GCP-30 Series Genset Control: Configuration
GCP-30 Series Genset Control: Configuration
GCP-30 Series Genset Control: Configuration
GCP-30 Series
Genset Control
Configuration
Software version 4.3xxx
Manual 37278B
Manual 37278B GCP-30 Series - Genset Control
WARNING
Read this entire manual and all other publications pertaining to the work to be performed before instal-
ling, operating, or servicing this equipment. Practice all plant and safety instructions and precautions.
Failure to follow instructions can cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an overspeed (overtempera-
ture, or overpressure, where applicable) shutdown unit(s), that operates totally independently of the
prime mover control unit(s) to protect against runaway or damage to the engine, turbine, or other type
of prime mover with possible personal injury or loss of life should the mechanical-hydraulic gover-
nor(s) or electric control(s), the actuator(s), fuel control(s), the driving mechanism(s), the linkage(s), or
the controlled unit(s) fail.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging unit, make sure the
charging unit is turned off before disconnecting the battery from the system.
Electronic controls contain static-sensitive parts. Observe the following precautions to prevent dam-
age to these parts.
Discharge body static before handling the control (with power to the control turned off, contact a
grounded surface and maintain contact while handling the control).
Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.
Do not touch the components or conductors on a printed circuit board with your hands or with
conductive units.
Important Definitions
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
Appropriate precautions have to be taken.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.
This note should absolutely be observed when connecting the unit.
NOTE
References to other notes and supplements as well as tables and lists are identified by means of the
"i" symbol. Most of the referenced sections are included in the Annex.
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Wood-
ward Governor Company is believed to be correct and reliable. However, Woodward Governor Company assumes no responsibility un-
less otherwise expressly undertaken.
Revision History
Contents
NOTE
All functions described in this manual are included in all controls (all versions) of the GCP-30 and
AMG 2 series. Any differences between the control units will be indicated by having the model number
for the applicable control unit at the beginning of the text. Please note that the AMG series controller is
not explicitly described in this manual.
[GCP-32] Functions marked and described like this are for applications with 2 power circuit breakers
(unit type GCP-32 and AMG 2/N2PB).
[GCP-31] Functions marked and described like this are for applications with 1 power circuit breaker
(unit type GCP-31 and AMG 2/N1PB).
only B+X The functions marked and described like this are contained in all units except the Rental
Package (unit types GCP-31 and GCP-32, Packages BPD, BPQ, XPD, and XPQ).
nur RPQ The functions marked and described like this are ONLY contained in the Rental Package
(unit type GCP-31 RPQ+SC08).
Measuring .............................................................................................................................................. 21
Rated Values Of The Frequency................................................................................................. 21
PTs (Voltage Transformers, only B + X Packages) .................................................................... 22
Rated Voltage Values.................................................................................................................. 23
Generator Current ....................................................................................................................... 26
Mains Current/Mains Power Measurement ................................................................................. 27
Password Configuration .............................................................................................................. 30
Controller ............................................................................................................................................... 31
Table Of Set Point Values ........................................................................................................... 31
Analog Controller Outputs (Package Q, Option Q) ..................................................................... 31
Real Power Controller, Set Point Values .................................................................................... 35
Frequency Controller ................................................................................................................... 36
Voltage Controller........................................................................................................................ 39
Power Factor cos Controller..................................................................................................... 43
Real Power Controller ................................................................................................................. 45
Load And/Or Var Sharing ............................................................................................................ 50
Automatic ............................................................................................................................................... 53
Load Management ...................................................................................................................... 53
Stop Of The Engine At Mains Failure [GCP-31] ......................................................................... 60
Interface....................................................................................................................................... 61
Breaker .................................................................................................................................................. 62
Functional Description ................................................................................................................. 62
Breaker Logic .............................................................................................................................. 68
Start/Stop Ramp, Open GCB With F2 Alarm .............................................................................. 74
GCB Pulse/Continuous Pulse ..................................................................................................... 75
Open/Close GCB......................................................................................................................... 76
Synchronization (With Synchronous Generators Only) .............................................................. 77
Phase Matching (only RPQ Package)......................................................................................... 78
Synchronization Time Monitoring (With Synchronous Generators Only) ................................... 79
Dead Bus Start (With Synchronous Generators Only)................................................................ 80
Connection Functions (With Induction/Asynchronous Generators Only) ................................... 81
Connect Time Monitoring (With Induction/Asynchronous Generators Only) .............................. 82
Breaker Monitoring ...................................................................................................................... 83
Mains Decoupling ........................................................................................................................ 84
Emergency Power (AMF) ...................................................................................................................... 86
Emergency Power With Breaker Logic "PARALLEL" ................................................................. 87
Emergency Power With Breaker Logic "OPEN TRANSIT." ........................................................ 87
Emergency Power With Breaker Logic "CLOSED TRANSIT." ................................................... 88
Emergency Power With Breaker Logic "INTERCHANGE" ......................................................... 88
Emergency Power With Breaker Logic "EXTERNAL"................................................................. 88
Emergency power With MCB Malfunction................................................................................... 88
Emergency Power; Parameters .................................................................................................. 89
Protection............................................................................................................................................... 90
Generator Power Monitoring ....................................................................................................... 91
Mains Power Monitoring (not with RPQ Package) ...................................................................... 92
Generator Overload Monitoring................................................................................................... 93
Generator Reverse/Reduced Power Monitoring ......................................................................... 94
Unbalanced Load Monitoring ...................................................................................................... 95
Time-Overcurrent Monitoring ...................................................................................................... 96
Generator Frequency Monitoring ................................................................................................ 98
Engine Overspeed Monitoring ..................................................................................................... 98
Generator Voltage Monitoring ..................................................................................................... 99
Mains Frequency Monitoring ..................................................................................................... 100
Mains Voltage Monitoring .......................................................................................................... 101
Phase/Vector Shift Monitoring d/dt ......................................................................................... 102
Mains Settling Time ................................................................................................................... 103
Battery Voltage Monitoring ........................................................................................................ 104
Time Of Active Horn .................................................................................................................. 104
Illustrations
Figure 3-1: Control loop ........................................................................................................................................................... 31
Figure 3-2: Step response (Example) ........................................................................................................................................ 32
Figure 3-3: Step responds - governor configuration ................................................................................................................. 34
Figure 3-4: CAN bus load/var sharing, wiring diagram ............................................................................................................ 51
Figure 3-5: CAN bus load/var sharing, diagram ....................................................................................................................... 51
Figure 3-6: Breaker control logic 'Impulse'............................................................................................................................... 75
Figure 3-7: Breaker control logic 'Continuous' ......................................................................................................................... 76
Figure 3-8: Characteristic of the time-overcurrent monitoring ................................................................................................. 96
Figure 3-11: Sprinkler operation ............................................................................................................................................. 113
Figure 3-12: VDO transmitter 323.805/001/001 (slope) ......................................................................................................... 120
Figure 3-13: Start-Stop sequence: Gas engine ........................................................................................................................ 126
Figure 3-14: Wiring diagram for opening gas valves with the GCP-30 from V4.1001 .......................................................... 127
Figure 3-15: Start-stop sequence: Diesel engine ..................................................................................................................... 129
Figure 3-16: Delayed engine monitoring ................................................................................................................................ 132
Figure 4-1: Analog outputs - cos scaling .............................................................................................................................. 143
Tables
Table 1-1: Manual - Overview .................................................................................................................................................... 7
Table 1-2: Functional overview .................................................................................................................................................. 8
Table 3-1: Event recorder - Messages, part 1 ........................................................................................................................... 19
Table 3-2: Event recorder Messages, part 2 ........................................................................................................................... 20
Table 3-3: Set point value table ................................................................................................................................................ 31
Table 3-4: Limit values, permissible limits............................................................................................................................... 62
Table 3-5: Limit values generator, dead bus start ..................................................................................................................... 65
Table 3-6: Limit values mains, dead bus start........................................................................................................................... 66
Table 3-7: Limit values, Emergency power .............................................................................................................................. 86
Table 3-9: Discrete alarm inputs - delay stages ...................................................................................................................... 106
Table 3-10: Function - external operation mode selection ...................................................................................................... 108
Chapter 1.
General Information
GCP-31/32 series
GCP-31/32 - Installation 37239 GR37239
GCP-31/32 - Configuration this manual 37278 GR37278
GCP-31/32 - Function/Operation 37238 GR37238
GCP-31/32 - Application 37240 GR37240
Option SB - Caterpillar CCM coupling 37200 GR37200
Option SC06/07/08 - CAN bus coupling 37182 GR37182
Option SC04 - IKD1 and ST3 coupling 37236 GR37236
Option SC02 - IKD1 coupling 37302 GR37302
Option D08- Preglow control 37286 GR37286
Option T7 - 7 analog inputs 37261 GR37261
Option TZ - Temperature-dependent start/stop 37241 GR37241
more options upon request
Additional manuals
IKD 1 - Manual 37135 GR37135
Discrete expansion board with 8 discrete inputs and 8 relay outputs that can be coupled via the CAN bus to the control unit. Evalua-
tion of the discrete inputs as well as control of the relay outputs is done via the control unit.
IKN 1 - Manual 37136 GR37136
20channel NiCrNi temperature scanner that monitors the temperature values for exceeding or falling below a threshold value, meas-
ured through senders on the IKN 1. A configured relay on the board of the IKN 1 will trip. The IKN 1 can be coupled with the con-
trol unit using the CAN bus to display measuring values as well as alarms.
LeoPC1 - Manual 37146 GR37146
PC program for visualization, for configuration, for remote control, for data logging, for language upload, for alarm and user man-
agement and for management of the event recorder. This manual describes the use of the program.
LeoPC1 - Manual 37164 GR37164
PC program for visualization, for configuration, for remote control, for data logging, for language upload, for alarm and user man-
agement and for management of the event recorder. This manual describes the programming of the program.
GW 4 - Manual 37133 GR37133
Gateway for transferring the CAN bus to any other interface or bus.
ST 3 - Manual 37112 GR37112
Control to govern the air fuel ratio of a gas engine. The ratio will be directly measured though a Lambda probe and controlled to a
configured value.
Table 1-1: Manual - Overview
Functional Overview
Function Package
GCP-31 GCP-32
XPQ+SC06
RPQ+SC08
XPQ+SC06
XPQ+SB03
XPQ+SB03
Option
XPQ
XPQ
BPQ
XPD
BPQ
XPD
BPD
BPD
Common Functions
1 readiness for operation relay Std.
4/6 control relay (form A, make contact) Std. 4
7 freely configurable relay outputs (form A, make contact) Std.
2 three-position controller for n/f/V/P, cos Std. -- -- -- -- -- -- -- --
2 three position controller for n/f/V/P, cos via relay manager Q
2 analog controller outputs for n/f/V/P/Q and PWM output Q
up to 14 discrete control inputs Std. 6 6 6 6 6 6 14 6 6 6 6 6 6
up to 16 discrete alarm inputs Std. 16 16 16 16 16 16 12 16 16 16 16 16 16
SYNCON Panel coupling via guidance bus RPQ -- -- -- -- -- -- -- -- -- -- -- --
CAN bus interface 'guidance level' Std.
CAN bus interface to 2 IKD 1 and ST 3 (RPQ: no ST 3) SC06 -- --
CAN bus coupling to mtu MDEC and Scania EMS/S6 SC06 -- --
CAN bus coupling to SAE J1939 SC06 -- --
RS-232 coupling via Caterpillar CCM to ECM & EMCP-II SB03 -- -- --
7 analog inputs T701
1 Pickup input Std.
2 analog outputs + external operation mode selection by term. 127/128 A2
Password system Std.
Configuration via DPC possible (direct configuration) Std.
Event recorder with real-time clock ZE
Language manager for LCD texts Std.
Running hours, maintenance, start, and kWh counter Std.
Additional running hours counter w. minute resolution (rental duty time) RPQ -- -- -- -- -- -- -- -- -- -- -- --
Control/Synchronization
Synchronization of 1 breaker with V and f correction Std.
Synchronization of 2 breakers with V and f correction Std. -- -- -- -- -- -- --
Closing to a dead/voltage free busbar (dead bus start) Std.
Voltage control Std.
Power factor (cos) control Std.
Speed/frequency control Std.
Phase control, V/f droop control RPQ -- -- -- -- -- -- -- -- -- -- -- --
Generator real power control & import/export real power control Std.
Real & var sharing Std.
Analog setpoint value for real power T701
Analog mains interchange (import/export) real power measuring T701
Breaker logic "open transition" & "closed transition" Std. -- -- -- -- -- -- --
Breaker logic "soft loading" Std. -- -- -- -- -- -- --
Breaker logic "parallel operation" Std.
Breaker logic "external" Std.
Remote control via interface Std.
Protective Functions
Over-/undervoltage protection, generator VGen>/< Std.
Over-/undervoltage protection, mains VMains>/< Std.
Over-/underfrequency protection f>/< Std.
d/dt vector/phase jump protection d/dt Std.
Reverse/reduce power protection +/-PGen< Std.
Overload protection PGen> Std.
Unbalanced load protection PGen> Std.
Time-overcurrent protection Iumz>/>> Std.
Battery voltage protection UBat< Std.
Table 1-2: Functional overview
Chapter 2.
Function
Considerations To Be Taken:
Different Options
According to a control unit's configuration, different parameters may be displayed and not all parameters will be
available:
Various inputs and outputs will be present or deleted, corresponding to the control configuration (depending
on your order). Please refer to the wiring diagram and the notes regarding the packages and options contained
in these. Refer to the data plate to see if the corresponding option is contained in the control. If the data plate
has been removed, the configuration screens may be called up in succession and the options may be deter-
mined with the assistance of this manual.
Specific display screens correspond to specific types of interfaces.
Case A - The MCB must remain closed (except at an emergency power operation): The "Enable MCB" (ter-
minal 53) always has to be logical "1".
Case B - The MCB can be opened (also outside an emergency power operation): The "Enable MCB" (termin-
al 53) must be set logical "1" if a mains parallel operation has to be established (a synchronization of the
MCB has to be performed). During the synchronization of the MCB (GCP-31: this function is performed ex-
ternally from the controller) the generator frequency is controlled with a slightly higher value than the mains
frequency (df max/2). Additionally a message is displayed on the controller. The "Enable MCB" (terminal
53) has to be logically "0", if the system has to be operated in isolated operation (control of set point frequen-
cy and set point voltage).
In the case of systems with asynchronous/induction generators, the following must be noted:
Systems with asynchronous/induction generators are 1-power-circuit-breaker systems [GCP-31].
Connect the remnant voltage to terminals 23/24. Terminals 23/24 are voltage sensitive and can detect voltag-
es from 0.5-480 volts. These terminals are utilized to determine the frequency (rotary speed) of the remnant
voltage with small amplitudes. If the GCB is not closed, only the remanence voltage, which is less than
10 volts, is measured instead of the generator voltage. The generator voltage and frequency is monitored only
once the GCB is closed. If the control is in mains parallel operation, the inputs from 23/24 are no longer taken
into account.
Signals
Discrete Inputs
NOTE
All emergency power (Parameter 164 "Emergency power" has to be configured to ON) or Critical
(Sprinkler) mode operations (terminal 6 must be configured accordingly; Parameter 239) will be carried
out in the TEST and AUTOMATIC operation modes regardless of the discrete inputs "Automatic 1" and
"Automatic 2". If terminals 3 and 5 are enabled simultaneously, priority is given to terminal 3.
If a set point value is specified externally (e. g. via an 0/4 to 20 mA analog input or a bi-directional in-
terface), the external set point value is adjusted with the discrete input (see Table 3-3: Set point value
table).
Control Outputs
Default values:
Relay 1 to 5 = relay number (e. g. relay 1 = alarm class 1, relay 2 = alarm class 2, etc.)
Relay 6 = Ignition / preheating
Relay 7 = Centralized alarm
Chapter 3.
Parameter
Configuration may be performed via the front panel keys or using a PC and the PC program LeoPC1 via the seri-
al interface. Use LeoPC1 version 3.1 or higher for this. Additionally it is possible to configure the unit via CAN
bus. The following Baud rates are therefore usable:
Configuration via direct configuration plug (RS-232) = 9,600 Baud (8 Bit, no parity, 1 Stop bit)
CAN bus (CiA) (RS-485) = 125, 250 or 500 kBaud configurable via the serial interface.
CAUTION
For configuration of this control (firmware software version starting with 4.3xxx) a PC software with
the following version number or higher must be used:
LeoPC1 from 3.1
Not all parameters may be configured directly at the GCP with Option SCxx anymore. Therefore, it is
recommended to have LeoPC1 and the specific configuration files available when commissioning.
Because of functional enhancements within the controls of the GCP-30 Series it is necessary (beginning with
firmware version 4.3xxx of the GCP) to use a newer version of the configuration software LeoPC1. This version
at least must be 3.1 or higher. If the LeoPC1 software you currently use has an older version the latest version
can be ordered at our technical sales or can be downloaded on our homepage at
http://www.woodward.com/software.
After an updated version of LeoPC1 has been installed older project files may still be used. These can be trans-
ferred to the appropriate file locations within the new program.
WARNING
Please note that configuration only should be performed while the system is not operating.
NOTE
Before configuring a control unit, familiarize yourself with the parameters listed at the end of this ma-
nual.
You can scroll through the parameters if you are in configuration mode (simultaneously pressing of "Digit" and
"Cursor" push buttons permits access to the configuration mode) using "Select". If you press and hold the "Se-
lect" push button the scroll function will be activated, allowing for the parameter screens to be advanced through
more rapidly. The control unit will permit the operator to reverse up to four previous screens (exception: it is not
possible to reverse from the first parameter to the last parameter or to backup through the service screens). To
perform the reverse function through the parameter screens, the "Select" and "Cursor" push buttons must be
pressed and released simultaneously. The control unit will revert to automatic mode, if an entry isn't performed, a
change made or any other action performed for 90 seconds.
NOTE
There are two different types of hardware, which are described in this manual: A 120 Vac version [1]
and a 480 Vac version [4]. The configuration screens and parameters differ in both versions, and the
setting limits also differ. The two types are identified by the preceding voltage values ([1] ... or [4] ...).
Basic Data
Configuration Access
The control is equipped with a three-level code and configuration hierarchy, which enables it to access various
configuration screens for different users. A distinction is made between:
NOTE
Once a password has been set it will not change unless a person alters that parameter with access to it
regardless of how often the configuration mode is accessed. If an incorrect code number is entered,
the code level is set to CS0 and the control is therefore locked for external users (setting of password
on page 28). The control unit automatically reverts to code level CS0 two hours after the entry of a
password. By entering the correct password, the corresponding level may again be accessed.
The code level may also be accessed using the PC program LeoPC1.
Direct Configuration
NOTE
To carry out direct configuration, you require a direct configuration cable (Part #5417-557), the
LeoPC1 1 program (supplied with the cable) and the corresponding configuration files. Please consult
the online help installed when the program is installed for a description of the LeoPC1 1 PC program
and its setup.
