Data Sheet

System pro M compact


Miniature Circuit Breaker S 200/S 200 M

2CDC021023S0012

2CDC021038S0012
The miniature circuit breakers of the Features
Clear contact position indication in red/green (real CPI)
System pro M compact series S 200 Unique, patented twin terminal with captive screws and
and S 200 M provide state-of-the-art an increased opening for cables up to max. 35 mm2,
safety and comfort. They stand out due finger-proof (IP20)
Busbar slot in the back for best visibility during installation
to their high performance and the wide High performance at an increased rated voltage for marine
range of accessories and approvals. and industrial applications: 10 kA/15 kA at Ue = 440 V AC
acc. to IEC/EN 60947-2
Individual product identification code
Approved acc. to IEC/EN 60898-1, IEC/EN 60947-2 and
UL 1077/CSA 22.2 No. 235 for global use
Miniature Circuit Breaker S 200/S 200 M
Technical data

S 200 S 200 M
General Data
Standards IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1, IEC/EN 60947-2
UL 1077 UL 1077, CSA 22.2 No. 235
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N
Tripping Characteristics B, C, D, K, Z
Rated current In 0.5 up to 63 A
Rated frequency 50/60 Hz
Rated insulation voltage Ui 250 V AC (phase to ground), 500 V AC (phase to phase)
Overvoltage Category III
Pollution Degree 3
IEC/EN 60898-1
Rated operational voltage Un 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P: 400 V AC; 3P+N: 400 V AC
Max. power frequency recovery voltage Umax 1P: 253 V AC; 1P+N: 253 V AC; 2P, 3P, 4P: 440 V AC; 3P+N: 440 V AC;
1P: 72 V DC; 2P: 125 V DC
Min. operating voltage 12 V AC, 12 V DC
Rated short-circuit capacity Icn 6 kA 10 kA
Energy limiting class (B, C up to 40 A) 3
Rated impulse withstand voltage Uimp (1.2/50 s) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C, D: 30 C
Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF
In 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF
IEC/EN 60947-2
Rated operational voltage Ue 1P: 230 V AC; 1P+N: 230 V AC; 2P, 3P, 4P: 440 V AC; 3P+N: 440 V AC
Max. power frequency recovery voltage Umax 1P: 253 V AC; 1P+N: 253 V AC; 2P, 3P,4P: 462 V AC; 3P+N: 462 V AC;
1P: 72 V DC; 2P: 125 V DC
Min. operating voltage 12 V AC, 12 V DC
Rated ultimate short-circuit breaking capacity Icu 10 kA 15 kA
Rated service short-circuit breaking capacity Ics 7.5 kA 40 A: 11.25 kA
50, 63 A: 7.5 kA
Rated impulse withstand voltage Uimp (1.2/50 s) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C, D: 55 C; K, Z: 20 C
Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF
In 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF
UL/CSA
Rated voltage 1P: 277 V AC, 60 V DC 1P: 277 V AC, 60 V DC
2...4P: 480 Y/277 V AC, 110 V DC 2...4P: 480 Y/277 V AC, 125 V DC
Rated interrupting capacity 6 kA (AC), 10 kA (DC)
Application Suppl. prot. for general use. Application Codes: TC2, OL0, SC: U1
Reference temperature for tripping characteristic B, C, D, K, Z: 25 C
Electrical endurance 6,000 ops. (AC), 6,000 ops. (DC); one cycle 1 s - ON, 9 s - OFF
Mechanical data
Housing Insulation group II, RAL 7035 Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Marking on toggle (I ON/0 OFF), Real CPI (red ON/green OFF)
Protection degree acc. to EN 60529 IP201), IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g, 2 shocks, 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5 g, 20 cycles at 51505 Hz with load 0.8 In
Environmental conditions acc. to IEC/EN 60068-2-30 28 cycles with 55 C/90-96 % and 25 C/95-100 %
Ambient temperature -25 ... +55 C
Storage temperature -40 ... +70 C
1)
Also fulfilling the requirements acc. to the protection degree IPXXB

