Muz A18 26yv (OB346E)
Muz A18 26yv (OB346E)
Muz A18 26yv (OB346E)
8 6:53 PM Page 1
Revision E:
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Check of outdoor thermistors has been corrected.
No. OB346
HFC REVISED EDITION-E
utilized
Wireless type
Models
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
CONTENTS
1. TECHNICAL CHANGES 3
2. PART NAMES AND FUNCTIONS6
Indication of
3. SPECIFICATION7
model name 4. NOISE CRITERIA CURVES 10
MUZ-A18YV - E1 5. OUTLINES AND DIMENSIONS11
MUZ-A24YV - E1 6. WIRING DIAGRAM 12
MUZ-A26YV - E1
7. REFRIGERANT SYSTEM DIAGRAM 14
8. PERFORMANCE CURVES 16
9. ACTUATOR CONTROL31
10. TROUBLESHOOTING32
11. DISASSEMBLY INSTRUCTIONS46
12. PARTS LIST50
NOTE:
This service manual describes technical data of the outdoor units.
As for indoor units MSZ-A18YV - E1 , MSZ-A24YV - E1 and MSZ-A26YV - E1 , refer to the
service manual OB345.
As for indoor units MCFZ-A18WV - E1 and MCFZ-A24WV - E1 , refer to the service manual
OB344.
OB346E --1qxp 07.2.8 6:53 PM Page 2
Revision A:
Revision B:
Part number of 4-WAY VALVE has been corrected.
Part Number
Model Revise point Part Name
Incorrect Correct
MUZ-A18YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961
MUZ-A24YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961
MUZ-A26YV - E1 12-1. No.18 4-WAY VALVE E02 679 961 E02 891 961
Revision C:
Revision D:
Compressor has been changed. (MUZ-A18/24YV)
Revision E:
Check of outdoor thermistors of 10. TROUBLESHOOTING has been corrected.
2
OB346E --1qxp 07.2.8 6:53 PM Page 3
1 TECHNICAL CHANGES
Suction muffler
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
3
OB346E --1qxp 07.2.8 6:53 PM Page 4
3.5
R410A
Saturated liquid pressure
3.0 R22
2.5
2.0
1.5 NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
1.0
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
0.5
0.0
-0.5
-30 -20 -10 0 10 20 30 40 50 60 (:)
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88).
Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is
insufficient.
4
OB346E --1qxp 07.2.8 6:53 PM Page 5
mm R410A R22
6.35 17 17
9.52 22 22
12.7 26 24
15.88 29 27
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, capacity of the refrigerating cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Liquid pipe
Gas pipe Outdoor unit
Refrigerant gas
cylinder
operating valve Service port
Gauge manifold
valve (for R410A)
Charge hose (for R410A)
Refrigerant (liquid)
Electronic scale for refrigerant charging
5
OB346E --1qxp 07.2.8 6:53 PM Page 6
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
OUTDOOR UNIT
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
1 Drain socket 1
2 Drain cap [33 2
6
OB346E --1qxp 07.2.8 6:53 PM Page 7
3 SPECIFICATION
MUZ-A18YV - E1 MUZ-A18YV - E1
Outdoor model Indoor model Indoor model
MSZ-A18YV - E1 MCFZ-A18WV - E1
Function Cooling Heating Cooling Heating
Single phase Single phase
Power supply
230V,50Hz 230V,50Hz
Capacity
"
resistance(at 20:) WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2
Dimensions WOHOD mm 840o850o330 840o850o330
Weight kg 53 53
Sound level(High/LowW) dB 53/51W 55/53W 53/51W 55/53W
Fan speed(High/LowW) rpm 800/480W 800/620W 800/480W 800/620W
Fan speed regulator 2 2
Refrigerant filling
remarks
kg 1.8 1.8
Special
capacity(R410A)
Refrigeration oil(Model) NEO22 NEO22
Thermistor RT61(at 100:) k" 13.4 13.4
Thermistor RT62(at 25:) k" 10.0 10.0
Thermistor RT65(at 50:) k" 17.0 17.0
Thermistor RT68(at 25:) k" 10.0 10.0
NOTE : Test conditions are based on ISO 5151.
