Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Muz A18 26yv (OB346E)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

OB346E --1qxp 07.2.

8 6:53 PM Page 1

Revision E:
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Check of outdoor thermistors has been corrected.

Please void OB346 REVISED EDITION-D.

No. OB346
HFC REVISED EDITION-E
utilized

SERVICE MANUAL R410A

Wireless type
Models

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

CONTENTS
1. TECHNICAL CHANGES 3
2. PART NAMES AND FUNCTIONS6
Indication of
3. SPECIFICATION7
model name 4. NOISE CRITERIA CURVES 10
MUZ-A18YV - E1 5. OUTLINES AND DIMENSIONS11
MUZ-A24YV - E1 6. WIRING DIAGRAM 12
MUZ-A26YV - E1
7. REFRIGERANT SYSTEM DIAGRAM 14
8. PERFORMANCE CURVES 16
9. ACTUATOR CONTROL31
10. TROUBLESHOOTING32
11. DISASSEMBLY INSTRUCTIONS46
12. PARTS LIST50

NOTE:
This service manual describes technical data of the outdoor units.
As for indoor units MSZ-A18YV - E1 , MSZ-A24YV - E1 and MSZ-A26YV - E1 , refer to the
service manual OB345.
As for indoor units MCFZ-A18WV - E1 and MCFZ-A24WV - E1 , refer to the service manual
OB344.
OB346E --1qxp 07.2.8 6:53 PM Page 2

Revision A:

MUZ-A18YV - E1 can be connected to MCFZ-A18WV - E1 .


MUZ-A24YV - E1 can be connected to MCFZ-A24WV - E1 .

Revision B:
Part number of 4-WAY VALVE has been corrected.

Part Number
Model Revise point Part Name
Incorrect Correct

MUZ-A18YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961

MUZ-A24YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961

MUZ-A26YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961

Revision C:

Check of HPS has been corrected.

Revision D:
Compressor has been changed. (MUZ-A18/24YV)

Model PARTS LIST number


Previous SNB130FLDH E02 851 900
New SNB130FLDH1 E02 939 900

Revision E:
Check of outdoor thermistors of 10. TROUBLESHOOTING has been corrected.

2
OB346E --1qxp 07.2.8 6:53 PM Page 3

1 TECHNICAL CHANGES

INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT


This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air
conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.

New refrigerant Previous refrigerant


Refrigerant R410A R22
Composition (Ratio) HFC-32: HFC-125 (50%:50%) R22 (100%)
Refrigerant handling Pseudo-azeotropic refrigerant Single refrigerant
Chlorine Not included Included
Safety group (ASHRAE) A1/A1 A1
Molecular weight 72.6 86.5
Refrigerant

Boiling point (:) -51.4 -40.8


Steam pressure [25:](Mpa) 1.557 0.94
Saturated steam density [25:](Kg/K) 64 44.4
Combustibility Non combustible Non combustible
ODP w1 0 0.055
GWP w2 1730 1700
Refrigerant charge method From liquid phase in cylinder Gas phase
Additional charge on leakage Possible Possible
Refrigeration

Kind Incompatible oil Compatible oil


oil

Color Non Light yellow


Smell Non Non
w1 :Ozone Destruction Parameter : based on CFC-11
w2 :Global Warmth Parameter : based on CO2

New Specification Current Specification


The incompatible refrigerating oil easily separates from Since refrigerant and refrigerating oil are compatible each,
refrigerant and is in the upper layer inside the suction muffler. refrigerating oil backs to the compressor through the lower
Raising position of the oil back hole enables to back the position oil back hole.
refrigerating oil of the upper layer to flow back to the
compressor. Suction muffler
Compressor

Suction muffler

Compressor Oil back hole Compressor


Refrigerating oil Oil back hole

Refrigerant Refrigerating oil /Refrigerant

NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f

3
OB346E --1qxp 07.2.8 6:53 PM Page 4

Conversion chart of refrigerant temperature and pressure


(MPa [Gauge])
4.0

3.5
R410A
Saturated liquid pressure

3.0 R22

2.5

2.0

1.5 NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
1.0
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
0.5

0.0

-0.5
-30 -20 -10 0 10 20 30 40 50 60 (:)

1.Tools dedicated for the air conditioner with R410A refrigerant


The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being
charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.

R410A tools Can R22 tools be used? Description


R410A has high pressures beyond the measurement range of existing
Gauge manifold No gauges. Port diameters have been changed to prevent any other refrigerant
from being charged into the unit.
Hose material and cap size have been changed to improve the pressure
Charge hose No
resistance.
Gas leak detector No Dedicated for HFC refrigerant.
Yes 6.35 mm and 9.52 mm
Torque wrench
No 12.7 mm and 15.88mm
Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Flare gauge New Provided for flaring work (to be used with R22 flare tool).
Vacuum pump Provided to prevent the back flow of oil. This adapter enables you to use
New
adapter vacuum pumps.
Electronic scale for It is difficult to measure R410A with a charging cylinder because the
New
refrigerant charging refrigerant bubbles due to high pressure and high-speed vaporization
No : Not Substitutable for R410A Yes : Substitutable for R410A

2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.

Outside diameter Wall


Pipe Insulation material
mm thickness
6.35 0.8 mm
For liquid
9.52 0.8 mm Heat resisting foam plastic
12.7 0.8 mm Specific gravity 0.045 Thickness 8 mm
For gas
15.88 1.0 mm

Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88).
Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is
insufficient.

4
OB346E --1qxp 07.2.8 6:53 PM Page 5

2 Flaring work and flare nut


Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual FLARING WORK.

Pipe diameter Dimension of flare nut

mm R410A R22
6.35 17 17
9.52 22 22
12.7 26 24
15.88 29 27

3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.

4.Air purge
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
Use the vacuum pump for air purging for the purpose of environmental protection.

5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, capacity of the refrigerating cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.

Union
Stop valve
Indoor unit
Liquid pipe
Gas pipe Outdoor unit
Refrigerant gas
cylinder
operating valve Service port

Gauge manifold
valve (for R410A)
Charge hose (for R410A)

Refrigerant gas cylinder


for R410A with siphon

Refrigerant (liquid)
Electronic scale for refrigerant charging

5
OB346E --1qxp 07.2.8 6:53 PM Page 6

2 PART NAMES AND FUNCTIONS

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
OUTDOOR UNIT

Air inlet
(back and side)

Piping

Drain hose

Air outlet

Drain outlet

ACCESSORIES

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1

1 Drain socket 1
2 Drain cap [33 2

6
OB346E --1qxp 07.2.8 6:53 PM Page 7

3 SPECIFICATION

MUZ-A18YV - E1 MUZ-A18YV - E1
Outdoor model Indoor model Indoor model
MSZ-A18YV - E1 MCFZ-A18WV - E1
Function Cooling Heating Cooling Heating
Single phase Single phase
Power supply
230V,50Hz 230V,50Hz
Capacity

Capacity Rated frequency(Min.~Max.) kW 5.0(0.9~5.9) 5.9(0.9~7.8) 4.8(10.9~5.5) 6.0(0.9~7.5)


Dehumidification r/h 2.5 2.4
Air flow(High/LowW) K /h 2,940/1,650W 2,940/2,210W 2,940/1,650W 2,940/2,210W
Power outlet A 20 20
Running current A 6.62 7.38 7.76 8.87
Electrical

Power input W 1,500 1,670 1,750 2,000


Power factor % 98.5 98.4 98
data

Starting current 1 A 7.38 8.87


Compressor motor current 1 A 6.32 7.08 7.46 8.57
Fan motor current A 0.30 0.30
Coefficient of performance(C.O.P) 1 3.21 3.41 2.62 2.88
Compressor

Model SNB130FLDH or SNB130FLDH1 SNB130FLDH or SNB130FLDH1


Output W 850 850
Winding U-V 0.45 W-U 0.45 U-V 0.45 W-U 0.45
"
resistance(at 20:) V-W 0.45 V-W 0.45
Model PM8H60-UB PM8H60-UB
motor

Winding BLK-WHT 15.2 BLK-WHT 15.2


Fan

"
resistance(at 20:) WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2
Dimensions WOHOD mm 840o850o330 840o850o330
Weight kg 53 53
Sound level(High/LowW) dB 53/51W 55/53W 53/51W 55/53W
Fan speed(High/LowW) rpm 800/480W 800/620W 800/480W 800/620W
Fan speed regulator 2 2
Refrigerant filling
remarks

kg 1.8 1.8
Special

capacity(R410A)
Refrigeration oil(Model) NEO22 NEO22
Thermistor RT61(at 100:) k" 13.4 13.4
Thermistor RT62(at 25:) k" 10.0 10.0
Thermistor RT65(at 50:) k" 17.0 17.0
Thermistor RT68(at 25:) k" 10.0 10.0
NOTE : Test conditions are based on ISO 5151.
Cooling : Indoor DB 27: WB 19:
Outdoor DB 35: WB (24:)
Heating : Indoor DB 20: WB 15:
Outdoor DB 7: WB 6:
Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
w Reference value

7
OB346E --1qxp 07.2.8 6:53 PM Page 8

MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1


Outdoor model Indoor model Indoor model Indoor model
MSZ-A24YV - E1 MCFZ-A24WV - E1 MSZ-A26YV - E1

Function Cooling Heating Cooling Heating Cooling Heating


Single phase Single phase Single phase
Power supply
230V,50Hz 230V,50Hz 230V,50Hz
Capacity

Capacity Rated frequency(Min.~Max.) kW 6.0(0.9~6.7) 6.8(0.9~8.1) 5.5(0.9~6.1) 6.4(0.9~7.9) 7.1(0.9~8.3) 8.1(0.9~9.6)


Dehumidification r/h 3.0 3.1 3.8
Air flow(High/LowW) K /h 2,940/1,650W 2,940/2,210W 2,940/1,650W 2,940/2,210W 2,940/1,650W 2,940/2,210W
Power outlet A 20 20 20
Running current A 8.49 8.75 10.38 10.47 10.75 11.42
Electrical

Power input W 1,921 1,981 2,340 2,360 2,431 2,581


Power factor % 98.4 98 98.3
data

Starting current 1 A 8.75 10.47 11.42


Compressor motor current 1 A 8.19 8.45 10.08 10.17 10.45 11.12
Fan motor current A 0.30 0.30 0.30
Coefficient of performance(C.O.P) 1 3.02 3.32 2.27 2.62 2.84 3.06
Compressor

Model SNB130FLDH or SNB130FLDH1 SNB130FLDH or SNB130FLDH1 TNB220FMCH


Output W 850 850 1,300
Winding U-V 0.45 W-U 0.45 U-V 0.45 W-U 0.45 U-V 1.41 W-U 1.41
"
resistance(at 20:) V-W 0.45 V-W 0.45 V-W 1.41
Model PM8H60-UB PM8H60-UB PM8H60-UB
motor

Winding BLK-WHT 15.2 BLK-WHT 15.2 BLK-WHT 15.2


Fan

"
resistance(at 20:) WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2
Dimensions WOHOD mm 840o850o330 840o850o330 840o850o330
Weight kg 53 53 58
Sound level(High/LowW) dB 53/51 W 55/53W 53/51 W 55/53 W 53/51 W 55/53W
Fan speed(High/LowW) rpm 800/480 W 800/620W 800/480 W 800/620 W 800/480 W 800/620W
Fan speed regulator 2 2 2
Refrigerant filling
remarks

kg 1.8 1.8 2.0


Special

capacity(R410A)
Refrigeration oil(Model) NEO22 NEO22 NEO22
Thermistor RT61(at 100:) k" 13.4 13.4 13.4
Thermistor RT62(at 25:) k" 10.0 10.0 10.0
Thermistor RT65(at 50:) k" 17.0 17.0 17.0
Thermistor RT68(at 25:) k" 10.0 10.0 10.0
NOTE : Test conditions are based on ISO 5151.
Cooling : Indoor DB 27: WB 19:
Outdoor DB 35: WB (24:)
Heating : Indoor DB 20: WB 15:
Outdoor DB 7: WB 6:
Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
w Reference value

8
OB346E --1qxp 07.2.8 6:53 PM Page 9

Specifications and rating conditions of main electric parts

OUTDOOR UNIT
Model
Item MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1

Smoothing capacitor (CB1,2,3) 560+ 450V


Current transformer (CT1,2) ETQ19Z68AY
Current transformer (CT61) ETQ19Z53AY
Fuse (F801, F912) 250V 3.15A
Fuse (F911) 250V 1A
Fet array (HC932) SLA5075
High pressure switch (HPS) ACB-DB156
Power transistor module (IPM) PS21244-A
Reactor (L) 340H 20A
Expansion valve (LEV) CAM-30YGME 12VDC CAM-40YGME 12VDC
Power factor controller (PFC) PS51259-A
Resistor (R64) 10" 20W
Resistor (R934A,B) 1.1" 2W 2%
Resistor (RS1~4) 0.04" 7W
Solenoid coil relay (SSR61) TLP3506
Terminal block (TB1) 3P
Terminal block (TB2) 2P
Relay (X64) G4A
R.V. coil (21S4) LD30013

9
OB346E --1qxp 07.2.8 6:53 PM Page 10

4 NOISE CRITERIA CURVES

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
SPEED FUNCTION SPL(dB(A)) LINE
COOLING 53
High
HEATING 55

Test conditions,
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

80

70
NC-70 OUTDOOR UNIT

60
1m
NC-60
MICROPHONE
50
NC-50

40
NC-40

30
NC-30

APPROXIMATE
20
THRESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

10
OB346E --1qxp 07.2.8 6:53 PM Page 11

5 OUTLINES AND DIMENSIONS

MUZ-A18YV - E1 Unit: mm
MUZ-A24YV - E1
MUZ-A26YV - E1
OUTDOOR UNIT
REQUIRED SPACE
Open as a rule
500mm or more if
515 the front and both
299 sides are open
66 40
100mm or more
51
34

200mm or more if
100mm or more there are obstacles
to both sides
330

360

500
840 80 Open as a rule
121 500mm or more if the back, 350mm or more
both sides and top are open

Service panel
Liquid refrigerant
pipe joint
850

Refrigerant pipe
(flared) [6.35 (MUZ-A18/A24YV)
[9.52 (MUZ-A26YV)
430

30-
35-
155
90

Gas refrigerant
pipe joint
Refrigerant pipe
198 (flared) [12.7 (MUZ-A18YV)
[15.88 (MUZ-A24/A26YV)

11
6
TAB1 L

PFC
CT2 W
POWER SUPPLY 2 1 R RED
OB346E --1qxp

~/N 230V 50Hz X64 4


CIRCUIT
RED RED S

F912
BREAKER R64

BRN
NF TAB4

CB1
CB2
CB3
TB1 3 4 YLW W
YLW V
L NR63 BLK V
MUZ-A24YV - E1
MUZ-A18YV - E1
BLU IPM MC
BLK OUTDOOR UNIT

2 1
N

CN5
PE TAB2 CT61 U
07.2.8 6:53 PM

WHT
BLK RS1 RS3 CT1 U

2 1 2 1

F911
BLK

SSR61
CN902 CN903

GRN/YLW
CN912 CN901 RS2 RS4
Page 12

CN2

LDE1
LDE2
1 3 1 2 3 5
1 2
CN3
CN4
RT65

7 6 5 4 3 2 1
NOISE FILTER 1 2 LD2 LD1 LD9 POWER

BLU
BLU
BOARD
WIRING DIAGRAM

P.C. BOARD

GRN
GRN
21S4

BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
GRN

WHT

RED
ELECTRONIC GRY
1 2 3 5 1 5 6 7 1 2 1 3

12
CONTROL PNK
P.C. BOARD CN781 CN702 CN701
CN801

TB2 RED ORN

1
TO INDOOR 3 BLU
CN931

UNIT CN661
CONNECTING

F801
BLU YLW MF

3
1 2 3 4 5

CN601
12V 1 2 3 4 7 8 CN795
N T801 RED
R934A
MODELS WIRING DIAGRAM

6 WHT
BLK
HC932
1 2 3

LEV
RT62 RT61 RT68 R934B CN932

SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT65 FIN TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR (INNER FUSE) diagram for servicing.
RT68 OUTDOOR HEAT EXCHANGER
CT61 CURRENT TRANSFORMER NF NOISE FILTER TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F801 FUSE (250V 3.15A) NR63 VARISTOR SSR61 SOLENOID COIL RELAY 3.Symbols below indicate.
F911 FUSE (250V 1A) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER :Terminal block :Connector
F912 FUSE (250V 3.15A) R64 RESISTOR TB1 TERMINAL BLOCK
HC932 FET ARRAY R934A, B RESISTOR TB2 TERMINAL BLOCK
IPM POWER TRANSISTOR MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT61 DISCHARGE TEMPERATURE THERMISTOR 21S4 R.V. COIL
LEV EXPANSION VALVE COIL RT62 DEFROST THERMISTOR
OB346E --1qxp

