Two-Channel
Digital Speed Switch
Installation Guide
The engine, turbine, or other type of prime mover should be equipped with an
overspeed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover
control system. An overtemperature or overpressure shutdown device may also be
needed for safety, as appropriate.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging
device, make sure the charging device is turned off before disconnecting the
battery from the system.
In systems where large inductive loads are switched on the DC power buss, surge
impulse energy will be present due to the switching. To address surge energy
affects on the control, appropriate suppression devices must be installed in the DC
power buss prior to the controls power connection.
IMPORTANT DEFINITIONS
WARNINGindicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
NOTEprovides other helpful information that does not fall under the warning or
caution categories.
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is
assumed by Woodward Governor Company unless otherwise expressly undertaken.
Woodward 2005
All Rights Reserved
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Regulatory Compliance
EMC Directive
Declared to 89/336/EEC COUNCIL DIRECTIVE of 03 May 1989 on the
approximation of the laws of the Member States relating to electromagnetic
compatibility.
Electromagnetic Compatibility
Testing was performed to ISO/EN 14982:1998 and EN 13309:2000 standards.
EMC Limitations
All cabling for these controllers is limited to less than 3m (9.84).
Power cabling is limited to less than 10m (32.8) in total length.
See wiring diagrams for specific cable types required.
Declaration of Conformity
The official Declaration of Conformity is available upon request. Please see the How
to Contact Woodward section in Chapter 7 to request a copy. It is also printed in
User Manual 36598, which can be accessed online at www.woodward.com
Woodward i
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
4. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
CAUTION
To prevent damage to electronic components caused by improper
handling, read and observe the precautions in Woodward manual
82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.
Woodward ii
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Chapter 1.
General Information
The DSS-2 is a two-channel electronic speed switch designed for use on engine
applications where it can perform a variety of speed related functions such as starter
motor disable and engine overspeed protection. The DSS-2 monitors engine rpm via a
magnetic pickup (MPU) input and controls two independent relays. Once engine speed
exceeds the user-selected speed setpoint, the relay will go to the designated set
condition. DSS-2 has two multi-turn potentiometers for speed setpoint adjustment. A serial
interface is provided for additional adjustments with the All-purpose Calibration Tool
(ACT).
DSS-2 can be re-configured with the ACT to act as a glow plug controller or engine
autocrank controller.
Intended Usage
The DSS-2 is intended as a sub-system for integration into construction/commercial and
industrial engine systems by original equipment manufacturers and industrial plants. It is
not intended for consumer or on-highway vehicles or for use by the general
consumer/public. Typical applications include generator sets, compressors, construction
machinery and farm vehicles.
Specifications
Woodward P/N: 8800-1001
Electrical
Power Input 9-30 Vdc, Reverse polarity protected
Electromagnetic Compatibility See Regulatory Compliance on page i.
Operating Current:
Both Channels On: 12 V: 100 mA / 24 V: 100 mA
Both Channels Off: 12 V: 50 mA / 24 V: 50 mA
Resistive Load: 1 to 10A
Relay Contact Ratings @ 28 Vdc
Inductive Load: 1 to 8A
Mechanical
Operating Temperature -40F to +185F (-40C to 85C)
Woodward 1
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Chapter 2.
Installation
CAUTION
Take adequate protection to ensure personal and equipment
safety and follow the suggested installation sequence given
below.
Mounting
Mount the unit in a location where the effects of vibration and temperature are within the
specified range. Operating temperature: -40F to +185F (-40C to +85C); vibration: 6
Gs from 40 to 2000 Hz. (See Figure 1 for controller dimensions.)
Woodward 2
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Wiring
DSS-2 has thirteen Euro-style screw terminals for:
Battery Positive and Negative (9-30 Vdc). Reverse voltage protected
Two form-C relays (10A continuous). Independent Common (C), Normally Closed
(NC) and Normally Open (NO) contacts are provided. DSS-2 is factory
programmed for standard relay logic (relay de-energized below set speed), but
may be modified with the ACT for reverse relay logic (relay energized below set
speed). External diodes should be added for transient suppression with inductive
loads.
Magnetic Pickup (MPU) Positive and Negative (2 Vac minimum at 1000 Hz). The
controller is factory programmed for 2500 to 5000 Hz. This range may be modified
with the All-purpose Calibration Tool (ACT) to cover
10-10,000 Hz or operate in units of rpm.
Reset Switch Input (RST): A switch to battery positive switch input is provided for
manual reset functions. DSS-2 is factory programmed for automatic reset at 80%
of set speed, but may be modified with the ACT for manual or latched reset.
Engine Protection Switch Input (EP): A switch to battery positive switch input is
provided for connection to external engine protection devices.
Verify Switch Input (VER): A switch to battery positive switch input is provided
for a verify function. Activating this switch will reduce both channel set
frequencies to 70% of their normal values.
2
Use insulated, automotive grade wiring (minimum 18 AWG or 1 mm ) for all connections. Shielded
wiring is recommended for the MPU.
2
Refer to Figure 2. Use proper wire gauges (18 AWG/ 1 mm minimum). All wire insulation
should be appropriate for engine applications. Terminations must be impervious to
moisture to prevent shorts and corrosion.
Use of convoluted tubing, conduit, or other wire shielding is recommended to minimize the
likelihood of mechanical damage to wires. Avoid routing wires near sharp edges or near
locations that can cause the wires to be pinched or damaged.
Woodward 3
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Controller Pinout
Use the diagram below to connect your DSS-2 controller to battery power, the mag pickup,
loads, switches and ACT.
NOTE
All cabling for the DSS-2 controller is limited to less than 3m (9.84).
Power cabling is limited to less than 10m (32.8) in total length. The
wiring diagram below shows specific cable types required.
CAUTION
To prevent damage to the controller, make sure that it is wired in
accordance with the wiring instructions and diagrams in this manual.
Woodward 4
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Chapter 3.
Calibration
Manual Calibration
Calibration is best done with a frequency generator to simulate the engine speed input and
a frequency meter. A zero-crossing input of 2 Vac minimum is required. Setup consists of
the following:
ACT Calibration
With the addition of the All-purpose Calibration Tool (ACT) computer interface (Woodward
P/N: SA-5206), the user can adjust the following features:
CAUTION
The serial/COM port and ACT software are intended only for
configuration and periodic service. Do not leave a computer
and/or serial/COM cable connected to the serial/COM port.
Woodward 5
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Chapter 4.
Diagnostics
The DSS-2 is equipped with three LEDs: one green and two red.
The green status LED on the DSS-2 can be used for diagnosing a variety of problems:
When the DSS-2 is powered up, all three LEDs will turn on for one second then
turn off. If they do not, the DSS-2 is either not receiving power or it is completely
non-functional.
If a fault condition exists, the green status LED will flash a code that indicates the
nature of the fault. Refer to the table below. The ACT can also be used to look up
current and historic faults.
If there are no faults, the green status LED will turn on continuously when the
DSS-2 receives a valid signal from the magnetic pickup. If it does not, then there
is not a valid signal.
The red channel LEDs indicate the condition of the assigned channel:
When the channel is in the Set condition (regardless of Forward or Reverse
configuration), the LED will be on.
When the channel is in the Reset condition (regardless of Forward or Reverse
configuration), the LED will be off.
FLASH
FAULT RESPONSE CAUSE
CODE
Woodward 6
Application Note 36599A DSS-2 Two-Channel Digital Speed Switch
Woodward 7