Auditguide PDF
Auditguide PDF
for
PERFORMING
WALK-THROUGH
ENERGY AUDITs
of
INDUSTRIAL FACILITIES
Table of Contents
Section Page
1. How to use this Guide ................................................................................................. 5
2. Guide Structure ............................................................................................................ 6
3. Lighting Systems .......................................................................................................... 7
4. Motors, Belts, and Drives ........................................................................................... 12
5. Fans and Pumps ........................................................................................................... 17
6. Compressed Air Systems ............................................................................................ 21
a. Throttle Control ...................................................................................................... 22
b. Load-Unload Control.............................................................................................. 23
c. Turn Value Control ................................................................................................ 25
d. Poppet Valve Control ............................................................................................. 26
e. On-Off Control......................................................................................................... 27
f. Low-Unload Control............................................................................................ 28
g. Variable Speed Drive Control .............................................................................. 29
7. Steam Systems .............................................................................................................. 35
8. Refrigeration Systems ................................................................................................. 39
9. Material Handling Systems ....................................................................................... 43
10. Hydraulic Systems ....................................................................................................... 44
11. Injection Molding or Extrusion ................................................................................. 45
12. Veneer Dryers ............................................................................................................... 46
13. Kiln Drying .................................................................................................................... 46
14. Energy Management ................................................................................................... 47
Audit Information
1. AC Alternating Current
2. ACFM Actual cubic feet per minute of air flow
3. ACFM-FAD Air flow before filter (Free Air Delivery)
4. VSD Adjustable Speed Drive
5. ASME American Society of Mechanical Engineers
6. BHP Brake Horsepower
7. BPR Back Pressure Regulator
8. CAGI Compressed Air and Gas Institute
9. ccf 100 Cubic feet
10. CFL Compact Fluorescent Lamps
11. CFM Cubic feet per minute of air flow
12. CSI Current Source Inverter
13. CO Carbon Monoxide
14. CW Cool White Fluorescent Lamps
15. DC Direct Current
16. F Degrees Fahrenheit
17. HPS High Pressure Sodium
18. HO High Output
19. HP Horsepower
20. HTD High Torque Drive
21. HVAC Heating Ventilation and Air Conditioning
22. ICFM Air flow at inlet flange
23. IESNA Illuminating Engineering Society of North America
24. LPA Liquid Pressure Amplifier
25. MH Metal Halide
26. O2 Oxygen
27. PCB Polychlorinated Biphenyls
28. Psi Pressure in pounds per square inch
29. Psia Psi absolute, which is 14.7 as sea level
30. Psig Psi gauge, referenced to atmospheric pressure
31. SCFM Equivalent air flow at Standard Conditions
32. PWM Pulse Width Modulated
33. VSD Variable Speed Drive
34. VSI Voltage Source Inverter
35. WW Warm White Fluorescent Lamps
36. WWX Warm White Deluxe Fluorescent Lamps
The purpose of this guide is to introduce the user, both technical and non-technical, to common
opportunities that may be found in an industrial facility to reduce the electrical energy
consumption. It has not been developed as a sole reference to support the user in completing an
analysis; but it has been developed to be an aide in the first and perhaps most critical step in
performing an audit: touring the facility and quickly identifying energy savings opportunities.
For the technical user this guide can help determine where to focus their effort for a detailed
energy audit. For the non-technical user this guide will assist them in developing a list of
potential energy saving opportunities to refer to qualified personnel for additional study. This
guide may also be used as a checklist when conducting a phone survey with a facility to
determine whether or not a detailed energy audit is necessary. Additional copies of this guide are
available from the Bonneville Power Administration, Energy Efficiency web site at
http://www.bpa.gov/indexmain.shtml
The contents of this report are offered as guidance. Neither the United States Government nor the
Bonneville Power Administration, nor any of their contractors, subcontractors, or their
employees, nor any agency thereof, make any warranty, express or implied, or assumes any legal
liability or responsibility for the accuracy, completeness, or usefulness of any information,
apparatus, product, process or software disclosed within this report.
Reference herein to any specific commercial product, process, trade name, trademark,
manufacturer, or others does not necessarily constitute or imply an endorsement,
recommendation or favoring by the United States Government or any agency thereof.
The views or opinion of authors expressed herein do not necessarily state or reflect those of the
United States Government or any agency thereof.
Acknowledgements
I would like to thank both Dr. Greg Wheeler, PE, Director, Industrial Assessment Center and Joe
Junker, PE, Industrial Energy Engineer from Oregon State University (OSU) for sharing with me
their invaluable knowledge gained from performing hundreds of industrial energy audits through
the Oregon Extension Energy Program at OSU. I would also like to thank Jonathan Maxwell for
sharing the wealth of information contained in his OSU Masters Thesis Improving Part Load
Efficiency of Screw Compressors. Most of all, I would like to thank the plant engineers,
equipment operators, and maintenance personnel for giving me the pleasure to work with them
over the past 20 years. I am constantly reminded that these folks take a lot of pride in keeping
their plants running as efficiently as they can every day with the resources available.