Cooling : Indoor DB 27: WB 19:
Outdoor DB 35: WB (24:)
Heating : Indoor DB 20: WB 15:
Outdoor DB 7: WB 6:
Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
w Reference value
7
OB346E --1qxp 07.2.8 6:53 PM Page 8
"
resistance(at 20:) WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2
Dimensions WOHOD mm 840o850o330 840o850o330 840o850o330
Weight kg 53 53 58
Sound level(High/LowW) dB 53/51 W 55/53W 53/51 W 55/53 W 53/51 W 55/53W
Fan speed(High/LowW) rpm 800/480 W 800/620W 800/480 W 800/620 W 800/480 W 800/620W
Fan speed regulator 2 2 2
Refrigerant filling
remarks
capacity(R410A)
Refrigeration oil(Model) NEO22 NEO22 NEO22
Thermistor RT61(at 100:) k" 13.4 13.4 13.4
Thermistor RT62(at 25:) k" 10.0 10.0 10.0
Thermistor RT65(at 50:) k" 17.0 17.0 17.0
Thermistor RT68(at 25:) k" 10.0 10.0 10.0
NOTE : Test conditions are based on ISO 5151.
Cooling : Indoor DB 27: WB 19:
Outdoor DB 35: WB (24:)
Heating : Indoor DB 20: WB 15:
Outdoor DB 7: WB 6:
Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
w Reference value
8
OB346E --1qxp 07.2.8 6:53 PM Page 9
OUTDOOR UNIT
Model
Item MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1
9
OB346E --1qxp 07.2.8 6:53 PM Page 10
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
SPEED FUNCTION SPL(dB(A)) LINE
COOLING 53
High
HEATING 55
Test conditions,
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
80
70
NC-70 OUTDOOR UNIT
60
1m
NC-60
MICROPHONE
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
10
OB346E --1qxp 07.2.8 6:53 PM Page 11
MUZ-A18YV - E1 Unit: mm
MUZ-A24YV - E1
MUZ-A26YV - E1
OUTDOOR UNIT
REQUIRED SPACE
Open as a rule
500mm or more if
515 the front and both
299 sides are open
66 40
100mm or more
51
34
200mm or more if
100mm or more there are obstacles
to both sides
330
360
500
840 80 Open as a rule
121 500mm or more if the back, 350mm or more
both sides and top are open
Service panel
Liquid refrigerant
pipe joint
850
Refrigerant pipe
(flared) [6.35 (MUZ-A18/A24YV)
[9.52 (MUZ-A26YV)
430
30-
35-
155
90
Gas refrigerant
pipe joint
Refrigerant pipe
198 (flared) [12.7 (MUZ-A18YV)
[15.88 (MUZ-A24/A26YV)
11
6
TAB1 L
PFC
CT2 W
POWER SUPPLY 2 1 R RED
OB346E --1qxp
F912
BREAKER R64
BRN
NF TAB4
CB1
CB2
CB3
TB1 3 4 YLW W
YLW V
L NR63 BLK V
MUZ-A24YV - E1
MUZ-A18YV - E1
BLU IPM MC
BLK OUTDOOR UNIT
2 1
N
CN5
PE TAB2 CT61 U
07.2.8 6:53 PM
WHT
BLK RS1 RS3 CT1 U
2 1 2 1
F911
BLK
SSR61
CN902 CN903
GRN/YLW
CN912 CN901 RS2 RS4
Page 12
CN2
LDE1
LDE2
1 3 1 2 3 5
1 2
CN3
CN4
RT65
7 6 5 4 3 2 1
NOISE FILTER 1 2 LD2 LD1 LD9 POWER
BLU
BLU
BOARD
WIRING DIAGRAM
P.C. BOARD
GRN
GRN
21S4
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
GRN
WHT
RED
ELECTRONIC GRY
1 2 3 5 1 5 6 7 1 2 1 3
12
CONTROL PNK
P.C. BOARD CN781 CN702 CN701
CN801
1
TO INDOOR 3 BLU
CN931
UNIT CN661
CONNECTING
F801
BLU YLW MF
3
1 2 3 4 5
CN601
12V 1 2 3 4 7 8 CN795
N T801 RED
R934A
MODELS WIRING DIAGRAM
6 WHT
BLK
HC932
1 2 3
LEV
RT62 RT61 RT68 R934B CN932
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT65 FIN TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR (INNER FUSE) diagram for servicing.