Remote configuration: For remote configuration the level CS2 password must be entered via the parameter
"password", otherwise, the values can only be read but not written. Entering via the CAN bus has no influence on
the displayed parameters. If the control is in code level CS0, the same level of access will be granted as described
in the previous section. The configuration via the bus is enabled for 2 hours from that point in time from the time
that the last readout of configuration was performed. After two hours the password must be entered again to
access the parameters. The password must also be entered prior to loading languages.
WARNING
If Parameter 3 "Direct para." is configured to "YES", communication via the interface with terminals X1-
X5 is blocked. If communication is to be re-established via interface X1-X5 after finishing the configura-
tion of the control (e.g. CAN bus connection via a Gateway GW 4), Parameter 3 must be configured to
"NO"!
The direct configuration port is diabled (Parameter 3 is automatically switched from YES to NO) once
the firing speed (Parameter 308) has been reached. This requires any further configuration of the con-
trol to be accomplished via the front display and push buttons or via the CAN bus interface. The de-
activation of direct configuration is performed as a safety precaution. If multiple systems starting si-
multaneously (e. g. emergency power situation) a simultaneous switching of the generator breakers to
the dead busbar is prevented.
Generator Number
Parameter 4 Generator number (number of the control on the CAN bus) 1 to 14
Generator number
0 If several controls are available and these are coupled via a CAN bus, a different
number must be assigned to each control for differentiation purposes. The genera-
tor number 1 should be assigned even in the case of a single control. The control
number entered here corresponds to the control number in the program LeoPC1.
The parameter range from 1 to 8 is valid for the Rental Package RPQ+SC08.
In order to load a different language into the control, follow the steps below:
1.) A communication link between your PC and the control unit must be established via the direct configura-
tion cable (DPC). To do this insert the serial cable into the COM port of your PC and the RJ45 plug into the
communication port of the control unit (a connection via CAN and GW 4 is also possible).
2.) Enter the password for code level CS2 into the control (Parameter 2).
3.) If the direct configuration cable (DPC) is to be utilized, the Parameter 3 "Direct para." must be configured
as "YES". If a GW 4 or the CAN bus is to be utilized for configuration, the Parameter 3 "Direct para." must
be configured as "NO".
4.) If the desired language is to be loaded via the CAN bus, enter the number (1 to 14) into the "Generator
number" screen (Parameter 4), so that LeoPC1 is able to communicate with the desired control unit.
5.) Scroll to the configuration screen "Language" (Parameter 5) and select the primary language for the control
unit by selecting "first".
6.) Start the program LeoPC1, and log into the program by selecting "System" from the tool bar and "User lo-
gin" from the drop down menu. Enter the user name and password and click the "OK" button.
7.) Open the applicable *.cfg file for the application by selecting "File" from the tool bar and "open" from the
drop down menu. Select the proper *.cfg file from the window that appears.
8.) To start communication between the control unit and LeoPC1 select "Communication" from the tool bar
and "Connect" from the drop down menu.
9.) Select "Devices" from the tool bar and "Parameterize" from the drop down menu. A window will appear
with all the tunable parameters in it. Move the cursor over the numbers for the password and double click.
10.) Enter the password for the code level CS 2 (Parameter 2).
11.) Close the parameterization window.
12.) Select "Devices" from the tool bar and "Load language" from the drop down menu.
13.) Load the desired language file using the button "Load LNG file ..."
14.) Select the desired language and click the "Transfer language" button.
15.) If an additional language is to be loaded into the control unit, return to step 5 and select "second" (not poss-
ible via LeoPC1). Repeat all steps in order as when programming the first language.
Service Display
NOTE
Displaying and clearing of events depends on access authorization:
# #
Displaying of events...................... Access authorization CS 1 und CS 2
#
Clearing of events ......................... Access authorization CS 2
#
CS = Code level (see chapter "Configuration" on page 15.
When an event (see following table) occurs it is stored in the event logger. The following information is record-
ed:
Event
Date of occurrence
Time of occurrence
Up to 50 events can be stored in the event logger (beginning with the most current one). For more than 50 en-
tries, the oldest event will be deleted. By pressing the "RESET" push-button, the event that is displayed is
cleared. The events are displayed on two lines. The top line indicates the date and time of the event that has oc-
curred; the lower line shows the type of event.
NOTE
Starting from version 4.3010, the event logger can also be read via CAN. This enables to read the event
logger via GW4/modem for example.
If the event logger is to be read via CAN, the respective connection, e.g. GW4, has to be selected in
LeoPc1. Reading the event logger is then performed like for direct configuration.
External expansions
Discrete input [D1.01] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.02] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.03] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.04] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.05] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.06] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.07] of IKD1.1 Option SC06 + IKD1
Discrete input [D1.08] of IKD1.1 Option SC06 + IKD1
frei parametrierbar freely configurable
Discrete input [D2.01] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.02] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.03] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.04] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.05] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.06] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.07] of IKD1.2 Option SC06 + IKD1
Discrete input [D2.08] of IKD1.2 Option SC06 + IKD1
Air-fuel-ratio sender alarm from ST 3 Option SC06 + ST3 Lambdasonde Lambda probe
Other Events
Switched into operation mode MANUAL BAW Hand Manual mode
Switched into operation mode AUTOMATIC BAW Automatik Automatic mode
Switched into operation mode STOP BAW Stop Stop mode
Switched into operation mode TEST BAW Probe Test mode
Switched into operation mode Load TEST BAW Lastprobe Loadtest mode
"MCB OFF" push-button pressed (in MANUAL MODE) Taste NLS AUS Button MCB OFF
"GCB OFF" push-button pressed (in MANUAL MODE) Taste GLS AUS Button GCB OFF
"GCB ON" push-button pressed (in MANUAL MODE) Taste GLS EIN Button GCB ON
"MCB ON" push-button pressed (in MANUAL MODE) Taste NLS EIN Button MCB ON
"START" push-button pressed (in MANUAL MODE) Taste Hand START Button START
"STOP" push-button pressed (in MANUAL MODE) Taste Hand STOP Button STOP
Remote start Fernstart Remote start
Remote stop Fernstop Remote stop
Remote acknowledgment via interface Fernquittierung Remote acknowl.
Remote acknowledgment via terminal 6 Quittierung Kl.6 Acknowledg-ter 6
Acknowledgment via "RESET" button Quittierg. Taste Ackn.button QUIT
Mains failure (AMF) Netzausfall Mains failure
Return of the mains (this entry occurs once the mains settling time expired) Netzwiederkehr Mains o.k.
Emergency power (AMF) started Notstrom Anfang Emerg. run start
Emergency power (AMF) ended Notstrom Ende Emerg. run stop
Engine successfully started (engine enabled, firing speed exceeded) Aggr. gestartet Start of engine
Engine stopped (engine not enabled, firing speed was undershot) Aggregatestop Stop of engine
Table 3-2: Event recorder Messages, part 2
Analog Inputs
The control unit is not able to display the entire text for the analog alarms. The 6 digits on the left side of the
screen are reserved for the analog values to be monitored. If the text for these alarms is expanded, the monitored
values will be overwritten and not displayed. The text below is the message that is displayed for each of the fault
conditions.
Parameter 8 Example
YY-MM-DD ss:mm
STOP Analog inpu Limit value 2 (STOP) of the analog input 1 was exceeded. The text of the analog
alarm input will be moved 6 letters to the right. In this case the measured value dis-
appears. Please note this text displacing already during the configuration of the
analog input!
Measuring
WARNING
The following values must be entered correctly for the generator to be monitored. Failure to do so may
lead to incorrect measuring resulting in damage to or destruction of the generator and/or personal in-
jury or death.
WARNING
If the value of the following parameter is changed, the values of the following parameters have to be
checked:
Generator rated voltage (Parameter 22)
Voltage controller dead band (Parameter 71)
Synchronizing dVmax (Parameter 133)
Dead bus start GCB dVmax (Parameter 147)
Threshold generator overvoltage (Parameter 202)
Threshold generator undervoltage (Parameter 204)
The secondary voltage is set here in V. This parameter is used to display the sec-
ondary voltages on the control unit screen.
The secondary voltage is set here in V. This parameter is used to display the sec-
ondary voltages on the control unit screen.
WARNING
If the value of the following parameter is changed, the values of the following parameters have to be
checked:
Threshold mains overvoltage (Parameter 212)
Threshold mains undervoltage (Parameter 214)
The secondary voltage is set here in V. This parameter is used to display the sec-
ondary voltages on the control unit screen.
This value of the voltage specifies the set point of the generator voltage for no-load
and isolated operation. The proportional entry of the parameter "Start voltage V
controller" (Parameter 67) refers to this value.
Instead of these two voltage parameters, The following voltage system parameters are displayed for the RPQ
Package:
The respective system is activated using the discrete input at the terminals 72 and 73. Refer to the Discrete Input
section in Installation Manual 37320 for further information about this.
NOTE
Terminal 0 must be isolated for the setting 'Ph-Ph/Ph-Ph' (voltage measuring Ph-Ph, voltage monitoring
Ph-Ph) since a contact voltage in inadmissible range may occur at terminal 0.
Generator Current
Parameter 30 Generator CT's 10 to 7,000/{X} A
Current transf.
generator 0000/x The input of the CT ratio is necessary in order to display and control the actual val-
ues. The CT ratio must be selected so that, at maximum power, at least 60 % of the
CT nominal current flows. A lower percentage may lead to malfunctions. Addition-
al inaccuracies in the control and monitoring functions also occur.
NOTE
With a positive real power, a positive real current flows in the "k-l" direction in the CT. Positive reactive
power means that with a positive effective direction, inductive reactive (lagging) current flows in the ef-
fective direction. If the control is connected to the terminals of a generator and if the outgoing circuits
of the CT facing the generator are connected to "k", the unit shows a positive real power when the ge-
nerator supplies real power. In this regard, note the explanations in manual 37238.
Mains power actual value measurement via analog input (Package XP, Option T701)
Measurement of the mains power actual value via an analog input T{x} [x = 1-7] is possible if at least one of the
analog inputs T{x} [x = 1-7] is a 0/4-20 input. Selection of the analog input is performed with the following pa-
rameters.
Note
Please note that the selected analog input T{x}
Must be configured to OFF (Parameter 243) in chapter "Analog inputs" and that
this analog input
Must not be configured as generator real power set point value (Parameter 91)
T{x}: Dependent on the control model these analog inputs are included and pos-
sibly built as 0/4-20 mA type. If the controller being configured is an analog in-
put model, only 0/4-20 mA inputs may be used (only these inputs are displayed
for selection at this parameter).
LeoPC1 is not a dynamic program and must be restarted after reconfiguration of a
control unit has been started so the changes are reflected in the graphical display
of the PC program.
Note
It is possible to adjust the display range of the mains interchange (import/export)
real power actual value. Thereto the wanted value must be entered and saved using
the Parameter 244 "name and unit" of the selected analog input (see chapter "Ana-
log inputs").
NOTE
For an import/export real power control application, ensure that the set point value selected is in the
middle of the measuring range. This will allow the controller dynamic to be used to its fullest capacity.
Parameter 36 Mains real power 0/4 mA [1] -9,990 to 9,990 kW; [4] -6,900 to 6,900 kW
Analog in Pmains
0% 0000kW The scaleable analog input is assigned a numerical value, which corresponds to the
lowest input value (0 % corresponds to -500 kW; 0 or 4 mA).
Package XP, Option T701 only
Parameter 37 Mains real power 20 mA [1] -9,990 to 9,990 kW; [4] -6,900 to 6,900 kW
Analog in Pmains
100% 0000kW The scaleable analog input is assigned a numerical value, which corresponds to the
highest input value (100 % corresponds to 500 kW; 20 mA).
Package XP, Option T701 only
ATTENTION
Since the LS 4 is only able to transmit a percentage value related to the rated pow-
er, it is absolutely necessary to configure the rated power in all units (LS 4 and
GCP Parameter 32) to the same value.
Measurement Units
NOTE
LeoPC1 is not a dynamic program and must be restarted after reconfiguration of a control unit has
been started so the changes are reflected in the graphical display of the PC program.
C F F C
T [F] = (T [C] x 1,8) + 32 T [C] = (T [F] 32) / 1,8
Password Configuration
NOTE
Once a password has been set, it will not change unless a person alters that parameter with access to,
it regardless of how often the configuration mode is accessed. If an incorrect code number is entered,
the code level is set to CS0 and the control is therefore locked for external users.
The control unit automatically reverts to code level CS0 two hours after the entry of a password or if
the power supply is disconnected from the control unit. By entering the correct password, the corres-
ponding level may again be accessed.
Controller
WARNING
Incorrect settings may lead to the errors in measurements and failures within the control unit resulting
in destruction of equipment or injury to personnel.
As an alternative to a three-position controller output, the control may also be equipped with an analog controller
output. If this option is selected, additional screens are displayed in the configuration mode. The analog PID con-
troller forms a closed-loop control loop with the controlled system (usually a first-order lag element). The para-
meters of the PID controller (proportional-action coefficient KPR, derivative-action time TV, and reset time Tn)
can be modified individually. The additional configuration screens are used for this purpose.
Influenciny
Kpr Tn Tv Tt Kp T1
quantity
If an abrupt disturbance variable is applied to the control loop, the reaction of the controlled system can be rec-
orded at the output as a function of time (step response).
x
xm
Tolerance band
xd
disturbance variable
Various values can be obtained from the step response; these are required for adjusting the controller to its opti-
mum setting:
Rise time Trise: Period starting when the value of the control variable leaves a predefined tolerance range for the
control variable following a step in the disturbance variable or reference input variable and ending the first time
the value re-enters this range.
Settling time Tsett: Period starting when the value of the control variable leaves a predefined tolerance range for
the control variable following a step in the disturbance variable or reference input variable and ending when the
value re-enters this range permanently.
Overshoot xm: Highest transient set point value deviation during the transition from one steady-state condition to
a new steady-state condition following modification of the disturbance variable or reference input variable (xm Op-
timal 10 %).
System deviation xd: Permanent deviation from the final value (PID controller: xd = 0).
The values for KPR, Tn, and TV may be determined through various calculations from the values in the table
above. Through these calculations (calculating compensation, adjustment of the time constants, T-sum rule,
symmetric optimum, and/or Bode-diagram) it is possible to determine the optimal controller settings. Other set-
ting procedures and information may be obtained from current literature.
CAUTION
The following must be observed regarding the controller setting:
Ensure that the emergency shutdown system is operational.
While determining the critical frequency, pay attention to the amplitude and frequency.
If the two values change uncontrollably:
EMERGENCY SHUTDOWN
Initial state: The start position of the controller is determined using the initial state of the controller. If the con-
troller is switched off, the basic setting can be used to output a fixed controller position. If operation mode MA-
NUAL has been selected, the initial state signal is output only with the "START" push button. Even when the
analog controller is switched off, the initial state can be freely adjusted (e.g. the speed controller can be con-
trolled in a linear manner). On setting the "STOP" push button, the analog controller is switched off again.
General settings: The setting rule described below only serves as an example. It cannot be assumed that this is
the proper method of control for your system since every system behaves uniquely.
There are various methods of setting a controller. The setting rules of Ziegler and Nichols are explained below
(determination for abrupt disturbances on the system input); this setting method assumes a pure lag element con-
nected in series with a first-order lag system.
ATTENTION
If the engine starts to oscillate uncontrollably, carry out an emergency shutdown and alter the screen set-
ting accordingly.
PID-controller PI-controller
KPR = 0.6 KPcrit KPR = 0.45 KPcrit
Tn = 0.5 Tcrit Tn = 0.83 Tcrit
TV = 0.125 Tcrit
Step response
Controller setting Controller setting Controller setting
Optimal (xm 10 %) Tcrit Incorrect
x x x
1 1 1
0 0 0
0 t/s 0 t/s 0 t/s
These screens appear only if the generator real power controller has been configured to "ON" (Parameter 87).
NOTE
The fixed-value power control does not take into account the mains interchange point. If excess power
is generated, it will be exported to the mains. If there isnt enough power generated, the deficit in pow-
er will be imported from the mains.
Engine starting depends on whether an automatic start/stop operation has been enabled or disabled
(Parameter 108 or Parameter 109). If it has been disabled, the engine will always start.
Frequency Controller
Parameter 48 f controller: initial frequency 0 to 100 %
Initial state
Frequency 000% Analog controller output setting with disabled controller. The set value in percent
refers to the range between minimum and maximum value of the output signal (see
Package Q, Option Q only
Parameter 60 and Parameter 61).
NOTE
The parameters for the speed/frequency controller influence the generator real power controller.
NOTE
The control logic of the PWM signal can be inverted by following steps:
- Select "F/P contr.type" (Parameter 54) = ANALOG.
- Select with Parameter 58 "F/P contr.output" any of above inverted control outputs
(e.g. "10 to 0mA (5 to 0V)", "4.5V to 0.5V", "20 to 0mA (10 to 0V)" or "20 to 4mA").
- Back up one screen (Parameter 54; by pressing "Select" and "Cursor" simultaneously).
- Select "F/P contr.type" (Parameter 54) = PWM.
Now the PWM signal is inverted.
Voltage Controller
Parameter 65 V controller: initial state 0 to 100 %
Starting point
voltage 000% Analog controller output setting with disabled controller. The set value in percent
refers to the range between minimum and maximum value of the output signal (see
Package Q, Option Q only
Parameter 75 and Parameter 76).
The voltage controller will be enabled, once the generator voltage has exceeded
this value. This prevents an unintentional change of the set point of the voltage
regulator when starting the engine.
NOTE
The following parameters for the voltage controller influence the power factor cos controller.
Isolated operation The generator set point voltage is controlled in such a manner
that the current value will deviate from the generator set point vol-
tage by no more than the configured dead band.
Synchronization The generator voltage is controlled in such a manner that the dif-
ferential voltage will not exceed the configured dead band. The
mains or busbar voltage are used as the set point value.
NOTE
Please note the settings for the voltage controller in chapter "Voltage Controller" at page 39. The set-
tings there for the voltage controller also influence the cos controller.
Power Limitation
The generator real power set point value may be monitored via an analog input T{x} [x = 1 to 7] if one of the
analog inputs T{x} [x = 1 to 7] is utilized as a 0/4 to 20 mA input. The selection of the analog input is done using
the following parameters.
Parameter 91 P set point value: external set point value OFF / T{x}
Power setpoint
external OFF OFF ..............If this parameter is configured to "OFF" a generator real power set
point value is not monitored via the 0/4 to 20 mA input to the con-
Package XP, Option T701 only
trol. The analog inputs can be used either as a mains interchange
(import/export) real power actual value or as freely configurable
alarm inputs. If terminal 5 is utilized, the internal set point value 2
"Pset2" (Parameter 47) is used as set point value. The subsequent
screens of this function are not displayed.