2 - 2CDC002157D0202
Miniature Circuit Breaker S 200/S 200 M
Technical data and tripping characteristics

S 200 S 200 M
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm2 / 35 mm2
flexible: 25 mm2 / 25 mm2
14 4 AWG1)
Cross-section of busbars (top/bottom) 10 mm 2 / 10 mm2
14 8 AWG2)
Torque 2.8 Nm
18 in-Ibs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x D x W) 88 x 69 x 17.5
Pole weight approx. 115 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal/auxiliary contact Yes
Shunt trip Yes
Undervoltage release Yes
Motor Operating Device Yes
1) 2)
AWG 18 4 acc. to UL 486A 486B AWG 18 8 acc. to UL 486A 486B

Tripping characteristics
Acc. to Tripping Rated Thermal release 3)
Electromagnetic release 4)
characte- current
ristics
Currents: Tripping Range of Tripping time
conventional conventional time instantaneous
non-tripping tripping tripping
current current
In I1 I2
IEC/EN 60898-1 B 6 to 63 A 1.13 I n >1h 3 In 0.1 ... 45 s (In 32 A)/0.1 ... 90 s (In > 32 A)
1.45 In <1h 5)
5 In < 0.1 s
C 0.5 to 63 A 1.13 In >1h 5 In 0.1 ... 15 s (In 32 A)/0.1 ... 30 s (In > 32 A)
1.45 In <1h 5)
10 In < 0.1 s
D 0.5 to 63 A 1.13 In >1h 10 In 0.1 ... 4 s (In 32 A)/0.1 ... 8 s (In > 32 A)
1.45 In <1h 5)
20 In < 0.1 s
IEC/EN 60947-2 K 0.5 to 63 A 1.05 I n >1h 10 In > 0.2 s
1.2 In <1h 5)
14 In < 0.2 s
Z 0.5 to 63 A 1.05 I n >1h 2 In > 0.2 s
1.2 In <1h 5)
3 In < 0.2 s
3)
The thermal releases are calibrated to a nominal reference ambient temperature; for B, C, D the reference value is 30 C, for K and Z the reference value is 20 C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
4)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
5)
As from operating temperature (after I1 > 1h)

2CDC002157D0202 - 3
Miniature Circuit Breaker S 200/S 200 M
Tripping characteristics

B characteristic C characteristic D characteristic

2CDC022006F0211

2CDC022008F0211

2CDC022108F0209
K characteristic Z characteristic
2CDC022060F0211
2CDC022010F0211

4 - 2CDC002157D0202
Miniature Circuit Breaker S 200/S 200 M
Derating

Deviating ambient temperature


For installations of miniature circuit breakers at other tempe- breakers with the characteristics B, C and D and 20 C for
ratures than the reference value derating factors have to be circuit breakers with the characteristics K and Z. The following
considered. table contains the derating of the load capability at ambient
The rated value of the current of a miniature circuit breaker temperatures from -40 C to 70 C for the characteristics B,
refers to a reference ambient temperature of 30 C for circuit C, D, K and Z.

