads such as capacitor banks and induction motors cause the current to lead or lag the voltage, resulting in a non-unity power factor. This is because they consume both active and reactive power.

www.gses.com.

au

GSES Technical Papers

Power Factor and Grid-Connected


Photovoltaics
As the level of Grid-Connected PV penetration power (also known as real or true power) is the useful
continues to rise, the importance of power factor component of the AC power and is what contributes
and power factor correction is going to become to the work done in a system (e.g. rotation of a motor
increasingly relevant both from the perspective of shaft or the glowing of a light bulb). Reactive power
the grid and the customer. oscillates between the generation source and the
load, and does no work in the system. Reactive
This article explains what power factor is, what it
power however is needed to maintain the voltage in
is caused by, its impact on the grid, and how Grid-
the system, provide magnetizing power to motors
Connected PV can both degrade and improve
and facilitate the transmission of the active power
power factor in a system.
through the AC circuit.
What is Power Factor?
The relationship between active and reactive
Power factor is a measure of the phase difference power is shown in Figure 2. The vectors for active
between the voltage and current in an AC power (measured in Watts) and reactive power
power system. In purely resistive loads (such as (measures in Volt Amps reactive VAr) are added
an incandescent lightbulb or electric kettle) the at right angles to give apparent power (measured
current is in phase with the voltage and there in VA). Apparent power is what a generator must
is unity power factor. Capacitive and inductive produce. The phase angle is given by the angle
loads (such as a capacitor banks or inductive motor between the active power vector, and apparent
respectively) will cause the current to lead or lag power vector. Power factor can then be calculated
the voltage, resulting in a non-unity power factor. by taking the cosine of this angle. As reactive power
An example of a lagging and unity power factor is is increased, the phase angle also increases, resulting
shown in Figure 1. in a lower power factor. If the reactive power is
reduced to zero, the phase angle also becomes zero,
+ giving a power factor of = 1 (unity power factor).
Voltage and Current

Voltage
Current for inductive loads
Current for resistive loads
Time
Apparent
power (VA) Reactive
power (var)
Phase
90 180 270 360
angle ()
Phase difference
Active power (W)
Figure 1: AC power system with a lagging power factor Power factor = cos
(current is lagging the voltage) and unity power factor
Figure 2: Phase diagram of AC power showing
A non-unity power factor means a load is active power, reactive power, and apparent power
consuming both active and reactive power. Active

Page | 1

Creating sustainable change through education, communication and leadership

Copyright 2015 Global Sustainable Energy Solutions Pty Ltd. All Rights Reserved.
www.gses.com.au

GSES Technical Papers

A common analogy of AC power is to a glass of about the direction of energy flow. A positive sign
beer (Figure 3). Reactive power is analogous with indicates import mode and a negative sign indicates
the head of the beer, while the liquid beer is active export mode.
power (that does the work), giving apparent power
In quadrants 1 and 4, a positive reactive power
as everything contained in the glass.
indicates an inductive load and a negative reactive
power indicates a capacitive load in the import
Reactive power (var)
mode. On the other hand in export mode quadrants
2 and 3, an inductive generator is indicated by a
positive reactive power and a capacitive generator
Apparent is indicated by a negative reactive power.
Active power (VA)
Positive reactive power
power (W) Export mode, inductive
Q
Import mode, inductive
negative active power positive active power
negative cos phi positive cos phi
positive reactive power positive reactive power
Quadrant 1
Quadrant 2 S
Q
P P
Negative active Positive active
power power
Quadrant 3 Quadrant 4
Export mode, capacitive Import mode, capacitive
Figure 3: The beer analogy of apparent power negative active power
negative cos phi
positive active power
positive cos phi
negative reactive power negative reactive power
Negative reactive power

Power factor is the cosine of the phase angle in


a power triangle. It is defined as the ratio between Figure 4 : 4 quadrant representation
the active power (W) and the apparent power (VA). of power factor and power flow
Power factor will vary between 0 and 1, and be
either leading or lagging.
Power Factor and the Grid
Active power (W) The supply of reactive power is very important in
Power factor = cos = an AC power grid. The amount of reactive power
Apparent power (VA)
produced by generators must closely match that
which is being consumed. A leading power factor
For purely resistive loads (such as heaters and in the system (due to capacitive loads) causes the
incandescent lamps) the voltage and current are voltage to rise and a lagging power factor (due
in synchronization, therefore they have a power to inductive loads) will cause the voltage to fall. If
factor of 1, or unity power factor. With inductive reactive power is either under or over supplied,
loads (such as induction motors) the current lags the the voltage on the network may rise or fall to a
voltage, therefore they have a lagging power factor. point where generators must switch off to protect
With capacitive loads, (such as capacitor banks), themselves thereby decreasing the generation and
the current leads the voltage, therefore they have a cause further problems.
leading power factor.
As can be seen from the phase diagram, increasing
the reactive power increases the apparent power
Four Quadrant representation of Power but has no effect on the active power. This means
Factor that the generators in the system must supply more
apparent power even though there is no additional
Figure 4 below shows the 4 quadrant representation work being done by the system (as there is no
of power flow and power factor. The sign of active increase in active power). Therefore power factor is
power P and power factor (cos ) provides details best corrected locally. The most common way for