T{x} ..............The generator real power set point value is monitored by the control
via an external signal using the 0/4 to 20 mA inputs (T{x}, {x) = 1 to
7). If terminal 5 is utilized, the internal set point value 2 "Pset2" (Para-
meter 47) is used as set point value. The subsequent screens of this
function are displayed.
Note
Please note the following if analog input T{x} has been selected:
Parameter 243 in chapter "Analog inputs" must be configured as OFF
Parameter 34) in chapter "Measuring" must not be configured as mains inter-
change real power actual value.
T{x}: Depending on the configuration of the control it is possible that various
analog inputs other than the 0/4 to 20mA type may be used. For this function, on-
ly 0/4 to 20mA may be used.
LeoPC1 is not a dynamic program and must be restarted after reconfiguration of a
control unit has been started so the changes are reflected in the graphical display
of the PC program.
CAUTION
The interchange real power set point may also be scaled. When controlling the interchange power, it is
vital to ensure that C power is not entered simultaneously with I or E power when scaling the external
analog input.
External setpoint 0/4 mA C I E I E
External setpoint 20 mA C I E E I
The control ensures load and/or var sharing adjusted to the rated power of the generators under every operating
condition (mains parallel operation, isolated operation in parallel with other gensets, or reverse synchronization
of the busbar to the mains).
The controls with the GCB close and not in constant/base load mode will load and/or var share.
The rated power of the generators is max. 10 MW. Thus, up to 14 generators with a maximum of 10 MW each
may share the power.
Operating in mains parallel with mains interchange (import/export) real power control: Each controller
participating in load/var sharing controls the generator set to which it is assigned so that the real power set point
at the mains interchange remains constant. The real power set point for the mains interchange must be configured
identically in each controller.
All controllers communicate via a CAN bus. This enables the controllers to adjust the real power generated by
the generator while remaining within the rated power of the generator. A smaller generator will contribute less
real power as compared to a large generator, but they will both be utilized to the same capacity factor. An exam-
ple of this would be a 100KW generator and a 1000KW generator and a mains interchange of 825KW. The
100KW generator would contribute 75KW and the 1000KW generator would contribute 750 KW or both genera-
tors would be at 75% of their rated capacity.
No reactive power sharing is performed when operating in parallel with the mains. The reactive power will be
defined by the configured power factor set point of the individual controllers.
The parameter "kW/kvar sharing: reference variable kW" can be used now to define the priority of the reference
variable (real power at interchange) for real power sharing. A higher percentage influences the control more to-
wards the real power set point for the interchange. A lower percentage influences the control more towards real
power sharing.
The parameter "kW/kvar sharing: reference variable kvar" has no influence here.
Isolated operation in parallel: Each controller participating in load/var sharing controls the generator set to
which it is assigned in such a manner that the set frequency and the set voltage at the bus remain constant. This
makes it imperative that the same frequency and voltage set points are configured for each controller.
All controllers communicate via a CAN bus. This enables the controllers to adjust the real power generated by
the generator while remaining within the rated power of the generator. A smaller generator will contribute less
real power as compared to a large generator, but they will both be utilized to the same capacity factor. An exam-
ple of this would be a 100KW generator and a 1000KW generator and a load of 825KW. The 100KW generator
would contribute 75KW and the 1000KW generator would contribute 750 KW or both generators would be at
75% of their rated capacity.
The reactive power will be allocated in a way that it is the same for all generators involved.
The parameter "kW/kvar sharing: reference variable kW" can be used now to define the priority of the reference
variable (frequency) for real power sharing. A higher percentage influences the control more towards frequency
control. A lower percentage influences the control more towards real power sharing.
The parameter "kW/kvar sharing: reference variable kvar" can be used now to define the priority of the reference
variable (voltage) for reactive power sharing. A higher percentage influences the control more towards voltage
control. A lower percentage influences the control more towards reactive power sharing.
Reverse synchronization of the busbar to the mains: Distribution is carried out according to the type of iso-
lated operation. The set point value for the bus frequency is determined by the mains frequency + dfmax/2.
Example: If dfmax = 0.2 Hz, this results for dfmax/2 = 0.1 Hz (i.e. in a system of 50 Hz, the busbar will be raised to
50.1 Hz).
The relay issues "Command: close GCB" to all controls so they may be paralleled.
Prerequisites: The rated system frequencies, the start/stop parameters, and the breaker logics must all be set to
the same values for all controls participating in the distribution control.
Description of the interface for distribution control: Distribution control is based on a multi-master-capable
bus between the controls. This structure enables the parallel operation of up to 14 gensets.
Wiring diagram
Termination Termination
resistor resistor
CAN-H
GND
CAN-H
GND
CAN-H
CAN-H
GND
CAN-L
CAN-L
CAN-L
CAN-L
Termination
Termination
Note:
The termination has to be
performed with a resisitance,
which corresponds to the
impedance of the used cable
(e.g 120 Ohms)
Diagram of load/var sharing via the CAN bus: The parameter "Active load sharing factor" determines if and
how a generator carries out real power or frequency control when paralleled with other generators in an isolated
operation. This parameter is defined as a percentage. In figure below 10 % means increased real power control
and 99 % increased frequency control. This parameter must be configured individually for each generator.
In the illustrated control system, it must be noted that each control calculates the mean utilization factor of all
controls from the data transmitted via the CAN bus and then compares this with its own utilization factor. The
utilization factor is compared with the reference variable and results in a new reference variable. Frequency and
real power control are carried out simultaneously in these controls (corresponding to the reference variable).
Frequency control is carried out via the measured voltage/frequency of the voltage system. The Pickup is used
merely for monitoring functions, or is available as a current control value to the secondary controller.
f actual [Hz]
P actual [kW]
f set
n actual [min-1]
Leading value 10..99 [%]
10 % = only P control
99 % = only f control
P nominal (via CAN)
P diff [%]
Calculation
P actual [kW]
P Utilization factor of this engine [%]
P actual (via CAN)
Calculation
P nominal [kW] 2001-08-06 Leistungsverteilung Blockschaltbild.skf
The smaller this factor the higher the priority to equally share the load to all genera-
tors.
Automatic
Parameter 107 Configuration of automatic YES/NO
Configure
automatic YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
Load Management
NOTE
To enable the automatic start/stop function, Parameter 103 Active power load-share must be confi-
gured to ON, regardless if additional generators are available for load sharing.
NOTE
To carry out an automatic start/stop of the engine, all participating controls must be configured with
the identical rated power (Parameter 32).
Parameter 110 Load dependent start/stop: generator minimum set point power 0 to 6,900 kW
Minimum load
generator 0000kW For the mains interchange (import/export) real power control to function, a genera-
tor power set point value is required. In many cases, starting of the engine should
only performed once a specific generator power set point value has been reached in
order to operate the generator with a reasonable degree of efficiency. For example:
At least 40 kW of real power has to be supplied by 80 kW generator before the en-
gine is to be started.
Stopping hysteresis
NOTE
The following Parameter 113 is used to determine stopping hysteresis for single gensets in mains pa-
rallel operation, for generators connected to other generators in mains parallel operation, and in iso-
lated operation in parallel with other gensets. However, the parameter appears only once in this text.
Mains parallel operation (mains interchange (import/export) real power control with one generator)
General
Example
The power supplied by the mains, which is to be adjusted, is 50 kW. This value is entered into the set point value
screen (see chapter "Controller") as "I0050kW". The generator should be operated with at least 30 kW.
PNT.setpoint = -50 kW Incoming/import power has to be entered negative, output/export power positive.
Pstar = 30 kW The minimum power requested by the generator.
PHyst = 10 kW The power hysteresis for stopping.
Case 1: The engine starts with the following import mains power: If formula (a) is inverted, this results in
The power supplied by the mains must be at least 80 kW in order for the engine to start. This is then oper-
ated with a minimum power of 30 kW.
Case 2: The engine stops if it has to supply less than the minimum power minus hysteresis. This is the case with
the following generator power: If formula (b) is inverted, this results in
If the generator falls below its minimum power minus hysteresis, the engine is stopped. The power im-
ported from the mains therefore remains at the value that is to be controlled until just prior to stopping.
Following stopping, the power supplied by the mains increases to 70 kW.
NOTE
The following Parameter 114 only applies if more than one generator is to be started in mains parallel
operation. The first engine is started as described under single generator in mains parallel operation
on the basis of the minimum generator power.
Mains parallel operation(mains interchange (import/export) real power control with several generators)
General
Case 5: Stopping
At least two GCB's in the group are closed.
If [PGN.act.tot + Preserve.parallel + Physt + Prated < Prated.tot] a engine is stopped. (e)
Example
The real power supplied by the mains, which is to be adjusted, is 0 kW. This value is entered as the set point val-
ue (see chapter "Controllers") as "I0000kW" (corresponds to "E0000kW"). The reserve power in the system
should be 40 kW. The power hysteresis should be 20 kW. Three generators are to be operated within the group.
The rated power of a generator is 200 kW. The minimum power of a generator should be 30 kW.
Case 3: Power supplied by the mains, with which the first engine is started:
The power supplied by the mains must be at least 30 kW in order for the first engine to start. This is then
operated with a minimum power of 30 kW.
If the generator real power exceeds 160 kW, negative deviation from the pre-specified reserve power has
occurred. As a result of this, the next engine is started.
Case 4: Generator real power of each individual generator, at which the third engine is started:
If the generator real power of both generators exceeds 360 kW (each generator supplies more than
180 kW), negative deviation from the pre-specified reserve power has occurred. As a result of this, the
next engine is started.
Case 5: Generator real power of each individual generators, at which one engine is stopped:
If the generator real power of the three generators falls below 340 kW (each individual generator below
113.3 kW), one engine is stopped. After one engine has been stopped, the reserve power is still available.
Case 5: Generator real power of each individual generator, at which one of the two engines is stopped:
If the generator real power of the two generators falls below 140 kW (each individual generator below
70 kW), one engine is stopped. After the engine has been stopped, the reserve power is still available.
If the generator falls below its minimum real power minus hysteresis, the engine is stopped. The power
imported from the mains therefore remains at the value that is to be controlled until just prior to stopping.
Following stopping, the power supplied by the mains increases to 10 kW.
NOTE
The reserve power (Parameter 116) should be selected in such a manner that expected load swings will
not overload the generator.
Parameter 116 Load dependent start/stop: reserve power (isolated operation) 0 to 9,999 kW
Reserve power
isol.op. 0000kW Starting of an additional engine is determined via the reserve power. The reserve
power results from the currently available total generator rated real power (genera-
tor rated real power number of closed GCB's) and the currently available total
generator actual real power. If the currently available total generator actual real
power is subtracted from the currently available total generator rated real power,
this results in the system's reserve power. If negative deviation from this reserve
power occurs, the next engine is started.
Parameter 117 Load dependent start/stop: start delay (isolated operation) 0 to 999 s
Add-on delay
isol.op. 000s Starting may be delayed even if the engine's start power (Parameter 110) has been
reached. In order to avoid starting the engine in the event of short-term load
swings, a start delay may be entered in seconds. The start power (Parameter 110)
must therefore be present without interruption during this period of time, in order
to ensure that the engine is started. If the load drops below the set start power limit
before the time configured here expires, the counter is reset to 0.
Parameter 118 Load dependent start/stop: stop delay (isolated operation) 0 to 999 s
Shed-off delay
isol.op. 000s Stopping can be delayed even if the engine's stop power (Parameter 113) has been
reached. In order to avoid shutting the engine down in the event of short-term load
swings, a stop delay may be entered in seconds. The stop power (Parameter 113)
must therefore be present without interruption during this period of time, in order
to ensure that the engine is stopped. If the load rises above the set stop power limit
before the time configured here expires, the counter is reset to 0.
General
Example
Two generators in an isolated operation are used in parallel with other generators. One generator should always
be in operation.
If the generator real power exceeds 140 kW negative deviation from the pre-specified minimum reserve
power occurs. As a result of this, the next engine is started.
If, in the case of outgoing isolated load, the total actual generator real power is reduced to such an extent
that one generator is enough to ensure the reserve power, the second engine is stopped.
Interface
NOTE
For remote acknowledgement of alarms, a remote stop while in idle mode must be performed. If the
control is in an isolated operation, an acknowledgement combined with a remote start must be per-
formed.
Parameter 122 Remote acknowledgment of F2/F3 alarms via the interface ON/OFF
Ackn. F2,F3 via
COM interf ON ON................ Alarm acknowledgement of alarms of the alarm classes F2/F3 via the
interface is enabled.
if COMX1X5 = ON only
OFF.............. Alarm acknowledgement of alarms of the alarm classes F2/F3 via the
interface is disabled. Acknowledgment can be performed via the dis-
crete input "Acknowledgment" (terminal 6) or via the push button
"RESET".
NOTE
For the description of the second interface (Option SB and Option SC) refer to the following manuals:
Option SB (e.g. Option SB03) = manual 37200
Option SC (e.g. Option SC06) = manual 37182
Breaker
Parameter 125 Configuration of the breakers YES/NO
Configure
breaker YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES ..............The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO ................The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
Functional Description
Permissible Limits
If the generator or mains monitoring for over-/undervoltage (Parameter 201) or over-/underfrequency (Para-
meter 195) is disabled, the CB logic (Parameter 126) and the control system are controlled by internally defined
limit values.
For the busbar, always the internally defined limit values are used.
Voltage Frequency
Generator VGen: 75 to 115 % VRatedSystem fGen: 80 to 110 % fRatedSystem
Busbar VBusbar: 85 to 112.5 % VRatedSystem fBusbar: 90 to 110 % fRatedSystem
Mains VMains: 85 to 112,5 % URatedSystem fMains: 90 to 110 % fRatedSystem
Table 3-4: Limit values, permissible limits
The permissible limits refer to the respective rated values in the system, i.e. the rated system voltage, configured
in Parameter 23, and the rated system frequency, configured in Parameter 11.
Synchronization
Automatic mode
The operation mode AUTOMATIC is selected
One of the circuit breaker logics (Parameter 126) "PARALLEL" (mains parallel operation), "INTER-
CHANGE" (mains interchange (import/export) real power control) or "CLOSED TRANSIT." (make-before-
break/overlap synchronization) has been selected
No class F2 or F3 alarms are present
An "Automatic 1" (terminal 3) or "Automatic 2" (terminal 5) input has been enabled, a remote starting signal
has be activated via the interface, or an additional engine will be started in an emergency power operation and
will be synchronized to the busbar
The busbar has been energized (the control measures a voltage)
The engine is running and the generator voltage and frequency are within the permissible limits
The delayed engine monitoring (Parameter 307) has expired (this does not apply in the case of emergency
power)
The rotating field of the generator and the mains voltages are identical and no alarms are displayed
Manual mode
The operation mode MANUAL has been selected
One of the circuit breaker logics (Parameter 126) "PARALLEL" (mains parallel operation), "INTER-
CHANGE" (mains interchange (import/export) real power control) or "CLOSED TRANSIT." (make-before-
break/overlap synchronization) has been selected
No class F2 or F3 alarms are present;
The busbar has been energized (the control measures a voltage)
The engine is running and the generator voltage and frequency are within the permissible limits
The push-button "GCB ON" has been pressed
The rotating field of the generator and the mains voltages are identical and no alarms are displayed
Automatic mode
The operation mode AUTOMATIC has been selected
One of the circuit breaker logics (Parameter 126) "PARALLEL" (mains parallel operation), "INTER-
CHANGE" (mains interchange (import/export) real power control) or "CLOSED TRANSIT." (make-before-
break/overlap synchronization) has been selected
No class F2 or F3 alarms are present
The busbar has been energized (the control measures a voltage)
The mains voltage is present and within the permissible limits
The engine is running and the generator voltage and frequency are within the permissible limits
The discrete input "Reply: GCB is open" has not been enabled (the GCB is closed)
The discrete input "Enable MCB" has been enabled;
The rotating field of the generator and the mains voltages are identical and no alarms are displayed
Manual operation
The operation mode MANUAL has been selected;
One of the circuit breaker logics (Parameter 126) "PARALLEL" (mains parallel operation), "INTER-
CHANGE" (mains interchange (import/export) real power control) or "CLOSED TRANSIT." (make-before-
break/overlap synchronization) has been selected;
No class F2 or F3 alarms are present;
The busbar has been energized (the control measures a voltage);
The mains voltage is present and within the permissible limits;
The engine is running and the generator voltage and frequency are within the permissible limits;
The discrete input "Reply: GCB is open" has not been enabled (the GCB is closed);
The discrete input "Enable MCB" has been enabled;
The push-button "MCB ON" has been pressed;
Load test: On termination of the load test (circuit breaker logics (Parameter 126) "INTERCHANGE" (mains
interchange (import/export) real power control) or "CLOSED TRANSIT." (make-before-break/overlap syn-
chronization), the GCB is opened;
The rotating field of the generator and the mains voltages are identical (and no alarms are displayed);
Automatic mode
The operation mode AUTOMATIC has been selected
No class F2 or F3 alarms are present
The Parameter 145 "GCB dead bus start" has been configured to "ON"
The busbar has not been energized (the control measures no voltage)
The engine is running, and the generator voltage and frequency are within the permissible limits
The discrete input "Reply: MCB is open" has been enabled (the MCB is open)
If load is shared via the CAN bus
- No GCB may be closed if the configured system is isolated operation in parallel with other generators
- The generator with the lowest control/generator number (Parameter 4) will be the first to close its GCB
Manual mode
The operation mode MANUAL has been selected
No class F2 or F3 alarms are present
The busbar has not been energized (the control measures no voltage)
The engine is running, and the generator voltage and frequency are within the permissible limits
The discrete input "Reply: MCB is open" has been enabled (the MCB is open)
If load is shared via the CAN bus
- No GCB may be closed if the configured system is isolated operation in parallel with other generators
- The generator with the lowest control/generator number (Parameter 4) will be the first to close its GCB)
The push-button "GCB ON" has been pressed
The permissible limits refer to the respective rated values in the system, i.e. the rated system voltage, configured
in Parameter 23, and the rated system frequency, configured in Parameter 11.
Automatic mode
The operation mode AUTOMATIC has been selected
The Parameter 149 "MCB dead bus start" has been configured to "ON"
The busbar is not been energized (the control measures no voltage)
The mains voltage is present and within the permissible limits
The discrete input "Reply: GCB is open" has been enabled (the GCB is open)
The discrete input "Enable MCB" has been enabled
If load is shared via the CAN bus
- No MCB may be closed if the configured system is isolated operation in parallel with other generators
- The generator with the lowest control/generator number (Parameter 4) will be the first to close its MCB
Manual mode
The operation mode MANUAL has been selected
The busbar is not been energized (the control measures no voltage)
The mains voltage is present and within the permissible limits
The discrete input "Reply: GCB is open" has been enabled (the GCB is open)
The discrete input "Enable MCB" has been enabled
The push button "MCB ON" has been pressed
If load is shared via the CAN bus
- No MCB may be closed if the configured system is isolated operation in parallel with other generators
- The generator with the lowest control/generator number (Parameter 4) will be the first to close its MCB
The permissible limits refer to the respective rated values in the system, i.e. the rated system voltage, configured
in Parameter 23, and the rated system frequency, configured in Parameter 11.