TAB1 L

PFC
CT2 W
POWER SUPPLY 2 1 R RED
~/N 230V 50Hz X64 4
CIRCUIT
RED RED S

F912
BREAKER R64

BRN
NF TAB4

CB1
CB2
CB3
TB1 3 4 YLW W
YLW V
L NR63 BLK V
BLU IPM
07.2.8 6:53 PM

MC
MUZ-A26YV - E1

BLK
OUTDOOR UNIT

2 1
N

CN5
PE TAB2 CT61 U
WHT
BLK RS1 RS3

2 1 2 1
CT1 U

F911
BLK
Page 13

SSR61
CN902 CN903

GRN/YLW
CN912 CN901 RS2 RS4

CN2

LDE1
LDE2
1 3 1 2 3 5
1 2
CN3

CN4
RT65

7 6 5 4 3 2 1
NOISE FILTER 1 2 LD2 LD1 LD9 POWER

BLU
BLU
P.C. BOARD BOARD

GRN
GRN
21S4

BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
GRN
WHT

ELECTRONIC RED GRY


CONTROL 1 2 3 5 1 5 6 7 1 2 1 3

13
PNK
P.C. BOARD CN781 CN702 CN701
CN801

TB2 RED ORN

1
TO INDOOR 3 BLU
CN931

UNIT CN681 CN661


CONNECTING
F801
BLU YLW MF

3
1 2 3 4 5

CN601
12V 1 2 1 2 3 4 7 8 CN795
N T801 RED
R934A
MODEL WIRING DIAGRAM

RED 6 WHT
BLK
HC932
1 2 3

HPS RED LEV


RT62 RT61 RT68 R934B CN932

SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR OUTDOOR HEAT EXCHANGER refer to the indoor unit electric wiring
RT68 TEMPERATURE THERMISTOR
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR (INNER FUSE) diagram for servicing.
CT61 CURRENT TRANSFORMER NF NOISE FILTER SSR61 SOLENOID COIL RELAY 2.Use copper conductors only (for field wiring).
F801 FUSE (250V 3.15A) NR63 VARISTOR T801 TRANSFORMER 3.Symbols below indicate.
F911 FUSE (250V 1A) PFC POWER FACTOR CONTROLLER TB1 TERMINAL BLOCK :Terminal block :Connector
F912 FUSE (250V 3.15A) R64 RESISTOR TB2 TERMINAL BLOCK
HC932 FET ARRAY R934A, B RESISTOR X64 RELAY
HPS HIGH PRESSURE SWITCH RS1~4 RESISTOR 21S4 R.V. COIL
IPM POWER TRANSISTOR MODULE RT61 DISCHARGE TEMPERATURE THERMISTOR
L REACTOR RT62 DEFROST THERMISTOR
LEV EXPANSION VALVE COIL RT65 FIN TEMPERATURE THERMISTOR
OB346E --1qxp 07.2.8 6:53 PM Page 14

7 REFRIGERANT SYSTEM DIAGRAM

MUZ-A18YV - E1 Unit:mm
MUZ-A24YV - E1
OUTDOOR UNIT
Refrigerant pipe [12.7 (MUZ-A18YV) Muffler
(with heat insulator) [15.88 (MUZ-A24YV) 4-way valve #100

Stop valve
(with service port) Outdoor
Flared connection Discharge heat
temperature exchanger
thermistor Defrost
RT61 thermistor
RT62

Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
Strainer LEV
Strainer
Receiver #100 #100 R.V. coil
heating ON
cooling OFF
Stop valve Capillary tube
[3.6[2.450
Refrigerant pipe [6.35 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
MUZ-A26YV - E1 Unit:mm
Capillary tube
OUTDOOR UNIT [1.8[0.61000
Refrigerant pipe [15.88 Oil separator High-pressure
(with heat insulator) 4-way valve switch

Stop valve
(with service port) Outdoor
Flared connection Strainer Defrost heat
#100 thermistor exchanger
RT62
Discharge
temperature
thermistor
RT61

Compressor
Outdoor
heat
exchanger
temperature
thermistor
RT68
Flared connection
LEV
Strainer Strainer
Receiver #100 #100 R.V. coil
heating ON
cooling OFF
Stop valve Capillary tube
[3.6[2.450
Refrigerant pipe [9.52 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
14
OB346E --1qxp 07.2.8 6:53 PM Page 15

MAX. REFRIGERANT PIPING LENGTH


Refrigerant piping
Piping size O.D : mm Length of connecting pipe : m
Model Max. length : m
A Gas Liquid Indoor unit Outdoor unit

MUZ-A18YV - E1 12.7
6.35 Gas 0.43 Gas 0
MUZ-A24YV - E1 30 Liquid 0.5 Liquid 0
15.88
MUZ-A26YV - E1 9.52

MAX. HEIGHT DIFFERENCE

Indoor
unit

w Max. Height
difference 15m
Refrigerant Piping
Max. length
A

Outdoor unit

w Height difference should be within 15m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Refrigerant piping length (one way)
Outdoor unit
Model precharged 7m 10m 15m 20m 25m 30m

MUZ-A18YV - E1 1,800 0 60 160 260 360 460

Calculation : Xg=20g/m (Refrigerant piping length (m)7)

Refrigerant piping length (one way)


Outdoor unit
Model precharged 7m 10m 15m 20m 25m 30m

MUZ-A24YV - E1 1,800 0 60 160 260 360 460

Calculation : Xg=20g/m (Refrigerant piping length (m)7)

Outdoor unit Refrigerant piping length (one way)


Model
precharged 7m 10m 15m 20m 25m 30m

MUZ-A26YV - E1 2,000 0 165 440 715 990 1,265

Calculation : Xg=55g/mo(Refrigerant piping length(m)-7)

15
OB346E --1qxp 07.2.8 6:53 PM Page 16

8 PERFORMANCE CURVES

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
207 ~ 253V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : C WB
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
(4) Total input :
(5) Indoor intake air dry-bulb temperature :
C WB
C DB
W
C DB
Cooling
}
(6) Outdoor intake air wet-bulb temperature :
(7) Total input :
C WB
W
Heating }
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the differ-
ence between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your
reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

Wet and dry-bulb Wet and dry-bulb


thermometers thermometers
Indoor air Wet-bulb temperature

11.4 11.1 11.3 12.9 13.9

10.5 10.2 10.3 11.7 12.7


difference (degree)

9.5 9.2 9.3 10.6 11.4

8.6 8.3 8.4 9.6 10.3


Indoo )
r inta
7.7 7.5 7.5 8.6 9.2 ke air ture (:
Wet-b mpera
ulb tem Wet-bulb te
6.8 6.6 6.7 7.6 8.1 peratu ke air
re (: r inta
) Indoo
Rated frequency 102Hz
MCFZ-A18WV - E1

MCFZ-A24WV - E1
Rated frequency 73Hz

Rated frequency 84Hz

Rated frequency 88Hz

Rated frequency 63Hz

Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:)
MUZ-A18YV - E1

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1
MSZ-A18YV - E1

MSZ-A24YV - E1

MSZ-A26YV - E1

16
OB346E --1qxp 07.2.8 6:53 PM Page 17

25.7 28.0 26.2 29.9 31.2


Indoor air Dry-bulb temperature

23.7 25.9 24.1 27.6 28.8 ) )


(:
ure re (:
t ratu
difference (degree)

21.8 23.7 22.1 25.3 26.4 p era te mpe


tem y -bulb
21.6 23.0 lb ir Dr
19.8 20.1 24.0 bu ke a
ry- or inta
17.8 19.4 18.1 20.7 21.6 ir D Indo
ea
in tak
15.8 17.2 16.1 18.4 19.2 or
Indo
13.8 15.1 14.1 16.1 16.8
11.9 12.9 12.1 13.8 14.4
MCFZ-A18WV - E1

MCFZ-A24WV - E1
Rated frequency 82Hz

Rated frequency 86Hz

Rated frequency 96Hz

Rated frequency 95Hz

Rated frequency 65Hz


MUZ-A18YV - E1

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1
MSZ-A18YV - E1

MSZ-A24YV - E1

MSZ-A26YV - E1
Outdoor intake air Wet-bulb temperature (:) Outdoor intake air Wet-bulb temperature (:)

NOTE:The above curves are for the heating operation without any frost.

MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1

Indoor unit : Indoor unit : Indoor unit : Indoor unit :


( MSZ-A18 YV -
Correction of Cooling capacity
E1 ) ( MSZ-A18YV - E1
Correction of Cooling total input
) ( MSZ-A18YV - E1 ) ( MSZ-A18YV - E1 )
Correction of Heating capacity Correction of Heating total input
1.5 1.5 1.5 1.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1


Indoor unit : Indoor unit : Indoor unit : Indoor unit :
( MCFZ-A18WV - E1
Correction of Cooling capacity
) ( MCFZ-A18WV - E1
Correction of Cooling total input
) ( MCFZ-A18WV - E1 ) ( MCFZ-A18WV - E1 )
Correction of Heating capacity Correction of Heating total input
1.5 1.5 1.5 1.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 (Hz) 0 50 100 150 (Hz)


The operational frequency of compressor The operational frequency of compressor The0 operational
50 100 150(Hz)
frequency of compressor
0 50 100 150(Hz)
The operational frequency of compressor

MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1

Indoor unit : Indoor unit : Indoor unit : Indoor unit :


( MSZ-A24YV -
Correction of Cooling capacity
E1 ) ( MSZ-A24YV -
Correction of Cooling total input
E1 ) ( MSZ-A24YV - E1 ) ( MSZ-A24YV - E1
Correction of Heating total input
)
Correction of Heating capacity
1.5 1.5 1.5 1.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

17
OB346E --1qxp 07.2.8 6:53 PM Page 18

MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1


Indoor unit : Indoor unit : Indoor unit : Indoor unit :
( MCFZ-A24WV - E1 ) (
Correction of Cooling capacity
MCFZ-A24WV - E1 ) (
Correction of Cooling total input
MCFZ-A24WV - E1 ) ( MCFZ-A24WV - E1
Correction of Heating total input
)
Correction of Heating capacity
1.5 1.5 1.5 1.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

MUZ-A26YV - E1 MUZ-A26YV - E1 MUZ-A26YV - E1 MUZ-A26YV - E1


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 1.5 1.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


<How to operate fixed-frequency operation (Test run operation)>
1. Press the EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continue to operate for 30 minutes.
3. Compressor starts at fixed-frequency.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the EMERGENCY OPERATION switch or any button on
remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


COOL operation
1 Both indoor and outdoor unit are under the Dry-bulb temperature(C) Relative humidity(%)
same temperature/humidity condition.
2 Air flow : High speed 20 50
3 Operational frequency : 25Hz(MUZ-A18YV) 25 60
25Hz(MUZ-A24YV)
30 70
24Hz(MUZ-A26YV)

MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1 MUZ-A18YV - E1


Indoor unit : Indoor unit :
( MSZ-A18YV - E1 ) ( Indoor unit :
MSZ-A18YV - E1 ) ( MCFZ-A18WV - E1 ) ( Indoor unit :
MCFZ-A18WV - E1 )
(kgf/F [Gauge])(MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge])
16 1.6 3 16 1.6 3
Outdoor unit current(A)
Outdoor unit current(A)

14 1.4 14 1.4
Outdoor low pressure
Outdoor low pressure

25Hz 2.5 25Hz 2.5


12 1.2 25Hz 12 1.2 25Hz

10 1.0 2 10 1.0 2

8 0.8 8 0.8
1.5 1.5
6 0.6 6 0.6

4 0.4 1 4 0.4 1
18 20 25 15
30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)

18
OB346E --1qxp 07.2.8 6:53 PM Page 19

MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1 MUZ-A24YV - E1


Indoor unit :
( MSZ-A24YV - E1 ) ( Indoor unit :
MSZ-A24YV - E1 ) ( Indoor unit :
MCFZ-A24YV - E1 ) ( Indoor unit :
MCFZ-A24YV - E1 )
(kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge])
16 1.6 5 16 1.6 5

14 1.4 14 1.4

Outdoor low pressure

Outdoor unit current(A)


Outdoor low pressure

Outdoor unit current(A)


25Hz 4 25Hz 4
12 1.2 25Hz 12 1.2 25Hz

10 1.0 3 10 1.0 3

8 0.8 8 0.8
2 2
6 0.6 6 0.6

4 0.4 1 4 0.4 1
15
18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)

MUZ-A26YV - E1 MUZ-A26YV - E1

(kgf/F [Gauge]) (MPa [Gauge])


16 1.6 4.5

14 1.4
Outdoor low pressure

Outdoor unit current(A)

24Hz
24Hz 4
12 1.2

10 1.0 3.5

8 0.8
3
6 0.6

4 0.4 2.5
15
18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)

HEAT operation
Condition indoor: Dry bulb temperature 20.0C
Wet bulb temperature 14.5C Operational frequency : 32Hz(MUZ-A18YV)
Condition outdoor: Dry bulb temperature 2,7,15,20.0C 32Hz(MUZ-A24YV)
Wet bulb temperature 1,6,12,14.5C 32Hz(MUZ-A26YV)

MUZ-A18YV - E1 MUZ-A18YV - E1
Indoor unit :

4.0
(MSZ-A18YV - E1 ) ( Indoor unit :
MCFZ-A18WV - E1 )
4.0

3.5 3.5
Outdoor unit current (A)

Outdoor unit current (A)

3.0 3.0
32Hz 32Hz
2.5 2.5

2.0 2.0

1.5 1.5

1.0 1.0
2 5 10 15 20 25(:) 2 5 10 15 20 25(:)
Ambient temperature(C) Ambient temperature(C)

MUZ-A24YV - E1 MUZ-A24YV - E1
Indoor unit :
(MSZ-A24YV - E1 ) ( Indoor unit :
MCFZ-A24WV - E1 ) MUZ-A26YV - E1
4.0 4.0 6
32Hz
3.5 3.5 5.5
Outdoor unit current (A)

Outdoor unit current (A)

Outdoor unit current (A)

3.0 3.0 5
32Hz 32Hz
2.5 2.5 4.5

2.0 2.0 4.0

1.5 1.5 3.5

1.0 1.0 3.0


2 5 10 15 20 25(:) 2 5 10 15 20 25(:) 2 5 10 15 20 25(:)
Ambient temperature(C) Ambient temperature(C) Ambient temperature(C)