RT68 OUTDOOR HEAT EXCHANGER
CT61 CURRENT TRANSFORMER NF NOISE FILTER TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F801 FUSE (250V 3.15A) NR63 VARISTOR SSR61 SOLENOID COIL RELAY 3.Symbols below indicate.
F911 FUSE (250V 1A) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER :Terminal block :Connector
F912 FUSE (250V 3.15A) R64 RESISTOR TB1 TERMINAL BLOCK
HC932 FET ARRAY R934A, B RESISTOR TB2 TERMINAL BLOCK
IPM POWER TRANSISTOR MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT61 DISCHARGE TEMPERATURE THERMISTOR 21S4 R.V. COIL
LEV EXPANSION VALVE COIL RT62 DEFROST THERMISTOR
OB346E --1qxp
TAB1 L
PFC
CT2 W
POWER SUPPLY 2 1 R RED
~/N 230V 50Hz X64 4
CIRCUIT
RED RED S
F912
BREAKER R64
BRN
NF TAB4
CB1
CB2
CB3
TB1 3 4 YLW W
YLW V
L NR63 BLK V
BLU IPM
07.2.8 6:53 PM
MC
MUZ-A26YV - E1
BLK
OUTDOOR UNIT
2 1
N
CN5
PE TAB2 CT61 U
WHT
BLK RS1 RS3
2 1 2 1
CT1 U
F911
BLK
Page 13
SSR61
CN902 CN903
GRN/YLW
CN912 CN901 RS2 RS4
CN2
LDE1
LDE2
1 3 1 2 3 5
1 2
CN3
CN4
RT65
7 6 5 4 3 2 1
NOISE FILTER 1 2 LD2 LD1 LD9 POWER
BLU
BLU
P.C. BOARD BOARD
GRN
GRN
21S4
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
GRN
WHT
13
PNK
P.C. BOARD CN781 CN702 CN701
CN801
1
TO INDOOR 3 BLU
CN931
3
1 2 3 4 5
CN601
12V 1 2 1 2 3 4 7 8 CN795
N T801 RED
R934A
MODEL WIRING DIAGRAM
RED 6 WHT
BLK
HC932
1 2 3
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR OUTDOOR HEAT EXCHANGER refer to the indoor unit electric wiring
RT68 TEMPERATURE THERMISTOR
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR (INNER FUSE) diagram for servicing.
CT61 CURRENT TRANSFORMER NF NOISE FILTER SSR61 SOLENOID COIL RELAY 2.Use copper conductors only (for field wiring).
F801 FUSE (250V 3.15A) NR63 VARISTOR T801 TRANSFORMER 3.Symbols below indicate.
F911 FUSE (250V 1A) PFC POWER FACTOR CONTROLLER TB1 TERMINAL BLOCK :Terminal block :Connector
F912 FUSE (250V 3.15A) R64 RESISTOR TB2 TERMINAL BLOCK
HC932 FET ARRAY R934A, B RESISTOR X64 RELAY
HPS HIGH PRESSURE SWITCH RS1~4 RESISTOR 21S4 R.V. COIL
IPM POWER TRANSISTOR MODULE RT61 DISCHARGE TEMPERATURE THERMISTOR
L REACTOR RT62 DEFROST THERMISTOR
LEV EXPANSION VALVE COIL RT65 FIN TEMPERATURE THERMISTOR
OB346E --1qxp 07.2.8 6:53 PM Page 14
MUZ-A18YV - E1 Unit:mm
MUZ-A24YV - E1
OUTDOOR UNIT
Refrigerant pipe [12.7 (MUZ-A18YV) Muffler
(with heat insulator) [15.88 (MUZ-A24YV) 4-way valve #100
Stop valve
(with service port) Outdoor
Flared connection Discharge heat
temperature exchanger
thermistor Defrost
RT61 thermistor
RT62
Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
Strainer LEV
Strainer
Receiver #100 #100 R.V. coil
heating ON
cooling OFF
Stop valve Capillary tube
[3.6[2.450
Refrigerant pipe [6.35 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
MUZ-A26YV - E1 Unit:mm
Capillary tube
OUTDOOR UNIT [1.8[0.61000
Refrigerant pipe [15.88 Oil separator High-pressure
(with heat insulator) 4-way valve switch
Stop valve
(with service port) Outdoor
Flared connection Strainer Defrost heat
#100 thermistor exchanger
RT62
Discharge
temperature
thermistor
RT61
Compressor
Outdoor
heat
exchanger
temperature
thermistor
RT68
Flared connection
LEV
Strainer Strainer
Receiver #100 #100 R.V. coil
heating ON
cooling OFF
Stop valve Capillary tube
[3.6[2.450
Refrigerant pipe [9.52 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
14
OB346E --1qxp 07.2.8 6:53 PM Page 15
MUZ-A18YV - E1 12.7
6.35 Gas 0.43 Gas 0
MUZ-A24YV - E1 30 Liquid 0.5 Liquid 0
15.88
MUZ-A26YV - E1 9.52
Indoor
unit