1. Before you begin your walk-through of the industrial facility, a meeting should be held with
the appropriate plant personnel that are familiar with the physical condition and day-to-day
operation of the manufacturing equipment in the facility. The purpose of the meeting is to
determine which of the systems, technologies, and equipment listed below actually apply to
the facility and where you should focus your attention during the walk-through audit.
Note: The energy savings opportunities are not limited to the systems, technologies, and
equipment listed above. These are just the more common ones.
2. The next step is to go through the checklist of questions in the guidebook that pertain to the
facility. All of these questions may not be answered in the meeting and therefore should be
flagged to be addressed during the walk-through. As you go through the checklist of
questions, this is a good opportunity to discuss any concerns that the plant personnel may
have with implementing the energy saving measures corresponding with each checklist item.
This process will help you to determine the energy savings measures that have already been
implemented and those that may or may not be applicable to this facility. At this point you
should have a better sense of which areas in the facility to focus your attention on during the
walk-through and who should accompany you. The following tools may be useful in
performing the walk-through audit:
Clipboard
Flashlight
Camera
Light Meter
Phillips and Standard Screwdrivers
True RMS meter, if not available, a Clamp on Amp Meter.
3. The next step is to tour the facility with the appropriate plant personnel that are familiar with
the various areas that you will be auditing. As you tour the facility, refer to the guide to
ensure that you answer any remaining checklist questions. The back of each page can be
used to record your observations, such as equipment nameplate data, gage readings, meter
readings, and to make notes, such as areas that require further study, equipment operators
names, phone numbers, etc.
4. After the tour is completed, a wrap up meeting should be held to review your findings. At
this point, a list of potential energy saving opportunities that should be considered for
additional study can be developed.
General Notes:
This section provides general information pertaining to the equipment, system, or technology
being covered, through the use of the symbols above.
Yes No This section provides a checklist of questions to ask or to look for that will
help you to identify existing conditions in the facility that offer opportunities
to save energy. If the answer is Yes, a list of energy savings measures are
listed below each question, and should be considered. If the answer is No,
move on to the next question.
For each checklist question answered Yes, these are the corresponding energy
saving measures that should be considered for additional study to determine the
feasibility of implementing them.
1
The following assumptions have been used unless otherwise noted: $.05/kilowatthour (kWh) for
electricity, eight hours a day (one typical shift), five days a week, 50 weeks a year. These estimates are
intended only for developing "ballpark estimates of potential energy savings.
General Notes:
Example: By changing from standard fluorescent lamps with magnetic ballasts to energy
efficient T8 fluorescent lamps with electronic ballasts, the energy consumption can be
reduced by approximately 50 percent, while still maintaining the same light level.
Yes No Are existing lighting levels higher than the recommended levels?
Use a hand held light meter to measure the amount of light available in work areas.
Hold the meter at work level. Refer to the table below for recommended lighting
levels. For additional information, refer to the Illuminating Engineering Society of
North America (IESNA) guidelines at http://www.iesna.org/ for more details.
Yes No Are magnetic ballasts installed on the existing fluorescent lights?
Install electronic ballasts.
Estimate: 10-25 percent increase in efficiency.
It can be difficult to determine the type of ballast installed without a visual
inspection.
2
Efficiency increase estimates assume maintaining same lighting level.
General Notes:
The following table can be used to estimate motor costs and efficiencies:*
Estimating Motor Cost and Efficiency
Motor Cost for Premium for Increase in Annual Savings
Horsepower Standard High Efficiency (for one shift @
Motor per Efficiency full load)
Horsepower Motor per
Horsepower
5 HP - 10 HP $55 - $70 per $13 - $20 per 5.0% - $5.00 - $3.00 per
HP HP 3.5% HP
15 HP - 30 $55 - $60 per $10 - $15 per same as $4.50 - $3.00 per
HP HP HP above HP
40 HP 125 Same as above same as above 3.5% - $3.00 - $2.50 per
HP 3.0% HP
150 HP - 300 Same as above same as above 2.0% $2.00 per HP
HP
*This table is only intended for field estimates of potential savings. Much more accurate
estimates can be developed with software tools such as MotorMaster at
http://www.oit.doe.gov or by contacting your motor supplier.
Motors have relatively constant power factor and efficiency down to approximately
50 percent of full load (within +/- 5 percent), then power factor and efficiency degrades
rapidly.
Larger motors are typically more efficient than smaller motors.
1 1
ES = .746 x Hp x %L x N x C x
EStnd.Eff EHigh.Eff
Where:
ES = The annual energy cost savings($/yr)
Hp = Motor Horsepower
%L = Percent Motor Load divided by 100
N = Annual Hours of Operation at this load
C = Cost of electricity ($/kWh)
EStnd Eff = Standard Motor Efficiency, as a fraction
EHigh Eff = High Efficiency Motor Efficiency, as a fraction
Yes No Are motors running during periods when the equipment or process they are driving is
idle?
