Ac Stress Distribution in The Insulation Single Core Screened Xlpe Cable - 132 KV 300 MM
Ac Stress Distribution in The Insulation Single Core Screened Xlpe Cable - 132 KV 300 MM
Ac Stress Distribution in The Insulation Single Core Screened Xlpe Cable - 132 KV 300 MM
ELECTRICAL DATA
U Phase to Phase Nominal Voltage (kV) 132
U0 Phase to Earth nominal Voltage (kV) 76
Uip Impulse Voltage (kV) 650
Upf Short Duration Power Frequency Withstand Voltage (kV) 275
CABLE DIMENSIONS
d Nominal Diameter of Conductor (mm) 20.60
tcs Nominal Thickness of Conductor Screen (mm) 1.20
D Nominal Diameter over Insulation Screen (mm) 60.20
tis Thickess of Semi Conductor screen over insulation (mm) 1.20
X Thickness of Insulation 17.40
Ex = V/{[(d/2)+tcs+x)]*ln[(D-2*tis)/(d+2*tcs)]} kV/mm
Where,
Ex : Stress Distribution at point X of inslulation (kV)
V : Potential applied between Conductor and Metalic Sheath (kV)
x: Distance from conductor screen at point X of insulation (mm)
XLPE Insulation
Conductor
kV
4.0
4 2.75 5.805 20.946 3.0
15.0
16 13.74 3.277 11.825 10.0
5.0
17 14.65 3.162 11.411
0.0
18 15.57 3.055 11.025
19 16.48 2.955 10.664
THICKNESS (mm)
20 17.40 2.862 10.326