Volvo Penta 200 KW TAD753GE EPA Tier 3 Emissions Engine Spec Sheet
Volvo Penta 200 KW TAD753GE EPA Tier 3 Emissions Engine Spec Sheet
Volvo Penta 200 KW TAD753GE EPA Tier 3 Emissions Engine Spec Sheet
TAD753GE
21813919 05
General
In-line four stroke diesel engine with direct injection. Rotation direction, anti-clockwise viewed towards flywheel.
Turbocharged
Number of cylinders 6
Displacement, total litre 7,15
in3 436,0
Firing order 1-5-3-6-2-4
Bore mm 108
in 4,25
Stroke mm 130
in 5,12
Compression ratio 18
Wet weight Engine only kg 780
lb 1720
Engine incl. cooling system and air kg 955
filtration system lb 2105
Engine incl. cooling system, air filtration kg
system, and frame lb
1 / 13
Document No Issue Index
TAD753GE
21813919 05
2 / 13
Document No Issue Index
TAD753GE
21813919 05
3 / 13
Document No Issue Index
TAD753GE
21813919 05
Fuel system rpm 1500 1800
Fuel to conform to
DIN EN590
System supply flow at: litre/h 164,0 197,0
US gal/h 43,3 52,0
Fuel supply line max restriction kPa 35,0 35,0
(Measured at fuel inlet connection) psi 5,1 5,1
Fuel supply line max pressure, engine stopped kPa 35,0 35,0
psi 5,1 5,1
System return flow litre/h 102,6 132,0
US gal/h 27,1 34,9
Fuel return line max restriction kPa 50,0 50,0
(Measured at fuel return connection) psi 7,3 7,3
Maximum allowable inlet fuel temp C 70 70
(Measured at fuel inlet connection) F 158 158
Prefilter / Water separator micron size 10
Fuel filter micron size 5
Governor type/make, standard EMS 2.2
Injection pump type/make BOSCH PF45
4 / 13
Document No Issue Index
TAD753GE
21813919 05
Cooling system rpm 1500 1800
Heat rejection radiation from engine at: Prime Power kW 18 21
BTU/min 1024 1194
Standby Power kW 21 25
BTU/min 1177 1405
Heat rejection to coolant at: Prime Power kW 114 123
BTU/min 6483 6995
Standby Power kW 119 131
BTU/min 6767 7450
Coolant Volvo Penta coolant "ready mix" or Volvo Penta
coolant mixed with clean fresh water 40 / 60
Radiator cooling system type Closed circuit
Standard radiator core area m 0,65
foot 7,00
Fan diameter mm 870
in 34,25
Fan power consumption kW 8,8 15,2
hp 12 21
Fan drive ratio 1,0:1
Coolant capacity, engine litre 10
US gal 2,64
engine with std radiator and litre 34
hoses US gal 8,98
Coolant pump drive/ratio 2,56:1
Coolant flow with standard system l/s 4,08 4,92
US gal/s 1,08 1,30
Minimum coolant flow l/s 3,3 3,9
US gal/s 0,86 1,04
Maximum outer circuit restriction, including piping kPa 35 35
psi 5,1 5,1
Thermostat start to open C 86
F 187
fully open C 98
F 208
Maximum static pressure head kPa 110
(expansion tank height + pressure cap setting) psi 16,0
Minimum static pressure head kPa 90
(expansion tank height + pressure cap setting) psi 13,1
Standard pressure cap setting kPa 100
psi 14,5
Maximum top tank temperature C 108
F 226
Draw down capacity. The difference between min coolant level in the litre
expansion tank and the lowest level where the engine's coolant system still US gal
are functioning
5 / 13
Document No Issue Index
TAD753GE
21813919 05
Charge air cooler system rpm 1500 1800
Heat rejection to charge air cooler Prime Power kW 30,5 39,7
BTU/min 1735 2258
Standby Power kW 32 43
BTU/min 1820 2445
Charge air mass flow Prime Power kg/s 0,21 0,24
Standby Power kg/s 0,23 0,28
Charge air inlet temp. Prime Power C 170 179
(Charge air temp after turbo compressor) F 338 354
Standby Power C 173 181
F 343 358
Charge air outlet temp. Prime Power C 40 40
(Charge air temp after intercooler) F 104 104
Standby Power C 40 40
F 104 104
Maximum pressure drop over charge air cooler incl. piping kPa 15
psi 2,18
Charge air pressure kPa 200
(After charge air cooler) psi 29,01
Standard charge air cooler core area m 0,41
foot 4,41
Cooling performance
Cooling air flow and external restriction at different radiator air temperatures based on 108C TTT and 40% coolant. Valid at
1 atm. (radiator and cooling fan, see optional equipment)
Engine speed Air on PRIME POWER STANDBY POWER
rpm temp Air flow External restriction Air flow External restriction
C 3
m /s Pa 3
m /s Pa
1500 55 3,3 450 3,6 360
60 3,6 340 4,1 210
65 4,2 170 4,8 30
66 4,9 0
69 4,9 0
1800 55
60 4,1 630 4,7 450
65 4,7 450 5,5 200
68 6,1 0
72 6,1 0
6 / 13
Document No Issue Index
TAD753GE
21813919 05
Engine management system
Functionality Alternatives Default setting
Governor mode Isochronous/droop switchable Isochronous
7 / 13
Document No Issue Index
TAD753GE
21813919 05
Electrical system
Voltage and type 24V
Alternator: make/output A Mitsubishi/100
tacho output Hz/alt. Rev
drive ratio
Starter motor make Mitsubishi
type M008T62471
kW 5,0
Number of teeth on: flywheel 129
starter motor 10
Max wiring resistance main circuit m
Cranking current at +20C A 400
Crank engine speed at 20C rpm 200
Starter motor battery capacity: max Ah/A 135
min at +5C Ah/A
Inlet manifold heater (at 20 V) kW
Power relay for the manifold heater A 2
8 / 13
Document No Issue Index
TAD753GE
21813919 05
0,3
0,25
0,2
0,15
0,1
0,05
0
0 50 100 150 200 250
kW
Prime Power 1500 rpm Prime Power 1800 rpm
0,6
0,5
0,4
0,3
0,2
0,1
0
0 50 100 150 200 250
kW
Prime Power 1500 rpm Prime Power 1800 rpm
9 / 13
Document No Issue Index
TAD753GE
21813919 05
60
50
40
30
20
10
0
0 50 100 150 200 250
kW
Prime Power 1500 rpm Prime Power 1800 rpm
Derating
120%
100%
80%
60%
40%
20%
0%
500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
Altitude
10 / 13
Document No Issue Index
21813919 05
100
90
80
70
60
50
40
20 31,5 50 80 125 200 315 500 800 1,25 2k 3,15 5k 8 12,5 20k
Frequency Hz
120,0
110,0
100,0
90,0
80,0
70,0
60,0
50,0
40,0
20 31,5 50 80 125 200 315 500 800 1,25 2k 3,15 5k 8 12,5 20k
Frequency Hz
11 / 13
Document No Issue Index
21813919 05
Outer circuit
Outer circuit restriction versus coolant flow
restriction bar
4,50
4,00
3,50
3,00
2,50
2,00
1,50
1,00
0,50
0,00
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
12 / 13
Document No Issue Index
21813919 05
kW Standard fan
25
20
15
10
0
0 2 4 6 8 10 12 14
0,8
0,6
0,4
0,2
0
0 2 4 6 8 10 12 14
13 / 13