Reduce equipment operation time to minimum required.
Turn off equipment during lunch and breaks, or other times when it is not
required.
This measure is only as reliable as the operator(s).
Interlock equipment with a related process.
If a particular piece of equipment is dedicated to specific process that requires
additional equipment, they can all be interlocked so all will be de-energized when
the operator turns off one piece of equipment.
Operate equipment such as a grinder in batches then shut off.
A piece of equipment like a grinder may run continuously although material only
runs through it occasionally. An alternative approach with no installation cost is
to allow material to collect and assign someone to periodically turn it on to
process the material in batches.
If material collection is left unmonitored, the collection bin can overflow
requiring additional labor for clean up. Jamming problems could also
develop.
Batch processing also has potential for increasing demand charges if the
equipment is more heavily loaded.
Install timers, level sensors, material sensors, or other controls for automatic
operation and/or to shut off equipment as required.
For example: Install material sensor and timer on equipment such as a grinder
set to turn on with set accumulation of material and turn off after allowable idle
time.
Care must be taken to avoid creating a safety hazard.
Yes No Does the facility utilize DC generator sets to provide variable speed control of
equipment?
Replace generator sets with solid state variable speed drives.
Before the advent of relatively inexpensive solid state variable speed drives, DC
Generator sets were commonly used to achieve variable speed control and to provide
high start up torque on a piece of equipment such as a de-barker in a lumber mill.
Solid state VSDs are typically more efficient and will provide soft starting of
equipment. However, a DC Generator can make up for lower efficiency by providing
a regenerative capturing breaking energy in a heavy piece of equipment.
Yes No Does the facility utilize Eddy Current drives for variable speed control?
Replace eddy current drives with solid state variable speed drives.
Eddy current drives are another older and less efficient method of achieving variable
speed control. Eddy current clutches can be high maintenance items, replacement
parts are expensive and difficult to locate.
Estimate: 86 percent efficiency for an eddy current clutch at full speed, 64
percent efficiency at 3/4 speed.
Estimate a 10 percent efficiency increase.
Yes No Are motors installed that operate continuously at part load?
Replace oversized motors with properly sized energy efficient motors.
Before downsizing a motor verify that it will not be loaded beyond its capacity at
some point in its operation.
Motors consume the least amount of energy when they operate at their highest
efficiency. For most motors, this is from 75 percent to 110 percent of their rated
load. As the motor loading drops below 50 percent, the efficiency and power
factor drops rapidly. The impact on larger motors (those over 50hp) is less. See
the Efficiency vs. Motor Loading graph.
98
40 hp
96
20 hp
94
10 hp
Motor Efficiency (%)
5 hp
92
90
88 10 hp
86
84
82
0 25 50 75 100
% Motor Load
The percent motor load can be estimated by the following equation:
Measured kW
% Motor Load = x 100,
Calculated kW @ FullLoad
Hprated .746 kW
Where: Calculated kW @ Full Load = X ,
Mtr.Eff full load Hp
rated
Example: A 50 hp motor with a full load efficiency rating of 90 percent was metered and
found to be operating at 25 kW. The percent Motor Load is estimated as follows:
50 Hprated .746 kW
Calculated kW @ Full Load = X = 41 kW,
.90 full load eff . Hprated
25 kW measured
% Motor Load = X 100 = 60%
41 kWcalculated
General Notes:
Actual efficiency can easily vary from 50 percent to 80 percent for optimum operation of a
particular pump.
When modifying or replacing pumps and fans, or adjusting their rpm, be sure that they can
operate under all conditions anticipated for the given system. System pressure or head
should not exceed the maximum pressure or head the fan or pump can sustain. Surge points
should be avoided. (Surge points occur when a fan or pump can operate at two different
flows at the same pressure).
For additional information, please refer to the following web sites:
http://www.oit.doe.gov/bestpractices/, http://www.ecw.org
Yes No Are pumps or fans installed that are not sized correctly for the task?
Pump or fan efficiency is very dependent upon flow and pressure, and the pump or fans
operating characteristics. For a given rpm there is one optimal operating point of flow
and pressure. As the pressure changes, flow changes and operating efficiency is also
affected. If system conditions have changed since the initial selection of the pump or fan,
they may be operating at a higher rpm than is required, therefore wasting energy. An
oversized pump or fan often works continuously against a throttle or damper causing
even greater inefficiencies.
Reduce pump or fan speed using a sheave adjustment or motor replacement.
It may be possible to tune the speed of a fan or pump so it can operate more
efficiently in a given system. If the fan or pump is belt driven the sheaves can be
modified in order to change the rpm. A motor that operates at a different rpm may
also be installed, particularly if it is oversized. Installing a two-speed motor could
also be an option.