Tripping Rated Maximum operating current at ambient temperature T


charac- current
teristics In
A A
- 40 C - 30 C - 20 C - 10 C 0 C 10 C 20 C 30 C 40 C 50 C 60 C 70 C
B, C, D 0.5 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.0 1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
1.6 2.13 2.07 2.00 1.92 1.85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2.0 2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
3.0 4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
4.0 5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
6.0 8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
8.0 10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
10.0 13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
13.0 17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
16.0 21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
20.0 26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
25.0 33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
32.0 42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
40.0 53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
50.0 66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
63.0 84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
K, Z 0.5 0.66 0.64 0.61 0.59 0.56 0.53 0.50 0.47 0.43 0.40 0.35 0.31
1.0 1.32 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61
1.6 2.12 2.04 1.96 1.88 1.79 1.70 1.60 1.50 1.39 1.26 1.13 0.98
2.0 2.65 2.55 2.45 2.35 2.24 2.12 2.00 1.87 1.73 1.58 1.41 1.22
3.0 4.0 3.8 3.7 3.5 3.4 3.2 3.0 2.8 2.6 2.4 2.1 1.8
4.0 5.3 5.1 4.9 4.7 4.5 4.2 4.0 3.7 3.5 3.2 2.8 2.4
6.0 7.9 7.6 7.3 7.0 6.7 6.4 6.0 5.6 5.2 4.7 4.2 3.7
8.0 10.8 10.2 9.8 9.4 8.9 8.5 8.0 7.5 6.9 6.3 5.7 4.9
10.0 13.2 12.7 12.2 11.7 11.2 10.6 10.0 9.4 8.7 7.9 7.1 6.1
13.0 17.2 16.6 15.9 15.2 14.5 13.8 13.0 12.2 11.3 10.3 9.2 8.0
16.0 21.2 20.4 19.6 18.8 17.9 17.0 16.0 15.0 13.9 12.6 11.3 9.8
20.0 26.5 25.5 24.5 23.5 22.4 21.2 20.0 18.7 17.3 15.8 14.1 12.2
25.0 33.1 31.9 30.6 29.3 28.0 26.5 25.0 23.4 21.7 19.8 17.7 15.3
32.0 42.3 40.8 39.2 37.5 35.8 33.9 32.0 29.9 27.7 25.3 22.6 19.6
40.0 52.9 51.0 49.0 46.9 44.7 42.4 40.0 37.4 34.6 31.6 28.3 24.5
50.0 66.1 63.7 61.2 58.6 55.9 53.0 50.0 46.8 43.3 39.5 35.4 30.6
63.0 83.3 80.3 77.2 73.9 70.4 66.8 63.0 58.9 54.6 49.8 44.5 38.6

Influence of adjacent devices


If several miniature circuit breakers are installed directly side Example
by side with high load on all poles, a correction factor has to Installation of 8 adjacent miniature circuit breakers S201-C16
be applied to the rated current (see table). If distance pieces at 40 C ambient temperature
are used, the factor is not to be considered.
Rated current I n = 16 A
Max. operating current at 40 C = 15,.1 A (see table above)
No. of adjacent devices Factor F
Factor F = 0.75 (see left table)
1 1
2, 3 0.9 In = 15.1 A x 0.75 = 11.33 A
4, 5 0.8 Result: The operating current can only add up to max.
6 0.75 11.33 A

2CDC002157D0202 - 5
Miniature Circuit Breaker S 200/S 200 M
Internal resistance and power loss

Internal resistance and power loss per pole


Rated Tripping characteristic
current B, C1) D K Z
Internal Power loss Internal Power loss Internal Power loss Internal Power loss
resistance resistance resistance resistance
In Ri Pv Ri Pv Ri Pv Ri Pv
A m W m W m W m W
0.5 5500 1.4 4300 1.1 4300 1.1 8100 2.4
1.0 1440 1.4 1250 1.25 1250 1.25 2100 2.3
1.6 630 1.6 600 1.5 600 1.5 1000 2.8
2.0 460 1.8 410 1.6 410 1.65 619 2.5
3.0 150 1.3 130 1.2 130 1.2 235 2.4
4.0 110 1.8 105 1.7 105 1.7 149 2.4
6.0 55 2.0 52 1.9 52 1.9 75 3.2
8.0 23 1.5 24 1.5 24 1.5 27 2.0
10.0 19 2.1 16 1.6 13.5 1.4 24 2.7
13.0 14 2.3 14 2.2 13.5 1.4
16.0 8.5 2.5 8.5 2.5 7.7 2.0 10.9 2.8
20.0 6.25 2.5 6.1 2.3 6.7 2.7 6.0 2.4
25.0 5.0 3.2 4.3 3.1 4.6 2.9 4.5 3.3
32.0 3.6 3.7 3.5 3.6 3.5 3.6 3.5 3.6
40.0 3.0 4.8 2.2 4.2 2.2 4.2 2.5 4.1
50.0 1.3 3.25 1.25 2.9 1.25 3.1 1.5 4.1
63.0 1.2 4.8 1.2 4.8 1.0 4.4 1.3 5.2
1)
Current ratings 0.5 4 A, 8 A apply to C characteristic only
Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be
considered as typical values.