Open Breaker
Open GCB
The GCB will be opened both when the relay "Command: GCB close" de-energizes (only if "continuous pulse"
has been configured; Parameter 130), and relay "Command: GCB open" is energized. The GCB will be opened
under the following circumstances:
If a mains failure is detected and the mains decoupling is configured to the GCB (Parameter 159 or Para-
meter 160 depending on control unit)
In the operation mode STOP
If a class F2 or F3 alarm is present
Upon pressing the push-button "GCB OFF" or [GCP-32] "MCB ON" (depending on the breaker logic which
has been configured) in operation mode MANUAL
Upon pressing the push-button "STOP" in operation mode MANUAL
Upon pressing the push-button "GCB OFF" or [GCP-32] "MCB ON" (depending on the breaker logic which
has been configured) in operation mode LOAD TEST
In the event of an automatic stopping in the operation mode AUTOMATIC
[GCP-32] following the "CLOSED TRANSIT." (make-before-break/overlap synchronization) of the MCB
[GCP-32] before the MCB is closed to the dead busbar in the case of the breaker logic "OPEN TRANSIT."
(break-before-make/changeover)
In critical mode/sprinkler operation, provided that no emergency power operation is present
[GCP-32] following the "INTERCHANGE" (mains interchange (import/export) real power control) of the
MCB
If a mains monitoring triggers and the mains decoupling is configured to EXT (Parameter 160)
If emergency power (AMF) is enabled (mains failure)
following the "CLOSED TRANSIT." (make-before-break/overlap synchronization) of the GCB
Before the GCB is closed to the dead busbar in the case of the breaker logic "OPEN TRANSIT." (break-
before-make/changeover)
Upon pressing the push-button "MCB OFF" or "GCB ON" (depending on the breaker logic which has been
configured) in operation mode MANUAL
Upon pressing the push-button "MCB OFF" or "GCB ON" (depending on the breaker logic which has been
configured) in operation mode LOAD TEST
Following the soft loading (interchange synchronization) of the MCB
Breaker Logic
NOTE
Using the discrete input "Change breaker logic via terminal 64" (Parameter 233), the breaker logic may
be switched between two different breaker logics (description on page 108). The desired standard
breaker logic is configured via the following parameter (Parameter 126). If Parameter 232 is configured
to "ON", the discrete input terminal 64 is used as a Control input. When a signal to terminal 64 is de-
tected, the breaker logic configured in Parameter 233 is used. If the signal is terminated, the breaker
logic configured in Parameter 126 is used again. Therefore it is possible during operation to change
between the breaker logic "PARALLEL" (automatic synchronizing) and "EXTERNAL" (manual synchro-
nizing).
GCP-31 GCP-32
EXTERNAL EXTERNAL
PARALLEL PARALLEL
--- OPEN TRANSIT.
--- CLOSED TRANSIT.
--- INTERCHANGE
A detailed explanation for each mode may be found in the following text.
Parallel operation is enabled via configuration of the parameter (Parameter 126) to "PARALLEL".
NOTE
Parallel breaker logic must be selected for the following operation modes:
Isolated operation
Isolated operation in parallel with other generators
Mains parallel operation
NOTE
When a stop command is issued to the engine, with the exception of a class F3 alarm, soft loading
(power reduction) is carried out before opening the GCB.
Mains interchange (import/export) real power control is enabled via configuration of the parameter (Para-
meter 126) to "INTERCHANGE".
NOTE
For this breaker logic to function correctly, the mains power measurement must be connected proper-
ly. The power measurement must also be assigned the properly process identifier (C, I, or E).
In the event of an add-on request, a change is made from mains to generator supply. The following occurs:
The GCB is synchronized and closed
The generator assumes load until the mains interchange (import/export) real power is "zero"
The MCB is opened
When a shed-off request has been issued, a change is made from generator to mains supply. The following oc-
curs:
The MCB is synchronized and closed
The generator sheds load until real power is "zero"
The GCB is opened
NOTE
The circuit breakers are opened irrespectively of the power.
In the event of an engine request, a change is made from mains to generator supply. The following occurs:
The GCB is synchronized and closed
The MCB is opened and the generator assumes all loads
After the engine shed-off request has been issued, a change is made from generator to mains supply. The follow-
ing occurs:
The MCB is synchronized and closed
The GCB is opened and the mains assume all loads
NOTE
The maximum time between reply CB and CB open command is 500 ms.
Open transition (break-before-make/change over logic) is enabled via configuration of Parameter 126 to "OPEN
TRANSIT.".
In the event of an engine add-on request, a change is made from mains to generator supply. The following oc-
curs:
The MCB is opened
The GCB is closed
After the engine shed-off request has been issued, a change is made from generator to mains supply. The follow-
ing occurs:
The GCB is opened
The MCB is closed
All breaker control must be carried out via master controller (e.g. a PLC). The GCP controller will only issue
opening and closing pulses to the MCB and GCB when in the MANUAL operating mode. The GCP controller
always issues the breaker open command under fault conditions.
Overview GCP-32
Overview GCP-31
Stop: The maximum amount of time generator will shed load is set here. If the gene-
rator load does not drop below 3 % of the generator rated power (Parameter 32)
within this time, the GCB is opened.
Start with soft loading: If the mains interchange (import/export) real power value
does not reach 0 kW in breaker logic "INTERCHANGE" within the time configured
here; a class F1 alarm and an alarm message are issued. At the same time, the relay
manager relay, which is programmed with relay manager function 78 (Appendix B)
is enabled and the MCB is prevented from opening.
Parameter 128 Max. perm. time with F2 alarms for starting a further engine 0 to 999 s
Open GCB with F2
max.time 000s Prerequisite: Load sharing (Parameter 103) and automatic start/stop (Parameter 108
or Parameter 109) are configured to "ON". The generator is in isolated operation and
at least one additional generator is connected to a busbar.
If a class F2 alarm occurs the engine shutdown may be delayed by the time confi-
gured here. This permits another engine to attempt to start in order to assume the
load. After the configured time expires the engine with the F2 alarm condition will
shutdown regardless if another engine was able to start and assume the load.
Closing and opening of the GCB and the MCB are described in the following figures (Figure 3-6 and
Figure 3-7). Changing of the breaker control logic is configured using Parameter 129 and has the described effect
on the signal sequence (the operation of the MCB cannot be carried out by means of the continuous pulse). If the
"Automatic breaker deblocking" (Parameter 137) is configured to "ON", an open pulse is issued prior to each
close pulse. The discrete input "Enable MCB" (terminal 54) enables/disables closing the MCB. A closed MCB is
not opened.
Time/s
4 7
'Command: close
MCB' (16/17)
Time/s
'Command: open .. 9 13
.. GCB' (41/42)
.. MCB' (39/40) 2/0,8 s
12
Time/s
'Reply: .. 5 6 11
.. GCB is open' (4/7)
.. MCB is open' (54/7)
10
Time/s
'Impulse' logic (GCB and MCB): 1 Enable MCB; 2 Synchronization; 3 Connect time reached:
close GCB/MCB: 4 Closing pulse for GCB/MCB enabled; 5 Inherent delay; 6 Reply GCB/MCB; 7 Closing
pulse disabled;
open GCB/MCB: 9 Opening pulse GCB/MCB enabled; 10 Inherent delay; 11 Reply GCB/MCB; 12 Time
delay (GCB: 2 s; MCB: 0.8 s); 13 Opening pulse disabled.
Time/s
4 7
'Command: close
GCB' (14/15)
Time/s
In both cases, the relay "Command: open GCB" (terminal 41/42) is energized to
open the GCB.
Open/Close GCB
Parameter 130 Opening the GCB (terminal 41/42) NO-contact/NC-contact
GCB open relay
---------------- NC-contact...If the GCB is to be opened, the relay "Command: open GCB" (ter-
minal 41/42) remains energized. Following the "Reply: GCB is open"
the relay de-energizes.
NO-contact .If the GCB is to be opened, the relay "Command: open GCB" (ter-
minal 41/42) de-energizes. Following the "Reply: GCB is open" the
relay energizes again.
Parameter 132 Max. perm. differential frequency for synchronization (neg. slip) 0.00 to -0.49 Hz
Synchronize
df min -0.00Hz The prerequisite for a connect command being issued is that the differential fre-
quency is above the configured differential frequency. This value specifies the low-
er frequency limit (negative value corresponds to negative slip generator fre-
quency is less than the busbar frequency in the case of GCB synchronization;
busbar frequency is lower than the mains frequency for MCB synchronization).
Parameter 133 Max. perm. differential voltage for synchronization 01.0 to 20.0 %
Synchronize
dV max 00.0% L This value refers to the parameter "Rated volt. in system" (Parameter 19).
A connect command will only be issued when the measured voltage falls below the
configured differential voltage.
Parameter 134 Min. pulse duration of connect relay for synchronization 0.02 to 0.26 s
Synchronize
time pulse>0.00s The duration of the close pulse can be adjusted to the breaker (valid for synchroni-
zation and dead bus start).
If the following parameter (Parameter 143) is configured to "ON", synchronization time monitoring is per-
formed: If the synchronization of the GCB or [GCP-32] MCB is initiated, the timer is started following the ter-
mination of the delayed engine monitoring. If the breaker has not closed following the expiration of the confi-
gured time, an F1 alarm message is issued.
NOTE
If during an enabled "MCB monitoring" (Parameter 158) an alarm is detected while closing the MCB, a
emergency power operation is performed (if this has been configured to ON; Parameter 164).
If the busbar is de-energized, a dead bus start of the GCB or the MCB is performed. If closing commands for the
MCB and the GCB are issued simultaneously, priority is given to the MCB provided the discrete input "Enable
MCB" (terminal 54) has been enabled.
Parameter 146 Maximum differential frequency for GCB dead bus start 0.05 to 5.00 Hz
GCB dead bus op.
df max 0.00Hz The prerequisite to issuing a close command is that the monitored generator fre-
quency may deviate from the generator rated frequency by no more than this value.
Parameter 147 Maximum differential voltage for GCB dead bus start 01,0 to 15,0 %
GCB dead bus op.
dV max. 00,0% L This value refers to the parameter "rated voltage in system" (Parameter 19).
The prerequisite to issuing a close command is that the monitored generator voltage
may deviate from the generator rated frequency by no more than this value.
Parameter 151 Max. perm. diff. frequency for GCB connection (pos. slip) 0.05 to 9.99 Hz
Switching-on GCB
df max 0.00Hz The prerequisite for issuing a close command is the monitored generator frequency
may deviate from the generator rated frequency by no more than this value. This
value specifies the upper frequency limit (positive value corresponds to positive
slip generator frequency is higher than the busbar frequency in the case of GCB
synchronization).
Parameter 152 Min. perm. diff. frequency for GCB connection (neg. slip) 0.0 to -9.99 Hz
Switching-on GCB
df min -0,00Hz The prerequisite for issuing a close command is the monitored generator frequency
may deviate from the generator rated frequency by no more than this value. This
value specifies the lower frequency limit (negative value corresponds to negative
slip generator frequency is less than the busbar frequency in the case of GCB
synchronization).
If Parameter 154 is configured to "ON", closing time monitoring is performed: A timer is started when the clos-
ing of the GCB is initiated following the termination of the delayed engine monitoring. If the breaker has not
closed following the expiration of the configured time, an F1 alarm message is issued.
Breaker Monitoring
Upon CLOSING - If "GCB monitoring" (Parameter 157) and/or "MCB monitoring" (Parameter 158) have been
configured "ON", GCB and/or MCB monitoring is performed (exception: the breaker logic is configured "EX-
TERNAL" (Parameter 126). If the breaker cannot be closed after five attempts, a class F1 alarm is issued. If a re-
lay has been assigned relay manager functions 74 or 75, it will be energized.
Upon OPENING - When opening a circuit breaker an open pulse is issued. If a reply is detected 2 seconds after
the open pulse was issued that the MCB or GCB has not opened, an class F1 alarm message is issued. If a relay
has been assigned relay manager functions 76 or 77, it will be energized:
Mains Decoupling
NOTE
If the mains monitoring (frequency and voltage) is disabled, no mains decoupling is performed.
Parameter 159 Decoupling from the mains via ... GCB; GCB->EXT; EXT; EXT->GCB
Mains decoupling
via ------ GCB .............If a mains failure (Parameter 206 to Parameter 219) occurs the GCB
will be opened. (The mains failure is detected by means of the mains
at GCP-31 only
voltage [terminals 50/51/52]).
GCB->EXT..If a mains failure (Parameter 206 to Parameter 219) occurs the GCB
will be opened. (The mains failure is detected by means of the mains
voltage [terminals 50/51/52]). An alarm message will be issued with
the end of the delay time (Parameter 161) if terminal 4 does not
detect a reply that the GCB has opened. The relay assigned relay
manager function 76 will be energized as well. The "Command: open
GCB" relay (terminal 41/42) will be de-energized and the "Com-
mand: MCB open" relay (terminals 39/40) is energized.
Issuing of class F1 alarm
EXT ..............If a mains failure (Parameter 206 to Parameter 219) occurs the relay
with the "Command: MCB open" relay (terminals 39/40) will be
energized. (The mains failure is detected by means of the mains vol-
tage [terminals 50/51/52]).
EXT->GCB..If a mains failure (Parameter 206 to Parameter 219) occurs the relay
with the "Command: MCB open" relay (terminals 39/40) will be
energized. (The mains failure is detected by means of the mains vol-
tage [terminals 50/51/52]). An alarm message will be issued with the
end of the delay time (Parameter 161) if terminal 54 does not detect a
reply that the breaker has opened. The relay assigned relay manager
function 77 will be energized as well. The "Command: MCB open"
relay (terminals 39/40) will be de-energized and the "Command:
open GCB" relay (terminals 41/42) is energized.
Issuing of class F1 alarm
NOTE
If the mains monitoring (frequency and voltage) is disabled, no mains decoupling is performed.
Parameter 160 Decoupling from the mains via ... GCB; GCB->MCB; MCB; MCB->GCB
Mains decoupling
via ------ GCB ............. If a mains failure (Parameter 206 to Parameter 219) occurs the GCB
will be opened. (The mains failure is detected by means of the mains
at GCP-32 only
voltage [terminals 50/51/52]).
GCB->MCB If a mains failure (Parameter 206 to Parameter 219) occurs the GCB
will be opened. (The mains failure is detected by means of the mains
voltage [terminals 50/51/52]). An alarm message will be issued with
the end of the delay time (Parameter 161) if terminal 4 does not
detect a reply that the GCB has opened. The relay assigned relay
manager function 76 will be energized as well. The "Command: open
GCB" relay (terminal 41/42) will de-energize and the "Command:
open MCB" relay (terminals 39/40) is energized.
Issuing of class F1 alarm
MCB ............ If a mains failure (Parameter 206 to Parameter 219) occurs the MCB
will be opened. (The mains failure is detected by means of the mains
voltage [terminals 50/51/52]).
MCB->GCB If a mains failure (Parameter 206 to Parameter 219) occurs the MCB
will be opened. (The mains failure is detected by means of the mains
voltage [terminals 50/51/52]). An alarm message will be issued with
the end of the delay time (Parameter 161) if terminal 54 does not
detect a reply that the MCB has opened. The relay assigned relay
manager function 77 will be energized as well. The "Command: open
MCB" relay (terminals 39/40) will de-energize and the "Command:
open GCB" relay (terminals 41/42) is energized.
Issuing of class F1 alarm
WARNING
During maintenance of the busbar be aware that an open MCB will be closed by the GCP when the
mains settling time (Parameter 220; starts when voltage is detected on the mains) expires if Para-
meter 162 is configured as "YES". Configuring Parameter 162 as "NO" or take other measures to pre-
vent the busbar from being energized.
NOTE
Emergency power is only possible with synchronous generators utilizing 2 circuit breakers (i.e. GCP-
32 or GCP-31 with LS 4 coupling).
Prerequisite: The emergency power (AMF) function may only be enabled with synchronous generators using
Parameter 163 ("Emergency power"). Emergency power operations are only performed in AUTOMATIC or
TEST mode regardless of the status of the discrete inputs "Automatic 1" and "Automatic 2".
NOTE
If the "Engine enable" or "Engine block" function is assigned to terminal 6 (Parameter 240), emergency
power can be prevented or interrupted from an external source through a discrete input. Refer to
"Terminal 6" on page 111.
If Parameter 236 is configured ON and discrete input 11 at terminal 68 is energized, emergency power
operation will also be prevented or interrupted (see
Enable 'Emergency OFF' via terminal 68 on page 110).
Activation of emergency power: If a mains voltage fault (over-/undervoltage, -frequency or phase/vector jump)
is detected on any single phase of terminals 50/51/52 without interruption for the duration of the emergency
power start delay time (Parameter 165), emergency power is activated. A mains voltage fault is defined as fol-
lows: If the mains watchdogs (Parameter 206 and/or Parameter 211) are configured to ON and the applicable
limit values set there are surpassed; otherwise, the limits are internally defined as follows:
Emergency power (AMF) is also initiated through the detection of a breaker alarm when the MCB is closed. In
order to enable this, Parameter 164 ("Emergency power) and Parameter 158 ("MCB monitoring") must be confi-
gured to "ON".
If emergency power is triggered, the engine is started unless the sequence is interrupted by an alarm or the
change of the operation mode.
If the mains return during the start cycle, the MCB is not opened. The engine starts and continues running un-
til the mains settling time (Parameter 220) expires. If another mains fault occurs during this time, the MCB is
opened and the GCB is closed to the dead busbar. The engine shuts down following the expiration of the
mains settling time (Parameter 220) if no additional mains faults occur.
The GCB will be closed regardless of the engine delay time once the dead bus limits have been reached.
If the mains returns during emergency power operation while the GCB is closed, the MCB will be synchro-
nized after the mains settling time (Parameter 220) has expired.
Emergency power: In the event of an active emergency power operation, the message "Emergency power" is
displayed.
Emergency power: Following a mains fault the "emergency power start delay" (Parameter 165) must expire be-
fore the engine is started. Once the voltage and frequency limit values are reached, the MCB is opened and the
GCB is closed to the dead busbar. The generator supplies the load.
Return of the mains: Following the return of the mains the control remains in the emergency power operation
until the mains settling time has expired (Parameter 220) before synchronization of the MCB is initiated. After
closing the MCB, the control returns to its original operation mode. If the engine is to be shut down after the
emergency power operation is over, a power reduction (soft unloading) is carried out if the real power controller
(Parameter 87) is configured to ON.