Trim or replace pump impellers.
A pumps operating characteristics can be adjusted by re-sizing the impeller. On a
given system, it may be possible to achieve greater efficiency with a different pump
impeller.
Replace fan or pump with a more energy efficient model.
It may not be possible to achieve an acceptable efficiency on a system with a given
pump or fan. New equipment may be the best option.
The tower fans can be turned off during periods when the ambient air
conditions will sufficiently cool the water without the aide of the fans. The
energy consumption is significantly reduced to just the cost of circulating the
water through the tower.
In addition, the following energy savings opportunities should be evaluated for each
Cooling Tower:
Replace the tower fill material with cellular film fill to improve the heat
transfer efficiency.
Install non-clogging, non-corroding spray nozzles to improve water
distribution through the tower.
Install energy efficient airfoil fans.
Install energy efficient motors on the cooling tower fans and pumps.
Cooling tower optimization reduces the cost to provide colder water for cooling. By
reducing the temperature of the cooling water, the efficiency of the equipment or
process being cooled is improved.
Yes No Are pumps or fans being throttled in order to control the flow rate?
One of the most common and inefficient methods to control a fan or pump is to restrict its
flow. As the pressure is increased the flow is reduced. However, work required to deliver
the reduced flow is greater than would otherwise be required. The following
recommendations apply best to systems with variable flow (such as a boiler feed-water
pump or an induced draft fan.). If flow is constant at a reduced level see
recommendations for incorrectly sized pumps or fans.
100
75
50
25
0
0 25 50 75 100 125
% of Design Speed
Yes No Is bypass control being utilized to vary the flow out of the Pump?
Although less common, bypass control can be an extremely inefficient method for
controlling flow. In the best case, pump energy use is constant regardless of delivery to
an end use. In the worst case, energy use increases with reduced delivery to the end use.
As less flow is required at the end use, the excess is diverted to the bypass circuit and re-
General Notes
Many air compressors include capacity and pressure gages, including pressure drop across
the oil separator and dryer.
Look for high-pressure drops through equipment and lines.
Look for intentional pressure reductions, such as with valves and pressure regulators.
Record gage readings of percent capacity and pressure for the air compressors and air
dryers. Record nameplate data for the air dryers, air compressors, and drive motors.
For additional information, please refer to the following web sites:
http://www.knowpressure.org/html/where.html, http://www.cagi.org/glossary1.htm, and
http://www.ecw.org
Common compressed air terms are shown below:
Term Meaning
CFM Cubic Feet per Minute of Air Flow
ICFM Air flow at inlet flange
ACFM Actual air flow delivered after compressor
losses
ACFM-FAD Air flow before filter (Free Air Delivery)
SCFM Equivalent air flow at Standard
Conditions
(2 different standards use this same term )
Psi Pressure in pounds per square inch
Psig Psi gauge, referred to atmospheric
pressure
Psia Psi absolute, which is 14.7 as sea level
Standard Conditions
- CAGI (Compressed Air & Gas 14.7 psia, 60F, 0% rh (relative humidity)
Institute): 14.7 psia, 68F, 36% rh
- ASME
Typical dryer dewpoints: Refrigerated Dryers +35F to +38F, Desiccant Dryers - 40F
Each CFM of compressed air at 100 psig requires: 1/3 to 1/5 hp, ~ 1/4 to 1/7 kW, ~ $10 to
$20 per year
Estimate 3 to 5 CFM per HP
Yes No Are large compressors serving minimal system needs during off-hours such as
maintaining the minimum pressure requirements for a Dry Fire Suppression System?
Install a smaller air compressor dedicated to serve minimal after hour needs,
and isolate from main plant air system.
It is common to leave a large compressor on continuously ~ 7 days a week to
serve a small use such as pressurizing a dry fire suppression system. The
compressor may operate for long periods at an extremely inefficient part load
Yes No Does the facility have Centrifugal Screw Compressors that operate at less than full load
capacity for more than 70 percent of the Time?
Yes No Is throttle control used to modulate the compressor output capacity?
Replace throttle control with Load-Unload controls.
It is not energy efficient for a throttle-controlled screw compressor to operate
below 70-80 percent capacity. Throttling is not desirable if extended low load
periods are expected.
A throttle-controlled compressor consumes approximately 70 percent of its full
load power when delivering no air. (See the following Throttling Controls
graph)
Throttle Control
How does it work? Throttling modulation works by starving the compressor of air.
The mechanism itself is usually a butterfly valve or a slide valve that is installed
upstream of the compressor inlet. When the system pressure sensor perceives that
the pressure is decreasing(because plant air demand has exceeded the storage
capacity), the valve opens and the compressor begins to build pressure. When the
system pressure sensor perceives that the pressure is increasing(because plant air
demand has decreased below the storage capacity), the valve starts to close. This
creates a partial vacuum at the compressor inlet. Consequently, the air entering the
compressor is less dense and less air mass enters the compression chamber between
the screws. This reduces the mass flow rate(cfm) of air delivered to the system.