w Max. Height
difference 15m
Refrigerant Piping
Max. length
A
Outdoor unit
w Height difference should be within 15m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Refrigerant piping length (one way)
Outdoor unit
Model precharged 7m 10m 15m 20m 25m 30m
15
OB346E --1qxp 07.2.8 6:53 PM Page 16
8 PERFORMANCE CURVES
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
207 ~ 253V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : C WB
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
(4) Total input :
(5) Indoor intake air dry-bulb temperature :
C WB
C DB
W
C DB
Cooling
}
(6) Outdoor intake air wet-bulb temperature :
(7) Total input :
C WB
W
Heating }
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the differ-
ence between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your
reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MCFZ-A24WV - E1
Rated frequency 73Hz
Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:)
MUZ-A18YV - E1
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
MSZ-A18YV - E1
MSZ-A24YV - E1
MSZ-A26YV - E1
16
OB346E --1qxp 07.2.8 6:53 PM Page 17
MCFZ-A24WV - E1
Rated frequency 82Hz
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
MSZ-A18YV - E1
MSZ-A24YV - E1
MSZ-A26YV - E1
Outdoor intake air Wet-bulb temperature (:) Outdoor intake air Wet-bulb temperature (:)
NOTE:The above curves are for the heating operation without any frost.
0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
17
OB346E --1qxp 07.2.8 6:53 PM Page 18
0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
14 1.4 14 1.4
Outdoor low pressure
Outdoor low pressure
10 1.0 2 10 1.0 2
8 0.8 8 0.8
1.5 1.5
6 0.6 6 0.6
4 0.4 1 4 0.4 1
18 20 25 15
30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)
18
OB346E --1qxp 07.2.8 6:53 PM Page 19
14 1.4 14 1.4
10 1.0 3 10 1.0 3
8 0.8 8 0.8
2 2
6 0.6 6 0.6
4 0.4 1 4 0.4 1
15
18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)
MUZ-A26YV - E1 MUZ-A26YV - E1
14 1.4
Outdoor low pressure
24Hz
24Hz 4
12 1.2
10 1.0 3.5
8 0.8
3
6 0.6
4 0.4 2.5
15
18 20 25 30 32 35(C) 15 18 20 25 30 32 35(C)
50 60 70 (%) 50 60 70 (%)
Ambient temperature(C) Ambient humidity(%) Ambient temperature(C) Ambient humidity(%)
HEAT operation
Condition indoor: Dry bulb temperature 20.0C
Wet bulb temperature 14.5C Operational frequency : 32Hz(MUZ-A18YV)
Condition outdoor: Dry bulb temperature 2,7,15,20.0C 32Hz(MUZ-A24YV)
Wet bulb temperature 1,6,12,14.5C 32Hz(MUZ-A26YV)
MUZ-A18YV - E1 MUZ-A18YV - E1
Indoor unit :
4.0
(MSZ-A18YV - E1 ) ( Indoor unit :
MCFZ-A18WV - E1 )
4.0
3.5 3.5
Outdoor unit current (A)
3.0 3.0
32Hz 32Hz
2.5 2.5
2.0 2.0
1.5 1.5
1.0 1.0
2 5 10 15 20 25(:) 2 5 10 15 20 25(:)
Ambient temperature(C) Ambient temperature(C)
MUZ-A24YV - E1 MUZ-A24YV - E1
Indoor unit :
(MSZ-A24YV - E1 ) ( Indoor unit :
MCFZ-A24WV - E1 ) MUZ-A26YV - E1
4.0 4.0 6
32Hz
3.5 3.5 5.5
Outdoor unit current (A)
3.0 3.0 5
32Hz 32Hz
2.5 2.5 4.5
19
OB346E --1qxp 07.2.8 6:53 PM Page 20
CAPACITY:5.9(kW) INPUT:1730(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.72 1125 4.48 1349 5.25 1522 6.02 1644 6.79 1747 7.49 1799 8.26 1834
21 3.54 1211 4.25 1436 5.02 1592 5.72 1713 6.49 1799 7.20 1851 7.94 1920
26 3.19 1298 3.95 1522 4.66 1678 5.43 1799 6.20 1886 6.90 1938 7.67 1990
CAPACITY:6.0(kW) INPUT:2080(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.78 1352 4.56 1622 5.34 1830 6.12 1976 6.90 2101 7.62 2163 8.40 2205
21 3.60 1456 4.32 1726 5.10 1914 5.82 2059 6.60 2163 7.32 2226 8.07 2309