6 - 2CDC002157D0202
Miniature Circuit Breaker S 200/S 200 M
Let-through energy I2t

Characteristics B, C - 230/400 V let-through energy

2CDC002157D0202 - 7
Miniature Circuit Breaker S 200/S 200 M
Let-through energy I2t

Characteristics D, K - 230/400 V let-through energy

8 - 2CDC002157D0202
Miniature Circuit Breaker S 200/S 200 M
Let-through energy I2t

Characteristic Z - 230/400 V let-through energy

2CDC002157D0202 - 9
Miniature Circuit Breaker S 200/S 200 M
Accessories and dimensional drawing

Accessory overview

2CDC092002F0212

H Auxiliary contact S2C-H6R H-L Auxiliary contact S2C-H...L

(change-over contact) H-BF Auxiliary contact for bottom fitting S2C-H01

H-R Auxiliary contact S2C-H6-...R (1 per pole) S2C-H10

S/H Signal/Auxiliary contact S2C-S/H6R BP Mechanical tripping device S2C-BP

S/H (H) Signal/Auxiliary contact NT Neutral disconnector S2C-Nt

used as auxiliary contact S2C-S/H6R MOD-S1) Motor operating device S2C-CM

ST Shunt trip S2C-A... DDA 200 RCD-block DDA 20...

UR Undervoltage release S2C-UA


1)
OR Overvoltage release S2C-OVP In case of using S 200/S 200 M coupled with DDA 200, MOD-S does not
operate in case of earth-leakage fault.

Dimensional drawing
2CDC022007F0010

10 - 2CDC002157D0202
Miniature Circuit Breaker S 200/S 200 M
Approvals

Country approvals Ship approvals


Approval mark Description Country Approval mark Description Country

RCM Australia BV France

VE Austria GL Germany

CEBEC Belgium RINA Italy

CSA Canada (S 200 M only) ABS USA

CCC China
Not all approvals are printed on the MCBs.
EZU Czech Republic
The indicated approvals generally cover all available appro-
DEMKO Denmark vals worldwide. To verify the approval status in your country
please get in touch with your ABB contact person.
FIMKO Finland

NF France

VDE Germany

IMQ Italy

SIRIM Malaysia

KEMA Netherlands

NEMKO Norway

BBJ Poland

CERTIF Portugal

GOST
Russia
GOST Fire

HDB Singapore

SIQ Slovenia

AENOR Spain

SEMKO Sweden

S+ Switzerland

UL1077 USA

2CDC002157D0202 - 11
Contact us

ABB STOTZ-KONTAKT GmbH Note:

Brochure number 2CDC002157D0202 (08/12-0.5-ZVD)


Eppelheimer Strae 82 We reserve the right to make technical changes
or modify the contents of this document without
69123 Heidelberg, Germany
prior notice. With regard to purchase orders, the
Phone: +49 (0) 6221 7 01-0 agreed particulars shall prevail. ABB AG does
Fax: +49 (0) 6221 7 01-13 25 not accept any responsibility whatsoever for
E-Mail: info.desto@de.abb.com potential errors or possible lack of information in
this document.

You can find the address of your We reserve all rights in this document and in
local sales organization on the the subject matter and illustrations contained
ABB home page therein. Any reproduction, disclosure to third
http://www.abb.com/contacts parties or utilization of its contents in whole
-> Low Voltage Products and Systems or in parts is forbidden without prior written
consent of ABB AG.

Copyright 2012 ABB


All rights reserved

You might also like