Energy Use: This method of control is often not efficient. Because the compressor
constantly works against system pressure at the discharge port, the motor never
really gets a chance to unload. As the compressor capacity drops below 70 percent,
the compressor efficiency declines rapidly, therefore consuming considerable energy
while producing minimal air.
This graph also indicates that 70 percent of full load power is consumed when the
compressor is providing no air, and 85 percent of full load power is consumed when
the compressor is operating at 50 percent capacity.
Load-Unload Control
The most efficient controls use a small oil pump and vent the air all the way to
atmospheric pressure (~0 psig). Some manufacturers maintain a pressure of ~
30 psig to circulate oil through the compressor while it is unloaded. In either case, a
check valve installed at the discharge prevents the back flow of air at system
pressure when the compressor is unloaded. In the unloaded condition, the
compressor does little work, because it is starved of air at the inlet and is working
against a minimum pressure at the outlet (0 or 30 psig).
Energy Use: Where appropriate, this method of control has very good energy use
characteristics since it only produces air at 100 percent capacity and idles with low
energy use at other times. There will be a small loss of energy each time the outlet blows
down, because any compressed air preceding the check valve will be vented to attain a
lower pressure. The simplest way to estimate energy use is to ignore these losses and
those that may accrue as the intake valve opens and closes. This may sound too
simplistic, but the volume of air lost will usually be less than 2 ft per cycle with most oil
separators.
The Load-Unload Controls graph above indicates that the compressor operates at
two points, full output (100 percent capacity and maximum efficiency) or unloaded
(0 percent capacity). This graph is for a compressor that is completely vented to
atmospheric pressure. A partially vented compressor at 0 percent capacity will
normally be near 25 percent of full load power.
Applications: Load-Unload control is most appropriate when conditions will not cause
unloading too often, though it can operate with more unloading cycles than on-off
controls can. An on-off controlled compressor would not be suited to restart every
2 minutes, for example, but a load-unload controlled compressor and motor could
handle the cycling.
A plant with a large air storage capacity and equipment without exacting
pressure requirements is ideally suited for load-unload control. Many
lumber mills fit this category because they have extensive piping
networks that act as receiver tanks and if necessary, space is usually
available to install larger receiver tanks.
How does it work? Turn valves or spiral valves are composed of a spirally threaded
shaft and discrete ports placed along the compression chamber wall. The shaft lies
parallel to the rotors. When the system pressure falls below its maximum pressure
set-point (usually 100 120 psig), the valves are closed and the compressor runs at
full capacity until the maximum pressure is maintained. The turn valves allow the
compressor to modulate between full capacity and zero capacity. This modulating
control is achieved by gradually rotating the spiral shaft. As the shaft is rotated, the
ports in the shaft allow some of the air being compressed in the rotors to escape and
return to the compressor inlet which is at atmospheric pressure (~0 psig). The air
that does not escape through these ports is discharged at system pressure.
Energy Use: This method is more efficient than throttling. However, since the
compressor works against system pressure at all times, this is still a relatively
energy-intensive modulation control strategy.
The Turn Valve Controls graph above indicates that the compressor can operate
continuously at any point between 0 percent and 100 percent capacity. This graph
shows good performance at high loads, but about 57 percent of full load power is
still consumed when the compressor is producing no air.
Applications: Turn valves are an effective control strategy when over-all plant demand
is high or erratic, when receiver size must be small, or when the acceptable range for
system pressure is small. Turn Valve modulation is a low-risk option and
consequently, a common control strategy. Though more efficient than throttling,
turn valve control is not desirable if extended low load periods are expected.
How does it work? Poppet valves operate using the same principle as the turn valve:
Opening discrete ports in the compression chamber walls reduces the volumetric
compression ratio. Instead of using a single rotating shaft, four or five pneumatic
valves open and close to expose the ports and allow the compressed air to escape to
the inlet, which is at atmospheric pressure.
The Poppet Valve Controls graph above shows good performance at high loads,
but about 60 percent of the full load power is still consumed when the compressor is
not producing any air.
Applications: Applications for Poppet Valve control are the same as those for Turn
Valve modulation controls.
On-Off Control
How does it work? The compressor runs at 100 percent capacity until the system
pressure reaches the maximum set point pressure. Then both the compressor and
motor completely shut off. A check valve prevents the flow of air back through the
compressor. When the compressor shuts off, an unloading valve opens so that air in
the discharge port is released to atmospheric pressure. This reduction in discharge
pressure makes it easier for the compressor to restart.
On-off control allows a compressor to operate at full output and maximum efficiency
and then turn off. However, on-off control requires larger receiver capacity and a
significant variation in system pressure. On-off control is not usually used in an
industrial setting except as a secondary control on a compressor that may operate at
low to zero capacity for an extended period of time.