19
OB346E --1qxp 07.2.8 6:53 PM Page 20

PERFORMANCE DATA COOL operation Rated frequency 73Hz


MSZ-A18YV - E1 : MUZ-A18YV - E1
CAPACITY:5.0(kW) SHF:0.65 INPUT:1560(W)
OUTDOOR DB(:)
INDOOR INDOOR 21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.88 2.76 0.47 1248 5.63 2.64 0.47 1310 5.40 2.54 0.47 1373 5.20 2.44 0.47 1435
21 20 6.13 2.14 0.35 1310 5.88 2.06 0.35 1388 5.70 2.00 0.35 1420 5.50 1.93 0.35 1482
22 18 5.88 3.00 0.51 1248 5.63 2.87 0.51 1310 5.40 2.75 0.51 1373 5.20 2.65 0.51 1435
22 20 6.13 2.39 0.39 1310 5.88 2.29 0.39 1388 5.70 2.22 0.39 1420 5.50 2.15 0.39 1482
22 22 6.38 1.72 0.27 1357 6.15 1.66 0.27 1443 6.00 1.62 0.27 1482 5.75 1.55 0.27 1544
23 18 5.88 3.23 0.55 1248 5.63 3.09 0.55 1310 5.40 2.97 0.55 1373 5.20 2.86 0.55 1435
23 20 6.13 2.63 0.43 1310 5.88 2.53 0.43 1388 5.70 2.45 0.43 1420 5.50 2.37 0.43 1482
23 22 6.38 1.98 0.31 1357 6.15 1.91 0.31 1443 6.00 1.86 0.31 1482 5.75 1.78 0.31 1544
24 18 5.88 3.47 0.59 1248 5.63 3.32 0.59 1310 5.40 3.19 0.59 1373 5.20 3.07 0.59 1435
24 20 6.13 2.88 0.47 1310 5.88 2.76 0.47 1388 5.70 2.68 0.47 1420 5.50 2.59 0.47 1482
24 22 6.38 2.23 0.35 1357 6.15 2.15 0.35 1443 6.00 2.10 0.35 1482 5.75 2.01 0.35 1544
24 24 6.70 1.54 0.23 1420 6.45 1.48 0.23 1498 6.30 1.45 0.23 1544 6.10 1.40 0.23 1622
25 18 5.88 3.70 0.63 1248 5.63 3.54 0.63 1310 5.40 3.40 0.63 1373 5.20 3.28 0.63 1435
25 20 6.13 3.12 0.51 1310 5.88 3.00 0.51 1388 5.70 2.91 0.51 1420 5.50 2.81 0.51 1482
25 22 6.38 2.49 0.39 1357 6.15 2.40 0.39 1443 6.00 2.34 0.39 1482 5.75 2.24 0.39 1544
25 24 6.70 1.81 0.27 1420 6.45 1.74 0.27 1498 6.30 1.70 0.27 1544 6.10 1.65 0.27 1622
26 18 5.88 3.94 0.67 1248 5.63 3.77 0.67 1310 5.40 3.62 0.67 1373 5.20 3.48 0.67 1435
26 20 6.13 3.37 0.55 1310 5.88 3.23 0.55 1388 5.70 3.14 0.55 1420 5.50 3.03 0.55 1482
26 22 6.38 2.74 0.43 1357 6.15 2.64 0.43 1443 6.00 2.58 0.43 1482 5.75 2.47 0.43 1544
26 24 6.70 2.08 0.31 1420 6.45 2.00 0.31 1498 6.30 1.95 0.31 1544 6.10 1.89 0.31 1622
26 26 6.90 1.31 0.19 1498 6.70 1.27 0.19 1576 6.60 1.25 0.19 1622 6.40 1.22 0.19 1669
27 18 5.88 4.17 0.71 1248 5.63 3.99 0.71 1310 5.40 3.83 0.71 1373 5.20 3.69 0.71 1435
27 20 6.13 3.61 0.59 1310 5.88 3.47 0.59 1388 5.70 3.36 0.59 1420 5.50 3.25 0.59 1482
27 22 6.38 3.00 0.47 1357 6.15 2.89 0.47 1443 6.00 2.82 0.47 1482 5.75 2.70 0.47 1544
27 24 6.70 2.35 0.35 1420 6.45 2.26 0.35 1498 6.30 2.21 0.35 1544 6.10 2.14 0.35 1622
27 26 6.90 1.59 0.23 1498 6.70 1.54 0.23 1576 6.60 1.52 0.23 1622 6.40 1.47 0.23 1669
28 18 5.88 4.41 0.75 1248 5.63 4.22 0.75 1310 5.40 4.05 0.75 1373 5.20 3.90 0.75 1435
28 20 6.13 3.86 0.63 1310 5.88 3.70 0.63 1388 5.70 3.59 0.63 1420 5.50 3.47 0.63 1482
28 22 6.38 3.25 0.51 1357 6.15 3.14 0.51 1443 6.00 3.06 0.51 1482 5.75 2.93 0.51 1544
28 24 6.70 2.61 0.39 1420 6.45 2.52 0.39 1498 6.30 2.46 0.39 1544 6.10 2.38 0.39 1622
28 26 6.90 1.86 0.27 1498 6.70 1.81 0.27 1576 6.60 1.78 0.27 1622 6.40 1.73 0.27 1669
29 18 5.88 4.64 0.79 1248 5.63 4.44 0.79 1310 5.40 4.27 0.79 1373 5.20 4.11 0.79 1435
29 20 6.13 4.10 0.67 1310 5.88 3.94 0.67 1388 5.70 3.82 0.67 1420 5.50 3.69 0.67 1482
29 22 6.38 3.51 0.55 1357 6.15 3.38 0.55 1443 6.00 3.30 0.55 1482 5.75 3.16 0.55 1544
29 24 6.70 2.88 0.43 1420 6.45 2.77 0.43 1498 6.30 2.71 0.43 1544 6.10 2.62 0.43 1622
29 26 6.90 2.14 0.31 1498 6.70 2.08 0.31 1576 6.60 2.05 0.31 1622 6.40 1.98 0.31 1669
30 18 5.88 4.88 0.83 1248 5.63 4.67 0.83 1310 5.40 4.48 0.83 1373 5.20 4.32 0.83 1435
30 20 6.13 4.35 0.71 1310 5.88 4.17 0.71 1388 5.70 4.05 0.71 1420 5.50 3.91 0.71 1482
30 22 6.38 3.76 0.59 1357 6.15 3.63 0.59 1443 6.00 3.54 0.59 1482 5.75 3.39 0.59 1544
30 24 6.70 3.15 0.47 1420 6.45 3.03 0.47 1498 6.30 2.96 0.47 1544 6.10 2.87 0.47 1622
30 26 6.90 2.42 0.35 1498 6.70 2.35 0.35 1576 6.60 2.31 0.35 1622 6.40 2.24 0.35 1669
31 18 5.88 5.11 0.87 1248 5.63 4.89 0.87 1310 5.40 4.70 0.87 1373 5.20 4.52 0.87 1435
31 20 6.13 4.59 0.75 1310 5.88 4.41 0.75 1388 5.70 4.28 0.75 1420 5.50 4.13 0.75 1482
31 22 6.38 4.02 0.63 1357 6.15 3.87 0.63 1443 6.00 3.78 0.63 1482 5.75 3.62 0.63 1544
31 24 6.70 3.42 0.51 1420 6.45 3.29 0.51 1498 6.30 3.21 0.51 1544 6.10 3.11 0.51 1622
31 26 6.90 2.69 0.39 1498 6.70 2.61 0.39 1576 6.60 2.57 0.39 1622 6.40 2.50 0.39 1669
32 18 5.88 5.35 0.91 1248 5.63 5.12 0.91 1310 5.40 4.91 0.91 1373 5.20 4.73 0.91 1435
32 20 6.13 4.84 0.79 1310 5.88 4.64 0.79 1388 5.70 4.50 0.79 1420 5.50 4.35 0.79 1482
32 22 6.38 4.27 0.67 1357 6.15 4.12 0.67 1443 6.00 4.02 0.67 1482 5.75 3.85 0.67 1544
32 24 6.70 3.69 0.55 1420 6.45 3.55 0.55 1498 6.30 3.47 0.55 1544 6.10 3.36 0.55 1622
32 26 6.90 2.97 0.43 1498 6.70 2.88 0.43 1576 6.60 2.84 0.43 1622 6.40 2.75 0.43 1669
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
20
OB346E --1qxp 07.2.8 6:53 PM Page 21

PERFORMANCE DATA COOL operation Rated frequency 73Hz


MSZ-A18YV - E1 : MUZ-A18YV - E1
CAPACITY : 5.0(kW) SHF : 0.65 INPUT : 1560(W)
OUTDOOR DB(:)
INDOOR INDOOR 35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.90 2.30 0.47 1529 4.50 2.12 0.47 1622 4.33 2.03 0.47 1654
21 20 5.15 1.80 0.35 1591 4.80 1.68 0.35 1669 4.63 1.62 0.35 1716
22 18 4.90 2.50 0.51 1529 4.50 2.30 0.51 1622 4.33 2.21 0.51 1654
22 20 5.15 2.01 0.39 1591 4.80 1.87 0.39 1669 4.63 1.80 0.39 1716
22 22 5.45 1.47 0.27 1654 5.10 1.38 0.27 1747 4.93 1.33 0.27 1778
23 18 4.90 2.70 0.55 1529 4.50 2.48 0.55 1622 4.33 2.38 0.55 1654
23 20 5.15 2.21 0.43 1591 4.80 2.06 0.43 1669 4.63 1.99 0.43 1716
23 22 5.45 1.69 0.31 1654 5.10 1.58 0.31 1747 4.93 1.53 0.31 1778
24 18 4.90 2.89 0.59 1529 4.50 2.66 0.59 1622 4.33 2.55 0.59 1654
24 20 5.15 2.42 0.47 1591 4.80 2.26 0.47 1669 4.63 2.17 0.47 1716
24 22 5.45 1.91 0.35 1654 5.10 1.79 0.35 1747 4.93 1.72 0.35 1778
24 24 5.75 1.32 0.23 1716 5.40 1.24 0.23 1794 5.25 1.21 0.23 1833
25 18 4.90 3.09 0.63 1529 4.50 2.84 0.63 1622 4.33 2.72 0.63 1654
25 20 5.15 2.63 0.51 1591 4.80 2.45 0.51 1669 4.63 2.36 0.51 1716
25 22 5.45 2.13 0.39 1654 5.10 1.99 0.39 1747 4.93 1.92 0.39 1778
25 24 5.75 1.55 0.27 1716 5.40 1.46 0.27 1794 5.25 1.42 0.27 1833
26 18 4.90 3.28 0.67 1529 4.50 3.02 0.67 1622 4.33 2.90 0.67 1654
26 20 5.15 2.83 0.55 1591 4.80 2.64 0.55 1669 4.63 2.54 0.55 1716
26 22 5.45 2.34 0.43 1654 5.10 2.19 0.43 1747 4.93 2.12 0.43 1778
26 24 5.75 1.78 0.31 1716 5.40 1.67 0.31 1794 5.25 1.63 0.31 1833
26 26 6.05 1.15 0.19 1778 5.70 1.08 0.19 1856 5.53 1.05 0.19 1895
27 18 4.90 3.48 0.71 1529 4.50 3.20 0.71 1622 4.33 3.07 0.71 1654
27 20 5.15 3.04 0.59 1591 4.80 2.83 0.59 1669 4.63 2.73 0.59 1716
27 22 5.45 2.56 0.47 1654 5.10 2.40 0.47 1747 4.93 2.31 0.47 1778
27 24 5.75 2.01 0.35 1716 5.40 1.89 0.35 1794 5.25 1.84 0.35 1833
27 26 6.05 1.39 0.23 1778 5.70 1.31 0.23 1856 5.53 1.27 0.23 1895
28 18 4.90 3.68 0.75 1529 4.50 3.38 0.75 1622 4.33 3.24 0.75 1654
28 20 5.15 3.24 0.63 1591 4.80 3.02 0.63 1669 4.63 2.91 0.63 1716
28 22 5.45 2.78 0.51 1654 5.10 2.60 0.51 1747 4.93 2.51 0.51 1778
28 24 5.75 2.24 0.39 1716 5.40 2.11 0.39 1794 5.25 2.05 0.39 1833
28 26 6.05 1.63 0.27 1778 5.70 1.54 0.27 1856 5.53 1.49 0.27 1895
29 18 4.90 3.87 0.79 1529 4.50 3.56 0.79 1622 4.33 3.42 0.79 1654
29 20 5.15 3.45 0.67 1591 4.80 3.22 0.67 1669 4.63 3.10 0.67 1716
29 22 5.45 3.00 0.55 1654 5.10 2.81 0.55 1747 4.93 2.71 0.55 1778
29 24 5.75 2.47 0.43 1716 5.40 2.32 0.43 1794 5.25 2.26 0.43 1833
29 26 6.05 1.88 0.31 1778 5.70 1.77 0.31 1856 5.53 1.71 0.31 1895
30 18 4.90 4.07 0.83 1529 4.50 3.74 0.83 1622 4.33 3.59 0.83 1654
30 20 5.15 3.66 0.71 1591 4.80 3.41 0.71 1669 4.63 3.28 0.71 1716
30 22 5.45 3.22 0.59 1654 5.10 3.01 0.59 1747 4.93 2.91 0.59 1778
30 24 5.75 2.70 0.47 1716 5.40 2.54 0.47 1794 5.25 2.47 0.47 1833
30 26 6.05 2.12 0.35 1778 5.70 2.00 0.35 1856 5.53 1.93 0.35 1895
31 18 4.90 4.26 0.87 1529 4.50 3.92 0.87 1622 4.33 3.76 0.87 1654
31 20 5.15 3.86 0.75 1591 4.80 3.60 0.75 1669 4.63 3.47 0.75 1716
31 22 5.45 3.43 0.63 1654 5.10 3.21 0.63 1747 4.93 3.10 0.63 1778
31 24 5.75 2.93 0.51 1716 5.40 2.75 0.51 1794 5.25 2.68 0.51 1833
31 26 6.05 2.36 0.39 1778 5.70 2.22 0.39 1856 5.53 2.15 0.39 1895
32 18 4.90 4.46 0.91 1529 4.50 4.10 0.91 1622 4.33 3.94 0.91 1654
32 20 5.15 4.07 0.79 1591 4.80 3.79 0.79 1669 4.63 3.65 0.79 1716
32 22 5.45 3.65 0.67 1654 5.10 3.42 0.67 1747 4.93 3.30 0.67 1778
32 24 5.75 3.16 0.55 1716 5.40 2.97 0.55 1794 5.25 2.89 0.55 1833
32 26 6.05 2.60 0.43 1778 5.70 2.45 0.43 1856 5.53 2.38 0.43 1895
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
21
OB346E --1qxp 07.2.8 6:53 PM Page 22

PERFORMANCE DATA COOL operation Rated frequency 84Hz


MCFZ-A18WV - E1 : MUZ-A18YV - E1
CAPACITY:4.8(kW) SHF:0.65 INPUT:1830(W)
OUTDOOR DB(:)
INDOOR INDOOR 21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.64 2.65 0.47 1464 5.40 2.54 0.47 1537 5.18 2.44 0.47 1610 4.99 2.35 0.47 1684
21 20 5.88 2.06 0.35 1537 5.64 1.97 0.35 1629 5.47 1.92 0.35 1665 5.28 1.85 0.35 1739
22 18 5.64 2.88 0.51 1464 5.40 2.75 0.51 1537 5.18 2.64 0.51 1610 4.99 2.55 0.51 1684
22 20 5.88 2.29 0.39 1537 5.64 2.20 0.39 1629 5.47 2.13 0.39 1665 5.28 2.06 0.39 1739
22 22 6.12 1.65 0.27 1592 5.90 1.59 0.27 1693 5.76 1.56 0.27 1739 5.52 1.49 0.27 1812
23 18 5.64 3.10 0.55 1464 5.40 2.97 0.55 1537 5.18 2.85 0.55 1610 4.99 2.75 0.55 1684
23 20 5.88 2.53 0.43 1537 5.64 2.43 0.43 1629 5.47 2.35 0.43 1665 5.28 2.27 0.43 1739
23 22 6.12 1.90 0.31 1592 5.90 1.83 0.31 1693 5.76 1.79 0.31 1739 5.52 1.71 0.31 1812
24 18 5.64 3.33 0.59 1464 5.40 3.19 0.59 1537 5.18 3.06 0.59 1610 4.99 2.95 0.59 1684
24 20 5.88 2.76 0.47 1537 5.64 2.65 0.47 1629 5.47 2.57 0.47 1665 5.28 2.48 0.47 1739
24 22 6.12 2.14 0.35 1592 5.90 2.07 0.35 1693 5.76 2.02 0.35 1739 5.52 1.93 0.35 1812
24 24 6.43 1.48 0.23 1665 6.19 1.42 0.23 1757 6.05 1.39 0.23 1812 5.86 1.35 0.23 1903
25 18 5.64 3.55 0.63 1464 5.40 3.40 0.63 1537 5.18 3.27 0.63 1610 4.99 3.14 0.63 1684
25 20 5.88 3.00 0.51 1537 5.64 2.88 0.51 1629 5.47 2.79 0.51 1665 5.28 2.69 0.51 1739
25 22 6.12 2.39 0.39 1592 5.90 2.30 0.39 1693 5.76 2.25 0.39 1739 5.52 2.15 0.39 1812
25 24 6.43 1.74 0.27 1665 6.19 1.67 0.27 1757 6.05 1.63 0.27 1812 5.86 1.58 0.27 1903
26 18 5.64 3.78 0.67 1464 5.40 3.62 0.67 1537 5.18 3.47 0.67 1610 4.99 3.34 0.67 1684
26 20 5.88 3.23 0.55 1537 5.64 3.10 0.55 1629 5.47 3.01 0.55 1665 5.28 2.90 0.55 1739
26 22 6.12 2.63 0.43 1592 5.90 2.54 0.43 1693 5.76 2.48 0.43 1739 5.52 2.37 0.43 1812
26 24 6.43 1.99 0.31 1665 6.19 1.92 0.31 1757 6.05 1.87 0.31 1812 5.86 1.82 0.31 1903
26 26 6.62 1.26 0.19 1757 6.43 1.22 0.19 1848 6.34 1.20 0.19 1903 6.14 1.17 0.19 1958
27 18 5.64 4.00 0.71 1464 5.40 3.83 0.71 1537 5.18 3.68 0.71 1610 4.99 3.54 0.71 1684
27 20 5.88 3.47 0.59 1537 5.64 3.33 0.59 1629 5.47 3.23 0.59 1665 5.28 3.12 0.59 1739
27 22 6.12 2.88 0.47 1592 5.90 2.77 0.47 1693 5.76 2.71 0.47 1739 5.52 2.59 0.47 1812
27 24 6.43 2.25 0.35 1665 6.19 2.17 0.35 1757 6.05 2.12 0.35 1812 5.86 2.05 0.35 1903
27 26 6.62 1.52 0.23 1757 6.43 1.48 0.23 1848 6.34 1.46 0.23 1903 6.14 1.41 0.23 1958
28 18 5.64 4.23 0.75 1464 5.40 4.05 0.75 1537 5.18 3.89 0.75 1610 4.99 3.74 0.75 1684
28 20 5.88 3.70 0.63 1537 5.64 3.55 0.63 1629 5.47 3.45 0.63 1665 5.28 3.33 0.63 1739
28 22 6.12 3.12 0.51 1592 5.90 3.01 0.51 1693 5.76 2.94 0.51 1739 5.52 2.82 0.51 1812
28 24 6.43 2.51 0.39 1665 6.19 2.41 0.39 1757 6.05 2.36 0.39 1812 5.86 2.28 0.39 1903
28 26 6.62 1.79 0.27 1757 6.43 1.74 0.27 1848 6.34 1.71 0.27 1903 6.14 1.66 0.27 1958
29 18 5.64 4.46 0.79 1464 5.40 4.27 0.79 1537 5.18 4.10 0.79 1610 4.99 3.94 0.79 1684
29 20 5.88 3.94 0.67 1537 5.64 3.78 0.67 1629 5.47 3.67 0.67 1665 5.28 3.54 0.67 1739
29 22 6.12 3.37 0.55 1592 5.90 3.25 0.55 1693 5.76 3.17 0.55 1739 5.52 3.04 0.55 1812
29 24 6.43 2.77 0.43 1665 6.19 2.66 0.43 1757 6.05 2.60 0.43 1812 5.86 2.52 0.43 1903
29 26 6.62 2.05 0.31 1757 6.43 1.99 0.31 1848 6.34 1.96 0.31 1903 6.14 1.90 0.31 1958
30 18 5.64 4.68 0.83 1464 5.40 4.48 0.83 1537 5.18 4.30 0.83 1610 4.99 4.14 0.83 1684
30 20 5.88 4.17 0.71 1537 5.64 4.00 0.71 1629 5.47 3.89 0.71 1665 5.28 3.75 0.71 1739
30 22 6.12 3.61 0.59 1592 5.90 3.48 0.59 1693 5.76 3.40 0.59 1739 5.52 3.26 0.59 1812
30 24 6.43 3.02 0.47 1665 6.19 2.91 0.47 1757 6.05 2.84 0.47 1812 5.86 2.75 0.47 1903
30 26 6.62 2.32 0.35 1757 6.43 2.25 0.35 1848 6.34 2.22 0.35 1903 6.14 2.15 0.35 1958
31 18 5.64 4.91 0.87 1464 5.40 4.70 0.87 1537 5.18 4.51 0.87 1610 4.99 4.34 0.87 1684
31 20 5.88 4.41 0.75 1537 5.64 4.23 0.75 1629 5.47 4.10 0.75 1665 5.28 3.96 0.75 1739
31 22 6.12 3.86 0.63 1592 5.90 3.72 0.63 1693 5.76 3.63 0.63 1739 5.52 3.48 0.63 1812
31 24 6.43 3.28 0.51 1665 6.19 3.16 0.51 1757 6.05 3.08 0.51 1812 5.86 2.99 0.51 1903
31 26 6.62 2.58 0.39 1757 6.43 2.51 0.39 1848 6.34 2.47 0.39 1903 6.14 2.40 0.39 1958
32 18 5.64 5.13 0.91 1464 5.40 4.91 0.91 1537 5.18 4.72 0.91 1610 4.99 4.54 0.91 1684
32 20 5.88 4.65 0.79 1537 5.64 4.46 0.79 1629 5.47 4.32 0.79 1665 5.28 4.17 0.79 1739
32 22 6.12 4.10 0.67 1592 5.90 3.96 0.67 1693 5.76 3.86 0.67 1739 5.52 3.70 0.67 1812
32 24 6.43 3.54 0.55 1665 6.19 3.41 0.55 1757 6.05 3.33 0.55 1812 5.86 3.22 0.55 1903
32 26 6.62 2.85 0.43 1757 6.43 2.77 0.43 1848 6.34 2.72 0.43 1903 6.14 2.64 0.43 1958
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
22
OB346E --1qxp 07.2.8 6:53 PM Page 23