If the mains return during the start cycle, the MCB is not opened. The engine remains in idle mode during the
mains settling time (Parameter 220) in order to enable the immediate closing of the GCB in the event of further
mains faults.
Emergency power: Following a mains fault the "emergency power start delay" (Parameter 165) must expire be-
fore the engine is started. Once the voltage and frequency limit values are reached, the MCB is opened and the
GCB is closed to the dead busbar. The generator supplies the load.
Return of the mains: Following the return of the mains the control remains in the emergency power operation
until the mains settling time has expired (Parameter 220) before transitioning back (via an open transition/over a
dead busbar) to mains supply. If an engine request is present following the expiration of the mains settling time
(Parameter 220), the generator will remain in isolated operation.
If the mains return during the start cycle, the MCB is not opened. The engine remains in idle mode during the
mains settling time (Parameter 220) in order to enable the immediate closing of the GCB in the event of further
mains faults.
Emergency power: Following a mains fault the "emergency power start delay" (Parameter 165) must expire be-
fore the engine is started. Once the voltage and frequency limit values are reached, the MCB is opened and the
GCB is closed to the dead busbar. The generator supplies the load.
Return of the mains: Following the return of the mains the control remains in the emergency power operation
until the mains settling time has expired (Parameter 220). Synchronization of the MCB (via a closed transi-
tion/over a live busbar) to mains supply is initiated if no engine request is present. Following the closure of the
MCB, the GCB is opened immediately and without any power reduction (soft unloading). If an engine request is
present following the expiration of the mains settling time (Parameter 220), the generator will remain in isolated
operation.
If the mains return during the start cycle, the MCB is not opened. The engine operates in idle mode during the
mains settling time (Parameter 220) in order to enable the immediate closing of the GCB in the event of further
mains faults.
Emergency power: Following a mains fault the "emergency power start delay" (Parameter 165) must expire be-
fore the engine is started. Once the voltage and frequency limit values are reached, the MCB is opened and the
GCB is closed to the dead busbar. The generator supplies the load.
Return of the mains: Following the return of the mains the control remains in the emergency power operation
until the mains settling time has expired (Parameter 220). Synchronization of the MCB (via a closed transi-
tion/over a live busbar) to mains supply is initiated if no engine request is present. Following the closure of the
MCB, the GCB is opened after a power reduction (soft unloading) is performed if the real power controller
(Parameter 87) is configured to "ON". If an engine request is present following the expiration of the mains set-
tling time (Parameter 220), the generator will remain in isolated operation.
If the mains return during the start cycle, the MCB is not opened. The engine operates in idle mode during the
mains settling time (Parameter 220) in order to enable the immediate closing of the GCB in the event of further
mains faults.
ATTENTION
This breaker logic will not permit emergency power in accordance with DIN VDE 0108!
Emergency power: Following a mains fault the "emergency power start delay" (Parameter 165) must expire be-
fore the engine is started. Once the voltage and frequency limit values are reached, the MCB is opened and the
GCB is closed to the dead busbar. The generator supplies the load. No further operation of the GCB and the
MCB are performed, regardless if the mains return.
MCB malfunction: In the operation mode AUTOMATIC without a starting request, the control is in emergency
power standby. If the MCB opens without initiation, the control attempts to reclose the breaker. If the MCB can-
not be reclosed due to an MCB failure, the engine is started and the alarm message "MCB malfunction" is dis-
played, if Parameter 163 ("Emergency power") and Parameter 158 ("Supervision MCB") are configured to "ON".
The GCB is closed and emergency power subsequently supplies the busbar. Following acknowledgement of the
"MCB malfunction" alarm, the MCB synchronized from generator supply to mains supply and the engine shut
down after the expiration of the mains settling time (Parameter 220).
Protection
Parameter 166 Configuration of the protection YES/NO
Configure
monitoring YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" affects only the
display of the subjacent menus. This parameter has the following effects:
YES ..............The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO ................The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
It is possible to monitor two independently configurable generator power limit values. It is possible to output the
tripping to one of these freely configurable relays by means of the relay manager (relay manager function 56
and 80). This function makes it possible to initiate external load shedding.
NOTE
With this function no centralized alarm is issued and no message is displayed. A relay output is
enabled which must be externally evaluated.
WARNING
This function does not operate as generator protection.
If generator protection is necessary, either the generator protection of this control (Parameter 178 and
Parameter 183) or an external protection device should be used.
It is possible to monitor two independently configurable generator power limit values. It is possible to output the
tripping to one of the freely configurable relays by means of the relay manager (relay manager function 67). This
function makes it possible to initiate external load shedding.
NOTE
With this function no centralized alarm is issued and no message is displayed. A relay output is
enabled which must be externally evaluated.
WARNING
This function does not operate as generator protection.
If generator protection is necessary, either the generator protection of this control (Parameter 178 and
Parameter 183) or an external protection device should be used.
NOTE
All percentage values refer to a percentage of the generator rated power (Parameter 32; page 26).
Function: "Positive real power not within the permissible range" - The single-phase or three-phase measured ge-
nerator real power is above the configured limit value of the real power.
NOTE
All percentage values refer to a percentage of the generator rated power (Parameter 32; page 26).
Function: "Real power not within the permissible range" - The real power measured in a single-phase or in a
three-phase system is below the configured limit value for the minimum load or below the configured value for
reverse power. By setting positive threshold values (minimum load monitoring), a shutdown can be performed
before the generator ends up in reverse power.
NOTE
All percentage values refer to a percentage of the generator rated power (Parameter 33; page 26).
Function: "Generator load imbalance not within the permissible range" - The percentage threshold value speci-
fies the permissible deviation of one phase current to the arithmetic mean value of all three phase currents.
Time-Overcurrent Monitoring
NOTE
All percentage values refer to a percentage of the generator rated power (Parameter 33; page 26).
Function: The GCP-30 utilizes a two tier time-overcurrent monitoring with separate adjustable time delays. The
threshold values and delays can be selected so that the monitored current level is independent from the tripping
time. The level 2 overcurrent is used as a fast-triggering high-current stage for protection against short circuits.
The level 1 overcurrent reacts overcurrents below level 2 but above permissible limits that are present over a
longer period of time.
I [%]
I >>
(I2)
I>
(I1)
t2 t1 t [s]
Figure 3-8: Characteristic of the time-overcurrent monitoring
Function: "Generator frequency not within the permissible range" - The generator frequency is outside of the
limit values set for overfrequency or underfrequency. The engine is shut down immediately (class F3 alarm), and
an alarm message is displayed. The activation of generator underfrequency monitoring is delayed by means of
"Delayed engine monitoring" (Parameter 307) in order to enable correct generator start-up.
If this threshold value has been exceeded for at least delay time (Parameter 197),
the following alarm class is initiated.
Issuing of class F3 alarm
If the current value has been fallen below this threshold value for at least the delay
time (Parameter 199), the following alarm class is initiated.
Issuing of class F3 alarm
Function: "Generator voltage not within the permissible range" - If one or more phases of the generator voltage
exceeds the limit values set for overvoltage or undervoltage, the engine is shut down immediately (class F3
alarm) and an alarm message is displayed. The activation of generator undervoltage monitoring is delayed by
means of "Delayed engine monitoring" (Parameter 307) in order to enable generator start-up.
If this threshold value has been exceeded for at least the delay time (Para-
meter 203), the following alarm class is initiated.
Issuing of class F3 alarm
NOTE
The threshold value for generator overvoltage may not exceed 149 V [1] or 495 V [4] for delta connec-
tions, because higher voltages cannot be detected.
If the current value has been fallen below this threshold value for the delay time
(Parameter 205), the following alarm class is initiated.
Issuing of class F3 alarm
Monitoring the mains frequency is absolutely vital if a generator is operated in conjunction with the infinite grid.
In the event of mains failure (e.g. utility power outage) the generator that is operating in parallel with the utility
must be automatically disconnected from the mains. Decoupling from the mains only occurs when both power
circuit breakers (MCB and GCB) are closed.
The limit values configured below are utilized for the assessment emergency power operations if the following
parameters are enabled. The parameters below define if the mains are or arent present. The breaker opening
times do not affect these parameters.
Function: "Mains frequency not within the permissible range" - The mains frequency exceeds the limit values
configured for overfrequency or underfrequency. The power circuit breaker that disconnects from the mains is
immediately opened. The prerequisite of mains frequency monitoring is that the generator is operating in mains
parallel (the MCB and GCB are both closed).
If this threshold value has been exceeded for at least the delay time (Para-
meter 208), the following alarm class is issued. Depending on the configured mains
decoupling procedure, the GCB, MCB, or an external CB will be opened.
Issuing of class F0 alarm
If the current value has been fallen below this threshold value for at least the delay
time (Parameter 210), the following alarm class is issued. Depending on the confi-
gured mains decoupling procedure, the GCB, MCB, or an external CB will be
opened.
Issuing of class F0 alarm
Monitoring the mains voltage is absolutely vital if a generator is operated in conjunction with the infinite grid. In
the event of mains failure (e.g. utility power outage) the generator that is operating in parallel with the utility
must be automatically disconnected from the mains. Decoupling from the mains only occurs when both power
circuit breakers (MCB and GCB) are closed.
The limit values configured below are utilized for the assessment emergency power operations if the following
parameters are enabled. The parameters below define if the mains are or arent present. The breaker opening
times do not affect these parameters.
Function: "Mains voltage not within the permissible range" - If one or more phases of the generator voltage ex-
ceeds the limit values set for overvoltage or undervoltage, the power circuit breaker that disconnects from the
mains is immediately opened. The prerequisite of mains voltage monitoring is that the generator is operating in
mains parallel (the MCB and GCB are both closed).
If this threshold value has been exceeded for at least the delay time (Para-
meter 213), the following alarm class is issued. Depending on the configured mains
decoupling procedure, the GCB, MCB, or an external CB will be opened.
Issuing of class F0 alarm
If the current value has been fallen below this threshold value for the delay time
(Parameter 215), the following alarm class is issued. Depending on the configured
mains decoupling procedure, the GCB, MCB, or an external CB will be opened.
Issuing of class F0 alarm
A phase/vector shift is a sudden change in the voltage curve that is caused by a large generator load change. The
measuring circuit detects a change in a single sine wave. This sine wave is compared with a calculated mean val-
ue from previous measurements. Monitoring encompasses all three phases. The threshold value in degrees speci-
fies the difference in time between the mean and the measured value in reference to a full cycle. Monitoring can
be set in various manners. The phase/vector shift watchdog may be used as an additional means for decoupling
from the mains. The minimum voltage that the phase shift is activated is 70 % of the rated secondary voltage.
Function: "Voltage cycle duration not within the permissible range" - The voltage cycle duration exceeds the
configured limit value for the phase/vector shift. The result is the power circuit breaker that disconnects from the
mains is opened and an alarm message is displayed. The prerequisite for phase/vector shift monitoring is that the
generator is operating in a mains parallel operation (the MCB and GCB are both closed).
NOTE
If monitoring is configured to "threephase", only the second of the following two parameters is visi-
ble; if monitoring is configured to "one-/threephase", both parameters are visible.
Note
For devices with one circuit breaker, refer also to Parameter 119.
If a GCP-32 has both the MCB and GCB open and the mains return, the mains set-
tling time is reduced to 2 seconds when the mains return if the mains settling time
is configured for longer.
Discrete Inputs
Parameter 224 Configuration of discrete inputs YES/NO
Configure
dig.inputs YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
NOTE
The discrete inputs can be used as alarm inputs or control inputs. If they were configured as alarm in-
puts (Parameter 230 to Parameter 238 are configured to "OFF") the parameters in "Alarm Inputs"
(page 106) are valid. If they have been configured as control inputs (Parameter 230 to Parameter 238
are configured to "ON") the parameters in "
Control Inputs" (page 108) are valid.
Alarm Inputs
Discrete input 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Name 1 2 3 4 5 6 7 8 9 A B C D E F G
Terminal 34 35 36 61 62 63 64 65 66 67 68 69 70 71 72 73
Function A A A A A/C A/C A/C A A A/C A A A/C A A A
A..Alarm input; A/C..Alarm or control input (dependent on the configuration)
NOTE
Operating current (NO): The discrete input is enabled by energizing it.
This does not provide wire break monitoring!
Closed circuit current (NC): The discrete input is enabled by de-energizing it.
This may provide wire break monitoring.
Parameter 227 Delayed by firing speed of the discrete alarm inputs 1 to 4 Y/N
Delayed by 1234
eng.speed YYYY If the discrete input used as an alarm input is only to be monitored when the engine
is running ("firing speed reached") is specified here.
Y ...................After engine monitoring has been enabled the discrete input is moni-
tored.
N ...................The discrete input is always monitored.
F0 - Warning alarm - This alarm does not lead to an interruption of the operation. An alarm message is dis-
played without a centralized alarm (horn)
Alarm text.
F1 - Warning alarm - This alarm does not lead to an interruption of the operation. A centralized alarm is issued.
Alarm text + flashing "alarm" LED + group alarm relay (horn).
F2 Triggering alarm - This alarm leads to the shutdown of the engine. A power reduction is performed prior
to the GCB being opened. An engine cool down is performed.
Alarm text + flashing "alarm" LED + group alarm relay (horn) + cool down.
F3 Triggering alarm - This alarm leads to the immediate opening of the GCB and shutdown of the engine.
Alarm text + flashing "alarm" LED + group alarm relay (horn) + shutdown.
NOTE
If terminal 6 is configured to "Sprinkler operation" (override or critical mode; Parameter 239) or if a gas
engine is selected (Parameter 290), the EMERGENCY STOP function must always be assigned to ter-
minal 34. If terminal 34 is not a discrete input, the EMERGENCY STOP function is assigned to the dis-
crete input with the lowest terminal number (this discrete input is then normally the input with terminal
number 61).
NOTE
Certain special characters, numbers, upper and lower case letters may be set.
NOTE
If the unit is equipped with a second interface (Y1-Y5), the alarm texts can only be configured via
LeoPC1.
Control Inputs
Parameter 231 Disabling the change of the mode using terminal 63 ON/OFF
Op.mode blocked
by Ter.63 ON OFF ..............This terminal is used as an alarm input.
ON ................Terminal 63 is used as control input.
If terminal 63 is energized, the operation mode cannot be changed
using the pushbuttons on the face of the control unit.
If this input is configured as control input and energized, it is possible for units with Option A2 from version
4.3010 to select the operation mode externally using the control inputs at terminals 127 and 128. The functionali-
ty is described in the following table:
Note: If several of the terminals 65, 66, 67, 69 are energized in their function as
control input, the terminal with the lowest number is prioritized.
Enable 'Close GCB without engine delay' via terminal 67 (onlyB + X Packages)
Parameter 235 Close GCB before the del. engine monit. expires via terminal 67 ON/OFF
Close GCB asap
by Ter.67 ON OFF.............. This terminal is used as an alarm input.
ON................ This terminal is used as control input.
only B + X Packages
High signal If this terminal utilizes a HIGH signal (energized),
the GCB closes before the delayed engine monitoring
expires.
Low signal If this terminal utilizes a LOW signal (de-energized),
the GCB closes after the delayed engine monitoring
has been expires.
Terminal 6
ATTENTION
The various functions of terminal 6 are enabled at different signal levels!
Sprinkler operation By de-energizing terminal 6 (setting a LOW signal), the sprinkler operation (critical mode)
is enabled in accordance with the functional description. The sprinkler operation is termi-
nated by energizing terminal 6 (application of a HIGH signal). For a description of the
sprinkler operation function read "Sprinkler (Critical) Operation" on page 112).
Engine enabled Terminal 6 has the same function as the STOP push-button: De-energizing terminal 6 (appli-
cation of a LOW signal) prevents the engine from starting and stops the engine if it is al-
ready running. Applying a HIGH signal enables the starting of the engine
Attention: By the use of this function, the emergency power operation may be aborted or
prevented. The emergency power operation is not possible without enabling this function!
The enable engine function only functions in the AUTOMATIC operation mode.
Engine blocked By energizing terminal 6 (application of a HIGH signal) a start of the engine can be pre-
vented. If the engine is running due to an active emergency power operation, energizing this
discrete input will stop it. The engine block function is only possible in the AUTOMATIC
operation mode. The function of this mode is the opposite of the function of the "Engine
enabled" mode.
Ext. acknowledgment Alarms can be acknowledged externally by energizing terminal 6 (change from a LOW to a
HIGH signal) in the STOP and AUTOMATIC operation modes. In order to achieve addi-
tional acknowledgements, terminal 6 must first be de-energized and then energized again. If
terminal 6 is continuously energized (HIGH signal), there is no effect on the acknowledge-
ment and suppression of alarm messages.
STOP mode By energizing terminal 6 (application of a HIGH signal) the STOP mode is enabled. If the
signal is removed (de-energized), the operation mode will revert back to the mode that was
active prior to terminal 6 being energized.
Start without CB If the terminal 6 is energized, the engine starts. No synchronization is performed and the
GCB is not closed (no switching to dead busbar). The GCB is closed only if an emergency
power operation is enabled. After the return of the mains, the load is transferred to the mains
according to the configured breaker logic. An engine start command from terminal 6 is a
higher priority than a start command from terminals 3/5. If terminal 6 is selected, termin-
als 3/5 are ignored. If the generator is in a mains parallel operation mode with "Parallel"
breaker logic and terminal 6 is energized, the GCB is opened following a power reduction.
The generator will continue to operate without load and an open GCB.
Parameter 240 Perform engine cool down if starting without CB has been selected ON/OFF
Start withno GCB
cool down ON ON ................After removing the start request, an engine cool down is performed
for the time configured in Parameter 306.
Only if terminal 6 has been con-
figured to "start without CB". OFF ..............After removing the start request, the engine is stopped immediately
without an engine cool down.
Parameter 241 Sprinkler alarm classes only active if terminal 6 is active ON/OFF
Sprinkler shutd.
F1 active ON ON ................If terminal 6 is configured as "Sprinkler operation", the primary
alarm classes will be enabled again after the sprinkler coasting has
Only if terminal 6 has been
configured to expired (energizing terminal 6 and sprinkler coasting 10 minutes).
"Sprinkler operation". OFF ..............If terminal 6 has been configured to "Sprinkler operation", the prima-
ry alarm classes will be enabled again after the sprinkler demand has
concluded (energizing terminal 6).
NOTE
The function "Sprinkler operation" must be assigned to terminal 6.
ATTENTION
Please note that terminal 6 must be energized (apply a HIGH signal) so that a Sprinkler (critical) opera-
tion is not performed. De-energizing terminal 6 (a LOW signal) initiates a Sprinkler (critical) operation
negative logic function.
Sprinkler "ON": If the signal at terminal 6 drops to a Low signal (de-energizes), the Sprinkler (critical) opera-
tion ON command is initiated. The message "Sprinkler operation" is shown on the display. Up to 6 attempts are
made to start the engine if it is not in operation. All fault conditions, which result in a shutdown, become mes-
sages with the exceptions of terminals 34 or 61 and overspeed. The alarm input for terminal 34 retains its set
alarm class. Terminal 61 is used for this if terminal 34 is not present on the control. It is recommended that
EMERGENCY STOP be assigned to one of these terminals.