Some processes are too sensitive to allow the variation in pressure required for
on-off control.
Beware of installing on-off control as a sole control on large motors. The
constant on-off cycle can reduce the life of the air compressor and motor.
On-off control may not be an option with many compressors.
Applications: This type of control strategy works best when the user is confident that
there will be long periods of either very high or very low use, and when the
maximum and minimum pressures are not close together. Large receivers are
required for efficient operation. A small plant with an occasionally used sandblaster
would be an appropriate application for this control strategy.
The compressor runs at 100 percent capacity and gradually increases the system
pressure, but before the maximum pressure is reached, the inlet control starts to modulate
and the capacity begins to reduce. This modulation continues until it either balances
compressed air demand with supply, or until the capacity falls to the unloading point (40-
50 percent capacity), whichever comes first. If the unloading point is reached, the
compressor drops to an unloaded idle condition, as described in the Load-Unload
section, and waits until the system pressure drops to the minimum allowed. At this
point, the modulating valve fully opens, the blow-down valve closes, and the compressor
returns to full capacity.
Energy Use: The energy efficiency of low-unload controls falls between that of
load-unload control and modulation-only control. Since the operating mode varies
depending on the magnitude and regularity of the plant air demand, receiver size,
pressure range, and unload point, it is not easy to make a simple mathematical
model. However, as an example the following simplified form can be used.
Assuming inlet throttling modulation is used, the unload point is set at 50 percent,
the compressor completely unloads to atmospheric pressure, and unloading losses are
ignored, energy use can be approximated as shown in the Throttle + Low-Unload
Controls graph below:
How does it work? A compressor system with a variable speed drive (VSD) controls
the compressor output by changing the rotational rate (rpm) of the screws. When air
demand is high, the screws rotate faster and therefore displace more air per minute
than when demand is low and rotation is slower. Typically a minimum speed is set
based upon the minimum internal pressure required to provide proper sealing of the
compression chamber. This may require modulation or unloading control to be
incorporated with the VSD control to drop capacity without further slowing the
screws.
Energy Use: VSD control offers modulation down to low loads while still
maintaining efficiency.
Like low-unload controls, there are two different operating modes. During periods
of high demand, the VSD controls the modulation. If the load drops below the
minimum level that can be compensated for with the VSD, the drive will stop
reducing speed and the capacity will be further reduced with a butterfly, slide, turn,
or poppet valve arrangement.
Note: VSD + Throttle Controls graph shows VSD control down 40% capacity
and Throttle Control down zero to 40% capacity.
Applications: VSDs can be the most expensive of all of the control options and are
not typically offered by compressor manufacturers as a standard configuration.
When combined with modulation, however, VSDs have the singular advantage of
The Combined Part Load Performance graph compares the performance of all of the
control methods discussed.
Yes No Does the facility have more than one compressor feeding into a common header? Are
these compressors operating at less than full output (cfm) capacity?
When more than one compressor is operating, all but one should operate at full capacity
and efficiency. A final trim compressor can match output to system requirements. In the
best case, the trim compressor can have more sophisticated controls for greater
efficiency at part load operation.
Manually sequence multiple compressors.
Set existing controls to load compressors sequentially so that unneeded
compressors can be turned off manually.
Install automatic compressor sequencing controls.
Sequence compressors to avoid operating several compressors at part load
and poor efficiently. The largest savings come from the sequencer turning
unneeded compressors off. The energy savings usually offset the cost of
installing additional receiver capacity.
Yes No Are compressors operating at zero capacity for extended periods of time?
Manually shut of air compressor.
If an air compressor is left on over the weekend or through the night, it can be
turned off manually.
This measure is only as reliable as the operator(s).
Install shut-off timers on air compressors.
Shut-off timers can be set to de-energize a compressor if it operates at zero
capacity for a set period of time. This can work particularly well if air may be
needed for short periods such as during night clean-up. The compressor will shut
off at the end of the production shift and only start up again when needed.
Yes No Is high pressure air being used for tasks that do not require high pressure air?
Compressed air may be used for inappropriate applications such as part drying or
aeration. A low- pressure blower or fan may be a better choice. Power is wasted to
compress the air to higher pressures than needed.
Meet end use requirements with lower pressure air delivery sources such as a
blower, fan, or a smaller horsepower air compressor.
Yes No Does the compressed air system have significant air leaks?
Most leaks are difficult to pinpoint and quantify on a leak by leak basis. Some leaks are
easy to find because of their location, sound, and air volume. Some leaks are intentional;
such as an open compressed air line directed to cool a hot bearing.
Leaks are easiest to find when the plant is quiet - plant is not in production
operation such as during lunch.
To quantify total air leaks in a plant: take note of air compressor loading and/or air
delivery during breaks or other times when there is no air use.
Ultrasonic tools provide the most reliable method to locate air leaks.