PERFORMANCE DATA COOL operation Rated frequency 84Hz


MCFZ-A18WV - E1 : MUZ-A18YV - E1
CAPACITY : 4.8(kW) SHF : 0.65 INPUT : 1830(W)
OUTDOOR DB(:)
INDOOR INDOOR 35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.70 2.21 0.47 1793 4.32 2.03 0.47 1903 4.15 1.95 0.47 1940
21 20 4.94 1.73 0.35 1867 4.61 1.61 0.35 1958 4.44 1.55 0.35 2013
22 18 4.70 2.40 0.51 1793 4.32 2.20 0.51 1903 4.15 2.12 0.51 1940
22 20 4.94 1.93 0.39 1867 4.61 1.80 0.39 1958 4.44 1.73 0.39 2013
22 22 5.23 1.41 0.27 1940 4.90 1.32 0.27 2050 4.73 1.28 0.27 2086
23 18 4.70 2.59 0.55 1793 4.32 2.38 0.55 1903 4.15 2.28 0.55 1940
23 20 4.94 2.13 0.43 1867 4.61 1.98 0.43 1958 4.44 1.91 0.43 2013
23 22 5.23 1.62 0.31 1940 4.90 1.52 0.31 2050 4.73 1.47 0.31 2086
24 18 4.70 2.78 0.59 1793 4.32 2.55 0.59 1903 4.15 2.45 0.59 1940
24 20 4.94 2.32 0.47 1867 4.61 2.17 0.47 1958 4.44 2.09 0.47 2013
24 22 5.23 1.83 0.35 1940 4.90 1.71 0.35 2050 4.73 1.65 0.35 2086
24 24 5.52 1.27 0.23 2013 5.18 1.19 0.23 2105 5.04 1.16 0.23 2150
25 18 4.70 2.96 0.63 1793 4.32 2.72 0.63 1903 4.15 2.62 0.63 1940
25 20 4.94 2.52 0.51 1867 4.61 2.35 0.51 1958 4.44 2.26 0.51 2013
25 22 5.23 2.04 0.39 1940 4.90 1.91 0.39 2050 4.73 1.84 0.39 2086
25 24 5.52 1.49 0.27 2013 5.18 1.40 0.27 2105 5.04 1.36 0.27 2150
26 18 4.70 3.15 0.67 1793 4.32 2.89 0.67 1903 4.15 2.78 0.67 1940
26 20 4.94 2.72 0.55 1867 4.61 2.53 0.55 1958 4.44 2.44 0.55 2013
26 22 5.23 2.25 0.43 1940 4.90 2.11 0.43 2050 4.73 2.03 0.43 2086
26 24 5.52 1.71 0.31 2013 5.18 1.61 0.31 2105 5.04 1.56 0.31 2150
26 26 5.81 1.10 0.19 2086 5.47 1.04 0.19 2178 5.30 1.01 0.19 2223
27 18 4.70 3.34 0.71 1793 4.32 3.07 0.71 1903 4.15 2.95 0.71 1940
27 20 4.94 2.92 0.59 1867 4.61 2.72 0.59 1958 4.44 2.62 0.59 2013
27 22 5.23 2.46 0.47 1940 4.90 2.30 0.47 2050 4.73 2.22 0.47 2086
27 24 5.52 1.93 0.35 2013 5.18 1.81 0.35 2105 5.04 1.76 0.35 2150
27 26 5.81 1.34 0.23 2086 5.47 1.26 0.23 2178 5.30 1.22 0.23 2223
28 18 4.70 3.53 0.75 1793 4.32 3.24 0.75 1903 4.15 3.11 0.75 1940
28 20 4.94 3.11 0.63 1867 4.61 2.90 0.63 1958 4.44 2.80 0.63 2013
28 22 5.23 2.67 0.51 1940 4.90 2.50 0.51 2050 4.73 2.41 0.51 2086
28 24 5.52 2.15 0.39 2013 5.18 2.02 0.39 2105 5.04 1.97 0.39 2150
28 26 5.81 1.57 0.27 2086 5.47 1.48 0.27 2178 5.30 1.43 0.27 2223
29 18 4.70 3.72 0.79 1793 4.32 3.41 0.79 1903 4.15 3.28 0.79 1940
29 20 4.94 3.31 0.67 1867 4.61 3.09 0.67 1958 4.44 2.97 0.67 2013
29 22 5.23 2.88 0.55 1940 4.90 2.69 0.55 2050 4.73 2.60 0.55 2086
29 24 5.52 2.37 0.43 2013 5.18 2.23 0.43 2105 5.04 2.17 0.43 2150
29 26 5.81 1.80 0.31 2086 5.47 1.70 0.31 2178 5.30 1.64 0.31 2223
30 18 4.70 3.90 0.83 1793 4.32 3.59 0.83 1903 4.15 3.45 0.83 1940
30 20 4.94 3.51 0.71 1867 4.61 3.27 0.71 1958 4.44 3.15 0.71 2013
30 22 5.23 3.09 0.59 1940 4.90 2.89 0.59 2050 4.73 2.79 0.59 2086
30 24 5.52 2.59 0.47 2013 5.18 2.44 0.47 2105 5.04 2.37 0.47 2150
30 26 5.81 2.03 0.35 2086 5.47 1.92 0.35 2178 5.30 1.86 0.35 2223
31 18 4.70 4.09 0.87 1793 4.32 3.76 0.87 1903 4.15 3.61 0.87 1940
31 20 4.94 3.71 0.75 1867 4.61 3.46 0.75 1958 4.44 3.33 0.75 2013
31 22 5.23 3.30 0.63 1940 4.90 3.08 0.63 2050 4.73 2.98 0.63 2086
31 24 5.52 2.82 0.51 2013 5.18 2.64 0.51 2105 5.04 2.57 0.51 2150
31 26 5.81 2.27 0.39 2086 5.47 2.13 0.39 2178 5.30 2.07 0.39 2223
32 18 4.70 4.28 0.91 1793 4.32 3.93 0.91 1903 4.15 3.78 0.91 1940
32 20 4.94 3.91 0.79 1867 4.61 3.64 0.79 1958 4.44 3.51 0.79 2013
32 22 5.23 3.51 0.67 1940 4.90 3.28 0.67 2050 4.73 3.17 0.67 2086
32 24 5.52 3.04 0.55 2013 5.18 2.85 0.55 2105 5.04 2.77 0.55 2150
32 26 5.81 2.50 0.43 2086 5.47 2.35 0.43 2178 5.30 2.28 0.43 2223
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
23
OB346E --1qxp 07.2.8 6:53 PM Page 24

PERFORMANCE DATA COOL operation Rated frequency 88Hz


MSZ-A24YV - E1 : MUZ-A24YV - E1
CAPACITY:6.0(kW) SHF:0.64 INPUT:1990(W)
OUTDOOR
DB(:)
INDOOR INDOOR 21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 7.05 3.24 0.46 1592 6.75 3.11 0.46 1672 6.48 2.98 0.46 1751 6.24 2.87 0.46 1831
21 20 7.35 2.50 0.34 1672 7.05 2.40 0.34 1771 6.84 2.33 0.34 1811 6.60 2.24 0.34 1891
22 18 7.05 3.53 0.50 1592 6.75 3.38 0.50 1672 6.48 3.24 0.50 1751 6.24 3.12 0.50 1831
22 20 7.35 2.79 0.38 1672 7.05 2.68 0.38 1771 6.84 2.60 0.38 1811 6.60 2.51 0.38 1891
22 22 7.65 1.99 0.26 1731 7.38 1.92 0.26 1841 7.20 1.87 0.26 1891 6.90 1.79 0.26 1970
23 18 7.05 3.81 0.54 1592 6.75 3.65 0.54 1672 6.48 3.50 0.54 1751 6.24 3.37 0.54 1831
23 20 7.35 3.09 0.42 1672 7.05 2.96 0.42 1771 6.84 2.87 0.42 1811 6.60 2.77 0.42 1891
23 22 7.65 2.30 0.30 1731 7.38 2.21 0.30 1841 7.20 2.16 0.30 1891 6.90 2.07 0.30 1970
24 18 7.05 4.09 0.58 1592 6.75 3.92 0.58 1672 6.48 3.76 0.58 1751 6.24 3.62 0.58 1831
24 20 7.35 3.38 0.46 1672 7.05 3.24 0.46 1771 6.84 3.15 0.46 1811 6.60 3.04 0.46 1891
24 22 7.65 2.60 0.34 1731 7.38 2.51 0.34 1841 7.20 2.45 0.34 1891 6.90 2.35 0.34 1970
24 24 8.04 1.77 0.22 1811 7.74 1.70 0.22 1910 7.56 1.66 0.22 1970 7.32 1.61 0.22 2070
25 18 7.05 4.37 0.62 1592 6.75 4.19 0.62 1672 6.48 4.02 0.62 1751 6.24 3.87 0.62 1831
25 20 7.35 3.68 0.50 1672 7.05 3.53 0.50 1771 6.84 3.42 0.50 1811 6.60 3.30 0.50 1891
25 22 7.65 2.91 0.38 1731 7.38 2.80 0.38 1841 7.20 2.74 0.38 1891 6.90 2.62 0.38 1970
25 24 8.04 2.09 0.26 1811 7.74 2.01 0.26 1910 7.56 1.97 0.26 1970 7.32 1.90 0.26 2070
26 18 7.05 4.65 0.66 1592 6.75 4.46 0.66 1672 6.48 4.28 0.66 1751 6.24 4.12 0.66 1831
26 20 7.35 3.97 0.54 1672 7.05 3.81 0.54 1771 6.84 3.69 0.54 1811 6.60 3.56 0.54 1891
26 22 7.65 3.21 0.42 1731 7.38 3.10 0.42 1841 7.20 3.02 0.42 1891 6.90 2.90 0.42 1970
26 24 8.04 2.41 0.30 1811 7.74 2.32 0.30 1910 7.56 2.27 0.30 1970 7.32 2.20 0.30 2070
26 26 8.28 1.49 0.18 1910 8.04 1.45 0.18 2010 7.92 1.43 0.18 2070 7.68 1.38 0.18 2129
27 18 7.05 4.94 0.70 1592 6.75 4.73 0.70 1672 6.48 4.54 0.70 1751 6.24 4.37 0.70 1831
27 20 7.35 4.26 0.58 1672 7.05 4.09 0.58 1771 6.84 3.97 0.58 1811 6.60 3.83 0.58 1891
27 22 7.65 3.52 0.46 1731 7.38 3.39 0.46 1841 7.20 3.31 0.46 1891 6.90 3.17 0.46 1970
27 24 8.04 2.73 0.34 1811 7.74 2.63 0.34 1910 7.56 2.57 0.34 1970 7.32 2.49 0.34 2070
27 26 8.28 1.82 0.22 1910 8.04 1.77 0.22 2010 7.92 1.74 0.22 2070 7.68 1.69 0.22 2129
28 18 7.05 5.22 0.74 1592 6.75 5.00 0.74 1672 6.48 4.80 0.74 1751 6.24 4.62 0.74 1831
28 20 7.35 4.56 0.62 1672 7.05 4.37 0.62 1771 6.84 4.24 0.62 1811 6.60 4.09 0.62 1891
28 22 7.65 3.83 0.50 1731 7.38 3.69 0.50 1841 7.20 3.60 0.50 1891 6.90 3.45 0.50 1970
28 24 8.04 3.06 0.38 1811 7.74 2.94 0.38 1910 7.56 2.87 0.38 1970 7.32 2.78 0.38 2070
28 26 8.28 2.15 0.26 1910 8.04 2.09 0.26 2010 7.92 2.06 0.26 2070 7.68 2.00 0.26 2129
29 18 7.05 5.50 0.78 1592 6.75 5.27 0.78 1672 6.48 5.05 0.78 1751 6.24 4.87 0.78 1831
29 20 7.35 4.85 0.66 1672 7.05 4.65 0.66 1771 6.84 4.51 0.66 1811 6.60 4.36 0.66 1891
29 22 7.65 4.13 0.54 1731 7.38 3.99 0.54 1841 7.20 3.89 0.54 1891 6.90 3.73 0.54 1970
29 24 8.04 3.38 0.42 1811 7.74 3.25 0.42 1910 7.56 3.18 0.42 1970 7.32 3.07 0.42 2070
29 26 8.28 2.48 0.30 1910 8.04 2.41 0.30 2010 7.92 2.38 0.30 2070 7.68 2.30 0.30 2129
30 18 7.05 5.78 0.82 1592 6.75 5.54 0.82 1672 6.48 5.31 0.82 1751 6.24 5.12 0.82 1831
30 20 7.35 5.15 0.70 1672 7.05 4.94 0.70 1771 6.84 4.79 0.70 1811 6.60 4.62 0.70 1891
30 22 7.65 4.44 0.58 1731 7.38 4.28 0.58 1841 7.20 4.18 0.58 1891 6.90 4.00 0.58 1970
30 24 8.04 3.70 0.46 1811 7.74 3.56 0.46 1910 7.56 3.48 0.46 1970 7.32 3.37 0.46 2070
30 26 8.28 2.82 0.34 1910 8.04 2.73 0.34 2010 7.92 2.69 0.34 2070 7.68 2.61 0.34 2129
31 18 7.05 6.06 0.86 1592 6.75 5.81 0.86 1672 6.48 5.57 0.86 1751 6.24 5.37 0.86 1831
31 20 7.35 5.44 0.74 1672 7.05 5.22 0.74 1771 6.84 5.06 0.74 1811 6.60 4.88 0.74 1891
31 22 7.65 4.74 0.62 1731 7.38 4.58 0.62 1841 7.20 4.46 0.62 1891 6.90 4.28 0.62 1970
31 24 8.04 4.02 0.50 1811 7.74 3.87 0.50 1910 7.56 3.78 0.50 1970 7.32 3.66 0.50 2070
31 26 8.28 3.15 0.38 1910 8.04 3.06 0.38 2010 7.92 3.01 0.38 2070 7.68 2.92 0.38 2129
32 18 7.05 6.35 0.90 1592 6.75 6.08 0.90 1672 6.48 5.83 0.90 1751 6.24 5.62 0.90 1831
32 20 7.35 5.73 0.78 1672 7.05 5.50 0.78 1771 6.84 5.34 0.78 1811 6.60 5.15 0.78 1891
32 22 7.65 5.05 0.66 1731 7.38 4.87 0.66 1841 7.20 4.75 0.66 1891 6.90 4.55 0.66 1970
32 24 8.04 4.34 0.54 1811 7.74 4.18 0.54 1910 7.56 4.08 0.54 1970 7.32 3.95 0.54 2070
32 26 8.28 3.48 0.42 1910 8.04 3.38 0.42 2010 7.92 3.33 0.42 2070 7.68 3.23 0.42 2129
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
24
OB346E --1qxp 07.2.8 6:53 PM Page 25