Power Factor and Grid-Connected Photovoltaics Page | 2

Creating sustainable change through education, communication and leadership

Copyright 2015 Global Sustainable Energy Solutions Pty Ltd. All Rights Reserved.
www.gses.com.au

GSES Technical Papers

this to be performed is by using banks of capacitors from the grid has been reduced to 40kW, while the
that can be shunted in and out of the system reactive power imported from the grid remains
depending on the operation of the load. constant at 32.9kVAr. As can be seen from the phase
diagram, this has the effect of reducing the power
Residential customers do not consume enough
factor to 0.77 - lagging.
energy to warrant the additional costs of metering
equipment to measure power factor. Large industrial
and commercial customers however are billed for Active power = 60 kW
Active power
consuming power at a poor power factor. There = 40 kW
is therefore an incentive for these customers to
improve the power factor of their loads and reduce
the amount of reactive power they draw from Reactive power
the grid. Grid = 32.9 kvar
Factory
Power Factor and Grid Connected PV
Systems
Most grid connected PV inverters are only set up to Apparent Power Reactive Power consumed
inject power at unity power factor, meaning they (from grid) (from grid) Q = 32.9kVAr
S = 51.79kVA
only produce active power. In effect this reduces the
power factor, as the grid is then supplying less active 39.4 Active Power offset
power, but the same amount of reactive power. (solar) P = -60kW

Consider the situation in Figure 5. The factory is Active Power consumed


consuming 100kW of active power, and 32.9kVAr P = 100kW
of reactive power, resulting in a power factor of
0.95 lagging.
Figure 6: Factory with 60kW PV system
Active power
Power factor = 0.95
producing power at a unity power factor
= 100 kW
This problem of poor power factor however can
be addressed through the selection of appropriate
Reactive power inverter products. Inverters with reactive power
Grid = 32.9 kvar control can be configured to produce both active
Factory and reactive power, i.e. an output that is at a non-
unity power factor. This means that the power factor
Apparent Power for the load can be kept within reasonable limits.
(from grid)
S = 105.26kVA Reactive Figure 7 (following page) shows the factory with
Power
consumed
the inverter set to a power factor of 0.95 - leading.
(from grid) The PV system is now producing 57kW of active
18.3 Q = 32.9kVAr power and 18.7kVAr of reactive power, reducing
Active Power consumed the amount of both active and reactive power from
P = 100kW the grid. The resultant power factor is therefore
maintained at what it was originally at 0.95 lagging.
Figure 5: Factory consuming active and reactive power

If this factory was to install a 60kW PV system


(Figure 6) that exported at a unity power factor,
only the active power that is imported from the
grid would be affected. The imported active power

Power Factor and Grid-Connected Photovoltaics Page | 3

Creating sustainable change through education, communication and leadership

Copyright 2015 Global Sustainable Energy Solutions Pty Ltd. All Rights Reserved.
www.gses.com.au

GSES Technical Papers

Active power = 57 kW
Reactive power = 18.7 kvar
Active power
= 43 kW

Reactive power
Grid = 14.2 kvar
Factory

Reactive Power
Consumed total
Q = 32.9kVAr
Reactive Power
Apparent Power offset (solar)
(from grid) Q=-18.7kVAr
S = 45.28kVA
Active Power offset
18.27 (solar) P = -57kW

Active Power consumed


P = 100kW

Figure 7: System installed with reactive power


control to produce both active and reactive power

It would be possible to configure this inverter to


produce more reactive power and bring the factory
to a unity power factor. The optimal power factor that
the inverter is programmed to export at will depend
on the energy contract of the consumer. Utilities
can bill industrial and commercial customers for the
energy they consume, their peak demand, and their
power factor. Any solar system should therefore
be designed to produce the maximum amount of
savings across all of these areas. For example, it may
be financially beneficial to reduce the amount of
active power drawn from the grid at the expense of
increased charges due to a poor power factor.

GSES welcomes feedback on technical papers and other


resources available on www.gses.com.au, please contact
GSES by email at info@gses.com.au or by telephone
on1300 265 525.

Power Factor and Grid-Connected Photovoltaics Page | 4

Creating sustainable change through education, communication and leadership

Copyright 2015 Global Sustainable Energy Solutions Pty Ltd. All Rights Reserved.

You might also like