NOTE
If "Sprinkler operation" (terminal 6) has been activated, class F2 and F3 alarms are converted to class
F1 alarms (exception: terminal 34 or 61 and overspeed).
Class F2 and class F3 alarms Class F1 alarm
"Sprinkler shutdown F1 active": Parameter 241 permits the user to select whether the Sprinkler alarm classes
are active during the Sprinkler coasting or if the primary alarm class will be active after the Sprinkler (critical
mode) request (terminal 6) has terminated.
Sprinkler "OFF": Disabling the Sprinkler (critical) mode discrete input (energizing terminal 6) terminates the
Sprinkler ON command and the message "Sprinkler coasting" appears on the display screen. The message
"Sprinkler coasting" appears. The Sprinkler (critical mode) operation is automatically finished 10 minutes later.
Earlier termination can be achieved by the changing into the STOP mode. When the Sprinkler (critical mode)
operation has concluded, fault conditions that result in shutdowns are enabled again.
Note
The analog inputs [T1] to [T7] are only available in the XP packages as well as the T701 option. The following
specification for the inputs is possible:
Analog input 1 2 3 4 5 6 7
Assignment 0/4 to 20 mA Pt100 VDO #1 VDO #2
Terminal 93/94/95 96/97/98 99/100/101 101/102/103 104/105/106 107/108/109 110/111/112
Function Alarm input/Control input 1 Alarm input
VDO #1 = 0 to 180 Ohm, VDO #2 = 0 to 380 Ohm
NOTE
If you want to visualize the analog inputs via the PC program LeoPC1 (Firmware Version 4.0.xxx or
higher) please note the following:
1. Establish a connection between LeoPC1 and the GCP-30.
2. Select in the menu "Devices" the topic "Refresh Configuration".
3. Restart LeoPC1 according to the requests.
1 The 0/4 to 20 mA inputs can be configured with the functions "Real power set value", "Mains interchange (import/export) real power actual
value" or "Alarm input". Read the description in this manual.
Page 114/174 Woodward
Manual 37278B GCP-30 Series - Genset Control
NOTE
The scalable analog inputs 0/4 to 20 mA can be configured alternatively for the following functions:
Mains interchange (import/export) real power actual value, or
real power set point value.
If one of the both functions is assigned to an available 0/4 to 20 mA input T{x} (see Parameter 34 and
Parameter 91), the corresponding analog input T{x} must be configured to OFF. The analog input can
no longer be used as an alarm input.
0/4 to 20 mA sensors may be measured here. A description and an engineering unit may be assigned to the input.
The analog input is displayed with its description. Two limit levels can be monitored. The first limit level in-
itiates a class F1 alarm, the second limit level initiates a class F3 alarm.
NOTE
If the unit is equipped with a second interface (Y1-Y5), this parameter can only be configured via
LeoPC1.
Parameter 248 0/4 to 20 mA input; limit value for class F1 alarm -9,999 to 9,999
Limit warning
value -0000 If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 251) for at least the delay time (Parameter 250), the fol-
lowing alarm class is initiated.
Issuing of class F1 alarm
Parameter 249 0/4 to 20 mA input; limit value for class F3 alarm -9,999 to 9,999
Limit shutdown
value -0000 If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 251) for at least the delay time (Parameter 250), the fol-
lowing alarm class is initiated.
Issuing of class F3 alarm
Parameter 250 0/4 to 20 mA input; delay time for limit values of class F1 and F3 alarm 0 to 650 s
Delay
limit 1/2 000s In order to initiate an alarm, the measured value must be over or under (dependent
upon Parameter 251) the configured threshold value (Parameter 248 or Para-
meter 249) without interruption for at least this time.
Parameter 251 0/4 to 20 mA input; monitoring for ... high limit mon. / low limit mon.
Monitoring for
---------------- A fault condition is recognized when the measured value has exceeded or fallen be-
low the threshold value (Parameter 248 or Parameter 249).
high limit mon.: The measured value must exceed the threshold value.
low limit mon.: The measured value must fall below the threshold value.
Pt100 inputs may be measured here. The analog input is displayed with its description. Two threshold limits can
be monitored. The first level initiates a class F1 alarm, the second level initiates a class F3 alarm.
NOTE
If the unit is equipped with a second interface (Y1-Y5), the alarm texts can only be configured via
LeoPC1.
Parameter 254 Pt100 input; limit value for class F1 alarm 0 to 200 C
Limit
warning 000C If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 257) for at least the delay time (Parameter 256), the fol-
only B + X Packages
lowing alarm class is initiated.
Issuing of class F1 alarm
Parameter 255 Pt100 input; limit value for class F3 alarm 0 to 200 C
Limit
shutdown 000C If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 257) for at least the delay time (Parameter 256), the fol-
only B + X Packages
lowing alarm class is initiated.
Issuing of class F3 alarm
Parameter 256 Pt100 input; delay time for limit values of class F1 and F3 alarm 0 to 650 s
Delay
limit 1/2 000s In order to initiate an alarm, the measured value must be over or under (dependent
upon Parameter 257) the configured threshold value (Parameter 254 or Para-
only B + X Packages
meter 255) without interruption for at least this time.
Parameter 257 Pt100 input; monitoring for ... high limit mon. / low limit mon.
Monitoring for
---------------- A fault condition is recognized when the measured value has exceeded or fallen be-
low the threshold value (Parameter 254 or Parameter 255).
only B + X Packages
high limit mon.: The measured value must exceed the threshold value.
low limit mon.: The measured value must fall below the threshold value.
NOTE
If temperature limit monitoring is not required, a threshold value, which is higher than the expected
temperature must be configured to the corresponding parameter (e.g. the ambient temperature is
100 C).
Parameter 259 0 to 400 Ohms input; smallest input value -9999 to 9999
Value at
0% 0000 The user must assign a numeric value to the scaleable analog input that corresponds
to the smallest input value Definition of the lower value (i.e. 0 %, e.g. 0 liters) at
only RPQ Package
the minimum analog input value (0 Ohms).
Parameter 260 0 to 400 Ohms input; largest input value -9999 to 9999
Value at
100% 0000 The user must assign a numeric value to the scaleable analog input that corresponds
to the largest input value Definition of the upper value (i.e.100 %, e.g. 1000 li-
only RPQ Package
ters) at the maximum analog input value (400 Ohms).
Parameter 261 0 to 400 Ohms input; limit value for class F1 alarm -9999 to 9999
Limit warning
value 0000 If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 264) for at least the delay time (Parameter 263), the fol-
only RPQ Package
lowing alarm class is initiated.
Issuing of class F1 alarm
Parameter 262 0 to 400 Ohms input; limit value for class F3 alarm -9999 to 9999
Limit shutdown
value 0000 If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 264) for at least the delay time (Parameter 263), the fol-
only RPQ Package
lowing alarm class is initiated.
Issuing of class F3 alarm
Parameter 263 0 to 400 Ohms input; delay time for limit values of class F1 and F3 alarm 0 to 650 s
Delay
limit 1/2 000s In order to initiate an alarm, the measured value must be over or under (dependent
upon Parameter 264) the configured threshold value (Parameter 260 or Para-
only RPQ Package
meter 261) without interruption for at least this time.
Parameter 264 0 to 400 Ohms input; monitoring for ... high limit mon. / low limit mon.
Monitoring for
---------------- A fault condition is recognized when the measured value has exceeded or fallen be-
low the threshold value (Parameter 260 or Parameter 261).
only RPQ Package
high limit mon.: The measured value must exceed the threshold value.
low limit mon.: The measured value must fall below the threshold value.
NOTE
The default threshold values are configured in "bar". If the unit "psi" is configured (Parameter 171) the
display of the measured values as well as the transmission via the interface appears in "psi".
VDO inputs for pressure may be measured here. The analog input is displayed with its description. Two thre-
shold levels can be monitored. The first level initiates a class F1 alarm, the second level initiates a class F3 alarm.
NOTE
If the unit is equipped with a second interface (Y1-Y5), the alarm texts can only be configured via
LeoPC1.
Parameter 268 VDO input, pressure; limit value for class F1 alarm 0.0 to 10.0 bar
Limit warning
value 00.0bar If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 271) for at least the delay time (Parameter 270), the fol-
lowing alarm class is initiated.
Issuing of class F1 alarm
Parameter 269 VDO input, pressure; limit value for class F3 alarm 0.0 to 10.0 bar
Limit shutdown
value 00.0bar If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 271) for at least the delay time (Parameter 270), the fol-
lowing alarm class is initiated.
Issuing of class F3 alarm
Parameter 270 VDO input, pressure; delay time for limit values of class F1 and F3 alarm 0 to 650 s
Delay
limit 1/2 000s In order to initiate an alarm, the measured value must be over or under (dependent
upon Parameter 271) the threshold value (Parameter 268 or Parameter 270) without
interruption for at least this time.
Parameter 271 VDO input, pressure; monitoring for ... high limit mon. / low limit mon.
Monitoring for
---------------- A fault condition is recognized when the measured value has exceeded or fallen be-
low the threshold value (Parameter 268 or Parameter 270).
high limit mon.: The measured value must exceed threshold.
low limit mon.: The measured actual value must fall below the threshold value.
VDO inputs may be measured here (the input has been calibrated to the VDO sender 323.805/001/001 (0 to
380 ohm, 40 to 120 C). The analog input is displayed with its description. Two threshold levels can be moni-
tored. The first level initiates a class F1 alarm, the second level initiates a class F3 alarm.
NOTE
If the unit is equipped with a second interface (Y1-Y5), the alarm texts can only be configured via
LeoPC1.
Parameter 274 VDO input, temperature; limit value for class F1 alarm 40 to 120 C
Limit warning
value 000C If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 277) for at least the delay time (Parameter 276), the fol-
lowing alarm class is issued.
Issuing of class F1 alarm
Parameter 275 VDO input, temperature; limit value for class F3 alarm 40 to 120 C
Limit
shutdown 000C If the measured value exceeds or falls below this configured threshold value (de-
pendent upon Parameter 277) for at least the delay time (Parameter 276), the fol-
lowing alarm class is issued.
Issuing of class F3 alarm
Parameter 276 VDO input, temperature; delay time for limit values of class F1 and F3 alarm 0 to 650 s
Delay
limit 1/2 000s In order to initiate an alarm, the measured value must be over or under (dependent
upon Parameter 277) the threshold value (Parameter 274 or Parameter 275) without
interruption for at least this time.
Parameter 277 VDO input, temperature; monitoring for ... high limit mon. / low limit mon.
Monitoring for
---------------- A fault condition is recognized when the measured value has exceeded or fallen be-
low the threshold value (Parameter 274 or Parameter 275).
high limit mon.: The measured value must exceed threshold value.
low limit mon.: The measured value must fall below the threshold value.
Ana.input --,- This message appears when the measured value exceeds or falls below the measur-
ing range occurs. A fault condition is initiated depending on the values specified
below.
NOTE
If it is determined that the measuring range has been exceeded (wire break) and a fault condition has
been initiated, limit value monitoring for the affected analog input is deactivated.
Fault conditions initiate when the measuring range is monitored at:
4 to 20 mA 2 mA and below
Pt100 216 C and above
180 VDO, 0 to 5 Bar 305 and above
180 VDO, 0 to 10 Bar 305 and above
Note: Above screen (8 inputs) appears if at least 5 analog inputs are equipped. If
less than 5 inputs are equipped, a screen with 4 inputs appears. If less inputs are
equipped than inputs appear in the screen, only the entries for the equipped inputs
are valid.
Note: Above screen (8 inputs) appears if at least 5 analog inputs are equipped. If
less than 5 inputs are equipped, a screen with 4 inputs appears. If less inputs are
equipped than inputs appear in the screen, only the entries for the equipped inputs
are valid.
Outputs
Parameter 281 Configuration of the outputs YES/NO
Configure
outputs YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
NOTE
The list of values and limits for the analog output manager is contained in Appendix A: "Analog Output
Manager" starting on page 141.
Relay Manager
The relay manager enables the assignment of an arbitrary combination of functions to each relay. In order to
achieve this, each function of the control has its own number. A text, which describes a logical condition that
energizes the relay, must now be entered in the configuration menu for each relay. Up to three function numbers
may be combined in this link. The length of the text must not exceed 16 characters. The control can detect incor-
rect function numbers or formula constructions and will not accept these.
NOTE
The relay manager functions are listed in Appendix B: "Relay Manager" starting on page 144.
NOTE
Entering an illegal logical combination deletes the equation.
Engine
Parameter 287 Configuration of the engine YES/NO
Configure
engine YES Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
CAUTION
This delay is ignored in the event of emergency power operation. The engine is
started immediately.
NOTE
The configured number of start attempts (Parameter 294) will be performed.
Speed governor
Approach idle
gas position
Engine monitoring
activated
Start request
Gas valve
Ignition
Starter
t/s
tSt tZV tSPZ tZV tGV tMV tN tZN
Delayed engine
monitoring 00s
Start Stop
Speed curve with Pickup (1) Disengaging of the starter (2) Switching-on of
Speed curve without Pickup the ignition
Ignition and gas ON
Starting Sequence
If the control is equipped with a three-position frequency controller, a continuous signal (time adjustable via
Parameter 298) is output prior to starting the engine at the "Frequency lower" relay output. The starter is then
enabled. Following the expiration of the ignition delay time (Parameter 292) and if the engine is rotating with at
least the configured "minimum speed for ignit." (Parameter 291), the ignition is enabled. Following the expira-
tion of the gas valve delay (Parameter 293), the gas valve is then enabled. If the starting sequence finishes suc-
cessfully (the firing speed (Parameter 308) was exceeded) the starter is disengaged. The gas valve and the igni-
tion remain enabled by means of the firing speed. After reaching the "f-controller: starting frequency" (Para-
meter 50) and the delayed engine monitoring has expired (Parameter 307), the speed controller is enabled.
Stopping Sequence
When the start request is terminated, a power reduction is performed (if the real power controller is enabled,
Parameter 87). After the GCB has opened, an engine cool down is performed (Parameter 306). When the engine
cool down period expires, the gas valve is closed, and the engine is stopped. If the engine speed falls below the
firing speed (Parameter 308), an engine starting sequence is disabled for 10 seconds. If the engine cannot be
stopped, an alarm message is issued after 30 s, and a class F3 alarm is initiated.
Following negative deviation from the firing speed, the ignition remains enabled for an additional
5 seconds so that the remaining gas is able to combust.
In order to ensure a safe shutdown of the gas valves, a separate shutdown circuit must be utilized.
To prevent gas from escaping through the gas line due to stuck relays the following is recommended.
Controlling gas valves with the GCP-30
The GCP-30 relay manager from V4.1001 and on contains function 131. This function exists in the GCP- 30 so
that a relay configured with this function behaves like the "Gas valve" relay.
The wiring diagram shown below is an example of a recommended gas valve control system in the gas line.
Emergency Relay
stop manager
param. 131 K1 K2
GCP-30 44 GCP-30
Figure 3-14: Wiring diagram for opening gas valves with the GCP-30 from V4.1001
Parameter
CAUTION
The engine starting is delay by means of the low-idle position in the event of emer-
gency power operation.
NOTE
The configured number of start attempts (Parameter 300) will be performed.
1500 1/min
Start frequency
f-contr. + time
ZD
Speed governor
Approach idle
gas position
Engine monitoring
activated
Start request
Start relay
Pre-glow
t/s
tSta tVG tEin tSPZ tVG tEin tMV tN
Delayed engine
monitoring 00s
Starting Sequence
If the control is equipped with a three-position frequency controller, a continuous signal (time adjustable via
Parameter 304) is output prior to starting the engine at the "Frequency lower" relay output. Following the expira-
tion of this time, the "Pre-glow" relay will be enabled (pre-glow time is configurable via Parameter 299). Follow-
ing preheating, the fuel relay is enabled (Parameter 305), followed by the crank relay. Once the firing speed
(Parameter 308) has been exceeded, the starter disengages, and the fuel relay remains enabled by means of the
firing speed. After reaching the "f-controller: starting frequency" (Parameter 50) and the delayed engine monitor-
ing has expired (Parameter 307), the speed controller is enabled.
Stopping Sequence
When the start request is terminated, a power reduction is performed (if the real power controller is enabled,
Parameter 87). Once the GCB has opened, an engine cool down is performed (Parameter 306). When the engine
cool down period expires, the fuel relay is de-energized and the engine is stopped. If the engine speed falls below
the firing speed (Parameter 308), the engine starting sequence is disabled for 10 seconds. If the engine cannot be
stopped, an alarm message is issued after 30 s, and a class F3 alarm is initiated.
Parameter
CAUTION
The engine starting is delay by means of the low-idle position in the event of emer-
gency power operation.
Parameter 305 Diesel engine; fuel solenoid logic open to stop / close to stop
Fuel relay logic
---------------- open to stop . The operating solenoid is energized prior to each start sequence. In
order to shutdown the engine, the operating solenoid is de-energized.
close to stop In order to shutdown the engine, the stop solenoid is energized. The
stop solenoid remains energized for an additional 10 seconds once
the engine speed drops below firing speed (Parameter 308) and the
generator voltage is less than 20 V.
Cool Down
Parameter 306 Engine; cool down time 0 to 999 s
Cool down time
000s If the engine performs a normal shutdown (i.e. STOP mode initiated) or stoppage
by means of a class F2 alarm has been initiated, an engine cool down period with
an open GCB and frequency control is performed for this time. If the engine cool
down has terminated (cool down time has been expired) and engine speed (Para-
meter 308) is still detected after 30 seconds, an engine failure to stop message is
displayed.
Note
An engine cool down is performed only if the reply of a closed GCB (terminal 4)
has been enabled for at least 5 seconds.
[RPM]
Rated speed
[1/min; RPM]
Firing
speed [ZD]
Delayed Engine Monitoring And Firing Speed
t [s]
Start request
t [s]
Ignition speed
reached [ZD]
tMV
t [s]
Delayed engine
monitoring
t [s]
Woodward
GCP-30 Series - Genset Control
Note
Accurate measurement is possible above 15 Hz, even if 5 Hz are displayed. If the
Pickup measurement has been configured to "ON", values down to 5 Hz are dis-
played.
Pick-Up
Measuring the engine speed can be performed alternatively by means of a Magnetic Pickup, the generator fre-
quency, or a tacho generator. Refer to the wiring diagram that pertains to your specific controller in ma-
nual 37239, chapter 4.
Plausibility monitoring:
Plausibility monitoring is the comparison of the measured electrical frequency (de-
termined from the generator voltage) and mechanical speed (determined from the
Pickup signal). If the two frequencies are not identical, a class F1 alarm is initiated.