PERFORMANCE DATA COOL operation Rated frequency 88Hz


MSZ-A24YV - E1 : MUZ-A24YV - E1
CAPACITY : 6.0(kW) SHF : 0.64 INPUT : 1990(W)
OUTDOOR DB(:)
INDOOR INDOOR 35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.88 2.70 0.46 1950 5.40 2.48 0.46 2070 5.19 2.39 0.46 2109
21 20 6.18 2.10 0.34 2030 5.76 1.96 0.34 2129 5.55 1.89 0.34 2189
22 18 5.88 2.94 0.50 1950 5.40 2.70 0.50 2070 5.19 2.60 0.50 2109
22 20 6.18 2.35 0.38 2030 5.76 2.19 0.38 2129 5.55 2.11 0.38 2189
22 22 6.54 1.70 0.26 2109 6.12 1.59 0.26 2229 5.91 1.54 0.26 2269
23 18 5.88 3.18 0.54 1950 5.40 2.92 0.54 2070 5.19 2.80 0.54 2109
23 20 6.18 2.60 0.42 2030 5.76 2.42 0.42 2129 5.55 2.33 0.42 2189
23 22 6.54 1.96 0.30 2109 6.12 1.84 0.30 2229 5.91 1.77 0.30 2269
24 18 5.88 3.41 0.58 1950 5.40 3.13 0.58 2070 5.19 3.01 0.58 2109
24 20 6.18 2.84 0.46 2030 5.76 2.65 0.46 2129 5.55 2.55 0.46 2189
24 22 6.54 2.22 0.34 2109 6.12 2.08 0.34 2229 5.91 2.01 0.34 2269
24 24 6.90 1.52 0.22 2189 6.48 1.43 0.22 2289 6.30 1.39 0.22 2338
25 18 5.88 3.65 0.62 1950 5.40 3.35 0.62 2070 5.19 3.22 0.62 2109
25 20 6.18 3.09 0.50 2030 5.76 2.88 0.50 2129 5.55 2.78 0.50 2189
25 22 6.54 2.49 0.38 2109 6.12 2.33 0.38 2229 5.91 2.25 0.38 2269
25 24 6.90 1.79 0.26 2189 6.48 1.68 0.26 2289 6.30 1.64 0.26 2338
26 18 5.88 3.88 0.66 1950 5.40 3.56 0.66 2070 5.19 3.43 0.66 2109
26 20 6.18 3.34 0.54 2030 5.76 3.11 0.54 2129 5.55 3.00 0.54 2189
26 22 6.54 2.75 0.42 2109 6.12 2.57 0.42 2229 5.91 2.48 0.42 2269
26 24 6.90 2.07 0.30 2189 6.48 1.94 0.30 2289 6.30 1.89 0.30 2338
26 26 7.26 1.31 0.18 2269 6.84 1.23 0.18 2368 6.63 1.19 0.18 2418
27 18 5.88 4.12 0.70 1950 5.40 3.78 0.70 2070 5.19 3.63 0.70 2109
27 20 6.18 3.58 0.58 2030 5.76 3.34 0.58 2129 5.55 3.22 0.58 2189
27 22 6.54 3.01 0.46 2109 6.12 2.82 0.46 2229 5.91 2.72 0.46 2269
27 24 6.90 2.35 0.34 2189 6.48 2.20 0.34 2289 6.30 2.14 0.34 2338
27 26 7.26 1.60 0.22 2269 6.84 1.50 0.22 2368 6.63 1.46 0.22 2418
28 18 5.88 4.35 0.74 1950 5.40 4.00 0.74 2070 5.19 3.84 0.74 2109
28 20 6.18 3.83 0.62 2030 5.76 3.57 0.62 2129 5.55 3.44 0.62 2189
28 22 6.54 3.27 0.50 2109 6.12 3.06 0.50 2229 5.91 2.96 0.50 2269
28 24 6.90 2.62 0.38 2189 6.48 2.46 0.38 2289 6.30 2.39 0.38 2338
28 26 7.26 1.89 0.26 2269 6.84 1.78 0.26 2368 6.63 1.72 0.26 2418
29 18 5.88 4.59 0.78 1950 5.40 4.21 0.78 2070 5.19 4.05 0.78 2109
29 20 6.18 4.08 0.66 2030 5.76 3.80 0.66 2129 5.55 3.66 0.66 2189
29 22 6.54 3.53 0.54 2109 6.12 3.30 0.54 2229 5.91 3.19 0.54 2269
29 24 6.90 2.90 0.42 2189 6.48 2.72 0.42 2289 6.30 2.65 0.42 2338
29 26 7.26 2.18 0.30 2269 6.84 2.05 0.30 2368 6.63 1.99 0.30 2418
30 18 5.88 4.82 0.82 1950 5.40 4.43 0.82 2070 5.19 4.26 0.82 2109
30 20 6.18 4.33 0.70 2030 5.76 4.03 0.70 2129 5.55 3.89 0.70 2189
30 22 6.54 3.79 0.58 2109 6.12 3.55 0.58 2229 5.91 3.43 0.58 2269
30 24 6.90 3.17 0.46 2189 6.48 2.98 0.46 2289 6.30 2.90 0.46 2338
30 26 7.26 2.47 0.34 2269 6.84 2.33 0.34 2368 6.63 2.25 0.34 2418
31 18 5.88 5.06 0.86 1950 5.40 4.64 0.86 2070 5.19 4.46 0.86 2109
31 20 6.18 4.57 0.74 2030 5.76 4.26 0.74 2129 5.55 4.11 0.74 2189
31 22 6.54 4.05 0.62 2109 6.12 3.79 0.62 2229 5.91 3.66 0.62 2269
31 24 6.90 3.45 0.50 2189 6.48 3.24 0.50 2289 6.30 3.15 0.50 2338
31 26 7.26 2.76 0.38 2269 6.84 2.60 0.38 2368 6.63 2.52 0.38 2418
32 18 5.88 5.29 0.90 1950 5.40 4.86 0.90 2070 5.19 4.67 0.90 2109
32 20 6.18 4.82 0.78 2030 5.76 4.49 0.78 2129 5.55 4.33 0.78 2189
32 22 6.54 4.32 0.66 2109 6.12 4.04 0.66 2229 5.91 3.90 0.66 2269
32 24 6.90 3.73 0.54 2189 6.48 3.50 0.54 2289 6.30 3.40 0.54 2338
32 26 7.26 3.05 0.42 2269 6.84 2.87 0.42 2368 6.63 2.78 0.42 2418
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
25
OB346E --1qxp 07.2.8 6:53 PM Page 26

PERFORMANCE DATA COOL operation Rated frequency 102Hz


MCFZ-A24WV - E1 : MUZ-A24YV - E1
CAPACITY:5.5(kW) SHF:0.65 INPUT:2420(W)
OUTDOOR DB(:)
INDOOR INDOOR 21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 6.46 3.04 0.47 1936 6.19 2.91 0.47 2033 5.94 2.79 0.47 2130 5.72 2.69 0.47 2226
21 20 6.74 2.36 0.35 2033 6.46 2.26 0.35 2154 6.27 2.19 0.35 2202 6.05 2.12 0.35 2299
22 18 6.46 3.30 0.51 1936 6.19 3.16 0.51 2033 5.94 3.03 0.51 2130 5.72 2.92 0.51 2226
22 20 6.74 2.63 0.39 2033 6.46 2.52 0.39 2154 6.27 2.45 0.39 2202 6.05 2.36 0.39 2299
22 22 7.01 1.89 0.27 2105 6.77 1.83 0.27 2239 6.60 1.78 0.27 2299 6.33 1.71 0.27 2396
23 18 6.46 3.55 0.55 1936 6.19 3.40 0.55 2033 5.94 3.27 0.55 2130 5.72 3.15 0.55 2226
23 20 6.74 2.90 0.43 2033 6.46 2.78 0.43 2154 6.27 2.70 0.43 2202 6.05 2.60 0.43 2299
23 22 7.01 2.17 0.31 2105 6.77 2.10 0.31 2239 6.60 2.05 0.31 2299 6.33 1.96 0.31 2396
24 18 6.46 3.81 0.59 1936 6.19 3.65 0.59 2033 5.94 3.50 0.59 2130 5.72 3.37 0.59 2226
24 20 6.74 3.17 0.47 2033 6.46 3.04 0.47 2154 6.27 2.95 0.47 2202 6.05 2.84 0.47 2299
24 22 7.01 2.45 0.35 2105 6.77 2.37 0.35 2239 6.60 2.31 0.35 2299 6.33 2.21 0.35 2396
24 24 7.37 1.70 0.23 2202 7.10 1.63 0.23 2323 6.93 1.59 0.23 2396 6.71 1.54 0.23 2517
25 18 6.46 4.07 0.63 1936 6.19 3.90 0.63 2033 5.94 3.74 0.63 2130 5.72 3.60 0.63 2226
25 20 6.74 3.44 0.51 2033 6.46 3.30 0.51 2154 6.27 3.20 0.51 2202 6.05 3.09 0.51 2299
25 22 7.01 2.73 0.39 2105 6.77 2.64 0.39 2239 6.60 2.57 0.39 2299 6.33 2.47 0.39 2396
25 24 7.37 1.99 0.27 2202 7.10 1.92 0.27 2323 6.93 1.87 0.27 2396 6.71 1.81 0.27 2517
26 18 6.46 4.33 0.67 1936 6.19 4.15 0.67 2033 5.94 3.98 0.67 2130 5.72 3.83 0.67 2226
26 20 6.74 3.71 0.55 2033 6.46 3.55 0.55 2154 6.27 3.45 0.55 2202 6.05 3.33 0.55 2299
26 22 7.01 3.02 0.43 2105 6.77 2.91 0.43 2239 6.60 2.84 0.43 2299 6.33 2.72 0.43 2396
26 24 7.37 2.28 0.31 2202 7.10 2.20 0.31 2323 6.93 2.15 0.31 2396 6.71 2.08 0.31 2517
26 26 7.59 1.44 0.19 2323 7.37 1.40 0.19 2444 7.26 1.38 0.19 2517 7.04 1.34 0.19 2589
27 18 6.46 4.59 0.71 1936 6.19 4.39 0.71 2033 5.94 4.22 0.71 2130 5.72 4.06 0.71 2226
27 20 6.74 3.98 0.59 2033 6.46 3.81 0.59 2154 6.27 3.70 0.59 2202 6.05 3.57 0.59 2299
27 22 7.01 3.30 0.47 2105 6.77 3.18 0.47 2239 6.60 3.10 0.47 2299 6.33 2.97 0.47 2396
27 24 7.37 2.58 0.35 2202 7.10 2.48 0.35 2323 6.93 2.43 0.35 2396 6.71 2.35 0.35 2517
27 26 7.59 1.75 0.23 2323 7.37 1.70 0.23 2444 7.26 1.67 0.23 2517 7.04 1.62 0.23 2589
28 18 6.46 4.85 0.75 1936 6.19 4.64 0.75 2033 5.94 4.46 0.75 2130 5.72 4.29 0.75 2226
28 20 6.74 4.24 0.63 2033 6.46 4.07 0.63 2154 6.27 3.95 0.63 2202 6.05 3.81 0.63 2299
28 22 7.01 3.58 0.51 2105 6.77 3.45 0.51 2239 6.60 3.37 0.51 2299 6.33 3.23 0.51 2396
28 24 7.37 2.87 0.39 2202 7.10 2.77 0.39 2323 6.93 2.70 0.39 2396 6.71 2.62 0.39 2517
28 26 7.59 2.05 0.27 2323 7.37 1.99 0.27 2444 7.26 1.96 0.27 2517 7.04 1.90 0.27 2589
29 18 6.46 5.11 0.79 1936 6.19 4.89 0.79 2033 5.94 4.69 0.79 2130 5.72 4.52 0.79 2226
29 20 6.74 4.51 0.67 2033 6.46 4.33 0.67 2154 6.27 4.20 0.67 2202 6.05 4.05 0.67 2299
29 22 7.01 3.86 0.55 2105 6.77 3.72 0.55 2239 6.60 3.63 0.55 2299 6.33 3.48 0.55 2396
29 24 7.37 3.17 0.43 2202 7.10 3.05 0.43 2323 6.93 2.98 0.43 2396 6.71 2.89 0.43 2517
29 26 7.59 2.35 0.31 2323 7.37 2.28 0.31 2444 7.26 2.25 0.31 2517 7.04 2.18 0.31 2589
30 18 6.46 5.36 0.83 1936 6.19 5.14 0.83 2033 5.94 4.93 0.83 2130 5.72 4.75 0.83 2226
30 20 6.74 4.78 0.71 2033 6.46 4.59 0.71 2154 6.27 4.45 0.71 2202 6.05 4.30 0.71 2299
30 22 7.01 4.14 0.59 2105 6.77 3.99 0.59 2239 6.60 3.89 0.59 2299 6.33 3.73 0.59 2396
30 24 7.37 3.46 0.47 2202 7.10 3.33 0.47 2323 6.93 3.26 0.47 2396 6.71 3.15 0.47 2517
30 26 7.59 2.66 0.35 2323 7.37 2.58 0.35 2444 7.26 2.54 0.35 2517 7.04 2.46 0.35 2589
31 18 6.46 5.62 0.87 1936 6.19 5.38 0.87 2033 5.94 5.17 0.87 2130 5.72 4.98 0.87 2226
31 20 6.74 5.05 0.75 2033 6.46 4.85 0.75 2154 6.27 4.70 0.75 2202 6.05 4.54 0.75 2299
31 22 7.01 4.42 0.63 2105 6.77 4.26 0.63 2239 6.60 4.16 0.63 2299 6.33 3.98 0.63 2396
31 24 7.37 3.76 0.51 2202 7.10 3.62 0.51 2323 6.93 3.53 0.51 2396 6.71 3.42 0.51 2517
31 26 7.59 2.96 0.39 2323 7.37 2.87 0.39 2444 7.26 2.83 0.39 2517 7.04 2.75 0.39 2589
32 18 6.46 5.88 0.91 1936 6.19 5.63 0.91 2033 5.94 5.41 0.91 2130 5.72 5.21 0.91 2226
32 20 6.74 5.32 0.79 2033 6.46 5.11 0.79 2154 6.27 4.95 0.79 2202 6.05 4.78 0.79 2299
32 22 7.01 4.70 0.67 2105 6.77 4.53 0.67 2239 6.60 4.42 0.67 2299 6.33 4.24 0.67 2396
32 24 7.37 4.05 0.55 2202 7.10 3.90 0.55 2323 6.93 3.81 0.55 2396 6.71 3.69 0.55 2517
32 26 7.59 3.26 0.43 2323 7.37 3.17 0.43 2444 7.26 3.12 0.43 2517 7.04 3.03 0.43 2589
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
26
OB346E --1qxp 07.2.8 6:53 PM Page 27