26 3.24 1560 4.02 1830 4.74 2018 5.52 2163 6.30 2267 7.02 2330 7.80 2392
CAPACITY:6.8(kW) INPUT:2050(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 4.28 1333 5.17 1599 6.05 1804 6.94 1948 7.82 2071 8.64 2132 9.52 2173
21 4.08 1435 4.90 1702 5.78 1886 6.60 2030 7.48 2132 8.30 2194 9.15 2276
26 3.67 1538 4.56 1804 5.37 1989 6.26 2132 7.14 2235 7.96 2296 8.84 2358
CAPACITY:6.4(kW) INPUT:2440(W)
OUTDOOR WB(:)
INDOOR -10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 4.03 1586 4.86 1903 5.70 2147 6.53 2318 7.36 2464 8.13 2538 8.96 2586
21 3.84 1708 4.61 2025 5.44 2245 6.21 2416 7.04 2538 7.81 2611 8.61 2708
26 3.46 1830 4.29 2147 5.06 2367 5.89 2538 6.72 2660 7.49 2733 8.32 2806
NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
30
OB346E --2qxp 07.2.8 6:56 PM Page 31
9 ACTUATOR CONTROL
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan
OFF
<COOL> <HEAT>
5 seconds 5 seconds
ON
Compressor OFF
R.V.coil ON
OFF
ON
Outdoor fan OFF
Actuator
Sensor Purpose Outdoor 4-way
Compressor LEV
fan motor valve
Discharge temperature thermistor Protection
Indoor pipe temperature thermistor Defrosting Protection
Defrost thermistor Defrosting
Fin temperature thermistor Protection
Outdoor heat exchanger temperature Protection
31
OB346E --2qxp 07.2.8 6:56 PM Page 32
10 TROUBLESHOOTING
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
10-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
32
OB346E --2qxp 07.2.8 6:56 PM Page 33
Flash on and 2-time flash MSZ type 4-time flash 5-time flash 6-time flash 7-time flash
off at Cause: 3-time flash Cause: Cause: Cause: Cause:
0.5-second Indoor unit Cause: Indoor unit Outdoor unit Outdoor unit Outdoor unit
intervals Trouble of Indoor unit Trouble of Outdoor Trouble of Trouble of
Cause: room temp- Trouble of indoor unit power thermistor outdoor
Indoor/ erature/
indoor fan control system in outdoor control
Outdoor unit indoor coil
thermistor motor system abnormality unit system
Mis-wiring
or trouble of
serial signal
Refer to B Check room Refer to Replace the Refer to E Refer to F Replace the
"How to temperature "Check of indoor "Check of "Check of outdoor
check thermistor indoor fan electronic inverter/ outdoor electronic
mis-wiring and indoor motor". control compressor" thermistors" control P.C.
and serial coil thermis- P.C. board. on page 40. on page 41. board.
signal error tor.
(When Refer to
outdoor unit "Test point
doesn't diagram and
work)". voltage".
When the nonvolatile memory data cannot be read properly on the Replace the outdoor electronic control
Lighting 7 times Outdoor control system
outdoor electronic control P.C. board. P.C. board.
Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later.
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
Discharge temperature When a short or open circuit occurs in the discharge temperature Check the characteristic of the discharge
Lighting 3 times temperature thermistor.
thermistor thermistor during compressor operating. Check the connector. (CN661)
Fin temperature When a short or open circuit occurs in the fin temperature thermistor Check the characteristic of the fin
temperature thermistor.
thermistor during compressor operating. Check the connector. (CN3)
Lighting 4 times
P.C. board temperature When a short or open circuit occurs in the P.C. board temperature Replace the outdoor electronic control
thermistor thermistor during compressor operating. P.C. board.