Common leak locations: valve packing, pneumatic cylinders, and hoses, quick
release hose fittings for hand equipment, hand equipment itself.
Example: For a compressed air system operating at 100 psig, one air leak 1/8in
diameter will loose 26 ft3 of air per minute. The power loss due to this air leak is:
3000 hrs
kWh/yr = (26 cfm )x
1 Bhp .746 Kw
x x = 12,931 kWh / yr ,
5 cfm ( Bhp)(.90 eff ) yr
12,931kWh $.05
The annual cost = x = $647 / yr
yr kWh
Yes No Does the facility have rotary vane air compressors?
The capacity of rotary vane compressors is commonly controlled by blowing off excess
air to atmosphere. In such cases there is no reduction in power with reduced air flow.
Replace rotary vane compressors with energy efficient centrifugal screw
compressors that are computer controlled to allow sequencing and
unloading.
Yes No Is the pressure drop across auxiliary equipment such as dryers, oil separators, or filters
excessive?
Some compressors display pressure drop across these devices. Pressure drop should not
exceed 8 to 10 psig; for oil separators, 5 psig for a dryer, 0.5 to 1 psig for a filter.
Replace filters, overhaul equipment to reduce pressure drop.
Clogged filters and fouled lines increase air velocity and pressure drop.
Size equipment to accommodate air flow with acceptable pressure drop.
Equipment such as a refrigerated dryer causes excessive pressure drop when air
flow exceeds design.
Yes No Is compressed air the best utility for the given application?
Compressed air is often chosen for its convenience; its safety in explosive situations; and
its comparatively high energy density for hand held tools, robotics, or other equipment.
Unfortunately it can be an inefficient method of getting the work done.
Replace compressed air use with another utility. For example, replace a
pneumatic motor with an electric motor or hydraulic motor.
Replace a venturi-type vacuum generator with a vacuum pump.
General Notes:
A 1/8 hole will lose 600 Mbtu/yr of steam in a 100 PSI system
Estimate 1 percent reduction in boiler efficiency for every 40F increase in stack
temperature.
Please refer to the following web sites for additional information:
http://www.oit.doe.gov/bestpractices/steam/totalsteam.shtml, http://www.ecw.org
Combustion efficiency and boiler operating targets for different fuels:
Boiler Recommended
Pressure Maximum Stack
Temperature
30 psig 375 F
75 psig 420 F
100 psig 440 F
125 psig 455 F
(No more than 100 F greater than saturated
steam pressure at boiler operating pressure)
Stack temperatures lower than 275 F can lead to corrosive condensation
Yes No Does the facility have a significant number of steam traps that are malfunctioning?
Steam traps are usually designed based upon a maximum back pressure rating. This
rating is determined by dividing the outlet pressure by the inlet pressure, absolute (psia).
If the back pressure of the present system is greater than the original design pressure, the
trap is not able to fully close, and can fail in the open position. When these traps fail
open, they blow steam into the return system, which increases the back pressure on other
traps in the system, causing them to fail. When the steam is induced into the return
piping, the vapor flows over the condensate, eventually causing enough turbulence to
create a mass or slug of condensate that fills the pipe.
The condensate slug can travel throughout the piping system at the same velocity as the
steam until it encounters a sudden change in direction and this energy is transferred into
a force referred to as water hammer. It can be difficult to identify traps that are
leaking, failed open or failed closed. When properly designed and maintained, steam
traps remove the condensate from the steam and purge air and other non-condensable
gases from the steam system which increases its thermal efficiency.
The most reliable method to identify traps that are malfunctioning is to use
ultrasonic tools.
Yes No Is an open condensate return system utilized?(condensate not returned to the boiler)
If condensate is not returned to the boiler all of the energy in the hot condensate return is
lost. Since this condensate also contains water treatment chemicals, these chemicals have
to be replaced. The energy and wastewater treatment costs will increase.
This loss has to be balanced against the significant cost of adding a condensate
return system. In large facilities, the installation of a condensate return system
may require extensive pumping, piping and valves.
Install a condensate return loop.
Yes No Is the efficiency and performance of the steam system being monitored manually?
Install a boiler stack gas thermometer with a maximum indicating hand.
Install a meter to measure the amount of boiler make-up water being consumed.
Yes No Is the flow rate of the induced draft and forced draft fans being controlled by throttling
methods?
Install VSD control on boiler induced draft and forced draft fans.
Boilers typically operate 24 hours a day, 365 days per year. Improving the
efficiency of any equipment associated with the day to day operation of the
boiler will produce significant energy savings.
General Notes:
Compressor energy use drops 1 - 1.5 percent for each F of head pressure drop.
Compressor energy use drops 2 - 3 percent for each F of suction pressure increase.