PERFORMANCE DATA COOL operation Rated frequency 102Hz


MCFZ-A24WV - E1 : MUZ-A24YV - E1
CAPACITY : 5.5(kW) SHF : 0.65 INPUT : 2420(W)
OUTDOOR DB(:)
INDOOR INDOOR 35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.39 2.53 0.47 2372 4.95 2.33 0.47 2517 4.76 2.24 0.47 2565
21 20 5.67 1.98 0.35 2468 5.28 1.85 0.35 2589 5.09 1.78 0.35 2662
22 18 5.39 2.75 0.51 2372 4.95 2.52 0.51 2517 4.76 2.43 0.51 2565
22 20 5.67 2.21 0.39 2468 5.28 2.06 0.39 2589 5.09 1.98 0.39 2662
22 22 6.00 1.62 0.27 2565 5.61 1.51 0.27 2710 5.42 1.46 0.27 2759
23 18 5.39 2.96 0.55 2372 4.95 2.72 0.55 2517 4.76 2.62 0.55 2565
23 20 5.67 2.44 0.43 2468 5.28 2.27 0.43 2589 5.09 2.19 0.43 2662
23 22 6.00 1.86 0.31 2565 5.61 1.74 0.31 2710 5.42 1.68 0.31 2759
24 18 5.39 3.18 0.59 2372 4.95 2.92 0.59 2517 4.76 2.81 0.59 2565
24 20 5.67 2.66 0.47 2468 5.28 2.48 0.47 2589 5.09 2.39 0.47 2662
24 22 6.00 2.10 0.35 2565 5.61 1.96 0.35 2710 5.42 1.90 0.35 2759
24 24 6.33 1.45 0.23 2662 5.94 1.37 0.23 2783 5.78 1.33 0.23 2844
25 18 5.39 3.40 0.63 2372 4.95 3.12 0.63 2517 4.76 3.00 0.63 2565
25 20 5.67 2.89 0.51 2468 5.28 2.69 0.51 2589 5.09 2.59 0.51 2662
25 22 6.00 2.34 0.39 2565 5.61 2.19 0.39 2710 5.42 2.11 0.39 2759
25 24 6.33 1.71 0.27 2662 5.94 1.60 0.27 2783 5.78 1.56 0.27 2844
26 18 5.39 3.61 0.67 2372 4.95 3.32 0.67 2517 4.76 3.19 0.67 2565
26 20 5.67 3.12 0.55 2468 5.28 2.90 0.55 2589 5.09 2.80 0.55 2662
26 22 6.00 2.58 0.43 2565 5.61 2.41 0.43 2710 5.42 2.33 0.43 2759
26 24 6.33 1.96 0.31 2662 5.94 1.84 0.31 2783 5.78 1.79 0.31 2844
26 26 6.66 1.26 0.19 2759 6.27 1.19 0.19 2880 6.08 1.15 0.19 2940
27 18 5.39 3.83 0.71 2372 4.95 3.51 0.71 2517 4.76 3.38 0.71 2565
27 20 5.67 3.34 0.59 2468 5.28 3.12 0.59 2589 5.09 3.00 0.59 2662
27 22 6.00 2.82 0.47 2565 5.61 2.64 0.47 2710 5.42 2.55 0.47 2759
27 24 6.33 2.21 0.35 2662 5.94 2.08 0.35 2783 5.78 2.02 0.35 2844
27 26 6.66 1.53 0.23 2759 6.27 1.44 0.23 2880 6.08 1.40 0.23 2940
28 18 5.39 4.04 0.75 2372 4.95 3.71 0.75 2517 4.76 3.57 0.75 2565
28 20 5.67 3.57 0.63 2468 5.28 3.33 0.63 2589 5.09 3.21 0.63 2662
28 22 6.00 3.06 0.51 2565 5.61 2.86 0.51 2710 5.42 2.76 0.51 2759
28 24 6.33 2.47 0.39 2662 5.94 2.32 0.39 2783 5.78 2.25 0.39 2844
28 26 6.66 1.80 0.27 2759 6.27 1.69 0.27 2880 6.08 1.64 0.27 2940
29 18 5.39 4.26 0.79 2372 4.95 3.91 0.79 2517 4.76 3.76 0.79 2565
29 20 5.67 3.80 0.67 2468 5.28 3.54 0.67 2589 5.09 3.41 0.67 2662
29 22 6.00 3.30 0.55 2565 5.61 3.09 0.55 2710 5.42 2.98 0.55 2759
29 24 6.33 2.72 0.43 2662 5.94 2.55 0.43 2783 5.78 2.48 0.43 2844
29 26 6.66 2.06 0.31 2759 6.27 1.94 0.31 2880 6.08 1.88 0.31 2940
30 18 5.39 4.47 0.83 2372 4.95 4.11 0.83 2517 4.76 3.95 0.83 2565
30 20 5.67 4.02 0.71 2468 5.28 3.75 0.71 2589 5.09 3.61 0.71 2662
30 22 6.00 3.54 0.59 2565 5.61 3.31 0.59 2710 5.42 3.20 0.59 2759
30 24 6.33 2.97 0.47 2662 5.94 2.79 0.47 2783 5.78 2.71 0.47 2844
30 26 6.66 2.33 0.35 2759 6.27 2.19 0.35 2880 6.08 2.13 0.35 2940
31 18 5.39 4.69 0.87 2372 4.95 4.31 0.87 2517 4.76 4.14 0.87 2565
31 20 5.67 4.25 0.75 2468 5.28 3.96 0.75 2589 5.09 3.82 0.75 2662
31 22 6.00 3.78 0.63 2565 5.61 3.53 0.63 2710 5.42 3.41 0.63 2759
31 24 6.33 3.23 0.51 2662 5.94 3.03 0.51 2783 5.78 2.95 0.51 2844
31 26 6.66 2.60 0.39 2759 6.27 2.45 0.39 2880 6.08 2.37 0.39 2940
32 18 5.39 4.90 0.91 2372 4.95 4.50 0.91 2517 4.76 4.33 0.91 2565
32 20 5.67 4.48 0.79 2468 5.28 4.17 0.79 2589 5.09 4.02 0.79 2662
32 22 6.00 4.02 0.67 2565 5.61 3.76 0.67 2710 5.42 3.63 0.67 2759
32 24 6.33 3.48 0.55 2662 5.94 3.27 0.55 2783 5.78 3.18 0.55 2844
32 26 6.66 2.86 0.43 2759 6.27 2.70 0.43 2880 6.08 2.61 0.43 2940
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
27
OB346E --1qxp 07.2.8 6:53 PM Page 28

PERFORMANCE DATA COOL operation Rated frequency 63Hz


MSZ-A26YV - E1 : MUZ-A26YV - E1
CAPACITY:7.1(kW) SHF:0.63 INPUT:2500(W)
OUTDOOR DB(:)
INDOOR INDOOR 21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 8.34 3.75 0.45 2000 7.99 3.59 0.45 2100 7.67 3.45 0.45 2200 7.38 3.32 0.45 2300
21 20 8.70 2.87 0.33 2100 8.34 2.75 0.33 2225 8.09 2.67 0.33 2275 7.81 2.58 0.33 2375
22 18 8.34 4.09 0.49 2000 7.99 3.91 0.49 2100 7.67 3.76 0.49 2200 7.38 3.62 0.49 2300
22 20 8.70 3.22 0.37 2100 8.34 3.09 0.37 2225 8.09 2.99 0.37 2275 7.81 2.89 0.37 2375
22 22 9.05 2.26 0.25 2175 8.73 2.18 0.25 2313 8.52 2.13 0.25 2375 8.17 2.04 0.25 2475
23 18 8.34 4.42 0.53 2000 7.99 4.23 0.53 2100 7.67 4.06 0.53 2200 7.38 3.91 0.53 2300
23 20 8.70 3.57 0.41 2100 8.34 3.42 0.41 2225 8.09 3.32 0.41 2275 7.81 3.20 0.41 2375
23 22 9.05 2.63 0.29 2175 8.73 2.53 0.29 2313 8.52 2.47 0.29 2375 8.17 2.37 0.29 2475
24 18 8.34 4.76 0.57 2000 7.99 4.55 0.57 2100 7.67 4.37 0.57 2200 7.38 4.21 0.57 2300
24 20 8.70 3.91 0.45 2100 8.34 3.75 0.45 2225 8.09 3.64 0.45 2275 7.81 3.51 0.45 2375
24 22 9.05 2.99 0.33 2175 8.73 2.88 0.33 2313 8.52 2.81 0.33 2375 8.17 2.69 0.33 2475
24 24 9.51 2.00 0.21 2275 9.16 1.92 0.21 2400 8.95 1.88 0.21 2475 8.66 1.82 0.21 2600
25 18 8.34 5.09 0.61 2000 7.99 4.87 0.61 2100 7.67 4.68 0.61 2200 7.38 4.50 0.61 2300
25 20 8.70 4.26 0.49 2100 8.34 4.09 0.49 2225 8.09 3.97 0.49 2275 7.81 3.83 0.49 2375
25 22 9.05 3.35 0.37 2175 8.73 3.23 0.37 2313 8.52 3.15 0.37 2375 8.17 3.02 0.37 2475
25 24 9.51 2.38 0.25 2275 9.16 2.29 0.25 2400 8.95 2.24 0.25 2475 8.66 2.17 0.25 2600
26 18 8.34 5.42 0.65 2000 7.99 5.19 0.65 2100 7.67 4.98 0.65 2200 7.38 4.80 0.65 2300
26 20 8.70 4.61 0.53 2100 8.34 4.42 0.53 2225 8.09 4.29 0.53 2275 7.81 4.14 0.53 2375
26 22 9.05 3.71 0.41 2175 8.73 3.58 0.41 2313 8.52 3.49 0.41 2375 8.17 3.35 0.41 2475
26 24 9.51 2.76 0.29 2275 9.16 2.66 0.29 2400 8.95 2.59 0.29 2475 8.66 2.51 0.29 2600
26 26 9.80 1.67 0.17 2400 9.51 1.62 0.17 2525 9.37 1.59 0.17 2600 9.09 1.54 0.17 2675
27 18 8.34 5.76 0.69 2000 7.99 5.51 0.69 2100 7.67 5.29 0.69 2200 7.38 5.09 0.69 2300
27 20 8.70 4.96 0.57 2100 8.34 4.76 0.57 2225 8.09 4.61 0.57 2275 7.81 4.45 0.57 2375
27 22 9.05 4.07 0.45 2175 8.73 3.93 0.45 2313 8.52 3.83 0.45 2375 8.17 3.67 0.45 2475
27 24 9.51 3.14 0.33 2275 9.16 3.02 0.33 2400 8.95 2.95 0.33 2475 8.66 2.86 0.33 2600
27 26 9.80 2.06 0.21 2400 9.51 2.00 0.21 2525 9.37 1.97 0.21 2600 9.09 1.91 0.21 2675
28 18 8.34 6.09 0.73 2000 7.99 5.83 0.73 2100 7.67 5.60 0.73 2200 7.38 5.39 0.73 2300
28 20 8.70 5.31 0.61 2100 8.34 5.09 0.61 2225 8.09 4.94 0.61 2275 7.81 4.76 0.61 2375
28 22 9.05 4.44 0.49 2175 8.73 4.28 0.49 2313 8.52 4.17 0.49 2375 8.17 4.00 0.49 2475
28 24 9.51 3.52 0.37 2275 9.16 3.39 0.37 2400 8.95 3.31 0.37 2475 8.66 3.20 0.37 2600
28 26 9.80 2.45 0.25 2400 9.51 2.38 0.25 2525 9.37 2.34 0.25 2600 9.09 2.27 0.25 2675
29 18 8.34 6.42 0.77 2000 7.99 6.15 0.77 2100 7.67 5.90 0.77 2200 7.38 5.69 0.77 2300
29 20 8.70 5.65 0.65 2100 8.34 5.42 0.65 2225 8.09 5.26 0.65 2275 7.81 5.08 0.65 2375
29 22 9.05 4.80 0.53 2175 8.73 4.63 0.53 2313 8.52 4.52 0.53 2375 8.17 4.33 0.53 2475
29 24 9.51 3.90 0.41 2275 9.16 3.76 0.41 2400 8.95 3.67 0.41 2475 8.66 3.55 0.41 2600
29 26 9.80 2.84 0.29 2400 9.51 2.76 0.29 2525 9.37 2.72 0.29 2600 9.09 2.64 0.29 2675
30 18 8.34 6.76 0.81 2000 7.99 6.47 0.81 2100 7.67 6.21 0.81 2200 7.38 5.98 0.81 2300
30 20 8.70 6.00 0.69 2100 8.34 5.76 0.69 2225 8.09 5.58 0.69 2275 7.81 5.39 0.69 2375
30 22 9.05 5.16 0.57 2175 8.73 4.98 0.57 2313 8.52 4.86 0.57 2375 8.17 4.65 0.57 2475
30 24 9.51 4.28 0.45 2275 9.16 4.12 0.45 2400 8.95 4.03 0.45 2475 8.66 3.90 0.45 2600
30 26 9.80 3.23 0.33 2400 9.51 3.14 0.33 2525 9.37 3.09 0.33 2600 9.09 3.00 0.33 2675
31 18 8.34 7.09 0.85 2000 7.99 6.79 0.85 2100 7.67 6.52 0.85 2200 7.38 6.28 0.85 2300
31 20 8.70 6.35 0.73 2100 8.34 6.09 0.73 2225 8.09 5.91 0.73 2275 7.81 5.70 0.73 2375
31 22 9.05 5.52 0.61 2175 8.73 5.33 0.61 2313 8.52 5.20 0.61 2375 8.17 4.98 0.61 2475
31 24 9.51 4.66 0.49 2275 9.16 4.49 0.49 2400 8.95 4.38 0.49 2475 8.66 4.24 0.49 2600
31 26 9.80 3.63 0.37 2400 9.51 3.52 0.37 2525 9.37 3.47 0.37 2600 9.09 3.36 0.37 2675
32 18 8.34 7.42 0.89 2000 7.99 7.11 0.89 2100 7.67 6.82 0.89 2200 7.38 6.57 0.89 2300
32 20 8.70 6.70 0.77 2100 8.34 6.42 0.77 2225 8.09 6.23 0.77 2275 7.81 6.01 0.77 2375
32 22 9.05 5.88 0.65 2175 8.73 5.68 0.65 2313 8.52 5.54 0.65 2375 8.17 5.31 0.65 2475
32 24 9.51 5.04 0.53 2275 9.16 4.85 0.53 2400 8.95 4.74 0.53 2475 8.66 4.59 0.53 2600
32 26 9.80 4.02 0.41 2400 9.51 3.90 0.41 2525 9.37 3.84 0.41 2600 9.09 3.73 0.41 2675
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
28
OB346E --1qxp 07.2.8 6:53 PM Page 29

PERFORMANCE DATA COOL operation Rated frequency 63Hz


MSZ-A26YV - E1 : MUZ-A26YV - E1
CAPACITY : 7.1(kW) SHF : 0.63 INPUT : 2500(W)
OUTDOOR DB(:)
INDOOR INDOOR 35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 6.96 3.13 0.45 2450 6.39 2.88 0.45 2600 6.14 2.76 0.45 2650
21 20 7.31 2.41 0.33 2550 6.82 2.25 0.33 2675 6.57 2.17 0.33 2750
22 18 6.96 3.41 0.49 2450 6.39 3.13 0.49 2600 6.14 3.01 0.49 2650
22 20 7.31 2.71 0.37 2550 6.82 2.52 0.37 2675 6.57 2.43 0.37 2750
22 22 7.74 1.93 0.25 2650 7.24 1.81 0.25 2800 6.99 1.75 0.25 2850
23 18 6.96 3.69 0.53 2450 6.39 3.39 0.53 2600 6.14 3.25 0.53 2650
23 20 7.31 3.00 0.41 2550 6.82 2.79 0.41 2675 6.57 2.69 0.41 2750
23 22 7.74 2.24 0.29 2650 7.24 2.10 0.29 2800 6.99 2.03 0.29 2850
24 18 6.96 3.97 0.57 2450 6.39 3.64 0.57 2600 6.14 3.50 0.57 2650
24 20 7.31 3.29 0.45 2550 6.82 3.07 0.45 2675 6.57 2.96 0.45 2750
24 22 7.74 2.55 0.33 2650 7.24 2.39 0.33 2800 6.99 2.31 0.33 2850
24 24 8.17 1.71 0.21 2750 7.67 1.61 0.21 2875 7.46 1.57 0.21 2938
25 18 6.96 4.24 0.61 2450 6.39 3.90 0.61 2600 6.14 3.75 0.61 2650
25 20 7.31 3.58 0.49 2550 6.82 3.34 0.49 2675 6.57 3.22 0.49 2750
25 22 7.74 2.86 0.37 2650 7.24 2.68 0.37 2800 6.99 2.59 0.37 2850
25 24 8.17 2.04 0.25 2750 7.67 1.92 0.25 2875 7.46 1.86 0.25 2938
26 18 6.96 4.52 0.65 2450 6.39 4.15 0.65 2600 6.14 3.99 0.65 2650
26 20 7.31 3.88 0.53 2550 6.82 3.61 0.53 2675 6.57 3.48 0.53 2750
26 22 7.74 3.17 0.41 2650 7.24 2.97 0.41 2800 6.99 2.87 0.41 2850
26 24 8.17 2.37 0.29 2750 7.67 2.22 0.29 2875 7.46 2.16 0.29 2938
26 26 8.59 1.46 0.17 2850 8.09 1.38 0.17 2975 7.85 1.33 0.17 3038
27 18 6.96 4.80 0.69 2450 6.39 4.41 0.69 2600 6.14 4.24 0.69 2650
27 20 7.31 4.17 0.57 2550 6.82 3.89 0.57 2675 6.57 3.74 0.57 2750
27 22 7.74 3.48 0.45 2650 7.24 3.26 0.45 2800 6.99 3.15 0.45 2850
27 24 8.17 2.69 0.33 2750 7.67 2.53 0.33 2875 7.46 2.46 0.33 2938
27 26 8.59 1.80 0.21 2850 8.09 1.70 0.21 2975 7.85 1.65 0.21 3038
28 18 6.96 5.08 0.73 2450 6.39 4.66 0.73 2600 6.14 4.48 0.73 2650
28 20 7.31 4.46 0.61 2550 6.82 4.16 0.61 2675 6.57 4.01 0.61 2750
28 22 7.74 3.79 0.49 2650 7.24 3.55 0.49 2800 6.99 3.43 0.49 2850
28 24 8.17 3.02 0.37 2750 7.67 2.84 0.37 2875 7.46 2.76 0.37 2938
28 26 8.59 2.15 0.25 2850 8.09 2.02 0.25 2975 7.85 1.96 0.25 3038
29 18 6.96 5.36 0.77 2450 6.39 4.92 0.77 2600 6.14 4.73 0.77 2650
29 20 7.31 4.75 0.65 2550 6.82 4.43 0.65 2675 6.57 4.27 0.65 2750
29 22 7.74 4.10 0.53 2650 7.24 3.84 0.53 2800 6.99 3.71 0.53 2850
29 24 8.17 3.35 0.41 2750 7.67 3.14 0.41 2875 7.46 3.06 0.41 2938
29 26 8.59 2.49 0.29 2850 8.09 2.35 0.29 2975 7.85 2.28 0.29 3038
30 18 6.96 5.64 0.81 2450 6.39 5.18 0.81 2600 6.14 4.97 0.81 2650
30 20 7.31 5.05 0.69 2550 6.82 4.70 0.69 2675 6.57 4.53 0.69 2750
30 22 7.74 4.41 0.57 2650 7.24 4.13 0.57 2800 6.99 3.99 0.57 2850
30 24 8.17 3.67 0.45 2750 7.67 3.45 0.45 2875 7.46 3.35 0.45 2938
30 26 8.59 2.84 0.33 2850 8.09 2.67 0.33 2975 7.85 2.59 0.33 3038
31 18 6.96 5.91 0.85 2450 6.39 5.43 0.85 2600 6.14 5.22 0.85 2650
31 20 7.31 5.34 0.73 2550 6.82 4.98 0.73 2675 6.57 4.79 0.73 2750
31 22 7.74 4.72 0.61 2650 7.24 4.42 0.61 2800 6.99 4.27 0.61 2850
31 24 8.17 4.00 0.49 2750 7.67 3.76 0.49 2875 7.46 3.65 0.49 2938
31 26 8.59 3.18 0.37 2850 8.09 2.99 0.37 2975 7.85 2.90 0.37 3038
32 18 6.96 6.19 0.89 2450 6.39 5.69 0.89 2600 6.14 5.47 0.89 2650
32 20 7.31 5.63 0.77 2550 6.82 5.25 0.77 2675 6.57 5.06 0.77 2750
32 22 7.74 5.03 0.65 2650 7.24 4.71 0.65 2800 6.99 4.55 0.65 2850
32 24 8.17 4.33 0.53 2750 7.67 4.06 0.53 2875 7.46 3.95 0.53 2938
32 26 8.59 3.52 0.41 2850 8.09 3.32 0.41 2975 7.85 3.22 0.41 3038
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
29
OB346E --1qxp 07.2.8 6:53 PM Page 30