Check the characteristic of the high
Lighting 5 times Outdoor heat exchanger When the outdoor heat exchanger temperature thermistor is short or pressure protect thermistor.
temperature thermistor open while compressor is operating. Check the connector. (CN661)
When the output from compressor current sensor becomes 25A or Check if the connection lead wires of com-
Lighting 6 times Current sensor pressor are correctly connected.
more while the compressor is operating.
Communication error When the communication failure between the outdoor electronic control Check if the connection wires between
Lighting 11 times outdoor electronic control P.C. board and
between P.C. boards P.C. board and power board occurs twice consecutively. power board are correctly connected.
When the zero cross signal cannot be detected while the compressor is Check if the connection wires between
Lighting 12 times Zero cross signal error noise filter P.C. board and power board are
operating. correctly connected.
Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
Check the outdoor unit air passage.
Check the outdoor fan motor.
4 times Goes out P.C. board temperature When the P.C. board temperature thermistor detects 70: or above.
overheat protection Replace the outdoor electronic control
P.C. board.
When the outdoor heat exchanger temperature thermistor detects 69:
5 times Goes out High-pressure protection or more. Check the outdoor unit air passage.
Check the outdoor fan motor.
When high-pressure switch detects 4MPa or more. (MUZ-A26YV)
Power factor control When the overcurrent to power factor controller occurs or the output Check the input voltage.
8 times Goes out module protection voltage from power factor controller becomes 400V or more. Check the inverter.
When it's detected that DC voltage becomes 200V or less, or reaches Check the voltage of power supply.
9 times Goes out DC voltage protection
400V or more. Check the inverter.
When the fan motor current is 2A or more, or when the abnormality is Check the outdoor fan motor.
13 times Goes out Fan motor protection
detected in the feedback signal from fan motor. Check the fan motor connector.
34
OB346E --2qxp 07.2.8 6:56 PM Page 35
When a short or open circuit occurs in the defrost thermistor during Check the characteristic of the defrost
Lighting 5 times Defrost thermistor temperature thermistor.
heating. Check the connector. (CN661)
11 times Lighting Initial-setting When the initial-setting information from an indoor unit is now being read.
9 times Lighting Service mode When the unit operates EMERGENCY OPERATION.
35
OB346E --2qxp 07.2.8 6:56 PM Page 36
Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20C ~ 40C)
Discharge temperature
thermistor Normal abnormal
100k ~ 250k Opened or short-circuit
Normal abnormal
V U MUZ-A18/A24YV MUZ-A26YV
WHT BLK Open or short-circuit
0.40 ~ 0.49 1.29 ~ 1.49
Outdoor fan motor Measure the resistance between lead wires using a tester.
(Part temperature : -10C ~ 40C)
RED
U (W)
Color of Normal abnormal
lead wire
WHT
V (V) RED - BLK Open or
BLK short-circuit
W (U) BLK - WHT 13.4 ~ 16.4 (Not including
WHT - RED WHT - ORN)
Linear expansion valve Measure the resistance using a tester.(Part temperature : -10C ~ 40C)
WHT Color of lead wire Normal Abnormal
RED LEV WHT - RED
ORN RED - ORN Open or
37.4 ~ 53.9
YLW - BRN short-circuit
BRN - BLU
YLW BRN BLU
MUZ-A26YV
High pressure switch Pressure Normal abnormal
(HPS) Operation OFF Other than
MUZ-A26YV Short
3.7 0.15MPa those list-
HPS1
4.8 +- 0.05
0.1 MPa Open ed at left
36
OB346E --2qxp 07.2.8 6:56 PM Page 37
Start
Yes
Replace the outdoor electronic control
P.C. board.
37
OB346E --2qxp 07.2.8 6:56 PM Page 38
B How to check mis-wiring and serial signal error (when outdoor unit does not work)
Start
38
OB346E --2qxp 07.2.8 6:56 PM Page 39
The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)
Start
Is there voltage of 230V AC between pin1 and No 1. Turn off power supply of indoor and outdoor unit, and
pin 2 at connector CN912? disconnect the connector CN781 in the outdoor electronic
control P.C. board.
Yes
2. 3 minutes after turning on the power supply, start
Turn off power supply of indoor and outdoor unit. EMERGENCY OPERATION in HEAT mode.