The plausibility monitoring is enabled by the expiration of delayed engine monitor-
ing (Parameter 307) and performed continuously while the generator is operating.
Maintenance Call
Parameter 313 Counter; maintenance call 0 to 9,999 h
Service interval
in 0000h A maintenance interval can be specified with this parameter. After the engine has
been in operation for the number of hours configured here, a maintenance message
(class F1 alarm) is displayed. Following the acknowledgement of the message, the
counter is reset to this value.
Note
Entering "0" will disable the maintenance call.
NOTE
In order to reset the maintenance call prior to the configured time (maintenance call alarm not yet in-
itiated), perform the following procedure:
- Navigate to the display screen "Service in 000h" using the "Select" button.
- Press and hold the "Digit" button for 10 seconds.
- The new maintenance interval is displayed.
Note: The operating hours counbter may only be accessed from code level 2 with
the RPQ Package.
NOTE
If the unit is equipped with option SC06, SC07, or SC08, and the MDEC or J1939 coupling is enabled as
well, the operating hours will be taken over from the engine control unit. Please refer to manual 37313
for further information.
NOTE
If a value is to be input in this parameter other than the factory default, the controller must be in code
level CS2. For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Set and store the desired operating hours
2. Step: Integrate the value which has been saved by ...
-- Terminate the configuration mode and switch to automatic mode
-- Display of the operating hours
-- Press and hold the "Digit" push-button for at least 5 seconds.
The RPQ Rental Package provides an rental duty time counter with minute resolution (max. 9999:59h). It may be
accessed in every code level. This counter is an additional operating hours counter which may be used for charg-
ing the cost when renting the unit.
The rental duty time counter may be reset to 0 before utilization for example. In order to perform this, the unit
must be in code level 2, the rental duty time counter must be displayed, and then the Digit button must be pressed
for at least 5 s.
NOTE
The rental duty time counter cannot be used to count the actual operating hours because it may be re-
set independently from the operating hours counter.
Start Counter
Parameter 315 Counter; number of engine starts 0 to 32,000
Set start
counter 00000 The start counter is used to display how many times the engine has been started.
Following each starting attempt the start counter is increased by one. This permits
the user to display the correct number of starts if this controller is used on an older
engine, a starter is replaced, or this controller is to replace an older controller.
NOTE
If the engine start counter is to be changed from the factory default setting, the controller must be in
code level CS2. For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Set and store the desired number of starts
2. Step: Integrate the value which has been saved by ...
-- Terminate the configuration mode and switch to automatic mode
-- Display the number of engine starts
-- Press and hold the "Digit" push-button for at least 5 seconds
kWh Counter
Parameter 316 Counter; kWh counter set in ... kWh/MWh
kWh counter
set in --- The power produced may be measured in kWh or MWh. The user defined which
scale is desired for the controller with this parameter.
Parameter 317 Counter; kWh counter set for ... 0 to 65,500 kWh/MWh
kWh counter
set 00000--- The user may input values into the kWh/MWh counter (depending on Para-
meter 316) with this parameter. This permits the user to display the correct number
of kWh/MWh for a generator if this controller is used on an older engine or this
controller is to replace an older controller.
NOTE
If the kWh counter is to be changed from the factory default setting, the controller must be in code lev-
el CS2. The counter is set in a two-step procedure due to safety reasons.
The following proceeding is valid:
1. Step: Set and store the desired counter values for the parameters 293 and 294
2. Step: Integrate the stored value by ...
-- Terminate the configuration mode and change to automatic mode
-- Displaying the kWh counter
-- Press and hold the "Digit" push-button for at least 5 seconds
NOTE
If several GCP-30 control units are on one common CAN bus all clocks are synchronized daily at 12:00
o'clock (noon) to the time of the control with the lowest control/generator number. This makes it essen-
tial that each control unit has a different control number.
The relay with Parameter 147 may be enabled time-dependent. There are two parameters to configure an enable
and a disable time for this relay. Another parameter is available to configure the weekdays at which these times
are enabled.
If you want to perform a time-dependent genset start for example, this relay output may be connected to the input
at terminal 3.
NOTE
Since this function affects a relay only, it cannot be enabled and disabled separately. If the function
shall not be used, Parameter 147 must not be configured in the Relay Manager.
A current slave pointer, which records and stores the maximum generator current, is implemented in the control.
The display of the maximum generator current can be selected in the Automatic mode by pressing the "Mes-
sage" push-button. The following screen appears in the display:
Parameter 324 Current slave pointer; display of the maximum generator current
000 000 000 000
max. Gen.current The maximum generator current in each phase is displayed.
Reset: Pressing and holding the "reset" button for 3 seconds while the current slave
pointer screen is being displayed will reset the memory.
Chapter 4.
Commissioning
LIFE THREATENING
CAUTION
Only a qualified technician may commission unit. The "EMERGENCY-STOP" function must be opera-
tional prior to commissioning of the system, and must not depend on the unit for its operation.
CAUTION
Prior to commissioning ensure that all measuring devices are connected in correct phase sequence.
The connect command for the unit circuit breaker must be disconnected at the unit circuit breaker. The
field rotation must be monitored for proper rotation. Any absence of or incorrect connection of voltage
measuring devices or other signals may lead to malfunctions and damage the unit, the engine, and/or
components connected to the unit!
Commissioning Procedure:
1. After wiring the unit and ensuring all voltage-measuring devices are phased correctly, apply the control
system voltage (i.e. 12/24 Vdc). The "Operation" LED will illuminate.
2. By simultaneously pressing the two push-buttons "Digit" and "Cursor", the configuration mode is ac-
cessed. After entering the access code number, the unit may be configured according to the application
requirements (see the chapter regarding the parameters).
3. After applying the measuring variables, the unit will display the measured values. These values should be
confirmed with a calibrated measuring instrument.
4. The initial start of the engine should be performed in the MANUAL operation mode (press the "MA-
NUAL" push-button). Start the engine ("START" push-button) and then stop it ("STOP" push-button).
All generator measured values must be checked. Any alarm messages should be investigated as well.
5. Check the automatic start sequence by means of the TEST operation mode (press the "TEST" push-
button). Test the protections that result in alarms with shutdowns.
6. "AUTO" operation mode (press the "AUTO" push-button): Applying the automatic control inputs and
the engine start request can now carry out automatic starting with subsequent synchronization.
Check synchronization: Check the generator and the generator busbar rotating fields. Check the connect
command with a zero voltmeter (determination of the phase angle) at the generator power circuit breaker
(GCB). If several correct synchronizing pulses have been output, switch the operation mode to "STOP"
and reconnect the connect pulse "Command: close GCB" with the engine in "STOP" mode.
7. If steps 1 through 6 have been carried out successfully, parallel operations may be commenced. It is rec-
ommended to start with a constant power/baseload operation (approx. 25 % of the generator rated power)
initially. While this operation is being carried out, the displayed measured values must be verified. Test
the GCB shutdown. Check the real power controller and if necessary the power factor controller for prop-
er operation. Enter various set point values and verify proper operation.
8. If the mains parallel operation performs in a satisfactory manner, the synchronization of the mains power
circuit breaker (MCB) must be checked:
A power failure in the system must be simulated or observed by the controller. During a mains parallel
operation, change the operation mode from AUTOMATIC to MANUAL. Open the MCB ("MCB ON"
LED will turn off). Press the AUTOMATIC push-button to return the controller back to the AUTOMAT-
IC operation mode.
Check the generator busbar and the mains rotating field. Check the connect command with a zero voltme-
ter (determination of the phase angle) at the MCB. If several correct synchronizing pulses have been out-
put, switch the operation mode to "STOP" and re-connect the connect pulse "Command: close MCB" with
the engine in "STOP" mode.
NOTE
The automatic operation mode is influenced by the input signals "Automatic 1" and "Automatic 2". En-
sure that the power circuit breaker reply messages are processed as the reverse of the condition (i.e.
when the circuit breaker is closed the reply message for the inputs: CB is open (terminal 54) is 0 volts.
The CB aux contacts should be configured as normally closed! Refer to the description of the auxiliary
and control inputs starting on page 10. It is vital that these replies be connected!
Electrical insulation between voltage supply and discrete control and feedback inputs: By the use of corres-
ponding external wiring, the common reference point of the discrete inputs can be electrically isolated from the
supply voltage (0 V, terminal 2). This is necessary if the discrete inputs are not to be triggered with 24 Vdc and
electrical isolation of the control voltage (e. g. 220 Vdc, 220 Vac) from the supply voltage must be insured.
Appendix A.
Analog output manager
(Package XP, Option A2)
NOTE
The functions listed below can only be output correctly if the existing version of the control permits
this.
18 --free-- [C] or
[F] or
freely scaleable
The designation 0 % stands for either 4 mA or 0 mA; the designation 100 % stands for 20 mA. The values may
also be assigned with prefixes (see relay manager function 1).
Definition of power factor cos scaling: According to the scaling of the analog output, the power factor cos
can be output within the range from capacitive values ranging from c0.00 via power factor = 1 to inductive
values up to i0.00.
Capacitive Inductive
Lower distance Higher distance
eg. 0030 eg. 0030
Scalable range (0..20 mA)
k 0.00 eg. k0.70..1.00..i0.70 i 0.00
Appendix B.
Relay Manager
Appendix C.
Interface Protocol
Transmission Telegram
Contents (words) Unit Note
MUX
No.
MUX
No.
Actual mains interchange (import/export)
3/2 11 W 10PNTEXPO
real power
3/3 12 Control register 1 Bit 15 =1 \ Starting enabled (in isolated operation or
Bit 14 =1 / mains parallel operation)
Bit 13 =1 \
--Internal--
Bit 12 =1 /
Bit 11 =1 \ Execution of acknowledgment
Bit 10 =1 / of a class F2/F3 alarm
Bit 9 =1 \ Execution of acknowledgment
Bit 8 =1 / of a class F1 alarm
Bit 7 =1 \
--Internal--
Bit 6 =1 /
Bit 5 =1 \ State of generator busbar 1 = OK
Bit 4 =1 / --Internal--
Note On double /fourfold bits the follow- Bit 3 =1 \
--Internal--
ing is valid: If the indicated bit combination Bit 2 =1 /
is fulfilled (high byte and low byte) ,the Bit 1 =1 \
--Internal--
message is active (otherwise inactive). Bit 0 =0 /
4/1 13 Alarm message IKD (SC06) Bit 15 =1 Failure DI8 of the IKD1
Bit 14 =1 Failure DI7 of the IKD1
Bit 13 =1 Failure DI6 of the IKD1
Bit 12 =1 Failure DI5 of the IKD1
Bit 11 =1 Failure DI4 of the IKD1
Bit 10 =1 Failure DI3 of the IKD1
Bit 9 =1 Failure DI2 of the IKD1
Bit 8 =1 Failure DI1 of the IKD1
Bit 7 =1 --Internal--
Bit 6 =1 --Internal--
Bit 5 =1 --Internal--
Bit 4 =1 --Internal--
Note On double /fourfold bits the follow- Bit 3 =1 --Internal--
ing is valid: If the indicated bit combination Bit 2 =1 --Internal--
is fulfilled (high byte and low byte) ,the Bit 1 =1 --Internal--
message is active (otherwise inactive). Bit 0 =1 --Internal--
4/2 14 Internal alarm 6 Bit 15 =1 MPU plausibility fault
Bit 14 =1 Engine shutdown malfunction
Bit 13 =1 Time overrun, GCB dead bus switching
Bit 12 =1 --Internal--
Bit 11 =1 MCB open switch malfunction
Bit 10 =1 GCB open switch malfunction
Bit 9 =1 MCB synchronization time monitoring
Bit 8 =1 GCB synchronization time monitoring
Bit 7 =1 Range alarm analog input [T8]
Bit 6 =1 Range alarm analog input [T7]
Bit 5 =1 Range alarm analog input [T6]
Bit 4 =1 Range alarm analog input [T5]
Note On double /fourfold bits the follow- Bit 3 =1 Range alarm analog input [T4]
ing is valid: If the indicated bit combination Bit 2 =1 Range alarm analog input [T3]
is fulfilled (high byte and low byte) ,the Bit 1 =1 Range alarm analog input [T2]
message is active (otherwise inactive). Bit 0 =1 Range alarm analog input [T1]
4/3 15 Generator voltage delta V23 V 10UGNEXPO
5/1 16 Generator voltage delta V31 V 10UGNEXPO
5/2 17 Generator voltage wye V1N V 10UGNEXPO
5/3 18 Generator voltage wye V2N V 10UGNEXPO
6/1 19 Generator voltage wye V3N V 10UGNEXPO
No.
MUX
No.
10/3 33 Configuration [T5]-[T8] Display in ... #1# C F bar/10 psi/10 % no unit
No.
MUX
No.
18/1 55 Internal alarm 3 Bit 15 =1 \ F3: Time-overcurrent, level 2 or
Bit 14 =1 / inverse time-overcurrent, IEC255
Bit 13 =1 \
F3: Generator overspeed (Pickup)
Bit 12 =1 /
Bit 11 =1 \
Import power 0 kW not reached
Bit 10 =1 /
Bit 9 =1 \
F3: Generator unbalanced load
Bit 8 =1 /
Bit 7 =1 \
F3: Time-overcurrent, level 1
Bit 6 =1 /
Bit 5 =1 \
Interface fault Y1-Y5
Bit 4 =1 /
Note On double /fourfold bits the follow- Bit 3 =1 \
F1: Maintenance call
ing is valid: If the indicated bit combination Bit 2 =1 /
is fulfilled (high byte and low byte) ,the Bit 1 =1 \
Start failure
message is active (otherwise inactive). Bit 0 =1 /
18/2 56 Internal alarm 4 Bit 15 =1 \
F1: Analog input [T1], level 1
Bit 14 =1 /
Bit 13 =1 \
F3: Analog input [T1], level 2
Bit 12 =1 /
Bit 11 =1 \
F1: Analog input [T2], level 1
Bit 10 =1 /
Bit 9 =1 \
F3: Analog input [T2], level 2
Bit 8 =1 /
Bit 7 =1 \
F1: Analog input [T3], level 1
Bit 6 =1 /
Bit 5 =1 \
F3: Analog input [T3], level 2
Bit 4 =1 /
Note On double /fourfold bits the follow- Bit 3 =1 \
F1: Analog input [T4], level 1
ing is valid: If the indicated bit combination Bit 2 =1 /
is fulfilled (high byte and low byte) ,the Bit 1 =1 \
F3: Analog input [T4], level 2
message is active (otherwise inactive). Bit 0 =1 /
18/3 57 Internal alarm 5 Bit 15 =1 \
F1: Analog input [T5], level 1
Bit 14 =1 /
Bit 13 =1 \
F3: Analog input [T5], level 2
Bit 12 =1 /
Bit 11 =1 \
F1: Analog input [T6], level 1
Bit 10 =1 /
Bit 9 =1 \
F3: Analog input [T6], level 2
Bit 8 =1 /
Bit 7 =1 \
F1: Analog input [T7], level 1
Bit 6 =1 /
Bit 5 =1 \
F3: Analog input [T7], level 2
Bit 4 =1 /
Note On double /fourfold bits the follow- Bit 3 =1 \
--Internal--
ing is valid: If the indicated bit combination Bit 2 =1 /
is fulfilled (high byte and low byte) ,the Bit 1 =1 \
--Internal--
message is active (otherwise inactive). Bit 0 =1 /
No.
MUX
No.
22/2 68 Alarm messages IKD2 (SC06) Bit 15 = 1 Failure DI8 of the IKD2
Bit 14 = 1 Failure DI7 of the IKD2
Bit 13 = 1 Failure DI6 of the IKD2
Bit 12 = 1 Failure DI5 of the IKD2
Bit 11 = 1 Failure DI4 of the IKD2
Bit 10 = 1 Failure DI3 of the IKD2
Bit 9 = 1 Failure DI2 of the IKD2
Bit 8 = 1 Failure DI1 of the IKD2
Bit 7 = 1 --Internal--
Bit 6 = 1 --Internal--
Bit 5 = 1 --Internal--
Bit 4 = 1 --Internal--
Note On double /fourfold bits the follow- Bit 3 = 1 --Internal--
ing is valid: If the indicated bit combination Bit 2 = 1 --Internal--
is fulfilled (high byte and low byte) ,the Bit 1 = 1 --Internal--
message is active (otherwise inactive). Bit 0 = 1 --Internal--
22/3 69 LCD-display / Pickup Currently active display message
Bit 15 = x
Bit 14 = x
Bit 13 = x A number is transmitted, please consult
Bit 12 = x the table for the meaning of the num-
Bit 11 = x ber 69 of the telegram "Monitoring of the
Bit 10 = x active display".
Bit 9 = x
Bit 8 = x
Pickup
Bit 7 = 1
Bit 6 = 1 Firing speed reached
Bit 5 = 1 f > parameter
Bit 4 = 1
Bit 3 = 1 Speed existing
Bit 2 = 1 without pickup (pickup = OFF): f > 15
Bit 1 = 1 Hz
Bit 0 = 1 with pickup (pickup = ON): f > 5 Hz
Meaning of the number 69 of the telegram " Currently active display message":
Number Meaning
0 GCB synchronization
1 MCB synchronization
2 GCB dead bus start
3 MCB dead bus start
4 Crank
5 Start pause
6 Cool down 000s (000s: the remaining time is displayed)
7 Engine stop!
8 Preglow
9 Purging operation
10 Initial state
11 Auxiliary prerun
12 Auxiliary postrun
13 Mains settling 000s (000s: the remaining time is displayed)
14 Lambda initial state
15 Sprinkler coasting
16 Ignition
17 --Internal--
18 --Internal--
19 --Internal--
20 --Internal--
21 --Internal--
22 --Internal--
23 --Internal--
24 Phase rotation incorrect!
25 Start without closing GCB and simultaneous emergency power
26 Start without closing GCB
27 Sprinkler operation (critical mode) and simultaneous emergency power
28 Sprinkler operation (critical mode)
29 Emergency power
30 TEST
31 Load TEST
32 --Internal--
33 --Internal--
34 --Internal--
35 --Internal--
36 --Internal--
37 --Internal--
38 --Internal--
39 --Internal--
40 --Internal--
41 --Internal--
42 --Internal--
43 --Internal--
44 --Internal--
45 --Internal--
46 --Internal--
47 Power reduction
...
255 No message on the display (basic screen)
Receiving Telegram
The CAN protocol for remote control of the GCP is available upon request. Woodward however recommends the
use of a GW 4. The following three data words can be received by the GCP. Refer to the GW 4 manual on how
to control several GCP control units.
No.