PERFORMANCE DATA HEAT operation


MSZ-A18YV - E1 : MUZ-A18YV - E1 Rated frequency 82Hz

CAPACITY:5.9(kW) INPUT:1730(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.72 1125 4.48 1349 5.25 1522 6.02 1644 6.79 1747 7.49 1799 8.26 1834
21 3.54 1211 4.25 1436 5.02 1592 5.72 1713 6.49 1799 7.20 1851 7.94 1920
26 3.19 1298 3.95 1522 4.66 1678 5.43 1799 6.20 1886 6.90 1938 7.67 1990

MCFZ-A18WV - E1 : MUZ-A18YV - E1 Rated frequency 86Hz

CAPACITY:6.0(kW) INPUT:2080(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.78 1352 4.56 1622 5.34 1830 6.12 1976 6.90 2101 7.62 2163 8.40 2205
21 3.60 1456 4.32 1726 5.10 1914 5.82 2059 6.60 2163 7.32 2226 8.07 2309
26 3.24 1560 4.02 1830 4.74 2018 5.52 2163 6.30 2267 7.02 2330 7.80 2392

MSZ-A24YV - E1 : MUZ-A24YV - E1 Rated frequency 96Hz

CAPACITY:6.8(kW) INPUT:2050(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 4.28 1333 5.17 1599 6.05 1804 6.94 1948 7.82 2071 8.64 2132 9.52 2173
21 4.08 1435 4.90 1702 5.78 1886 6.60 2030 7.48 2132 8.30 2194 9.15 2276
26 3.67 1538 4.56 1804 5.37 1989 6.26 2132 7.14 2235 7.96 2296 8.84 2358

MCFZ-A24WV - E1 : MUZ-A24YV - E1 Rated frequency 95Hz

CAPACITY:6.4(kW) INPUT:2440(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 4.03 1586 4.86 1903 5.70 2147 6.53 2318 7.36 2464 8.13 2538 8.96 2586
21 3.84 1708 4.61 2025 5.44 2245 6.21 2416 7.04 2538 7.81 2611 8.61 2708
26 3.46 1830 4.29 2147 5.06 2367 5.89 2538 6.72 2660 7.49 2733 8.32 2806

MSZ-A26YV - E1 : MUZ-A26YV - E1 Rated frequency 65Hz


CAPACITY:8.1(kW) INPUT:2650(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 5.10 1723 6.16 2067 7.21 2332 8.26 2518 9.32 2677 10.29 2756 11.34 2809
21 4.86 1855 5.83 2200 6.89 2438 7.86 2624 8.91 2756 9.88 2836 10.89 2942
26 4.37 1988 5.43 2332 6.40 2571 7.45 2756 8.51 2889 7.96 2968 10.53 3048

NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature

30
OB346E --2qxp 07.2.8 6:56 PM Page 31

9 ACTUATOR CONTROL

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds 15 seconds
ON
Compressor

OFF

ON
Outdoor fan

OFF

9-2. R.V. coil control


Heating . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<COOL> <HEAT>
5 seconds 5 seconds

ON
Compressor OFF

R.V.coil ON
OFF
ON
Outdoor fan OFF

9-3. Relation between main sensor and actuator


Relation between main sensor and actuator.

Actuator
Sensor Purpose Outdoor 4-way
Compressor LEV
fan motor valve
Discharge temperature thermistor Protection
Indoor pipe temperature thermistor Defrosting Protection
Defrost thermistor Defrosting
Fin temperature thermistor Protection
Outdoor heat exchanger temperature Protection

31
OB346E --2qxp 07.2.8 6:56 PM Page 32

10 TROUBLESHOOTING

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
10-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

Lead wiring Housing point


3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
4) When troubleshooting, refer to the flow chart on page 33 and the check table on page 34 and 35.

32
OB346E --2qxp 07.2.8 6:56 PM Page 33

10-2. Instruction of troubleshooting


Start

Indoor unit Indoor unit


operates. Indoor unit operates. OPERATION INDICATOR
Outdoor unit doesn't doesn't receive
Outdoor unit lamp on the indoor unit is
operate normally. the signal from
doesn't flashing on and off.
remote controller.
operate.

Outdoor unit Unit doesn't Indoor unit


Indoor unit
Outdoor unit doesn't operate doesn't operate,
operates, when
operates in operate normal when the
the EMERGENCY
only Test Run even in operation in EMERGENCY
OPERATION
operation. Test Run COOL or OPERATION
switch is pressed.
operation. HEAT mode. switch is pressed.

1. Check indoor/ outdoor


Check room connecting wire.
temperature Refer to E Refer to (Check if the power
Refer to C
thermistor. "Check of "Check of is supplied to the
"Check of
Refer to inverter/ remote controller indoor unit.)
R.V. coil"
"Test point compressor" and receiver 2. Refer to
on page 39. "Check of indoor
diagram and on page 40. P.C. board".
voltage". electronic control
P.C. board".

Flash on and 2-time flash MSZ type 4-time flash 5-time flash 6-time flash 7-time flash
off at Cause: 3-time flash Cause: Cause: Cause: Cause:
0.5-second Indoor unit Cause: Indoor unit Outdoor unit Outdoor unit Outdoor unit
intervals Trouble of Indoor unit Trouble of Outdoor Trouble of Trouble of
Cause: room temp- Trouble of indoor unit power thermistor outdoor
Indoor/ erature/
indoor fan control system in outdoor control
Outdoor unit indoor coil
thermistor motor system abnormality unit system
Mis-wiring
or trouble of
serial signal

Refer to B Check room Refer to Replace the Refer to E Refer to F Replace the
"How to temperature "Check of indoor "Check of "Check of outdoor
check thermistor indoor fan electronic inverter/ outdoor electronic
mis-wiring and indoor motor". control compressor" thermistors" control P.C.
and serial coil thermis- P.C. board. on page 40. on page 41. board.
signal error tor.
(When Refer to
outdoor unit "Test point
doesn't diagram and
work)". voltage".

As for indoor unit MSZ type, refer to service manual OB345.


As for indoor unit MCFZ type, refer to service manual OB344.
33
OB346E --2qxp 07.2.8 6:56 PM Page 34

1. Troubleshooting check table


LED 1 (Red) LED 2 (Yellow) Error mode
Lighting Lighting Normal

Symptom: Outdoor unit does not operate.


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
When the compressor operation has been interrupted by overcurrent
protection continuously three times within 1 minute after start-up, or
Lighting Twice Outdoor power system when power factor control module protection or DC control protection is Check the inverter/compressor.
activated three times within 3 minutes after the compressor gets started.

When the nonvolatile memory data cannot be read properly on the Replace the outdoor electronic control
Lighting 7 times Outdoor control system
outdoor electronic control P.C. board. P.C. board.

Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later.
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)

Discharge temperature When a short or open circuit occurs in the discharge temperature Check the characteristic of the discharge
Lighting 3 times temperature thermistor.
thermistor thermistor during compressor operating. Check the connector. (CN661)

Fin temperature When a short or open circuit occurs in the fin temperature thermistor Check the characteristic of the fin
temperature thermistor.
thermistor during compressor operating. Check the connector. (CN3)
Lighting 4 times
P.C. board temperature When a short or open circuit occurs in the P.C. board temperature Replace the outdoor electronic control
thermistor thermistor during compressor operating. P.C. board.
Check the characteristic of the high
Lighting 5 times Outdoor heat exchanger When the outdoor heat exchanger temperature thermistor is short or pressure protect thermistor.
temperature thermistor open while compressor is operating. Check the connector. (CN661)
When the output from compressor current sensor becomes 25A or Check if the connection lead wires of com-
Lighting 6 times Current sensor pressor are correctly connected.
more while the compressor is operating.

Communication error When the communication failure between the outdoor electronic control Check if the connection wires between
Lighting 11 times outdoor electronic control P.C. board and
between P.C. boards P.C. board and power board occurs twice consecutively. power board are correctly connected.

When the zero cross signal cannot be detected while the compressor is Check if the connection wires between
Lighting 12 times Zero cross signal error noise filter P.C. board and power board are
operating. correctly connected.

Check the inverter/ compressor.


Check the amount of gas.
Twice Goes out Overcurrent protection When overcurrent is applied to the power module. Check the indoor/ outdoor air flow for
short cycle.
Check the indoor unit air filter for clogging.

Check the amount of gas and the


3 times Goes out Discharge temperature When the discharge temperature thermistor detects 116: or above. refrigerant cycle.
overheat protection (Protection will be released at 100: or below.) Check the outdoor unit air passage.

Fin temperature Check the outdoor unit air passage.


4 times Goes out When the fin temperature thermistor detects 87: or above. Check the outdoor fan motor.
overheat protection Check the power module.

Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
Check the outdoor unit air passage.
Check the outdoor fan motor.
4 times Goes out P.C. board temperature When the P.C. board temperature thermistor detects 70: or above.
overheat protection Replace the outdoor electronic control
P.C. board.
When the outdoor heat exchanger temperature thermistor detects 69:
5 times Goes out High-pressure protection or more. Check the outdoor unit air passage.
Check the outdoor fan motor.
When high-pressure switch detects 4MPa or more. (MUZ-A26YV)

Power factor control When the overcurrent to power factor controller occurs or the output Check the input voltage.
8 times Goes out module protection voltage from power factor controller becomes 400V or more. Check the inverter.

When it's detected that DC voltage becomes 200V or less, or reaches Check the voltage of power supply.
9 times Goes out DC voltage protection
400V or more. Check the inverter.

Connectivity of indoor Check if the indoor unit can be connected


11 times Goes out When the unusual signal is transmitted from the indoor unit.
and outdoor unit with the outdoor unit.

When the fan motor current is 2A or more, or when the abnormality is Check the outdoor fan motor.
13 times Goes out Fan motor protection
detected in the feedback signal from fan motor. Check the fan motor connector.

34
OB346E --2qxp 07.2.8 6:56 PM Page 35

Symptom: Outdoor unit operates (The compressor operates at reduced frequency)


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
Once Lighting Current protection When the outdoor unit input current exceeds 14.5A.
Twice Lighting High-pressure protection When the indoor gas pipe temperature exceeds 55C during heating.
Twice Lighting Defrosting in cooling When the indoor gas pipe temperature falls to 6C or below during cooling. These symptoms do not mean any
abnormality of the product, but check
3 times Lighting Discharge temperature When the discharge temperature exceeds 104C. the following points.
protection Air filter clogging
Amount of gas
Low discharge When the state with low discharge temperature of which 37C or below
4 times Lighting Short cycle of indoor/outdoor air flow
temperature protection in COOL and 35C or below in HEAT lasts for 20 minutes.
When outdoor heat exchanger temperature thermistor detects 58: or
5 times Lighting High-pressure protection
more.

Symptom: Outdoor unit operates.


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)

When a short or open circuit occurs in the defrost thermistor during Check the characteristic of the defrost
Lighting 5 times Defrost thermistor temperature thermistor.
heating. Check the connector. (CN661)

11 times Lighting Initial-setting When the initial-setting information from an indoor unit is now being read.
9 times Lighting Service mode When the unit operates EMERGENCY OPERATION.

35
OB346E --2qxp 07.2.8 6:56 PM Page 36

2. Trouble criterion of main parts


MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
Part name Check method and criterion
Measure the resistance using a tester.
Defrost thermistor/ (Part temperature : -10C ~ 40C)
Outdoor heat exchanger
temperature thermistor Normal abnormal
5k ~ 55k Open or short-circuit

Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20C ~ 40C)
Discharge temperature
thermistor Normal abnormal
100k ~ 250k Opened or short-circuit

Measure the resistance using a tester.


(Part temperature : 10C ~ 40C)
Fin temperature thermistor
Normal abnormal
25k ~ 100k Open or short-circuit

Compressor Measure the resistance between terminals using a tester.


W (Winding temperature : -10C ~ 40C)
RED

Normal abnormal
V U MUZ-A18/A24YV MUZ-A26YV
WHT BLK Open or short-circuit
0.40 ~ 0.49 1.29 ~ 1.49

Outdoor fan motor Measure the resistance between lead wires using a tester.
(Part temperature : -10C ~ 40C)

RED
U (W)
Color of Normal abnormal
lead wire
WHT
V (V) RED - BLK Open or
BLK short-circuit
W (U) BLK - WHT 13.4 ~ 16.4 (Not including
WHT - RED WHT - ORN)

Measure the resistance using a tester. (Part temperature : -10C ~ 40C)

R. V. coil Normal abnormal


2.6k ~ 3.3k Open or short-circuit

Linear expansion valve Measure the resistance using a tester.(Part temperature : -10C ~ 40C)
WHT Color of lead wire Normal Abnormal
RED LEV WHT - RED
ORN RED - ORN Open or
37.4 ~ 53.9
YLW - BRN short-circuit
BRN - BLU
YLW BRN BLU

MUZ-A26YV
High pressure switch Pressure Normal abnormal
(HPS) Operation OFF Other than
MUZ-A26YV Short
3.7 0.15MPa those list-
HPS1
4.8 +- 0.05
0.1 MPa Open ed at left

36
OB346E --2qxp 07.2.8 6:56 PM Page 37

Outdoor unit does not operate. (LED display: display OFF)

A Check of power supply

Start

Check the connecting of parts of main power supply circuit.

Turn on power supply.

Is there voltage of 230V AC in the No


Check the power supply cable.
power supply terminal block?
Yes
Is the output voltage from the noise No No Replace the noise
Is fuse (F912) blown? filter P.C. board.
filter P.C. board 230V AC?
Yes
Yes Replace the fuse.

Is the input voltage to the power board No Replace the reactor.


230V AC?
Yes
Is the input voltage to the outdoor No
Replace the power board.
electronic control P.C. board 325V DC?

Yes
Replace the outdoor electronic control
P.C. board.

37
OB346E --2qxp 07.2.8 6:56 PM Page 38

When OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second.


Outdoor unit doesnt operate. (LED display: Both LED1 and LED2 lighting)

B How to check mis-wiring and serial signal error (when outdoor unit does not work)

Start

Turn ON the power supply (Indoor/ outdoor unit).


Press once EMERGENCY OPERATION switch.
w Short circuit of JPG and JPS on the indoor
After 3 minutes, mis-wiring is indicated electronic control P.C. board enables
(0.5-second ON, 0.5-second OFF) self-check to be displayed in 3 seconds.
on OPERATION INDICATOR
lamp on the indoor unit.w

Yes Is there any mis-wiring, poor contact,


Correct them.
or wire disconnection? w2
No
A

Turn OFF the power supply (Indoor/ outdoor unit).


Disconnect the indoor/ outdoor connecting wire.
Short-circuit indoor terminal block N and 3. w2 Mis-wiring may damage indoor electronic
Turn ON the power supply (Indoor/ outdoor unit). control P.C. board during the operation.
During pressing the OPERATION SELECT button on Be sure to confirm the wiring is correct
the remote controller, press the RESET button. before the operation starts.
At first, release the RESET button.
And release the OPERATION SELECT button since all
B
LCD in operation display section of the remote controller
C
is displayed after 3 seconds.
CLOCK
AMPM Transmit the signal of remote controller, pressing
AMPM
OPERATE/STOP (ON/OFF) button on the remote
controller.
(The above procedure allows OPERATION INDICATOR
The following indication lamp to indicate the failure-mode.)
applies regardless of shape
of the indicator.
Blinking
No Replace the indoor
Does the right side of OPERATION INDICATOR
electronic control
Operation Indicator lamp blink quickly? (light up or OFF) P.C. board.
Yes

Release the failure mode. w3

Remove the short-circuit between indoor terminal block N


and 3.
Reconnect the indoor/ outdoor connecting wire. Replace the
Turn ON the power supply (Indoor/ outdoor unit). No
indoor/ outdoor
Press the EMERGENCY OPERATION switch. connecting wire.
Is there amplitude of 5 to 10V DC between outdoor
terminal block N and 3 after 3 minutes (for confirmation of w3 Be sure to release the failure-mode
serial signal)? recall function after checking.
Yes Procedure of release of failure-mode.
1 Press the EMERGENCY
Reconnect the
No Is there 230V AC between outdoor terminal OPERATION switch.
power supply
block L and N? 2 Turn OFF the power supply
cable.
(Indoor/ outdoor unit).
Yes 3 Press the RESET button on the
remote controller.
Check of power No Is there 325V DC between CN801 1 and 3 on the A
supply. outdoor electronic control P.C. board? Turn OFF inverter-controlled lighting
equipment.
Yes
Turn OFF the power supply and then
turn ON again (Indoor/ outdoor unit).
Replace the outdoor
Press the EMERGENCY
electronic control P.C.
OPERATION switch.
board.
Reinstall
After 3 minutes, either the
As for indoor unit MSZ type, refer to service manual OB345. is mis-wiring unit or the
As for indoor unit MCFZ type, refer to service manual OB344. indicated on light each
No
OPERATION other away.
INDICATOR Attach a filter
lamp on the on receiving
indoor unit? section of
the indoor
Yes unit.
B

38
OB346E --2qxp 07.2.8 6:56 PM Page 39

The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)

C Check of R.V. coil

When heating operation does not work.