Start
39
OB346E --2qxp 07.2.8 6:56 PM Page 40
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the
LEV body securely.
Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION.
W After the outdoor fan starts running, wait for 1 minutes or more before
Measure the voltage between each measuring the voltage.
lead wire leading to the compressor. The output voltage values have the tolerance of i20%.
U (BLK) - V (WHT)
V (WHT) - W (RED) No
W (RED) - U (BLK)
Output voltage
COOL: 150V(48Hz) HEAT: 170V(64Hz)
Is there voltage output? W
Yes
No
Is output balanced?
Yes
Is the input voltage to the outdoor electronic No
control P.C. board 370V or more? Replace the power board.
Yes
Start
Disconnect the connector in the electronic control P.C. board (see below table), and No
Replace the thermistor.w
measure the resistance of thermistor. Is the thermistor normal?
w When RT65 is abnormal,
Yes
replace the outdoor power
Reconnect the connector of thermistor, disconnect the lead wire leading to the compressor. board.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does thermistor operate 10 minutes or more though the No Replace the outdoor electronic
thermistor abnormality is not displayed? control P.C. board.
Yes
Normal
Fan motor does not operate or stops operating shortly after starting the operation.
Start
Rotate the outdoor fan motor manually and measure the voltage of
CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
No
(Fixed to either 5V or 0V DC) Does the voltage between each terminal become 5V DC and 0V DC
repeatedly?
Yes
No
Does the outdoor fan motor rotate smoothly?
Yes
Replace the outdoor DC fan motor. Replace the outdoor electronic control P.C. board.
41
OB346E --2qxp 07.2.8 6:57 PM Page 42
H Check of HPS
MUZ-A26YV
Start
Normal
42
OB346E --2qxp 07.2.8 6:57 PM Page 43
Resistance (k')
Resistance (k')
80
600 140
120 70
Resistance (k')
500
100 60
400 80
50
CN661
300 60
40
40
200
20 30
100
0 20
5V DC pulse wave
(From power board) GND
Signal reception
CN702
Defrost thermistor (RT62) (
Temperature (;)
0
5V DC pulse wave
(To power board)
Signal transmission
CN701
12V
motor
To fan
(
pulse wave
12V DC
CN795
GND (power board)
CN781
( pulse wave
5V DC
CN931 GND
20-90V AC
CN932
LEV
R.V. coil ()
(
(
(
(+) (
()
15V
15V
5V
(+)
()
(+)
()
(+)
(
(
LED 1
LED 2
(
CN601
325V DC
~
370V DC
Input
F801
FUSE
3.15A/250V
(+)
CN601
()
( Serial signal
5~10V DC
CN681
MUZ-A26YV
( High pressure switch
43
OB346E --2qxp 07.2.8 6:57 PM Page 44
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
Noise filter P.C. board
CN901
Electronic
control CN902 CN903 230V AC
board Power board 50Hz
Input
{
{
{
CN912
R.V. coil
230V AC {
230V AC
50Hz Output
44
OB346E --2qxp 07.2.8 6:57 PM Page 45
CN5
Primary current detection
(Connect to the noise filter)
325-370V DC
Output (Red) CN2
Connect to the controller board
(+) 1 (+)1-5(): Signal transmission
(To electronic control P.C. board)
() 3 5V DC pulse wave
(+)2-5(): Zero cross signal
(White) 3-4 : Not used
(+)6-5(): 15V
(+)7-5(): 15V
CN3
Fin temperature thermistor RT64
CN5
Primary current detection
(Connect to the noise filter)
45
OB346E --2qxp 07.2.8 6:57 PM Page 46
11 DISASSEMBLY INSTRUCTIONS
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
Sleeve
NOTE :
MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1 These photos are MUZ-A26YV.
OUTDOOR UNIT Other models are almost the same as MUZ-A26YV.
Screws
of the
top
Screws
panel
of the
back
panel Screws
of the
cabinet
Screw
of the
valve
cover
Set screws of the back panel
46
OB346E --2qxp 07.2.8 6:57 PM Page 47
47
OB346E --2qxp 07.2.8 6:57 PM Page 48
Photo 6
Outdoor heat
exchanger
temperature
thermistor
Defrost
thermistor
48
OB346E --2qxp 07.2.8 6:57 PM Page 49
Photo 9
R.V. coil
Welded part
of the dis-
charge pipe
Welded part
of the suction
pipe
49
OB346E --2qxp 07.2.8 6:57 PM Page 50
12 PARTS LIST
26
30 29 28 27
25
1 24
23
2
22
3
21
4
6
20
7 18
17
8 16
15
14
19
9 10 11 12 13
These figures show about MUZ-A26YV.