Please refer to the following web sites for additional information: http://www.ecw.org,
http://www.oit.doe.gov, http://www.ecw.org/products/commindu.html#502/
Cooling
water
HIGH
HIGH
Pressure, 2 1 Pressure,
GAS
LIQUID
CONDENSER
THROTTLE VALVE
COMPRESSOR
EVAPORATOR
3 4 Low Pressure,
GAS
Low Pressure,
LIQUID/GAS
mix
Note: The Simple Refrigeration Cycle diagram is for information only and will be
described in detail at a later time.
Yes No Can the operation of the existing refrigeration system be optimized by implementing any
of the following meausres?
Optimize inter-stage pressure.
A two-stage system has three separate pressures maintained by high- and low-
stage compressors. Choose intermediate pressure so that each compressor has
approximately the same pressure ratio to minimize compressor energy use.
Economized single stage system.
For applications that require extremely low temperatures such as a blast freezer,
a two- stage compressor is usually preferred. An economized single stage
system may allow operation at slightly lower suction temperatures while
providing the necessary cooling and avoiding the cost of a two-stage system.
Install 2-speed or VSD speed control on condenser and evaporator fans.
By reducing fan speed when full capacity is not needed, the energy consumption
of the fan motors is significantly reduced.
Cycle evaporator and condenser fans.
Evaporator fans move air across refrigerant coils to condition the space.
Condenser fans remove the heat generated during compression of the refrigerant.
Evaporator fans can turn off when not needed for temperature control or to de-
stratify air in the space. Cycling fans saves fan and compressor energy. Duty
cycles can be reduced as much as 50 percent. A timer can be used to cycle
primary fans after a given amount of operation
Yes No Can the timing of heavy process or other refrigeration loads be distributed better?
Consider load shifting during periods of high energy use and or thermal storage
during periods of low energy use to reduce the total energy demand.
Yes No Are head pressures significantly higher than rated pressures?
Yes No Are the compressors on a regular maintenance schedule? If so, verify that the following
is being done on a scheduled basis.
Maintain evaporative condensers.
Water evaporates as it absorbs heat from the condensing refrigerant. The heat
exchange surface must be clean and free of corrosion. Air must pass through freely
for efficient heat transfer. Water should be treated to reduce scale and corrosion,
and reduce biological growth.
Purge non-condensable gasses.
Non-condensable gasses such as air or CO2 reduces the effective surface area of the
condenser used to condense refrigerant vapor, thereby decreasing heat exchanger
General Notes:
The following option should be considered when exploring opportunities to save energy
with material handling fans and blowers:
For belt driven devices, the speed can be reduced by re-sheaving the motor to determine
the minimum speed allowed to move the material and avoid design and safety problems.
After this speed is determined, the actual motor rpm can be measured with a tachometer.
The proper drive mechanism can be selected.(VSD, two speed motor, an energy efficient
motor at reduced rpm and horsepower, etc.)
This approach can provide energy savings at the least cost. The preferred method is to
evaluate the entire system and to size the fan and motor to efficiently handle the present
operating conditions.
For additional information, please refer to the following web sites:
http://www.energy.wsu.edu/industry/research.htm, http://www.ecw.org
Yes No Does the facility utilize high or low pressure blowers to convey material?
The following energy savings opportunities should be evaluated:
Reduce the speed of the blower or fan to capture the energy savings and
reduce the wear and tear on the distribution piping by reducing the velocity.
Replace Dust Collection System Material Handling fans with High Efficiency
Clean side fans.
Install high efficiency bag houses.
Replace Pneumatic chip transfer with conveyors or vibrating transfer
systems.
Yes No Does the facility have more than one baghouse and multiple distribution lines feeding
into these baghouses?
Determine if these distribution lines can be valved/knifed off when not operating
to reduce the load on the fan and baghouse.
Determine if these distribution lines should be re-routed to allow a dedicated fan
that requires less horsepower to perform the same task.
Quite often the pant distribution lines, fans, and blowers have been modified over
the years and are not operating under design conditions and could be wasting a
lot of energy.
General Notes:
General Notes:
Yes No Does the manufacturing process involve Extrusion or Injection Molding?
The following energy savings opportunities should be evaluated:
Install a variable speed extruding machine.
The drive runs at the minimum speed necessary for the product being produced. The
input signal to the drive is typically a 4 to 20mA control signal that maintains the desired
set-point.
Insulate heater bands to reduce thermal losses.
Grind and reuse reject parts and trim pieces.
General Notes:
Yes No Does the manufacturing process involve the use of Veneer Dryers?
The following energy savings opportunities should be evaluated:
Perform an air balance on the dryer.
Provide uniform drying, sufficient air circulation, optimize air contact with
product.
Install electronic dryer controls (VSD) to control drying time.
Install VSD fan control if there is a significant variation in species and
moisture content of the product being dried.
Plastic bearings reduce friction loss and last longer than carbon/steel
bearings.
Investigate alternate drying methods
- Infra-red
- Microwave
- Radio frequency
Preheat dryer makeup air with heat from exhaust.
General Notes:
Energy Management