Start

1. Disconnect the lead wire leading to the compressor.


2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in HEAT mode.

Is there voltage of 230V AC between pin1 and No 1. Turn off power supply of indoor and outdoor unit, and
pin 2 at connector CN912? disconnect the connector CN781 in the outdoor electronic
control P.C. board.
Yes
2. 3 minutes after turning on the power supply, start
Turn off power supply of indoor and outdoor unit. EMERGENCY OPERATION in HEAT mode.

Disconnect the connector Is there voltage 12V DC


CN912 in noise filter P. C. No No Replace the electronic
Replace the R.V. coil. between the connector CN781
board. Is there normal control P.C. board.
pin 5 (+) and pin 3 (-)?
resistance to R.V. coil?
Yes
Yes
Replace the noise filter P.C. board.
Replace the 4-way valve.

When cooling operation does not work.

Start

1. Disconnect the lead wire leading to the compressor.


2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in COOL mode.

Is there voltage of 230V AC between pin1 and No


Replace the 4-way valve.
pin 2 at connector CN912?
Yes
1. Turn off power supply of indoor and outdoor unit, and
disconnect the connector CN781 in the outdoor electronic
control P.C. board.
2. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION in COOL mode.

Is there voltage 12V DC


No
between the connector CN781 Replace the noise filter P.C. board.
pin 5 (+) and pin 3 (-)? W
W If the connector CN912 is not connected or R.V. coil is open, voltage
Yes occurs between terminals even when the control is OFF.
Replace the outdoor electronic control P.C. board.

39
OB346E --2qxp 07.2.8 6:56 PM Page 40

When cooling, heat exchanger of non-operating indoor unit is frosted.


When heating, non-operating indoor unit get warm.

D Check of LEV LED display: LED1 LED2


Lighting Lighting
Start 6 time Goes out

Turn on power supply to the outdoor unit after checking LEV coil is mounted to the
LEV body securely.

Is "click - click" sound heard? Yes


Normal
Or, do you feel vibration of the LEV coil with a hand?
No

Disconnect the connector CN795. Yes Replace the outdoor electronic


Is there normal resistance to LEV coil? control P.C. board.
No
Replace the LEV coil.

When OPERATION INDICATOR lamp flashes 5-time.


When heating, room does not get warm.
When cooling, room does not get cool.

E Check of inverter/ compressor LED display: LED1 LED2


Lighting Lighting
Lighting Twice
Start
Twice Goes out

Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION.

W After the outdoor fan starts running, wait for 1 minutes or more before
Measure the voltage between each measuring the voltage.
lead wire leading to the compressor. The output voltage values have the tolerance of i20%.
U (BLK) - V (WHT)
V (WHT) - W (RED) No
W (RED) - U (BLK)
Output voltage
COOL: 150V(48Hz) HEAT: 170V(64Hz)
Is there voltage output? W
Yes
No
Is output balanced?
Yes
Is the input voltage to the outdoor electronic No
control P.C. board 370V or more? Replace the power board.

Yes

Turn off power supply of indoor and outdoor unit,


and measure the compressor winding resistance No
between the compressor terminals.
Is the resistance between each terminal normal?
Replace the
Yes compressor.
Reconnect the lead wire of compressor, and turn on
power supply to indoor and outdoor unit.
3 minutes later, starts EMERGENCY OPERATION.

Clarify the causes by counting time until the inverter stops.


0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
40
OB346E --2qxp 07.2.8 6:56 PM Page 41

When OPERATION INDICATOR lamp flashes 6-time.


When thermistor is abnormal.

F Check of outdoor thermistors

Start

Disconnect the connector in the electronic control P.C. board (see below table), and No
Replace the thermistor.w
measure the resistance of thermistor. Is the thermistor normal?
w When RT65 is abnormal,
Yes
replace the outdoor power
Reconnect the connector of thermistor, disconnect the lead wire leading to the compressor. board.
Turn ON the power supply and press EMERGENCY OPERATION switch.

Does thermistor operate 10 minutes or more though the No Replace the outdoor electronic
thermistor abnormality is not displayed? control P.C. board.
Yes
Normal

Thermistor Symbol Connector, Pin No. Board


Discharge temperature RT61 Between CN661 pin3 and pin4
Defrost RT62 Between CN661 pin1 and pin2 Outdoor electronic control P.C. board
Outdoor heat exchanger temperature RT68 Between CN661 pin7 and pin8
Fin temperature RT65 Between CN3 pin1 and pin2 Outdoor power board

Fan motor does not operate or stops operating shortly after starting the operation.

G Check of outdoor fan motor

Start

Check the connection between the


connector CN931 and CN932.

Is the resistance between each terminal Yes


of outdoor fan motor normal?

Disconnect CN932 from outdoor electronic control P.C. board, and


turn on the power supply.

Rotate the outdoor fan motor manually and measure the voltage of
CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
No
(Fixed to either 5V or 0V DC) Does the voltage between each terminal become 5V DC and 0V DC
repeatedly?
Yes
No
Does the outdoor fan motor rotate smoothly?
Yes
Replace the outdoor DC fan motor. Replace the outdoor electronic control P.C. board.

41
OB346E --2qxp 07.2.8 6:57 PM Page 42

When the operation frequency does not go up from lowest frequency.

H Check of HPS
MUZ-A26YV

Start

1. Disconnect the connector CN681 in the electronic control P.C. board.


2. Check the resistance of HPS after 1 minute have passed since the outdoor unit power supply was turned off.

Check the resistance between Infinity


Replace HPS.
each terminal.
0"
Reconnect CN681.
Turn on power supply to the indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.

Is HPS protection displayed


Yes
immediately after compressor Replace the electronic control P.C. board.
starts?
No

Normal

42
OB346E --2qxp 07.2.8 6:57 PM Page 43

MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1 Defrost temperature thermistor (RT62)


Fin temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
Outdoor electronic control P.C. board 200 100
Discharge temperature thermistor (RT61) 180
90
700 160

Resistance (k')

Resistance (k')
80
600 140
120 70
Resistance (k')

500
100 60
400 80
50

Discharge temperature thermistor (RT61) (

CN661
300 60
40
40
200
20 30
100
0 20

temperature thermistor (RT68) (


Outdoor heat exchanger
0 10 20 30 40 50 60 70 80
0
0 10 20 30 40 50 60 70 80 90 100 110 120 Temperature (;) 10

5V DC pulse wave
(From power board) GND
Signal reception
CN702
Defrost thermistor (RT62) (
Temperature (;)
0

5V DC pulse wave
(To power board)
Signal transmission
CN701

12V
motor
To fan

DC Rush current relay ()


-20 -10 0 10 20 30 40
Temperature (;)

(
pulse wave
12V DC
CN795
GND (power board)

CN781
( pulse wave
5V DC

CN931 GND
20-90V AC
CN932

LEV
R.V. coil ()

(
(
(

(+) (

()
15V
15V
5V

(+)
()
(+)

()
(+)
(
(

LED 1
LED 2
(

CN601
325V DC
~
370V DC
Input

F801
FUSE
3.15A/250V

(+)
CN601

()
( Serial signal

5~10V DC
CN681
MUZ-A26YV
( High pressure switch

43
OB346E --2qxp 07.2.8 6:57 PM Page 44

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
Noise filter P.C. board

CN901
Electronic
control CN902 CN903 230V AC
board Power board 50Hz
Input
{
{
{

CN912
R.V. coil
230V AC {

230V AC
50Hz Output

F911 FUSE F912 FUSE


1A/250V 3.15A/250V
NR63 VARISTOR

44
OB346E --2qxp 07.2.8 6:57 PM Page 45

MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1


Power board

Connect to the compressor


Voltage among phases: 5V to
180V

325-370V DC Connect to the earth


Output
(Red)
(+) 1
CN2
Connect to the controller board
() 3 (+)1-5(): Signal transmission
(White) (To electronic control P.C. board)
5V DC pulse wave
(+)2-5(): Zero cross signal
3-4 : Not used
(+)6-5(): 15V
(+)7-5(): 15V
CN3
Fin temperature thermistor RT64

) Signal reception (From


electronic control P.C. board)
5V DC pulse wave

CN5
Primary current detection
(Connect to the noise filter)

Connect to the compressor


Voltage among phases: 5V to 180V

Connect to the earth

325-370V DC
Output (Red) CN2
Connect to the controller board
(+) 1 (+)1-5(): Signal transmission
(To electronic control P.C. board)
() 3 5V DC pulse wave
(+)2-5(): Zero cross signal
(White) 3-4 : Not used
(+)6-5(): 15V
(+)7-5(): 15V
CN3
Fin temperature thermistor RT64

) Signal reception (From


electronic control P.C. board)
5V DC pulse wave

CN5
Primary current detection
(Connect to the noise filter)

45
OB346E --2qxp 07.2.8 6:57 PM Page 46

11 DISASSEMBLY INSTRUCTIONS

<"Terminal with lock mechanism" Detaching points>


In case of terminal with lock mechanism, detach the terminal as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism.
The terminal with no lock mechanism can be removed by pulling it out.
Check the shape of the terminal and work.

(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
Sleeve

1Slide the sleeve. 1Hold the sleeve, and


2Pull the terminal while pull out the terminal
Locking lever pushing the locking slowly.
lever.
Connector

NOTE :
MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1 These photos are MUZ-A26YV.
OUTDOOR UNIT Other models are almost the same as MUZ-A26YV.

OPERATING PROCEDURE PHOTOS


1. Removing the cabinet Photo 1
(1) Remove the screws of the service panel. Screw of the top panel
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Remove the screws of the cabinet.
(8) Remove the cabinet. Screws
(9) Remove the screws of the back panel. of the
(10) Remove the back panel. cabinet

Screws of the cabinet


Photo 3
Screw of the motor support Photo 2
Screw of the service panel

Screws
of the
top
Screws
panel
of the
back
panel Screws
of the
cabinet

Screw
of the
valve
cover
Set screws of the back panel

46
OB346E --2qxp 07.2.8 6:57 PM Page 47

OPERATING PROCEDURE PHOTOS


2. Removing the inverter assembly, inverter P.C. board Photo 4
and power board Screws of the power board assembly
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel.(Refer to 1.)
(3) Disconnect the following connectors;
<Electronic control P.C. board>
CN931 and CN932 (Fan motor)
CN975 (LEV)
CN661 (Discharge temperature thermistor, defrost
thermistor and outdoor heat exchanger
temperature thermistor)
<Noise filter P.C. board>
CN912 (4-way valve)
(4) Remove the compressor connector.
(5) Remove the screws fixing the relay panel.
(6) Remove the inverter assembly.
(7) Disconnect all connectors and lead wires on the electronic
control P.C. board. Screws of the relay panel
(8) Remove the electronic control P.C. board from the inverter
assembly.
(9) Remove the screws fixing the power board assembly.
(10) Disconnect all connectors and lead wires on the power
board.
(11) Remove the power board from the inverter assembly.
(12) Disconnect all connectors and lead wires on the noise filter
P.C. board.
(13) Remove the noise filter P.C. board from the inverter
assembly.

3. Removing R.V. coil


(1) Remove the top panel, cabinet and service panel.
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the R.V. coil. (Photo 9)

47
OB346E --2qxp 07.2.8 6:57 PM Page 48

OPERATING PROCEDURE PHOTOS


4. Removing the defrost thermistor, discharge temper- Photo 5
ature thermistor and outdoor heat exchanger tem -
perature thermistor Discharge temperature thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its
holder. (Photo 5)
(6) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)

Photo 6
Outdoor heat
exchanger
temperature
thermistor

Defrost
thermistor

5. Removing outdoor fan motor Photo 7


(1) Remove the top panel, cabinet and service panel.
(Refer to 1.) Screws of the outdoor fan motor
Propeller
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.

48
OB346E --2qxp 07.2.8 6:57 PM Page 49

OPERATING PROCEDURE PHOTOS


6. Removing the compressor and 4-way valve Photo 8
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm2 (0 MPa).
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (Photo 9)
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the welded part of 4-way valve and pipe. (Photo 8)

Welded parts of 4-way valve

Photo 9

R.V. coil

Welded part
of the dis-
charge pipe

Welded part
of the suction
pipe

7. Removing the reactor Photo 10


(1) Remove the top panel. (Refer to 1.)
(2) Disconnect the reactor lead wire.
(3) Remove the screws of the reactor, and remove the reactor.

Screws of the reactor

49
OB346E --2qxp 07.2.8 6:57 PM Page 50

12 PARTS LIST

MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1


12-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND
FUNCTIONAL PARTS

26

30 29 28 27

25

1 24

23
2
22
3
21
4

6
20
7 18
17
8 16

15
14
19

9 10 11 12 13
These figures show about MUZ-A26YV.

50
OB346E --2qxp 07.2.8 6:57 PM Page 51

MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1


12-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND
FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.

Symbol Q'ty/unit
No. Part No. Part Name in Wiring MUZ-A18 MUZ-A24 MUZ-A26 Remarks
Diagram YV - E1 YV - E1 YV - E1
1 E02 819 297 TOP PANEL 1 1 1
E02 851 630 OUTDOOR HEAT EXCHANGER 1 1
2
E02 853 630 OUTDOOR HEAT EXCHANGER 1
3 E02 851 301 OUTDOOR FAN MOTOR MF 1 1 1 PM8H60-
4 E02 851 501 PROPELLER 1 1 1
E02 851 290 BASE 1 1
5
E02 853 290 BASE 1
6 E02 819 232 CABINET 1 1 1
7 E02 819 009 HANDLE 1 1 1
8 E02 819 521 FAN GUARD 1 1 1
9 E02 853 646 HIGH PRESSURE SWITCH HPS 1
E02 065 506 COMPRESSOR RUBBER SET 3 3 3RUBBERS/SET
10
E02 853 506 COMPRESSOR RUBBER SET 3 3RUBBERS/SET
E02 939 900 COMPRESSOR MC 1 1 SNB130FLDH1
11
E02 853 900 COMPRESSOR MC 1 TNB220FMCH
E02 851 661 STOP VALVE(GAS) 1 {12.7
12
E02 819 661 STOP VALVE(GAS) 1 1 {15.88
E02 821 662 STOP VALVE(LIQUID) 1 1 {6.35
13
E02 822 662 STOP VALVE(LIQUID) 1 {9.52
E02 851 640 EXPANSION VALVE 1 1
14
E02 853 640 EXPANSION VALVE 1
15 E02 851 493 EXPANSION VALVE COIL LEV 1 1 1
16 E02 853 299 OIL SEPARATOR 1
17 E02 851 490 R.V. COIL 21S4 1 1 1
18 E02 891 961 4-WAY VALVE 1 1 1
19 E02 819 650 VALVE COVER 1 1 1
20 E02 819 245 SERVICE PANEL 1 1 1
E02 851 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
21 E02 852 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
E02 853 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
22 E02 836 374 TERMINAL BLOCK TB2 1 1 1 2P
23 E02 823 375 TERMINAL BLOCK TB1 1 1 1 3P
24 E02 851 337 REACTOR L 1 1 1
25 E02 851 444 NOISE FILTER P.C. BOARD 1 1 1
DISCHARGE, DEFROST
26 E02 851 308 THERMISTOR SET RT61,RT62,RT68 1 1 1 OUTDOOR HEAT EXCHANGER

27 E02 851 440 POWER BOARD 1 1 1 Including heat sink and RT65
28 E02 819 233 BACK PANEL(OUT) 1 1 1
29 E02 817 009 HANDLE 1 1 1
30 E02 851 515 MOTOR SUPPORT 1 1 1
31 E02 127 382 FUSE F801 1 1 1 250V/3.15A
32 E02 737 382 FUSE F911 1 1 1 250V/1A
33 E02 735 385 FUSE & VARISTOR F912,NR63 1 1 1 250V/3.15A
E02 851 936 CAPILLARY TUBE(TAPER PIPE) 1 1 {3.6x{2.4x50
34 E02 853 936 CAPILLARY TUBE(TAPER PIPE) 1 {3.6x{2.4x50
E02 861 936 CAPILLARY TUBE 1 {1.8x{0.6x1000

51
OB346E --2qxp 07.2.8 6:57 PM Page 52

MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
12-2. ACCESSORY 1 2

Symbol Q'ty/unit
No. Part No. Part Name in Wiring MUZ-A18 MUZ-A24 MUZ-A26 Remarks
Diagram YV - E1 YV - E1 YV - E1
1 E02 817 704 DRAIN SOCKET 1 1 1
2 E02 444 705 DRAIN CAP 2 2 2 [33

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

C Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD


Distributed in Feb. 2007. No. OB346 REVISED EDITION - E 6
Distributed in Aug. 2006. No. OB346 REVISED EDITION - D 6
Distributed in May 2006. No. OB346 REVISED EDITION - C 6
Distributed in Jul. 2005. No. OB346 REVISED EDITION - B 6
Distributed in Jun. 2004. No. OB346 REVISED EDITION - A 6 New publication, effective Feb. 2007
Distributed in Apr. 2004. No. OB346 6 Specifications subject to change without notice.
Made in Japan

You might also like