1/1 1 Set point value for the generator real power kW with control argument; see below
1/2 2 Set point value for the generator power fac- Example: FF9EH cos = c 0.98 (capacitive)
tor cos FF9DH cos = c 0.99 (capacitive)
0064H cos = 1.00
0063H cos = i 0.99 (inductive)
0062H cos = i 0.98 (inductive)
1/3 3 Control word Bit 15 = 1 --Internal--
Bit 14 = 1 --Internal--
Bit 13 = 1 --Internal--
Bit 12 = 1 --Internal--
Bit 11 = 1 --Internal--
Bit 10 = 1 --Internal--
Bit 9 = 1 --Internal--
Bit 8 = 1 --Internal--
Bit 7 = 1 --Internal--
Bit 6 = 1 --Internal--
Bit 5 = 1 --Internal--
Bit 4 = 1 Remote acknowledgement
Bit 3 = 1 Always "0"
Bit 2 = 1 Always "0"
Bit 1 = 1 Remote stop (high priority)
Bit 0 = 1 Remote start
Transmission Telegram
The data of the following table can be handled by a Gateway GW 4 or a PLC and can be transferred to other
busses. A GCP is sending the data via circular CAN messages.
(The item number, Parameter 4, is adjustable and influences directly the CAN ID on which the item sends the vi-
sualization message).
A visualization message which is send out of a GCP has 8 Bytes and is built as follows:
In a visualization message the byte 0 is always used to show the hexadecimal value DD. This one defines the
message as a visualization message. As the complete transmission telegram of the GCP includes more than three
words byte 1 sends additionally a MUX number starting with 0. Therefore it is theoretically possible to send
(256 3 = 768) words via the CAN ID. The whole telegram is built up as follows:
n depends on the total length of the item special telegram and cannot be larger than HFF.
The current direction can be recognized via the code word prefix. A positive transmitted value indicates power
export (power output, supply) and a negative transmitted value indicates power import (power input, consump-
tion).
The following power values may be pre-specified: constant/baseload power (C power), outgoing/export power (E
power) and incoming/import power (I power). The real power set point value is transmitted in binary form using
bits 0-13. The control argument must be transmitted in the basis of bits 14 and 15. In this case, the following cod-
ing applies:
Example:
C power of 150 kW is to be compensated. The value transmitted is then:
01/00 0000 1001 0110 B 4096 H
I power of 600 kW is to be compensated. Negative power is transmitted. The value transmitted is then:
11/11 1101 1010 1000 B FDA8 H
The IDs given in the following are reserved for the data exchange between GCPs and LS4s. If third-party devices
are connected to the bus, it has to be ensured their IDs do not result conflicts with these IDs.
CAN-ID in
[hex] [decimal]
GCP sends
Distribution message to other GCPs 180 + GENNO 384 + GENNO
Control message to LS4 (the GCP with the lowest ID) 311 785
Visualization 320 + GENNO 800 + GENNO
GCP receives
Distribution message from other GCP 180 + GENNO 384 + GENNO
Control message from an LS4 300 + GENNO 768 + GENNO
Configuration messages from a higher control 33F 831
LS4 sends
Logic message to other LS4s 180 + LS4NO 384 + LS4NO
Control message to GCP (the LS4 with the lowest ID) 300 + GENNO 768 + GENNO
LS4 receives
Logic message from other LS4 180 + LS4NO 384 + LS4NO
Control message from a GCP 311 785
Configuration messages and
configuration messages from a higher control 33F 831
[hex] [decimal]
GENNO = 1 to E 1 to 14 GENNO = Generator number
LS4NO = 11 to 1E 17 to 30 LS4NO = LS4 number
Appendix D.
List of Parameters
Project ______________________________________________________________________
CONTROLLER CONFIGURATION
Pow.fact.contr. ON/OFF OFF on off on off
Pow.fact.contr. setpoint i0.70 to 1.00 to k0.70 1.00
Pow.fact.contr. dead band 0.5 to 25.0 % 0.5 %
Pow.fact.contr. gain Kp 0.1 to 99.9 20.0
Pow.fact.contr. gain Kpr 1 to 240 20
Pow.fact.contr. reset Tn 0.0 to 60.0 s 1.0 s
Pow.fact.contr. derivat.Tv 0.0 to 6.0 s 0.0 s
Power controller ON/OFF ON on off on off
power controller ramp 0 to 100 %/s 20 %/s
Power limit P max. 10 to 120 % 100 %
Power limit P min. 0 to 50 % 0%
Power setpoint external OFF/ T1 / T2 / T3 OFF OFF OFF
T1 T1
T2 T2
T3 T3
Analog input 0 to 20 mA 4 to 20 mA 0-20 mA 0-20 mA
4 to 20 mA 4-20 mA 4-20 mA
Ext.setpoint 0mA C/I/E 0 to 9,999 kW C 0 kW
Ext.setpoint 20mA C/I/E 0 to 9,999 kW C 200 kW
Power controller dead band 0.1 to 25.0 % 0.5 %
Power controller gain Kp 0.1 to 99.9 20.0
Powercontr. dead band ratio 1.0 to 9.9 2.0
Power controller gain Kpr 1 to 240 20
Power controller reset Tn 0.0 to 60.0 s 1.0 s
Power controller derivat.Tv 0.0 to 6.0 s 0.0 s
Warm up load derivat.Tv 5 to 110 % 15 %
Warm up load time 0 to 600 s 0s
Active power load-share ON/OFF ON on off on off
Act. load share factor 10 to 99 % 50 %
Reactive power load share ON/OFF OFF on off on off
React.load share factor 10 to 99% 50 %
LOAD MANAGEMENT CONFIGURATION
Configure automatic YES/NO NO Y N Y N
Loadd.start/stop at ter.3 ON/OFF OFF on off on off
Loadd.start/stop at ter.5 ON/OFF OFF on off on off
Minimum load generator 0 to 6,900 kW 15 kW
Add-on delay mains oper. 0 to 999 s 1s
Shed-off delay mains oper. 0 to 999 s 3s
Hysteresis add-. on/off op. 0 to 9,999 kW 5 kW
Reserve power mains op. 0 to 9,999 kW 10 kW
Priority of generators 0 to 14 0
Reserve power isol.op. 0 to 9,999 kW 20 kW
Add-on delay isol.op. 0 to 999 s 1s
Shed-off delay isol.op. 0 to 999 s 4s
Mains error - stop eng. ON/OFF OFF on off on off
L Control via COM X1X5 ON/OFF OFF on off on off
L Supervision COM X1X5 ON/OFF OFF on off on off
L Ackn. F2,F3 via COM interf ON/OFF OFF on off on off
RPQ L Power On Mode STOP / MANUAL / AUTO- STOP S M S M
MATIC / as before A b A b
RPQ L Interchange Mode in Manual YES/NO NO Y N Y N
BREAKER CONFIGURATION
Configure breaker YES/NO NO Y N Y N
Breaker logic: EXTERNAL [EXT] PARALLEL EXT EXT
PARALLEL [PAR] PAR PAR
OPEN TRANSIT [OPEN] OPEN OPEN
CLOSED TRANSIT [CLOSE] CLOSE CLOSE
INTERCHANGE [CHANG] CHANG CHANG
Add-on/off ramp max.time 0 to 999 s 20 s
Open GCB with F2 max.time 0 to 999 s 10 s
GCB close.relay Impulse [I] Constant I I
Constant [C] C D
GCB open relay NO-contact [NO] NO-contact NO NO
NC-contact [NC] NC NC
synchSynchronize df max 0.02 to 0.49 Hz 0.20 Hz
Synchronize
.. df min 0.0 to 0,49 Hz -0.10 Hz
Synchronize
.. dV max 1.0 to 20.0 % 2.0 %
Synchronize
.. time pulse> 0.02 to 0.26 s 0.24 s
Closing time
.. GCB 40 to 300 ms 80 ms
synchClosing time MCB 40 to 300 ms 80 ms
RPQ Phase matching ON/OFF ON on off on off
Phase matching
.. gain 1 to 36 2
Phase matching
.. df start 0.02 to 0.25 Hz 0,20 Hz
Detection Mains
.. connected < 1 to 15 5
RPQ Detection Mains conn. after 0 to 999 s 10 s
synchAutomat.breaker deblocking ON/OFF OFF on off on off
Sync.time contr.
.. ON/OFF ON on off on off
Sync.time contr.
.. delay 10 to 999 s 180 s
LGCB dead bus op. ON/OFF ON on off on off
GCB dead bus op.
.. df max 0.05 to 5.00 Hz 2.0 Hz
GCB dead bus op.
.. dV max. 1.0 to 15.0 % 10.0 %
GCB dead bus op
.. max.time 0 to 999 s 30 s
synchMCB dead bus op. ON/OFF ON on off on off
Switching-on GCB
induct. ON/OFF ON on off on off
Switching-on GCB
.. df max 0.05 to 9.99 Hz 0.20 Hz
Switching-on GCB
.. df min 0.0 to -9.99 Hz -0.10 Hz
Switching-on GCB
.. T.impuls > 0.02 to 0.26 s 0.24 s
Automat.breaker
.. deblocking ON/OFF ON on off on off
Switch.time cntr
.. ON/OFF ON on off on off
Switch.time cntr
induct. delay 2 to 999 s 180 s
Supervision GCB ON/OFF ON on off on off
Supervision MCB ON/OFF ON on off on off
GCP31 Mains decoupling via GCB [GCB] GCB GCB GCB
GCB->EXT [GCB>EX] GCB>EX GCB>EX
EXT [EXT] EXT EXT
EX>GCB EX>GCB
EXT->GCB [EX>GCB]
GCP32 Mains decoupling via GCB [GCB] GCB GCB GCB
GCB->MCB [GCB>MC] GCB>MC GCB>MC
MCB [MCB] MCB MCB
MC>GCB MC>GCB
MCB->GCB [MC>GCB]
L Mains decoupling -> after 0.10 to 5.00 s 0.14 s
Switch MCB in STOP mode YES/NO NO Y N Y N
EMERGENCY POWER CONFIGURATION
Configure emergency YES/NO NO Y N Y N
Emergency power ON/OFF ON on off on off
Emergency power start del. 0.5 to 99.9 s 3.0 s
MONITORING CONFIGURATION
Configure monitoring YES/NO NO Y N Y N
Gen.power monit. ON/OFF OFF on off on off
Gen.power monit. resp.val1 0 to 9,999 kW 100 kW
Gen.power monit. hyst.lv1 0 to 999 kW 10 kW
Gen.power monit. delay lv1 0 to 650 s 1s
Gen.power monit. resp.val2 0 to 9,999 kW 120 kW
Gen.power monit. hyst.lv2 0 to 999 kW 10 kW
Gen.power monit. delay lv2 0 to 650 s 1s
Mains power mon. ON/OFF OFF on off on off
Mains power mon. res.val. I/E 0 to 9,999 kW E100 kW
Mains power mon. hysteresis 0 to 999 kW 10 kW
Mains power mon. delay 0 to 650 s 1s
Overload monit. ON/OFF OFF on off on off
Gen.overload MOP resp.value 80 to 150 % 120 %
Gen.overload MOP delay 0 to 99 s 1s
Gen.overload IOP resp.value 80 to 150 % 105 %
Gen.overload IOP delay 0 to 99 s 1s
Rev./red.power monitoring ON/OFF OFF on off on off
Rev./red.power resp.value -99 to +99 % -10 %
Rev./red.power delay 0,0 to 9,9 s 1.0 s
Load unbalanced ON/OFF OFF on off on off
Load unbalanced max. 0 to 100 % 30 %
Load unbalanced delay 0.02 to 9.98 s 1.00 s
Gen.overcurrent monitoring ON/OFF OFF on off on off
Gen.overcurrent limit 1 0 to 300 % 110 %
Gen.overcurrent delay 1 0.02 to 9.98 s 1.00 s
Gen.overcurrent limit 2 0 to 300 % 120 %
Gen.overcurrent delay 2 0.02 to 9.98 s 0.04 s
Gen.overcurrent Cool down ON/OFF OFF on off on off
Gen.frequency- monitoring ON/OFF ON on off on off
Gen.overfreq. f > 50.0 to 140.0 % 110.0 %
Gen.overfreq. delay 0.02 to 9.98 s 0.30 s
Gen.underfreq. f < 50.0 to 140.0 % 90.0 %
Gen.underfreq. delay 0.02 to 9.98 s 0.30 s
Engine overspeed > 0 to 9,999 rpm 1,900 rpm
Gen.voltage monitoring ON/OFF ON on off on off
Gen.overvoltage U > 20.0 to 150.0 % 110.0 %
Gen.overvoltage delay 0.02 to 9.98 s 0.30 s
Gen.undervoltage U < 20.0 to 150.0 % 90.0 %
Gen.undervoltage delay 0.2 to 9.98 s 0.30 s
Mains frequency monitoring ON/OFF ON on off on off
Mains overfreq. f > 80.0 to 140.0 % 110.0 %
Mains overfreq. delay 0.02 to 9.98 s 0.06 s
Mains underfreq. f < 80.0 to 140.0 % 90.0 %
Mains underfreq. delay 0.02 to 9.98 s 0.06 s
Mains voltage monitoring ON/OFF ON on off on off
Mains overvolt. U > 20.0 to 150.0 % 110.0 %
Mains overvolt. delay 0.02 to 9.98 s 0.06 s
Mains undervolt. U < 20.0 to 150.0 % 90.0 %
Mains undervolt. delay 0.02 to 9.98 s 0.06 s
Phase shift monitoring ON/OFF ON on off on off
Monitoring one-phase [1] three-phase 1 3 1 3
three-phase [3]
Phase shift one-phase 3 to 30 12
Phase shift three-phase 3 to 30 8
Mains settling time 0- to 999 s 10 s
Batt.undervolt. U < 9.5 to 30.0 V 10.0 V
Batt.undervolt. delay 0 to 99 s 10 s
Horn self reset 1 to 9,999 s 180 s
ENGINE CONFIGURATION
Configure engine YES/NO NO Y N Y N
L Aux.services prerun 0 to 999 s 0s
L Aux.services postrun 0 to 999 s 0s
L Start-stop-logic for DIESEL DIESEL DIESEL DIESEL
GAS GAS GAS
EXTERNAL [EXT] EXT EXT
L Min.speed for ignit. 0 to 999 rpm 100 rpm
Gas Ignition delay 0 to 99 s 3s
.. L Gasvalve delay 0 to 99 s 5s
.. Max. attempts to start 1 to 6 3
.. Starter time 2 to 99 s 10 s
.. Start pause time 1 to 99 s 8s
.. L f lower before start ON/OFF OFF on off on off
Gas L time f lower bef.start 0 to 999 s 5s
Diesel Preglow time 0 to 99 s 3s
.. Max. attempts to Start 1 to 6 3
.. Starter time 2 to 99 s 10 s
.. Start pause time 1 to 99 s 5s
L.. f lower before start ON/OFF OFF on off on off
L.. time f lower bef.start 0 to 999 s 5s
Diesel L Fuel relay logic Open to stop [OPEN] Open to stop OPEN OPEN
Close to stop [STOP] STOP STOP
Cool down time 0 to 999 s 15 s
Delayed engine monitoring 1 to 99 s 8s
Firing speed reached f> 5 to 70 Hz 15 Hz
Pickup input ON/OFF ON on off on off
Number of pickup teeth 30 to 280 160
L Gen.rated speed 0 to 3,000 rpm 1,500 rpm
COUNTER CONFIGURATION
Configure counters YES/NO NO Y N Y N
Service interval in 0 to 9,999 h 300 h
Set oper.hours counter 0 to 65,000 h 0h
Set start counter 0 to 32,000 0
kWh counter set in kWh kWh kWh kWh
MWh MWH MWH
kWh counter set 0 to 65,500 kWh/MWh 0 kWh
Time 00:00 to 23:59 00:00
Year,month 00 to 99,01 to 12 00,00
Day/weekday 01 to 31/1 to 7 00,0
RPQ Timer on at 00:00 00:00 to 23:59 00:00
RPQ Timer off at 00:00 00:00 to 23:59 00:00
RPQ Week M S days NNNNNNN Y(es)/N(o) NNNNNNN
RPQ This parameter is only available in the RPQ Package and may only be accessed via LeoPC1 depending on the unit
B+X This parameter is only available in the B+X Packages and may only be accessed via LeoPC1 depending on the unit
L This parameter may only be accessed via LeoPC1 depending on the unit
Appendix E.
Service Options
CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the pre-
cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules.
Packing A Control
When returning equipment to Woodward, please telephone and ask for the Customer Service Department in
Stuttgart, Germany [+49 (0) 711 789 54-0]. They will help expedite the processing of your order through our dis-
tributors or local service facility. To expedite the repair process, contact Woodward in advance to obtain a Re-
turn Authorization Number, and arrange for issue of a purchase order for the unit(s) to be repaired. No work will
be started until a purchase order is received.
NOTE
We highly recommend that you make arrangement in advance for return shipments. Contact a
Woodward customer service representative at +49 (0) 711 789 54-0 for instructions and for a Re-
turn Authorization Number.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part numbers P/N (XXXX-XXX) that is on the enclosure nameplate;
the unit serial number S/N, which is also on the nameplate.
Phone: +49 (0) 711 789 54-0 (8.00 - 16.30 German time)
Fax: +49 (0) 711 789 54-100
eMail: sales-stuttgart@woodward.com
For assistance outside Germany, call one of the following international Woodward facilities to obtain the address
and phone number of the facility nearest your location where you will be able to get information and service.
You can also contact the Woodward Customer Service Department or consult our worldwide directory on
Woodwards website (www.woodward.com) for the name of your nearest Woodward distributor or service fa-
cility. [For worldwide directory information, go to www.woodward.com/ic/locations.]
Engineering Services
Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward
products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website.
Technical support
Product training
Field service during commissioning
Technical Support is available through our many worldwide locations, through our authorized distributors, or
through GE Global Controls Services, depending on the product. This service can assist you with technical ques-
tions or problem solving during normal business hours. Emergency assistance is also available during non-
business hours by phoning our toll-free number and stating the urgency of your problem. For technical engineer-
ing support, please contact us via our toll-free or local phone numbers, e-mail us, or use our website and refer-
ence technical support.
Product Training is available on-site from several of our worldwide facilities, at your location, or from GE
Global Controls Services, depending on the product. This training, conducted by experienced personnel, will as-
sure that you will be able to maintain system reliability and availability. For information concerning training,
please contact us via our toll-free or local phone numbers, e-mail us, or use our website and reference customer
training.
Field Service engineering on-site support is available, depending on the product and location, from our facility
in Colorado, or from one of many worldwide Woodward offices or authorized distributors. Field engineers are
experienced on both Woodward products as well as on much of the non-Woodward equipment with which our
products interface. For field service engineering assistance, please contact us via our toll-free or local phone
numbers, e-mail us, or use our website and reference field service.
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information. Please write
it down here before phoning:
Contact
Your company ___________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
Please be sure you have a list of all parameters available. You can print this using LeoPC1. Additionally you can
save the complete set of parameters (standard values) and send them to our Service department via e-mail.
Homepage
http://www.woodward.com/smart-power
08/5/S