50
OB346E --2qxp 07.2.8 6:57 PM Page 51
Symbol Q'ty/unit
No. Part No. Part Name in Wiring MUZ-A18 MUZ-A24 MUZ-A26 Remarks
Diagram YV - E1 YV - E1 YV - E1
1 E02 819 297 TOP PANEL 1 1 1
E02 851 630 OUTDOOR HEAT EXCHANGER 1 1
2
E02 853 630 OUTDOOR HEAT EXCHANGER 1
3 E02 851 301 OUTDOOR FAN MOTOR MF 1 1 1 PM8H60-
4 E02 851 501 PROPELLER 1 1 1
E02 851 290 BASE 1 1
5
E02 853 290 BASE 1
6 E02 819 232 CABINET 1 1 1
7 E02 819 009 HANDLE 1 1 1
8 E02 819 521 FAN GUARD 1 1 1
9 E02 853 646 HIGH PRESSURE SWITCH HPS 1
E02 065 506 COMPRESSOR RUBBER SET 3 3 3RUBBERS/SET
10
E02 853 506 COMPRESSOR RUBBER SET 3 3RUBBERS/SET
E02 939 900 COMPRESSOR MC 1 1 SNB130FLDH1
11
E02 853 900 COMPRESSOR MC 1 TNB220FMCH
E02 851 661 STOP VALVE(GAS) 1 {12.7
12
E02 819 661 STOP VALVE(GAS) 1 1 {15.88
E02 821 662 STOP VALVE(LIQUID) 1 1 {6.35
13
E02 822 662 STOP VALVE(LIQUID) 1 {9.52
E02 851 640 EXPANSION VALVE 1 1
14
E02 853 640 EXPANSION VALVE 1
15 E02 851 493 EXPANSION VALVE COIL LEV 1 1 1
16 E02 853 299 OIL SEPARATOR 1
17 E02 851 490 R.V. COIL 21S4 1 1 1
18 E02 891 961 4-WAY VALVE 1 1 1
19 E02 819 650 VALVE COVER 1 1 1
20 E02 819 245 SERVICE PANEL 1 1 1
E02 851 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
21 E02 852 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
E02 853 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
22 E02 836 374 TERMINAL BLOCK TB2 1 1 1 2P
23 E02 823 375 TERMINAL BLOCK TB1 1 1 1 3P
24 E02 851 337 REACTOR L 1 1 1
25 E02 851 444 NOISE FILTER P.C. BOARD 1 1 1
DISCHARGE, DEFROST
26 E02 851 308 THERMISTOR SET RT61,RT62,RT68 1 1 1 OUTDOOR HEAT EXCHANGER
27 E02 851 440 POWER BOARD 1 1 1 Including heat sink and RT65
28 E02 819 233 BACK PANEL(OUT) 1 1 1
29 E02 817 009 HANDLE 1 1 1
30 E02 851 515 MOTOR SUPPORT 1 1 1
31 E02 127 382 FUSE F801 1 1 1 250V/3.15A
32 E02 737 382 FUSE F911 1 1 1 250V/1A
33 E02 735 385 FUSE & VARISTOR F912,NR63 1 1 1 250V/3.15A
E02 851 936 CAPILLARY TUBE(TAPER PIPE) 1 1 {3.6x{2.4x50
34 E02 853 936 CAPILLARY TUBE(TAPER PIPE) 1 {3.6x{2.4x50
E02 861 936 CAPILLARY TUBE 1 {1.8x{0.6x1000
51
OB346E --2qxp 07.2.8 6:57 PM Page 52
MUZ-A18YV - E1
MUZ-A24YV - E1
MUZ-A26YV - E1
12-2. ACCESSORY 1 2
Symbol Q'ty/unit
No. Part No. Part Name in Wiring MUZ-A18 MUZ-A24 MUZ-A26 Remarks
Diagram YV - E1 YV - E1 YV - E1
1 E02 817 704 DRAIN SOCKET 1 1 1
2 E02 444 705 DRAIN CAP 2 2 2 [33